PCE-HT 420monitor is designed for continuous
measurement and conversion of relative humidity and ambient
temperature into digital form (Modbus TCP/IP , HTTP protocols).
The monitor programming is possible with the built-in web server.
The monitor has an LCD display with 2x16 characters. The device
allows you to send e-mail messages informing about the current
environmental parameters as well as events that lead to exceeding
the alarm values. The monitor is powered via Ethernet - PoE
(Power Over Ethernet) or standard DC jack.
Features of PCE-HT 420 monitor:
●measurement, display and archiving of ambient temperature,
relative humidity, dew point and absolute humidity,
●signaling when set alarm values are exceeded
●programming logic alarm outputs with reaction to the selected
input value.
●real-time clock function with clock supply support in case of the
monitor power failure
All quantities and configuration parameters are available through
the embedded Web server, if the parameter is not visible, set it in
the tab Settings-> registers on the website.
Fig.1. View of PCE-HT 420 monitor:
2. The set of the monitor
●PCE-HT 420 monitor
●User’s manual
3. Basic requirements, operational safety
1 pc.
1 pc.
In terms of operational safety the monitor meets the
requirements of EN 61010-1.
Safety instructions
●The assembly and the installation of the electrical connections
may be carried out only by a duly qualified electrician.
Page 5
PCE-HT 420 (User's manual)
5 m
●Before turning on the monitor verify the connections.
●The monitor is intended for installation and use in industrial
electromagnetic environments.
●A switch or a circuit-breaker should be installed in the building or
facility. It should be located near the device, easily accessible to the
operator, and suitably marked.
4. Assembly
4.1. Installation
PCE-HT 420 monitor is mounted on a wall using a screw
connection. The monitor housing consists of an upper and a lower
part.
Fig.2 Location of mounting holes
4.2. External connections diagram
The monitor has 2 external slots:
- Ethernet por
- DC power socket
t 10/100 base-T
5.5 / 2.1 mm
and 1 button to reset the device to standard parameters - "Reset"
Page 6
PCE-HT 420 (User's manual)
Fig.3 View of the upper part of PCE-HT 420 monitor
5. Operation
6 m
After wiring, mounting and powering the monitor is ready to
work with factory settings. The monitor can be programmed with the
built-in web server.
The following parameters can be programmed in the monitor:
•Ethernet interface settings,
•Modbus settings,
•Archive settings,
•Alarm settings,
•SMTP client settings - e-mail (only as unencrypted connection)
•System settings.
Caution: Do not remove the cover of the sensor as this may
damage the device!
5.1. Messages after powering the monitor up
After powe
r is turned on the display shows the name of the d
evice
and the manufacturer and software version. After about 4s the serial
number of the device is displayed and after another 4s the IP
Page 7
PCE-HT 420 (User's manual)
7 m
address in the network, if the device has been connected to
Ethernet network - the address can be static or obtained from
DHCP server.
Fig. 4 Startup messages of PCE-HT 420 monitor
5.2. Functions of the button
The device contains only one physical button for
restoring the factory settings or displaying the current IP address of
the monitor. This button is located on the connector panel – fig. 3.
- restoring factory parameters - after pressing and holding the
button for 10 seconds; Note: each successive restoration of factory
parameters enables or disables the service of obtaining network
address from a DHCP server, i.e. if the DHCP service is enabled
and restoring the factory parameters will be forced , the DHCP
service will be disabled (you will be informed about the change with
a message on the display) and the default static IP address will be
assigned to the device: 192.168.1.19 (subnet mask:
Page 8
PCE-HT 420 (User's manual)
8 m
255.255.255.0), another request for restoring the factory
parameters will enable the DHCP server service - the network
parameters will be obtained dynamically from the server;
- displaying the current IP address of the monitor – after a short
press of the button – about 1 sec.
