12. MAINTENANCE AND GUARANTEE ........................................... 53
3
Page 3
1. APPLICATION
The
PCE-ND10 meter is a digital programmable panel
meter destined for the measurement of the 3-phase, 4-wire
power network parameters in balanced and
unbalanced systems. It is also capable of displaying
measured quantities and their simultaneous digital
transmission. The meter is also capable of controlling and
optimization of the power electronic devices, systems, and
industrial installations. The meter can be used for measuring:
RMS value of voltage and current; active, reactive and
apparent power; active and reactive energy, power
parameters; frequency, 15-, 30- and 60-minute mean active
power and THD. Additionally, a current in the neutral wire
is calculated from the phase current vectors . Voltage and
cur-rent values are multiplied by given voltage and current
ratios of measuring transformers. Power and energy
indications take into account all programmed ratio values. Any
and all measured values can be sent to the master via the
RS-485 interface. The relay outputs signal alarm when
selected parameters exceed set limits. Impulse output can
be used for consump-tion check of the 3-phase real energy.
This meter is also able to detect and signal incorrect phase
sequence. The meter is powered by the measuring
circuit, i.e. from the voltage output.
There is a galvanic separation between following units of
the meter:
- voltage and current inputs,
- RS-485 output,
- pulse output.
5
Page 4
2. METER SET
Complete set of the meter includes:
- PCE-ND10 Meter
- connection clamps
- user’s manual
1 pcs.
2 pcs.
1 pcs.
3. BASIC REQUIREMENTS AND
OPERATIONAL SAFETY
In the safety service scope, the transducer meets to
requirements of the EN 61010-1 standard.
•Always check the connections before turning the meter on.
•Removal of the meter housing during the warranty period
voids the warranty.
•This meter conforms to all requirements of the electromag-
netic compatibility in the industrial environment.
•Building power network should include switch or automatic
circuit breaker positioned in the convenient vicinity of the
meter. It should be properly marked and available to operator at all times.
6
Page 5
4. INSTALLATION
PCE-ND10 Meter is adapted to be mounted to the panel
with mounting brackets (see Fig. 1). Meter housing is made
of plastic.
Housing dimensions: 96 x 96 x 77 mm. On the outer side of the
meter there are screw and tab terminal strips that can be us
for connecting external wires with diameter up to 2.5 mm2.
Prior to installation a 92.5
+0.6
x 92.5
+0.6
mm slot must be made
in the panel. The thickness of the panel material should not
exceed 15 mm. The meter must be placed in the panel from
the front. During installation the powering voltage must be
off. When the panel is inserted in the slot, mount it in place
with provided mounting brackets.
Fig. 1. Meter tting.
ed
7
Page 6
96
22
92
76,7
69
Fig. 2. Meter dimensions.
5. METER DESCRIPTION
5.1. Current inputs
All current inputs are galvanically isolated (internal current transformers). The meter is suited to operate together with external
measuring current transformers. Displayed values of currents as
well as their derivative values are automatically calculated using
set ratio value of the external transformer. Current inputs are
speciedintheorderaseither1Aor5A.
5.2 Voltage inputs
Displayed values of voltages as well as their derivative values
are automatically calculated using set ratio value of the external
transformer.Voltageinputs are specied in the order aseither
3 x 57,7/100 V, 3 x 230/400 V or 3 x 290/500 V.
8
Page 7
5.3 Connection diagrams
OUT
Direct measurement
in a 4-wire network
PCE-ND10
9
Page 8
Semi-indirect measurement
in a 4-wire network
OUTimp
PCE-ND10
10
Page 9
Indirect measurement using
3 current transformers and 3 voltage
transformers in 4-wire network
OUT
PCE-ND10
Caution: It is recommended to connect PCE-ND10 meters
(RS-485) to a computer with a shielded wire. A shield should be
connected to ground in a single point. Shielded wire must be
used in case there are many interferences in the environment.
Fig 3. Connection diagrams of the meter in the 4‑wire
network.
11
Page 10
6. PCE-ND10 METER PROGRAMMING
6.1 Front panel
Fig. 4. Front panel.
Front panel description:
1 – cancel button (ESC)
2 – move left button
3 – decrease value button
4 – increase value button
5 – move right button
6–conrmbutton(ENTER)
7 – digital data transmission symbols
12
8 – connection / alarm symbols
9 – unit at displaying THD and power
guard
10 – THD value display symbols
11–powercoefcientandpower
tangent display symbol
Page 11
12 – mean active power value
display symbol
13 – menu safety symbol
14 – units of the displayed values
15 – 3-phase values display
symbol
16 – base values ratios
17–eldfordisplayingbase
values, power, THD, date,
mean values, frequency,
time and power guard
18 – min / max value symbols
19 – symbols of value-phase
connection
20 – power and energy characte ristics symbol
6.2 Power-on messages
After connection of voltage inputs the meter performs a
display test and displays the PCE-ND10 meter name, build
and current software version.
where: r n.nn is a number of the current software version or special build number.
b n.nn is a bootloader version number.
