PCE Instruments PCE-PCM 1 Users guide

Page 1
OPERATING MANUAL
Page 2
1
Overview
This Operating Manual covers information on safety and cautions. Please read the relevant information carefully and observe all the Warnings and Notes strictly.
Warning
To avoid electric shock or personal injury, read the
“Safety Information” and “Rules for Safe
Operation” carefully before using the Meter.
This clamp is a three phase intelligent handheld
digital power clamp meter (hereafter referred to as “the Meter”) which has both the features of digital current
meter and also power measurement meter.
The Meter can measure Voltage, Current, Active Power, Apparent Power, Reactive Power, Power Factor, Phase Angle, Frequency, Active Energy and etc.
Page 3
2
Unpacking Inspection
Item
Description
Qty
1
English Operating
Manual
1 piece
2
Red Test Lead
3 piece
3
Black Test Lead
1 piece
4
Red Alligator Clip
3 piece
5
Black Alligator Clip
1 piece
6
USB Interface Cable
1 piece
7
Software
1 piece
8
Tool Box
1 piece
9
9V Battery
1 piece
Open the package case and take out the Meter. Check the following items carefully to see any missing or damaged part:
In the event you find any missing or damage, please contact your dealer immediately.
Page 4
3
Safety Information
This Meter complies with the standards IEC61010: in pollution degree 2, overvoltage category (CAT. III 600V, CAT IV 300V) and double insulation.
CAT. III: Distribution level, fixed installation, with smaller transient overvoltages than CAT. IV CAT.IV: Primary supply level, overhead lines, cable systems etc.
Use the Meter only as specified in this operating manual, otherwise the protection provided by the Meter may be impaired.
In this manual, a Warning identifies conditions and actions that pose hazards to the user, or may damage the Meter or the equipment under test.
A Note identifies the information that user should pay attention to.
Rules For Safe Operation
Warning
To avoid possible electric shock or personal injury, and to avoid possible damage to the Meter or to the equipment under test, adhere to the following rules:
Before using the Meter inspect the case. Do not use the Meter if it is damaged or the case (or part of
Page 5
4
the case) is removed. Look for cracks or missing plastic. Pay attention to the insulation around the connectors. Inspect the test leads for damaged insulation or exposed metal. Replace damaged test leads with identical model number or electrical specifications before using the Meter.  Do not apply more that the rated voltage, as marked on the Meter.  When measurement has been completed, disconnect the connection between the test leads and the circuit under test, remove the esting leads away from the input terminals of the Meter and turn the Meter power off. Do not carry out the measurement when the Meter’s back case and / or battery door is opened to avoid electric shock. When the Meter working at an effective voltage over 30V in AC, special care should be taken. Use the proper terminals and functionyou're your measurements. Do not use or store the Meter in an environment of high temperature, humidity, explosive, inflammable and strong magnetic field. The performance of the Meter may deteriorate after dampened. Do not use the Meter if the surface of it is wet or the user’s hands are wet. When using the test leads, keep your fingers behind the finger guards.
Page 6
5
Replace the battery as soon as the battery indicator appears. With a low battery, the Meter might produce false readings that can lead to electric shock and personal injury.
When opening the battery door, must make sure the Meter is power off. When servicing the Meter, use only the same model number or identical electrical specifications replacement parts. The internal circuit of the Meter shall not be altered at will to avoid damage of the Meter and any accident. Soft cloth and mild detergent should be used to clean the surface of the Meter when servicing. No abrasive and solvent should be used to prevent the surface of the Meter from corrosion, damage and accident.
The Meter is suitable for indoor use. Turn the Meter off when it is not in use and take
out the battery when not using for a long time. Constantly check the battery as it may leak when it has been using for some time, replace the battery as soon as leaking appears. A leaking battery will damage the Meter.
Page 7
6
The Meter Structure
Red Blue Yellow Black
A. The Meter Front Structure (see figure 1)
Figure 1
Page 8
7
1
Transformer Jaw: designed to pick up the AC and DC current flowing through the conductor. It could transfer current to voltage. The tested conductor must vertically go through the Jaw center.
2
Hand Guards: to protect user’s hand from
touching the dangerous area.
