PCE Instruments PCE-P18-2A0E0, PCE-P18D Users guide

Page 1
TEMPERATURE AND HUMIDITY TRANSDUCER
PCE-P18
PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 info@pce-americas.com www.pce-instruments.com/us
www.industrial-needs.com
PCE Instruments UK Ltd.
Units 12/13
Southpoint Business Park
Ensign way
Hampshire / Southampton
United Kingdom, SO31 4RF
From outside UK: +44
Tel: (0) 2380 98703 0
Fax: (0) 2380 98703 9
info@industrial-needs.com
www.pce-instruments.com/english
USER’S MANUAL
1
Page 2
2
Page 3
Contents
1. APPLICATION ............................................................................... 5
2. TRANSDUCER SET .....................................................................7
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY .................. 7
4. INSTALLATION ............................................................................. 7
4.1. Way of fixing ........................................................................... 7
4.2. External connection diagrams ................................................9
5. SERVICE ..................................................................................... 11
5.1. Power-on messages of the P18D transducer ...................... 11
5.2. Description of the P18D transducer readout field ................. 12
5.3. Functions of the P18D transducer capacitive button ............ 13
5.4. Programming parameters menu of the P18D transducer ..... 14
5.5. Functions of the P18(D) transducer ...................................... 15
5.5.1. Calculated values ..............................................................16
5.5.2. Selection of controlling values for analog outputs .............16
5.5.3. Individual characteristic of analog outputs ......................... 17
5.5.4. Support of a sensor heater ................................................ 19
5.5.5. Default settings .................................................................. 20
6. RS-485 INTERFACE ................................................................... 21
6.1. Connection of the serial interface ......................................... 21
6.2. Description of the MODBUS protocol implementation .......... 23
6.3 Description of the functions used .......................................... 23
6.4 Map of the registers ............................................................... 26
6.5 Registers for writing and readout ........................................... 27
6.6 Registers for readout ............................................................. 33
6.7 Emergency restoration of default parameters ....................... 36
7. ERROR CODES .......................................................................... 37
8. ACCESSORIES ..........................................................................38
9. TECHNICAL DATA .....................................................................39
10. ORDERING CODE .................................................................... 41
3
Page 4
4
Page 5
1. APPLICATION
The PCE-P18 transducers are the devices destined for the continuous measurement and conversion of relative humidity and ambient temperature into a digital form and into a voltage or cur-rent standard signal. The transducers are fixed on a wall. Programming of the transmitters is possible via the RS?-485 interface. LPCon or eCon software designed for configuration of the transducers is available on the manufacturer’s website: www.pce-instruments.com. Applied sensor shields enable the application of the transducers in various ambient conditions.
Fig. 1. Overview of the P18 and P18D transducers with the probe
on the housing.
5
Page 6
Fig. 2. Overview of the P18 and P18D transducers with the probe
on the wire 0,5 m.
6
Page 7
2. TRANSDUCER SET
Transducer 1 pc
User’s manual 1 pc
Warranty card 1 pc
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY
In terms of operational safety, the transducer meets the requirements of the EN 61010-1 standard.
Comments concerning safety
Assembly and installation of the electrical connections should
• conducted only by people authorised to perform assembly of elec­tric devices.
Always check the connections before turning the transducer on.
The transducer is designed to installation and usage in the indu-
• strial electromagnetic environment.
4. INSTALLATION
4.1. Assembly
The P18(D) transducer is designed to be mounted on a wall by means of a screw connection or glue without the loss of IP65 tightness. The transducer housing is made of a self-extinguishing plastics. The trans­ducer has screw connectors placed inside the transducer, which enable the connection of external wires of 1 mm
2
cross-section.
7
Page 8
Fig. 3. Overall dimensions of the P18(D) transducer
mounting holes
Fig. 4. Lay-out of mounting holes of the P18(D) transducer
8
Page 9
4.2. External connection diagrams
The P18(D) transducer version P18(D)-1XXX or P18(D)2XXX has 8 connecting terminals, version P18(D)-0XXX has 4 terminals (ver­sion without analog outputs). Access to the terminals is possible after removing the cover of the transducer housing. You should use a multi­conductor round wire with external diameter from 3.5 mm up to 6 mm for electrical connections. Remove the display prior to connecting the wires in a screw terminal of the P18D transducer. Pass supplying wi­res through the packing and twist the packing seal in order to obtain the leaktightness. If the packing seal is not twisted, the required IP 65 leaktightness is not ensured. The LCD display should be put back after screwing the wires to the screw terminal of the P18D transducer.
a) b)
Fig. 5. Marking of the terminals for the connection of external signals
of the P18(D) transducers in versions: a) without analog outputs,
b) with analog outputs.
