PCE Instruments PCE-ND30 Users guide

Page 1
PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 info@pce-americas.com
www.pce-instruments.com/english
www.pce-instruments.com
PCE Instruments UK Ltd.
Southpoint Business Park
Hampshire / Southampton
United Kingdom, SO31 4RF
From outside UK: +44
Tel: (0) 2380 98703 0
Fax: (0) 2380 98703 9
info@industrial-needs.com
POWER INDICATOR
PCE-ND30
Units 12/13 Ensign way
USER’S MANUAL
Page 2
Contents
1 APPLICATION..............................................................................................................................2
2 METER SET.................................................................................................................................2
3 BASIC REQUIREMENTS, OPERATIONAL SAFETY...................................................................3
4 INSTALLATION............................................................................................................................3
5 METER DESCRIPTION...............................................................................................................4
5.1 Current inputs .......................................................................................................................4
5.2 Voltage inputs........................................................................................................................4
5.3 External connection diagrams...............................................................................................4
6 ND30 Programming......................................................................................................................8
6.1 Front panel............................................................................................................................8
6.2 Starting work.......................................................................................................................10
7 OPERATING MODES................................................................................................................10
7.1 Measurement mode............................................................................................................14
7.2 Measurement of voltage and current harmonics.................................................................15
7.3 Parameters mode................................................................................................................15
7.4 Alarms mode.......................................................................................................................18
7.5 Analog output mode............................................................................................................20
7.6 Display mode......................................................................................................................21
7.7 Archiving mode....................................................................................................................25
7.8 Ethernet mode.....................................................................................................................28
7.9 Modbus mode.....................................................................................................................29
7.10 Settings mode ..................................................................................................................29
7.11 Information mode .............................................................................................................30
8 MEASURING VALUES ARCHIVING..........................................................................................30
8.1 INTERNAL MEMORY.........................................................................................................30
8.2 COPYING ARCHIVE ..........................................................................................................30
8.3 ARCHIVE FILES STRUCTURE..........................................................................................31
8.4 DOWNLOADING ARCHIVE ...............................................................................................32
9 SERIAL INTERFACES...............................................................................................................32
9.1 RS485 INTERFACE – list of parameters.............................................................................32
9.2 Examples of registers' readout and write............................................................................32
9.3 Ethernet interface 10/100-BASE-T......................................................................................35
9.3.1 Connecting 10/100-BASE-T interface.........................................................................35
9.3.2 Web Server.................................................................................................................36
9.3.2.1 General view........................................................................................................37
9.3.2.2 Web user selection .............................................................................................37
9.3.3 FTP Server..................................................................................................................38
9.3.3.1 FTP user selection................................................................................................39
9.3.4 Modbus TCP/IP...........................................................................................................41
10 MAP OF ND30 METER REGISTERS......................................................................................41
11 SOFTWARE UPGRADE...........................................................................................................58
11.1 Upgrade of the meter website...........................................................................................58
11.2 Firmware update - main program of the meter..................................................................59
12 ERROR CODES.......................................................................................................................60
13 TECHNICAL DATA...................................................................................................................60
14 ORDERING CODE...................................................................................................................63
Page 3
2 User's manual
1 APPLICATION
The ND30 meter is a programmable digital instrument designed for the measurement of 1-phase 2­wire and 3-phase 3 and 4-wire power network parameters in balanced or unbalanced systems. The measured values are displayed on a 3,5’’ TFT full-color screen, resolution: 320 x 240 pixel. The meter enables control and optimization of the power electronic devices, systems and industrial installations. The meter provides measurement of: RMS of voltage and current, active, reactive and apparent power, active, reactive and apparent energy, power factors, frequency, the harmonics of current and voltage /up to 51st/, THD of voltage and current, averaged active and apparent power P Demand, S Demand, averaged current I Demand /15, 30 or 60 minutes/. Voltages and currents are multiplied by given voltage and current ratios of the measuring transformers. Power and energy indications take into account all programmed ratio values. The value of each measured value can be transmitted to the master system via the RS-485 or Ethernet interface. Three relay outputs signal the overflow of the chosen value and the programmable analog output maps the assigned parameter. The temperature inputs can be used to control the temperature of the transformers windings, motors.
There is a galvanic separation between following units of the meter:
- supply
- voltage inputs
- current inputs
- RS485 interface
- Ethernet interface
- alarm outputs
- analog output
- temperature input Pt100
2 METER SET
Complete set of the meter includes:
1. ND10 m
2. seal 1 pc
3. screw clamp to fix in the panel 4 pcs
4. plug with 16 screw terminals 1 pc
5. plug with 14 screw terminals 1 pc
6. user's manual 1 pc
eter 1 pc
Page 4
3 User's manual
1
2
Fig. 1. Meter set
3 BASIC REQUIREMENTS, OPERATIONAL SAFETY
In terms of operational safety the controller meets the requirements of the EN 61010-1 standard. Remar
ks concerning safety:
The meter should be installed and connected only by a qualified personnel. All relevant safety measures should be observed during installation.
Always check the connections before turning the meter on.
Prior to taking the meter housing off, always turn the supply off and disconnect the measuring
circuits.
Removal of the meter housing during the warranty period voids the warranty.
This meter conforms to all requirements of the electromagnetic compatibility in the industrial
environment.
A switch or a circuit-breaker should be installed in the building or facility. It should be located near the device, easily accessible by the operator, and suitably marked.
4 INSTALLATION
The meter is intended to be fixed to the panel with mounting brackets as presented on Fig. 1. The meter
ng is made of a self-extinguishing plastics.
housi
Fig. 2. Meter fitting
Housing overall dimensions 96 x 96 x 77 mm, dimensions of the assembly hole 92.5 x 92.5 mm. There are screw t diameter up to 2.5 mm
erminal strips on the outer side of the meter which enable the connection of external wires of
2
.
Page 5
4 User's manual
Fig. 3. Overall dimensions of the ND30 meter
5 METER DESCRIPTION
5.1 C
All current inputs are galvanically isolated (internal current transformers). The meter is adapted to work with exter automatically converted in relation to the introduced external current transformer ratio.
urrent inputs
nal measuring current transformers / 1 A or 5 A /. Displayed current values and derivative values are
5.2 Voltage inputs
All voltage inputs are galvanically isolated (internal transformers). Values on voltage inputs are automatically converted according to the introduced ratio of the external voltage transformer. Voltage inputs are specified in the order as 3x57.7/100 V, 3x230/400 V or 3x110/190 V, 3x400/690 V.
5.3 External connection diagrams
External connections are shown in Fig. 4.
Page 6
5 User's manual
ND30
option
Fig. 4. Meter connections
296 7431 1185
2 11
1 3
Ethernet (option)
11 32
a
b
1
L1
N
S
S
1
L1
P
1
N
. 5. Direct measurement, indirect and semi-indirect in a 1-phase network
Fig
2
P
2
L1
N
B
A
S
P
1
S
1
2
P
2
Page 7
6 User's manual
Direct measurement in 4-wire network
L1 L2
L3
N
Semi-indirect measurement in 4-wire network
ND30
296 7431 1185
ND30
296 7431 1185
L1
L2
L3
N
Indirect measurement in 4-wire network
a A
L1 L2
L3
N
a
b B
S
S
2
1
P
P
1
2
S
S
2
1
P
P
1
2
S
2
S
1
P
P
1
2
ND30
296 7431 1185
2 5
8
b
BA
a
L1
L2
L3 N
a
b
BA
a
b
BA
b
B
A
S2S
1
P
P
1
2
S2S
1
P
P
1
2
S
2
S
1
P
P
1
2
Fig. 6. Meter connections of input signals in a 3-phase 4-wire network
Page 8
Direct measurement in a 3-wire network
L1 L2
L3
Semi-indirect measurement using 2 current transformers in a 3-wire network
7 User's manual
ND30
296 7431 1185
ND30
296 7431 1185
L1
L2
L3
Indirect measurement using 2 current transformers and 2 or 3 voltage transformers in a 3-wire network
2 5
8
a A
L1
a
b B
b
BA
L2
L3
L1
L2
L3
a
b BA
S
S
2
1
P
P
1
2
S
2
S
1
P
P
1
2
ND30
296 7431 1185
a
a
b
BA
b
B
A
S
2S1
P
P
1
2
S
S
2
1
P
P
1
2
Fig. 7. Meter connections of input signals in a 3-phase 3-wire network
Page 9
6 ND30 PROGRAMMING
6.1 Front panel
8 User's manual
Fig. 8. Front panel
ND30 meter has 6 buttons and a full-color graphic screen.
The Front panel description:
f1, ... , f8 8 field displays - the digits for readout
and settings,
V, A, W, var,
VA, Wh, varh,
Hz,
U1, I1, P1, ...
nQ
..E
units of the displayed values
displayed parameters markings
DMD
k, M
Averaged value indicator (Demand)
kilo = 10
The markers indicating the inductive, capacity load character
3,
Mega = 10
6
The values of the measured parameters are shown on the active pages selected by subsequent pressing the buttons (next page) or (previous page).
The page consists any 8 values selected from the Table 1 and displayed simultaneously on the display. The page definition is described in the Display mode. Depending on the location, meter buttons can perform different functions. Functions are described in the bar on the bottom of the screen. If the button lacks description, it is inactive at the moment.
Function
of button 1
Function
of button 2
Function
of button 3
Function
of button 4
Function
of button 5
Function
of button 6
Fig. 9. Buttons marking – example
Page 10
9 User's manual
Information bar at the top of the screen displays the status of the alarm outputs, alarm conditions, T1 and T2 temperature of the sensors connected to the first and second input of PT100, files archive memory status, archive status, a symbol of Ethernet connection, the indicators of receiving and transmitting data on the RS485 link, date and real-time clock. A symbol "phase sequence error" will be blinking in case of a negative phase sequence.
Fig. 10. Information bar
Icon Icon color Comments
Black – archive memory mounted correctly
Black – no archive memory Red – wrong file system of the card
Copying from internal memory to files archive memory. The field of percentage of files archive memory used flashes blue while displaying the percentage of copying progress.
Current state of the archiving: Black – archiving in a group enabled, waiting for the archiving conditions to be met. Red – the archiving conditions have been met and saving the records is in progress. White – archiving in a group disabled.
Percentage of files archive memory used Green background Value in the range 0 ... 70% Orange background 70% of files archive space is full. It is
Red background It is less than 7% of free space in the
1st archiving group 2nd archiving group
recommended to remove unnecessary files via FTP.
files archive memory left. Time to completely use a the files archive space is approximately 14 days at 1 sec. interval. Immediately delete any
unnecessary files via FTP. Percentage of the archive copying progress. Blue flashing background Copying from internal memory to files
archive memory in progress
Page 11
10 User's manual
6.2 Starting work
After switching the supply on, the meter displays the ND30 meter name, version, current software version and MAC for the version with Ethernet and then moves to the measurement mode and last saved page. Displayed information:
ND30 v:1.00 – meter type, program version number Bootloader v.01.05 – bootloader version number U: 57.7/230.0 V – voltage versions I: 1.0/5.0 A – current versions
MAC: AA:BB:CC:DD:EE:FF (for versions with Ethernet)
Fig. 11. Screen of meter measuring mode
7 OPERATING MODES
The ND30 meter has 10 operating modes:
sure – normal work mode. In the Measure mode the values are displayed according to the pages that
Mea
are preset at the factory or configured by the user.
Parameters – meter parameters configuration Alarms – Alarm 1, Alarm 2 configuration Analog output – analog output configuration Display – displayed pages configuration Archiving – archived values configuration Ethernet – Ethernet interface configuration Modbus – RS485 interface parameters configuration Settings – settings: password, language, time, date Information – preview of a program version, serial number, MAC address
To move from the Measure mode to any other mode, press the button for approx. 3 seconds. Buttons allow to select the appropriate mode, to accept press the button
To return to a measurement mode use the button
Exit
Menu
Select
Page 12
11 User's manual
Fig. 12a. Programming matrix
Page 13
12 User's manual
Fig. 12b. Programming matrix
Fig. 12c. Programming matrix
Page 14
13 User's manual
Fig. 12d. Programming matrix
Page 15
14 User's manual
Fig. 12e. Programming matrix
7.1 Measurement mode
In the Measure mo configured by the user in the Display mode.
Changing the page is done by pressing the buttons or . Preview of the maximum or minimum values respectively is done while the button or is
pressed down. Reset of maximum or minimum values is done by pressing the button while viewing their values, i.e. first the button or and then must be pressed.
Simultaneously pressing the button and will copy internal memory to files archive. When reactive power or reactive inductive or capacity energy is displayed, this indication is accompanied by a symbol of the load character: for an inductive load or for a capacity load.
When displaying the active power, the sign "+" is displayed for active energy import or "-" for active energy export. Exceeding of the upper or lower indication range is signaled on the display by ∧∧∧∧ or ∨∨∨∨. For measurement of the averaged values (P DMD, S DMD, I DMD) single measurements are carried out with
0.25 second quantum. Averaging time to choose from: 15, 30 or 60 minutes. Until all samples of the averaged values are acquired, the values are calculated from already measured samples.
Current value in the neutral wire IN is calculated from phase current vectors.
de the values are displayed according to the pages that are preset at the factory or
Max
Max
Min
Max
Del
Del
Min
Min
Page 16
15 User's manual
7.2 Measurement of voltage and current harmonics
The choice of harmonics is done by selecting the pages dedicated to display the values of voltage harmonics U1, U2, U3 and currents I1, I2, I3 simultaneously for 3-phase (page 11). The number of a
displayed harmonics can be changed in the range of 2..51 by the buttons or Page 12 shows a bar chart of the harmonics for each phase: voltage at the top and currents at the bottom of the screen. Page 12 shows a bar chart of the harmonics. The choice of displayed harmonics is done by
pressing a button . The button is used to select the groups of harmonics: harm2 - harm26, harm
- harm52 or harm2 - harm51.
7
2
L1,2,3
+
Fig. 13. Screens 11 and 12 - visualization of harmonics
7.3 Parameters mode
This mode is used to determine the parameters of the meter. To enter Parameters mode press the button fo
Menu
accept press the button . The parameters configuration mode is protected by a password, if it was entered and it is different from zero. The password prompt is skipped for the password 0000. If the
password is incorrect, the message "Wrong password. Read only menu" is displayed. Then it is possible to view the parameters, but the changes are not possible.
r approx. 3 seconds and next using the button or select Parameters mode, to
Select
Fig. 14. Screens while entering a password
Page 17
16 User's manual
If the password is correct or it has not been entered, you can set the values according to Table 2. Buttons are used to choose the parameter, to accept press the button . Then use the
buttons to choose the features of a parameter or set the requested parameter values, i.e. you can choose the digit in the decimal position by the button or the digit value by the button
or . The active position is signaled by the cursor. Set value or parameter can be accepted by
Select
the button or canceled by pressing . Exit from the Parameters procedure follows pressing simultaneously the button or after waiting for approx. 120 seconds. Exit from the Selecting
parameters menu follows pressing the button or after waiting for approx. 120 seconds.
OK
Cancel
Esc
Exit
Measurement
The buttons
Button
Select
Menu button min. 3 sec.
