The PCE-P18 transducers are the devices destined for
the continuous measurement and conversion of relative
humidity and ambient temperature into a digital form and
into a voltage or cur-rent standard signal. The
transducers are fixed on a wall. Programming of the
transmitters is possible via the RS?-485 interface. LPCon
or eCon software designed for configuration of the
transducers is available on the manufacturer’s website:
www.pce-instruments.com. Applied sensor shields
enable the application of the transducers in various
ambient conditions.
Fig. 1. Overview of the P18 and P18D transducers with the probe
on the housing.
5
Page 6
Fig. 2. Overview of the P18 and P18D transducers with the probe
on the wire 0,5 m.
6
Page 7
2. TRANSDUCER SET
−
Transducer 1 pc
−
User’s manual 1 pc
−
Warranty card 1 pc
3. BASIC REQUIREMENTS,
OPERATIONAL SAFETY
In terms of operational safety, the transducer meets
the requirements of the EN 61010-1 standard.
Comments concerning safety
Assembly and installation of the electrical connections should
•
conducted only by people authorised to perform assembly of electric devices.
Always check the connections before turning the transducer on.
•
The transducer is designed to installation and usage in the indu-
•
strial electromagnetic environment.
4. INSTALLATION
4.1. Assembly
The P18(D) transducer is designed to be mounted on a wall by
means of a screw connection or glue without the loss of IP65 tightness.
The transducer housing is made of a self-extinguishing plastics. The transducer has screw connectors placed inside the transducer, which enable
the connection of external wires of 1 mm
2
cross-section.
7
Page 8
Fig. 3. Overall dimensions of the P18(D) transducer
mounting holes
Fig. 4. Lay-out of mounting holes of the P18(D) transducer
8
Page 9
4.2. External connection diagrams
The P18(D) transducer version P18(D)-1XXX or P18(D)2XXX
has 8 connecting terminals, version P18(D)-0XXX has 4 terminals (version without analog outputs). Access to the terminals is possible after
removing the cover of the transducer housing. You should use a multiconductor round wire with external diameter from 3.5 mm up to 6 mm
for electrical connections. Remove the display prior to connecting the
wires in a screw terminal of the P18D transducer. Pass supplying wires through the packing and twist the packing seal in order to obtain
the leaktightness. If the packing seal is not twisted, the required IP 65
leaktightness is not ensured. The LCD display should be put back after
screwing the wires to the screw terminal of the P18D transducer.
a)b)
Fig. 5. Marking of the terminals for the connection of external signals
of the P18(D) transducers in versions: a) without analog outputs,
b) with analog outputs.
9
Page 10
Transducer without
analog outputs
Out
Out
1
Out2Out
1
2
Transducer with current
outputs
Transducer with voltage
outputs
Fig. 6. Wiring diagram of the P18(D) transducer with analog outputs
Use shielded cable for supply and output signals in environments with high levels of interference. The shield must be connected
to the nearest PE point from the feeder side.
10
Page 11
5. SERVICE
The P18D transducer is equipped with a display field
8x2 characters with illumination and one capacitive button located
on the housing. The P18 transducer is not equipped with a display
or a button. After connecting the wires, closing and servicing
the housing, and connecting to the supply, the transducer is ready
to work with manufacturer’s settings (Tab. 4). The transducer can be
programmed through the RS-485 interface. You can program following
parameters in the transducer:
communication parameters
−
- averaging time of the measurement
−
- individual characteristics of analog outputs (for executions with
−
analog outputs).
The P18D transducers allow programming communication parameters (address, baud rate, mode) using the capacitive button.
There is the possibility to connect the transducer through another transmission media, like: ETHERNET, USB using LUMEL S.A.’s converters.
5.1. Power-on messages of the P18D transducer
After connecting the external signals and connecting
to the supply, the transducer displays the type, current program version,
serial number and set communication parameters (address, baud rate
and operating mode).
