The ND30 meter is a programmable digital instrument designed for the measurement of 1-phase 2wire and 3-phase 3 and 4-wire power network parameters in balanced or unbalanced systems. The
measured values are displayed on a 3,5’’ TFT full-color screen, resolution: 320 x 240 pixel. The meter
enables control and optimization of the power electronic devices, systems and industrial installations.
The meter provides measurement of: RMS of voltage and current, active, reactive and apparent power,
active, reactive and apparent energy, power factors, frequency, the harmonics of current and voltage /up to
51st/, THD of voltage and current, averaged active and apparent power P Demand, S Demand, averaged
current I Demand /15, 30 or 60 minutes/. Voltages and currents are multiplied by given voltage and current
ratios of the measuring transformers. Power and energy indications take into account all programmed ratio
values. The value of each measured value can be transmitted to the master system via the RS-485 or
Ethernet interface. Three relay outputs signal the overflow of the chosen value and the programmable
analog output maps the assigned parameter. The temperature inputs can be used to control the
temperature of the transformers windings, motors.
There is a galvanic separation between following units of the meter:
- supply
- voltage inputs
- current inputs
- RS485 interface
- Ethernet interface
- alarm outputs
- analog output
- temperature input Pt100
2 METER SET
Complete set of the meter includes:
1. ND10 m
2. seal1 pc
3. screw clamp to fix in the panel4 pcs
4. plug with 16 screw terminals1 pc
5. plug with 14 screw terminals1 pc
6. user's manual1 pc
eter1 pc
Page 4
3 User's manual
1
2
Fig. 1. Meter set
3 BASIC REQUIREMENTS, OPERATIONAL SAFETY
In terms of operational safety the controller meets the requirements of the EN 61010-1 standard.
Remar
ks concerning safety:
•The meter should be installed and connected only by a qualified personnel. All relevant safety
measures should be observed during installation.
•Always check the connections before turning the meter on.
•Prior to taking the meter housing off, always turn the supply off and disconnect the measuring
circuits.
•Removal of the meter housing during the warranty period voids the warranty.
•This meter conforms to all requirements of the electromagnetic compatibility in the industrial
environment.
•A switch or a circuit-breaker should be installed in the building or facility. It should be located near
the device, easily accessible by the operator, and suitably marked.
4 INSTALLATION
The meter is intended to be fixed to the panel with mounting brackets as presented on Fig. 1. The meter
ng is made of a self-extinguishing plastics.
housi
Fig. 2. Meter fitting
Housing overall dimensions 96 x 96 x 77 mm, dimensions of the assembly hole 92.5 x 92.5 mm.There are
screw t
diameter up to 2.5 mm
erminal strips on the outer side of the meter which enable the connection of external wires of
2
.
Page 5
4 User's manual
Fig. 3. Overall dimensions of the ND30 meter
5 METER DESCRIPTION
5.1 C
All current inputs are galvanically isolated (internal current transformers). The meter is adapted to work with
exter
automatically converted in relation to the introduced external current transformer ratio.
urrent inputs
nal measuring current transformers / 1 A or 5 A /. Displayed current values and derivative values are
5.2 Voltage inputs
All voltage inputs are galvanically isolated (internal transformers). Values on voltage inputs are
automatically converted according to the introduced ratio of the external voltage transformer. Voltage inputs
are specified in the order as 3x57.7/100 V, 3x230/400 V or 3x110/190 V, 3x400/690 V.
5.3 External connection diagrams
External connections are shown in Fig. 4.
Page 6
5 User's manual
ND30
option
Fig. 4. Meter connections
296 74311185
2 11
13
Ethernet(option)
1132
a
b
1
L1
N
S
S
1
L1
P
1
N
. 5. Direct measurement, indirect and semi-indirect in a 1-phase network
Fig
2
P
2
L1
N
B
A
S
P
1
S
1
2
P
2
Page 7
6 User's manual
Direct measurement
in 4-wire network
L1
L2
L3
N
Semi-indirect measurement
in 4-wire network
ND30
296 74311185
ND30
296 74311185
L1
L2
L3
N
Indirect measurement
in 4-wire network
a
A
L1
L2
L3
N
a
b
B
S
S
2
1
P
P
1
2
S
S
2
1
P
P
1
2
S
2
S
1
P
P
1
2
ND30
296 74311185
2
5
8
b
BA
a
L1
L2
L3
N
a
b
BA
a
b
BA
b
B
A
S2S
1
P
P
1
2
S2S
1
P
P
1
2
S
2
S
1
P
P
1
2
Fig. 6. Meter connections of input signals in a 3-phase 4-wire network
Page 8
Direct measurement in
a 3-wire network
L1
L2
L3
Semi-indirect measurement
using 2 current
transformers in a 3-wire
network
7 User's manual
ND30
29674311185
ND30
296 74311185
L1
L2
L3
Indirect measurement using 2 current
transformers and 2 or 3 voltage
transformers in a 3-wire network
2
5
8
a
A
L1
a
b
B
b
BA
L2
L3
L1
L2
L3
a
b
BA
S
S
2
1
P
P
1
2
S
2
S
1
P
P
1
2
ND30
296 74311185
a
a
b
BA
b
B
A
S
2S1
P
P
1
2
S
S
2
1
P
P
1
2
Fig. 7. Meter connections of input signals in a 3-phase 3-wire network
Page 9
6 ND30 PROGRAMMING
6.1 Front panel
8 User's manual
Fig. 8. Front panel
ND30 meter has 6 buttons and a full-color graphic screen.
The
Front panel description:
f1, ... , f88 field displays - the digits for readout
and settings,
V, A, W, var,
VA, Wh, varh,
Hz,
U1, I1, P1, ...
nQ
..E
units of the displayed values
displayed parameters markings
DMD
k, M
Averaged value indicator (Demand)
kilo = 10
The markers indicating the inductive, capacity
load character
3,
Mega = 10
6
The values of the measured parameters are shown on the active pages selected by subsequent pressing
the buttons (next page) or (previous page).
The page consists any 8 values selected from the Table 1 and displayed simultaneously on the display. The
page definition is described in the Display mode. Depending on the location, meter buttons can perform
different functions. Functions are described in the bar on the bottom of the screen. If the button lacks
description, it is inactive at the moment.
Function
of button 1
Function
of button 2
Function
of button 3
Function
of button 4
Function
of button 5
Function
of button 6
Fig. 9. Buttons marking – example
Page 10
9 User's manual
Information bar at the top of the screen displays the status of the alarm outputs, alarm conditions, T1 and
T2 temperature of the sensors connected to the first and second input of PT100, files archive memory
status, archive status, a symbol of Ethernet connection, the indicators of receiving and transmitting data on
the RS485 link, date and real-time clock. A symbol "phase sequence error" will be blinking in case of a
negative phase sequence.
Fig. 10. Information bar
Icon Icon color Comments
Black – archive memory mounted correctly
Black – no archive memory
Red – wrong file system of the card
Copying from internal memory to files archive
memory. The field of percentage of files archive
memory used flashes blue while displaying the
percentage of copying progress.
Current state of the archiving:
Black – archiving in a group enabled, waiting for
the archiving conditions to be met.
Red – the archiving conditions have been met and
saving the records is in progress.
White – archiving in a group disabled.
Percentage of files archive memory used
Green background Value in the range 0 ... 70%
Orange background 70% of files archive space is full. It is
Red backgroundIt is less than 7% of free space in the
1st archiving group
2nd archiving group
recommended to remove unnecessary
files via FTP.
files archive memory left. Time to
completely use a the files archive space
is approximately 14 days at 1 sec.
interval. Immediately delete any
unnecessary files via FTP.
Percentage of the archive copying progress.
Blue flashing backgroundCopying from internal memory to files
archive memory in progress
Page 11
10 User's manual
6.2 Starting work
After switching the supply on, the meter displays the ND30 meter name, version, current software version
and MAC for the version with Ethernet and then moves to the measurement mode and last saved page.
Displayed information:
ND30 v:1.00 – meter type, program version number
Bootloader v.01.05 – bootloader version number
U: 57.7/230.0 V – voltage versions
I: 1.0/5.0 A – current versions
MAC: AA:BB:CC:DD:EE:FF (for versions with Ethernet)
Fig. 11. Screen of meter measuring mode
7 OPERATING MODES
The ND30 meter has 10 operating modes:
sure – normal work mode. In the Measure mode the values are displayed according to the pages that
Mea
are preset at the factory or configured by the user.
Parameters – meter parameters configuration
Alarms – Alarm 1, Alarm 2 configuration
Analog output – analog output configuration
Display – displayed pages configuration
Archiving – archived values configuration
Ethernet – Ethernet interface configuration
Modbus – RS485 interface parameters configuration
Settings – settings: password, language, time, date
Information – preview of a program version, serial number, MAC address
To move from the Measure mode to any other mode, press the button for approx. 3 seconds.
Buttons allow to select the appropriate mode, to accept press the button
To return to a measurement mode use the button
Exit
Menu
Select
Page 12
11 User's manual
Fig. 12a. Programming matrix
Page 13
12 User's manual
Fig. 12b. Programming matrix
Fig. 12c. Programming matrix
Page 14
13 User's manual
Fig. 12d. Programming matrix
Page 15
14 User's manual
Fig. 12e. Programming matrix
7.1 Measurement mode
In the Measure mo
configured by the user in the Display mode.
Changing the page is done by pressing the buttons or .
Preview of the maximum or minimum values respectively is done while the button or is
pressed down. Reset of maximum or minimum values is done by pressing the button while viewing
their values, i.e. first the button or and then must be pressed.
Simultaneously pressing the button and will copy internal memory to files archive.
When reactive power or reactive inductive or capacity energy is displayed, this indication is accompanied
by a symbol of the load character: for an inductive load or for a capacity load.
When displaying the active power, the sign "+" is displayed for active energy import or "-" for active energy
export.
Exceeding of the upper or lower indication range is signaled on the display by ∧∧∧∧ or ∨∨∨∨. For
measurement of the averaged values (P DMD, S DMD, I DMD) single measurements are carried out with
0.25 second quantum. Averaging time to choose from: 15, 30 or 60 minutes. Until all samples of the
averaged values are acquired, the values are calculated from already measured samples.
Current value in the neutral wire IN is calculated from phase current vectors.
de the values are displayed according to the pages that are preset at the factory or
Max
Max
Min
Max
Del
Del
Min
Min
Page 16
15 User's manual
7.2 Measurement of voltage and current harmonics
The choice of harmonics is done by selecting the pages dedicated to display the values of voltage
harmonics U1, U2, U3 and currents I1, I2, I3 simultaneously for 3-phase (page 11). The number of a
displayed harmonics can be changed in the range of 2..51 by the buttons or
Page 12 shows a bar chart of the harmonics for each phase: voltage at the top and currents at the bottom
of the screen. Page 12 shows a bar chart of the harmonics. The choice of displayed harmonics is done by
pressing a button . The button is used to select the groups of harmonics: harm2 - harm26,
harm
- harm52 or harm2 - harm51.