3
MR button (recall data)
4
SEL / ▲ button (press to select phase and sum of Watts measurement)
5
MAXMIN / ▼ button
6
SAVE button (data store button)
7
LCD Display
8
L2 Input Terminal(Second phase measurement)
9
L3 Input Terminal (Third phase measurement)
10
COM Input Terminal
11
L1 Input Terminal (First phase measurement)
Page 9
8
12
USB button
13
CLEAR button
14
LIGHT button (auto display backlight button)
15
button (Sum)
16
HOLD button
17
Rotary function switch
18
NCV indicate lamp
B. The Meter Back and Bottom Structure
(see figure 2)
Figure 2
Page 10
9
1
Infrared slot
2
USB Interface Cable
Button
Operation Performed
HOLD
Press HOLD to enter the Hold mode any mode, appears and the
Meter beeps. Press HOLD again to exit the Hold mode to return to measurement mode,
the Meter beeps and, disappears.
Press the backlight button when needed. Auto shut-down backlight after lighting 20secs.Press the button again, turn the backlight off manually
At Active power (main display) + Phase angle (secondary display) mode, press once button to sum up
FUNCTION Below table indicated for information about the functional button operations.
Page 11
10
the current phase of 3 phase measurement result. Then carry out second phase power measurement. Press and hold for over 1 second to sum up the phase power measurement result which had been selected.  if you didn`t select any phase of 3 phase, is invaild.
SAVE
Press once to store single reading, and the Meter beeps.The index number shown on the left secondary display keep on increasing. The maximum number of data store is 99, when it achieves 99, the Meter shows .
SEL
press SEL button to step through first phase, second phase, third phase and sum of watts. Press SEL and hold for over 2 second to enter 3P3W mode.
MAXMIN
Press to start recording of maxinmum it valid at voltage, current, active power
Page 12
11
and apparent power ranges only.
CLEAR
At active energy range, press CLEAR and hold for over 1 second to reset time the zero, then restart the timing. At all other ranges, press CLEAR and hold for over 1 second to clear stored readings.
MR
Press once to enter Memory Record mode, appears and the Meter
beeps.
/
If the Meter steps through sum of
power press /button to switch display of active power (main display) , sum of reactive power (secondary display) , sum of power factor (main display) and sum of apparent power.
In the MR mode, press / to
select recoded data.
USB
Measurement data will be sent to the PC
Page 13
12
1. Turn the rotary switch deasil to make the position away from the OFF position. Hearing a beep sound indicates the meter is turned on. The LCD displays all symbols firstly and then return to the normal mode. If the symbol is displayed, please changed the battery.
2. After auto-shut-off, there are some parts of the circuit of the meter which is still work. If no measurement needed in a
longer time, you’d better turn the rotary switch back to the
OFF position.
3. Press the backlight button when needed. Auto shut-down backlight after lighting 18secs.Press the button again, turn the backlight off manually
Display Symbols (see figure 3)
Figure 3
Page 14
13
USB
Data Output is in progress
First phase symbol
Second phase symbol
Third phase symbol
h
Unit for hour
mm
Unit for minute
HZ
PG
KVAr
Hz: Hertz.The unit of frequency.
PG: The unit of phase angle
KVAr. The unit of reactive power
W
Watt: Sum of Watt
The battery is low.
Warning: To avoid false
readings, which could lead to
possible electric shock or
personal injury, replace the
battery as soon as the battery
indicator appears.
S
Unit for second
Page 15
14
MAX
MIN
Maxinum and Minimum reading
Analogue Bar Graph
Overloading
Ruler
CLEAR
Indicator for clear the stored reading
Negative symbol
High voltage symbol
AC
Indicator for AC voltage or current
MR
Indicator for recall the stored
reading
Hz
Frequency symbol
MEM
Indicator for data store
FUL
Indicator for data stored is full
Data hold is active
Page 16
15
Measurement Operation
Preparation
Dial the Rotary to any active measure range
Replace the battery as soon as the battery indicator
appears on the display. Non-Contact Voltage Detector
WARNING: Risk of Electrocution. Before use, always test the
Voltage Detector on a known live circuit to verify proper operation.
1. Rotate the Function switch to any measurement position.
2. Place the detector probe tip on the conductor to be tested. NOTE: The conductors in electrical cord sets are often twisted.
For best results, move the probe tip along a length of the cord to assure placing the tip close to the live conductor.
NOTE: The detector is designed with
high sensitivity. Static electricity or other sources of energy may randomly trip the sensor. This is normal operation.