The transmitter automatically switches to the operating mode of measurement and processing the analog output signal after approx. 5 seconds. It displays the measuring value with the unit in the bottom line
of the display, the top line of the display contains information about the
type of displayed quantity and the pictograms of: transmission via RS485, the presentation mode of the measuring value, the read pointer of
the measuring value of the sensor and the operating state of the internal
heater.
11
Page 12
5.2. Description of the P18D transducer readout field
The illuminated character LCD is a readout field in the transducer P18D. The illumination is turned on after switching on the supply
and after the capacitive button on the housing is pressed. The illumination is automatically switched off after 30 sec. of inactivity.
Indicator of the measuring value
from the sensor
Type of the displayed value
Value of the displayed
value
Indicator of automatic presentation of the measuring values
Transmission indicator on
RS-485 link
Unit of the displayed
value
Fig. 7. Description of the P18D transducer readout field
Description of the symbols displayed by the P18D transducer is in the Table 1.
Table 1
SymbolMeaning
T:
RH:
Type of the displayed value in the bottom line
of the LCD - temperature
Type of the displayed value in the bottom line
of the LCD - relative humidity
12
Page 13
DP:
AH:
h
5.3. Functions of the P18D transducer capacitive button
The P18D transducers are equipped with one capacitive
button located on the housing. The location of the button shows in Fig. 8.
Type of the displayed value in the bottom line
of the LCD - dew-point
Type of the displayed value in the bottom line
of the LCD - absolute humidity
The indicator of the measuring value from the sensor
Automatic mode of measurement results presentation
- a type of displayed value is automatically switched
every 3 seconds in the following order: temperature →
relative humidity → dew-point → absolute humidity →
temperature ….
Data receiving indicator by the P18D transducer
on RS-485
Data sending indicator by the P18D transducer
on RS-485
Switching on the internal heater indicator to dry
the sensor
Fig. 8. Location of the P18D transducer capacitive button
13
Page 14
Capacitive button is used to:
switch the display illumination on
•
change the presentation mode of the measurement results -
•
holding the button for about 2 seconds switches from automatic
mode to manual mode or inversely
change the type of displayed values in the manual mode of presen-
•
tation of the measurement results - pressing the button for a short
time changes the displayed value.
program communication parameters (address, baud rate, mode)
•
5.4. Programming parameters menu of the P18D transducer
Enter the programming menu by pressing and holding
the capacitive button for approx. 5 sec. When entering the menu a first
time, changes direction marker is set to - increasing the value;
next entry in the menu will cause the cyclic switching of the direction
of changes (2 input in the menu will set the marker at v – decreasing
the value). If the idle time exceeds 20 seconds, the transducer will leave
the menu and switch to displaying the measuring value.
Baud
rate
Mode
Address
Direction
of changes
Fig. 9. The displayed information of the transmission parameters in the
P18D transmitter menu
14
Page 15
Confirmation
of changes
5 seconds
Application
of changes
Measurement
5 seconds
Mode programming
increase/
decrease
the value
decreasing the value
increasing the value
5 seconds
Baud rate programming
increase/
decrease
the value
5 seconds
Address programming
increase/
decrease
the value
Fig. 10. Programming parameters algorithm of the P18D transducer
5.5. Functions of the P18(D) transducer
The P18(D) transducer carries out the functions:
measurement of the ambient temperature and relative humidity
•
calculation of chosen physical quantities (dew-point temperature,
•
absolute humidity, wet bulb temperature)
conversion of measured values into an output signal on the base
•
of the individual linear characteristic (2 configurable analog outputs
- optional)
memory storage of maximal and minimal values for each
•
of the measured and calculated value
programming of the measurement averaging time
•
RS-485 interface servicing in the MODBUS protocol, in RTU
•
mode.
Displaying measuring and calculated values (only P18D)
•
5 seconds
15
Page 16
5.5.1. Calculated values
Based on the measurement of a temperature and relative
humidity, the P18D transducer calculates dew-point and absolute humidity of the following dependencies.