Fig. 15. Screens of Parameters mode
Button Select
- choice of the features OK - acceptance
Cancel - resignation
Page 18
17 User's manual
Table 1
Ite
m
1 Connection wire 3 phase -4 wire
2 Current input range 1A, 5A Input range: 1A or 5A 5A 3 Voltage input range 3x57.7/100 V;
4 Voltage transformer primary 1 .. 1245183 V 100 5 Voltage transformer secondary 0.1 .. 01000.0 100.0 6 Current transformer primary 1…20000 5 7 Current transformer secondary 1…1000 5 8 Damend integ. time 15 min, 30 min, 60
9 AVG synchronization none, with RTC Averaging synchronized with
10 PT100 resist on inp 1 0000.00 11 PT100 resist on inp 2 0000.00 12 Voltage connector 2 U1, U2, U3 U1 13 Voltage connector 5 U1, U2, U3 U2 14 Voltage connector 8 U1, U2, U3 U3 15 Current connector 1-3 I1,-I1,I2,-I2,I3,-I3 I1 16 Current connector 4-6 I1,-I1,I2,-I2,I3,-I3 I2 17 Current connector7-9 I1,-I1,I2,-I2,I3,-I3 I3 18 Delete energy counters No, Active, Reactive,
19 Delete demand values No, Yes No 20 Default parameters No, Yes No
During changing the parameter, it is check if the value is in the range. If the set value falls outside the allowable range, the value is set to the maximum value (when entered value is too high) or minimum value (when it is too low).
Parameter name Feature / value Description Default
settings
3 phase -3 wire 1 phase -2 wire
3x230/400 V;
or 3x110/190 V; 3x400/690 V;
min
Apparent, All
Type of power network
3-phase 4-wire
3-phase 3-wire 1-phase 2-wire
Choice of the ranges
depending on the ordering
code
Averaging time
active power P DMD,
apparent power S DMD,
current I DMD
the real-time clock Resistance value in 0.00 Resistance value in 0.00
3 phase -4
wire
3x230/400 V
or
3x400/690
V
15 min
none
No
Free eCon software can also be used for configuration of the ND30 meters, it is available by request from PCE Instruments.
Page 19
7.4 Alarms mode
18 User's manual
In the options, select the Alarms mode and confirm selection by pressing the button .
Button
Select
The buttons
and Select
Select
The buttons
and Select
Fig. 16. Screens of Alarms mode
Table 2
Ite
m
1
Settings
2 Relay state if alarm on Off/On State of the relay at the alarm 3 Holdback alarm off Off/On Off
4 Display alarm event Off/On When alarm indication function is
Parameter name range Notes/description Default
settings
Logical conditions C1
C1 v C2 v C3
C1 ∧ C2 ∧ C3
(C1 ∧ C2) v C3
(C1 v C2) ∧ C3
switched on Off/On
enabled and the alarm state ends,
alarm symbol is not turned off but
begins to flash.
Signalization symbol flashes until it
is turned off by pressing
the button and
(> 1 sec.). This function refers only
to the alarm signalization, so the
relay contacts will operate without
Del
Alarm
C1
On
Off
Page 20
19 User's manual
a latch according to the selected
alarm type.
Values U1, I1,...,T2, hh:mm Value on the alarm output
parameters acc. to Table 8
6 Condition type n_on, noFF, on,oFF,
H_on,
HoFF, 3non, 3noF, 3_on,
3_oF 7 Low limit condition -144.0…144.0 in % of the rated input value 90.0 8 High limit condition -144.0…144.0 in % of the rated input value 110.0 9 Delay to condition on 0 … 3600 in seconds 0
10 Delay to condition off 0 … 3600 in seconds 0 11
Condition 1
12 Display condition event Off/On When a latch function is enabled
Holdback condition off->on
Condition 2
Condition 3
0 … 3600 in seconds 0
condition symbol is not turned off
Signalization symbol flashes until it
is turned off by pressing the button
Entering "Condition upper value" lower then "Condition lower value" disables a condition.
Acc. to Fig.17. n-on
and the condition state ends,
but begins to flash.
and
AlarmCancel
(> 3 sec.).
U1
Off
Condition state
stan warunku
1 0
Warunek nie
Condition
spełniony
is false
Dolna
Condition
warto
lower
warunku
value
Warunek
spełniony
Condition
Górna
upper
warto c
value
warunku
Condition
is true
wielko mierzona
Measured value
Condition state
1 0
a) n_on b) n
stan warunku
Condition state
1 0
Warunek nie
Condition
spełniony
is false
Condition
Warunek
is true
spełniony
Dolna
Condition
warto
lower
warunku
value
Warunek nie
Condition
spełniony
is false
Górna
Condition
warto c
upper
warunku
value
Measured value
wielko mierzona
1 0
d) oFF
c) on
stan warunku
Condition
Warunek
is true
spełniony
Condition
Dolna
lower
warto
value
warunku
oFF
stan warunku
Condition state
Warunek
Condition
spełniony
is true
Warunek nie
Condition
Dolna
Condition
warto
lower
warunku
value
Condition
warto c
warunku
spełniony
is false
Condition
Warunek nie
Condition
spełniony
is false
Górna
upper
value
Condition
Górna
warto c
upper
warunku
value
wielko mierzona
Measured value
Warunek
spełniony
is true
Measured value
wielko mierzona
Fig. 17. Condition types: a) n_on b) noFF c) on d) OFF
Remaining types of the condition:
H_o
n – always true;
HoFF – always not true,
3non – when the measuring value on any phase exceeds the "Condition upper value" -
condition is true. The condition will be disabled if the measuring value on all phases will be lower than "Condition lower value".
Page 21
20 User's manual
3noF – when the measuring value on any phase will be lower than the "Condition lower value" - condition is true. The condition will be disabled if the measuring value on all phases will be higher than "Condition upper value".
3_on – when the measuring value on any phase will be between the "Condition lower value" and "Condition upper value" - condition is true. The condition will be disabled if the measuring value on all phases will be below "Condition lower value" or above "Condition upper value".
3_oF – when the measuring value on any phase will be below the "Condition lower value" or above "Condition upper value" - condition is true. The condition will be disabled if the measuring value on all phases will be between the "Condition lower value" and "Condition upper value".
The alarm value in the series 3 alarms must be in the range: 01-09, 10-18 and 19-27 (acc. to Table
8). They work with identical thresholds "Condition lower value" and "Condition upper value" for each phase. The blanking of the alarm signalization latch follows pressing the buttons and
Alarm
(> 3 sec.).
Del
7.5 Analog output mode
the options, select the Analog output mode and confirm selection by pressing the button
In
Select
.
Fig.18. Screens of Analog output mode
Table 3
Ite
m
1 Value U1, I1,...,T2, hh:mm Value on analog output
2 Output range 0...20 mA, 4...20 mA, Analog output range 0...20 mA 3 Low limit input -144.0 .. 144.0% Lower value of the input range in %
4 High limit input -144.0 .. 144.0% Upper value of the input range in %
5 Low limit output 00.00 .. 24.00 Lower value of the output range in
6 High limit output 0.01 .. 24.00 Upper value of the output range in
7 Out mode Normal
Parameter name Feature / value Description Default
settings
ΣP
parameter acc. to Table 8
0.0
of the rated range
100.0
of the rated range
0.00
mA
20.00
mA
Continuous output working mode Normal
Low limit output
High limit output
Page 22
21 User's manual
7.6 Display mode
In this mode, you can configure the pages displayed in a normal work mode of the meter Measurement
The buttons
and Select
The buttons
and Select
The buttons
and Select
Fig. 19. Screens of Display mode
It e
m
1
2 Pages color Green
3 Display field 1 No
4
Settings
Page 1
: :
Page 10
Parameter name Range Notes/description Default
Backlight level
Time to Backlight level min
Pages cfg
Display field 1
: :
Display field 8
Minimum, Medium,
Maximum
0 .. 9999
Page 1 Page 2
: Page 11 Page 12
Red
Yellow
:
Olive
Yes
Off U1
I1 P1 Q1
:
En S
in seconds
Selection of pages visualized in
Measurement mode
Color of displayed values in
Measurement mode
Selection of displayed values on a
selected page and selected field
acc. to Table 5.
Table 4
settings
Maximum
0 Page 1 Page 2
:
Page 11 Page 12 Green
No
Table 6a or 6b
or 6c -
depending on
the connection
system
Page 23
22 User's manual
Selection of displayed values: Table 5
Item value name
no value - blanked display field
00
L1 phase voltage
01
L1 phase wire current
02
L1 phase active power
03
L1 phase reactive power
04
L1 phase apparent power
05
L1 phase active power factor
06
(PF1=P1/S1)
07
tgϕ factor of L1 phase (tg1=Q1/P1) L1 phase voltage THD*
08
L1 phase current THD
09
L2 phase voltage
10
L2 phase wire current
11
L2 phase active power
12
L2 phase reactive power
13
L2 phase apparent power
14
L2 phase active power factor
15
2=P2/S2)
(PF
16
tgϕ factor of L2 phase (tg2=Q2/P2) L2 phase voltage THD*
17
L2 phase current THD
18
L3 phase voltage
19
L3 phase wire current
20
L3 phase active power
21
L3 phase reactive power
22
L3 phase apparent power
23
L3 phase active power factor
24
(PF3=P3/S3)
25 26
27 2 29 30 31
tg factor of L3 phase (tg3=Q3/P3)
L3 phase voltage THD* L3 phase current THD mean phase voltage
8
mean 3-phase current 3-phase active power 3-phase reactive power
marking unit Signaling
Off
U1
I1
P1
Q1
S1
(M, k)V
(k)A
(G, M, k)W
M,
(G,
k)var
(G, M,
/
k)VA
PF1
tg1
THD U1
THD I1
U2
I2
P2
Q2
S2
% %
(M,k)V
(k)A
(G, M, k)W
(G, M,
k)var
(G, M,
/
k)VA
PF2
PF
tg2
THD U2
THD I2
U3
I3
P3
Q3
S3
% %
(M,k)V
(k)A
(G, M, k)W
(G, M,
k)var
(G, M,
/
k)VA
PF3
tg3
THD U3
THD I3
U avg
I avg
ΣP
ΣQ
V% A%
(M, k)V
(k)A
(G, M, k)W +/-
(G, M,
k)var
/
3Ph
/
4W
3Ph
/
3W
√ √
x
√ √ √
x x
x
x
x
√ √ √ √
x x
√ √ √
x x x x
x x
x x
x x
√ √ √ √
x x
√ √ √
x x x x
x x
x x
x x
√ √ √ √ √
x x
√ √ √ √
1Ph
/
2W
√ √
x
x x
x
x x
x
Page 24
23 User's manual
32 3-phase apparent power
active power factor
33
3-phase (PF=P/S) tgϕ factor average for 3 phases
34
(tg=Q/P)
35
THD U mean 3-phase*
36
THD I mean 3-phase
37
frequency
38
phase-to-phase voltage L1-L2
39 phase-to-phase voltage L2-L3 40
phase-to-phase voltage L3-L1
41
mean phase-to-phase voltage
42
active power averaged (P Demand)
43
reactive power averaged (S Demand)
44
current averaged (I Demand)
45
neutral wire current
46
Temperature T1 of input 1
47
Temperature T2 of input 2
48
Active 3-phase import energy
49
Active 3-phase export energy
50
Reactive 3-phase inductive energy
ΣS
PF avg
tg avg
THD U
THD I
f
U12
U23
U31
U123
P DMD
S DMD
I DMD
I N
T1
T2
En P+
En P-
En Q
(G, M, k)VA
% %
Hz
(M,k)V
k)V
(M, (M,k)V (M,k)V
(G, M, k)W
(G, M,
k)VA
(k)A (k)A
°C °C
kWh kWh
kvarh
√ √
√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √ √
x x
x
x
x x
x x x x
51
Reactive 3-phase capacity energy
52
3-phase apparent energy
* In the 3-phase 3-wire system (3Ph / 3W) respectively THD U12, THD U23, THD U31, THD U123
Default settings of the displayed pages in 3-phase 4-wire system Table 6a
En Q
En S
kvarh kVAh
√ √
P1 P2 P3 P4 P5
U1 V I1 A U12 V
U2 V I2 A U23 V
U3 V I3 A U31 V
ΣP W
ΣQ var
ΣS VA
f Hz I avg A U123 V PF avg
P1 W PF1 P1 W Q1 var THD U1 %THD I1 %
P2 W PF2 P2 W Q2 var THD U2 %THD I2 %
P3 W PF3 P3 W Q3 var THD U3 %THD I3 %
ΣP W
PF avg
ΣP W ΣQ var
THD U %THD I %
P6 P7 P8 P9 P10
U1 V S1 VA U2 V S2 VA U3 V S3 VA
ΣP W
P DMD W
ΣP W
+En P kWh
I1 A PF1 I2 A PF2 I3 A PF3
ΣQ var
S DMD
W
P1 W tg1 P2 W tg2 P3 W tg3 I avg A I DMD A
ΣQ var
ΣS VA
-En P kWh
En Q
Page 25
24 User's manual
kvarh
Q1 var f Hz Q2 var f Hz Q3 var f Hz I(N) A f Hz En S
kVAh
P11 P12
U1 % I1 % HARM.:U1U2U3 U2 % I2 %
%
bargraf
U3 % I3 % HARM.:I1I2I3 %
HARM.2..51
Pages 11 and 12 cannot be configured.
bargraf
ault settings of the displayed pages in 3-phase 3-wire system Table 6b
Def
P1 P2 P3 P4 P5
U12 V I1 A U12 V
ΣP W ΣP W
P DMD WTHD U12 %THD I1
ΣP W
%
U23 V I2 A U23 V
ΣQ var ΣQ var
S DMD WTHD U23 %THD I2
ΣQ var
%
U31 V I3 A U31 V
ΣS VA
I avg A I DMD A THD U31 %THD I3
ΣS VA
%
En Q
kvarh
En P+ kWh
En P- kWh
En Q
kvarh
f Hz I avg AU123 VPF avg
Default settings of the displayed pages in 1-phase system Table 6c
tg avg
PF avg THD U123 %THD I % En S
P1 P2 P3
U1 V S1 VA P1 W P DMD WP1 W En P+ kWh
I1 A PF1 S1 VA S DMD WQ1 var En P- kWh
P1 W tg1 I1 A I DMD A S1 VA
Q1 var f Hz PF1 f Hz En S
kVAh
En Q kvarh
En Q
kvarh
kVAh
En Q
kvarh
Page 26
7.7 Archiving mode
25 User's manual
In the options, select the Archiving mode and confirm selection by pressing the button .
