PCE Americas Inc.
1201 Jupiter Park Drive
Suite 8
Jupiter
FL-33458
USA
From outside US: +1
Tel: (561) 320-9162
Fax: (561) 320-9176
info@pce-americas.com
● measurement, display and archiving of ambient temperature, relative humidity, dew
point, absolute humidity, illuminance, total volatile organic compounds (TVOC),
CO2 concentration
● signaling of exceeding set alarm values
● programming logic alarm outputs with reaction to the selected input value.
● real-time clock function with clock supply support in case of the monitor power
failure
● registration of input signals in programmed time
● interface RS485
◦ protocol: Modbus RTU
● Ethernet 10/100 BASE-T
◦ protocol: Modbus TCP/IP, HTTP, FTP, MQTT
◦ services: web server, ftp server, DHCP client, SMTP client,
All quantities and configuration parameters are available through the embedded Web
server, if the parameter is not visible, set it in the tab Settings-> registers on the website.
1. Application
PCE-HT 422 monitor is designed for continuous measurement and
conversion of selected environmental parameters into a digital form (prot. Modbus
TCP/IP, Modbus RTU , HTTP). The monitor programming is possible with the
built-in web server. The monitor has an LCD display field with 2x16 characters. The
device allows you to send e-mail messages informing about the current environmental
parameters as well as events that cause exceeding the alarm values. The monitor is
powered via Ethernet - PoE (Power Over Ethernet) or standard DC jack.
Features of PCE-HT 422 monitor:
Page 5
PCE-HT 422 User’s Manua l
4
1 pc.
1 pc.
3. Basic requirements, operational safety
In terms of operational safety, the monitor meets the requirements of EN 61010-1.
Safety instructions
● The assembly and the installation of the electrical connections may be carried out
only by a duly qualified electrician.
● Before turning on the monitor verify the connections.
● The monitor is intended for installation and use in industrial electromagnetic
environments.
● A switch or a circuit-breaker should be installed in the building or facility. It should
be located near the device, easily accessible to the operator, and suitably marked.
Fig. 1. View of PCE-HT 422 monitor
2. What is included
● PCE-HT 422 monitor
● User’s manual
Page 6
PCE-HT 422 User’s Manua l
5
4. Fitting
4.1. Installation
Fig. 2 Location of mounting holes
4.2. External connections diagram
The monitor has 3 external slots:
- Ethernet port 10/100 base-T
- DC power socket ɸ5.5 / 2.1 mm
- RS485 interface disconnectable socket
and 1 button to reset the device to the standard parameters - "Reset"
PCE-HT 422 monitor is mounted on a wall using a screw connection. The
monitor housing consists of an upper and a lower part.
Page 7
PCE-HT 422 User’s Manua l
6
5. Operation
After wiring, mounting and powering the monitor is ready to work with factory
settings. The monitor can be programmed using the built-in web server, free eCon
software or through access to MODBUS registers.
The following parameters can be programmed in the monitor:
•Ethernet interface settings,
•Modbus settings,
•Archive settings,
•alarm settings,
•SMTP client settings - e-mail (only as unencrypted connection)
•MQTT settings
•system settings.
Caution: Do not remove the cover of the sensor as this may damage the device!
5.1. Messages after Switching the Supply on
After power is turned on the display shows the device and the manufacturer’s name
and software version. After about 4s the serial number of the device is displayed and after
subsequent 4s the IP address in the network, if the device has been connected to Ethernet
network - the address can be static or obtained from DHCP server.
Fig. 3. View of the upper part of PCE-HT 422 monitor
Page 8
PCE-HT 422 User’s Manua l
7
- restoring factory parameters - after pressing and holding the button for 10 seconds;
Note: each successive restoring of factory parameters enables or disables the service of
obtaining network address from a DHCP server, i.e. if the DHCP service is enabled and
restoring the factory parameters will be forced , the DHCP service will be disabled (you will
be informed about the change by a message on the display) and default static IP address
will be assigned to the device: 192.168.1.19 (subnet mask: 255.255.255.0), another
request for restoring the factory parameters will enable the DHCP server service -
the network parameters will be obtained dynamically from the server;
- displaying the current IP address of the monitor – occurs after a short press
of the button – about 1 sec.
Fig. 4. Startup messages of PCE-HT 422 monitor
5.2. Functions of the button
The device contains one physical button for restoring the factory settings or
displaying the current IP address of the monitor. This button is located on the connector
panel – fig. 3.