5.3. Connection of the device – configuration
5.3.1. Connection of the monitor to the network equipped with
a DHCP server
The easiest way to connect an PCE-HT 420
monitor to Ethernet is to use the existing DHCP server,
which assigns communication parameters, i.e. IP address, subnet
mask, gateway, DNS address to the devices
being connected. In order to use the automatic configuration
with a DHCP server, make sure the monitor is running with DHCP
client service enabled - to do so, switch on the power of the monitor
and observe the initial messages:
a)message about the monitor operation
with DHCP client enabled – the displayed
IP address is the current address of the monitor acquired from
DHCP server;
b) message about the monitor operation
with a DHCP client disabled – the
displayed IP address is the current
address of the monitor set manually or the default address (after
restoration of default parameters); in order to obtain an address
Page 9
PCE-HT 420 (User's manual)
9 m
from a DHCP server you must restore the monitor to factory
defaults, p. 5.2, and restart the device - then you should see the
message a) with the IP address acquired from DHCP server.
In order to further configure the device a computer (tablet,
phone) must be connected to the same Ethernet network (also
with DHCP client enabled - automatic acquisition of IP address),
open a web browser and in the browser address field type the IP
address displayed by PCE-HT 420. This will display the login
screen to log the web server that will allow further configuration sign up to the administrator account, p. 5.6.3.2.
After gaining access to the full configuration we recommend
that you disable the DHCP client, leaving the acquired network
parameters unchanged – IP address, subnet mask, gateway, DNS
address will be stored as static parameters.
5.3.2. Connecting the monitor to the network without using
a DHCP server
In order to use the automatic configuration with a DHCP server,
make sure the monitor is running with DHCP client service disabled
- to do so, switch on the power of the monitor and observe the initial
messages:
a)message about the monitor operation
with DHCP client service enabled – the
displayed IP address is the current address of the monitor acquired
from DHCP server; to set the a static IP address factory parameters
Page 10
PCE-HT 420 (User's manual)
10 m
should be restored, p. 5.2, and the device should be restarted –
then a message should be displayed b) with the static default IP
address.
b) a message about the monitor operation
with disabled DHCP client service - the
displayed IP address is the current
address of the monitor set manually or the default IP address (after
restoring the default parameters), if the displayed address is
different from 192.168.1.19 the factory defaults should be restored
twice, p. 5.2;
In order to further configure the device a computer (tablet,
phone) must be connected to the same Ethernet network
(or directly to the monitor) and the automatic acquisition of network
parameters must be disabled. Then, the static parameters
corresponding to the default network parameters of PCE-HT 420
must be manually entered into the computer (tablet, phone) p.
5.6.2 (the same subnet mask and any IP address from the pool
192.168.1.X except for the address 192.168.1.19 assigned by
default to PCE-HT 420). After the connection, open your web
browser and type the default IP address 192.168.1.19. in the
address field of the browser. This will display the login screen to
the web server of the monitor that allows further configuration –
sign up to the administrator account, p. 5.6.3.2.
After logging in to the monitor web server it is possible to change
the network parameters according to our needs - especially the IP
address must be changed to make sure that the monitor does not
Page 11
PCE-HT 420 (User's manual)
11 m
have the default IP address, otherwise the configuration of other
monitors working in the same Ethernet network will be difficult.
5.4. Functions of the monitor
Monitor PCE-HT 420 performs the following functions:
•measurement of the ambient temperature and relative humidity,
•calculation of selected physical quantities,
•memory of minimum and maximum values measured and
5.5. Description of PCE-HT 420 monitor reading field
PCE-HT 420 is equipped with a backlit LCD display consisting
of two lines of 16 characters each. The top line of the display is
used for the presentation of measured values - temperature
and relative humidity and to display status pictographs of the file
system internal memory. The bottom line of the display is used for
presentation of the state of the internal memory, alarm no. 1 status,
time and date. During normal operation the monitor displays
measured values alternately with their symbols.
Page 12
PCE-HT 420 (User's manual)
Fig. 5 Description of the monitor reading field
Tables 1, 2 show the symbols displayed on the LCD, and their
12 m
meanings.