7
2
L1,2,3
+
Fig. 13. Screens 11 and 12 - visualization of harmonics
7.3 Parameters mode
This mode is used to determine the parameters of the meter. To enter Parameters mode press the button
fo
Menu
accept press the button. The parameters configuration mode is protected by a password, if it was
entered and it is different from zero. The password prompt is skipped for the password 0000. If the
password is incorrect, the message "Wrong password. Read only menu" is displayed. Then it is possible to
view the parameters, but the changes are not possible.
r approx. 3 seconds and next using the button or select Parameters mode, to
Select
Fig. 14. Screens while entering a password
Page 17
16 User's manual
If the password is correct or it has not been entered, you can set the values according to Table 2.
Buttons are used to choose the parameter, to accept press the button . Then use the
buttons to choose the features of a parameter or set the requested parameter values, i.e.
you can choose the digit in the decimal position by the button or the digit value by the button
or . The active position is signaled by the cursor. Set value or parameter can be accepted by
Select
the button or canceled by pressing . Exit from the Parameters procedure follows pressing
simultaneously the button or after waiting for approx. 120 seconds. Exit from the Selecting
parameters menu follows pressing the button or after waiting for approx. 120 seconds.
During changing the parameter, it is check if the value is in the range. If the set value falls outside the
allowable range, the value is set to the maximum value (when entered value is too high) or minimum value
(when it is too low).
Parameter nameFeature / valueDescriptionDefault
settings
3 phase -3 wire
1 phase -2 wire
3x230/400 V;
or
3x110/190 V;
3x400/690 V;
min
Apparent, All
Type of power network
3-phase 4-wire
3-phase 3-wire
1-phase 2-wire
Choice of the ranges
depending on the ordering
code
Averaging time
active power P DMD,
apparent power S DMD,
current I DMD
the real-time clock
Resistance value in Ω0.00 Ω
Resistance value in Ω0.00 Ω
3 phase -4
wire
3x230/400 V
or
3x400/690
V
15 min
none
No
Free eCon software can also be used for configuration of the ND30 meters, it is
available by request from PCE Instruments.
Page 19
7.4 Alarms mode
18 User's manual
In the options, select the Alarms mode and confirm selection by pressing the button .
Button
Select
The buttons
and Select
Select
The buttons
and Select
Fig. 16. Screens of Alarms mode
Table 2
Ite
m
1
Settings
2Relay state if alarm onOff/OnState of the relay at the alarm
3Holdback alarm offOff/OnOff
4Display alarm eventOff/OnWhen alarm indication function is
Parameter namerangeNotes/descriptionDefault
settings
Logical conditionsC1
C1 v C2 v C3
C1 ∧ C2 ∧ C3
(C1 ∧ C2) v C3
(C1 v C2) ∧ C3
switched on Off/On
enabled and the alarm state ends,
alarm symbol is not turned off but
begins to flash.
Signalization symbol flashes until it
is turned off by pressing
the button and
(> 1 sec.). This function refers only
to the alarm signalization, so the
relay contacts will operate without
Del
Alarm
C1
On
Off
Page 20
19 User's manual
a latch according to the selected
alarm type.
Values U1, I1,...,T2, hh:mmValue on the alarm output
parameters acc. to Table 8
6Condition typen_on, noFF, on,oFF,
H_on,
HoFF, 3non, 3noF, 3_on,
3_oF
7Low limit condition-144.0…144.0in % of the rated input value90.0
8High limit condition-144.0…144.0in % of the rated input value 110.0
9Delay to condition on0 … 3600in seconds 0
10Delay to condition off0 … 3600in seconds 0
11
Condition 1
12Display condition event Off/OnWhen a latch function is enabled
Holdback condition off->on
Condition 2
Condition 3
0 … 3600in seconds 0
condition symbol is not turned off
Signalization symbol flashes until it
is turned off by pressing the button
Entering "Condition upper value" lower then "Condition lower value" disables a condition.
Acc. to Fig.17.n-on
and the condition state ends,
but begins to flash.
and
AlarmCancel
(> 3 sec.).
U1
Off
Condition state
stanwarunku
1
0
Waruneknie
Condition
spełniony
is false
Dolna
Condition
warto
lower
warunku
value
Warunek
spełniony
Condition
Górna
upper
wartoc
value
warunku
Condition
is true
wielkomierzona
Measured value
Condition state
1
0
a) n_onb) n
stanwarunku
Condition state
1
0
Waruneknie
Condition
spełniony
is false
Condition
Warunek
is true
spełniony
Dolna
Condition
warto
lower
warunku
value
Waruneknie
Condition
spełniony
is false
Górna
Condition
wartoc
upper
warunku
value
Measured value
wielkomierzona
1
0
d) oFF
c) on
stanwarunku
Condition
Warunek
is true
spełniony
Condition
Dolna
lower
warto
value
warunku
oFF
stanwarunku
Condition state
Warunek
Condition
spełniony
is true
Waruneknie
Condition
Dolna
Condition
warto
lower
warunku
value
Condition
wartoc
warunku
spełniony
is false
Condition
Waruneknie
Condition
spełniony
is false
Górna
upper
value
Condition
Górna
wartoc
upper
warunku
value
wielkomierzona
Measured value
Warunek
spełniony
is true
Measured value
wielkomierzona
Fig. 17. Condition types: a) n_on b) noFF c) on d) OFF
Remaining types of the condition:
−H_o
n – always true;
−HoFF – always not true,
−3non – when the measuring value on any phase exceeds the "Condition upper value" -
condition is true. The condition will be disabled if the measuring value on all phases will be
lower than "Condition lower value".
Page 21
20 User's manual
−3noF – when the measuring value on any phase will be lower than the "Condition lower value" -
condition is true. The condition will be disabled if the measuring value on all phases will be higher
than "Condition upper value".
−3_on – when the measuring value on any phase will be between the "Condition lower value" and
"Condition upper value" - condition is true. The condition will be disabled if the measuring value on
all phases will be below "Condition lower value" or above "Condition upper value".
−3_oF – when the measuring value on any phase will be below the "Condition lower value" or above
"Condition upper value" - condition is true. The condition will be disabled if the measuring value on
all phases will be between the "Condition lower value" and "Condition upper value".
−The alarm value in the series 3 alarms must be in the range: 01-09, 10-18 and 19-27 (acc. to Table
8). They work with identical thresholds "Condition lower value" and "Condition upper value" for each
phase. The blanking of the alarm signalization latch follows pressing the buttonsand
Alarm
(> 3 sec.).
Del
7.5 Analog output mode
the options, select the Analog output mode and confirm selection by pressing the button
In
Select
.
Fig.18. Screens of Analog output mode
Table 3
Ite
m
1Value U1, I1,...,T2, hh:mmValue on analog output
2Output range 0...20 mA, 4...20 mA,Analog output range0...20 mA
3Low limit input-144.0 .. 144.0%Lower value of the input range in %
4High limit input-144.0 .. 144.0%Upper value of the input range in %
5Low limit output00.00 .. 24.00 Lower value of the output range in
6High limit output0.01 .. 24.00 Upper value of the output range in
7Out modeNormal
Parameter nameFeature / valueDescriptionDefault
settings
ΣP
parameter acc. to Table 8
0.0
of the rated range
100.0
of the rated range
0.00
mA
20.00
mA
Continuous output working modeNormal
Low limit output
High limit output
Page 22
21 User's manual
7.6 Display mode
In this mode, you can configure the pages displayed in a normal work mode of the meter Measurement
The buttons
and Select
The buttons
and Select
The buttons
and Select
Fig. 19. Screens of Display mode
It
e
m
1
2Pages colorGreen
3Display field 1No
4
Settings
Page 1
:
:
Page 10
Parameter nameRangeNotes/descriptionDefault
Backlight level
Time to Backlight level min
Pages cfg
Display field 1
:
:
Display field 8
Minimum, Medium,
Maximum
0 .. 9999
Page 1
Page 2
:
Page 11
Page 12
Red
Yellow
:
Olive
Yes
Off
U1
I1
P1
Q1
:
En S
in seconds
Selection of pages visualized in
Measurement mode
Color of displayed values in
Measurement mode
Selection of displayed values on a
selected page and selected field
acc. to Table 5.