Page 9
PCE-HT 422 User’s Manua l
8
a)message about the monitor operation with DHCP
client enabled – the displayed IP address is the current
address of the monitor acquired from DHCP server;
b) message about the work of the monitor with disabled
DHCP client service - the displayed IP address is the
current address of the monitor set manually or the default
address (after restoring the default parameters); in order
5.3. Connection of the device – configuration
Configuration of the device is possible through free e-CON software, available on the
manufacturer's website (https://www.pce-instruments.com/english/download-win_4.htm).
Access to most configuration parameters is also available from the device's website via
the embedded HTTP server.
5.3.1. Connection of the monitor to the network equipped with a DHCP server
The easiest way to connect the PCE-HT 422 monitor to the Ethernet network is to
use an existing DHCP server in the network, which assigns the communication
parameters to the devices connected, i.e. IP address, subnet mask, gateway, DNS
address. In order to use the automatic configuration with DHCP server, make sure the
monitor is running with DHCP client service enabled - to do this, switch on the power of
the monitor and observe the initial messages:
to obtain the address from the DHCP server, restore the monitor to the factory parameters,
point 5.2, and restart the device - then a) message should be displayed with the IP
address obtained from the DHCP server.
In order to further configure the device a computer (tablet, phone) must be
connected to the same Ethernet network (also with DHCP client enabled - automatic
acquisition of IP address), open a web browser and in the browser address field type the
IP address displayed by PCE-HT 422. This will display the login screen to log the web server
that will allow further configuration - sign up to the administrator account, p. 5.6.3.2.
After gaining access to the full configuration we recommend that you disable the
DHCP client, leaving the acquired network parameters unchanged – IP address, subnet
mask, gateway, DNS address will be stored as static parameters.
Page 10
PCE-HT 422 User’s Manua l
9
5.3.2. Connecting the monitor to the network without using DHCP server
In order to use static configuration of network parameters, make sure the monitor is
running with the DHCP client service disabled - to do this switch on the power of the
monitor and observe the initial messages:
a)message about the monitor operation with DHCP client
service enabled – the displayed IP address is the current
address of the monitor acquired from DHCP server;
to set the a static IP address factory parameters should be
restored, p. 5.2, and the device should be restarted – then a message should be displayed
b) with the static default IP address.
b) a message about the monitor operation with disabled
DHCP client service - the displayed IP address is the current
address of the monitor set manually or the default IP
address (after restoring the default parameters), if the
displayed address is different from 192.168.1.19 the factory
defaults should be restored twice, p. 5.2;
In order to further configure the device a computer (tablet, phone) must be
connected to the same Ethernet network (or directly to the monitor) and the automatic
acquisition of network parameters must be disabled. Then, the static parameters
corresponding to the default network parameters of PCE-HT 422 must be manually
entered into the computer (tablet, phone p. 5.6.2 (the same subnet mask and any IP
address from the pool 192.168.1.X except for the address 192.168.1.19
assigned by default to PCE-HT 422). After the connection, open your web browser and
type in the address field of the browser the default IP address 192.168.1.19. This will
display the login screen to log the web server that will allow further configuration - sign up
to the administrator account, p. 5.6.3.2. After logging in to the monitor web server it is
possible to change the network parameters according to our needs - especially the IP
address must be changed to make sure that the monitor does not have the default IP
address, otherwise the configuration of other monitors working in the same Ethernet
network will be difficult.
5.4. Functions of the monitor
Monitor PCE-HT 422 performs the following functions:
•measurement of the ambient temperature and relative humidity,
•measurement of luminous,
•measurement of the total amount of volatile organic compounds,
•measurement of CO2 concentration,
•calculation of selected physical quantities: absolute humidity, dew point
•memory of minimum and maximum values measured and calculated:
Page 11
PCE-HT 422 User’s Manua l
10
◦ temperature,
◦ relative humidity,
◦ absolute humidity,
◦ dew point.
Table 1, 2 shows the symbols displayed on the LCD, and their meanings.
Table 1
SymbolDisplay modeMeaning
constantfile system internal memory installed and ready
for operation
flashingerror of file system internal memory
flashingfile system internal memory full
5.5. Description of PCE-HT 422 monitor reading field
Fig. 5 Description of the PCE-HT 422 monitor reading field
The PCE-HT 422 monitor is equipped with a backlit LCD display consisting of two
lines of 16 characters each. The top line of the display is used for the presentation of
measured values - temperature and relative humidity and to display status pictographs
of the file system internal memory. The bottom line of the display shows the internal
memory usage, status of alarms, time and date. The display (top line) cyclically
changes the displayed parameters. The change interval and displayed parameters are
configurable items.