SymbolDisplay modeMeaning
constantfile system internal memory installed and
ready for operation
flashingerror of file system internal memory
flashingfile system internal memory full
flashingfile system internal memory installed and
ready for operation, active FTP connection
constantalarm activity indicator - alarms 1, 2 active
When measuring ranges are overrun it is indicated by displaying
special characters on the top line of the LCD:
●- lower overrun of the range of the displayed value
●- upper overrun of the range of the displayed value
5.6.Ethernet 10/100-BASE-T
PCE-HT 420 monitors are equipped with Ethernet interface
for the connection (using RJ45 slot) to a local or global network
(LAN or WAN) and the use of network services implemented in the
monitors: Web server, FTP server, Modbus Slave TCP/IP, SMTP
client. In order to use the network services Ethernet
parameters of the monitor must be configured. Standard
Ethernet parameters of the monitor are shown in Table 4. The
basic parameter is the IP address of the monitor - by default
192.168.1.19, which must be unique within the network to which
we connect the device. The IP address can be assigned to the
monitor automatically by DHCP server present on the network
provided that the option to acquire IP address from DHCP server is
enabled. DHCP service is disabled by default, then the monitor
initializes with the default IP address
Page 14
PCE-HT 420 (User's manual)
14 m
allowing the user to change the IP address through the website.
Note: The monitor allows for up to 10 connections simultaneously!!
The applications implemented in the monitor use from 1 to 2
connections:
●Modbus TCP/IP- 1 connection
●Web server- minimum 1 connection
●FTP server- 2 connections
●SMTP client- 1 connection
5.6.1. Connection of 10/100 BASE-T interface
To access the Ethernet services, it is required to connect the
monitor to the network via the RJ45 slot located at the top of the
monitor, operating in accordance with TCP/IP.
Fig.6 View and numbering of RJ45 slot pins
Description of the monitor RJ45 slot diodes function:
●
yellow LED - illuminates when PCE-HT 420 is properly
connected to the Ethernet network 100 Base-T, does not light up
when PCE-HT 420 is not connected to the network or is connected
to 10-Base-T network.
●
green LED - Tx/Rx flickers when the monitor sends and receives
data, illuminates constantly when data is transmitted
In order to connect PCE-HT 420 to the network the User should
use
Page 15
PCE-HT 420 (User's manual)
15 m
twisted pair cable.
●U/FTP – twisted pair cable with each pair foiled,
●F/FTP – twisted pair cable with each pair foiled, additionally cable
with foil shield,
●S/FTP (formerly SFTP) – twisted pair cable with each pair foiled,
additionally cable with wire mesh shield,
●SF/FTP (formerly S-STP) – twisted pair cable with each pair foiled,
additionally with foil and wire mesh shield,
Categories of twisted pair cable according to the European
standard EN 50173 minimum: Class D (category 5) - for high-speed
local area networks, includes applications using the frequency band
up to 100 MHz. The description of the connection is shown in Table
3. For Ethernet interface the User should use twisted pair cable of
STP type (shielded) category 5 with RJ-45 connector with
conductors in colors (in accordance with the colors described in
table 3) acc. to the following standard:
●EIA/TIA 568A for both connectors at the so-called simple
connection of PCE-HT 420 to the network hub or switch,
●EIA/TIA 568A for the first connector and EIA/TIA 568B for the
second connector atthe so-called patch cord connection
(crossover) used, among others, when connecting PCE-HT420 to a computer.
1.DHCPEnabled or disabled
(cycled when default parameters
restoration is forced)
2.IP Address192.168.1.19
3.Subnet mask255.255.255.0
4.Gateway192.168.1.1
5.DNS8.8.8.8
5.6.2.1. Changing the parameters of Ethernet interface
nging the parameters of the Ethernet interface is possible
Cha
through the built-in web server.
Page 17
PCE-HT 420 (User's manual)
17 m
Fig.7 View of the window to change the parameters of the
Ethernet interface
5.6.3 Web Server
Monitor PCE-HT 420 provides its own Web server that allows
remote monitoring of measured values and remote
configuration and readout of the monitor status. With the web page
the user can:
●obtain device information (serial number, execution code,
firmware version, bootloader version, variant (standard or special),
●preview the current measured values,
●read the status of the device,
Page 18
PCE-HT 420 (User's manual)
18 m
●select the language for the Web page,
●perform configuration
Access to the Web server is achieved by entering the monitor IP
address in the web browser, e.g .: http://192.168.1.19 (where
192.168.1.19 is set at the monitor). The standard port for web
server is port "80". Server port may be changed by the user.
Note: For proper web page operation a browser with JavaScript
enabled and compatible with XHTML 1.0 is required (all popular
browsers, Internet Explorer, version 8 minimum).