Table 4
settings
Maximum
0
Page 1
Page 2
:
Page 11
Page 12
Green
No
Table 6a or 6b
or 6c -
depending on
the connection
system
Page 23
22 User's manual
Selection of displayed values: Table 5
Itemvalue name
no value - blanked display field
00
L1 phase voltage
01
L1 phase wire current
02
L1 phase active power
03
L1 phase reactive power
04
L1 phase apparent power
05
L1 phase active power factor
06
(PF1=P1/S1)
07
tgϕ factor of L1 phase (tg1=Q1/P1)
L1 phase voltage THD*
08
L1 phase current THD
09
L2 phase voltage
10
L2 phase wire current
11
L2 phase active power
12
L2 phase reactive power
13
L2 phase apparent power
14
L2 phase active power factor
15
2=P2/S2)
(PF
16
tgϕ factor of L2 phase (tg2=Q2/P2)
L2 phase voltage THD*
17
L2 phase current THD
18
L3 phase voltage
19
L3 phase wire current
20
L3 phase active power
21
L3 phase reactive power
22
L3 phase apparent power
23
L3 phase active power factor
24
(PF3=P3/S3)
25
26
27
2
29
30
31
❊tg factor of L3 phase (tg3=Q3/P3)
L3 phase voltage THD*
L3 phase current THD
mean phase voltage
8
mean 3-phase current
3-phase active power
3-phase reactive power
markingunitSignaling
Off
U1
I1
P1
Q1
S1
(M, k)V
(k)A
(G, M, k)W
M,
(G,
k)var
(G, M,
/
k)VA
PF1
tg1
THD U1
THD I1
U2
I2
P2
Q2
S2
%
%
(M,k)V
(k)A
(G, M, k)W
(G, M,
k)var
(G, M,
/
k)VA
PF2
PF
tg2
THD U2
THD I2
U3
I3
P3
Q3
S3
%
%
(M,k)V
(k)A
(G, M, k)W
(G, M,
k)var
(G, M,
/
k)VA
PF3
tg3
THD U3
THD I3
U avg
I avg
ΣP
ΣQ
V%
A%
(M, k)V
(k)A
(G, M, k)W+/-
(G, M,
k)var
/
3Ph
/
4W
3Ph
/
3W
√√√
√
x
√√√
√
√
√
√
√
x
x
x
x
x
√√√
√√√
√
xx
√√
√
√
√
√
√
xx
xx
xx
xx
xx
√√
√√
√
xx
√√
√
√
√
√
√
xx
xx
xx
xx
xx
√√
√√
√
√
xx
√
√√√
√√√
1Ph
/
2W
√
√
√
√
√
√
x
x
x
x
x
x
x
Page 24
23 User's manual
323-phase apparent power
active power factor
33
3-phase (PF=P/S)
tgϕ factor average for 3 phases
34
(tg=Q/P)
35
THD U mean 3-phase*
36
THD I mean 3-phase
37
frequency
38
phase-to-phase voltage L1-L2
39phase-to-phase voltage L2-L3
40
phase-to-phase voltage L3-L1
41
mean phase-to-phase voltage
42
active power averaged (P Demand)
43
reactive power averaged (S Demand)
44
current averaged (I Demand)
45
neutral wire current
46
Temperature T1 of input 1
47
Temperature T2 of input 2
48
Active 3-phase import energy
49
Active 3-phase export energy
50
Reactive 3-phase inductive energy
ΣS
PF avg
tg avg
THD U
THD I
f
U12
U23
U31
U123
P DMD
S DMD
I DMD
I N
T1
T2
En P+
En P-
En Q
(G, M, k)VA
%
%
Hz
(M,k)V
k)V
(M,
(M,k)V
(M,k)V
(G, M, k)W
(G, M,
k)VA
(k)A
(k)A
°C
°C
kWh
kWh
kvarh
√√√
√√
√√
√√
√√
√√√
√√
√√
√√
√√
√√√
√√√
√√√
√
√√√
√√√
√√√
√√√
√√√
xx
x
x
x
x
x
x
x
x
51
Reactive 3-phase capacity energy
52
3-phase apparent energy
* In the 3-phase 3-wire system (3Ph / 3W) respectively THD U12, THD U23, THD U31,
THD U123
Default settings of the displayed pages in 3-phase 4-wire system Table 6a
En Q
En S
kvarh
kVAh
√√√
√
√√
P1P2P3P4P5
U1 VI1 AU12 V
U2 VI2 AU23 V
U3 VI3 AU31 V
ΣP W
ΣQ var
ΣS VA
f HzI avg A U123 V PF avg
P1 WPF1P1 WQ1 varTHD U1 %THD I1 %
P2 WPF2P2 WQ2 varTHD U2 %THD I2 %
P3 WPF3P3 WQ3 varTHD U3 %THD I3 %
ΣP W
PF avg
ΣP WΣQ var
THD U %THD I %
P6P7P8P9P10
U1 VS1 VAU2 VS2 VAU3 VS3 VA
ΣP W
P DMD W
ΣP W
+En P kWh
I1 APF1I2 APF2I3 APF3
ΣQ var
S DMD
W
P1 Wtg1P2 Wtg2P3 Wtg3I avg AI DMD A
ΣQ var
ΣS VA
-En P kWh
En Q
Page 25
24 User's manual
kvarh
Q1 varf HzQ2 varf HzQ3 varf HzI(N) Af HzEn S
kVAh
P11P12
U1 %I1 %HARM.:U1U2U3
U2 %I2 %
%
bargraf
U3 %I3 %HARM.:I1I2I3 %
HARM.2..51
Pages 11 and 12 cannot be configured.
bargraf
ault settings of the displayed pages in 3-phase 3-wire system Table 6b
Def
P1P2P3P4P5
U12 VI1 AU12 V
ΣP WΣP W
P DMD WTHD U12 %THD I1
ΣP W
%
U23 VI2 AU23 V
ΣQ varΣQ var
S DMD WTHD U23 %THD I2
ΣQ var
%
U31 VI3 AU31 V
ΣS VA
I avg A I DMD ATHD U31 %THD I3
ΣS VA
%
En Q
kvarh
En P+ kWh
En P- kWh
En Q
kvarh
f HzI avg AU123 VPF avg
Default settings of the displayed pages in 1-phase system Table 6c
tg avg
PF avgTHD U123 %THD I %En S
P1P2P3
U1 VS1 VAP1 WP DMD WP1 WEn P+ kWh
I1 APF1S1 VAS DMD WQ1 varEn P- kWh
P1 Wtg1I1 AI DMD AS1 VA
Q1 varf HzPF1f HzEn S
kVAh
En Q kvarh
En Q
kvarh
kVAh
En Q
kvarh
Page 26
7.7 Archiving mode
25 User's manual
In the options, select the Archiving mode and confirm selection by pressing the button .
Select
Fig. 20. Screens of Archiving mode
Table 7
Ite
m
1
2ParametersU1, I1, P1, ... T1, T2Archived values (acc. to Table
3TriggerU1, I1, P1, ... T1, T2,
4Interval0 .. 3600 sArchiving period in seconds0 s
Entering a value "Archive high" lower than "Archive low" or equal switches the registration off. Not
licable for H_on mode.
app
Page 27
26 User's manual
a) n_on
Archiving
Archiwizacja
1
0
disabled
wyłczona
c) on
Archiving
Archiwizacja
1
0
disabled
wyłczona
Ar_L
Ar_L
włczona
enabled
Ar_H
Ar_H
włczona
enabled
wielkowyzwalajca
tiggering valuetiggering value
disabled
wyłczona
tiggering valuetiggering value
b) noFF
Archiving
Archiwizacja
1
enabled
włczona
0
d) oFF
Archiving
Archiwizacja
1
enabled
włczona
0
Ar_L
wyłczona
Ar_L
disabled
Ar_H
Ar_H
disabled
wyłczona
wielko
enabled
włczona
wielkowyzwalajcawielkowyzwalajca
wyzwalajca
Fig.21. Archiving types: a) n_on b) noFF c) on d) OFF
aining types of the archiving:
Rem
−H_on – always enabled;
−HoFF – always disabled,
−3non – archiving is enabled when n_on type condition occurs on any phase. It will be switched off
only when all triggering condition are disabled.
−3noF – archiving is enabled when noFF type condition occurs on any phase. It will be switched off
only when all triggering condition are disabled.
−3_on – archiving is enabled when on type condition occurs on any phase. It will be switched off only
when all triggering condition are disabled.
−3_oF – archiving is enabled when oFF type condition occurs on any phase. It will be switched off
only when all triggering condition are disabled.
−The value triggering an archiving in the series 3 archiving must be in the range: 01-09 (acc. to Table
8). Archiving works with identical thresholds of the Ar_L and Ar_H hysteresis for each phase.
Selection of the values on the alarm outputs, analog and archived: Table 8
Value of the needed for
Value in
registers
01
02
03
04
05
06
07
08
09
10
11
12
13
Displayed
element
U1
I1
P1
Q1
S1
PF1
tg1
THD U1
THD I1
U2
I2
P2
Q2
Value type
calculations of percentage
corresponding to 100% of
the rated range.
L1 phase voltageUn [V] *
L1 phase wire currentIn [A] *
L1 phase active powerUn x In x cos(0°) [W] *
L1 phase reactive powerUn x In x sin(90°) [Var] *
L1 phase apparent powerUn x In [VA] *
L1 phase power factor (PF)1
tg factorϕ of L1 phase
1
L1 phase voltage THD**100.00 [%]
L1 phase current THD100.00 [%]
L2 phase voltageUn [V] *
L2 phase wire currentIn [A] *
L2 phase active powerUn x In x cos(0°) [W] *
L2 phase reactive powerUn x In x sin(90°) [Var] *
L2 phase apparent powerUn x In [VA] *
L2 phase active power factor PF1
tgϕ factor of L2 phase
L2 phase voltage THD**100.00 [%]
L2 phase current THD100.00 [%]
L3 phase voltageUn [V] *
L3 phase wire current In [A] *
L3 phase active powerUn x In x cos(0°) [W] *
L3 phase reactive powerUn x In x sin(90°) [Var] *
L3 phase apparent powerUn x In [VA] *
L3 phase active power factor PF1
tgϕ factor of L3 phase
L3 phase voltage THD**100.00 [%]
L3 phase current THD100.00 [%]
mean phase voltage0.00 [%]
mean 3-phase current In [A] *
3-phase active power (P1+P2+P3)3 x Un x In x cos(0°) [W] *
3-phase reactive power (Q1+Q2+Q3)3 x Un x In x sin(90°) [Var] *
3-phase apparent power (S1+S2+S3)3x Un x In [VA] *
3-phase power factor (PF)1
tg factorϕ for 3 phases
3-phase voltage THD**100.00 [%]
3-phase current THD100.00 [%]
frequency100 [Hz]
phase-to-phase voltage L1-L2
phase-to-phase voltage L2-L3
phase-to-phase voltage L3-L1
mean phase-to-phase voltage
active power averaged (P Demand)*3 x Un x In x cos(0°) [W] *
reactive power averaged (S Demand )*3 x Un x In [VA] *
current averaged (I Demand) *In [A] *
neutral wire current In [A] *
Temperature T1 of input 1
Temperature T2 of input 2
Active 3-phase import energy
Reactive 3-phase inductive energy
Reactive 3-phase capacity energy
3-phase apparent energy
Phase sequence
1
1
1
Un [V] *
Un [V] *
Un [V] *
Un [V] *
400 [°C]
400 [°C]
100,000 [kWh]
100,000 [kWh]
100,000 [kvarh]
100,000 [kvarh]
100,000 [kVAh]
L1, L2, L3 - 0.00 [%]
L1, L3, L2 - 100.00 [%]
54
hh:mm
time, hhx100+mm2,400 - 100 [%]
*Un, In - rated values of rated voltages and currents
** In the 3-phase 3-wire (3Ph / 3W) respectively THD U12, THD U23, THD U31 THD U123
To register in each group, you can select 16 of 53 parameters (bits 1 to 53 of the registers 4106...4109 and
5...4118). Bit set to "1" adds a parameter to a registration, set to "0" deletes. It is possible to set all 53
411
bits but only the first 16 bits set to "1" will be taken for a registration.
Page 29
7.8 Ethernet mode
28 User's manual
In the options, select the Ethernet mode and confirm your choice by pressing the button .