Select
Fig. 20. Screens of Archiving mode
Table 7
Ite
m
1
2 Parameters U1, I1, P1, ... T1, T2 Archived values (acc. to Table 3 Trigger U1, I1, P1, ... T1, T2, 4 Interval 0 .. 3600 s Archiving period in seconds 0 s
Group 1
5 Archive low -144.0 .. +144.0 Archiving lower limit
6 Archive high -144.0 .. +144.0 Archiving upper limit
7
CSV settings
8 Decimal separator Dot, comma Dot 9
Actions
10 Clear archive No, Yes No
Group 2
Parameter name Range Notes/description Default
settings
Archive type n_on, noFF, on,oFF,
H_on,
HoFF, 3non, 3noF,
3_on, 3_oF
hh:mm
Value separator Comma, Semicolon,
Tabulator
Copy arch. to CSV
No, Yes copying of internal memory to
Archiving type - archiving on
condition acc. to Fig. 21
8)
Value triggering archiving U1
in % of the rated triggering
value
in % of the rated triggering
value
CSV files settings in files
archive
files archive
n_on
0.0%
0.0%
Comma
No
Entering a value "Archive high" lower than "Archive low" or equal switches the registration off. Not
licable for H_on mode.
app
Page 27
26 User's manual
a) n_on
Archiving
Archiwizacja
1 0
disabled
wył czona
c) on
Archiving
Archiwizacja
1 0
disabled
wył czona
Ar_L
Ar_L
wł czona
enabled
Ar_H
Ar_H
wł czona
enabled
wielko wyzwalaj ca
tiggering value tiggering value
disabled
wył czona
tiggering value tiggering value
b) noFF
Archiving
Archiwizacja
1
enabled
wł czona
0
d) oFF
Archiving
Archiwizacja
1
enabled
wł czona
0
Ar_L
wył czona
Ar_L
disabled
Ar_H
Ar_H
disabled
wył czona
wielko
enabled
wł czona
wielko wyzwalaj cawielko wyzwalaj ca
wyzwalaj ca
Fig.21. Archiving types: a) n_on b) noFF c) on d) OFF
aining types of the archiving:
Rem
H_on – always enabled;
HoFF – always disabled,
3non – archiving is enabled when n_on type condition occurs on any phase. It will be switched off
only when all triggering condition are disabled.
3noF – archiving is enabled when noFF type condition occurs on any phase. It will be switched off only when all triggering condition are disabled.
3_on – archiving is enabled when on type condition occurs on any phase. It will be switched off only when all triggering condition are disabled.
3_oF – archiving is enabled when oFF type condition occurs on any phase. It will be switched off only when all triggering condition are disabled.
The value triggering an archiving in the series 3 archiving must be in the range: 01-09 (acc. to Table
8). Archiving works with identical thresholds of the Ar_L and Ar_H hysteresis for each phase.
Selection of the values on the alarm outputs, analog and archived: Table 8
Value of the needed for
Value in
registers
01 02 03 04 05 06 07 08 09 10 11 12 13
Displayed
element
U1
I1
P1
Q1
S1
PF1
tg1
THD U1
THD I1
U2
I2
P2
Q2
Value type
calculations of percentage
corresponding to 100% of
the rated range.
L1 phase voltage Un [V] * L1 phase wire current In [A] * L1 phase active power Un x In x cos(0°) [W] * L1 phase reactive power Un x In x sin(90°) [Var] * L1 phase apparent power Un x In [VA] * L1 phase power factor (PF) 1 tg factorϕ of L1 phase
1 L1 phase voltage THD** 100.00 [%] L1 phase current THD 100.00 [%] L2 phase voltage Un [V] * L2 phase wire current In [A] * L2 phase active power Un x In x cos(0°) [W] * L2 phase reactive power Un x In x sin(90°) [Var] *
Page 28
27 User's manual
3
3
3
3
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
51 52
53
S2
PF2
tg2
THD U2
THD I2
U3
I3
P3
Q3
S3
PF3
tg3
THD U3
THD I3
U avg
I avg
PQS
PF avg
tg avg
THD U
THD I
f U12 U23 U31
U123 P DMD S DMD
I DMD
I N T1 T2
En P+
En P- Active 3-phase export energy
En Q
En Q
En S
Phase sequence
L2 phase apparent power Un x In [VA] * L2 phase active power factor PF 1 tgϕ factor of L2 phase L2 phase voltage THD** 100.00 [%] L2 phase current THD 100.00 [%] L3 phase voltage Un [V] * L3 phase wire current In [A] * L3 phase active power Un x In x cos(0°) [W] * L3 phase reactive power Un x In x sin(90°) [Var] * L3 phase apparent power Un x In [VA] * L3 phase active power factor PF 1 tgϕ factor of L3 phase L3 phase voltage THD** 100.00 [%] L3 phase current THD 100.00 [%] mean phase voltage 0.00 [%] mean 3-phase current In [A] * 3-phase active power (P1+P2+P3) 3 x Un x In x cos(0°) [W] * 3-phase reactive power (Q1+Q2+Q3) 3 x Un x In x sin(90°) [Var] * 3-phase apparent power (S1+S2+S3) 3x Un x In [VA] * 3-phase power factor (PF) 1 tg factorϕ for 3 phases 3-phase voltage THD** 100.00 [%] 3-phase current THD 100.00 [%] frequency 100 [Hz] phase-to-phase voltage L1-L2 phase-to-phase voltage L2-L3 phase-to-phase voltage L3-L1 mean phase-to-phase voltage active power averaged (P Demand)* 3 x Un x In x cos(0°) [W] * reactive power averaged (S Demand )* 3 x Un x In [VA] * current averaged (I Demand) * In [A] * neutral wire current In [A] * Temperature T1 of input 1 Temperature T2 of input 2
Active 3-phase import energy
Reactive 3-phase inductive energy
Reactive 3-phase capacity energy
3-phase apparent energy Phase sequence
1
1
1
Un [V] * Un [V] * Un [V] * Un [V] *
400 [°C]
400 [°C] 100,000 [kWh] 100,000 [kWh]
100,000 [kvarh] 100,000 [kvarh]
100,000 [kVAh]
L1, L2, L3 - 0.00 [%]
L1, L3, L2 - 100.00 [%]
54
hh:mm
time, hhx100+mm 2,400 - 100 [%]
*Un, In - rated values of rated voltages and currents
** In the 3-phase 3-wire (3Ph / 3W) respectively THD U12, THD U23, THD U31 THD U123
To register in each group, you can select 16 of 53 parameters (bits 1 to 53 of the registers 4106...4109 and
5...4118). Bit set to "1" adds a parameter to a registration, set to "0" deletes. It is possible to set all 53
411 bits but only the first 16 bits set to "1" will be taken for a registration.
Page 29
7.8 Ethernet mode
28 User's manual
In the options, select the Ethernet mode and confirm your choice by pressing the button .
Select
Fig.22. Screens of Ethernet mode
It
e
m
1
2 Mode Auto, 10 Mb/s, 100
Address
3 Address IP 4 Subnet Mask 5 Gateway 6 DNS address
7 MAC address Aa:bb:cc:00:21:01 -
8
9 Port 80 … 32,000 1 1 0
11 Waiting Time 10 .. 360 60s
1 2 1 3 1 4
es
Modbus
TCP
FTP
WWW Port
Parameter name range Notes/description Manufactur
er’s value
DHCP
0.0.0.0...255.255.255.255
0.0.0.0...255.255.255.255
0.0.0.0...255.255.255.255
0.0.0.0...255.255.255.255
Address 1 .. 247 1
Max. connection
limit
Command port
Data port
Off/On
Mb/s
1 … 4 1
20 .. 32000 21 20 .. 32000 1025 80 .. 32000 80
Enabling / disabling the DHCP
Client (supports automatic obtaining
of IP protocol parameters of the
meter's Ethernet interface from
external DHCP servers in the same
LAN)
10.0.1.161
55.0.0.1 -
2
0.0.0.0 ­entered
10.0.0.44 -
DHCP or
Obtained from
DHCP is
disabled
manually when
Auto
Table 9
Off
-
Page 30
7.9 Modbus mode
29 User's manual
In the options, select the Modbus mode and confirm your choice by pressing the button .
Select
Fig.23. Screens of Modbus mode
Ite
m
1 Address 1…247 Modbus Network Address
2 Baud rate 4800 b/s, 9600 b/s,
3 Mode RTU 8N2, RTU 8N1,
4 Set Defaults 42xx registers No, Yes Programmable group of registers for
Parameter name
Feature / value Description Manufact
Baud rate 9600 b/s
19.2 kb/s, 38.4 kb/s,
57.7 kb/s, 115.2 kb/s Transmission mode RTU 8N2
RTU 8O1, RTU 8N1
readout
Table 10
urer’s
value
1
No
7.10 Settings mode
In the options, select the Set
Ite
m
Parameter name
tings mode and confirm your choice by pressing the button .
Select
Fig.24. Screens of Settings mode
Table 11
Feature / value Description Manufact
urer’s
value
Page 31
30 User's manual
1 Password 0 .. 9999 0 - disabled 0 2 Language English, Polski,
Deutsch
3 Time hh:mm hour:minute 00:00:00 4 Date dd/mm/yyyy Day/month/year 1.01.2015 5 Set defaults No, Yes No
Polish
7.11 Information mode
In the options, select the Inf
ormation mode and confirm your choice by pressing the button .
Select
Fig.25. Screens of Information mode
Table 12
Ite
m
Parameter name
1 Type Meter type 2 Order code Fir 3 Boot version Bootloader version e.g. 1.04
4 Program version Main program version of the meter e.g. 0.60 5 Serial number ddmmxxxx Current serial number of the meter
MAC address xx:xx:xx:xx:xx:xx 48-bit hardware address of Ethernet
Feature / value Description Manufacturer’s
value
ND30
st 5 digits of the ordering code e.g. 12200
e.g. 15070006
day month current number
e.g.
interface in hexadecimal format
64:0E:0D:0C:0B:0A
8 MEASURING VALUES ARCHIVING
8.1 INTERNAL MEMORY
The ND30 meters are equipped with 4MB of internal memory and 8GB memory for storing the recorded data. 4MB internal memory allows to register 40,960 records. The memory is a ring buffer type one.
8.2 COPYING ARCHIVE
If the 4MB internal memory is full at 70% or forced at any time: in Arc "Copy the archive to a CSV file" parameter to "Yes". The recorded data will be copied to the files archive. To start the procedure of copying archive can also be done via the RS485 interface (register 4125) or by
simultaneously pressing the button and .
Max
Min
hiving mode, select Actions and set
Page 32
31 User's manual
Example: files archive with archiving period of 5 seconds allows you to register data for 2 years. If the files archive is full at 70% - archive used in % will become orange (see: Status 3 Register – address 7561).
When the files archive is full (less then 14 days at 1 sec. interval to completely use a the files archive space) the color will change to flashing red.
The ND30 meter creates the directories and the files the files archive while the internal memory is being copied. An example of the directory structure is shown in Figure 26.
Fig.26. Directory structure in the files archive
a in the files archive is stored in the files in the directories (year, month archive copy) - see Fig.
Dat
26. The file names are marked by day and time of the first record and have the ddhhmmss.csv format, where: dd-day, hh-hour, mm-minute, ss-second.
8.3 ARCHIVE FILES STRUCTURE
The archived data files are in the form of the columns, where each column of data is separated by
mma. A column description is in the first line of the file. Data records are sequentially
a co arranged in the rows. An example of the file is shown in Figure 27.
Fig.27. An example of the archive data file
The fields in the line describing the record have the following meanings:
date – date of data recording, date separator is the character "-"time – hour, minute, second of recorded data, a time separator is the character ":"record index – unique index record. Each record has a unique number. This number increases
Page 33
32 User's manual
when writing new records.
block – reservedregister1 – Modbus register address of the first archived valuename1 – Modbus register description of the first archived valuevalue1 – first archived value. The decimal separator is ".", the values are saved in a
engineering notation format.
 :
register16 – Modbus register address of the sixteenth archived value name16 – Modbus register description of the sixteenth archived valuevalue16 – sixteenth archived value. The decimal separator is ".", the values are saved in a
ineering notation format.
eng
name1, ...,name16 – description according to Table 8 (Displayed parameter).
8.4 DOWNLOADING ARCHIVE
Archived data can be downloaded via Ethernet using FTP protocol.
9 SERIAL INTERFACES
9.1 RS485 INTERFACE – list of parameters
The implemented protocol is compliant with the PI-MBUS-300 Rev G specification of Modicon. List of ND30 meter serial interface parameters:
identifier 0xD9
meter address 1..247,
baud rate 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbit/s
operating mode Modbus RTU
transmission mode 8N2, 8E1, 8O1, 8N1
max. response time 600 ms
max. no. of registers read in a single query
- 61 – for 4-byte registers
- 122 – for 2-byte registers
implemented functions - 03, 04, 06, 16, 17
- 03, 04 register readout
- 06 single register writing
- 16 writing of n-registers,
- 17 device identification
Default settings: address 1, baud rate 9.6 kbit/s, mode RTU 8N2
9.2 Examples of registers' readout and write
Readout of n-registers (code 03h)
mple 1. Readout of two 16-bit integer registers, starting with the register address 0FA0h (4000) -
Exa
register values 10, 100. Request:
Device address Register address Number of registers CRC
Page 34
33 User's manual
Function checksum
B1 B0 B1 B0
01 03 0F A0 00 02 C7 3D
Response:
Device
address Function
Number of
bytes
Value from the register
0FA0 (4000)
Value from the register
0FA1 (4001)
B1 B0 B1 B
CRC
checksum
0
01 03 04 00 0A 00 64 E4 6F
Example 2. Readout of two 32-bit float registers as a combination of two 16-bit registers, starting with the register address 1B58h (7000) - register values 10, 100.
Request:
Device address
Function
Register address Number of registers CRC
B1 B0 B1 B0
checksum
01 03 1B 58 00 04 C3 3E
Response:
Device
address Function
Number of
bytes
Value from the
register
1B58 (7000)
Value from the
register
1B59 (7001)
Value from
the register
1B5A (7002)
Value from
the register
1B5B (7003)
CRC
checksum
B3 B2 B1 B0 B3 B2 B1 B0
01 0
3 08 41 20 00 00 42 C8 00 00 E4 6F
Example 3. Readout of two 32-bit float registers as a combination of two 16-bit registers, starting with the register address 1770h (6000) - register values 10, 100.
Request:
Device
address Function
Register address Number of registers
B1 B0 B1 B0
CRC
checksum
01 03 17 70 00 04 4066
Response:
Device
address Function
01 0
3 08 00 00 41 20 00 00 42 C8 E4 6F
Number of
bytes
Value from the
register
1770h (6000)
Value from the
register
1770h (6000)
Value from
the register
1772h (6002)
Value from
the register
1772h (6002)
B1 B0 B3 B2 B1 B0 B3 B2
CRC
checksum
Page 35
34 User's manual
Example 4. Readout of two 32-bit float registers, starting with the register address 1D4Ch (7500) - register values 10, 100.