9
Page 10
Transducer without
analog outputs
Out
Out
1
Out2Out
1
2
Transducer with current
outputs
Transducer with voltage
outputs
Fig. 6. Wiring diagram of the P18(D) transducer with analog outputs
Use shielded cable for supply and output signals in environ­ments with high levels of interference. The shield must be connected to the nearest PE point from the feeder side.
10
Page 11
5. SERVICE
The P18D transducer is equipped with a display field 8x2 characters with illumination and one capacitive button located on the housing. The P18 transducer is not equipped with a display or a button. After connecting the wires, closing and servicing the housing, and connecting to the supply, the transducer is ready to work with manufacturer’s settings (Tab. 4). The transducer can be programmed through the RS-485 interface. You can program following parameters in the transducer:
communication parameters
- averaging time of the measurement
- individual characteristics of analog outputs (for executions with
analog outputs).
The P18D transducers allow programming communication parame­ters (address, baud rate, mode) using the capacitive button.
There is the possibility to connect the transducer through another trans­mission media, like: ETHERNET, USB using LUMEL S.A.’s converters.
5.1. Power-on messages of the P18D transducer
After connecting the external signals and connecting to the supply, the transducer displays the type, current program version, serial number and set communication parameters (address, baud rate and operating mode).
The transmitter automatically switches to the operating mode of me­asurement and processing the analog output signal after approx. 5 se­conds. It displays the measuring value with the unit in the bottom line of the display, the top line of the display contains information about the type of displayed quantity and the pictograms of: transmission via RS­485, the presentation mode of the measuring value, the read pointer of the measuring value of the sensor and the operating state of the internal heater.
11
Page 12
5.2. Description of the P18D transducer readout field
The illuminated character LCD is a readout field in the trans­ducer P18D. The illumination is turned on after switching on the supply and after the capacitive button on the housing is pressed. The illumina­tion is automatically switched off after 30 sec. of inactivity.
Indicator of the measuring value from the sensor
Type of the displayed value
Value of the displayed value
Indicator of automatic presenta­tion of the measuring values
Transmission indicator on RS-485 link
Unit of the displayed value
Fig. 7. Description of the P18D transducer readout field
Description of the symbols displayed by the P18D transducer is in the Table 1.
Table 1
Symbol Meaning
T:
RH:
Type of the displayed value in the bottom line of the LCD - temperature
Type of the displayed value in the bottom line of the LCD - relative humidity
12
Page 13
DP: AH:
h
5.3. Functions of the P18D transducer capacitive button
The P18D transducers are equipped with one capacitive button located on the housing. The location of the button shows in Fig. 8.
Type of the displayed value in the bottom line of the LCD - dew-point
Type of the displayed value in the bottom line of the LCD - absolute humidity
The indicator of the measuring value from the sensor
Automatic mode of measurement results presentation
- a type of displayed value is automatically switched
every 3 seconds in the following order: temperature → relative humidity → dew-point → absolute humidity →
temperature …. Data receiving indicator by the P18D transducer
on RS-485 Data sending indicator by the P18D transducer
on RS-485 Switching on the internal heater indicator to dry
the sensor
Fig. 8. Location of the P18D transducer capacitive button
13
Page 14
Capacitive button is used to:
switch the display illumination on
• change the presentation mode of the measurement results -
• holding the button for about 2 seconds switches from automatic mode to manual mode or inversely change the type of displayed values in the manual mode of presen-
• tation of the measurement results - pressing the button for a short time changes the displayed value. program communication parameters (address, baud rate, mode)
5.4. Programming parameters menu of the P18D transducer
Enter the programming menu by pressing and holding the capacitive button for approx. 5 sec. When entering the menu a first time, changes direction marker is set to - increasing the value; next entry in the menu will cause the cyclic switching of the direction of changes (2 input in the menu will set the marker at v – decreasing the value). If the idle time exceeds 20 seconds, the transducer will leave the menu and switch to displaying the measuring value.