Select
Fig.22. Screens of Ethernet mode
It
e
m
1
2ModeAuto, 10 Mb/s, 100
Address
3 Address IP
4Subnet Mask
5Gateway
6DNS address
7MAC addressAa:bb:cc:00:21:01-
8
9Port80 … 32,0001
1
0
11Waiting Time10 .. 36060s
1
2
1
3
1
4
es
Modbus
TCP
FTP
WWWPort
Parameter namerangeNotes/descriptionManufactur
er’s value
DHCP
0.0.0.0...255.255.255.255
0.0.0.0...255.255.255.255
0.0.0.0...255.255.255.255
0.0.0.0...255.255.255.255
Address1 .. 2471
Max. connection
limit
Command port
Data port
Off/On
Mb/s
1 … 41
20 .. 3200021
20 .. 320001025
80 .. 3200080
Enabling / disabling the DHCP
Client (supports automatic obtaining
of IP protocol parameters of the
meter's Ethernet interface from
external DHCP servers in the same
LAN)
10.0.1.161
55.0.0.1-
2
0.0.0.0entered
10.0.0.44-
DHCP or
Obtained from
DHCP is
disabled
manually when
Auto
Table 9
Off
-
Page 30
7.9 Modbus mode
29 User's manual
In the options, select the Modbus mode and confirm your choice by pressing the button .
Select
Fig.23. Screens of Modbus mode
Ite
m
1Address1…247Modbus Network Address
2Baud rate4800 b/s, 9600 b/s,
3ModeRTU 8N2, RTU 8N1,
4Set Defaults 42xx registersNo, YesProgrammable group of registers for
Parameter name
Feature / valueDescriptionManufact
Baud rate9600 b/s
19.2 kb/s, 38.4 kb/s,
57.7 kb/s, 115.2 kb/s
Transmission modeRTU 8N2
RTU 8O1, RTU 8N1
readout
Table 10
urer’s
value
1
No
7.10 Settings mode
In the options, select the Set
Ite
m
Parameter name
tings mode and confirm your choice by pressing the button .
Select
Fig.24. Screens of Settings mode
Table 11
Feature / valueDescriptionManufact
urer’s
value
Page 31
30 User's manual
1Password0 .. 99990 - disabled0
2LanguageEnglish, Polski,
ormation mode and confirm your choice by pressing the button .
Select
Fig.25. Screens of Information mode
Table 12
Ite
m
Parameter name
1TypeMeter type
2Order codeFir
3Boot versionBootloader versione.g. 1.04
4Program version Main program version of the meter e.g. 0.60
5Serial number ddmmxxxxCurrent serial number of the meter
MAC addressxx:xx:xx:xx:xx:xx48-bit hardware address of Ethernet
Feature / valueDescriptionManufacturer’s
value
ND30
st 5 digits of the ordering codee.g. 12200
e.g. 15070006
day month current number
e.g.
interface in hexadecimal format
64:0E:0D:0C:0B:0A
8 MEASURING VALUES ARCHIVING
8.1 INTERNAL MEMORY
The ND30 meters are equipped with 4MB of internal memory and 8GB memory for storing the
recorded data. 4MB internal memory allows to register 40,960 records. The memory is a ring
buffer type one.
8.2 COPYING ARCHIVE
If the 4MB internal memory is full at 70% or forced at any time: in Arc
"Copy the archive to a CSV file" parameter to "Yes". The recorded data will be copied to the files archive.
To start the procedure of copying archive can also be done via the RS485 interface (register 4125) or by
simultaneously pressing the button and .
Max
Min
hiving mode, select Actions and set
Page 32
31 User's manual
Example: files archive with archiving period of 5 seconds allows you to register data for 2 years. If the files
archive is full at 70% - archive used in % will become orange (see: Status 3 Register – address 7561).
When the files archive is full (less then 14 days at 1 sec. interval to completely use a the files archive
space) the color will change to flashing red.
The ND30 meter creates the directories and the files the files archive while the internal memory is being
copied. An example of the directory structure is shown in Figure 26.
Fig.26. Directory structure in the files archive
a in the files archive is stored in the files in the directories (year, month archive copy) - see Fig.
Dat
26. The file names are marked by day and time of the first record and have the ddhhmmss.csv
format, where: dd-day, hh-hour, mm-minute, ss-second.
8.3 ARCHIVE FILES STRUCTURE
The archived data files are in the form of the columns, where each column of data is separated by
mma. A column description is in the first line of the file. Data records are sequentially
a co
arranged in the rows. An example of the file is shown in Figure 27.
Fig.27. An example of the archive data file
The fields in the line describing the record have the following meanings:
date – date of data recording, date separator is the character "-"
time – hour, minute, second of recorded data, a time separator is the character ":"
record index – unique index record. Each record has a unique number. This number increases
Page 33
32 User's manual
when writing new records.
block – reserved
register1 – Modbus register address of the first archived value
name1 – Modbus register description of the first archived value
value1 – first archived value. The decimal separator is ".", the values are saved in a
engineering notation format.
:
register16 – Modbus register address of the sixteenth archived value
name16 – Modbus register description of the sixteenth archived value
value16 – sixteenth archived value. The decimal separator is ".", the values are saved in a
ineering notation format.
eng
name1, ...,name16 – description according to Table 8 (Displayed parameter).
8.4 DOWNLOADING ARCHIVE
Archived data can be downloaded via Ethernet using FTP protocol.
9 SERIAL INTERFACES
9.1 RS485 INTERFACE – list of parameters
The implemented protocol is compliant with the PI-MBUS-300 Rev G specification of Modicon.
List of ND30 meter serial interface parameters:
mple 1. Readout of two 16-bit integer registers, starting with the register address 0FA0h (4000) -
Exa
register values 10, 100.
Request:
Device address Register addressNumber of registersCRC
Page 34
33 User's manual
Functionchecksum
B1B0B1B0
01030FA00002C7 3D
Response:
Device
address Function
Number of
bytes
Value from the register
0FA0 (4000)
Value from the register
0FA1 (4001)
B1B0B1B
CRC
checksum
0
010304000A0064E4 6F
Example 2. Readout of two 32-bit float registers as a combination of two 16-bit registers, starting with the
register address 1B58h (7000) - register values 10, 100.
Request:
Device address
Function
Register addressNumber of registersCRC
B1B0B1B0
checksum
01031B580004C3 3E
Response:
Device
address Function
Number of
bytes
Value from the
register
1B58 (7000)
Value from the
register
1B59 (7001)
Value from
the register
1B5A (7002)
Value from
the register
1B5B (7003)
CRC
checksum
B3B2B1B0B3B2B1B0
010
3084120000042C80000E4 6F
Example 3. Readout of two 32-bit float registers as a combination of two 16-bit registers, starting with the
register address 1770h (6000) - register values 10, 100.
Request:
Device
address Function
Register addressNumber of registers
B1B0B1B0
CRC
checksum
0103177000044066
Response:
Device
address Function
010
30800004120000042C8E4 6F
Number of
bytes
Value from the
register
1770h (6000)
Value from the
register
1770h (6000)
Value from
the register
1772h (6002)
Value from
the register
1772h (6002)
B1B0B3B2B1B0B3B2
CRC
checksum
Page 35
34 User's manual
Example 4. Readout of two 32-bit float registers, starting with the register address 1D4Ch (7500) - register
values 10, 100.
Request:
Device address
Function
Register addressNumber of registersCRC
B1B0B1B
0
01031D4C000203 B0
Response:
Device
address Function
Number of
bytes
Value from the register
1D4C (7500)
Value from the register
1D4D (7501)
B3B2B1B0B3B2B1B0
0103084120000042C80000E4 6F
Single register writing (code 06h)
Example 5. Writing the value 543 (0x021F) to the register 4000 (0x0FA0)
Request:
Device address
Function
Register addressRegister valueCRC
B1B0B1B
0
01060FA0021FCA 54
checksum
CRC
checksum
checksum
Response:
Device address
Function
Register addressRegister valueCRC
B1B0B1B0
01060FA0021FCA 54
Writing to n-registers (code 10h)
Example 6. Writing two registers starting with the register address 0FA3h (4003)
Writing the values 20, 2000.
Request:
Device
address Function
011
Addres
reg.Hi
Addre
s
reg.Lo
ss
No. of
regist
ers Hi
No. of
regist
ers
Lo
Numb
er of
bytes
Value for the
register 0FA3
(4003)
Value for the
register 0FA4
B1B0B1B0
00FA3000204001407D0BB 9A
checksum
CRC
checksum
(4004)
Page 36
Response:
35 User's manual
Device address
Function
Register addressNumber of registersCRC
B1B0B1B0
01100FA30002B2 FE
Device identification report (code 11h)
Example 7. Device identification
Information field of the device software version (e.g.
"ND30-1.00 b-1.06” - ND30 device with software
version 1.00 and bootloader version 1.06)
31 2E 30 36 20
checksum
Checksu
m (CRC)
E0 24
9.3 Ethernet interface 10/100-BASE-T
The ND30 meters version ND30-XX2XXXX are equipped with an Ethernet interface for connecting
the meter (using the RJ45 socket) to the local or global network (LAN or WAN). The Ethernet interface
allows to use the web services implemented in the meter: web server, FTP server, Modbus TCP/IP.
Configure Ethernet group parameters to use the meter's network services. The standard Ethernet
parameters of the meter are shown in Table 9.The main parameter is the IP address of the meter, e.g.
.0.1.161, which must be unique in a network the device will be connected to. The IP address can be
10
assigned to the meter automatically by the DHCP server present in the network if the meter has an option
to obtain an address from DHCP server enabled: Ethernet Addresses DHCP On If the DHCP
service is disabled then the meter will work with the default IP address allowing the user to change the IP
address, e.g. from the menu of the meter. Change of the Ethernet parameters can also be done via the
RS485 interface. So it is required to confirm the changes by writing the value "1" to the register 4149. The
Ethernet interface is rebooted in accordance with the new parameters after applying changes - all services
of the Ethernet interface are restarted.
9.3.1 Connecting 10/100-BASE-T interface
Connect the device to a TCP/IP network using the RJ45 socke
of the meter to get access to the Ethernet services.
The meter's RJ45 socket LEDs description:
•yellow LED
- illuminates when the meter is properly connected to the Ethernet 100 Base-T, does not
t located at the back / terminal side /
Page 37
36 User's manual
illuminate when the meter is not connected to a network or is connected to a 10-Base-T.