Page 17
16
A. AC Voltage (main display) + Frequency
Red
(secondary display) Measurement (see figure 4)
Figure 4
The AC Voltage ranges are:100V, 400V and 750V
The frequency range is:50Hz~60Hz
To measure AC voltage + frequency, connect the Meter as follows:
1. Insert the red test lead into the L1, L2, L3 input terminal, and black test lead to the COM input terminal.
2. Dial the Rotary to VAC to select Voltage + Frequency range.
3. Connect the red test leads (L1, L2, L3 input terminal)to the corresponding three phases loaded live wire. Black test lead (COM input terminal) to the corresponding three phases loaded neutral wire.
Page 18
17
4. Press SEL to select phase location, the display shows the corresponding phase symbol. L1 means the first phase , L2 means the second phase , L3 means the third phase .
5. The display shows the corresponding True RMS voltage value and frequency value of each phase.
6. Press MAXMIN, the LCD displays , it starts recording the maximum AC voltage True RMS value.
7. Press MAXMIN the LCD displays , it starts recording the minimum AC voltage True RMS value. Press MAXMIN again to show the current AC voltage True RMS value.
8. The display shows 0L when the input voltage is higher than 750V rms.
Note
When the measurement has been completed, disconnect the connection between the testing leads and the circuit under test and remove testing leads from the input terminals.
Page 19
18
B. AC Current (main display) + AC Voltage (secondary display) Measurement (see figure 5)
Figure 5
The AC current ranges are: 40A, 100A, 400A and 1000A
The AC Voltage ranges are: 100V, 400V and 750V
To measure AC current + AC voltage, connect the Meter as follows:
1. Dial the Rotary to AAC to select AC Curren + AC Voltage range.
Page 20
19
2. Press the lever to open the transformer jaw.
3. Center the conductor within the transformer jaw, then release the Meter slowly until the trasnformer jaw is completely closed, Make sure the conductor to be tested is placed at the center of the transformer jaw, otherwise it will casue deviation. The Meter can only measure one conductor at a time, to meausre more than one condutor at a time will cause deviation.
4. The double display shows the AC current True RMS value and AC voltage True RMS value.
5. Press MAXMIN, the LCD displays , it starts recording the maximum AC current True RMS value.
6. Press MAXMIN, the LCD displays , it starts recording the minimum AC current True RMS value. Press MAXMIN, again to show the present AC current True RMS value.
7. The display shows 0L when the current of the tested conductor is higher than 1000A rms.
Note
When the measurement has been completed, disconnect the connection between the conductor under test and the jaw, and remove the conductor away from the transformer jaw of the Meter.
Page 21
20
C. Active Power (main display) + Phase Angle (secondary display) Measurement
Warning To avoid damages to the Meter or harms to you, do you measure higher than AC voltage 750 v and AC current 1000A.
To measure active power + phase angle, connect the Meter as follows:
1. Diar the Rotary to KW to select Active power + Phase angle range.
2. Press the lever to open the transformer jaw, and clamp them to the corrresponding phase of tested conductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phase’s conductor.
3. Connecting method (see figure 6, 7, 8):
4. Insert red test leads to L1, L2, L3 input terminal and connecting it to every live wire of the 3 phase.
5. Insert black test leads to COM input terminal and connect it to the neutrual wire of the 3 phase. When measuring 3 phase 4 wires, connecting the Meter as figure 6.
Page 22
21
Figure 6
Red
Blue
Yellow
Measuring instruction
1. Press SEL to choose first phase , see figure 7. The double displays show the acitve power kW value and the PG value of the second phase 1.
Figure 7
Page 23
22
If necessary, press to get the sum of watts as figure
8.
Figure 8
2. After record the current power measurement value of the first phase, then press SEL to choose , The double display shows the value of acitve power kW and PG of the second phase 2. as figure 9
Figure 9
Page 24
23
If ncessary, press to get the sum of watts as figure
10.
Figure 10
3. After record the current power meaursuremnt value of the second phase, then press SEL again to choose
, The double display shows the value of acitve
power KW and PG of the third phase. as figure 11.
Figure 11
Page 25
24
If ncessary, press to get the sum of watts as figure12
Figure 12
4. After record the current power measurement value of the third phase, finally press and hold for 1seconds to display the 3 phase sum of acitve power value and apparent power value, as figure 13.
Figure 13
Press as figure 14 to step through in sequence
three
Page 26
25
phase sum of active power+three phase sum of reacitve power, and three phase sum of power factor + 3 phase sum of apparent power.
Figure 14
Press and hold for 1seconds again back to the normal measuring mode. In figure 6 W = W1 + W2 + W3. When measuring 3 phase 3 wires, Hold SEL for 5 seconds and the Meter show , press SEL again for 5 seconds to exit 3 phase 3 wires ,connecting the Meter as figure 15.