Fig. 5. Meter start messages
Caution! If the display shows Err Cal or Err EE message,
please contact the maintenance service.
13
Page 12
6.3 Parameter display
In the measurement mode, values are displayed
according to set tables. Pressing button
allows user to switch between displayed base values (Table 1).
Pressing button
button
are displayed, pressing the
or maximal values. When buttons
sed simultaneously, respective mean 3-phase values are displayed, together with minimal and maximal values (see Table 2).
RS-485 interface allows setting the values that are to be
displayed.
Error display is described in section 8.
When reactive power is displayed, this indication is accompanied by a symbol of the load: capacity load ( ) or inductive
load ( ).
Basevaluesdisplayedintheeld17(Fig.4.).Option(parameter)
shown in the Table 1 indicated that displaying of this parameter may be turned off in register 4056 via RS485. Turning this
parameter off (from U to tg) disables displaying their respective
mean / 3-phase values.
displays maximal value. When these values
displays minimal value and pressing
button resets all minimal
and are pres-
or
14
Page 13
L1, V
L1-2, V
L1, A
L1, W
L1, Var
L1, VA
Displayed
symbols
row 1U1U12I1P1Q1S1PF1tg1
row 2U2U23I2P2Q2S2PF2tg2
row 3U3U31I3P3Q3S3PF3tg3
Displayed values
Display
2-3
2
2
L
L2
L3
xedoptionalxedoptional
L
L3-1
L3
2
L
L
L3
L3
L1, PF
2
L
L
L3
L3
Table 1
L1, tg
2
2
kWh
L
L3
Imported
active
energy
Displayed
symbols
row 1
row 2
row 3
Displayed values
Display
Displayed
symbols
row 1
row 2
row 3
Displayed values
Display
-, kWh
Exported
active
energy
Hz
f(L3)
min
max
kVarhkVarh
reactive inductive
energy
/
reactive positive
energy
3L, W P
AVG
ΩP3-phase(15,30
or 60 min.)
min
max
1,THD U
L
L
2,
3
L
reactive capacitive
energy
/
reactive negative
energy
optional
A%Date/Time
I
(N)
min
max
optional
THD U1 %THD I1 %
THD U2 %THD I2 %
THD U3 % THD I3 %
Ordered
power con
sumption
(within 15, 30
or 60 min.)
-
L1, THD I
L
2,
3
L
Year
Month. day
Hours: minutes
Mean values and corresponding minimal and maximal values
(when pressed
ontherst8basevaluescreens,following
markers are highlighted: 3L, ,) .
15
Page 14
Table 2
Displayed
symbols
Displayed values
3L, V3L, V3L, A3L, W3L, Var 3L, VA 3L, PF 3L, tg
row
row
row
U
1
3-phase
2
3
LNav.
U
LLav.
3-phase
I
av.
3-phase
PQSPFtg
min
max
When upper limit of the indication range is exceeded, it is indicated by two horizontal lines in upper part of the display.
Conversely, when lower limit is exceeded, it is indicated by two
horizontal lines in the lower part of the display. When mean
powerismeasuredΣP
for 15-second quantum. Depending on chosen value (15 min, 30
separate measurements are made
3-phase
min, 60 min) calculated mean value is based on 60, 120 or 240
measurements. After the meter is turned on or after the power is
meter on or resetting. Until all probed values of the active power
are acquired, mean power value is calculated from values already
measured. Current in the neutral wire I(N) is calculated from
phase current vectors.
When alarms are activated, symbols A1 and/or A2 are displayed.
When alarms are deactivated and alarm signalization latch is
PCE-ND10 meters are configured with the use of LPConsoftware available for free on the https://www.pceinstruments.com/english/download-win_4.htm web site.
Fig 7. Setup menu.
Programming mode is enabled by pressing and holding
button for about 3 seconds. To enable the programming user
bust enter a correct access code. If there is not such a code,
the program transits into the programming option. Message SET (inthe rst row) and rst parameter group PA r are displayed.
User can view parameters at any time by pressing and holding
button for about 3 seconds.
18
Page 17
6.5.1 Setting of Meter Parameters
In options menu choose PAr (using
buttons)andconrmselectionwiththe
Item
1
2
3
4
5
name
arameter
P
Access
code entry
Current
transformer
ratio
Voltage
transformer
ratio
-
Mean ac
tive power
synchronization
Recording
minimal
-
and maxi
mal values
complete
with errors
Marking
SEC
tr_I1 … 100001
tr_U
Syn
erLio
Range
oFF,
1 … 60000
0.1 … 4000.01
Mean active power synchro
15, c_15,
c_30, c_60
FF
c_15 – measurement synchr
with clock every 15 min.
c_30 – measurement synchr.
with clock every 30 min.
c_60 – measurement synchr.
with clock every 60 min.
o
FF – recording only correct
values (within measurement
, on
on – recording all errors
occurring in measurements
(values in 1e20 and -1e20
or
button.
Notes/
description
0 – no code0
nization:
15 - 15-minute moving
window
range),
registers)
Table 3
Manufacturer’s
-
.