T
n
m
ws
RH
- 1
)
DP → dwe-point:
DP =
log (P
10000 A
RH
P
DP → absolute humidity:
AH = 2,1668
ws
100 (T + 273,2)
gdzie:
T → measured temperature [
o
C]
RH → measured absolute humidity [%]
DP → dew-point temperature [
P
→ saturated water vapor pressure (water vapor pressure) [mbar]
ws
AH → absolute humidity [g/m
Table 2
o
C]
3
]
The factors used to calculate the dew-point
o
C]AmT
T [
< 0
0...50
50...100
6.1198667.926104250.4138
6.10787.5237.3
5.99877.3313229.1
n
5.5.2. Selection of controlling values for analog outputs
The P18(D) transducers in versions P18(D)-1XX, P18(D)2XX, P18(D)-4XX, P18(D)-5XX are equipped with two programmable
analog outputs (voltage or current). By default, the first analog output
is set for a presentation of the ambient temperature and the second
analog output is controlled by the value of the relative humidity. The analog outputs can respond to any of the measuring or calculated values
16
Page 17
(T, RH, DP, AH, wet bulb temperature). The value controlling the analog
outputs is defined by the registers, respectively 4015 for the first output
and 4016 for the second analog output (Tab. 14).
5.5.3. Individual characteristic of analog outputs
The P18(D) transducers in the version with analog outputs
enable the conversion of measured values into an output signal based on the strength of individual linear characteristic of analog outputs.
On the base of given coordinates of two points by the user, the transducer determines (from the system of equations) coefficients a and b
of the individual characteristic.
Y1out = a X1in + b
{
where:
X1 in and X2 in - displayed value,
Y1 out and Y2 out - oexpected value of the analog output
Y2out = a X2in + b
Fig. 11. Individual characteristic of analog output
17
Page 18
The configuration of the individual characteristic of analog
outputs amounts to the introduction of suitable values X1, X2, Y1, Y2
in corresponding registers to them from the range 4007 – 4014 Tab. 3.
The values introduced in these registers must be integral values corresponding to the set point values multiplied by the value 100.
Example 1
Configuration of the individual characteristic of the first analog current
output (temperature):
Expected processing temperature in the range -12,25
o
C ÷ 77,75 oC
to the analog current signal in the range 4,5 mA ÷ 18,5 mA.
Table 3
NameRegister addressValue
X1 temperature4007-1225
Y1 current4008450
X2 temperature40097775
Y2 current40101850
Caution:
The analog outputs are not isolated from the supply,
the RS-485 interface and each other, the analog current outputs don’t
have a common potential (low potential terminals can not be connected together), analog voltage outputs have a common low potential
(low potential terminals can be connected together).
18
Page 19
5.5.4. Support of a sensor heater
The sensors used in the P18(D) transducers are equipped
with internal heating elements to allow faster release of water molecules from the sensor being flooded or working a long time in highly humid environments. Switching the heater on is possible by writing the
appropriate value to the register 4021 (see Tab. 14). Status of the heater
is available in the status register (register 4017) at the bit position 11
(if the bit 11 of the register 4017 is set to „1” - this means that the heater
is switched on).
Caution:
The transducer with a heating element switched on does not measure
the proper ambient temperature and humidity! (the temperature measured by the sensor increases and the humidity decreases). The value
200 is added to the measuring values (temperature, relative humidity)
when using the transducer with the heater switched on in order to avoid
distortions of a measurement in the measurement systems!
The P18D transducers working with a heating element switched on display a flashing symbol h.
Fig. 12. Indication of the P18D transducer operation
with a heater switched on
19
Page 20
5.5.5. Default settings
The Table 4 shows the standard settings of the P18D transducer. The settings can be restored via the RS-485 interface after writing
the value „1” to the registry 4020.