Page 12
PCE-HT 422 User’s Manua l
11
flashingfile system internal memory installed and ready
for operation, active FTP connection
constantAlarm activity indicator - alarms 1, 2 active
Measuring ranges exceedings are indicated by displaying special characters on the top
line of the LCD:
●- lower exceeding of the range of the displayed value
●-upper exceeding of the range of the displayed value
5.6. Ethernet 10/100-BASE-T
PCE-HT 422 monitors are equipped with Ethernet interface for the connection
(using RJ45 slot) to a local or global network (LAN or WAN) and the use of network
services implemented in the monitors: Web server, FTP server, Modbus Slave TCP/IP,
SMTP client. In order to use the network services Ethernet parameters of the
monitor must be configured. Standard Ethernet parameters of the monitor are shown in
table 4. The basic parameter is the IP address of the monitor - by default
192.168.1.19, which must be unique within the network to which we connect the
device. The IP address can be assigned to the monitor automatically by DHCP
server present on the network provided that the option to acquire IP address from
DHCP servers is enabled in the monitor.
Page 13
PCE-HT 422 User’s Manua l
12
DHCP service is disabled by default, then the monitor initializes with the default IP address
allowing the user to change the IP address through the website.
Caution: The monitor allows for up to 10 connections simultaneously!! The applications
implemented in the monitor use from 1 to 2 connections:
● Modbus TCP/IP- 1 connection
● Web server - minimum 1 connection
● FTP server- 2 connections
● SMTP client- 1 connection
5.6.1. Connection of 10/100 BASE-T interface
To access the Ethernet services, it is required to connect the monitor to the network
via the RJ45 slot located at the top of the monitor, operating in accordance with TCP/IP.
Fig. 6 View and numbering of RJ45 slot pins
Description of the monitor RJ45 slot diodes function:
● U/FTP – twisted pair cable with each pair foiled,
● F/FTP – twisted pair cable with each pair foiled, additionally cable with foil shield,
● S/FTP (formerly SFTP) – twisted pair cable with each pair foiled, additionally cable
with wire mesh shield,
● yellow LED - illuminates when PCE-HT 422 is properly connected to the Ethernet
network
100 Base-T, does not light up when PCE-HT 422 is not connected to the network
or is connected to 10-Base-T network.
● green LED - Tx/Rx flickers when the monitor sends and receives data, illuminates
constantly when data is transmitted
In order to connect PCE-HT 422 to the network the user should use twisted pair cable.
Page 14
PCE-HT 422 User’s Manua l
13
● SF/FTP (formerly S-STP) – twisted pair cable with each pair foiled, additionally with
foil and wire mesh shield,
Categories of twisted pair cable according to the European standard EN 50173
minimum: Class D (category 5) - for high-speed local area networks, includes applications
using the frequency band up to 100 MHz. The description of the connection is shown in
table 3. For Ethernet interface the User should use twisted pair cable of STP type
(shielded) category 5 with RJ-45 connector with conductors colors (in accordance with the
colors described in table 3) acc. to the following standard:
Table 3
Conductor
no.
SignalConductor color acc. to standard
EIA/TIA 568AEIA/TIA 568B
1TX+white-greenwhite-orange
2TX-greenorange
3RX+white-orangewhite-green
4EPWR+blueblue
5EPWR+white-bluewhite-blue
6RX-orangegreen
7EPWR-white-brownwhite-brown
8EPWR-brownbrown
5.6.2. Ethernet interface default parameters
Table 4
No.NameDefault value
1.DHCPEnabled or disabled
(cycled when default parameters restoration is forced)
2.IP Address192.168.1.19
3.Subnet mask255.255.255.0
4.Default192.168.1.1
5.DNS8.8.8.8
● EIA/TIA 568A for both connectors at the so-called simple connection of PCE-HT
422 tothe network hub or switch,
● EIA/TIA 568A for the first connector and EIA/TIA 568B for the second connector at
the so-called patch cord connection (crossover) used, among others, when
connecting PCE-HT 422 to a computer.
Page 15
PCE-HT 422 User’s Manua l
14
5.6.2.1. Changing the parameters of Ethernet interface
Changing the parameters of the Ethernet interface is possible through the built-in
web server.
Fig. 7. View of the window to change the parameters of the Ethernet interface
● obtain device information (serial number, execution code, firmware version,
bootloader version, variant (standard or special),
● preview the current measured values,
● read the status of the device,
● select the language for the Web page,
● perform configuration of most parameters.