•green LED - Tx/Rx, illuminates (irregularly illuminates) when the meter sends and receives data,
illuminates continuously when no data is transmitted
It is recommended to use a twisted pair cable to connect the meter to the network:
•U/FTP – twisted pair cable with a separate foil for every pair
•F/FTP – twisted pair cable with separate foil for every pair and additional foil shielding for the cable
•S/FTP (former SFTP) – twisted pair cable with separate foil for every pair and additional mesh cable
shielding
•SF/FTP (former S-STP) – twisted pair cable with separate foil for every pair and additional mesh
and foil cable shielding
The twisted pair cable categories according to the European standard EN 50173 are minimum:
Class D (category 5) - for high-speed local area networks, includes the applications using the frequency
band up to 100 MHz. For Ethernet connection use the category 5 STP type twisted-pair cable (shielded)
with RJ-45 connector, wiring colors (according to Table 11), compliant to the following standards:
•EIA/TIA 568A for both connectors in strike-through connection (i.e. between ND30 and hub or
switch)
•EIA/TIA 568A for the first connector and EIA/TIA 568B for the second one in the cross-over
connection (i.e. when connecting the ND30 meter to the computer).
• Table 13
Wire no.SignalWire color according to the standard
Fig. 28. View and pin
numbering of the RJ45 socket
9.3.2 Web Server
ND30 meter provides its own web server which enables remote monitoring of the measuring
The
values and reading a status of the meter. A web page allows in particular to:
•obtain information about the device (serial number, code execution, software version, bootloader
version, version (standard or special),
•preview current measuring values, read a device status,
•select the web page language
Page 38
37 User's manual
Access to the server can be achieved by entering the IP address of the meter in the web browser,
for example: http://192.168.1.030 (where 192.168.1.030 is set address of the meter). The default web
server port is the port "80". The server port can be changed by the user.
Note: A browser with JavaScript enabled and compatible with XHTML 1.0 is required for correct
operation of the website (all popular browsers, Internet Explorer version 8 minimum).
9.3.2.1 General view
Fig. 29. View of the meter website
9.3.2.2 Web user selection
The meter has two user accounts for the web server protected by the individual passwords:
•user:
•user: "user”, password: "pass” - access only to the preview of the parameters.
Calling the IP address of the meeter in a browser, e.g. http://192.168.1.30 will display a start website to
enter a user name and a password.
"admin”, password: "admin” - access to the configuration and preview of the parameters
Page 39
38 User's manual
Fig. 30. View of the meter's web server login window
server user name can not be changed. You can change the password for each user - for safety
Web
reasons it is recommended to change the passwords. Changing the password is possible only through a
web page in the "Ethernet" parameter group. The passwords can be up to 8 characters. If the password is
lost (what disables using the web server), restore the default settings of the Ethernet interface e.g. from the
menu: Settings Default settings Yes or entering the value "1" to the register 4152. All standard meter
parameters and Ethernet interface parameters (see Table 9) and the passwords of the web server users
will be restored:
user "admin” password: "admin”;
user "user” password "pass”.
9.3.3 FTP Server
FTP file sharing protocol has been implemented in the ND30 meters. The meter acts as a
The
server, allowing the users to access the internal memory of its file system. Access to the files is possible
using a computer, a tablet with installed FTP client or other device acting as a FTP client. The standard
FTP ports are used for transferring files, "1025" - data port and "21" -- commands port. A user can change
the port used by the FTP protocol if necessary. Please note, that the port configuration of the FTP server
and the client must be the same.
The FTP client program can work in a passive mode. The connection is fully made by the FTP client in the
passive mode (a client chooses the data port). It is possible to use up to one connection at the same time
for the file transfer with the meter, so you should limit the maximum number of a FTP client connections to 1.
Page 40
39 User's manual
9.3.3.1 FTP user selection
The meter has two user accounts for the FTP server protected by the individual passwords:
•user: "admin”, password: "admin” - access to read and write the files
•user: "user”, password: "passftp” - access to read only the archive files.
The FTP user names can not be changed but you can change the password for each user - for
safety reasons it is recommended to change the passwords. Changing the password is possible only
through a web page in the "Ethernet" parameter group. The passwords can be up to 8 characters. If the
password is lost (what disables using the FTP server), restore the default settings of the Ethernet interface
e.g. from the menu: Settings
Default settings Yes or entering the value "1" to the register 4152. All
standard meter parameters and Ethernet interface parameters (see Table 9) and the passwords of the FTP
server users will be restored:
user "admin” password: "admin”;
user "user” password "passftp”.
The program FileZilla could be an example of the FTP client. You can view and download the
archive files by entering the IP address of the meter in the address field.
Page 41
40 User's manual
Fig. 31. View of the FTP session in the program FileZilla
Page 42
41 User's manual
9.3.4 Modbus TCP/IP
The ND30 meter allows access to the internal registers via the Ethernet interface and Modbus
TCP/IP protocol. It is necessary to set the unique IP address of the meter and set the connection
parameters listed in Table 14 to set up a connection.
Table 14
Register DescriptionDefault value
4146
4147
145
4
4144
The device address is the address of the device for Modbus TCP/IP protocol and is not a value
equal to a address value for Modbus RS485 protocol (Modbus network address register 4100). Setting the
parameter "Device address for Modbus TCP/IP protocol" of the meter to the value "255", the meter will skip
the address analysis in the frame of Modbus protocol (broadcast mode).
Device address for Modbus TCP/IP protocol1
Modbus TCP port number502
Port closing time of Modbus TCP/IP service [s]60
The maximum simultaneous connections to Modbus TCP/IP service4
10 MAP OF ND30 METER REGISTERS
In the ND30 meter, data are placed in 16 and 32-bit registers. Process variables and
meter parameters are placed in the address area of registers in a way depended on the
variable value type. Bits in 16-bit register are numbered from the youngest to the oldest (b0b15). The 32-bit registers contain numbers of float type in IEEE-754 standard. 3210 byte
sequence - the oldest is sent first.
ble 15
Ta
Address rangeValue typeDescription
Value set in the 16-bit register. Registers for meter configuration.
Description of registers is shown in Table 16. Registers for writing and
readout.
Value set in the 16-bit register. Registers for configuration of programmable
group of registers for readout. Description of registers is shown in Table 15.
Registers for writing and readout.
Value set in the 16-bit register. Registers for displayed pages configuration.
Description of registers is shown in Table 19. Registers for writing and
readout.
Value set in the 16-bit register. Status registers, energy value, MAC address
of the meter, configuration data. Description of registers is shown in Table
20. Readout registers.
Value is set in the two following 16-bit registers. Registers contain exactly
the same data, as 32-bit registers of 7500 – 7953 range. Readout registers.
Bytes sequence (1-0-3-2)
Content of the registers set in the registers 4200 – 4359. Bytes sequence
(3-2-1-0)
Content of the registers set in the registers 4200 – 4359. Bytes sequence
(1-0-3-2)
Content of the registers set in the registers 4200 – 4359. Values set in one
32-bit register.
Values set in one 32-bit register. Description of registers is shown in Table
21. Readout registers.
Value is set in the two following 16-bit registers. Registers contain exactly
the same data, as 32-bit registers of 7500 – 7953 range. Readout registers.
Bytes sequence (3-2-1-0)
4000 – 4159
4200 – 4260
4300 - 4385
4400- 4440
6000 – 6922
7000 - 7118
7200 – 7318
7400 - 7459
7500 – 7961
8000 - 8922
Integer
(16 bits)
Integer
(16 bits)
Integer
(16 bits)
Integer
(16 bits)
Float
(2x16 bits)
Float
(2x16 bits)
Float
(2x16 bits)
Float
(32 bits)
Float
(32 bits)
Float
(2x16 bits)
Page 43
42 User's manual
Table 16
Register
address
4000RW0…9999Protection - password0
4001RW0 .. 1
4002RW0 .. 2
4003RW0 .. 2
4004RW0 .. 2
4005RW0..5
4006RW0..5
400
4008RW0,1Input current range: 1 A or 5 A: 0 - 1 A, 1 - 5 A 1
4009RW0,1
4010RW0..18Transformer primary voltage, two older bytes 0
4011RW0..65535Transformer primary voltage, two younger bytes100
4012RW1 .. 10000Transformer secondary voltage x 101000
4013RW1 .. 20000Transformer primary current5
4014RW1 .. 1000Transformer secondary current5
4015RW0…2
4016RW0.1
4017RWreserved
4018RWreserved
4019RWreserved
Operati
ons
RangeDescription
7RW0..5
Type of connection
0 - 3Ph/4W
1 - 3Ph/3W
2 - 1Ph/2W
Voltage on terminal 2
0 - first L1 phase voltage
1 - second L2 phase voltage
2 - third L3 phase voltage
Voltage on terminal 5
0 - first L1 phase voltage
1 - second L2 phase voltage
2 - third L3 phase voltage
Voltage on terminal 8
0 - first L1 phase voltage
1 - second L2 phase voltage
2 - third L3 phase voltage
Current on terminals 1, 3:
0 - first phase IL1 current
reversed direction of the current of phase L1: -I
1 -
2 - second phase IL2 current
3 - reversed direction of the current of phase L2: -I
4 - third phase IL3 current
5 - reversed direction of the current of phase L3: -I
Current on terminals 4, 6:
0 - first phase IL1 current
1 - reversed direction of the current of phase L1: -I
2 - second phase IL2 current
3 - reversed direction of the current of phase L2: -I
4 - third phase IL3 current
reversed direction of the current of phase L3: -I
5 -
Current on terminals 7, 9:
0 - first phase IL1 current
reversed direction of the current of phase L1: -I
1 -
2 - second phase IL2 current
3 - reversed direction of the current of phase L2: -I
4 - third phase IL3 current
5 - reversed direction of the current of phase L3: -I
Input voltage range:
0 – 3 x 57.7/100 V; 1 – 3 x 230/400 V (version 1)
0 – 3 x 110/190 V; 1 – 3 x 400/690 V (version 2)
Averaging time of the active power P Demand
apparent power S Demand
current I Demand
0 – 15, 1- 30, 2- 60 minutes
Synchronizationwith real-time clock
0 - no synchronization
1 - synchronization with a clock
L1
L2
L3
L1
L2
L3
L1
L2
L3
Defau
lt
0
0
1
2
0
2
4
1
0
1
Page 44
43 User's manual
4020RWResistance of wires for the input T1 x 1000
4021RWResistance of wires for the input T2 x 1000
4022RWreserved
4023RWreserved
"1" – copy archive to files archive memory / only the records which
The third and the second byte (B3.B2) of the IP address of the
meter, the IPv4 address format: B3.B2.B1.B0
The first and zero byte (B1.B0) of the IP address of the meter, the
IPv4 address format: B3.B2.B1.B0
The third and the second byte (B3.B2) of the subnet mask of the
meter, the mask format: B3.B2.B1.B0
The first and zero byte (B1.B0) of the subnet mask of the meter,
the mask format: B3.B2.B1.B0
The third and the second byte (B3.B2) of the default gateway of
the meter, the gateway address format: B3.B2.B1.B0
The first and zero byte (B1.B0) of the default gateway of the
meter, the gateway address format: B3.B2.B1.B0
The third and the second byte (B3.B2) of the DNS address of the
meter, the IPv4 address format: B3.B2.B1.B0
The first and zero byte (B1.B0) of the DNS address of the meter,
the IPv4 address format: B3.B2.B1.B0
Enabling / disabling the DHCP Client (supports automatic
aining of IP protocol parameters of the meter's Ethernet
obt
interface from external DHCP servers in the same LAN)
0 - DHCP disabled - you should manually configure the IP
address and subnet mask of the meter;
1 - DHCP enabled, the meter will automatically receive the IP
address, subnet mask, and gateway address from the DHCP
server when switching the supply on or selecting APPL option
from the menu or entering the value "1" to the register 4099. The
gateway address is the address of the server that assigned the
parameters to the meter;
The maximum simultaneous connections to Modbus TCP/IP
service
Saving the new parameters and initiate Ethernet interface
0 – no changes
1 - saving the new parameters and initiate the Ethernet interface
Group 2, archiving upper limit w o/
Copying archive to files archive memory.
have been registered since the last copy /
Decimal separator 0 - dot '.' 1 - comma ','.