Request:
Device address
Function
Register address Number of registers CRC
B1 B0 B1 B
0
01 03 1D 4C 00 02 03 B0
Response:
Device
address Function
Number of
bytes
Value from the register
1D4C (7500)
Value from the register
1D4D (7501)
B3 B2 B1 B0 B3 B2 B1 B0
01 03 08 41 20 00 00 42 C8 00 00 E4 6F
Single register writing (code 06h) Example 5. Writing the value 543 (0x021F) to the register 4000 (0x0FA0)
Request:
Device address
Function
Register address Register value CRC
B1 B0 B1 B
0
01 06 0F A0 02 1F CA 54
checksum
CRC
checksum
checksum
Response:
Device address
Function
Register address Register value CRC
B1 B0 B1 B0
01 06 0F A0 02 1F CA 54
Writing to n-registers (code 10h) Example 6. Writing two registers starting with the register address 0FA3h (4003)
Writing the values 20, 2000. Request:
Device
address Function
01 1
Addres
reg.Hi
Addre
s
reg.Lo
ss
No. of
regist
ers Hi
No. of
regist
ers
Lo
Numb
er of
bytes
Value for the
register 0FA3
(4003)
Value for the
register 0FA4
B1 B0 B1 B0
0 0F A3 00 02 04 00 14 07 D0 BB 9A
checksum
CRC
checksum
(4004)
Page 36
Response:
35 User's manual
Device address
Function
Register address Number of registers CRC
B1 B0 B1 B0
01 10 0F A3 00 02 B2 FE
Device identification report (code 11h) Example 7. Device identification
Request:
Device address Function Checksum
01 11 C0 2C
Response:
Addre
Function Numbe
ss
bytes
01 11 19 CF FF 4E 34 33 20 2D 31 2E 30 30 20 20 20 20 20 20 20 62 2D
IdentifierDevice
r
of
status
Information field of the device software version (e.g.
"ND30-1.00 b-1.06” - ND30 device with software
version 1.00 and bootloader version 1.06)
31 2E 30 36 20
checksum
Checksu m (CRC)
E0 24
9.3 Ethernet interface 10/100-BASE-T
The ND30 meters version ND30-XX2XXXX are equipped with an Ethernet interface for connecting the meter (using the RJ45 socket) to the local or global network (LAN or WAN). The Ethernet interface allows to use the web services implemented in the meter: web server, FTP server, Modbus TCP/IP. Configure Ethernet group parameters to use the meter's network services. The standard Ethernet parameters of the meter are shown in Table 9. The main parameter is the IP address of the meter, e.g.
.0.1.161, which must be unique in a network the device will be connected to. The IP address can be
10 assigned to the meter automatically by the DHCP server present in the network if the meter has an option to obtain an address from DHCP server enabled: Ethernet Addresses DHCP On If the DHCP service is disabled then the meter will work with the default IP address allowing the user to change the IP address, e.g. from the menu of the meter. Change of the Ethernet parameters can also be done via the RS485 interface. So it is required to confirm the changes by writing the value "1" to the register 4149. The Ethernet interface is rebooted in accordance with the new parameters after applying changes - all services of the Ethernet interface are restarted.
9.3.1 Connecting 10/100-BASE-T interface
Connect the device to a TCP/IP network using the RJ45 socke of the meter to get access to the Ethernet services.
The meter's RJ45 socket LEDs description:
yellow LED
- illuminates when the meter is properly connected to the Ethernet 100 Base-T, does not
t located at the back / terminal side /
Page 37
36 User's manual
illuminate when the meter is not connected to a network or is connected to a 10-Base-T.
green LED - Tx/Rx, illuminates (irregularly illuminates) when the meter sends and receives data, illuminates continuously when no data is transmitted
It is recommended to use a twisted pair cable to connect the meter to the network:
U/FTP – twisted pair cable with a separate foil for every pair
F/FTP – twisted pair cable with separate foil for every pair and additional foil shielding for the cable
S/FTP (former SFTP) – twisted pair cable with separate foil for every pair and additional mesh cable
shielding
SF/FTP (former S-STP) – twisted pair cable with separate foil for every pair and additional mesh and foil cable shielding
The twisted pair cable categories according to the European standard EN 50173 are minimum:
Class D (category 5) - for high-speed local area networks, includes the applications using the frequency band up to 100 MHz. For Ethernet connection use the category 5 STP type twisted-pair cable (shielded) with RJ-45 connector, wiring colors (according to Table 11), compliant to the following standards:
EIA/TIA 568A for both connectors in strike-through connection (i.e. between ND30 and hub or switch)
EIA/TIA 568A for the first connector and EIA/TIA 568B for the second one in the cross-over connection (i.e. when connecting the ND30 meter to the computer).
Table 13
Wire no. Signal Wire color according to the standard
EIA/TIA 568A EIA/TIA 568B 1 TX+ white-green white-orange 2 TX- green orange 3 RX+ white-orange white-green 4 EPWR+ blue blue 5 EPWR+ white-blue white-blue 6 RX- orange green 7 EPWR- white-brown white-brown 8 EPWR- brown brown
Fig. 28. View and pin numbering of the RJ45 socket
9.3.2 Web Server
ND30 meter provides its own web server which enables remote monitoring of the measuring
The
values and reading a status of the meter. A web page allows in particular to:
obtain information about the device (serial number, code execution, software version, bootloader version, version (standard or special),
preview current measuring values, read a device status,
select the web page language
Page 38
37 User's manual
Access to the server can be achieved by entering the IP address of the meter in the web browser, for example: http://192.168.1.030 (where 192.168.1.030 is set address of the meter). The default web server port is the port "80". The server port can be changed by the user.
Note: A browser with JavaScript enabled and compatible with XHTML 1.0 is required for correct operation of the website (all popular browsers, Internet Explorer version 8 minimum).
9.3.2.1 General view
Fig. 29. View of the meter website
9.3.2.2 Web user selection
The meter has two user accounts for the web server protected by the individual passwords:
user:
user: "user”, password: "pass” - access only to the preview of the parameters.
Calling the IP address of the meeter in a browser, e.g. http://192.168.1.30 will display a start website to enter a user name and a password.
"admin”, password: "admin” - access to the configuration and preview of the parameters
Page 39
38 User's manual
Fig. 30. View of the meter's web server login window
server user name can not be changed. You can change the password for each user - for safety
Web reasons it is recommended to change the passwords. Changing the password is possible only through a web page in the "Ethernet" parameter group. The passwords can be up to 8 characters. If the password is lost (what disables using the web server), restore the default settings of the Ethernet interface e.g. from the menu: Settings Default settings Yes or entering the value "1" to the register 4152. All standard meter parameters and Ethernet interface parameters (see Table 9) and the passwords of the web server users will be restored:
user "admin password: "admin”; user "user password "pass”.
9.3.3 FTP Server
FTP file sharing protocol has been implemented in the ND30 meters. The meter acts as a
The server, allowing the users to access the internal memory of its file system. Access to the files is possible using a computer, a tablet with installed FTP client or other device acting as a FTP client. The standard FTP ports are used for transferring files, "1025" - data port and "21" -- commands port. A user can change the port used by the FTP protocol if necessary. Please note, that the port configuration of the FTP server and the client must be the same.
The FTP client program can work in a passive mode. The connection is fully made by the FTP client in the passive mode (a client chooses the data port). It is possible to use up to one connection at the same time
for the file transfer with the meter, so you should limit the maximum number of a FTP client connections to 1.
Page 40
39 User's manual
9.3.3.1 FTP user selection
The meter has two user accounts for the FTP server protected by the individual passwords:
user: "admin”, password: "admin” - access to read and write the files
user: "user”, password: "passftp” - access to read only the archive files.
The FTP user names can not be changed but you can change the password for each user - for safety reasons it is recommended to change the passwords. Changing the password is possible only through a web page in the "Ethernet" parameter group. The passwords can be up to 8 characters. If the password is lost (what disables using the FTP server), restore the default settings of the Ethernet interface e.g. from the menu: Settings
Default settings Yes or entering the value "1" to the register 4152. All
standard meter parameters and Ethernet interface parameters (see Table 9) and the passwords of the FTP server users will be restored:
user "admin password: "admin”; user "user password "passftp”.
The program FileZilla could be an example of the FTP client. You can view and download the archive files by entering the IP address of the meter in the address field.
Page 41
40 User's manual
Fig. 31. View of the FTP session in the program FileZilla
Page 42
41 User's manual
9.3.4 Modbus TCP/IP
The ND30 meter allows access to the internal registers via the Ethernet interface and Modbus TCP/IP protocol. It is necessary to set the unique IP address of the meter and set the connection parameters listed in Table 14 to set up a connection.
Table 14
Register Description Default value
4146 4147
145
4 4144
The device address is the address of the device for Modbus TCP/IP protocol and is not a value equal to a address value for Modbus RS485 protocol (Modbus network address register 4100). Setting the parameter "Device address for Modbus TCP/IP protocol" of the meter to the value "255", the meter will skip the address analysis in the frame of Modbus protocol (broadcast mode).
Device address for Modbus TCP/IP protocol 1 Modbus TCP port number 502 Port closing time of Modbus TCP/IP service [s] 60 The maximum simultaneous connections to Modbus TCP/IP service 4
10 MAP OF ND30 METER REGISTERS
In the ND30 meter, data are placed in 16 and 32-bit registers. Process variables and meter parameters are placed in the address area of registers in a way depended on the variable value type. Bits in 16-bit register are numbered from the youngest to the oldest (b0­b15). The 32-bit registers contain numbers of float type in IEEE-754 standard. 3210 byte sequence - the oldest is sent first.
ble 15
Ta
Address range Value type Description
Value set in the 16-bit register. Registers for meter configuration. Description of registers is shown in Table 16. Registers for writing and readout. Value set in the 16-bit register. Registers for configuration of programmable group of registers for readout. Description of registers is shown in Table 15. Registers for writing and readout. Value set in the 16-bit register. Registers for displayed pages configuration. Description of registers is shown in Table 19. Registers for writing and readout. Value set in the 16-bit register. Status registers, energy value, MAC address of the meter, configuration data. Description of registers is shown in Table
20. Readout registers. Value is set in the two following 16-bit registers. Registers contain exactly the same data, as 32-bit registers of 7500 – 7953 range. Readout registers. Bytes sequence (1-0-3-2) Content of the registers set in the registers 4200 – 4359. Bytes sequence (3-2-1-0)
Content of the registers set in the registers 4200 – 4359. Bytes sequence (1-0-3-2)
Content of the registers set in the registers 4200 – 4359. Values set in one 32-bit register.
Values set in one 32-bit register. Description of registers is shown in Table
21. Readout registers. Value is set in the two following 16-bit registers. Registers contain exactly
the same data, as 32-bit registers of 7500 – 7953 range. Readout registers. Bytes sequence (3-2-1-0)
4000 – 4159
4200 – 4260
4300 - 4385
4400- 4440
6000 – 6922
7000 - 7118
7200 – 7318
7400 - 7459
7500 – 7961
8000 - 8922
Integer
(16 bits)
Integer
(16 bits)
Integer
(16 bits)
Integer
(16 bits)
Float
(2x16 bits)
Float
(2x16 bits)
Float
(2x16 bits)
Float
(32 bits)
Float
(32 bits)
Float
(2x16 bits)
Page 43
42 User's manual
Table 16
Register
address
4000 RW 0…9999 Protection - password 0
4001 RW 0 .. 1
4002 RW 0 .. 2
4003 RW 0 .. 2
4004 RW 0 .. 2
4005 RW 0..5
4006 RW 0..5
400
4008 RW 0,1 Input current range: 1 A or 5 A: 0 - 1 A, 1 - 5 A 1 4009 RW 0,1 4010 RW 0..18 Transformer primary voltage, two older bytes 0
4011 RW 0..65535 Transformer primary voltage, two younger bytes 100 4012 RW 1 .. 10000 Transformer secondary voltage x 10 1000 4013 RW 1 .. 20000 Transformer primary current 5 4014 RW 1 .. 1000 Transformer secondary current 5
4015 RW 0…2
4016 RW 0.1 4017 RW reserved
4018 RW reserved 4019 RW reserved
Operati
ons
Range Description
7 RW 0..5
Type of connection
0 - 3Ph/4W 1 - 3Ph/3W 2 - 1Ph/2W
Voltage on terminal 2
0 - first L1 phase voltage
1 - second L2 phase voltage
2 - third L3 phase voltage
Voltage on terminal 5
0 - first L1 phase voltage
1 - second L2 phase voltage
2 - third L3 phase voltage
Voltage on terminal 8
0 - first L1 phase voltage
1 - second L2 phase voltage