Page 19
PCE-HT 420 (User's manual)
5.6.3.1 General view
19 m
Fig.8 General view of the main website
The function of each tile of the website:
1)The
view of measurements and after clicking on the tile graphs
with trends are displayed.
2)Ethernet interface settings.
3)Archive settings and information about memory usage and the
process of data dump to the file system memory.
4)Alarm settings and information about their status.
5)Information about the device, giving an individual name to the
monitor.
6)Setting the time, LCD display and configuration of our displayed
values - the groups of any of the 12 values of the monitor registers
Page 20
PCE-HT 420 (User's manual)
20 m
to which we can assign our own name and display it as a separate
tile on the website. Defined records can be archived and they
control the alarms.
7)Email configuration.
8)Logging off, return to the login page.
9)Configurable device name
10) Changing the language
11) Time to log off when inactive
Fig.9 View of the window to configure the groups of our own
records
Fig.10 View of a tile displaying a group of our 12 values
Page 21
PCE-HT 420 (User's manual)
21 m
5.6.3.2. Selection of Web server user
The monitor has two user accounts for the Web server secured by
individual passwords:
●user: ”admin”, password: ”admin” - access to configuration and
the preview of parameters
●user: ”user”, password: ”pass” - access to the preview of
parameters only.
●user: "guest" - access to the preview of the measured values on
the home page only, log on to the guest account does not require
entering a user name or password, it is enough to select "Login as a
guest” and then click on "Login"
Fig.11 View of the login window to the website
Calling the monitor’s IP address in the browser, for example
http://192.168.1.19 will display the start display in the browser
where the user must enter name and password. Additionally, you
can log in to the "guest” account, when you select "Login as a
guest" on the login page. "guest” user account is limited to view the
measured values on the main page. Log off occurs after 5 minutes
of inactivity.
5.6.3.3. Messages to the user
The web server is equipped with a system of messages
Page 22
PCE-HT 420 (User's manual)
22 m
to the user. If the user tries to save the settings
into the monitor, a message is returned on the status of such
operation. For mobile applications there is a user notification
system built-in the web browser.
Fig.12 View of the message window informing that
parameters have been correctly recorded in the device
Fig.13 View of the message window informing about incorrect
ata of the web form
d
Fig. 14 View of the message window informing about lack of
permission to view the website content.
Page 23
PCE-HT 420 (User's manual)
23 m
5.6.3.4. Access to the archive file through the web
server
PCE-HT 420 allows for access to archive files through the file
manager
implemented on the web server that allows the user to retrieve and
delete individual files. To start the archive file manager, click on the
tile Archive, and then click the button Browse arch. Files.
Fig.15 View of the window of the file manager on the web server
In order to download the file, click the file icon, and to delete a file,
click the trash can symbol next to the file icon.
5.6.3.5 Logic alarms
PCE-HT 420 is equipped with 2 logic alarm outputs. Each
alarm can
Page 24
PCE-HT 420 (User's manual)
24 m
operate in one of six modes. Fig. 17 shows the operation of alarm
in the following modes: n-on, n-off, on, off. The other two modes: hon and h-off mean respectively, always On and always Off. These
modes are designed for manual simulation of alarm states.
Fig. 16 View of alarms configuration window
Page 25
PCE-HT 420 (User's manual)
a) n-on
stan
Alarm status
alarmu
1
0
wyłczony
Disabled
AL_L
załczony
Enabled
AL_HWielkosterujca
25 m
c) off
stan
Alarm status
alarmu
1
załczonyzałczony
Enabled
0
wyłczony
Disabled
Enabled
WielkosterujcaAL_LAL_H
Controlling quantityControlling quantity
b) n-off
stan
Alarm status
alarmu
1
załczony
Enabled
0
Disabled
wyłczony
Wielko
Controlling quantity
sterujcaAL_LAL_HWielko steruj caAL_LAL_H
d) on
stan
Alarm
alarmu
status
1
0
wyłczonywyłczony
Disabled
Enabled
załczony
Disabled
Controlling quantity
AL_L - Lower threshold of the alarm
AL_H - Upper threshold of the alarm
Fig. 17 Types of alarms: a) n-on; b) n-off; c) on; d) off.
Note: In the case of alarm types n-on, n- off, on, off entering AL_L > AL_H will
disable the alarm.