Table 4
Parameter
description
Address40011
Baud rate40029600
Mode4003RTU 8N2
Averaging time400530 [s]
X1 of the 1st
analog output
Y1 of the 1st
analog output
X2 of the 1st
analog output
Y2 of the 1st
analog output
X1 of the 2nd
analog output
Y1 of the 2nd
analog output
X2 of the 2nd
analog output
Y2 of the 2nd
analog output
Parameter
address
40070-2000-2000
400804000
4009060006000
4010020001000
4011000
401204000
401301000010000
4014020001000
P18D-0XX,
P18D-3XX
Standard value
P18D-1XX,
P18D-4XX
P18D-2XX,
P18D-5XX
20
Page 21
Value controlling the first
analog output.
Value controlling the second
analog output.
Custom configuration
4015000
4016111
4019888
6. RS-485 INTERFACE
The P18(D) programmable digital transducers have a serial link
RS-485 for communication in the computer systems and with other devices that serve as a Master. Asynchronous character MODBUS communication protocol has been implemented in a serial link. The transmission protocol describes how to exchange information between devices
via a serial link.
Caution:
For the transmitter versions without analog outputs (P18 (D) -0XX
and P18 (D) -3XX), the RS-485 interface is galvanically isolated from
the supply - 1 kV separation.
For the transmitter versions with analog outputs, the RS-485 interface is not isolated from the supply or from the analog outputs.
6.1. Connection of the serial interface
Standard RS-485 allows a direct connection up to 32 devices
on a single serial link to a length of 1200 m (at baud rate 9600 b/s).
It is necessary to use additional intermediate-separation circuits for connecting higher number of the devices, for example PD51 manufactured
by LUMEL S.A.
21
Page 22
Output of the interface line is shown in Fig. 6. It is required to connect the lines A and B in parallel with their equivalents in other devices
to obtain the correct transmission. The connection must use a shielded
wire. The cable shield should be connected to the protective terminal
in close proximity to the transmitter (connect a shield to the protective
terminal at one point only).
RS-485 interface card or the converter is required for a connection
to a PC, for example PD10. The method of connecting devices is shown
in Fig. 13.
22
Fig. 13. Connecting the RS-485 interface.
Page 23
6.2. Description of the MODBUS protocol implementation
The implemented protocol is compliant with the PI-MBUS-300
Rev G specification of Modicon.
Set of parameters of the P18D transducer serial link in the MODBUS
protocol:
Configuration of the serial link parameters consists of determining
the baud rate, the device address and the format of the transmission
mode - protocol.
Caution: Each transmitter connected to the communication network must:
•
have a unique address, different from the addresses of other devices connected to the network.
•
Identical baud rate and type of a transmission mode
6.3 Description of the functions used
Following functions of the MODBUS protocol have been implemented
in P18D transducers:
•
03 (03h) – readout of registers group,
•
04 (04h) – readout of input registers group,
•
06 (06h) – single register writing,
•
16 (10h) – registers group writing,
•
17 (11h) – slave device identification.
23
Page 24
Readout of n-registers (code 03h)
Example 1. Readout of 2 registers, starting with the register address
Example 2. Writing the value 78h (120) to the register FA1h (4001)
Request:
Device
address
01h06h0FhA1h00h78hDB1Eh
Function
Register addressRegister value
B1B0B1B0
Table 7
CRC
checksum
Response:
Device
address
01h06h0FhA1h00h78hDB1Eh
Function
Register addressRegister value
B1B0B1B0
Table 8
CRC
checksum
24
CRC
check-
sum
Page 25
Writing n-registers (code 10h)
Example 3. Writing the value 78h (120) and the value 4h (4) to the regi-
sters FA1h, FA2h (4001, 4002)
Register
value
4002
Table 9
Table 10
checksum
Request:
De-
vice
Function
Register
address
Function
ad-
dress
01h10h0Fh A1h 00h 78h04h00h 78h 0004F831h
Response:
Device
address
01h10h0FhA1h00h02h133Eh
Number of
registers
Register addressNumber of registers
B1B0B1B0
Register
Number of
bytes
B1B0B1B0
value
4001
Device identification report (code 11h)
Example 4. Device identification
Request:
Device
address
Response:
Device
ad-
dress
01h11h0EhCChFFh
FunctionChecksum
01h11hC02Ch
Function
Number of
bytes
Table 11
Identi-
fier
P18D
De-
The field depending on the
vice
status
device software version
50h 31h 38h 44h 76h 2Eh
30h 2Eh 30h 34h 20h 00h
(e.g. 0.70)
Table 12
check-
B154h
CRC
check-
CRC
CRC
sum
sum
25
Page 26
6.4 Map of the registers
In the P18D transducer, data are placed in 16 and 32-bit
registers. Process variables and transducer parameters are placed
in the address area of registers in a way depended on the variable
value type. Bits in 16-bit registers are numbered from the youngest
to the oldest (b0 … b15). The 32-bit registers (4 bytes) contain numbers
of float type in IEEE-754 standard. Bytes sequence: B3 B2 B1 B0 –
the oldest byte is transmitted as the first.