2 - third L3 phase voltage Current on terminals 1, 3:
0 - first phase IL1 current
reversed direction of the current of phase L1: -I
1 -
2 - second phase IL2 current
3 - reversed direction of the current of phase L2: -I
4 - third phase IL3 current
5 - reversed direction of the current of phase L3: -I
Current on terminals 4, 6:
0 - first phase IL1 current
1 - reversed direction of the current of phase L1: -I
2 - second phase IL2 current
3 - reversed direction of the current of phase L2: -I
4 - third phase IL3 current
reversed direction of the current of phase L3: -I
5 -
Current on terminals 7, 9:
0 - first phase IL1 current
reversed direction of the current of phase L1: -I
1 -
2 - second phase IL2 current
3 - reversed direction of the current of phase L2: -I
4 - third phase IL3 current
5 - reversed direction of the current of phase L3: -I
Input voltage range:
0 – 3 x 57.7/100 V; 1 – 3 x 230/400 V (version 1)
0 – 3 x 110/190 V; 1 – 3 x 400/690 V (version 2)
Averaging time of the active power P Demand
apparent power S Demand
current I Demand
0 – 15, 1- 30, 2- 60 minutes
Synchronizationwith real-time clock
0 - no synchronization
1 - synchronization with a clock
L1
L2
L3
L1
L2
L3
L1
L2
L3
Defau
lt
0
0
1
2
0
2
4
1
0
1
Page 44
43 User's manual
4020 RW Resistance of wires for the input T1 x 100 0 4021 RW Resistance of wires for the input T2 x 100 0 4022 RW reserved 4023 RW reserved
Energy counters erasing
4024 RW 0…4
4025 RW 0.1 4026 RW 0.1 Min, max erasing 0
4027 RW 4028 RW reserved 4029 RW reserved
4030 RW
4031 RW
4032 RW 4033 RW
4034 RW 0.1..43
4035 RW 0..9
4036 RW
4037 RW 4038 RW 0..3600 s Alarm output 1 - condition 1 activation delay 0
4039 RW 0..3600 s Alarm output 1 - condition 1 deactivation delay 0 4040 RW 0..3600 s Alarm output 1 - condition 1 re-activation lock 0
4041 RW 4042 RW reserved
4043 RW 0.1..43
4044 RW 0..9
4045 RW
4046 RW 4047 RW 0..3600 s Alarm output 1 - condition 2 activation delay 0
4048 RW 0..3600 s Alarm output 1 - condition 2 deactivation delay 0 4049 RW 0..3600 s Alarm output 1 - condition 2 re-activation lock 0
4050 RW 4051 RW reserved
4052 RW 0.1..43
4053 RW 0..9
0.1
0…4
0,1
0,1 0,1
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
0,1
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
0,1
2 – erase reactive energies, 3 – erase apparent energies, 4 –
Alarm output 1 - State of the relay at the alarm switched on: 0 -
Alarm output 1 - type for the condition 1: 0 – n_on, 1 – noFF,
2 – on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
rm output 1 - lower value of the condition 1 switch of the rated
Ala
Alarm output 1 - upper value of the condition 1 switch of the rated
Alarm output 1 - type for the condition 2: 0 – n_on, 1 – noFF,
2 – on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
Alarm output 1 - lower value of the condition 2 switch of the rated
Alarm output 1 - upper value of the condition 2 switch of the rated
Alarm output 1 - type for the condition 3: 0 – n_on, 1 – noFF, 2– on,
3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF, 8 – 3_on, 9– 3_oF
0 – no changes, 1 – erase active energies
erase all energies
Erasing averaged parameters
P Demand, S Demand, I Demand
Erasing alarm signalization latch 0
Alarm output 1 - Logic tasks of the conditions 1, 2, 3
0 – C1
1 – C1 v C2 v C3
2 – C1 ∧ C2 ∧ C
3 – C1 ∧ C2 v C3
4 – (C1 v C2 ∧ C3
relay disabled
1 - relay enabled
Alarm output 1 - alarm deactivation lock 0
Alarm output 1 - alarm signalization 0
Alarm output 1 - value for the condition 1 (c1)
(code as in Table 8)
8 – 3_on, 9 – 3_oF
input range
input range
Alarm output 1 - condition 1 signalization 0
Alarm output 1 - value for the condition 2 (c2)
(code as in Table 8)
8 – 3_on, 9 – 3_oF
input range
input range
Alarm output 1– condition 2 signalization 0
Alarm output 1 - value for the condition 3 (c3)
(code as in Table 8)
3
38
900
1100
38
900
1100
38
0
0
0
1
0
0
0
Page 45
44 User's manual
4054 RW
4055 RW 4056 RW 0..3600 s Alarm output 1 - condition 3 activation delay 0
4057 RW 0..3600 s Alarm output 1 - condition 3 deactivation delay 0 4058 RW 0..3600 s Alarm output 1 - condition 2 re-activation lock 0
4059 RW 4060 RW reserved
4061 RW
4062 RW
4063 RW 4064 RW
4065 RW 0.1..43
4066 RW 0..9
4067 RW
4068 RW 4069 RW 0..3600 s Alarm output 2 - condition 1 activation delay 0
4070 RW 0..3600 s Alarm output 2 - condition 1 deactivation delay 0 4071 RW 0..3600 s Alarm output 2 - condition 1 re-activation lock 0
4072 RW
3 RW reserved
407 4074 RW 0.1..43
4075 RW 0..9
4076 RW
4077 RW 4078 RW 0..3600 s Alarm output 2 - condition 2 activation delay 0
4079 RW 0..3600 s Alarm output 2 - condition 2 deactivation delay 0 4080 RW 0..3600 s Alarm output 2 - condition 2 re-activation lock 0
4081 RW 4082 RW reserved
4083 RW 0.1..43
4084 RW 0..9
4085 RW
4086 RW
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
0,1
0…4
0,1
0,1 0,1
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
0,1
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
0,1
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
Alarm output 1 - lower value of the condition 3 switch of the rated
input range
Alarm output 1 - upper value of the condition 3 switch of the rated
input range
Alarm output 1– condition 2 signalization 0
Alarm output 2 - Logic tasks of the conditions 1, 2, 3
0 – C1
1 – C1 v C2 v C3
2 – C1 ∧ C2 ∧ C3
– C1 ∧ C2 v C3
3
4 – (C1 v C2 ∧ C3
Alarm output 2 - State of the relay at the alarm switched on: 0 -
relay disabled
1 - relay enabled
Alarm output 2 - alarm deactivation lock 0
Alarm output 2 - alarm signalization 0
Alarm output 2 - value for the condition 1 (c1)
(code as in Table 8)
Alarm output 2 - type for the condition 1: 0 – n_on, 1 – noFF,
2 – on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8 – 3_on, 9 – 3_oF
Alarm output 2 - lower value of the condition 1 switch of the rated
input range
Alarm output 2 - upper value of the condition 1 switch of the rated
input range
Alarm output 2condition 1 signalization
Alarm output 2 - value for the condition 2 (c2)
(code as in Table 8)
Alarm output 2 - type for the condition 2: 0 – n_on, 1 – noFF,
2 – on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8 – 3_on, 9 – 3_oF
Alarm output 2 - lower value of the condition 2 switch of the rated
input range
Alarm output 2 - upper value of the condition 2 switch of the rated
input range
Alarm output 2condition 2 signalization
Alarm output 2 - value for the condition 3 (c3)
(code as in Table 8)
Alarm output 2 - type for the condition 3: 0 – n_on, 1 – noFF,
2 – on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8 – 3_on, 9 – 3_oF
rm output 2 - lower value of the condition 3 switch of the rated
Ala
input range
Alarm output 2 - upper value of the condition 3 switch of the rated
input range
900
1100
900
1100
900
1100
900
1100
0
1
38
0
0
38
0
0
38
0
Page 46
45 User's manual
4087 RW 0..3600 s Alarm output 2 - condition 3 activation delay 0 4088 RW 0..3600 s Alarm output 2 - condition 3 deactivation delay 0 4089 RW 0..3600 s Alarm output 2 - condition 2 re-activation lock 0
4090 RW
0,1
4091 RW reserved 4092 RW 0.1..43
4093 RW 0..1
Continuous output 1 - type: 0 – (0...20) mA; 1 – (4…20) mA;
Alarm output 2 - condition 2 signalization 0
Continuous output 1 - output value
/code as in Tab. 8/
38
0 4094 RW 4095 RW
-1440..0..1440 [o/oo]
-1440..0..1440 [o/oo]
4096 RW -2400..0..2400 4097 RW 1..2400
Continuous output 1 - lower value of the input range in [o/oo] of the
rated input range
tinuous output 1 - upper value of the input range in [o/oo] of the
Con
rated input range
Continuous output 1 - lower value of the current output range (1 =
10 uA)
Continuous output 1 - upper value of the current output range (1 =
10uA)
1000
2000
Continuous output 1 - manual switching on
4098 RW 0..2
0 – normal work, 1 – value set from the register 4096,
2 – value set from the register 4097 4099 RW reserved 4100 RW 1..247 Modbus Network Address 1
4101 RW 0..3 4102 RW 0..5
Transmission mode: 0->8n2, 1->8e1, 2->8o1,
3->8n1
Baud rate: 0->4800, 1->9600
2->19200, 3->38400, 4->57600, 5->115200 4103 RW reserved 4104 RW 0.1 Upgrade change of transmission parameters 0 4105 RW reserved
4106 RW 0...0xFFFF 4107 RW 0...0xFFFF 4108 RW 0...0xFFFF 4109 RW 0...0x003F
Group 1, archived values bit0 – reserved, bit1- U_1, bit2- I_1, ... ,
bit15- PF2, acc. to Table 8
Group 1, archived values bit16 – tg2,
bit17-THDU2, ... , bit31– ΣQ, acc. to Table 8
Group 1, archived values bit32- ΣS,
bit33- PF avg, ... , bit43 – T2, acc. to Table 8
Group 1, archived values bit48 EnP+,...,bit53-Phase sequence
acc. to Table 8
4110 RW 0…48 Group 1, value triggering archiving
0x00
00
0x00
00
0x00
00
0x00
00
0x00
00
Group 1, archiving type 0 – n_on, 1 – noFF, 2 – on,
4111 RW 0..9
3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8 – 3_on, 9 – 3_oF
4112 RW
3 RW
411
-1440..0..1440
-1440..0..1440
Group 1, archiving lower limit w o/
Group 1, archiving upper limit w o/
oo
oo
900
1100
4114 RW 1 .. 3600 Group 1, archiving period in seconds 1 4115 RW 0...0xFFFF
4116 RW 0...0xFFFF 4117 RW 0...0xFFFF 4118 RW 0...0x003F
Group 2, archived values bit0 – reserved, bit1- U_1, bit2- I_1, ... ,
bit15- PF2, acc. to Table 8
Group 2, archived values bit16 – tg2,
bit17-THDU2, ... , bit31– ΣQ, acc. to Table 8
Group 2, archived values bit32- ΣS,
bit33- PF avg, ... , bit43 – T2, acc. to Table 8
Group 2, archived values bit48 EnP+,...,bit53-Phase sequence
acc. to Table 8
4119 RW 0…48 Group 2, value triggering archiving
up 2, archiving type 0 – n_on, 1 – noFF, 2 – on,
Gro
20 RW 0..9
41
3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
0x00
00
0x00
00
0x00
00
0x00
00
0x00
00
8 – 3_on, 9 – 3_oF
4121 RW
-1440..0..1440
Group 2, archiving lower limit w o/
oo
900
0
0
0
0 1
0
0
Page 47
46 User's manual
4122 RW 4123 RW 1 .. 3600 Group 2, archiving period in seconds 1
4124 RW reserved 4125 RW 0,1 4126 RW 0,1 Deleting the entire internal archive 0
4127 RW 0 .. 2 Field separator: 0 - comma , 1 - semicolon ; 2 - tab ' ' , 4128 RW 4129 RW reserved 4130 RW reserved
4131 RW 0…65535
4132 RW 0…65535
4133 RW 0…65535 4134 RW 0…65535 4135 RW 0…65535 4136 RW 0…65535 4137 RW 0…65535 4138 RW 0…65535
4139 RW reserved
4140 RW
4141 RW 0 .. 2
4142 RW 20…65535 FTP server commands port number 21 4143 RW 20…65535 FTP server data port number 1025
4144 RW 1…4 4145 RW 10…600 Port closing time of Modbus TCP/IP service, in seconds 60
4146 RW 0…255 Device address for Modbus TCP/IP protocol 1 4147 RW 0…65535 Modbus TCP port number 502 4148 RW 80…65535 Web server port number 80
4149 RW 0,1 4150 RW 0..2 Menu language: 0-ENG, 1-PL, 2-DE 1
-1440..0..1440
0,1
0,1
"1" – copy archive to files archive memory / only the records which
The third and the second byte (B3.B2) of the IP address of the meter, the IPv4 address format: B3.B2.B1.B0
The first and zero byte (B1.B0) of the IP address of the meter, the IPv4 address format: B3.B2.B1.B0
The third and the second byte (B3.B2) of the subnet mask of the meter, the mask format: B3.B2.B1.B0 The first and zero byte (B1.B0) of the subnet mask of the meter, the mask format: B3.B2.B1.B0 The third and the second byte (B3.B2) of the default gateway of the meter, the gateway address format: B3.B2.B1.B0 The first and zero byte (B1.B0) of the default gateway of the meter, the gateway address format: B3.B2.B1.B0 The third and the second byte (B3.B2) of the DNS address of the meter, the IPv4 address format: B3.B2.B1.B0 The first and zero byte (B1.B0) of the DNS address of the meter, the IPv4 address format: B3.B2.B1.B0
Enabling / disabling the DHCP Client (supports automatic
aining of IP protocol parameters of the meter's Ethernet
obt interface from external DHCP servers in the same LAN) 0 - DHCP disabled - you should manually configure the IP address and subnet mask of the meter; 1 - DHCP enabled, the meter will automatically receive the IP address, subnet mask, and gateway address from the DHCP server when switching the supply on or selecting APPL option from the menu or entering the value "1" to the register 4099. The gateway address is the address of the server that assigned the parameters to the meter;
The maximum simultaneous connections to Modbus TCP/IP service
Saving the new parameters and initiate Ethernet interface 0 – no changes 1 - saving the new parameters and initiate the Ethernet interface
Group 2, archiving upper limit w o/
Copying archive to files archive memory.
have been registered since the last copy /
Decimal separator 0 - dot '.' 1 - comma ',' .
Baud rate of the Ethernet interface:
0 – automatic selection of the baud rate 1 – 10 Mb/s 2 – 100 Mb/s
oo
1100
49320
(0xC0
A8 =
192.1
(0x01
1.100
65535 65280 49320
0x080
8=8.8
0x080
8=8.8
0
68)
356
64 =
)
257
1
0
1
0
Page 48
47 User's manual
4151 RW 0,1 reserved 0 4152 RW 0.1 4153 RW 0..59 Seconds 0
4154 RW 0…2359 Hour *100 + minutes 0 4155 RW 101…1231 Month * 100 + day 101 4156 RW 2015…2077 Year 2015 4157 RW reserved 4158 RW reserved 4159 RW reserved
The alarm switching values stored in the registers 4036, 4037, 4054, 4055, 4067, 4068, 4076, 4077, 4085,
6 are multiplied by 10, e.g. the value of 100% should be entered as "1000".
408 The lower and upper values of the input range of the continuous output stored in the registers 4094, 4095 are multiplied by 10, e.g. the value of 100% should be entered as "1000". The lower and upper values of the current output range stored in the registers 4096, 4097 are multiplied by 100, e.g. the value of 20 mA should be entered as "2000".