15
on
value
19
Page 18
6
7
8
9
10
11
Method of
reactive
energy
calculation
Display
panel illumination
Energy
counters
erasing
Mean acti
ve power
erasing
Ordered
power
Default
settings
En_qcAP, sIGn
oFF
diSP
En_0
P
A_0no, yESyES – erase powerno
PAor0 … 144.0
dEfno, yES
,1…60,
on
no, EnP, Enq,
ALL
cAP – inductive and capacity
energy
sIGn – positive and negative
energy
off, on, 1..60 – illumination
time (in seconds) from pres-
sing the button
no – no activity,
EnP – erase active energy,
Enq – erase reactive,
ALL – erase all energies
Power ordered to establish
power consumption in % of
rated power
Reverting to default (factory)
group settings
cAP
on
no
100
no
The automatic erasing of energy is carried out:
- for active energy when changing: voltage or current ratio;
- for reactive energy when changing: voltage or current ratio,
reactive energy calculation method;
Buttons
buttons
and are used for setting the values while
and are used for choosing position
of the number to be set. The active position is signaled by the
cursor. Set value can be accepted by pressing the
or canceled by pressing the
button. When value is to
button
be accepted, it is checked against the acceptable value range.
If the set value falls outside the allowable range, the meter
remains in parameter setting mode and the value is set to
the highest possible value (when entered value is too high)
or lowest possible value (when it is too low).
In Options choose ALr1 or ALr2modeandconrmyourselection
by pressing the
button.
Table 5
Item
Value on alarm
1
output (code as
in Tab. 6)
Alarm typeA1_t,
2
Lower value of
3
the input range
Upper value of
4
the input range
Time delay of the
5
switch reaction
name
Parameter
22
A1_n,
A2_n
A2_t
A1oF,
A2oF
A1on,
A2on
A1dt,
A2dt
Marking
Range
table 6P
n-on,
Fig. 8.n-on
n-oFF,
on,oFF,
H-on,
H-oFF
-144.0…
-144.0…
0…900 in seconds (for A1_n =
in % of the rated quantity
144.0
value
in % of the rated quantity
144.0
value
P_ord, delay occurs only
when alarm is activated)
Notes/
description
value
Manufacturer’s
99.0
101.0
0
Page 21
Alarm signaliza-
6
tion latch
Alarm re-activa-
7
tion block
Default settingsdEfno,
8
A1_S,
A2_S,
A1_b,
A2_b,
oFF, onWhen alarm signaliza-
tion latch is enabled
and the alarm state
ends, alarm symbol
is not turned off but
beginstoash.Alarm
symbolashesuntilit
is turned off by pressing
both and
buttons (for 3
seconds). This function
refers only to the alarm
signalization, so the
relay connectors will
operate without support
according to the selected
alarm type.
0 …
in seconds0
900
reverting to default
yES
(factory) group settings
no
The write of the value ALon lower than ALoF switches the alarm
off.
Selection of the monitored value:
Table 6
4015 register
Item / value in
Quantity type
element
Displayed
00oFFno quantity /alarm
disabled/
01
U
_1L1 phase voltage
outputs and
Value needed
alarm values
of percentage
for calculations
none
U
n [V] *
(100 %)
23
Page 22
02I_1L1 phase wire currentIn [A] *
03P_1L1 phase active powerUn x In x cos(0°) [W] *
04q_1L1 phase reactive
power
05S_1L1 phase apparent
power
06PF1L1 phase active power
factor
07tg1tgj factor of L1 phase1
08U_2L2 phase voltageUn [V] *
09I_2L2 phase wire currentIn [A] *
10P_2L2 phase active powerUn x In x cos(0°) [W] *
11q_2L2 phase reactive
power
12S_2L2 phase apparent
power
13PF2L2 phase active power
factor
14tg2tgj factor of L2 phase1
15U_3L3 phase voltageUn [V] *
16I_3L3 phase wire currentIn [A] *
17P_3L3 phase active powerUn x In x cos(0°) [W] *
18q_3L3 phase reactive
power
19S_3L3 phase apparent
power
20PF3L3 phase active power
factor
21tg3tgj factor of L3 phase1
Un x In x sin(90°) [var] *
Un x In [VA] *
1
Un x In x sin(90°) [var] *
Un x In [VA] *
1
Un x In x sin(90°) [var] *
Un x In [VA] *
1
24
Page 23
22U_Amean 3-phase voltageUn [V] *
3
3
3
3
23I_Amean 3-phase currentIn [A] *
24P
25q3-phase reactive power
26S
27PF_A3-phase active power
28tg_Atgj factor for 3 phases1
F
29
30
U
31
U
32U31phase-to-phase voltage
U
33
34P_Atmean active power3 x Un x In x cos(0°) [W]*
35P_ordused % of the ordered
36I_neneutral wire currentIn [A] *
3-phase active power
(P1+P2+P3)
Q1+Q2+Q3)
(
3-phase apparent
power (S1+S2+S3)
factor
rEqfrequency100 [Hz]
12phase-to-phase voltage
L1-L2
23phase-to-phase voltage
L2-L3
L3-L1
4_Amean phase-to-phase
voltage
active power (used
energy)
3 x
Un x In x cos(0°)
[W] *
3 x Un x In x sin(90°)
[var] *
Un x In [VA]*
3x
1
n [V] *
U
n [V] *
U
Un [V] *
U
n [V] *
100 [%]
*Un, In – voltage and current rated values
25
Page 24
a) n-on
b) n-oFF
c) On
d) OFF
Fig. 8. Alarm types (x – alarm no.): a),b) normal c) off d) on.