In the "alarm output" tab the user can decide what action will be
performed following the change of the alarm state:
- Buzzer – audible alarm
- E-mail address 1 – sending an e-mail to recipient No. 1
- E-mail address 2 – sending an e-mail to recipient No. 2
It is possible to simultaneously select several options at once.
Note: If the user selects the audible alarm for alarm number 1 (2),
the same option should not be selected for alarm 2 (1).
5.6.4 FTP Server
FTP file sharing protocol is implemented in PCE-HT 420
monitors. The monitor acts as a server, allowing clients to
access the internal memory of the meter file system. Access to
files is possible using a computer, tablet with installed FTP client
or another device acting
Page 26
PCE-HT 420 (User's manual)
26 m
as FTP client. To transfer files using FTP the following ports are
normally used: "1025" - data port and "21" - command port. If
necessary, the user can change the port used by the FTP. Please
note,
that the configuration of the server and FTP client ports must be the
same.
FTP client program should work in passive mode, then the
connection is established fully by the client (the customer chooses
the data port). For file transfer with the monitor it is possible to use
maximum one connection at the same time, that is why the
maximum number of connections must be limited to "1” in the client
program.
Fig.18 View of FTP ports configuration window
5.6.4.1 Selection of FTP user
The monitor has two user accounts for the FTP server se
individual passwords:
•user: ”admin”,
password: “admin” - access to saving and reading
cured by
Page 27
PCE-HT 420 (User's manual)
27 m
files
•user: ”user”, password: ”passftp” - access to reading archive files
only.
FTP user names cannot be changed, however, it is possible to
change the password for each user - it is recommended to change
passwords for security reasons. The password must contain a
minimum of 4 characters. Password change is only possible
through the web page in "Ethernet” parameters group. Passwords
can have a maximum of 8 characters. If the password is lost making it impossible to use the FTP, the factory defaults of the
Ethernet interface must be restored through the Web site, or all
settings can be restored to the factory defaults using the "Reset"
button. 4.2. All standard parameters of the monitor including the
Ethernet parameters and password for FTP server users will be
restored:
user ”admin”
password: ”admin” ;
user ”user” password ”passftp”.
FileZilla can be used as the FTP client. By typing the monitor IP
address in the address field we can view and download archive
files.
5.6.5 E-mail service
PCE-HT 420 monitors have been equipped with a function to
send email messages using SMTP. To send a message a user
must provide authentication data to SMTP proxy server. It is
recommended that the server is located in the same network as the
device.
Page 28
PCE-HT 420 (User's manual)
28 m
Caution:
SMTP proxy server must support AUTH PLAIN
authentication for unencrypted connection.
The service allows a user to send information about alarm events
and information in the form of regular short e-mail messages that
contain the following information:
•The time at which the event occurred,
•The quantity that caused the event,
•The measured values which occurred at the moment of alarm
status change,
•The name of the device from which the information was sent.
PCE-HT 420 monitor has a memory buffer allowing for
storage of maximum 20 e-mail messages. If an e-mail cannot be
sent on a regular basis, for example, due to lack of connection
they are queued up one after the other until their number exceeds
20.
When the limit is exceeded, the subsequent messages will be lost.
In the case of transmission errors, wrong configuration or other
factors beyond the control of the device (e.g. Anti-spam protection
of SMTP server) messages may not reach their destination.
1)SMTP server address, for example, "smtp.wp.pl"
2)Address of the sender, .eg. "MyName@gmail.com"
3)Username registered on the SMTP server
4)The password for the specified account on the SMTP server
5)The name of the first recipient to which the message is to be
delivered
6)The name of the second recipient
Page 29
PCE-HT 420 (User's manual)
29 m
7)The period of sending regular messages
Fig. 19 View of e-mail configuration window
The correct SMTP server port must be configured at "Ethernet" tile
in "SMTP” tab. For unencrypted connections usually ports 25 or 587
are used.
Fig. 20 View of SMTP port configuration window on "Ethernet” tile
To verify the configuration of e-mail, click on the "Send a test
message" button on "E-mail" tile and then, in order to determine the
configuration errors, watch the messages appearing in the upper
left corner of the website.