Register address
4200 RW 7500 .. 7957 Register 1 of programmable group of registers for readout 7500 4201 RW 7500 .. 7957 Register 2 of programmable group of registers for readout 7501 4202 RW 7500 .. 7957 Register 3 of programmable group of registers for readout 7502 4203 RW 7500 .. 7957 Register 4 of programmable group of registers for readout 7503 4204 RW 7500 .. 7957 Register 5 of programmable group of registers for readout 7504 4205 RW 7500 .. 7957 Register 6 of programmable group of registers for readout 7505 4206 RW 7500 .. 7957 Register 7 of programmable group of registers for readout 7506 4207 RW 7500 .. 7957 Register 8 of programmable group of registers for readout 7507 4208 RW 7500 .. 7957 Register 9 of programmable group of registers for readout 7508 4209 RW 7500 .. 7957 Register 10 of programmable group of registers for readout 7509 4210 RW 7500 .. 7957 Register 11 of programmable group of registers for readout 7510 4211 RW 7500 .. 7957 Register 12 of programmable group of registers for readout 7511 4212 RW 7500 .. 7957 Register 13 of programmable group of registers for readout 7512 4213 RW 7500 .. 7957 Register 14 of programmable group of registers for readout 7513 4214 RW 7500 .. 7957 Register 15 of programmable group of registers for readout 7514 4215 RW 7500 .. 7957 Register 16 of programmable group of registers for readout 7515 4216 RW 7500 .. 7957 Register 17 of programmable group of registers for readout 7516 4217 RW 7500 .. 7957 Register 18 of programmable group of registers for readout 7517 4218 RW 7500 .. 7957 Register 19 of programmable group of registers for readout 7518 4219 RW 7500 .. 7957 Register 20 of programmable group of registers for readout 7519 4220 RW 7500 .. 7957 Register 21 of programmable group of registers for readout 7520 4221 RW 7500 .. 7957 Register 22 of programmable group of registers for readout 7521 4222 RW 7500 .. 7957 Register 23 of programmable group of registers for readout 7522 4223 RW 7500 .. 7957 Register 24 of programmable group of registers for readout 7523 4224 RW 7500 .. 7957 Register 25 of programmable group of registers for readout 7524 4225 RW 7500 .. 7957 Register 26 of programmable group of registers for readout 7525 4226 RW 7500 .. 7957 Register 27 of programmable group of registers for readout 7526 4227 RW 7500 .. 7957 Register 28 of programmable group of registers for readout 7527 4228 RW 7500 .. 7957 Register 29 of programmable group of registers for readout 7528 4229 RW 7500 .. 7957 Register 30 of programmable group of registers for readout 7529 4230 RW 7500 .. 7957 Register 31 of programmable group of registers for readout 7530 4231 RW 7500 .. 7957 Register 32 of programmable group of registers for readout 7531 4232 RW 7500 .. 7957 Register 33 of programmable group of registers for readout 7532 4233 RW 7500 .. 7957 Register 34 of programmable group of registers for readout 7533 4234 RW 7500 .. 7957 Register 35 of programmable group of registers for readout 7534 4235 RW 7500 .. 7957 Register 36 of programmable group of registers for readout 7535
Operati
ons
Range Description Default
Saving default parameters (complete with resetting energy as well
as min, max and mean power to 0) and Ethernet,
Table 17
0
Page 49
48 User's manual
Register
address
4236 RW 7500 .. 7957 Register 37 of programmable group of registers for readout 7536 4237 RW 7500 .. 7957 Register 38 of programmable group of registers for readout 7537 4238 RW 7500 .. 7957 Register 39 of programmable group of registers for readout 7538 4239 RW 7500 .. 7957 Register 40 of programmable group of registers for readout 7539 4240 RW 7500 .. 7957 Register 41 of programmable group of registers for readout 7540 4241 RW 7500 .. 7957 Register 42 of programmable group of registers for readout 7541 4242 RW 7500 .. 7957 Register 43 of programmable group of registers for readout 7542 4243 RW 7500 .. 7957 Register 44 of programmable group of registers for readout 7543 4244 RW 7500 .. 7957 Register 45 of programmable group of registers for readout 7544 4245 RW 7500 .. 7957 Register 46 of programmable group of registers for readout 7545 4246 RW 7500 .. 7957 Register 47 of programmable group of registers for readout 7546 4247 RW 7500 .. 7957 Register 48 of programmable group of registers for readout 7547 4248 RW 7500 .. 7957 Register 49 of programmable group of registers for readout 7548 4249 RW 7500 .. 7957 Register 50 of programmable group of registers for readout 7549 4250 RW 7500 .. 7957 Register 51 of programmable group of registers for readout 7550 4251 RW 7500 .. 7957 Register 52 of programmable group of registers for readout 7551 4252 RW 7500 .. 7957 Register 53 of programmable group of registers for readout 7552 4253 RW 7500 .. 7957 Register 54 of programmable group of registers for readout 7553 4254 RW 7500 .. 7957 Register 55 of programmable group of registers for readout 7554 4255 RW 7500 .. 7957 Register 56 of programmable group of registers for readout 7559 4256 RW 7500 .. 7957 Register 57 of programmable group of registers for readout 7560 4257 RW 7500 .. 7957 Register 58 of programmable group of registers for readout 7561 4258 RW 7500 .. 7957 Register 59 of programmable group of registers for readout 7566 4259 RW 7500 .. 7957 Register 60 of programmable group of registers for readout 7567
4260 RW 0,1
Operati
ons
Range Description Default
Restore default group 0 – no changes, 1 – restore default
group
0
16-bit register
address
2x16 1032/
2x16 3210
7200/7000 7400 R Content of the register set in the registers 4200 7202/7002 7401 R Content of the register set in the registers 4201 7204/7004 7402 R Content of the register set in the registers 4202 7206/7006 7403 R Content of the register set in the registers 4203 7208/7008 7404 R Content of the register set in the registers 4204 7210/7010 7405 R Content of the register set in the registers 4205 7212/7012 7406 R Content of the register set in the registers 4206 7214/7014 7407 R Content of the register set in the registers 4207 7216/7016 7408 R Content of the register set in the registers 4208 7218/7018 7409 R Content of the register set in the registers 4209 7220/7020 7410 R Content of the register set in the registers 4210 7222/7022 7411 R Content of the register set in the registers 4211 7224/7024 7412 R Content of the register set in the registers 4212 7226/7026 7413 R Content of the register set in the registers 4213 7228/7028 7414 R Content of the register set in the registers 4214 7230/7030 7415 R Content of the register set in the registers 4215 7232/7032 7416 R Content of the register set in the registers 4216 7234/7034 7417 R Content of the register set in the registers 4217 7236/7036 7418 R Content of the register set in the registers 4218 7238/7038 7419 R Content of the register set in the registers 4219 7240/7040 7420 R Content of the register set in the registers 4220 7242/7042 7421 R Content of the register set in the registers 4221 7244/7044 7422 R Content of the register set in the registers 4222 7246/7046 7423 R Content of the register set in the registers 4223
Register
address
32-bit
Operations Description
Table 18
Page 50
49 User's manual
7248/7048 7424 R Content of the register set in the registers 4224 7250/7050 7425 R Content of the register set in the registers 4225 7252/7052 7426 R Content of the register set in the registers 4226 7254/7054 7427 R Content of the register set in the registers 4227 7256/7056 7428 R Content of the register set in the registers 4228 7258/7058 7429 R Content of the register set in the registers 4229 7260/7060 7430 R Content of the register set in the registers 4230 7262/7062 7431 R Content of the register set in the registers 4231 7264/7064 7432 R Content of the register set in the registers 4232 7266/7066 7433 R Content of the register set in the registers 4233 7268/7068 7434 R Content of the register set in the registers 4234 7270/7070 7435 R Content of the register set in the registers 4235 7272/7072 7436 R Content of the register set in the registers 4236 7274/7074 7437 R Content of the register set in the registers 4237 7276/7076 7438 R Content of the register set in the registers 4238 7278/7078 7439 R Content of the register set in the registers 4239 7280/7080 7440 R Content of the register set in the registers 4240 7282/7082 7441 R Content of the register set in the registers 4241 7284/7084 7442 R Content of the register set in the registers 4242 7286/7086 7443 R Content of the register set in the registers 4243 7288/7088 7444 R Content of the register set in the registers 4244 7290/7090 7445 R Content of the register set in the registers 4245 7292/7092 7446 R Content of the register set in the registers 4246 7294/7094 7447 R Content of the register set in the registers 4247 7296/7096 7448 R Content of the register set in the registers 4248 7298/7098 7449 R Content of the register set in the registers 4249 7300/7100 7450 R Content of the register set in the registers 4250 7302/7102 7451 R Content of the register set in the registers 4251 7304/7104 7452 R Content of the register set in the registers 4252 7306/7106 7453 R Content of the register set in the registers 4253 7308/7108 7454 R Content of the register set in the registers 4254 7310/7110 7455 R Content of the register set in the registers 4255 7312/7112 7456 R Content of the register set in the registers 4256 7314/7114 7457 R Content of the register set in the registers 4257 7316/7116 7458 R Content of the register set in the registers 4258 7318/7118 7459 R Content of the register set in the registers 4259
Registe
r
address
4300 RW 1…3
Operati
ons
Range Description Default
Luminosity level: 1 – Minimum, 2 - Medium
3 - Maximum 4301 RW 0 .. 3600 Time to min. luminosity 0 4302 RW reserved 0
4303 RW 0x0001...0x03FF
Enabling page display Bit0 – page 1, Bit1 – page
2, ...Bit9 – page 10
0x03FF
4304 RW reserved 4305 RW 00..49 Page 1 display 1, U1 1 4306 RW 00..49 Page 1 display 2, U2 10
4307 RW 00..49 Page 1 display 3, U3 19 4308 RW 00..49 Page 1 display 4, f 37
4309 RW 00..49 Page 1 display 5, I1 2 4310 RW 00..49 Page 1 display 6, I2 11
4311 RW 00..49 Page 1 display 7, I3 20 4312 RW 00..49 Page 1 display 8, I avg 28 4313 RW 00..49 Page 2 display 1, U12 38
Table 19
3
Page 51
50 User's manual
Registe
r
address
Operati
ons
Range Description Default
4314 RW 00..49 Page 2 display 2, U23 39 4315 RW 00..49 Page 2 display 3, U31 40 4316 RW 00..49 Page 2 display 4, U123 41 4317 RW 00..49 4318 RW 00..49 4319 RW 00..49
Page 2 display 5, ΣP Page 2 display 6, ΣQ
Page 2 display 7, ΣS 4320 RW 00..49 Page 2 display 8, PF avg 33 4321 RW 00..49 Page 3 display 1, P1 3 4322 RW 00..49 Page 3 display 2, P2 12 4323 RW 00..49 Page 3 display 3, P3 21 4324 RW 00..49
Page 3 display 4, ΣP 4325 RW 00..49 Page 3 display 5, PF1 6 4326 RW 00..49 Page 3 display 6, PF2 15 4327 RW 00..49 Page 3 display 7, PF3 24 4328 RW 00..49 Page 3 display 8, PF avg 33 4329 RW 00..49 Page 4 display 1, P1 3 4330 RW 00..49 Page 4 display 2, P2 12 4331 RW 00..49 Page 4 display 3, P3 21 4332 RW 00..49
Page 4 display 4, ΣP 4333 RW 00..49 Page 4 display 5, Q1 4 4334 RW 00..49 Page 4 display 6, Q2 13 4335 RW 00..49 Page 4 display 7, Q3 22 4336 RW 00..49
Page 4 display 8, ΣQ 4337 RW 00..49 Page 5 display 1, THD U1 8 4338 RW 00..49 Page 5 display 2, THD U2 17 4339 RW 00..49 Page 5 display 3, THD U3 26 4340 RW 00..49 Page 5 display 4, THD U 35 4341 RW 00..49 Page 5 display 5, THD I1 9 4342 RW 00..49 Page 5 display 6, THD I2 18 4343 RW 00..49 Page 5 display 7, THD I3 27 4344 RW 00..49 Page 5 display 8, THD I 36 4345 RW 00..49 Page 6 display 1, U1 1 4346 RW 00..49
Page 6 display 2, I1 2 4347 RW 00..49 Page 6 display 3, P1 3 4348 RW 00..49 Page 6 display 4, Q1 4 4349 RW 00..49 Page 6 display 5, S1 5 4350 RW 00..49 Page 6 display 6, PF1 6 4351 RW 00..49 Page 6 display 7, tg1 7 4352 RW 00..49 Page 6 display 8, f 37 4353 RW 00..49 Page 7 display 1, U2 10 4354 RW 00..49 Page 7 display 2, I2 11 4355 RW 00..49 Page 7 display 3, P2 12 4356 RW 00..49 Page 7 display 4, Q2 13 4357 RW 00..49 Page 7 display 5, S2 14 4358 RW 00..49 Page 7 display 6, PF2 15 4359 RW 00..49 Page 7 display 7, tg2 16 4360 RW 00..49 Page 7 display 8, f 37 4361 RW 00..49 Page 8 display 1, U3 19 4362 RW 00..49
Page 8 display 2, I3 20 4363 RW 00..49 Page 8 display 3, P3 21 4364 RW 00..49 Page 8 display 4, Q3 22 4365 RW 00..49 Page 8 display 5, S3 23 4366 RW 00..49
Page 8 display 6, PF3 24
4367 RW 00..49 Page 8 display 7, tg3 25
30 31 32
30
30
31
Page 52
51 User's manual
Registe
r
address
Operati
ons
Range Description Default
4368 RW 00..49 Page 8 display 8, f 37 4369 RW 00..49 4370 RW 00..49
Page 9 display 1, ΣP
Page 9 display 2, ΣQ 4371 RW 00..49 Page 9 display 3, I avg 29 4372 RW 00..49 Page 9 display 4, I(N) 45 4373 RW 00..49 Page 9 display 5, P DMD 42 4374 RW 00..49 Page 9 display 6, S DMD 43 4375 RW 00..49 Page 9 display 7, I DMD 44 4376 RW 00..49 Page 9 display 8, f 37 4377 RW 00..49 4378
RW 00..49
4379 RW 00..49
Page 10 display 1, ΣP Page 10 display 2, ΣQ
Page 10 display 3, ΣS 4380 RW 00..49 Page 10 display 4, En S 52 4381 RW 00..49 Page 10 display 5, +En P 48 4382 RW 00..49 Page 10 display 6, -En P 49
4383 RW 00..49 4384 RW 00..49
Page 10 display 7, En Q
Page 10 display 8, En Q
Restore manufacturer's pages
0 - no
4385 RW 0..3
1 - 3Ph/4W 2 - 3Ph/3W
3 - 1PH/2W
30
31
30
31 32
50
51
0
Table 20
Register
address
4400 R reserved 4401 R 0..65535 Identifier D9 4402 R 0..65535 Bootloader version x 100 ­4403 R 0..65535 Program version x100 ­4404 R reserved 4405 R 0..65535 Ordering codes ­4406 R 0..65535 Nominal voltage x10 577/2300 4407 R 0..65535 Nominal voltage x10 1100/4000 4408 R 0..65535 Nominal current (1 A) x 100 100 4409 R 0..65535 Nominal current (5 A) x 100 500 4410 R reserved
4411 R 0..65535 4412 R 0..65535 4413 R 0..65535 4414 R 0..65535
4415 R 0..65535 Status 1 Register – see description below 0 4416 R 0..65535 Status 2 Register – see description below 0 4417 R 0..65535 Status 3 Register – see description below 0 4418 R 0..65535 Status 4 Register – see description below 0 4419 R 0..65535 Status 5 Register – see description below 0 4420 R 0..65535 Status 6 Register – see description below 0
4421 R 0…65535 4422 R 0…65535 Third and second byte (B3.B2) of MAC address of the -
Operati
ons
Range Description Default
Seventh and sixth byte (B7.B6) of a serial number, format
B7:B6:B5:B4:B3:B2:B1:B0
Fifth and fourth byte (B5.B4) of a serial number, format
B7:B6:B5:B4:B3:B2:B1:B0
Third and second byte (B3.B2) of a serial number, format
B7:B6:B5:B4:B3:B2:B1:B0
First and zero byte (B1.B0) of a serial number, format
B7:B6:B5:B4:B3:B2:B1:B0
Fifth and fourth byte (B5.B4) of MAC address of the meter, format B5:B4:B3:B2:B1:B0
-
-
-
-
-
Page 53
52 User's manual
meter, format B5:B4:B3:B2:B1:B0 4423 R 0…65535 4424 R reserved 0
4425 R reserved 0 4426 R 0..152 Active import energy, two older bytes 0 4427 R 0..65535 Active import energy, two younger bytes 0 4428 R 0..152 Active export energy, two older bytes 0 4429 R 0..65535 Active export energy, two younger bytes 0 4430 R 0..152 Reactive inductive energy, two older bytes 0 4431 R 0..65535 Reactive inductive energy, two younger bytes 0 4432 R 0..152 Reactive capacity energy, two older bytes 0 4433 R 0..65535 Reactive capacity energy, two younger bytes 0 4434 R 0..152 Apparent energy, two older bytes 0 4435 R 0..65535 Apparent energy , two younger bytes 0
6 R reserved
443 4437 R reserved 4438 R 0..2000 Resistance Pt100 x100 (T1) ­4439 R 0..2000 Resistance Pt100 x100 (T2) ­4440 R 0..1000 Files archive usage in o/ 4441 R 0..1000 Group 1 archive internal memory usage in o/ 4442 R 0..1000 Group 2 archive internal memory usage in o/
4443 R 0..1000 4444 R 0..1000 4445 R 0..1000 4446 R 0..1000
The fifth and fourth byte (B1.B0) of MAC address of the
meter, format B5:B4:B3:B2:B1:B0
oo
oo oo
Total archive internal memory usage
for the groups 1 and 2 in o/
oo
Percentage of the archive copying progress to files archive
for group 1 in o/
oo
Percentage of the archive copying progress to files archive
for group 2 in o/
oo
Total percentage of the archive copying progress to files
archive for group 1 and 2 in o/
oo
-
0 0 0
0 0 0 0
Energy is made available in hundreds of watt-hours (var-hours) in double 16-bit register, and for this reason, you should divide them by 100 when calculating values of particular energy from registers, e.g.:
Active import energy = (reg. value 4426 x 65536 + reg. value 4427) / 100 [kWh] Active export energy = (reg. value 4428 x 65536 + reg. value 4429) / 100 [kWh] Reactive inductive energy = (reg. value 4430 x 65536 + reg. value 4431) / 100 [kVarh] Reactive capacity energy = (reg. value 4432 x 65536 + reg. value 4433) / 100 [kVarh] Apparent energy = (reg. value 4434 x 65536 + reg. value 4435) / 100 [kVAh]
Status 1 Register of a device (address 4415, R):
Bit 15 – "1” – FRAM memory damage Bit Bit 14 – "1” – no calibration of the input Bit 6 – "1” – reserved Bit 13 – "1” – no calibration of the output Bit 5 – "1” – reserved Bit 12 – "1” – PT100 calibration error Bit 4 – "1” – present analog output Bit 11 – "1” – error in configuration registers Bit 3 – "1” – present PT100 Bit 10 – "1” – error in displayed pages registers Bit 2 – "1” – present Ethernet and internal memory Bit 9 – "1” – error in registers for configuration of programmable group of registers for readout Bit 8 – "1” – energy value error Bit 0 – reserved
7 – "1” – phase sequence error
Bit 1 – "1” – used battery of RTC
Page 54
53 User's manual
Status 2 Register – (address 4416, R):
Bit 15 – "1” – condition 3 for alarm 2 signalization
Bit 14 – "1” – condition 2 for alarm 2 signalization Bit 13 – "1” – condition 1 for alarm 2 signalization Bit 12 – "1” – alarm 2 signalization Bit 11 – "1” – alarm 2 condition 3 activated Bit 10 – "1” – alarm 2 condition 2 activated Bit 9 – "1” – alarm 2 condition 1 activated
Bit 8 – "1” – alarm 2 activated
Status 3 Register – (address 4417, R): Files archive status
Bit 15 – Ethernet connected
14 – reserved
Bit Bit 13 – reserved Bit 12 – reserved Bit 11 – "0” - waiting for the archiving conditions to be met
"1” - archiving in the archiving group 2
Bit 10 – "0” - waiting for the archiving conditions to be met
"1” - archiving in the archiving group 1 Bit 9 – reserved Bit 8 – Archiving group 2 enabled
Bit 7 – "1” – condition 3 for alarm 1 signalization
Bit 6 – "1” – condition 2 for alarm 1 signalization Bit 5 – "1” – condition 1 for alarm 1 signalization Bit 4 – "1” – alarm 1 signalization Bit 3 – "1” – alarm 1 condition 3 activated Bit 2 – "1” – alarm 1 condition 2 activated Bit 1 – "1” – alarm 1 condition 1 activated Bit 0 – "1” – alarm 1 activated
Bit 7 – Archiving group 1 enabled Bit 6 – reserved Bit 5 – copying of internal memory to
Bit 4 – copying of internal memory to Bit 3 – Files archive space is full, (less then 14
days at 1 sec. interval to completely use a the files archive space) Bit 2 – 70% of files archive space is full Bit 1 – Files archive initialized correctly
Bit 0 – Files archive file system error
files archive from archiving group 2
files archive from archiving group 1
Status 4 Register – (address 4418, R) reactive power characteristics:
Bit 15 – measurement with phase L3 synchronization Bit 14 – measurement with phase L2 synchronization Bit 13 – measurement with phase L1 synchronization Bit 12 – measurement with current synchronization Bit 11 – "1” – capacity 3L max. Bit 10 – "1” – capacity 3L min. Bit 9 – "1” – capacity 3L Bit 8 – "1” – leading L3 max.