Page 27
26
Figure 15
1. Insert red test leads to L1, L3 input terminal.
2. Insert black test leads to COM input terminal and connect it to the neutrual wire of the 3 phase.
3. Jump over the second phase measurement.
4. The first and the third phase measuring method is same as 3 phase 4 wires. In figure 15 W = W2 + W3. NOTE It can only sum up the current measurement value. The maximum and minimum value cannot be summed up.
Only at KW range can carry out sum of watts measurement, other ranges cannot carry out this measurement. When testing has been completed, disconnect the connection between the testing leads and the circuit under test and remove testing leads from the input terminals.
Page 28
27
D. Apparent Power (main display) + Reactive Power (secondary display) Measurement  Please refer to C E. Reactive Power (main display) + Apparent Power (secondary display) Measurement Please refer to C. F. Power Factor (main display) + Phase Angle (secondary display) Measurement
Warning To avoid damages to the Meter or harms to you, do you measure higher than AC voltage 750V rms and AC current 1000A rms.
To test for Power factor (main display) + Phase angle (secondary display), connect the Meter as follows:
1. Dial the Rotary to cosθ to select Power factor + Phase angle range.
2. Press the lever to open the transformer jaw, and clamp them to the corrresponding phase of tested conductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phase’s conductor.
3. The connecting method of 3 phases 4 wires or 3 phases 3 wires, refer to figure 6 and 15
4. When measuring 3 phase 4 wires: (see figure 18, 19 and 20) Press SEL to choose the first phase , see figure
18.
Page 29
28
Figure 18
The double display shows the first phase value of
power factor PF and phase angle PG.
Then press SEL again to choose the second phas,
see figure 19. Press SEL to choose the second phase , see
figure 19.
Figure 19
The double display shows the second phase value of
Page 30
29
power factor PF and phase angle PG.
Then press SEL again to choose the third phas, see figure 20. Press SEL to choose the third phase , see figure
20.
Figure 20
5. When measuring 3 phase 3 wires: The first phase and third phase operating method is same as 3 phase 4 wires. Jump over the second phase measurement.
6. MAXMIN button are not valid when measuring power factor.
F. Active Energy (main display) + Time (secondary display) Measurement
Warning To avoid damages to the Meter or harms to you, do you measure higher than AC voltage 750V rms and AC current 1000A rms.
To test for Active Energy (main display) + Time (secondary display), connect the Meter as follows:
Page 31
30
1. Dial Rotary to ENERGY range.
2. Press the lever to open the transformer jaw, and clamp them to the corrresponding phase of tested conductor. If user needs to mesaure any phase of the 3 phase, then clamp them to that phase’s conductor.
3. The connecting method of 3 phase 4 wires and 3 phases 3 wires, see figure 6 and 15
4. Press SEL to choose one of the three phases, see figure 21.
Figure 21
The double display shows the value of tested
object’s active engergy kWh value and the measuring time of the corresponding phase. The measuring reading gets increasing along with the time increases. Press HOLD to read a particular time kWh value. Then the reading and time are locked, but still continuous accumulate measuring time. After read the data, press HOLD again to continous measurement. kWh value continous accumulate and the measuring time jumps to the present measuring time.
Page 32
31
When the measuring time is over 24 hours or the Meter is switched to other measuring ranges, active energy measuring will stop. The maximum readinng of acitve energy is 9999kWh. OL will be displayed when the reading is over than that.
5. MAXMIN are not valid when measuring active energy.
6. Press CLEAR and hold for 1 seconds to reset the time and energy.
Note
When there is no input signal, it cannot carry out active energy measurement. When testing has been completed, disconnect the connection between the testing leads and the circuit under test and remove testing leads from the input terminals.
True RMS Measurement and Average Value Measurement
The True RMS measurement method can measure accurately the effective value of non-sine wave input signal.