Page 30
PCE-HT 420 (User's manual)
30 m
5.6.6 Modbus TCP/IP
PCE-HT 420 monitors allow access to internal registers via
Ethernet and Modbus TCP/IP Slave. Modbus protocol functions
and structure of the records are described in points 5.5.6.1 –
5.5.6.3. In order to set up a connection it is necessary to set a
unique IP address for the monitor and to set the connection
parameters listed in Table 5.
Table 5
No. DescriptionDefault value
1.
2.
3.
4.
Device address for MODBUS TCP/IP
Port number of Modbus TCP
Time to close the port of Modbus TCP/IP service [s]
The maximum number of simultaneous connections
to Modbus TCP / IP service
1
502
60
2
The device’s address is the address of the device for Modbus TCP /
By setting the address of the monitor to "255" the monitor will
IP.
skip the analysis of the address in Modbus frame (broadcast mode).
Page 31
PCE-HT 420 (User's manual)
31 m
Fig.21 View of Modbus TCP configuration parameters on "Ethernet”
tile
The implemented protocol is in accordance with the standard PIMBUS-300 Rev G of Modicon Company.
5.6.6.1. Description of implemented functions
PCE-HT 420 monitors have the following MODBUS functions:
●03 (03h) – readout of group of register.
●04 (04h) – readout of group of input registers.
●17 (11 h) - identification of slave device.
5.6.6.2. Map of registers
In PCE-HT 420 monitor the data is placed in 16- and 32-bit
registers. Process variables and parameters of the monitor are
located in the address space of registers in a manner dependent
on the type of the variable. Bits in 16-bit registers are
numbered from the
Page 32
PCE-HT 420 (User's manual)
32 m
youngest to the oldest (b0 ... b15). 32-Bit registers (4 Bytes) contain
floating point numbers in IEEE-754 standard. Order of bytes: B3 B2
B1 B0 – the oldest byte is sent first. 16-Bit registers representing
32-bit values in two subsequent registers are doubled in another
address area with the following bytes order: B1 B0 B3 B2 (Tab. 6).
The map of PCE-HT 420 registers is presented below.
Note: All given addresses are physical addresses.
In some computer programs, logical addressing is applied, then
addresses must be increased by 1.
Table 6
Address
range
6000-6198float (32 bits)Value is placed in two successive 16-bit
7000 -7198float (32 bits)Value is placed in two successive 16-bit
7500-7599float (32 bits)Value is placed in 32-bit register. Registers are
Value typeDescription
registers. Registers contain the same data as
32-bit registers of 7500 range. Registers are
read-only. Bytes order (B1,B0,B3,B2)
registers. Registers contain the same data as
32-bit registers of 7500 range. Registers are
read-only. Bytes order (B3,B2,B1,B0)
read-only.
Page 33
PCE-HT 420 (User's manual)
33 m
5.6.6.3. Read-only registers.
Value is
placed in
two
successive
16-bit
registers.
These
registers
contain the
same data
as 32-bit
registers of
7500 range.
7000/60007500To
Value is
placed in
32-bit
registers.
Name
Unit
Record(z)/readout(o)
o
CMeasured temperature
Table 7
Unit name
7002/60027501R
7004/60047502DPo
Ho%Measured relative humidity
o
CCalculated dew point
7006/60067503 AHog/m3Calculated absolute humidity
7008/60087504o
o
CWet bulb temperature
7010/60107505ohPASaturated vapor pressure
7012/60127506Enthalpy
7014/60147507Reserved
7016/60167508Reserved
7018/60187509Reserved
7020/60207510min To
7022/60227511
Current date - month, day
7052/60527526Reserved
7054/60547527othe amount of file system memory
available space (kB), value ”-1”
means a memory error
7056/60567528oTotal storage capacity of file system
memory (kB), value ”-1” means no
properly installed memory
7058/6058
...7072/6072
7074/60747537oThe fir
7529-
7536
oReserved
st defined register displayed
7076/60767538oThe second defined register
displayed
7078/60787539oThe third defined register displayed
...…. ……….
7096/60967548oThe twelfth defined register
displayed
5.7. Firmware upgrade
Software updates are available from PCE Instruments.