Bit 7 – "1” – capacity L3 min. Bit 6 – "1” – capacity L3 Bit 5 – "1” – capacity L2 max. Bit 4 – "1” – capacity L2 min. Bit 3 – "1” – capacity L2 Bit 2 – "1” – capacity L1 max. Bit 1 – "1” – capacity L1 min. Bit 0 – "1” – capacity L1
Status 5 Register – (address 4419, R)
Bit 8 – "1” – alarm 1 condition 3 for phase L3 active
7 – "1” – alarm 1 condition 3 for phase L2 active
Bit Bit 6 – "1” – alarm 1 condition 3 for phase L1 active Bit 5 – "1” – alarm 1 condition 2 for phase L3 active Bit 4 – "1” – alarm 1 condition 2 for phase L2 active Bit 3 – "1” – alarm 1 condition 2 for phase L1 active Bit 2 – "1” – alarm 1 condition 1 for phase L3 active Bit 1 – "1” – alarm 1 condition 1 for phase L2 active Bit 0 – "1” – alarm 1 condition 1 for phase L1 active
Status 6 Register – (address 4420, R)
Bit 8 – "1” – alarm 2 condition 3 for phase L3 active Bit 7 – "1” – alarm 2 condition 3 for phase L2 active Bit 6 – "1” – alarm 2 condition 3 for phase L1 active Bit 5 – "1” – alarm 2 condition 2 for phase L3 active Bit 4 – "1” – alarm 2 condition 2 for phase L2 active Bit 3 – "1” – alarm 2 condition 2 for phase L1 active Bit 2 – "1” – alarm 2 condition 1 for phase L3 active Bit 1 – "1” – alarm 2 condition 1 for phase L2 active Bit 0 – "1” – alarm 2 condition 1 for phase L1 active
Page 55
54 User's manual
16-bit
register
address
2x16
1032/
2x16 3210
6000/8000 7500 R L1 phase voltage V 6002/8002 7501 R L1 phase current A 6004/8004 7502 R L1 phase active power W 6006/8006 7503 R L1 phase reactive power VAr 6008/8008 7504 R L1 phase apparent power VA 6010/8010 7505 R L1 phase active power factor (PF1=P1/S1)) ­6012/8012 7506 R tg 6014/8014 7507 R THD U1* % 6016/8016 7508 R THD I1 % 6018/8018 7509 R L2 phase voltage V 6020/8020 7510 R L2 phase current A 6022/8022 7511 R L2 phase active power W 6024/8024 7512 R L2 phase reactive power VAr 6026/8026 7513 R L2 phase apparent power VA 6028/8028 7514 R L2 phase active power factor (PF2=P2/S2)) ­6030/8030 7515 R tg factor of L2 phase (tg2=Q2/P2) ­6032/8032 7516 R THD U2* % 6034/8034 7517 R THD I2 % 6036/8036 7518 R L3 phase voltage V 6038/8038 7519 R L3 phase current A 6040/8040 7520 R L3 phase active power W 6042/8042 7521 R L3 phase reactive power VAr 6044/8044 7522 R L3 phase apparent power VA 6046/8046 7523 R L3 phase active power factor (PF3=P3/S3)) ­6048/8048 7524 R tg 6050/8050 7525 R THD U3* % 6052/8052 7526 R THD I3 % 6054/8054 7527 R Mean 3-phase voltage V 6056/8056 7528 R Mean 3-phase current A 6058/8058 7529 R 3-phase active power (P1+P2+P3) W 6060/8060 7530 R 3-phase reactive power (Q1+Q2+Q3) VAr 6062/8062 7531 R 3-phase apparent power (S1+S2+S3) VA 6064/8064 7532 R 3-phase active power factor (PF=P/S) ­6066/8066 7533 R Mean tg factor for 3 phases (tg=Q/P) ­6068/8068 7534 R THD U* mean 3-phase % 6070/8070 7535 R THD I mean 3-phase % 6072/8072 7536 R Frequency f 6074/8074 7537 R Phase-to-phase voltage L 6076/8076 7538 R Phase-to-phase voltage L 6078/8078 7539 R Phase-to-phase voltage L 6080/8080 7540 R Mean phase-to-phase voltage V 6082/8082 7541 R Active power averaged (P Demand) W 6084/8084 7542 R Reactive power averaged (S Demand ) VA 6086/8086 7543 R Current averaged (I Demand) A 6088/8088 7544 R Neutral wire current (calculated from vectors) A
6090/8090 7545 R
6092/8092 7546 R 6094/8094 7547 R Active 3-phase export energy (no. of register 100
Register
address
32-bit
Operation
s
Description Unit
factor of L1 phase (tg1=Q1/P1) -
factor of L3 phase (tg3=Q3/P3) -
1-2 2-3 3-1
Active 3-phase import energy (no. of register 7546 overflows, resets to 0 after reaching 9999.9 MWh) Active 3-phase import energy (counter counting up to 99999.99 kWh)
V V V
100
MWh
kWh
Table 21
3Ph
3Ph
/
/
4W
3W
x
√ √
x
x
x
x
x
x
x
x x
√ √
x x
x x
x x
x x
x x
x x
x x
x x
√ √
x x
x x
x x
x x
x x
x x
x x
x x
√ √ √ √ √ √ √ √ √ √ √ √
x x
x x
√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √
x x
√ √
√ √
1Ph
/
2W
√ √ √ √ √ √ √
x
x
x x x x x x
x x x x x x x
Page 56
55 User's manual
7548 overflows, resets to 0 after reaching 9999.9 MWh)
6096/8096 7548 R
6098/8098 7549 R
6100/8100 7550 R
6102/8102 7551 R
6104/8104 7552 R 6106/8106 7553 R 6108/8108 7554 R
6110/8110 7555 R Time – seconds sec 6112/8112 7556 R Time – hours, minutes 6114/8114 7557 R Date – month, day 6116/8116 7558 R Year – 2014 - 2100
6118/8118 7559 R Status 1 register ­6120/8120 7560 R Status 2 register ­6122/8122 7561 R Status 3 register ­6124/8124 7562 R Status 4 register ­6126/8126 7563 R Status 5 register ­6128/8128 7564 R Status 6 register ­6130/7130 7565 R Continuous output 1 activation mA 6132/8132 7566 R Temperature Pt100 1 6134/8134 7567 R Temperature Pt100 2 6136/8136 7568 R Voltage L1 min V 6138/8138 7569 R Voltage L1 max V 6140/8140 7570 R Voltage L2 min V 6142/8142 7571 R Voltage L2 max V 6144/8144 7572 R Voltage L3 min V 6146/8146 7573 R Voltage L3 max V 6148/8148 7574 R Current L1 min A 6150/8150 7575 R Current L1 max A
/8152 7576 R Current L2 min A
6152 6154/8154 7577 R Current L2 max A 6156/8156 7578 R Current L3 min A 6158/8158 7579 R Current L3 max A 6160/8160 7580 R Active power L1 min W 6162/8162 7581 R Active power L1 max W 6164/8164 7582 R Active power L2 min W 6166/8166 7583 R Active power L2 max W 6168/8168 7584 R Active power L3 min W 6170/8170 7585 R Active power L3 max W 6172/8172 7586 R Reactive power L1 min Var 6174/8174 7587 R Reactive power L1 max Var
76/8176 7588 R Reactive power L2 min Var
61 6178/8178 7589 R Reactive power L2 max Var
/8180 7590 R Reactive power L3 min Var
6180 6182/8182 7591 R Reactive power L3 max Var 6184/8184 7592 R Apparent power L1 min VA
Active 3-phase export energy (counter counting up to 99999.99 kWh) Reactive 3-phase inductive energy (no. of register 7550 overflows, resets to 0 after reaching 9999.9 MVArh). Reactive 3-phase inductive energy (counter counting up to 99999.99 kVArh) Reactive 3-phase capacity energy (no. of register 7552 overflows, resets to 0 after reaching 9999.9 MVArh) Reactive 3-phase capacity energy (counter counting up to 99999.99 kVArh) Apparent energy (no. of register 7554 overflows,
ts to 0 after reaching 9999.9 MVAh)
rese Apparent energy (counter counting up to
99999.99 kVAh)
MWh
kWh
100
MVArh
kVArh
100
MVArh
kVArh
100
MVAh
kVAh
°C √ °C
√ √ √ √
√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √
x
x
x x
x x
x x
x x
√ √
√ √ √ √ √ √ √ √
x
x
x
x
x
x
x
x
x
x
x
x
x
√ √
x x x x x x
√ √
x x x x
√ √
x x x x
Page 57
56 User's manual
6186/8186 7593 R Apparent power L1 max VA 6188/8188 7594 R Apparent power L2 min VA 6190/8190 7595 R Apparent power L2 max VA 6192/8192 7596 R Apparent power L3 min VA 6194/8194 7597 R Apparent power L3 max VA 6196/8196 7598 R Power factor (PF) L1 min ­6198/8198 7599 R Power factor (PF) L1 max ­6200/8200 7600 R Power factor (PF) L2 min ­6202/8202 7601 R Power factor (PF) L2 max ­6204/8204 7602 R Power factor (PF) L3 min ­6206/8206 7603 R Power factor (PF) L3 max -
8/8208 7604 R Reactive to active power ratio L1 min -
620 6210/8210 7605 R Reactive to active power ratio L1 max ­6212/8212 7606 R Reactive to active power ratio L1 min ­6214/8214 7607 R Reactive to active power ratio L2 max ­6216/8216 7608 R Reactive to active power ratio L3 min ­6218/8218 7609 R Reactive to active power ratio L3 max ­6220/8220 7610 R Phase-to-phase voltage L 6222/8222 7611 R Phase-to-phase voltage L 6224/8224 7612 R Phase-to-phase voltage L 6226/8226 7613 R Phase-to-phase voltage L 6228/8228 7614 R Phase-to-phase voltage L 6230/8230 7615 R Phase-to-phase voltage L 6232/8232 7616 R Mean 3-phase voltage (min) V 6234/8234 7617 R Mean 3-phase voltage (max) V 6236/8236 7618 R Mean 3-phase current (min) A 6238/8238 7619 R Mean 3-phase current (max) A 6240/8240 7620 R 3-phase active power (min) W 6242/8242 7621 R 3-phase active power (max) W 6244/8244 7622 R 3-phase reactive power (min) var
246/8246 7623 R 3-phase reactive power (max) var
6 6248/8248 7624 R 3-phase apparent power (min) VA 6250/8250 7625 R 3-phase apparent power (max) VA 6252/8252 7626 R Power factor (PF) min ­6254/8254 7627 R Power factor (PF) max -
6256/8256 7628 R 6258/8258 7629 R
6260/8260 7630 R Min. frequency Hz 6262/8262 7631 R Frequency max Hz 6264/8264 7632 R Mean phase-to-phase voltage (min.) V 6266/8266 7633 R Mean phase-to-phase voltage (max.) V 6268/8268 7634 R Active power averaged (P Demand) min W
6270/8270 7635 R Active power averaged (P Demand) max W 6272/8272 7636 R Apparent power averaged (S Demand) min VA 6274/8274 7637 R Apparent power averaged (S Demand) max VA 6276/8276 7638 R Current averaged (I Demand) min A 6278/8278 7639 R Current averaged (I Demand) max A 6280/8280 7640 R Neutral wire current (min.) A
2/8282 7641 R Neutral wire current (max.) A
628 6284/8284 7642 R Temperature T1 min 6286/8286 7643 R Temperature T1 max
Reactive to active power ratio (3-phase mean min.) Reactive to active power ratio (3-phase mean max.)