26
Page 25
Remaining types of the alarm:
H-on – always on;
H-oFF – always off.
Example 1 of alarm setting:
Set n-on alarm type for monitored quantity P – 3-phase active
power,
Version: 5 A; 3 x 230/400 V. Setting the alarm on after exceeding
3800 W, switching the alarm off after power drops to 3100 W.
Calculations: rated 3-phase active power: P = 3 x 230 V x 5 A
= 3450 W
3450 W – 100 % 3450 W – 100 %
3800 W – A1on % 3100 W – A1oF %
In conclusion: A1on = 110,0 % A1oF = 90,0 %
Set: Monitored quantity: P; type of alarm: n-on, A1on 110,0,
A1oF 90,0.
Example no 2 of alarm setting:
The value of ordered power consumption may be used for
the purpose of prior warning that ordered power might be exceeded. Ordered power consumption is calculated according
to time period set for the mean active power synchronization
and value of the ordered power. Pre-emptive alarm should
be set so that it indicates the possibility of exceeding ordered power of 1MW at 90 %
(900 s). Measuring current transformer 2500: 5A, voltage 230 V.
Peak max power consumption 1,5 MW.
Calculations:
PCE-ND10 meter active rated 3-phase power: P = 3 x kU x Un x
kI x In = 3 x 1 x 230 V x 500 x 5A = 1,725 MW g100 %.
Ordered-to-rated power ratio = 1 MW / 1.725 ≈ MW 57,97 %
of meter rated value (rounded down) - Pord;
assuming allocation of 15-minutes
27
Page 26
Alarm operation hysteresis: alarm should be activated at 90 %
to=10 %∗
[
1 MW∗900 s
1,5 MW
]
=60 s
1.5 MW
ordered power (A1on), and deactivated for e.g.: at 1 % lower
89 % (A1of).
Optimization of power limit function (delay at alarm activation):
alarm activation delay
A1on=90.% A1of=89.9%
Time of delay A1dt= 0 sec
Fig. 9 shows an example of how the consumed ordered active power parameter can be used to alarm activation. Delay time is set at 0 seconds (A1dt).
In presented example for the remaining 10 % of ordered power at
maximum power consumption, all devices could operate for additional
60 seconds without imposing penalties. If the delay time A1dt had been
set to 60 seconds, alarm would not have been activated.
Fig. 9. Measurement of used ordered 15 minutes’ active
power consumption synchronized with the clock,
with alarm set on a 90% consumption.
28
(A1dt).
Page 27
Set alarm as following: monitored quantity: A1_n = P_ord; alarm
type: A1_t = n-on; A1on = 90,0, AL1oF = 89,9; delay time A1dt
= 0 or 60 s; A1_s = 0; A1_b = 0. Parameters should be set as
following: tr_I = 500; Syn = 15 or c_15, and Pord = 57.9.
6.5.4 Setting Date and Time
In Options choose dAtE mode and conrm the selection with
button. Seconds are reset to 0 after hour and minute
values are set.
Table 7
Item
Parameter
name
1Hour, minutet_H0…23,
2Month, dayt_d1…12,
3Yeart_y2001 …
MarkingRange
0..59
1…31
2100
Manufacturer’s
value
00.00
1.01
2001
29
Page 28
7. SOFTWARE UPGRADE
Function enabling updating of software from the com-puter of
the PC with software eCon was implementation in meter PCE-
are accessible on the site https://www.pce-instruments.com/
english/download-win_4.htm. The connected to the computer
converter RS485 is required on USB to the updat-ing, e.g.: the
converter PCE-PD10.
Note! After updating the software, the manufacturer’s settings
of the meter should be set, so it is recommended to save the meter
parameters before updating using the software eCon.
30
Page 29
After starting eCon’s software COM port, baudrate,
transmission mode and adress should be set. It can be done in
Options. Then, PCE-ND10 meter should be selected from
Device. Push icon Load to read and save current settings.
Open window Updater – from Updating->Updating of devices
rmware. Push Connect. Update progress is shown in
Messages section. Text Port opened appear after correctly
opened port. Putting meter in update’s mode can be done in
two ways: remote from Updater (with settings from eCon –
port, baudrate, transmission mode and adress) or by turning
power on while button pressed. Meter display shows
the „boot” inscription with bootloader version, Updater shows
message „Device found” with name and current version of
firmware. Using button browse to the meter upgrade file.