5.6.3 Web Server
PCE-HT 422 monitor provides its own Web server that allows remote
monitoring of measured values and remote configuration and readout of the monitor
status. With the web page the user can:
Page 16
PCE-HT 422 User’s Manua l
15
Access to the Web server is achieved by entering the monitor IP address in the web
browser, e.g .: http://192.168.1.19 (where 192.168.1.19 is the monitor address).
The standard port for web server is port "80". Server port may be changed by the user.
Caution: For proper web page operation a browser with JavaScript enabled and
compatible with XHTML 1.0 is required (all popular browsers, Internet Explorer, version 8
minimum).
5.6.3.1 General view
Fig. 8. General view of the main website
The function of each tile of the website:
1) The view of measurements and after clicking on the tile displaying graphs with
trends.
2) Ethernet interface settings.
PCE-HT 42x
Page 17
PCE-HT 422 User’s Manua l
16
3) Archive settings and information about memory usage and the process of data
dump to the file system memory.
4) Alarm settings and information about their status.
5) Information about the device, giving an individual name to the monitor.
6) Setting the time, LCD display and configuration of our displayed values - the groups
of 12 values of any registers of the monitor registers to which we can assign our
own name and display them as a separate tile on the website. Defined records can
be archived and control the alarms.
7) Email configuration.
8) Logging off, return to the login page.
9) Configurable device name
10) Changing the language
11) Time to log off during inactivity
Fig. 9. View of the window to configure the group of our own registers
Page 18
PCE-HT 422 User’s Manua l
17
Fig. 10. View of a tile displaying a group of our 12 values
5.6.3.2. Selection of Web server user
The monitor has two user accounts for the Web server secured by individual
passwords:
● user: ”admin”, password: ”admin” - access to configuration and the preview of
parameters
● user: ”user”, password: ”pass” - access to the preview of parameters only.
● user: "guest" - access to the preview of the measured values on the home page
only, log on to the guest account does not require entering a user name or
password, it is enough to select "Login as a guest” and then click on "Login"
Fig. 11. View of the login window to the website
Page 19
PCE-HT 422 User’s Manua l
18
Fig. 12. View of the message window informing that parameters has been
correctly recorded in the device
Fig. 13. View of the message window informing about incorrect data
of the web form
Calling the monitor IP address in the browser, for example http://192.168.1.19
will display the start window in the browser where the user must enter the name
and password. Additionally, you can log in to the "guest” account when you select “Login
as a guest” on the login page. "Guest” user account is
limited to view the measured values on the main page. Log off occurs after 5 minutes
of inactivity.
5.6.3.3. Messages to the user
The web server is equipped with a system of messages to the user. If the user tries
to save the settings into the monitor, a message is returned on the status of
such operation. For mobile applications there is a user notification system built-in
the web browser.
Page 20
PCE-HT 422 User’s Manua l
19
Fig. 14. View of the message window informing about lack of permission
to view the website content.
Fig. 15. View of the window of the file manager on the web server
In order to download the file, click the file icon, and to delete a file, click the trash
can symbol next to the file icon.
5.6.3.4. Access to the archive file through the web server
PCE-HT 422 allows for access to archive files through the file manager
implemented on the web server that allows the user to retrieve and delete individual
files. To start the archive file manager, click on the tile Archive, and then click the
button Browse arch. Files.
Page 21
PCE-HT 422 User’s Manua l
20
5.6.3.5 Logic alarms
Fig. 16. View of alarms configuration window
PCE-HT 422 is equipped with 2 logic alarm outputs. Each alarm can operate in one
of six modes. Fig. 17 shows the operation of alarm in the following modes: n-on, n-off, on,
off. The other two modes: h-on and h-off mean respectively, always On and always
Off. These modes are designed for manual simulation of alarm states.
Page 22
PCE-HT 422 User’s Manua l
21
AL_L - Lower threshold of the alarm
AL_H - Upper threshold of the alarm
Fig. 17. Types of alarms: a) n-on; b) n-off; c) on; d) off.
Caution: In the case of alarm types n-on, n- off, on, off entering AL_L > AL_H will disable
the alarm.
In the "alarm output" tab the user can decide what action will be performed following the
change of the alarm state:
- Buzzer – audible alarm
- E-mail address 1 – sending an e-mail to the recipient No. 1
- E-mail address 2 – sending an e-mail to the recipient No. 2
It is possible to simultaneously select several options at once.