A following map is the map of P18(D) transducers registers.
Caution:
All listed addresses are physical addresses. Some computer programs
use logic addressing, then the addresses should be increased by 1.
Table 13
Address
range
4000-4022integer
6000-6030float (32 bits)
7000-7030float (32 bits)
7500-7515float (32 bits)
Value typeDescription
The value is located in the 16-bit register.
(16 bits)
Value set in the two following 16-bit
registers. These registers contain the same
data as 32-bit registers from 7500-7515
range. Readout registers. Bytes sequence
(B1,B0,B3,B2)
Value set in the two following 16-bit
registers. These registers contain the same
data as 32-bit registers from 7500-7515
range. Readout registers. Bytes sequence
(B3,B2,B1,B0)
The value is located in the 32-bit register.
Registers contain measured and calculated
data by the transducer. Registers are only
for readout.
Transducer status. Shows
the current state of the transducer and the hardware configuration. Successive bits
represent the event. Bit set
to 1 indicates that the event
took place.
Bit15 Restart of the supp-
ly, writing the value
-32768 (8000h) will
clear the status bit
Bit14 Error of the calibra-
tion parameters
Bit13 Error of the transmit-
ter settings - enter the
new settings
29
Page 30
Bit12 not used
Bit11 Indicator of switching
the heater on
Bit10 Indicator of erasing
the extremes, writing
the value 1024 (400h)
erases the status bit
Bit9Temporary commu-
nication parameters
are set (shorten jum-
per „ZW”)
Bit8LCD display error
Bit7Error reading the va-
lue from the sensor
Bit5,6Value controlling 2
analog output
00011011
30
temperature
dew-point
relative humidity
absolute humidity
Bit3,4Value controlling 1
analog output
00011011
temperature
dew-point
relative humidity
absolute humidity
Page 31
4018 Software
version
4019 Custom
configuration
Bit2results averaging in-
terval has ended
Bit1The transducer is equi-
pped with the analog
outputs - voltage.
Bit0The transducer is equi-
pped with the analog
outputs - current.
o
1...999Software version x100
w/
0...31Bit0ValueDescrip-
r
Bit1
Number of characters
...4
of a response delay
to the query for the
RS-485 transmission
tion
0The stan-
dard map
of the registers in
the range
7000 and
7500
1Map of
the registers in
the range 7500
and 7000
compliant
with the
map of
the P14W
transducers
31
Page 32
4020 Default
settings
4021 Controlling
the heater
4022 reserved
w/
r
0...1Value
0no change
1przywraca parametry
Value
0switching a heater off
1permanent switching
3displaying remaining
60
...
32768
Description
fabryczne
Description
a heater on
time of a heater switched on
switching a heater on
for Xn seconds (Xn value from the range
60...32768 )
32
Page 33
6.6 Registers for readout
Table 15
Name
32-bit registers
from the area 7500.
Unit
Quantity name
Write (w)/ readout (r)
The value is located in the
Value set in the two following 16-bit registers.