Baud rate of the Ethernet interface:
0 – automatic selection of the baud rate
1 – 10 Mb/s
2 – 100 Mb/s
The alarm switching values stored in the registers 4036, 4037, 4054, 4055, 4067, 4068, 4076, 4077, 4085,
6 are multiplied by 10, e.g. the value of 100% should be entered as "1000".
408
The lower and upper values of the input range of the continuous output stored in the registers 4094, 4095
are multiplied by 10, e.g. the value of 100% should be entered as "1000".
The lower and upper values of the current output range stored in the registers 4096, 4097 are multiplied by
100, e.g. the value of 20 mA should be entered as "2000".
Register
address
4200RW7500 .. 7957Register 1 of programmable group of registers for readout7500
4201RW7500 .. 7957Register 2 of programmable group of registers for readout7501
4202RW7500 .. 7957Register 3 of programmable group of registers for readout7502
4203RW7500 .. 7957Register 4 of programmable group of registers for readout7503
4204RW7500 .. 7957Register 5 of programmable group of registers for readout7504
4205RW7500 .. 7957Register 6 of programmable group of registers for readout7505
4206RW7500 .. 7957Register 7 of programmable group of registers for readout7506
4207RW7500 .. 7957Register 8 of programmable group of registers for readout7507
4208RW7500 .. 7957Register 9 of programmable group of registers for readout7508
4209RW7500 .. 7957Register 10 of programmable group of registers for readout7509
4210RW7500 .. 7957Register 11 of programmable group of registers for readout7510
4211RW7500 .. 7957Register 12 of programmable group of registers for readout7511
4212RW7500 .. 7957Register 13 of programmable group of registers for readout7512
4213RW7500 .. 7957Register 14 of programmable group of registers for readout7513
4214RW7500 .. 7957Register 15 of programmable group of registers for readout7514
4215RW7500 .. 7957Register 16 of programmable group of registers for readout7515
4216RW7500 .. 7957Register 17 of programmable group of registers for readout7516
4217RW7500 .. 7957Register 18 of programmable group of registers for readout7517
4218RW7500 .. 7957Register 19 of programmable group of registers for readout7518
4219RW7500 .. 7957Register 20 of programmable group of registers for readout7519
4220RW7500 .. 7957Register 21 of programmable group of registers for readout7520
4221RW7500 .. 7957Register 22 of programmable group of registers for readout7521
4222RW7500 .. 7957Register 23 of programmable group of registers for readout7522
4223RW7500 .. 7957Register 24 of programmable group of registers for readout7523
4224RW7500 .. 7957Register 25 of programmable group of registers for readout7524
4225RW7500 .. 7957Register 26 of programmable group of registers for readout7525
4226RW7500 .. 7957Register 27 of programmable group of registers for readout7526
4227RW7500 .. 7957Register 28 of programmable group of registers for readout7527
4228RW7500 .. 7957Register 29 of programmable group of registers for readout7528
4229RW7500 .. 7957Register 30 of programmable group of registers for readout7529
4230RW7500 .. 7957Register 31 of programmable group of registers for readout7530
4231RW7500 .. 7957Register 32 of programmable group of registers for readout7531
4232RW7500 .. 7957Register 33 of programmable group of registers for readout7532
4233RW7500 .. 7957Register 34 of programmable group of registers for readout7533
4234RW7500 .. 7957Register 35 of programmable group of registers for readout7534
4235RW7500 .. 7957Register 36 of programmable group of registers for readout7535
Operati
ons
RangeDescriptionDefault
Saving default parameters (complete with resetting energy as well
as min, max and mean power to 0) and Ethernet,
Table 17
0
Page 49
48 User's manual
Register
address
4236RW7500 .. 7957Register 37 of programmable group of registers for readout7536
4237RW7500 .. 7957Register 38 of programmable group of registers for readout7537
4238RW7500 .. 7957Register 39 of programmable group of registers for readout7538
4239RW7500 .. 7957Register 40 of programmable group of registers for readout7539
4240RW7500 .. 7957Register 41 of programmable group of registers for readout7540
4241RW7500 .. 7957Register 42 of programmable group of registers for readout7541
4242RW7500 .. 7957Register 43 of programmable group of registers for readout7542
4243RW7500 .. 7957Register 44 of programmable group of registers for readout7543
4244RW7500 .. 7957Register 45 of programmable group of registers for readout7544
4245RW7500 .. 7957Register 46 of programmable group of registers for readout7545
4246RW7500 .. 7957Register 47 of programmable group of registers for readout7546
4247RW7500 .. 7957Register 48 of programmable group of registers for readout7547
4248RW7500 .. 7957Register 49 of programmable group of registers for readout7548
4249RW7500 .. 7957Register 50 of programmable group of registers for readout7549
4250RW7500 .. 7957Register 51 of programmable group of registers for readout7550
4251RW7500 .. 7957Register 52 of programmable group of registers for readout7551
4252RW7500 .. 7957Register 53 of programmable group of registers for readout7552
4253RW7500 .. 7957Register 54 of programmable group of registers for readout7553
4254RW7500 .. 7957Register 55 of programmable group of registers for readout7554
4255RW7500 .. 7957Register 56 of programmable group of registers for readout7559
4256RW7500 .. 7957Register 57 of programmable group of registers for readout7560
4257RW7500 .. 7957Register 58 of programmable group of registers for readout7561
4258RW7500 .. 7957Register 59 of programmable group of registers for readout7566
4259RW7500 .. 7957Register 60 of programmable group of registers for readout7567
4260RW0,1
Operati
ons
RangeDescriptionDefault
Restore default group 0 – no changes, 1 – restore default
group
0
16-bit register
address
2x16 1032/
2x16 3210
7200/70007400RContent of the register set in the registers 4200
7202/70027401RContent of the register set in the registers 4201
7204/70047402RContent of the register set in the registers 4202
7206/70067403RContent of the register set in the registers 4203
7208/70087404RContent of the register set in the registers 4204
7210/70107405RContent of the register set in the registers 4205
7212/70127406RContent of the register set in the registers 4206
7214/70147407RContent of the register set in the registers 4207
7216/70167408RContent of the register set in the registers 4208
7218/70187409RContent of the register set in the registers 4209
7220/70207410RContent of the register set in the registers 4210
7222/70227411RContent of the register set in the registers 4211
7224/70247412RContent of the register set in the registers 4212
7226/70267413RContent of the register set in the registers 4213
7228/70287414RContent of the register set in the registers 4214
7230/70307415RContent of the register set in the registers 4215
7232/70327416RContent of the register set in the registers 4216
7234/70347417RContent of the register set in the registers 4217
7236/70367418RContent of the register set in the registers 4218
7238/70387419RContent of the register set in the registers 4219
7240/70407420RContent of the register set in the registers 4220
7242/70427421RContent of the register set in the registers 4221
7244/70447422RContent of the register set in the registers 4222
7246/70467423RContent of the register set in the registers 4223
Register
address
32-bit
OperationsDescription
Table 18
Page 50
49 User's manual
7248/70487424RContent of the register set in the registers 4224
7250/70507425RContent of the register set in the registers 4225
7252/70527426RContent of the register set in the registers 4226
7254/70547427RContent of the register set in the registers 4227
7256/70567428RContent of the register set in the registers 4228
7258/70587429RContent of the register set in the registers 4229
7260/70607430RContent of the register set in the registers 4230
7262/70627431RContent of the register set in the registers 4231
7264/70647432RContent of the register set in the registers 4232
7266/70667433RContent of the register set in the registers 4233
7268/70687434RContent of the register set in the registers 4234
7270/70707435RContent of the register set in the registers 4235
7272/70727436RContent of the register set in the registers 4236
7274/70747437RContent of the register set in the registers 4237
7276/70767438RContent of the register set in the registers 4238
7278/70787439RContent of the register set in the registers 4239
7280/70807440RContent of the register set in the registers 4240
7282/70827441RContent of the register set in the registers 4241
7284/70847442RContent of the register set in the registers 4242
7286/70867443RContent of the register set in the registers 4243
7288/70887444RContent of the register set in the registers 4244
7290/70907445RContent of the register set in the registers 4245
7292/70927446RContent of the register set in the registers 4246
7294/70947447RContent of the register set in the registers 4247
7296/70967448RContent of the register set in the registers 4248
7298/70987449RContent of the register set in the registers 4249
7300/71007450RContent of the register set in the registers 4250
7302/71027451RContent of the register set in the registers 4251
7304/71047452RContent of the register set in the registers 4252