Page 35
PCE-HT 420 (User's manual)
35
m
5.8. Archiving measured values
5.8.1. The monitor memory structure
PCE-HT 420 monitors are normally equipped with 4MB of internal
memory for storing current data recorded by the monitor. The
monitor can record any parameter of the 4 measured values temperature, relative humidity, dew point and absolute
humidity. Additionally, a user can archive each of 12 defined
displayed quantities. Internal memory of the monitor allows for
storage of 534336 records. If the default 50% of the internal
memory is used (or other value defined by the user) the archive is
automatically rewritten to the file system memory. The memory is a
circular buffer. After the memory is full, the oldest data is
overwritten. The internal archive can be read, copied and deleted.
PCE-HT 420 monitors have file system internal memory of the size
of 8GB (memory size of the file system can be increased on request
or according to the needs of the manufacturer) to which the data
from the internal memory are automatically rewritten in the form of
files. Data can be downloaded via Ethernet using FTP or Web site.
Minimum archiving period is 10 seconds.
5.8.2. Configuration of archiving
Website is used to configure the archiving parameters. Archiving
can be continuous and conditional. Triggering conditional archiving
may be performed according to one of the four possibilities shown
in Fig. 23 (n-on, n-off, off, on). Continuous archiving is activated by
selecting h-on archiving type, and it is turned off by selecting the hoff option.
Page 36
PCE-HT 420 (User's manual)
36
m
a) n-on
Archiwizacja
Archiving
1
0
wył czona
Disabled
b) n-off
Archiving
Archiwizacja
1
załczona
Enabled
0
Ar_L
c) off
Archiwizacja
Archiving
załczona
Enabled
Ar_HWielkosterujca
Controlling quantity
1
załczonazałczona
Enabled
0
wyłczona
Disabled
Enabled
d) on
Archiwizacja
Disabled
wyłczona
Wielko
Controlling quantity
sterujcaAr_LAr_HWielko steruj caAr_LAr_H
Archiving
1
0
wył czonawyłczona
Disabled
Enabled
załczona
Disabled
Fig. 23 Types of conditional archiving
Wielko steruj caAr_LAr_H
Controlling quantity
Controlling quantity
Ar_L - Lower threshold of archiving
Ar_H - Upper threshold of archiving
5.8.3. File system internal memory
PCE-HT 420 monitors are equipped with file system internal
memory. FAT and FAT32 file systems are supported. During
operation the monitor creates file directories containing historical
data.
During registration the monitor creates directories and files of the
file system in the internal memory. An example of the directory
structure is shown in Fig. 24.
Fig. 24 Directories structure in the memory.
Page 37
PCE-HT 420 (User's manual)
37
m
Apart from the ARCH directory, in which the archived data is placed,
SYSTEM directory is also created on the card where the following
files are located:
-start.txt - date and time of the file system internal memory
installation (when the monitor is restarted after power failure)
- manual.pdf - current user’s manual
-enarch.gif – graphic file with info about alarms / archiving
configuration
Note: If these files are deleted, some elements of the website hints, instructions, may not be displayed; these files can be
removed after logging in FTP server to admin account.
Data in the memory is stored in files located in the directories with
names corresponding to the device name and the serial number see Fig. 24. Whereas the names of the files correspond to the date
of recording and they have the following format XXXX_YY.Dzz,
where XXXX
year , YY month. The format of the archive file
extension is Dzz, where "zz" is the subsequent number of the
archive file from a given month. For example, the first file in the
archive in the month of May 2016 will be 2016_05.D00, the next file:
2016_05.D01 etc. For a given month it is possible to create
maximum 32 files (*.D00 … *.D31). The file is changed
automatically when the file size reaches 29 MB.
5.8.4. Structure of archive files
Files containing archived data in the internal memory of
the file
system are structured as columns, where successive columns of
data are separated from each other by a tab character.
The first line of the file contains the columns header. Data records
are s
equentially arranged in rows and the fields of the record are
Page 38
PCE-HT 420 (User's manual)
38
m
separated from each other by a tab character. View a sample
archive file with archiving of further 12 user’s displayed values is
shown in Fig. 25.
Fig. 25 Sample data file
Subsequent fields included in a row describing the record
have the following meanings:
●date – the date of the data registration, the date
separator character is "-"
●time – hour, minute, second of the recorded data, time
separator character is ” : ”
●T, RH, DP, AH, name1, user reg , ….– name of the value
to be archived, the default separator character is ” . ”
however, the separator can be changed to ” , ” by selecting
the proper option in the Archive window of the website.