If the file is opened correctly, a File opened message is
displayed. Press the Send button. When upgrade is
successfully completed, meter reverts to the default settings
and begins normal operation while the information window
displays Done message and upgrade elapsed time. Close
Updater and go to Restoration of default parameters. Select
checkbox and press Apply button. After the Updater window is
closed, press the Save icon to save all initially read
parameters. Current firmware version can be checked when
meter is power on.
Warning! Turning the meter off during upgrade process may
result in permanent damage!
PCE-ND10 meter has data contained in 16-bit and 32-bit
registers. Process variables and meter parameters are placed
in the address area of registers in a way depended on
the variable value type. Bits in 16-bit registers are numbered
from the youngest to the oldest (b0-b15). 32-bit registers include
num-bers of float type in IEEE-754 standard. Sequence of
Value set in the 16-bit register.
Register description is presented
in Table 9. Read and write registers.
Value is set in the two following 16-bit
registers. These registers contain the
same data as 32-bit registers from
7500 – 7659 range. Readout registers.
Bit sequence (1-0-3-2).
Value is set in the two following 16-bit
registers. These registers contain the
same data as 32-bit registers from
7500 – 7659 range. Readout registers.
Bit sequence (3-2-1-0).
Value set in the 32-bit register.
Register description is presented in
Table 10. Readout registers.
33
Page 32
Regi-
Table 9
Ope-
ster
ra-
ad-
tions
dress
4000RW0 … 60000Protection - password0
4001RWReserved
4002RW0...1200 [
4003RW1 … 10000Current transformer ratio 1
4004RW1 … 40000Voltage transformer ratio *1010
4005RW0...3
4006RWReserved
4007RW0.1
4008RWReserved
4009RW0.1
4010RW0 … 61
4011RW0..3
4012RW0.1Erasing of mean active power P
4013RWReserved
4014RW0.1Erasing of min. and max.0
RangeDescription
o
/oo]
Mean ordered power *10
nominal signals
Mean active power synchronization:
0 - 15-minute moving window
1 – measurement synchr. with
clock every 15 minutes,
2 – measurement synchr. with
clock every 30 minutes,
3 – measurement synchr. with
clock every 60 minutes
Max and min value saving
method: 0 – no errors,
1 – with errors
Reactive energy calculation
method:
0 – inductive and capacity energy
1 – positive and negative energy
Display panel illumination:
0 – off,
1-60 – illumination time in seconds from pressing the button;
61 – always on
Energy counters erasing
0 – no changes,
1 – erase active energies,
2 – erase reactive energies,
3 – erase all energies
AV
De-
fault
1000
0
0
0
61
0
0
34
Page 33
4015RW0.1...35
Quantity on the relay output of
alarm 1 (code as in Table 6)
Output type 1: 0 – n-on, 1– n-oFF,
4016RW0..5
2 – on, 3 – oFF, 4 – H-on,
5 – H-oFF
4017RW
4018RW
-1440...0...1440
o
[
/oo]
-1440...0...1440
o
[
/oo]
Lower value of the alarm 1 switch
of the rated input range
Upper value of the alarm 1 switch
of the rated input range
990
1010
Alarm 1 switch delay value
4019RW0...900 s
(for AL_n = P_ord – register 4015
= 35, delay occurs only at alarm
activation)
4020RW0.1Alarm 1 signalization latch0
4021RW0...900 sAlarm 1 re-activation block0
4022RW0.1..35
Quantity on the relay output of
alarm 2 (code as in Table 6)
Output type 1: 0 – n-on, 1– n-
4023RW0..5
oFF, 2 – on, 3 – oFF, 4 – H-on,
5 – H-oFF
4024RW
4025RW
-1440...0...1440
o
/oo]
[
-1440...0...1440
o
/oo]
[
Lower value of the alarm 2
switch of the rated input range
Upper value of the alarm 2 switch
of the rated input range
990
1010
Alarm 2 switch delay value (for AL_n
4026RW0...900 s
= P_ord – register 4015 = 35, delay
occurs only at alarm activation)
4027RW0.1Alarm 2 signalization latch0
4028RW0...900 sAlarm 2 re-activation block0
4029RW5000 … 20000
No. of impulses for the impulse
output
5000
4030RW1..247MODBUS Network Address1
4031RW0..3
Transmission mode: 0->8n2,
1->8e1, 2->8o1, 3->8n1
24
0
0
24
0
0
0
35
Page 34
4032RW0...3
4033RW0.1
4034RW0 … 2359Hour *100 + minutes0
4035RW101 … 1231Month * 100 + day101
4036RW2009 … 2100Year2009
4037RW0.1
4038RW0..15258
4039RW0..65535
4040RW0..15258
4041RW0..65535
4042RW0..15258
4043R0..65535
4044R0..15258
4045R0..65535
4046Reserved
4047Reserved
4048Reserved
4049Reserved
4050R0..65535
4051R0..65535
4052Reserved
4053R0..65535Serial number two older bytes-
Transmission speed: 0->4800,
1->9600, 2->19200, 3->38400
Upgrade change of transmission
parameters
Standard parameters save
(complete with reseting energy
as well as min, max and mean
power to 0)
Imported active energy,
two older bytes
Imported active energy,
two younger bytes
Exported active energy,
two older bytes
Exported active energy,
two younger bytes
Reactive inductive energy,
two older bytes
Reactive inductive energy,
two younger bytes
Reactive capacity energy,
two older bytes
Reactive capacity energy,
two younger bytes
Status Register –
see description below
Status Register 2 –
see description below
1
0
0
0
0
0
0
0
0
0
0
36
Page 35
4054R0..65535Serial number two younger bytes-
4055R0..65535Software version (*100)-
4056RW0..65535
4057Reserved
uantity parameters displayed 0xFFFF
Q
Brackets [ ] contain, respectively: resolution or unit.