Baud
rate
Mode
Address
Direction
of changes
Fig. 9. The displayed information of the transmission parameters in the
P18D transmitter menu
14
Page 15
Confirmation
of changes
5 seconds
Application of changes
Measurement
5 seconds
Mode programming
increase/ decrease the value
decreasing the value increasing the value
5 seconds
Baud rate programming
increase/ decrease the value
5 seconds
Address programming
increase/ decrease the value
Fig. 10. Programming parameters algorithm of the P18D transducer
5.5. Functions of the P18(D) transducer
The P18(D) transducer carries out the functions:
measurement of the ambient temperature and relative humidity
• calculation of chosen physical quantities (dew-point temperature,
• absolute humidity, wet bulb temperature) conversion of measured values into an output signal on the base
• of the individual linear characteristic (2 configurable analog outputs
- optional) memory storage of maximal and minimal values for each
• of the measured and calculated value programming of the measurement averaging time
• RS-485 interface servicing in the MODBUS protocol, in RTU
• mode. Displaying measuring and calculated values (only P18D)
5 seconds
15
Page 16
5.5.1. Calculated values
Based on the measurement of a temperature and relative humidity, the P18D transducer calculates dew-point and absolute humi­dity of the following dependencies.
T
n
m
ws
RH
- 1
)
DP → dwe-point:
DP =
log (P
10000 A
RH
P
DP → absolute humidity:
AH = 2,1668
ws
100 (T + 273,2)
gdzie:
T → measured temperature [
o
C]
RH → measured absolute humidity [%] DP → dew-point temperature [ P
→ saturated water vapor pressure (water vapor pressure) [mbar]
ws
AH → absolute humidity [g/m
Table 2
o
C]
3
]
The factors used to calculate the dew-point
o
C] A m T
T [
< 0
0...50
50...100
6.119866 7.926104 250.4138
6.1078 7.5 237.3
5.9987 7.3313 229.1
n
5.5.2. Selection of controlling values for analog outputs
The P18(D) transducers in versions P18(D)-1XX, P18(D)­2XX, P18(D)-4XX, P18(D)-5XX are equipped with two programmable analog outputs (voltage or current). By default, the first analog output is set for a presentation of the ambient temperature and the second analog output is controlled by the value of the relative humidity. The ana­log outputs can respond to any of the measuring or calculated values
16
Page 17
(T, RH, DP, AH, wet bulb temperature). The value controlling the analog outputs is defined by the registers, respectively 4015 for the first output and 4016 for the second analog output (Tab. 14).
5.5.3. Individual characteristic of analog outputs
The P18(D) transducers in the version with analog outputs enable the conversion of measured values into an output signal ba­sed on the strength of individual linear characteristic of analog outputs. On the base of given coordinates of two points by the user, the trans­ducer determines (from the system of equations) coefficients a and b of the individual characteristic.
Y1out = a  X1in + b
{
where:
X1 in and X2 in - displayed value, Y1 out and Y2 out - oexpected value of the analog output
Y2out = a  X2in + b
Fig. 11. Individual characteristic of analog output
17
Page 18
The configuration of the individual characteristic of analog outputs amounts to the introduction of suitable values X1, X2, Y1, Y2 in corresponding registers to them from the range 4007 – 4014 Tab. 3. The values introduced in these registers must be integral values corre­sponding to the set point values multiplied by the value 100.
Example 1
Configuration of the individual characteristic of the first analog current output (temperature):
Expected processing temperature in the range -12,25
o
C ÷ 77,75 oC
to the analog current signal in the range 4,5 mA ÷ 18,5 mA.
Table 3
Name Register address Value
X1 temperature 4007 -1225
Y1 current 4008 450
X2 temperature 4009 7775
Y2 current 4010 1850
Caution:
The analog outputs are not isolated from the supply, the RS-485 interface and each other, the analog current outputs don’t have a common potential (low potential terminals can not be connec­ted together), analog voltage outputs have a common low potential (low potential terminals can be connected together).