7306/71067453RContent of the register set in the registers 4253
7308/71087454RContent of the register set in the registers 4254
7310/71107455RContent of the register set in the registers 4255
7312/71127456RContent of the register set in the registers 4256
7314/71147457RContent of the register set in the registers 4257
7316/71167458RContent of the register set in the registers 4258
7318/71187459RContent of the register set in the registers 4259
Registe
r
address
4300RW1…3
Operati
ons
RangeDescriptionDefault
Luminosity level: 1 – Minimum, 2 - Medium
3 - Maximum
4301RW0 .. 3600Time to min. luminosity0
4302RWreserved0
4400Rreserved
4401R0..65535IdentifierD9
4402R0..65535Bootloader version x 1004403R0..65535Program version x1004404Rreserved
4405R0..65535Ordering codes4406R0..65535Nominal voltage x10577/2300
4407R0..65535Nominal voltage x101100/4000
4408R0..65535Nominal current (1 A) x 100100
4409R0..65535Nominal current (5 A) x 100500
4410Rreserved
The fifth and fourth byte (B1.B0) of MAC address of the
meter, format B5:B4:B3:B2:B1:B0
oo
oo
oo
Total archive internal memory usage
for the groups 1 and 2 in o/
oo
Percentage of the archive copying progress to files archive
for group 1 in o/
oo
Percentage of the archive copying progress to files archive
for group 2 in o/
oo
Total percentage of the archive copying progress to files
archive for group 1 and 2 in o/
oo
-
0
0
0
0
0
0
0
Energy is made available in hundreds of watt-hours (var-hours) in double 16-bit register, and for this
reason, you should divide them by 100 when calculating values of particular energy from registers, e.g.:
Active import energy = (reg. value 4426 x 65536 + reg. value 4427) / 100 [kWh]
Active export energy = (reg. value 4428 x 65536 + reg. value 4429) / 100 [kWh]
Reactive inductive energy = (reg. value 4430 x 65536 + reg. value 4431) / 100 [kVarh]
Reactive capacity energy = (reg. value 4432 x 65536 + reg. value 4433) / 100 [kVarh]
Apparent energy = (reg. value 4434 x 65536 + reg. value 4435) / 100 [kVAh]
Status 1 Register of a device (address 4415, R):
Bit 15 – "1” – FRAM memory damageBit
Bit 14 – "1” – no calibration of the inputBit 6 – "1” – reserved
Bit 13 – "1” – no calibration of the outputBit 5 – "1” – reserved
Bit 12 – "1” – PT100 calibration errorBit 4 – "1” – present analog output
Bit 11 – "1” – error in configuration registers Bit 3 – "1” – present PT100
Bit 10 – "1” – error in displayed pages registers Bit 2 – "1” – present Ethernet and internal memory
Bit 9 – "1” – error in registers for configuration of
programmable group of registers for readout
Bit 8 – "1” – energy value error Bit 0 – reserved
7 – "1” – phase sequence error
Bit 1 – "1” – used battery of RTC
Page 54
53 User's manual
Status 2 Register – (address 4416, R):
Bit 15 – "1” – condition 3 for alarm 2 signalization
Bit 14 – "1” – condition 2 for alarm 2 signalization
Bit 13 – "1” – condition 1 for alarm 2 signalization
Bit 12 – "1” – alarm 2 signalization
Bit 11 – "1” – alarm 2 condition 3 activated
Bit 10 – "1” – alarm 2 condition 2 activated
Bit 9 – "1” – alarm 2 condition 1 activated
Bit 8 – "1” – alarm 2 activated
Status 3 Register – (address 4417, R): Files archive status
Bit 15 – Ethernet connected
14 – reserved
Bit
Bit 13 – reserved
Bit 12 – reserved
Bit 11 – "0” - waiting for the archiving conditions to be met
"1” - archiving in the archiving group 2
Bit 10 – "0” - waiting for the archiving conditions to be met
"1” - archiving in the archiving group 1
Bit 9 – reserved
Bit 8 – Archiving group 2 enabled
Bit 7 – "1” – condition 3 for alarm 1 signalization
Bit 6 – "1” – condition 2 for alarm 1 signalization
Bit 5 – "1” – condition 1 for alarm 1 signalization
Bit 4 – "1” – alarm 1 signalization
Bit 3 – "1” – alarm 1 condition 3 activated
Bit 2 – "1” – alarm 1 condition 2 activated
Bit 1 – "1” – alarm 1 condition 1 activated
Bit 0 – "1” – alarm 1 activated
Bit 7 – Archiving group 1 enabled
Bit 6 – reserved
Bit 5 – copying of internal memory to
Bit 4 – copying of internal memory to
Bit 3 – Files archive space is full, (less then 14
days at 1 sec. interval to completely use a the files
archive space)
Bit 2 – 70% of files archive space is full
Bit 1 – Files archive initialized correctly
Bit 0 – Files archive file system error
files archive from archiving group 2
files archive from archiving group 1
Status 4 Register – (address 4418, R) reactive power characteristics:
Bit 15 – measurement with phase L3 synchronization
Bit 14 – measurement with phase L2 synchronization
Bit 13 – measurement with phase L1 synchronization
Bit 12 – measurement with current synchronization
Bit 11 – "1” – capacity 3L max.
Bit 10 – "1” – capacity 3L min.
Bit 9 – "1” – capacity 3L
Bit 8 – "1” – leading L3 max.
Bit 7 – "1” – capacity L3 min.
Bit 6 – "1” – capacity L3
Bit 5 – "1” – capacity L2 max.
Bit 4 – "1” – capacity L2 min.
Bit 3 – "1” – capacity L2
Bit 2 – "1” – capacity L1 max.
Bit 1 – "1” – capacity L1 min.
Bit 0 – "1” – capacity L1
Status 5 Register – (address 4419, R)
Bit 8 – "1” – alarm 1 condition 3 for phase L3 active
7 – "1” – alarm 1 condition 3 for phase L2 active
Bit
Bit 6 – "1” – alarm 1 condition 3 for phase L1 active
Bit 5 – "1” – alarm 1 condition 2 for phase L3 active
Bit 4 – "1” – alarm 1 condition 2 for phase L2 active
Bit 3 – "1” – alarm 1 condition 2 for phase L1 active
Bit 2 – "1” – alarm 1 condition 1 for phase L3 active
Bit 1 – "1” – alarm 1 condition 1 for phase L2 active
Bit 0 – "1” – alarm 1 condition 1 for phase L1 active
Status 6 Register – (address 4420, R)
Bit 8 – "1” – alarm 2 condition 3 for phase L3 active
Bit 7 – "1” – alarm 2 condition 3 for phase L2 active
Bit 6 – "1” – alarm 2 condition 3 for phase L1 active
Bit 5 – "1” – alarm 2 condition 2 for phase L3 active
Bit 4 – "1” – alarm 2 condition 2 for phase L2 active
Bit 3 – "1” – alarm 2 condition 2 for phase L1 active
Bit 2 – "1” – alarm 2 condition 1 for phase L3 active
Bit 1 – "1” – alarm 2 condition 1 for phase L2 active
Bit 0 – "1” – alarm 2 condition 1 for phase L1 active
Page 55
54 User's manual
16-bit
register
address
2x16
1032/
2x16 3210
6000/80007500RL1 phase voltageV
6002/80027501RL1 phase currentA
6004/80047502RL1 phase active powerW
6006/80067503RL1 phase reactive powerVAr
6008/80087504RL1 phase apparent powerVA
6010/80107505RL1 phase active power factor (PF1=P1/S1))6012/80127506Rtg
6014/80147507R THD U1* %
6016/80167508R THD I1 %
6018/80187509RL2 phase voltageV
6020/80207510RL2 phase currentA
6022/80227511RL2 phase active powerW
6024/80247512RL2 phase reactive powerVAr
6026/80267513RL2 phase apparent powerVA
6028/80287514RL2 phase active power factor (PF2=P2/S2))6030/80307515Rtg factor of L2 phase (tg2=Q2/P2)6032/80327516R THD U2* %
6034/80347517R THD I2 %
6036/80367518RL3 phase voltageV
6038/80387519RL3 phase currentA
6040/80407520RL3 phase active powerW
6042/80427521RL3 phase reactive powerVAr
6044/80447522RL3 phase apparent powerVA
6046/80467523RL3 phase active power factor (PF3=P3/S3))6048/80487524Rtg
6050/80507525R THD U3*%
6052/80527526R THD I3 %
6054/80547527RMean 3-phase voltageV
6056/80567528RMean 3-phase currentA
6058/80587529R3-phase active power (P1+P2+P3)W
6060/80607530R3-phase reactive power (Q1+Q2+Q3)VAr
6062/80627531R3-phase apparent power (S1+S2+S3)VA
6064/80647532R3-phase active power factor (PF=P/S)6066/80667533RMean tg factor for 3 phases (tg=Q/P)6068/80687534RTHD U* mean 3-phase %
6070/80707535RTHD I mean 3-phase %
6072/80727536RFrequencyf
6074/80747537RPhase-to-phase voltage L
6076/80767538RPhase-to-phase voltage L
6078/80787539RPhase-to-phase voltage L
6080/80807540RMean phase-to-phase voltageV
6082/80827541RActive power averaged (P Demand)W
6084/80847542RReactive power averaged (S Demand )VA
6086/80867543RCurrent averaged (I Demand)A
6088/80887544RNeutral wire current (calculated from vectors) A
6090/80907545R
6092/80927546R
6094/80947547RActive 3-phase export energy (no. of register 100
Register
address
32-bit
Operation
s
DescriptionUnit
factor of L1 phase (tg1=Q1/P1)-
factor of L3 phase (tg3=Q3/P3)-
1-2
2-3
3-1
Active 3-phase import energy (no. of register
7546 overflows, resets to 0 after reaching 9999.9
MWh)
Active 3-phase import energy (counter counting
up to 99999.99 kWh)
V
V
V
100
MWh
kWh
Table 21
3Ph
3Ph
/
/
4W
3W
x
√
√√√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
xx
√
√√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
√√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
√√
√√
√√
√√
√√
√√
xx
√
xx
√
√√√
√√
√√
√√
√√
√√
√√
√√
xx
√
√√√
√√√
√√√
1Ph
/
2W
√
√
√
√
√
√
√
√
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Page 56
55 User's manual
7548 overflows, resets to 0 after reaching 9999.9
MWh)
6152
6154/81547577RCurrent L2 maxA
6156/81567578RCurrent L3 minA
6158/81587579RCurrent L3 maxA
6160/81607580RActive power L1 minW
6162/81627581RActive power L1 maxW
6164/81647582RActive power L2 minW
6166/81667583RActive power L2 maxW
6168/81687584RActive power L3 minW
6170/81707585RActive power L3 maxW
6172/81727586RReactive power L1 minVar
6174/81747587RReactive power L1 maxVar
76/81767588RReactive power L2 minVar
61
6178/81787589RReactive power L2 maxVar
/81807590RReactive power L3 minVar
6180
6182/81827591RReactive power L3 maxVar
6184/81847592RApparent power L1 minVA
Active 3-phase export energy (counter counting
up to 99999.99 kWh)
Reactive 3-phase inductive energy (no. of
register 7550 overflows, resets to 0 after
reaching 9999.9 MVArh).