Energy is made available in hundreds of watt-hours (var-hours)
in double 16-bit register, and for this reason, one must divide
them by 10 when calculating values of particular energy from
registers, e.g.:
Imported active energy = (reg. value 4038 x 65536 +
reg. value 4039) / 10 [kWh]
Exported active energy = (reg. value 4040 x 65536 +
reg. value 4041) / 10 [kWh]
Exported inductive energy = (reg. value 4042 x 65536 +
reg. value 4043) / 10 [kVarh]
Exported capacity energy = (reg. value 4044 x 65536
+ reg. value 4045) / 10 [kVarh]
37
Page 36
Status Register (address 4050, R):
Bit 15 – „1” – damage of non-volatile memory
Bit 14 – „1” – lack of calibration or invalid calibration
Bit 13 – „1” – error of parameter values
Bit 12 – „1” – error of energy values
Bit 11 – „1” – error of phase sequence
Bit 10 – current range „0” – 1 A ~; „1” – 5 A ~
Bit 9 Bit 8 Voltage range:
0 057.8 V ~
0 1 230 V~
Bit 7 – „1” – the interval of power averaging has not elapsed
Bit 6 – „1” – frequency for THD calculation outside ranges:
- 48 – 52 for 50 Hz,
- 58 – 62 for 60 Hz
Bit 5 – „1” – too low voltage to measure the frequency
Bit 4 – „1” – L3 phase voltage too low
Bit 3 – „1” – L2 phase voltage too low
Bit 2 – „1” – L1 phase voltage too low
Bit 1 – „1” – RTC
Bit 0 – „1” – relay output state „1” – on, „0” - off
38
Page 37
Status Register 2 – reactive power characteristics
(address 4051, R):
Bit 15...12 - reserved
Bit 11 – „1” – capacity 3L max,
Bit 10 – „1” – capacity 3L min.
Bit 9 – „1” – capacity 3L
Bit 8 – „1” – capacity L3 max.
Bit 7 – „1” – capacity L3 min.
Bit 6 – „1” – capacity L3
Bit 5 – „1” – capacity L2 max.
Bit 4 – „1” – capacity L2 min.
Bit 3 – „1” – capacity L2
Bit 2 – „1” – capacity L1 max.
Bit 1 – „1” – capacity L1 min.
Bit 0 – „1” – capacity L1
(address 4056, R/W):
Bit 15 – „1” – date and time display
Bit 14 – „1” – usage of ordered power display
Bit 13 – „1” – neutral wire current display
Bit 12 – „1” – mean active power display
Bit 11 – „1” – frequency display
Bit 10 – „1” – current THD display
Bit 9 – „1” – voltage THD display
Bit 8 – „1” – reactive inductive energy display
Bit 7 – „1” – reactive capacitive energy display
Bit 6 – „1” – active exported energy display
Bit 5 – „1” – active imported energy display
Bit 4 – „1” – power tangent display
Bit 3 – „1” – power factor display
Bit 2 – „1” – apparent power display
Bit 1 – „1” – reactive power display
Bit 0 – „1” – phase-to-phase volage display
39
Page 38
Table 10
Ad-
Address
of 16 bit
registers
6000/70007500R L1 phase voltageV
6002/70027501R L1 phase currentA
6004/70047502R L1 phase active powerW
6006/70067503R L1 phase reactive powervar
6008/70087504R L1 phase apparent powerVA
6010/70107505R L1 phase power factor (PF)-
6012/70127506R L1 phase reactive to active power ratio-
6014/70147507R L2 phase voltageV
6016/70167508R L2 phase currentA
6018/70187509R L2 phase active powerW
6020/70207510R L2 phase reactive powervar
6022/70227511R L2 phase apparent powerVA
6024/70247512R L2 phase power factor (PF)-
6026/70267513R L2 phase reactive to active power ratio-
6028/70287514R L3 phase voltageV
6030/70307515R L3 phase currentA
6032/70327516R L3 phase active powerW
6034/70347517R L3 phase reactive powervar
6036/70367518R L3 phase apparent powerVA
6038/70387519R L3 phase power factor (PF)-
6040/70407520R L3 phase reactive to active power ratio-
6042/70427521R Mean 3-phase voltageV
6044/70447522R Mean 3-phase currentA
6046/70467523R 3-phase active power (P1+P2+P3)W
6048/70487524R 3-phase reactive power (Q1+Q2+Q3)var
dress
of 32
bit
regi-
sters
Description
Operations
Unit
40
Page 39
6050/70507525R 3-phase apparent power (S1+S2+S3)VA
6052/70527526R Mean power factor (PF)-
6054/70547527R Mean reactive to active power ratio-
6056/70567528R FrequencyHz
6058/70587529R Phase-to-phase voltage L1-L2V
6060/70607530R Phase-to-phase voltage L2-L3V
6062/70627531R Phase-to-phase voltage L3-L1V
6064/70647532R Mean phase-to-phase voltageV