6. Additional accessories
PCE-HT 420 monitors are available with additional
accessories such as D.C. and PoE IEEE 802.3af. power
supply units Table 7 shows the available items with their codes.
Page 39
PCE-HT 420 (User's manual)
No. AccessoryAppearanceOrdering codeTechnical data
39
m
Table 8
1.6 VDC
power
supply unit
2.PoE
power
supply
20-072-00-00094Voltage: 6 V d.c. ± 5%
Maximum power: 6W*
Input voltage:
90...253 V a.c.
Operating temperature:
0...40oC*
Dimensio
63.6 x 29.5 x 45.6 mm*
Conductor length:
1.4 m ± 10%*
Plug: 5.5 / 2.1 mm
*power supply parameters can
change
20-090-00-00022Input voltage:
100 – 240 VAC
Input frequency:
47 – 63 Hz
Current consumption: 0.35 A
max.
for 240 VAC
Output voltage: 48 VDC
Power output: 15.4 W
Operating temperature: 0 –
40oC
Dimensio
Weight: 0.2 kg
ns:
ns: 140 x 65 x 36 mm
3.power
cordfor
PoE
power
supply
20-069-00-00146conductor length: 1.8 m
Page 40
PCE-HT 420 (User's manual)
7. Technical data
40
m
Basic parameters:
–measuring range of relative humidity (RH)
0...95 % without condensation
–intrinsic error of humidity processing
±3% of the range for RH = 10...90%
±5% in the remaining range
–hysteresis humidity measurement± 1% RH
–basic range of temperature measurement (T)– 20...60 °C
–intrinsic error of temperature processing
±0.6o C in the range of 10...40o C
±1.0o C
–calculated quantitiesabsolute humidity (a) [g/m
in the remaining range
dew point temperature (Td) [°C]
Ethernet Interface:10/100-Base-T
- max. number of simultaneous connections10
Nominal operating conditions:
3
]
– power s
upply6 V d.c.
or PoE IEEE 802.3af
– power c
–ambient temperature– 20...23
onsumption< 2 VA
–air relative humidity:< 95%
…60 °C
Page 41
PCE-HT 420 (User's manual)
41
–time of initial warm-up15 minutes
–degree of protection provided by housingIP 20
– mountingon a wall
– weight<0.3 kg
–dimensions(120 x 80 x 25) mm
–operating position:with sensor directed to
the bottom
Electromagnetic compatibility
–Immunity to electromagnetic interference:
acc. to PN-EN 61000-6-2
m
–emission of electromagnetic interference:
acc. to PN-EN 61000-6-4
Safety requirements according to PN-EN 61010-1 standard
–installation categoryIII
–degree of pollution2
–operating voltage relative to earth50V
–altitude< 2000m
Parameters of DC power supply unit (option):
–voltage 6 V d.c. ± 5%
–maximum power 6W
*
–input voltage 90...253 V a.c.
erating temperature 0...40 o C
–op
–dimensions 63.6 x 29.5 x 45.6 mm
–cord length 1.4 m ± 10%
–plug
5.5 / 2.1 mm
*
*
*
*power supply parameters can change
Page 42
PCE-HT 420 (User's manual)
8. Ordering code
42
m
Table 9
Humidity and temperature monitor PCEHT 420 type
Power supply*
6 V d.c.1
6 V d.c. , PoE IEEE 802.3af2
Accessories
none0
6 V d.c. power supply unit1
Version
Standard00
Special**XX
Language
PolishP
EnglishE
other**X
Acceptance tests:
without additional requirements0
with quality inspection certificate1
acc. to customer’s requirementsX
XXXXXX
* - Monitor of PCE-HT 420 1XXXXX version require external supply voltage of 6 V
d.c. Monitors of PCE-HT 420 2XXXXX version can be supplied both from Ethernet
interface through PoE (Power over Ethernet), and from external power supply 6 V
d.c.
** - only after agreement with the manufacturer
Coding example:
PCE-HT 420-2100P1 means a monitor supplied by PoE IEEE
802.3af and
6 V d.c. with 6 V d.c.
power supply unit included in
standard version with Polish language version and quality
inspection certificate.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.