Note: If the user selects the audible alarm for alarm number 1 (2), the same option should
not be selected for alarm 2 (1) !!!
5.6.4 FTP Server
FTP file sharing protocol is implemented in PCE-HT 422 monitors. The monitor
acts as a server, allowing clients to access the internal memory of the meter file system.
Access to files is possible using a computer, tablet with installed FTP
client or another device acting as FTP client. To transfer files using FTP the following
ports are normally used: "1025" - data port and "21" - command port. If necessary, the
user can change the port used by the FTP. Please note, that the configuration of the
server and FTP client ports must be the same.
Page 23
PCE-HT 422 User’s Manua l
22
FTP client program should work in passive mode, then the connection is
established fully by the client (the client chooses the data port). For file transfer with the
monitor it is possible to use maximum one connection at the same time, that is why the
maximum number of connections must be limited to "1” in the client program.
Fig. 18. View of FTP ports configuration window
5.6.4.1 Selection of FTP user
The monitor has two user accounts for the FTP server secured by individual
passwords:
•user: ”admin”, password: “admin” - access to files saving and reading
FTP user names can not be changed, however it is possible to change the
password for each user - it is recommended to change passwords for security reasons.
The password must contain a minimum of 4 characters. Password change is only possible
through the web page in "Ethernet” parameters group. Passwords can have a maximum of
8 characters. If the password is lost - making it impossible to use the FTP, the factory
defaults of the Ethernet interface must be restored through the Web site, or all settings can
be restored to the factory defaults using the "Reset" button point 4.2. All standard
parameters of the monitor including the Ethernet parameters and password for FTP server
users will be restored:
user ”admin” → password: ”admin” ;
user ”user” → password ”passftp”.
FileZilla can be used as the FTP client. By typing the monitor IP address in the address
field we can view and download archive files.
Page 24
PCE-HT 422 User’s Manua l
23
5.6.5 E-mail service
Caution:
SMTP proxy server must support AUTH PLAIN
authentication for unencrypted connection.
The service allows the user to send information about alarm events and information in the
form of regular short e-mail messages that contain the following information:
•The time at which the event occurred,
•The quantity that caused the event,
•The measured values which occurred at the moment of alarm status change,
•The name of the device from which the information was sent.
PCE-HT 422 monitors have been equipped with a function to send email
messages using SMTP. To send a message the user must provide authentication data to
SMTP proxy server. The server should be located in the same network as the device.
PCE-HT 422 monitor has a memory buffer allowing for storage of maximum of 20 e-
mail messages. If an e-mail can not be sent on a regular basis, for example, due to
lack of connection they are queued up one after the other until their number does not
exceed 20. When the limit is exceeded, the subsequent messages will be lost. In
the case of transmission errors, wrong configuration or other factors beyond the control
of the device (e.g. Anti-spam protection of SMPT server), the messages may not reach
the recipient.
Page 25
PCE-HT 422 User’s Manua l
24
1) SMTP server address, for example, "smtp.wp.pl"
2) Address of the sender, .eg. "MyName@gmail.com"
3) Username registered on the SMTP server
4) The password for the specified account on the SMTP server
5) The name of the first recipient to which the message is to be delivered
6) The name of the second recipient
7) The period of sending regular messages
Fig. 19. View of e-mail configuration window
The correct SMTP server port must be configured at "Ethernet" tile in "SMTP” tab.
For unencrypted connections usually ports 25 or 587 are used.
Fig. 20. View of SMTP port configuration window on "Ethernet” tile
To verify the configuration of e-mail, click on the "Send a test message" button on
"E-mail" tile and then, in order to determine the configuration errors, watch the messages
appearing in the upper left corner of the website.
Page 26
PCE-HT 422 User’s Manua l
25
5.6.6 Modbus TCP/IP
Table 5
NoDescription
Modbus RTU
(RS485)
Modbus TCP/IP
(Ethernet)
Default value
1.
Device address for MODBUS
protocol
1
2Baud rate
9600
3Transmission mode
RTU 8N2
4.Port number of Modbus TCP
502
5.
Time to close the port of Modbus
TCP/IP service [s]
60
6.
The maximum number of
simultaneous connections to
Modbus TCP / IP service
2
The device address is the address of the device for Modbus TCP / IP. By setting the
address of the monitor to "255" the monitor will skip the analysis of the address in Modbus
frame (broadcast mode).