6066/70667533R
Active power, 3-phase, 15, 30, 60 minutes
(P1+P2+P3)
6068/70687534R THD U1%
6070/70707535R THD U2%
6072/70727536R THD U3%
6074/70747537R THD I1%
6076/70767538R THD I2%
6078/70787539R THD I3%
6080/70807540R Cosine of U1 and I1 angle-
6082/70827541R Cosine of U2 and I2 angle-
6084/70847542R Cosine of U3 and I3 angle-
6086/70867543R Mean 3-phase cosine-
6088/70887544R Angle between U1 and I1
6090/70907545R Angle between U2 and I2
6092/70927546R Angle between U3 and I3
6094/70947547R
6096/70967548R
6098/70987549R
6100/71007550R
6102/71027551R
Neutral wire current (calculated from
vectors)
Active 3-phase input energy (no. of register
7549overows,resetsto0afterreaching
99999999.9 kWh)
Active 3-phase input energy (counter counting up to 99999.9 kWh)
Active 3-phase output energy (no. of
register7551overows,resetsto0after
reaching 99999999,9 kWh)
Active 3-phase output energy (counter
counting up to 99999.9 kWh)
100
MWh
kWh
100
MWh
kWh
W
o
o
o
A
41
Page 40
6104/71047552R
Reactive 3-phase inductive energy (no. of
register7553overows,resetsto0after
reaching 99999999,9 kVarh).
100
Mvarh
6106/71067553R
6108/71087554R
6110/71107555R
6112/71127556R Reserved
6114/71147557R Reserved
6116/71167558R Reserved
6118/71187559R Reserved
6120/71207560R Time – hours, minutes-
6122/71227561R Time – month, day-
6124/71247562R Time - year6126/71267563R Usage of ordered power%
6128/71287564R Voltage L1 minV
6130/71307565R Voltage L1 maxV
6132/71327566R Voltage L2 minV
6134/71347567R Voltage L2 maxV
6136/71367568R Voltage L3 minV
6138/71387569R Voltage L3 maxV
6140/71407570R Current L1 minA
6142/71427571R Current L1 maxA
6144/71447572R Current L2 minA
6146/71467573R Current L2 maxA
6148/71487574R Current L3 minA
6150/71507575R Current L3 maxA
6152/71527576R Active power L1 minW
6154/71547577R Active power L1 maxW
Reactive 3-phase inductive energy (counter
counting up to 99999.9 kVarh)
Reactive 3-phase capacity energy (no. of
register7555overows,resetsto0after
reaching 99999999,9 kVarh)
Reactive 3-phase capacity energy (counter
counting up to 99999.9 kVarh)
kvarh
100
Mvarh
kvarh
42
Page 41
6156/71567578R Active power L2 minW
6158/71587579R Active power L2 maxW
6160/71607580R Active power L3 minW
6162/71627581R Active power L3 maxW
6164/71647582R Reactive power L1 minvar
6166/71667583R Reactive power L1 maxvar
6168/71687584R Reactive power L2 minvar
6170/71707585R Reactive power L2 maxvar
6172/71727586R Reactive power L3 minvar
6174/71747587R Reactive power L3 maxvar
6176/71767588R Apparent power L1 minVA
6178/71787589R Apparent power L1 maxVA
6180/71807590R Apparent power L2 minVA
6182/71827591R Apparent power L2 maxVA
6184/71847592R Apparent power L3 minVA
6186/71867593R Apparent power L3 maxVA
6188/71887594R Power factor (PF) L1 min-
6190/71907595R Power factor (PF) L1 max-
6192/71927596R Power factor (PF) L2 min-
6192/71947697R Power factor (PF) L2 max-
6196/71967698R Power factor (PF) L3 min-
6198/71987699R Power factor (PF) L3 max-
6200/72007600R Reactive to active power ratio L1 min-
6202/72027601R Reactive to active power ratio L1 max-
6204/72047602R Reactive to active power ratio L2 min-
6206/72067603R Reactive to active power ratio L2 max-
6208/72087604R Reactive to active power ratio L3 min-
6210/72107605R Reactive to active power ratio L3 max-
6212/72127606R Phase-to-phase voltage L1-2 minV
6214/72147607R Phase-to-phase voltage L1-2 maxV
6216/72167608R Phase-to-phase voltage L2-3 minV
6218/72187609R Phase-to-phase voltage L2-3 maxV
6220/72207610R Phase-to-phase voltage L3-1 minV
43
Page 42
6222/72227611R Phase-to-phase voltage L3-1 maxV
6224/72247612R Mean 3-phase voltage (min)V
6226/72267613R Mean 3-phase voltage (max)V
6228/72287614R Mean 3-phase current (min)A
6230/72307615R Mean 3-phase current (max)A
6232/72327616R 3-phase active power (min)W
6234/72347617R 3-phase active power (max)W
6236/72367618R 3-phase reactive power (min)var