18
Page 19
5.5.4. Support of a sensor heater
The sensors used in the P18(D) transducers are equipped with internal heating elements to allow faster release of water molecu­les from the sensor being flooded or working a long time in highly hu­mid environments. Switching the heater on is possible by writing the appropriate value to the register 4021 (see Tab. 14). Status of the heater is available in the status register (register 4017) at the bit position 11 (if the bit 11 of the register 4017 is set to „1” - this means that the heater is switched on).
Caution:
The transducer with a heating element switched on does not measure the proper ambient temperature and humidity! (the temperature mea­sured by the sensor increases and the humidity decreases). The value 200 is added to the measuring values (temperature, relative humidity) when using the transducer with the heater switched on in order to avoid distortions of a measurement in the measurement systems! The P18D transducers working with a heating element swit­ched on display a flashing symbol h.
Fig. 12. Indication of the P18D transducer operation
with a heater switched on
19
Page 20
5.5.5. Default settings
The Table 4 shows the standard settings of the P18D transdu­cer. The settings can be restored via the RS-485 interface after writing the value „1” to the registry 4020.
Table 4
Parameter
description
Address 4001 1 Baud rate 4002 9600 Mode 4003 RTU 8N2 Averaging time 4005 30 [s] X1 of the 1st
analog output Y1 of the 1st
analog output X2 of the 1st
analog output Y2 of the 1st
analog output X1 of the 2nd
analog output Y1 of the 2nd
analog output X2 of the 2nd
analog output Y2 of the 2nd
analog output
Para­meter
address
4007 0 -2000 -2000
4008 0 400 0
4009 0 6000 6000
4010 0 2000 1000
4011 0 0 0
4012 0 400 0
4013 0 10000 10000
4014 0 2000 1000
P18D-0XX,
P18D-3XX
Standard value
P18D-1XX,
P18D-4XX
P18D-2XX,
P18D-5XX
20
Page 21
Value control­ling the first analog output.
Value control­ling the second analog output.
Custom confi­guration
4015 0 0 0
4016 1 1 1
4019 8 8 8
6. RS-485 INTERFACE
The P18(D) programmable digital transducers have a serial link RS-485 for communication in the computer systems and with other de­vices that serve as a Master. Asynchronous character MODBUS com­munication protocol has been implemented in a serial link. The transmis­sion protocol describes how to exchange information between devices via a serial link.
Caution:
For the transmitter versions without analog outputs (P18 (D) -0XX and P18 (D) -3XX), the RS-485 interface is galvanically isolated from the supply - 1 kV separation.
For the transmitter versions with analog outputs, the RS-485 interfa­ce is not isolated from the supply or from the analog outputs.
6.1. Connection of the serial interface
Standard RS-485 allows a direct connection up to 32 devices on a single serial link to a length of 1200 m (at baud rate 9600 b/s). It is necessary to use additional intermediate-separation circuits for con­necting higher number of the devices, for example PD51 manufactured by LUMEL S.A.
21
Page 22
Output of the interface line is shown in Fig. 6. It is required to con­nect the lines A and B in parallel with their equivalents in other devices to obtain the correct transmission. The connection must use a shielded wire. The cable shield should be connected to the protective terminal in close proximity to the transmitter (connect a shield to the protective terminal at one point only).
RS-485 interface card or the converter is required for a connection to a PC, for example PD10. The method of connecting devices is shown in Fig. 13.
22
Fig. 13. Connecting the RS-485 interface.
Page 23
6.2. Description of the MODBUS protocol implementation
The implemented protocol is compliant with the PI-MBUS-300 Rev G specification of Modicon.
Set of parameters of the P18D transducer serial link in the MODBUS protocol:
Transducer address 1..247.
Baud rate: 4800, 9600, 19200, 38400, 57600, 115200 [b/s].
Operating mode: RTU frame format: 8N2, 8E1, 8O1, 8N1.
Maximum response time: 500 ms
Configuration of the serial link parameters consists of determining the baud rate, the device address and the format of the transmission mode - protocol.
Caution: Each transmitter connected to the communication network must:
have a unique address, different from the addresses of other devi­ces connected to the network.