Fig. 21 View of Modbus TCP configuration parameters on "Ethernet” tile
The implemented protocol is in accordance with the PI-MBUS-300 Rev G of Modicon
Company.
PCE-HT 422 monitors allow access to internal registers via Ethernet and
Modbus TCP/IP Slave. Modbus protocol functions and structure of the registers are
described in points 5.5.6.1 – 5.5.6.3. In order to set up a connection it is necessary to set
a unique IP address for the monitor and to set the connection parameters listed in table 5.
Page 27
PCE-HT 422 User’s Manua l
26
● 03 (03h) – readout of registers group.
● 04 (04h) – readout of input registers group.
● 17 (11 h) - identification of slave device.
Table 6
Address rangeValue typeDescription
6000-6198float (32 bits)Value is placed in two successive 16-bit registers. Registers
contain the same data as 32-bit registers of 7500 range.
Registers are read-only. Bytes order (B1,B0,B3,B2)
7000 -7198float (32 bits)Value is placed in two successive 16-bit registers. Registers
contain the same data as 32-bit registers of 7500 range.
Registers are read-only. Bytes order (B3,B2,B1,B0)
7500-7599float (32 bits)Value is placed in 32-bit register. Registers are read-only.
5.6.6.1. Description of implemented functions
PCE-HT 422 monitors have the following MODBUS functions:
5.6.6.2. Map of registers
In PCE-HT 422 monitor the data is placed in 16- bit registers. Process variables
and parameters of the monitor are located in the address space of registers in a
manner dependent on the type of the variable. Bits in 16-bit registers are numbered
from the youngest to the oldest (b0 ... b15). 32-Bit registers (4 Bytes) contain floating
point numbers in IEEE-754 standard. Order of bytes: B3 B2 B1 B0 – the oldest byte is
sent first. 16-Bit registers representing 32-bit values in two subsequent registers are
doubled in another address area with the following bytes order: B1 B0 B3 B2 (Tab. 6).
The map of the PCE-HT 422 monitor registers is presented below.
Caution: All given addresses are physical addresses. In some computer programs, logical
addressing is applied, then addresses must be increased by 1.
Page 28
PCE-HT 422 User’s Manua l
27
5.6.6.3. Read-only registers
32-bit
registers
(2 x 16)
32-bit
registers
(float)Name
Unit
Unit name
7000/60007500T
o
CMeasured temperature
7002/60027501RH%Measured relative humidity
7004/60047502DP
o
CCalculated dew point
7006/60067503 AHg/m3Calculated absolute humidity
7008/60087504
o
CTemperature of wet-bulb thermometer
7010/60107505hPASaturated vapor pressure
7012/60127506Enthalpy
7014/60147507Reserved
7016/60167508Reserved
7018/60187509Reserved
7020/60207510min T
o
CMinimum temperature
7022/60227511max T
o
CMaximum temperature
7024/60247512min RH%Minimum relative humidity
7026/60267513max RH%Maximum relative humidity
7028/70287514min DP
o
CMinimum dew point
7030/60307515max DP
o
CMaximum dew point
7032/60327516min AHg/m3Minimum absolute humidity
7034/60347517max AHg/m3Maximum absolute humidity
7036/60367518Device ID
7038/60387519Status
7040/60407520% of internal archive usage
Page 29
PCE-HT 422 User’s Manua l
28
7042/60427521Reserved
7044/60447522Progress of internal archive rewriting To the file
system
7046/60467523Current time-Current time
7048/60487524
Month, day
MMDD
Current date - month, day
7050/60507525Date - year
YYYY
Current date - year
7052/60527526Reserved
7054/60547527the amount of file system memory free space
(kB), value ”-1” means a memory error
7056/60567528Total storage capacity of file system memory
(kB), value ”-1” means no properly installed
memory
7058/6058
...7072/6072
7529-
7536
Reserved
7074/60747537The first defined register displayed
7076/60767538The second defined register displayed
7078/60787539The third defined register displayed
...…. ……….
7096/60967548The twelfth defined register displayed
7098/60987549EluxIlluminance
7100/61007550Reserved
7102/61027551TVOCppbTotal amount of volatile organic compounds
7104/61047552eCO2ppmCO2 concentration
5.6.7 MQTT Protocol
The PCE-HT 422 recorder has a built-in MQTT client, enabling the
export of measurement data to a master system based on the MQTT protocol.