Registers contain the same data as 32-bit registers
70007500IDr-P18(D) device identifier
o
70027501Tr
Measured temperature
C
70047502RHr%Measured relative humidity
o
70067503DPr
70087504AHr
CCalculated dew-point
3
Calculated absolute humi-
g/m
dity
o
70107505min Tr
70127506max Tr
Min. of temperature
C
o
Max. of temperature
C
70147507min RHr%Min. of relative humidity
70167508max RHr%Max. of relative humidity
o
70187509min DPr
Min. of dew-point
C
33
Page 34
70207510max DPr
70227511min AHr
70247512max AHr
70267513r
o
Max. of dew-point
C
3
Min. of absolute humidity
g/m
3
Max. of absolute humidity
g/m
o
Wet bulb temperature
C
70287514rkPaWater vapor pressure
Table 16 shows the registers of measuring values of the P18D transducer working in the registers 7000 and 7500 compatibility mode with the
P14W transducer
Table 16
from the area 7500.
gisters contain the same data as 32-bit registers
Value set in the two following 16-bit registers. Re-
Name
32-bit registers
The value is located in the
Unit
Quantity name
Write (w) /readout (r)
70007500IDo-P18(D) device iden-
tifier
34
Page 35
70027501To
70047502DPo
70067503---
70087504RHo%
70107505AHo
g/m
70127506--70147507--70167508--70187509min T
70207510max T
70227511min DP
70247512max DP
70267513--
70287514--
70307515min RH
o%
70327516max RHo
70347517min AH
70367518max AHo
o
g/m
g/m
o
Measured tempera-
C
ture
o
Calculated dew-point
C
Measured relative
humidity
3
Calculated absolute
humidity
o
Min. of temperature
C
o
Max. of temperature
C
o
Min. of dew-point
C
o
Max. of dew-point
C
-
-
Min. of relative
humidity
Max. of relative
%
humidity
Min. of absolute
3
humidity
Max. of absolute
3
humidity
35
Page 36
6.7 Emergency restoration of default parameters
If the communication parameters have been changed and the
new configuration is lost, you can use the jumper marked „ZW” on the
transmitter’s board to set the temporary communication parameters:
address 247
•
baud rate 9600 kb/s
•
mode RTU 8N2
•
You can connect to the transmitter after setting the temporary parameters and adjust them or restore the defaults settings. After removing
the jumper, the transducer returns to previous settings or to settings
changed during the operation with the jumper.
jumper ZW
Fig. 13. Placement of the jumper setting temporary communication
parameters
36
Page 37
7. ERROR CODES
The error messages could be displayed on the transducer
P18D display during operation. The table below lists the error codes
which are possible to be displayed and their reasons as well as the
recommended user responses. Information about the existing errors is
also available in the P18(D) transducers status register - register 4017.
Table 17
Message
Error
Sensor
Error
Calibr.
Error
Param.XX
bit no.
reg. Status
(reg. 4017)
Description
7Sensor failure - transmitter should be
returned to a service
14Loss of calibration parameters - loss
of efficiency of the analog outputs,
measurements are correct - returning
a transmitter to a service should be
considered
13
Loss of transmitter settings - XX
- number of a parameter (register
number 40XX) configured incorrectly
- correct value should be written to
the register 40XX or default settings
restored
37
Page 38
8. ACCESSORIES
As a standard, the P18(D) transducer is equipped with a shield
of the sensor, destined only for indoors applications. It is recommended
to use additional shields of the sensor (interchangeable) for outdoors or
indoors applications exposed to the possibility of water vapor condensation, depending of the transducer working conditions.