Identical baud rate and type of a transmission mode
6.3 Description of the functions used
Following functions of the MODBUS protocol have been implemented in P18D transducers:
03 (03h) – readout of registers group,
04 (04h) – readout of input registers group,
06 (06h) – single register writing,
16 (10h) – registers group writing,
17 (11h) – slave device identification.
23
Page 24
Readout of n-registers (code 03h) Example 1. Readout of 2 registers, starting with the register address
1D4Dh (7501) float (32-bit), (register values 25.68, 20.25.)
Request:
Device
address
Function
01h 03h 1Dh 4Dh 00h 02h 5270h
Register address Number of registers
B1 B0 B1 B0
Table 5
CRC check-
sum
Response:
Device
Fun-
ad-
ction
dress
01h 03h 08h 41h CDh 70h A4h 41h A2h 00h 00h 83D0h
Value from the register
Num­ber of bytes
1DB 0 (7501)
B3 B2 B1 B0 B3 B2 B1 B0
Value from the register
1DB1 (7502)
Table 6
Single register writing (code 06h)
Example 2. Writing the value 78h (120) to the register FA1h (4001)
Request:
Device
address
01h 06h 0Fh A1h 00h 78h DB1Eh
Function
Register address Register value
B1 B0 B1 B0
Table 7
CRC
checksum
Response:
Device
address
01h 06h 0Fh A1h 00h 78h DB1Eh
Function
Register address Register value
B1 B0 B1 B0
Table 8
CRC
checksum
24
CRC
check-
sum
Page 25
Writing n-registers (code 10h)
Example 3. Writing the value 78h (120) and the value 4h (4) to the regi-
sters FA1h, FA2h (4001, 4002)
Register
value 4002
Table 9
Table 10
checksum
Request:
De-
vice
Fun­ction
Register address
Function
ad-
dress
01h 10h 0Fh A1h 00h 78h 04h 00h 78h 00 04 F831h
Response:
Device
address
01h 10h 0Fh A1h 00h 02h 133Eh
Number of
registers
Register address Number of registers
B1 B0 B1 B0
Register
Num­ber of bytes
B1 B0 B1 B0
value 4001
Device identification report (code 11h)
Example 4. Device identification
Request:
Device
address
Response:
Device
ad-
dress
01h 11h 0Eh CCh FFh
Function Checksum
01h 11h C02Ch
Fun­ction
Num­ber of
bytes
Table 11
Identi-
fier
P18D
De-
The field depending on the
vice
status
device software version
50h 31h 38h 44h 76h 2Eh 30h 2Eh 30h 34h 20h 00h
(e.g. 0.70)
Table 12
check-
B154h
CRC
check-
CRC
CRC
sum
sum
25
Page 26
6.4 Map of the registers
In the P18D transducer, data are placed in 16 and 32-bit
registers. Process variables and transducer parameters are placed in the address area of registers in a way depended on the variable value type. Bits in 16-bit registers are numbered from the youngest to the oldest (b0 … b15). The 32-bit registers (4 bytes) contain numbers of float type in IEEE-754 standard. Bytes sequence: B3 B2 B1 B0 – the oldest byte is transmitted as the first. A following map is the map of P18(D) transducers registers.
Caution:
All listed addresses are physical addresses. Some computer programs use logic addressing, then the addresses should be increased by 1.
Table 13
Address
range
4000-4022 integer
6000-6030 float (32 bits)
7000-7030 float (32 bits)
7500-7515 float (32 bits)
Value type Description
The value is located in the 16-bit register.
(16 bits)
Value set in the two following 16-bit registers. These registers contain the same data as 32-bit registers from 7500-7515 range. Readout registers. Bytes sequence (B1,B0,B3,B2)
Value set in the two following 16-bit registers. These registers contain the same data as 32-bit registers from 7500-7515 range. Readout registers. Bytes sequence (B3,B2,B1,B0)
The value is located in the 32-bit register. Registers contain measured and calculated data by the transducer. Registers are only for readout.