6238/72387619R 3-phase reactive power (max)var
6240/72407620R 3-phase apparent power (min)VA
6242/72427621R 3-phase apparent power (max)VA
6244/72447622R Power factor (PF) min-
6246/72467623R Power factor (PF) max-
6248/72487624R
6250/72507625R
6252/72527626R Frequency minHz
6254/72547627R Frequency maxHz
6256/72567628R Mean phase-to-phase voltage (min.)V
6258/72587629R Mean phase-to-phase voltage (max.)V
6260/72607630R Active power, 3-phase, 15, 30, 60 minutes (min.)W
6262/72627631R Active power, 3-phase, 15, 30, 60 minutes (max.)W
6264/72647632R harmonic U1 / THD U1 minV/%
6266/72667633R harmonic U1 / THD U1 maxV/%
6268/72687634R harmonic U2 / THD U2 minV/%
6270/72707635R harmonic U2 / THD U2 maxV/%
6272/72727636R harmonic U3 / THD U3 minV/%
6274/72747637R harmonic U3 / THD U3 maxV/%
6276/72767638R harmonic I1 / THD I1 minA/%
6278/72787639R harmonic I1 / THD I1 maxA/%
6280/72807640R harmonic I2 / THD I2 minA/%
6282/72827641R harmonic I2 / THD I2 maxA/%
6284/72847642R harmonic I3 / THD I3 minA/%
6286/72867643R harmonic I3 / THD I3 maxA/%
Reactive to active power ratio (3-phase
mean min.)
Reactive to active power ratio (3-phase
mean max.)
-
-
44
Page 43
6288/72887644R Cos of U1 and I1 angle (min.)-
6290/72907645R Cos of U1 and I1 angle (max.)-
6292/72927646R Cos of U2 and I2 angle (min.)-
6294/72947647R Cos of U2 and I2 angle (max.)-
6296/72967648R Cos of U3 and I3 angle (min.)-
6298/72987649R Cos of U3 and I3 angle (max.)-
6300/73007650R Mean 3-phase cos (min.)-
6302/73027651R Mean 3-phase cos (max.)-
6304/73047652R U1 and I1 angle (min.)
6306/73067653R U1 and I1 angle (max.)
6308/73087654R U2 and I2 angle (min.)
6310/73107655R U2 and I2 angle (max.)
6312/73127656R U3 and I3 angle (min.)
6314/73147657R U3 and I3 angle (max.)
o
o
o
o
o
o
6316/73167658R Neutral wire current (min.)A
6318/73187659R Neutral wire current (max.)A
When lower limit is exceeded, a -1e20 value is displayed.
Conversely, when upper limit is exceeded, a 1e20 value is
displayed.
45
Page 44
9. ERROR CODES
During the meter operation, error messages may be
displayed. Following list shows causes of particular errors.
- Err1 – too low voltage or current during measurement:
- PF
, tgji, cos, THD less than 10% Un,
i
- PF
, tgji, cos less than 1% In,
i
- THD less than 10% In,
- f less than 10% Un,
- I
less than 10% In;
(N)
- bAd Freq – during THD measurement, when frequency value
is outside 48 – 52 Hz range for 50Hz and outside
58 – 62 Hz range for 60 Hz;
- Err bat – internal RTC battery. The measurement is carried out
after switching the supply on and every day at midnight.
Then the message may be turned off by pressing
the button. Then the message will be inactive until
the meter is turned off and on again;
- Err CAL, Err EE – meter memory damaged. In such case meter
should be sent back to the manufacturer.
- Err PAr – incorrect operational parameters of the meter.
In such case meter should be set to default (factory)
settings (from menu or via RS-485 interface). Message
can be disabled by pressing button.
- Err Enrg – incorrect energy parameters. Message can be
disabled by pressing button. Incorrect energy values are
set to 0.
46
Page 45
- Err L3 L2 – phase sequence error. Switch phase 2 and
phase 3 connections. Message may be disabled
by pressing the button. Then the message will be
inactive until the meter is turned off and on again;
-
– lower limit exceeded. Measured value is lower that
----
the lower measuring limit for a given quantity.
----
-
– upper limit exceeded. Measured value is higher that
the upper measuring limit for a given quantity
or measurement error occurred.
47
Page 46
10. TECHNICAL DATA
Measuring Ranges and Admissible Basic Errors
Measured
value
Current In
1 A
A
5
Voltage L-N
57.7 V
230 V
290 V
Voltage L-L
100 V
400 V
500 V
F
requency47.0 ... 63.0 Hz47,0 ... 63.0 Hz
Active power
Reactive power
Apparent power0,00 VA ... 9999 MVA1,0 VA ... 1,52 kVA