Reactive 3-phase inductive energy (counter
counting up to 99999.99 kVArh)
Reactive 3-phase capacity energy (no. of register
7552 overflows, resets to 0 after reaching 9999.9
MVArh)
Reactive 3-phase capacity energy (counter
counting up to 99999.99 kVArh)
Apparent energy (no. of register 7554 overflows,
ts to 0 after reaching 9999.9 MVAh)
rese
Apparent energy (counter counting up to
99999.99 kVAh)
MWh
kWh
100
MVArh
kVArh
100
MVArh
kVArh
100
MVAh
kVAh
°C√√√
°C√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
√√√
x
√
x
√
xx
√
xx
√
xx
√
xx
√
√√
√√
√√
√√
√√
√√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
√
√
x
x
x
x
x
x
√
√
x
x
x
x
√
√
x
x
x
x
√
Page 57
56 User's manual
6186/81867593RApparent power L1 maxVA
6188/81887594RApparent power L2 minVA
6190/81907595RApparent power L2 maxVA
6192/81927596RApparent power L3 minVA
6194/81947597RApparent power L3 maxVA
6196/81967598RPower factor (PF) L1 min6198/81987599RPower factor (PF) L1 max6200/82007600RPower factor (PF) L2 min6202/82027601RPower factor (PF) L2 max6204/82047602RPower factor (PF) L3 min6206/82067603RPower factor (PF) L3 max-
8/82087604RReactive to active power ratio L1 min-
620
6210/82107605RReactive to active power ratio L1 max6212/82127606RReactive to active power ratio L1 min6214/82147607RReactive to active power ratio L2 max6216/82167608RReactive to active power ratio L3 min6218/82187609RReactive to active power ratio L3 max6220/82207610RPhase-to-phase voltage L
6222/82227611RPhase-to-phase voltage L
6224/82247612RPhase-to-phase voltage L
6226/82267613RPhase-to-phase voltage L
6228/82287614RPhase-to-phase voltage L
6230/82307615RPhase-to-phase voltage L
6232/82327616RMean 3-phase voltage (min)V
6234/82347617RMean 3-phase voltage (max)V
6236/82367618RMean 3-phase current (min)A
6238/82387619RMean 3-phase current (max)A
6240/82407620R3-phase active power (min)W
6242/82427621R3-phase active power (max)W
6244/82447622R3-phase reactive power (min)var
246/82467623R3-phase reactive power (max)var
6
6248/82487624R3-phase apparent power (min)VA
6250/82507625R3-phase apparent power (max)VA
6252/82527626RPower factor (PF) min6254/82547627RPower factor (PF) max-
6256/82567628R
6258/82587629R
6260/82607630RMin. frequencyHz
6262/82627631RFrequency maxHz
6264/82647632RMean phase-to-phase voltage (min.)V
6266/82667633RMean phase-to-phase voltage (max.)V
6268/82687634RActive power averaged (P Demand) minW
6270/82707635RActive power averaged (P Demand) maxW
6272/82727636RApparent power averaged (S Demand) minVA
6274/82747637RApparent power averaged (S Demand) maxVA
6276/82767638RCurrent averaged (I Demand) minA
6278/82787639RCurrent averaged (I Demand) maxA
6280/82807640RNeutral wire current (min.)A
2/82827641RNeutral wire current (max.)A
628
6284/82847642RTemperature T1 min
6286/82867643RTemperature T1 max
Reactive to active power ratio (3-phase mean
min.)
Reactive to active power ratio (3-phase mean
max.)
6288/82887644RTemperature T2 min
6290/82907645RTemperature T2 max
6292/82927646R THD U1 min%
6294/82947647R THD U1 max%
6296/82967648R THD U2 min%
6298/82987649R THD U2 max%
6300/83007650R THD U3 min%
6302/83027651R THD U3 max%
6304/83047652R THD U min%
6306/83067653R THD U max%
6308/83087654R THD I1 min%
/83107655R THD I1 max%
6310
6312/83127656R THD I2 min%
6314/83147657R THD I2 max%
6316/83167758R THD I3 min%
6318/83187759R THD I3 max%
6320/83207660RTHD I min%
6322/83227661RTHD I max%
6324/83247662RHarU1[2] 2nd harmonic of L1 phase voltage%
6326/83267663RHarU1[3] 3rd harmonic of L1 phase voltage%
::R:
::R:
6420/84207710RHarU1[50] 50th harmonic of L1 phase voltage%
6422/84227711RHarU1[51] 51st harmonic of L1 phase voltage%
6424/84247712RHarU2[2] 2nd harmonic of L2 phase voltage%
6426/84267713RHarU2[3] 3rd harmonic of L2 phase voltage%
::R:
::R:
6520/85207760RHarU2[50] 50th harmonic of L2 phase voltage%
6522/85227761RHarU2[51] 51st harmonic of L2 phase voltage%
6524/85247762RHarU3[2] 2nd harmonic of L3 phase voltage%
6526/85267763RHarU3[3] 3rd harmonic of L3 phase voltage%
::R:
::R:
/86207810RHarU3[50] 50th harmonic of L3 phase voltage%
6620
6622/86227811RHarU3[51] 51st harmonic of L3 phase voltage%
6624/86247812RHarl1U1[2] 2nd harmonic of L1 phase current%
6626/86267813RHarl1U1[3] 3rd harmonic of L1 phase current%
::R:
::R:
6720/87207860RHarl1U1[50] 50th harmonic of L1 phase current%
6722/87227861RHarl1[51] 51st harmonic of L1 phase current%
6724/87247862RHarl2[2] 2nd harmonic of L2 phase current%
6726/87267863RHarl2[3] 3rd harmonic of L2 phase current%
::R:
::R:
6820/88207910RHarl2[50] 50th harmonic of L2 phase current%
6822/88227911RHarl2[51] 51st harmonic of L2 phase current%
6824/88247912RHarl3[2] 2nd harmonic of L3 phase current%
6826/88267913RHarl3[3] 3rd harmonic of L3 phase current%
::R:
::R:
6920/89207960RHarl3[50] 50th harmonic of L3 phase current%
6922/89227961RHarl3[51] 51st harmonic of L3 phase current%
°C
°C
√√√
√√√
x
√
x√
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
x
√
x
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
x
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
xx
√
√
√
√
√
√
√
√
x
x
x
x
x
x
x
x
√
√
√
√
* In the 3-phase 3-wire (3Ph / 3W) respectively THD U12, THD U23, THD U31, THD U123
Page 59
58 User's manual
11 SOFTWARE UPGRADE
11.1 Upgrade of the meter website
Upgrade can be done via FTP server.
You can upgrade the website in the tab Website upgrade. Copy the file ND30_upd.tar to the main folder of
the meter. Then turn off and turn on the meter, i.e. reset the meter. The file ND30 upd.tar will be extracted
to the appropriate folders. It can take approx. 1 minute. The messages informing about the progress of
extracting will be displayed on the meter screen.
a)
b)
. 32. View of the window a) logging on, b) website upgrade file
Fig
Page 60
59 User's manual
11.2 Firmware update - main program of the meter
A feature implemented in the ND30 meters enables to upgrade firmware using a PC with eCon
software installed. Free eCon software and the update files are available by request from PCE Instruments. Upgrade of meter software (firmware) can be done via RS-485 interface. Go to UPDATER
tab to upgrade.
Fig. 33. Program window view: a) eCon, b) software upgrade
Note: Software update automatically resets meter settings to default settings, so it is recommended to
save meter settings using eCon software before upgrading. After launching eCon software, set in the
settings required serial port, baud rate, mode and address of the meter. Next, select the ND30 meter and
click Config. Click the down arrow icon to read all of the settings then the disk icon to save the settings
to a file (required to restore the settings later). After selecting the option Update firmware (in the upper
right corner of the screen) the window Updater will be opened – Fig. 33b. Click Connect.
The Messages information window displays information concerning upgrade
process. If the port is opened correctly, a Port opened message appears. Upgrade mode is enabled
using either of the two methods: remotely via the Updater (using LPCon settings: address, mode, baud
rate, COM port) and by turning a meter on while pressing the button (while entering bootloader
mode the button is used to set communication settings: baud rate 9600, RTU8N2, address 1). The
display will show the bootloader version, while the Updater program displays the message Device found
and the name and version of the connected device. Click the "...” button and browse to the meter upgrade
file. If the file is opened correctly, File opened message is displayed. Press the Send button. When
upgrade is successfully completed, the meter begins normal work while the information window
displays Done message and upgrade elapsed time. After the Updater window is closed, go to
parameter group Service parameters, select the option Set default settings of a meter and press a button
Restore. Then press the folder icon to open a previously saved settings file and press the up arrow
icon to save the settings in the meter. Current software version can be checked by reading the
welcome message when switching the meter on.
Note: Turning meter supply off during upgrade may result in permanent damage!
Page 61
60 User's manual
12 ERROR CODES
During the meter operation the error messages may be displayed. Following list shows reasons
of errors.
- Err bat – displayed when the battery of the internal RTC clock is used up. Measurement is
carried out after switching the supply on and every day at midnight. The message can be turned off by
pressing the button . The disabled message remains inactive till the renewed switching of the
meter on.
- Err CAL, Err EE – meter memory is damaged. In such case a meter should be sent back to the
manufacturer.
- Err PAr – incorrect operational parameters of the meter. In such case a meter should be set to
default settings (from menu or via RS-485 interface). The message can be turned off by
pressing the button .
–
∧∧∧∧
–
∨∨∨∨
per overrun. Measuring value is out of the measuring range.
– up
–lower overrun. Measuring value is out of the measuring range.
13 TECHNICAL DATA
Measuring ranges and permissible basic errors Table 22
Measuring valueMeasuring rangeL1L2L3∑Class
Current I 1/5 A 1 A~
5 A~
Voltage U L-N: 57.7 V~
110 V~
230 V~
400 V~
Voltage U L-L: 100 V~
190 V~
400 V~
690 V~
Active power P -19999 MW .. 0.000 W ..
Reactive power Q-19999 MVar .. 0.000 Var ..
Apparent power S 0.000 .. 1999,9 VA ..
Active energy EnP
/ import or export /
Reactive energy EnQ
/ capacity or inductive /
Apparent energy EnS 0.000 .. 99 999 999.999 kVAh
Active power factor PF-1.00 .. 0 .. 1.00••••1 (EN 61557-12)
Factor tg-1.20 .. 0 .. 1.20••••1
Frequency f45.000 ..65.000
Harmonic distortion factor of
voltage THDU, current THDI0.0 .. 100.0
Harmonic amplitudes of
voltage U
of current I
...U
h2
h2 … Ih51
h51
,
0.0 .. 100.0%•••II (IEC61000-4-7)
Hz•0.1 (EN 61557-12)
%••••5 (EN 61557-12)
Page 62
61 User's manual
tr_I - Current transformer ratio = Transformer primary current / Current transformer secondary current
tr_U - Voltage transformer ratio = Transformer primary voltage / Voltage transformer secondary voltage