26
Page 27
6.5 Registers for writing and readout
Table 14
Name
The value is located
in the 16-bit registers
4000 Identifier
4001 Address
4002 RS-485
baud rate
4003 RS-485
transmis­sion mode
Range Description
Write (w) / readout (r)
w/
180 P18 device identifier
r
204 P18D device identifier
w/
1...247 Device address
r
0...5 Va­lue
0 4800 bit/s 1 9600 bit/s 2 19200 bit/s 3 38400 bit/s 4 57600 bit/s 5 115200 bit/s
0...3 Va­lue
0 RTU 8N1 1 RTU 8N2 2 RTU 8E1 3 RTU 8O1
Description
Description
27
Page 28
4004 Confir-
mation of trans­mission parameters changes
4005 Averaging
time
4006 Erasing
the extre­mes
4007 X1 of out-
put 1
4008 Y1 of out-
put 1
4009 X2 of out-
put 1
4010 Y2 of out-
put 1
4011 X1 of out-
put 2
4012 Y1 of out-
put 2
4013 X2 of out-
put 2
4014 Y2 of out-
put 2
4015 Value
controlling 1 analog output.
0...1 Va-
Description
lue
0 No change 1 Confirmation of changes
w/
6...3600 Averaging time of the mea-
r
w/
r
0...1 Va-
surement [s]
Description
lue
0 No change 1 Erasing the min. and
max. values
w/
r
w/
r
w/
r
w/
r
w/
r
w/
r
w/
r
w/
r
w/
r
-32768
...32767
-32768
...32767
-32768
...32767
-32768
...32767
-32768
...32767
-32768
...32767
-32768
...32767
-32768
...32767
0...3 Va-
Value controlling out-
put 1 - point X1[ x100]
Expected value of output 1 for point X1
Value controlling output
1 - point X2 [ x100]
Expected value of output 1 for point X2
Value controlling output
2 - point X1 [ x100]
Expected value of output 2 for point X1
Value controlling output
2 - point X2 [ x100]
Individual characteristic of analog outputs
Expected value of out­put 2 for point X2
Description
lue
0 Temperature 1 Relative humidity
28
Page 29
4016 Value
controlling 2 analog output.
4017 Status
w/
r
w/
r
0...3 Va-
-32768
...32767
2 Dew-point 3 Absolute humidity 4 Wet bulb tempera-
ture Description
lue
0 Temperature 1 Relative humidity 2 Dew-point 3 Absolute humidity 4 Wet bulb tempera-
ture
Transducer status. Shows the current state of the trans­ducer and the hardware con­figuration. Successive bits represent the event. Bit set to 1 indicates that the event took place.
Bit15 Restart of the supp-
ly, writing the value
-32768 (8000h) will clear the status bit
Bit14 Error of the calibra-
tion parameters
Bit13 Error of the transmit-
ter settings - enter the new settings
29
Page 30
Bit12 not used Bit11 Indicator of switching
the heater on
Bit10 Indicator of erasing
the extremes, writing the value 1024 (400h) erases the status bit
Bit9 Temporary commu-
nication parameters are set (shorten jum-
per „ZW”) Bit8 LCD display error Bit7 Error reading the va-
lue from the sensor
Bit5,6Value controlling 2
analog output
00 01 10 11
30
temperature
dew-point
relative humidity
absolute humidity
Bit3,4Value controlling 1
analog output
00 01 10 11
temperature
dew-point
relative humidity
absolute humidity
Page 31
4018 Software
version
4019 Custom
configura­tion
Bit2 results averaging in-
terval has ended
Bit1 The transducer is equi-
pped with the analog outputs - voltage.
Bit0 The transducer is equi-
pped with the analog outputs - current.
o
1...999 Software version x100
w/
0...31 Bit0 Value Descrip-
r
Bit1
Number of characters
...4
of a response delay to the query for the RS-485 transmission
tion
0 The stan-
dard map of the re­gisters in the range 7000 and 7500
1 Map of
the regi­sters in the ran­ge 7500 and 7000 compliant with the map of the P14W transdu­cers
31
Page 32
4020 Default
settings
4021 Controlling
the heater
4022 reserved
w/
r
0...1 Va­lue
0 no change 1 przywraca parametry
Va­lue
0 switching a heater off 1 permanent switching
3 displaying remaining
60
...
32768
Description
fabryczne Description
a heater on
time of a heater swit­ched on
switching a heater on for Xn seconds (Xn ­value from the range
60...32768 )
32
Page 33
6.6 Registers for readout
Table 15
Name
32-bit registers
from the area 7500.