Communication configuration requires setting the correct address of the MQTT server
(broker), the port on which the server is listening, the name of the device under which the
PCE-HT 422 recorder is to be visible in the parent system, and the name (topic)
under which the data from the recorder will be published. It is also possible to
specify at what time interval the data should be published. MQTT configuration is
available from the e-Con program level, available free of charge from the
manufacturer's website (https://www.pce-instruments.com/english/download-win_4.htm) .
Page 30
PCE-HT 422 User’s Manua l
29
Fig. 22 View of the MQTT parameter configuration window
Fig. 23. View oftheprogram toupgradethefirmware.
5.7. Firmware upgrade
PCE-HT 422-CLIENT
PCE-HT 422-DATA
PCE-HT 422 monitors implements a feature that allows the user
to upgrade the software using a PC. Free eCon software and update
files are available on the https://www.pce-instruments.com/english/download-
win_4.htm. RS-485 to USB converter connected to a computer is needed to
perform the upgrade, e.g.: PCE-PD10 converter.
Page 31
PCE-HT 422 User’s Manua l
30
Caution! After upgrading the software, set up the factory setting of
the monitor.
Caution: Software upgrade is only possible when the monitor is directly
connected to PC (no other Master devices connected to RS-485).
Caution: Turning off the power during the software upgrade may result in
permanent damage to the monitor!
5.8. Measured values archiving
5.8.1. The monitor memory structure
Prior to the upgrade, remove the housing of the device and connect the RS-485
conductors to the connector marked "BA"
After starting the eCon program the speed, mode, the monitor IP address and
RS-485 port must be set in the Communication tab. Then click the icon. Connect.
Then click the link Upgrade firmware which will display the window of UPDATER – Fig.
23. Click the Connect button Messages information window contains info about the
progress of the upgrade process. When the port is properly opened the display shows:
Port opened. Switching to the upgrade mode is performed remotely via UPDATER (based
on the settings in eCon or the website - address, mode, speed, COM port) - upgrade
according to the recommended communication parameters, i.e. speed 115200 kb/s, 8N2
mode. If the monitor establishes communication with UPDATER the following
message is displayed in UPDATER program Device found: PCE-HT 422 and the version
of the main program and the bootloader of the connected device, and the monitor display
will show the message "Device is ready." Then, while pressing the button „ ... ” load the file
with the new version of the software in UPDATER. When the file is properly opened,
UPDATER program displays information File opened. Press the Send button. During
upgrade, the percentage update progress is displayed on the bottom row of the
display. After successful upgrade the monitor switches to normal operation, and the
information window shows Done and the upgrade duration.
The current software version can also be checked by reading the greeting messages of
the monitor displayed after powering up.
PCE-HT 422 monitors are normally equipped with 4MB of internal memory for
storing the the current data recorded by the monitor. The monitor can record any
parameter of the 4 measured values - temperature, relative humidity, dew point and
absolute humidity. Additionally, the user can archive each of 12 defined displayed
quantities. Internal memory of the monitor allows for storage of 534336 records. If you
save by default 50% of
Page 32
PCE-HT 422 User’s Manua l
31
Minimum archiving period is 10 seconds.
Ar_L - Lower threshold of archiving
Ar_H - Upper threshold of archiving
the internal memory (or other value defined by the user), the archive is automatically
rewritten to the file system's memory. The memory is a circular buffer. After the memory is
full, the oldest data is overwritten. The internal archive can be read, copied and deleted.
PCE-HT 422 monitors have file system internal memory of the size of 8GB
(memory size of the file system can be increased on request or according to the
needs of the manufacturer) to which the data from the internal memory are automatically
rewritten in the form of files. Data can be downloaded via Ethernet using FTP or Web site.
5.8.2. Configuration of archiving
Website is used to configure the archiving parameters. Archiving can be continuous
and conditional. Triggering conditional archiving can be carried out in one of
four possibilities presented in Fig. 23 ( n-on, n-off, off, on). Continuous archiving is
activated by selecting h-on archiving type, and it is turned off by selecting the h-off option.
Fig. 23. Types of conditional archiving
5.8.3. File system internal memory
PCE-HT 422 monitors are equipped with file system internal memory. FAT and
FAT32 file systems are supported. During registration the monitor creates directories and
files of the file system in the internal memory. An example of the directory structure is
shown in Fig. 24.
Page 33
PCE-HT 422 User’s Manua l
32
Apart from the ARCH directory, in which the archived data is placed, SYSTEM
directory is also created on the card where the following files are located:
- start.txt - date and time of the file system internal memory installation (when the monitor
is restarted after power failure)
- manual.pdf - current user’s manual
- enarch.gif – graphic file with info about alarms / archiving configuration
Fig. 24. Directories structure in the memory.