Table 18
Item
Order code
1 0874-490-016
2 0874-490-015
3 0874-490-014
38
Drawing
Name
DesignFeatures
PCV housing, PTFE
membrane
with a laminated film,
pore size:
Membrane filter
1 µm
Sintered
PTFE, pore
size 50 µm
PTFE filter
Sintered
bronze,
pore size
60 µm
Sintered bronze filter
Average effect of filtration,
maximal temperature: up to
80oC, response time t10/90:
15 s
High chemical
resistance, maximal temperature: up to 180 oC,
response time
t10/90:14 s
High mechanical resistance,
used in high
pollution and
low humidity,
response time
t10/90: 10 s
Typical appli-
cations
Building automation, for use
in the rooms
with small pollution
Drying process
in chemical applications
Agriculture
Page 39
6. TECHNICA L D ATA
Basic parameters:
- range of relative humidity
measurement (RH) 0...100%, without condensation
- basic error of humidity
conversioni ± 2% of the range for RH = 10...90%± 3% for the remaining range
- hysteresis of the humidity
measurement ± 1% RH
- basic range of temperature
measurement (T) -20...60°C
2)
- basic error of temperature
conversion ± 0.7°C
1)
- calculated values absolute humidity (a) [g/m3]
dew-point temperature (Td) [
o
C]
- additional errors:
± 25% of the basic error /10°C
RS-485 digital output:
- transmission protocol MODBUS
- baud rate 4800, 9600,19200,38400,
57600 bit/s
- mode RTU: 8N2, 8E1, 8O1, 8N1
- max. response time 300 ms
Analog outputs:
- current 4...20 mA
- voltage 0...10 V
- max. load resistance
of the current output 100 Ω
- min. load resistance
of the voltage output 1 kΩ
39
Page 40
Rated operating conditions:
- supply 9...24 V a.c./d.c.
- power consumption < 0.5 VA
- ambient temperature - 20...23...60
- relative air humidity < 95%
- rate of air flow 0,5 m/s
o
C
3)
4)
- preheating time 15 minutes
- protection grade ensured
by the housing IP 65
- fixing on a wall
- weight 125 g
- dimensions (35
´ 58 ´ 118) mm
- working position:
in applications non-exposed to a direct contact with water: any
•
in applications exposed to a direct contact with water:
•
with the sensor chamber directed towards the ground
Electromagnetic compatibility:
- noise immunity acc. to EN 61000-6-2
- noise emission acc. to EN 61000-6-4
Safety requirements acc. to EN 61010-1
- installation category III
- pollution grade 2
- phase-to-earth operating voltage 50 V
- altitude above sea level < 2000 m
1)
In case of condensation of water vapor on the sensor surface,
the measurement error may exceed the basic error till a moment
of drying up the sensor structure
2)
The absolute temperature measurement range is –30...85oC but the
measurement class is not guaranteed beyond the basic range
3)
Admissible condensation of water vapor when using additional sensor
shields, see Tab. 9)
4)
For air flow < 0.5 ms, the temperature and humidity measurement
error may increase by 100%.
40
Page 41
7. ORDERING CODE
Table 10
P18(D) -
Analog outputs - sensor:
without outputs, sensor on the housing0
current 4...20 mA, sensor on the housing1
voltage 0...10V, sensor on the housing2
without outputs, probe on the wire 0,5 m3
current 4...20 mA, probe on the wire 0,5 m4
voltage 0...10V, probe on the wire 0,5 m5
Version:
standard00
custom-made*XX
Language:
PolishP
EnglishE
other*X
Acceptance tests:
Without extra quality requirements0
With quality inspection certificate1
Acc. to customer’s request*X
*
after agreeing with the manufacturer
Code example:
P18D-100E1 means the P18D transducer, standard version with the
sensor on the housing with analog current output, English language,
with quality inspection certificate.
X XX X X
41
Page 42
42
Page 43
43
Page 44
P18-09C
PCE Americas Inc.
711 Commerce Way
Suite 8
Jupiter
FL-33458
USA
From outside US: +1
Tel: (561) 320-9162
Fax: (561) 320-9176
info@pce-americas.com
www.pce-instruments.com/us
www.industrial-needs.com
PCE Instruments UK Ltd.
Units 12/13
Southpoint Business Park
Ensign way
Hampshire / Southampton
United Kingdom, SO31 4RF
From outside UK: +44
Tel: (0) 2380 98703 0
Fax: (0) 2380 98703 9
info@industrial-needs.com
www.pce-instruments.com/english
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.