Unit
Quantity name
Write (w)/ readout (r)
The value is located in the
Value set in the two following 16-bit registers.
Registers contain the same data as 32-bit registers
7000 7500 ID r - P18(D) device identifier
o
7002 7501 T r
Measured temperature
C
7004 7502 RH r % Measured relative humidity
o
7006 7503 DP r 7008 7504 AH r
C Calculated dew-point
3
Calculated absolute humi-
g/m
dity
o
7010 7505 min T r
7012 7506 max T r
Min. of temperature
C
o
Max. of temperature
C 7014 7507 min RH r % Min. of relative humidity 7016 7508 max RH r % Max. of relative humidity
o
7018 7509 min DP r
Min. of dew-point
C
33
Page 34
7020 7510 max DP r
7022 7511 min AH r
7024 7512 max AH r
7026 7513 r
o
Max. of dew-point
C
3
Min. of absolute humidity
g/m
3
Max. of absolute humidity
g/m
o
Wet bulb temperature
C
7028 7514 r kPa Water vapor pressure
Table 16 shows the registers of measuring values of the P18D transdu­cer working in the registers 7000 and 7500 compatibility mode with the P14W transducer
Table 16
from the area 7500.
gisters contain the same data as 32-bit registers
Value set in the two following 16-bit registers. Re-
Name
32-bit registers
The value is located in the
Unit
Quantity name
Write (w) /readout (r)
7000 7500 ID o - P18(D) device iden-
tifier
34
Page 35
7002 7501 T o
7004 7502 DP o 7006 7503 - - -
7008 7504 RH o %
7010 7505 AH o
g/m
7012 7506 - - ­7014 7507 - - ­7016 7508 - - ­7018 7509 min T
7020 7510 max T
7022 7511 min DP
7024 7512 max DP
7026 7513 - -
7028 7514 - -
7030 7515 min RH
o %
7032 7516 max RH o
7034 7517 min AH
7036 7518 max AH o
o
g/m
g/m
o
Measured tempera-
C
ture
o
Calculated dew-point
C
Measured relative humidity
3
Calculated absolute humidity
o
Min. of temperature
C
o
Max. of temperature
C
o
Min. of dew-point
C
o
Max. of dew-point
C
-
-
Min. of relative humidity
Max. of relative
%
humidity Min. of absolute
3
humidity Max. of absolute
3
humidity
35
Page 36
6.7 Emergency restoration of default parameters
If the communication parameters have been changed and the new configuration is lost, you can use the jumper marked „ZW” on the transmitter’s board to set the temporary communication parameters:
address 247
• baud rate 9600 kb/s
• mode RTU 8N2
You can connect to the transmitter after setting the temporary parame­ters and adjust them or restore the defaults settings. After removing the jumper, the transducer returns to previous settings or to settings changed during the operation with the jumper.
jumper ZW
Fig. 13. Placement of the jumper setting temporary communication
parameters
36
Page 37
7. ERROR CODES
The error messages could be displayed on the transducer P18D display during operation. The table below lists the error codes which are possible to be displayed and their reasons as well as the recommended user responses. Information about the existing errors is also available in the P18(D) transducers status register - register 4017.
Table 17
Message
Error
Sensor
Error
Calibr.
Error
Param.XX
bit no.
reg. Status
(reg. 4017)
Description
7 Sensor failure - transmitter should be
returned to a service
14 Loss of calibration parameters - loss
of efficiency of the analog outputs, measurements are correct - returning a transmitter to a service should be considered
13
Loss of transmitter settings - XX
- number of a parameter (register number 40XX) configured incorrectly
- correct value should be written to the register 40XX or default settings restored
37
Page 38
8. ACCESSORIES
As a standard, the P18(D) transducer is equipped with a shield of the sensor, destined only for indoors applications. It is recommended to use additional shields of the sensor (interchangeable) for outdoors or indoors applications exposed to the possibility of water vapor condensa­tion, depending of the transducer working conditions.
