Wind Direction sensor designed for dierent industries and sector
PCE-WV detects the vane position by using
magnetic sensors avoiding wear and tear. It
generates a 4-20mA analogue output or RS485
MODBUS signal, depending on version. The heated
version generates 4-20mA output and works from -20
ºC. When the temperature is higher than +6º C, the
heater switches itself o automatically to reduce the
High resistance to radio frequency interference
(RFI) and electromagnetic interference (EMI)
RS485 MODBUS signal or 4-20mA passive
analogue output
Stainless Steel bearings
Magnetic measuring principle, with no wear and
tear or dead zones
Made in Spain
Page 2
APPLICATIONS
PCE-WV series has been designed to be used in industrial
applications. Connected to devices such as dataloggers, PLCs,
analogue signal displays (see our reference PCE-DPD-U), it
measures the wind direction and/or activates predened alarm
values.
Application examples:
Irrigation control system, automation in greenhouses, solar
trackers, ropeways at ski resorts, cranes, wind turbines,
weather stations etc. All those applications that contribute to a
greater control and greater security. Besides, PCE-WV AH has
been designed for those applications that involve working with
sub-zero temperatures.
OPERATING
Survival speed: 200 km/h of wind speed
It gives a RS485 MODBUS signal or 4-20 mA analogue output
which depends on the wind speed. (see graphic)
The vane must be orientated north as shown in the orientation
section.
RS485 version gives the wind direction in degrees. It calculates
the average position in the last second. In static position it has
20 positions of 18º each one.
The heater works from -20ºC up to +6ºC. Above this
temperature, it switches itself o automatically to reduce the
consumption.
The wind vane must be xed on a vertical position.
DIMENSIONS
PCE-WV CABLE
134,97
Ø5,2
50
924246,065
Ø
185
ORIENTATION VANE
To orientate the vane north, the vane edge must be orientated north as shown
in the picture.
Once the vane has been orientated north, the output signal will correspond to
the angles and directions in the table.
PCE-WV M12 UNDERSIDE
13
Ø18
5
,7
6
Ø
PCE-WV SERIES
Page 3
WIND DIRECTION - OUTPUT RATIO TABLE
DirectionAngleAnalogue
output
North
North-northeast
Northeast
East-northeast
East
East-southeast
Southeast
South-southeast
South
South-southwest
Southwest
West-southwest
West
West-northwest
Northwest
Northwest-North
Static wind
0.04mA00 00
22.55mA00 16
45.06mA00 2D
67.57mA00 43
90.08mA00 5A
112.59mA00 70
135.010mA00 87
157.511mA00 9D
180.012mA00 B4
202.513mA00 CA
225.014mA00 E1
247.515mA00 F7
270.016mA01 0E
292.517mA01 24
315.018mA01 3B
337.519mA01 51
If the wind speed is below 3km/h, the angle will be
uncertain
RS485 output
NOTES:
• There is no version with both outputs (analogue
and RS485).
• The output of the 1s AVERAGE versions when
the vane is moving is a continuous analog output
as result of the average of the last second. When
the vane is static, the output has 20 positions of
18º each one.
CONNECTION
PCE-WV A 4-20mA
PCE-WV AH 4-20mA
Vcc (12-30 Vdc)
Analog Input
(4-20mA)
RL
PLC ground
White wire
Wires colours referenced to the cable
supplied by PCE.
Cable not included in all versions.
1 start bit, 8 data bits and 1 stop bit. 19200 baudios. Even parity. (For other options, please, contact us)
Protocol type:
MODBUS RTU
Addr0400000001CRCHCRCL
The wind direction in degrees is stored in 2 registers: @30001 y @40001. The user can read this value by using any of the 2 available
functions (Read Input Register and Read Holding Register).
The PCE-WV RS485 default adress is 243 <=> 0xF3. This value is stored in Holding Register @40002 and can be edited by the user.
The user can congure any adress in the range 1 (0x01) to 255 (0xFF).
Example: If Addr =3
READING. METHOD 1
Read request of wind direction from master by Read Input Register (function 0x04):
0304000000013028
Slave's answer (PCE-WV RS485 MODBUS RTU):
030402SHSLCRCHCRCL
SHSL is the wind direction value in degrees.
Slave's answer example for 90º (0x005A):
030402005A40CB
READING. METHOD 2
Read request of wind direction from master by Read Holding Register (función 0x03):
03030000000185E8
Slave's answer (PCE-WV RS485 MODBUS RTU):
030302SHSLCRCHCRCL
SHSL is the wind direction value in degrees.
Slave's answer example for 90º (0x005A):
030302005A41BF
PCE-WV SERIES
Page 5
WRITING
Write request of Address by Write Single Register (función 0x06):
0306000100NEW_ADDRCRCHCRCL
Note: The unit adress (Addr) is stored in the Holding Register @40002
Slave's answer (PCE-WV RS485 MODBUS RTU):
0306000100NEW_ADDRCRCHCRCL
NEW_ADDR is the new unit address. It must be in the range from 1 (0x01) to 255 (0xFF).
Example for NEW-ADDR 0x02:
Write request:
0306000100025829
Slave's answer:
0306000100025829
NOTE: the slave's address changes its value inmediately after the answer message.
TECHNICAL FEATURES
PCE-WV A 4-20 mA Electrical features
Power supply12…30 Vdc
Maximum current20 mA
OutputAnalogue (4-20 mA)
Maximum loop impedance
PCE-WV RS485 MODBUS Electrical features
Power supply9…30 Vdc
Maximum current50 mA
OutputRS485
ProtocolMODBUS RTU
Termination resistorNot included
PCE-WV AH 4-20 mA Electrical features
Power supply15…24 Vdc
Consumption with heater
tª >6ºC ( +-3ºC)
Average consumption with
heater
tª <6ºC ( +-3ºC)
Maximum current1.2 A @ 15 V
OutputAnalogue (4-20 mA)
Maximum loop impedance
VCC — 8V
<
L
0.02 A
<0.5 W
<17 W
1.8 A @ 24 V
VCC — 9V
<
L
0.02 A
ΩR
ΩR
Measurements
Range0-360º
Starting speed3 km/h
Survival speed200 km/h
ResolutionAll versions:
22.5º
1 second AVERAGE
versions:
Static position: 18º
Non-static position: 1º
Optional mounting kit for PCE-WS
anemometers & PCE-WV wind vanes
190
65
*Check availability and MOQ
Ø5
Ø27
7,5
50
22,5
25
Ø7
54
Disposal
For the disposal of batteries in the EU, the 2006/66/EC directive of the European Parliament applies. Due to the contained pollutants,
batteries must not be disposed of as household waste. They must be given to collection points designed for that purpose.
In order to comply with the EU directive 2012/19/EU devices must be properly disposed of in accordance with this regulation, we give
them to a recycling company which disposes of the devices in line with law. For countries outside the EU, batteries and devices should
be disposed of in accordance with your local waste regulations. If you have any questions, please contact PCE Instruments.
10
70
54
Ø8
Contact information for each country and user manuals in various
languages can be found on our website: www.pce-instruments.com
All dimensions and sizes are approximate. Specications and prices are subject to change without notice.