Average value measurement method can measure the mean value of one sine wave input signal, and then displays it as RMS value When the input waveform has distortion, measuring
tolerance will be included. The total tolerance depends on the total distortion. Below table 1 shows the waveform coefficient and the relationship and the requested changing factor of sine wave, square wave,
Page 33
32
pulse rectangle wave, sawtooth triangle wave, RMS
22
KVArKW
value and average value. The clamp Meter software designning base on the following formula:
KW = KVA × Cosθ KVAr = KVA × Sinθ KVA =
Page 34
33
Accurate Specifications
Range
Reso lution
Accuracy
Allowable Maximum overload protection voltage
Input Imped ance
Frequency Range
100V
0.1V
±
(1.2%+5)
750 RMS
10M
50Hz~200 Hz
400V
750V
Range
Resolution
Accuracy
50Hz~200Hz
1Hz
±(0.5%+5)
Accuracy: (a% reading + b digits), guarantee for 1 year. Operating temperature: 23℃±5 Operating humidity: 45~75%R.H
A. AC Voltage (True RMS)
B. Frequency
Page 35
34
C. AC Current (True RMS)
Range
Resolution
Accuracy
Allowable Maximum
overload
protection
current
Frequency
Range
40A
0.1A
±(2%+5)
1000A RMS
50Hz~60Hz
100A
400A
1000A
1A
Current / Voltage
Voltages Range
100V
400V
750V
Current Range
40A
4.00KW
16.00KW
30.00KW
100A
10.00KW
40.00KW
75.00KW
400A
40.00KW
160.0KW
300.0KW
1000A
100.0KW
400.0KW
750.0KW Accuracy
±(3%+5)
Resolution
<1000KW: 0.01KW 100kW: 0.1KW
D. Active Power ( W=V x A x COSθ )
Page 36
35
E. Apparent Power (VA = V x A)
Current / Voltage
Voltages Range
100V
400V
750V
Current Range
40A
4.00KVA
16.00KVA
30.00KVA 100A
10.00KVA
40.00KVA
75.00KVA
400A
40.00KVA
160.0KVA
300.0KVA
1000A
100.0KVA
400.0KVA
750.0KVA
Accuracy
±(3%+5)
Resolution
<1000KVA: 0.01KVA 100kW: 0.1KVA
Page 37
36
F. Reactive Power (Var = V x A x SINθ )
Current / Voltage
Voltages Range
100V
400V
750V
Current
Range
40A
4.00KVAr
16.00KVAr
30.00KVAr
100A
10.00KVAr
40.00KVA
75.00KVAr
400A
40.00KVAr
160.0KVAr
300.0KVAr
1000A
100.0KVAr
400.0KVAr
750.0KVAr Accuracy
±(3%+5)
Resolution
<1000KVAr: 0.01KVAr 100kW: 0.1KVAr
Range
Accuracy
Resolution
Measuring Condition
0.3~1
(capacitive
or
inductive)
±0.022
0.001
The minimum measuring
current 10A
The minimum measuring
voltage 45V
0.3~1
(capacitive
or
inductive)
For reference only
Measuring current less
than 10A OR
Measuring voltage less
than 45V
G. Power Factor (PF = W / VA)
Page 38
37
H. Phase Angle (PG=acos (PF))
Range
Accuracy
Resolution
Measuring Condition
0O ~90
O
(capacitive or inductive)
±2O
1O
The minimum measuring current 10A The minimum measuring voltage 45V
0O ~90O (capacitive or inductive)
For reference only
Measuring current less than 10A OR Measuring voltage less than 45V
Range
Accuracy
Resolution
1~9999kWh
±(3%+2)
0.001kWh
I. Active Energy (kWh)
Remarks: Allowable maximum overload protection voltage: 750V RMS Allowable maximum overload protection current: 1000A RMS
Page 39
38
SPECIFICATIONS
Basic Functions
Range
Best Accuracy
AC Voltage
100V/400V/750V
±(1.2%+5digits)
AC Current
40A/100A/400A/1000A
±(2%+5 digits)
Active Power
0.01kW-750kW
±(3%+5 digits)
Apparent Power
0.01kVA-750kVA
±(3%+5 digits)
Reactive Power
0.01kVAr-750kVAr
±(4%+5 digits)
Power Factor
0.3~1(Capacitive or
Inductive )
±(0.02+2 digits)
Phase Angle
0O ~90
O
±2
O
Frequency
50Hz-200Hz
Active Energy
0.001~9999 kWh
±(3%+2 digits)
Temperature
-50OC~1300OC
-58OF~2372OF
Special Functions
Auto Ranging
Single-phase 2-wire
Balance 3-phase
3-wire
Page 40
39
3-phase 4-wire
True RMS
AC Voltage or Curren
Data Logging
99
Data Recall
Max/Min Mode
Data Hold
USB
Display Backlight
Full Icon Display
Sleep Mode
Low Battery Display
Input Impedance for
AC Voltage
Measurement
Around 10MW
Max. Display
9999
Analogue Bar Graph
Page 41