Caution: If these files are deleted, some elements of the website - hints, instructions, may
not be displayed; these files can be removed after logging in FTP server to administrator
account.
Data in the memory is stored in files located in the directories with names
corresponding to the device name and the serial number - see Fig. 24. Whereas the
names of the files correspond to the date of recording and they have the following format
XXXX_YY.Dzz, where XXXX → year , YY → month. The format of the archive file
extension is Dzz, where "zz" is the subsequent number of the archive file from a given
month. For example, the first file in the archive in the month of May 2016 will be
2016_05.D00, the next file: 2016_05.D00 etc. Max. 32 files can be created for a given
month (*.D00 … *.D31). The file is changed automatically when the file size reaches
29 MB.
5.8.4. Structure of archive files
Files containing archived data in the internal memory of the file system are
structured as columns, where successive columns of data are separated from each other
by a tab character. The first line of the file contains the columns header. Data records are
sequentially arranged in rows and the fields of the record are separated from each other
by a tab character. View a sample archive file with archiving further 12 displayed values of
the user is shown in Fig 25.
Page 34
PCE-HT 422 User’s Manua l
33
Fig. 26. Sample data file
Subsequent fields included in the row describing the record have the following meaning:
● date – the date of the data registration, the date separator character is "-"
● time – hour, minute, second of the recorded data, time separator character is ” : ”
● T, RH, DP, AH, name1, user reg , ….– name of the value to be archived, the default
decimal separator character is ” . ” however, the separator can be changed to ” , ” by
selecting the proper option in the Archive window of the website.
Page 35
PCE-HT 422 User’s Manua l
34
–range of relative humidity (RH) measurement: 0...95 % without condensation
–intrinsic error of humidity processing: ±3% of the range for RH = 10...90%
±5% in the remaining range
–range of measurement of illuminance0...60000 lux
resolution 1 lux
–TVOC measuring range0...60000 ppb
resolution:
0...2008 ppb- 1 ppb
2008...11110 ppb- 6 ppb
11110...60000 ppb- 32 ppb
–measuring range for CO2 concentration400...60000 ppm
resolution :
400...1479 ppm- 1 ppm
1479...5144 ppm- 3 ppm
5144...17597 ppm- 9 ppm
17597...60000 ppm- 31 ppm
–hysteresis of humidity measurement: ± 1% RH
–basic range of temperature measurement (T): – 20...60 °C
–intrinsic error of temperature processing: ±0.6o C within the range 10...40o C
–- immunity to electromagnetic interferenceacc. to EN 61000-6-2
–- emission of electromagnetic disturbancesacc. to EN 61000-6-4
Safety requirements according to EN 61010-1 standard
–installation categoryIII
–degree of pollution2
–operating voltage relative to earth50V
–altitude< 2000m
Interface RS-485:
Page 37
PCE-HT 422 User’s Manua l
36
Parameters of DC power supply unit (option):
–voltage 6 V d.c. ± 5%
–maximum power 6W
[2]
–input voltage 90...253 V a.c.
–operating temperature 0...40 o C
[2]
–dimensions 63.6 x 29.5 x 45.6 mm
[2]
–cable length 1.4 m ± 10%
[2]
–plug ɸ5.5 / 2.1 mm
[1] air humidity without condensation
[2] power supply parameters can be changed
Page 38
PCE-HT 422 User’s Manua l
37
Table 8
Humidity and temperature monitor
XXXXXXXXXX
Power supply*:
6 V d.c.
1
6 V d.c. , PoE IEEE 802.3af
2
Accessories:
none
0
6 V d.c. power supply unit
1
Version:
0.0.0.0.0.0
Standard
XXXXXX
Special
Language:
Polish/EnglishM
other**X
Acceptance tests:
without additional requirements0
with quality inspection certificate1
acc. to customer requirementsX
Coding example:
7. Ordering code
PCE-HT 422
* - Monitors of PCE-HT 422 1XXXXXXXXX version require external supply voltage 6
V DC. Monitors of PCE-HT 422 2XXXXXXXXX version can be supplied both from
Ethernet interface through PoE (Power over Ethernet), and from external power supply 6 V
DC.
** - after agreeing with the manufacturer
PCE-HT 422 21000000M1 means a monitor supplied through PoE IEEE 802.3af and 6 V
DC with 6V DC power supply included in the set in the standard version in the Polish
and English language version with the Quality Inspection certificate.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.