T8532-IAQ
3 H / 2 C - Programmable
with Humidifi cation /
Dehumidifi cation Control
T8532-001
3 H / 2 C - Programmable
T8522-001
2 H / 2 C - Programmable
5 Year Warranty
PECO WavePRO™ WIRELESS SYSTEM
Performance PRO™ T8000 Series
Category leading extra-large display, commercial thermostats
for multi-stage & heat pump applications.
Large BLUE backlit display - 8 inch
in sleek-design housing,
allowing easy viewing in low light.
Memory card interface,
enabling quick confi guring of
large-project installations.
365 Day programmable calendar,
with 20 holidays & daylight-saving time
shift, giving set-and-forget-it convenience.
Humidifi cation / dehumidifi cation control,
maximizing occupant comfort with a
programmable environment.
Battery or hard-wire with power harvesting,
or (Green) mode, preserving battery life
& reducing disposals.
Performance PRO Series common wallplate,
allowing installer or customer to easily
upgrade to richer function thermostats.
TM
(Model T8532-IAQ)
2
High Performance
Commercial Functions
7 Day, 5-1-1, 5-2, non-programmable modes
Programmable & intermittent fan
Economizer / damper control output
3 Levels of keypad lockout with PIN access
Meets CA Building Code, Title 24 with
pre-occupancy purge & override limitations
Compressor & auxiliary lockout for dual fuel
(fossil) or electric auxiliary heat
Heating / Cooling LED indicator
Low battery & change filter indicators
Occupancy sensor / setback input
Remote indoor & outdoor sensor support
Commercial proportional integral control
with configurable ramp recovery
Innova on & experience you can count on
Oil
T12532-001
T12532-IAQ
Electric
Gas
Heat Pump
T12000
T8000
Series
Series

Performance PRO™ T8000 Series
Specifications
Specifications
T8000 Thermostat
Memory
Card
Temperature Control Range 50° to 90° F (10° to 32° C)
Operating Temperature Range 0° to 120° F (-18° to 49° C)
Storage Temperature Range -20° to 130° F (-29° to 55° C)
Electrical Input Frequency 50/60 Hz +/- 10%
Input Power 24 V
AC (20-30 VAC) and/or 2 AA alkaline
batteries (Installing batteries recommended)
Output Terminal W - Heating 20-30 VAC 0.02-1.0 A
Output Terminal Y - Cooling 20-30 V
Output Terminal G - Fan 20-30 V
Output Terminal A - Economizer 20-30 V
AC 0.02-1.0 A
AC 0.02-0.6 A
AC 0.02-1.0 A
Dehumidifi cation Sensor 0 - 100% RH
Dehumidifi cation Range 25% - 99% RH
Termination Connections Wallplate w/ terminal blocks
Memory Card SD (Secure Digital)
Total load not to exceed 2.5 A
Technical Data
Dimensions
Mounting
LCD Viewable Size
Physical Dimensions 5.7”W x 4.3"H x 1.3"D
Direct mount; 2" x 4" horizontal
or vertical, or 4" x 4"
8 inch2 - 2.5" W x 3.2" H
51.8 cm2 - 6.4 cm W x 8.1 cm H
Performance PRO Wallplate
& Terminal Connections
CONVENTIONAL
HEAT PUMP B/O AUX
Conventional
Unswitched side 24 VAC
Stage 1 Heat
Stage 2 Heat
4.3”
(10.9 cm)
5.7”
cm)
(14.5
C W1 W2 G A E Y1 Y2 RH RC SC S1 S2 S3
CONVENTIONAL
HEAT PUMP B/O AUX
C W1 W2 G A E Y1 Y2 RH RC SC S1 S2 S3
(3.3 cm)
1.3”
Terminals
Heat Pump
Unswitched side 24 VAC
Reversing valve
Auxiliary (Stage 3 Heat)
W1
W2
C
B/O
AUX
Model Part No. Description
T8532-IAQ 70337 Performance PRO 3 Heat/2
T8532-001 69922 Performance PRO 3 Heat / 2
T8522-001 70333 Performance PRO 2 Heat
70271 70271 Wallplate. Performance PRO
69308 69308 Indoor remote sensor
70327 70327 Outdoor remote sensor
SB200-001 68375 Occupancy sensor - time based
SK200-001 68381 Occupancy sensor - guest room
T8000
Series
Models & Accessories
Cool staging, programmable w/
Humidifi cation/Dehumidifi cation
control
Cool staging, programmable.
/2 Cool staging, programmable.
common wallplate: applicable to
all series models.
Oil
Electric
Gas
Heat Pump
Fan Relay
Economizer, Damper Control
or Humidify
Stage 3 Heat
Stage 1 Cool
Stage 2 Cool or Dehumidify
Power to Heating switched side Power to Heating switched side
Power to Cooling switched side Power to Cooling switched side
Sensor Common
Indoor remote sensor
Setback input
Outside remote sensor
Automation & Controls
Division of PECO, Inc.
Portland, OR 97282
G
A
E
Y1
Y2
RH
RC
SC
S1
S2
S3
Fan Relay
Economizer, Damper Control
or Humidify
Emergency
Compressor Stage 1
Heat / Cool
Compressor Stage 2
Heat / Cool or Dehumidify
Sensor Common
Indoor remote sensor
Setback input
Outside remote sensor
RoHS Compliant
DS-T8000 - 9/10 © PECO, Inc. 2010
800-874-8547 or 503-233-6401
sales@pecomanufacturing.com
www.pecomanufacturing.com