Table 18
Item
Order code
1 0874-490-016
2 0874-490-015
3 0874-490-014
38
Dra­wing
Name
Design Features
PCV ho­using, PTFE membrane with a lami­nated film, pore size:
Membrane filter
1 µm
Sintered PTFE, pore size 50 µm
PTFE filter
Sintered bronze, pore size 60 µm
Sintered bronze filter
Average effe­ct of filtration, maximal tem­perature: up to 80oC, respon­se time t10/90: 15 s
High chemical resistance, ma­ximal temperatu­re: up to 180 oC, response time t10/90:14 s
High mechani­cal resistance, used in high pollution and low humidity, response time t10/90: 10 s
Typical appli-
cations
Building auto­mation, for use in the rooms with small pol­lution
Drying process in chemical ap­plications
Agriculture
Page 39
6. TECHNICAL DATA
Basic parameters:
- range of relative humidity
measurement (RH) 0...100%, without condensation
- basic error of humidity
conversioni ± 2% of the range for RH = 10...90% ± 3% for the remaining range
- hysteresis of the humidity
measurement ± 1% RH
- basic range of temperature measurement (T) -20...60°C
2)
- basic error of temperature
conversion ± 0.5% of the range*
* for the versions with analog outputs P18(D)-1, P18(D)-2, P18(D)-4 or P18(D)-5,
a basic error of temperature conversion may increase by 0.2°C
- calculated values absolute humidity (a) [g/m3]
dew-point temperature (Td) [
- additional errors:
- temperature influence ± 25% of the basic error /10°C
RS-485 digital output:
- transmission protocol MODBUS
- baud rate 4800, 9600,19200,38400,
57600 bit/s
- mode RTU: 8N2, 8E1, 8O1, 8N1
- max. response time 300 ms
Analog outputs:
- current 4...20 mA
- voltage 0...10 V
- max. load resistance
of the current output 100
- min. load resistance
W
of the voltage output 1 kW
1)
o
C]
39
Page 40
Rated operating conditions:
- supply 9...24 V a.c./d.c.
- power consumption < 0.5 VA
- ambient temperature - 20...23...60
- relative air humidity < 95%
- rate of air flow 0,5 m/s
o
C
3)
4)
- preheating time 15 minutes
- protection grade ensured by the housing IP 65
- fixing on a wall
- weight 125 g
- dimensions (35
´ 58 ´ 118) mm
- working position:
in applications non-exposed to a direct contact with water: any
• in applications exposed to a direct contact with water:
• with the sensor chamber directed towards the ground
Electromagnetic compatibility:
- noise immunity acc. to EN 61000-6-2
- noise emission acc. to EN 61000-6-4
Safety requirements acc. to EN 61010-1
- installation category III
- pollution grade 2
- phase-to-earth operating voltage 50 V
- altitude above sea level < 2000 m
1)
In case of condensation of water vapor on the sensor surface, the measurement error may exceed the basic error till a moment of drying up the sensor structure
2)
The absolute temperature measurement range is –30...85oC but the measurement class is not guaranteed beyond the basic range
3)
Admissible condensation of water vapor when using additional sensor shields, see Tab. 9)
4)
For air flow < 0.5 ms, the temperature and humidity measurement
error may increase by 100%.
40
Page 41
7. ORDERING CODE
Table 10
P18(D) -
Analog outputs - sensor:
without outputs, sensor on the housing 0 current 4...20 mA, sensor on the housing 1 voltage 0...10V, sensor on the housing 2 without outputs, probe on the wire 0,5 m 3 current 4...20 mA, probe on the wire 0,5 m 4 voltage 0...10V, probe on the wire 0,5 m 5
Version:
standard 00 custom-made* XX
Language:
Polish P English E other* X
Acceptance tests:
Without extra quality requirements 0 With quality inspection certificate 1
Acc. to customer’s request* X
*
after agreeing with the manufacturer
Code example:
P18D-100E1 means the P18D transducer, standard version with the sensor on the housing with analog current output, English language, with quality inspection certificate.
X XX X X
41
Page 42
42
Page 43
43
Page 44
P18-09C
PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 info@pce-americas.com www.pce-instruments.com/us
www.industrial-needs.com
PCE Instruments UK Ltd.
Units 12/13
Southpoint Business Park
Ensign way
Hampshire / Southampton
United Kingdom, SO31 4RF
From outside UK: +44
Tel: (0) 2380 98703 0
Fax: (0) 2380 98703 9
info@industrial-needs.com
www.pce-instruments.com/english
Loading...