min V
1-2
max V
1-2
min V
2-3
max V
2-3
min V
3-1
max V
3-1
°C °C
x
√ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √
-
-
√ √
x x x x x x x x x x x x x x x x x x x x x x x x x x x x
x x x x
√ √
√ √
x x x x x x
x x x x x x x x x x
x x
√ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √
√ √
√ √
x x
x x x x
Page 58
57 User's manual
6288/8288 7644 R Temperature T2 min 6290/8290 7645 R Temperature T2 max 6292/8292 7646 R THD U1 min % 6294/8294 7647 R THD U1 max % 6296/8296 7648 R THD U2 min % 6298/8298 7649 R THD U2 max % 6300/8300 7650 R THD U3 min % 6302/8302 7651 R THD U3 max % 6304/8304 7652 R THD U min % 6306/8306 7653 R THD U max % 6308/8308 7654 R THD I1 min %
/8310 7655 R THD I1 max %
6310 6312/8312 7656 R THD I2 min % 6314/8314 7657 R THD I2 max % 6316/8316 7758 R THD I3 min % 6318/8318 7759 R THD I3 max % 6320/8320 7660 R THD I min % 6322/8322 7661 R THD I max % 6324/8324 7662 R HarU1[2] 2nd harmonic of L1 phase voltage %
6326/8326 7663 R HarU1[3] 3rd harmonic of L1 phase voltage %
: : R :
: : R : 6420/8420 7710 R HarU1[50] 50th harmonic of L1 phase voltage % 6422/8422 7711 R HarU1[51] 51st harmonic of L1 phase voltage % 6424/8424 7712 R HarU2[2] 2nd harmonic of L2 phase voltage % 6426/8426 7713 R HarU2[3] 3rd harmonic of L2 phase voltage %
: : R :
: : R :
6520/8520 7760 R HarU2[50] 50th harmonic of L2 phase voltage % 6522/8522 7761 R HarU2[51] 51st harmonic of L2 phase voltage % 6524/8524 7762 R HarU3[2] 2nd harmonic of L3 phase voltage % 6526/8526 7763 R HarU3[3] 3rd harmonic of L3 phase voltage %
: : R :
: : R :
/8620 7810 R HarU3[50] 50th harmonic of L3 phase voltage %
6620 6622/8622 7811 R HarU3[51] 51st harmonic of L3 phase voltage % 6624/8624 7812 R Harl1U1[2] 2nd harmonic of L1 phase current % 6626/8626 7813 R Harl1U1[3] 3rd harmonic of L1 phase current %
: : R :
: : R :
6720/8720 7860 R Harl1U1[50] 50th harmonic of L1 phase current % 6722/8722 7861 R Harl1[51] 51st harmonic of L1 phase current % 6724/8724 7862 R Harl2[2] 2nd harmonic of L2 phase current % 6726/8726 7863 R Harl2[3] 3rd harmonic of L2 phase current %
: : R :
: : R :
6820/8820 7910 R Harl2[50] 50th harmonic of L2 phase current % 6822/8822 7911 R Harl2[51] 51st harmonic of L2 phase current % 6824/8824 7912 R Harl3[2] 2nd harmonic of L3 phase current % 6826/8826 7913 R Harl3[3] 3rd harmonic of L3 phase current %
: : R :
: : R : 6920/8920 7960 R Harl3[50] 50th harmonic of L3 phase current % 6922/8922 7961 R Harl3[51] 51st harmonic of L3 phase current %
°C °C
√ √
x
x
x x
x x
x x
x x
x x
x x
x
x
x x
x x
x x
x x
x x
x x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x x
x x
x x
x x
x x
x x
x x
x x
√ √
√ √
√ √
x x
x x x x
x x
√ √
√ √
* In the 3-phase 3-wire (3Ph / 3W) respectively THD U12, THD U23, THD U31, THD U123
Page 59
58 User's manual
11 SOFTWARE UPGRADE
11.1 Upgrade of the meter website
Upgrade can be done via FTP server. You can upgrade the website in the tab Website upgrade. Copy the file ND30_upd.tar to the main folder of the meter. Then turn off and turn on the meter, i.e. reset the meter. The file ND30 upd.tar will be extracted
to the appropriate folders. It can take approx. 1 minute. The messages informing about the progress of extracting will be displayed on the meter screen.
a)
b)
. 32. View of the window a) logging on, b) website upgrade file
Fig
Page 60
59 User's manual
11.2 Firmware update - main program of the meter
A feature implemented in the ND30 meters enables to upgrade firmware using a PC with eCon software installed. Free eCon software and the update files are available by request from PCE Instruments. Upgrade of meter software (firmware) can be done via RS-485 interface. Go to UPDATER tab to upgrade.
Fig. 33. Program window view: a) eCon, b) software upgrade
Note: Software update automatically resets meter settings to default settings, so it is recommended to
save meter settings using eCon software before upgrading. After launching eCon software, set in the settings required serial port, baud rate, mode and address of the meter. Next, select the ND30 meter and click Config. Click the down arrow icon to read all of the settings then the disk icon to save the settings to a file (required to restore the settings later). After selecting the option Update firmware (in the upper right corner of the screen) the window Updater will be opened – Fig. 33b. Click Connect.
The Messages information window displays information concerning upgrade process. If the port is opened correctly, a Port opened message appears. Upgrade mode is enabled using either of the two methods: remotely via the Updater (using LPCon settings: address, mode, baud rate, COM port) and by turning a meter on while pressing the button (while entering bootloader mode the button is used to set communication settings: baud rate 9600, RTU8N2, address 1). The display will show the bootloader version, while the Updater program displays the message Device found and the name and version of the connected device. Click the "... button and browse to the meter upgrade file. If the file is opened correctly, File opened message is displayed. Press the Send button. When upgrade is successfully completed, the meter begins normal work while the information window displays Done message and upgrade elapsed time. After the Updater window is closed, go to parameter group Service parameters, select the option Set default settings of a meter and press a button Restore. Then press the folder icon to open a previously saved settings file and press the up arrow icon to save the settings in the meter. Current software version can be checked by reading the welcome message when switching the meter on.
Note: Turning meter supply off during upgrade may result in permanent damage!
Page 61
60 User's manual
12 ERROR CODES
During the meter operation the error messages may be displayed. Following list shows reasons of errors.
- Err bat – displayed when the battery of the internal RTC clock is used up. Measurement is
carried out after switching the supply on and every day at midnight. The message can be turned off by pressing the button . The disabled message remains inactive till the renewed switching of the
meter on.
- Err CAL, Err EE – meter memory is damaged. In such case a meter should be sent back to the manufacturer.
- Err PAr – incorrect operational parameters of the meter. In such case a meter should be set to default settings (from menu or via RS-485 interface). The message can be turned off by
pressing the button .
∧∧∧∧
∨∨∨∨
per overrun. Measuring value is out of the measuring range.
– up – lower overrun. Measuring value is out of the measuring range.
13 TECHNICAL DATA
Measuring ranges and permissible basic errors Table 22
Measuring value Measuring range L1 L2 L3 Class Current I 1/5 A 1 A~
5 A~
Voltage U L-N: 57.7 V~
110 V~ 230 V~ 400 V~
Voltage U L-L: 100 V~
190 V~ 400 V~
690 V~ Active power P -19999 MW .. 0.000 W .. Reactive power Q -19999 MVar .. 0.000 Var .. Apparent power S 0.000 .. 1999,9 VA .. Active energy EnP
/ import or export / Reactive energy EnQ / capacity or inductive / Apparent energy EnS 0.000 .. 99 999 999.999 kVAh
0.002 ..0.100..1.200 A
0.010 ..0.500.. 6.000 A ...100.00 kA (tr_I1)
5.700..11.500 ..70.000 V
11.000..22.000 ..132.00 V
23.000..46.000 .. 276.00 V
40.000..80.000 .. 480.00 V ...1920.0 kV
10.000 ..20.000..120.00
19.000 ..38.000..228.00 V
40.000..80.00 .. 480.00 V
69.000..138.00 .. 830.00 V ...1999.0 kV (tr_U1)
..19999 MW (tr_U1,tr_I1) ..19999 MVar (tr_U1,tr_I1) ..19999 MVA (tr_U1,tr_I1)
0.000 .. 99 999 999.999 kWh 0.51) (EN 61557-12)
0.000 .. 99 999 999.999 kVarh 1 (EN 61557-12)
V
0.2 (EN 61557-12)
0.2 (EN 61557-12)
0.5 (EN 61557-12)
0.5 (EN 61557-12) 1 (EN 61557-12)
0.5 (EN 61557-12)
0.5 (EN 61557-12)
Active power factor PF -1.00 .. 0 .. 1.00 1 (EN 61557-12) Factor tg -1.20 .. 0 .. 1.20 1 Frequency f 45.000 ..65.000 Harmonic distortion factor of voltage THDU, current THDI 0.0 .. 100.0
Harmonic amplitudes of voltage U of current I
...U
h2
h2 … Ih51
h51
,
0.0 .. 100.0% II (IEC61000-4-7)
Hz 0.1 (EN 61557-12)
% 5 (EN 61557-12)
Page 62
61 User's manual
tr_I - Current transformer ratio = Transformer primary current / Current transformer secondary current tr_U - Voltage transformer ratio = Transformer primary voltage / Voltage transformer secondary voltage
1)
Class 0.5 S acc. to EN 62053-22
Power consumption:
- in supply circuit
- in voltage circuit
- in current circuit
Readout field 3.5’’ TFT full-color screen, resolution: 320 x 240 pixel Relay outputs (A1, A2) 2 programmable relays, volt-free NO contacts, load capacity
Analog output (0 .. 20 mA) 1 output: 0… 20 mA (4…20mA) programmable Load resistance
Inputs (T1, T2) 2 x Pt100, 2-wire, -50 ..+400 °C, basic error 0.5 % Serial interface RS-485 Modbus RTU 8N2, 8E1, 8O1, 8N1. Address 1..247,
6 VA 0.5 VA 0.1 VA
(resistive) 0.5 A/250 V AC or 5 A/30 V DC Switching number: mechanical min. 5 ´ 10 6
ric min. 1 x 10 5
elect
400 . Voltage 10 V. Basic error 0.2%.
Baud rate 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbit/s Maximum response time: 600 ms
Ethernet interface 10/100 Base-T, RJ45 socket, web server. FTP Server
Modbus TCP/IP server, DHCP client
Sampling
A/D Converter 16-bit sampling rate 6.4 kHz at 50 Hz
7.68 kHz at 60 Hz
Simultaneous sampling of all loops, 128 samples per cycle
Harmonics
Harmonic (n) 1..51 Harmonic distortion factor referred to the voltage THD, current THD (n=2..51) 0.0 ..100.0% FFT analysis (Fast Fourier Transform)
Real Time Clock
Registration
±20 ppm, real time clock battery CR2032 Archiving period (registration interval) 1..3600 sec.
Registration activation modes: n_on, noFF, on,oFF, H_on, HoFF, 3non, 3noF, 3_on, 3_oF,
Registration time: depends on the configuration e.g. approx. 220 days for interval 1 sec.
Files archive memory 8 GB
Terminals
Cross section 0.05 .. 2.5 mm² Clamping screws M3
Tightening torque 0.5 Nm
Protection grade ensured by the housing
from the front IP 65 from terminals side IP 20
Weight 0.3 kg
Page 63
62 User's manual
Overall dimensions 96 x 96 x 77 mm Reference and rated operating conditions
- supply voltage 85..253 V a.c. (40..50..400 Hz), 90..300 V d.c. or 20..40 V a.c., 20..60 V d.c.
- input signal: 0 .. 0.1..1.2In; 0.1..0.2..1.2Un for current, voltage, PFi ,tg
frequency 45 ..50 .. 60 .. 65 Hz; sinusoidal (THD ≤ 8%)
- power factor -1...0...1
- ambient temperature -10..23..+55 oC, class K55 acc. to EN61557-12
- storage temperature -20..+70 oC
- humidity 0 .. 40 ..60 ..95% (no condensation)
- max. peak factor
- current 2
- voltage 2
- external magnetic field 40...400 A/m DC
3 A/m AC 50/60 Hz
- short-term overload
voltage inputs 5 sec. 2 Un current inputs 1 sec. 50 A
- working position any
- warm-up time 15 min.
i
Real time clock battery: CR2032 Additional errors:
in % of the base error
from ambient temperature changes < 50% / 10
for
Standards fulfilled by the meter:
Electromagnetic compatibility:
noise immunity in industrial environments acc. to EN 61000-6-2
noise emission acc. to EN 61000-6-4
Safety requirements:
isolation between circuits: basic
installation category III for voltage to earth up to 300 V
installation category II for voltage to earth up to 600 V
pollution grade 2,
maximum phase-to-earth operating voltage:
THD > 8% < 50%
radio-frequency common mode:
- level 2: 0,15… 1 MHz
- level 3: 1 MHz...80 MHz
according to EN 61010-1 standard
o
C
for supply circuits and relay outputs 300 V
Page 64
63 User's manual
for measurement input 500 V
for circuits RS-485, Ethernet, analog outputs: 50 V
altitude a.s.l. < 2000 m,
14 ORDERING CODE
ND30 network parameters meter ordering code.
Table 23
ND30 Meter- X X X X XX X X Input voltage (phase/phase-to-phase) Un
3x 57, 7/100 V, 3x 230/400 V 1 3x 110/190 V, 3x 400/690 V 2 Additional outputs/inputs 2 relays 1 2 relays, 1 analog output, 2 Pt100 inputs 2
Interfaces
RS485 1 RS485 and Ethernet interface, internal memory file system 2
Supply voltage:
85..253 V a.c., 90..300 V d.c. 1
20..40 V a.c., 20..60 V d.c. 2
Version
standard 00 custom-made* XX
Language version
Polish P English E other* X
Acceptance tests
without extra requirements 0 with quality inspection certificate 1 acc. to customer’s request* X
* only after agreeing with a manufacturer
ORDERING CODE EXAMPLE, the code ND30-1 2 2 1 00 E 0 means:
ND30 – ND30 meter, 1 – input voltage 3 x 57.7/100 V, 3 x 230/400 V, 2 – 2 relays, 1 analog output 0..20 mA, 2 inputs Pt100 2 – RS-485 and Ethernet, internal memory file system
1 – supply voltage: 85..253 V a.c., 90..300 V d.c.
00 – standard version E – English language version 0 – without extra requirements.
Loading...