PCE Instruments PCE-GPA 62-ICA Users guide

Page 1
Graphic AC Power Analyzer
PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 [email protected]
www.pce-instruments.com/english
www.pce-instruments.com
PCE Instruments UK Ltd.
Southpoint Business Park
Hampshire / Southampton
United Kingdom, SO31 4RF
Units 12/13
Ensign way
From outside UK: +44
Tel: (0) 2380 98703 0
Fax: (0) 2380 98703 9
PCE-GPA 62
Users Manual
Page 2
Caution, risk of danger. Refer to accompanying documents
Caution, risk of electric shock.
Double Insulation
Application around and removal from HAZARDOUS LIVE conductors is permitted.
Earth (ground)
AC (Alternating Current)
DC (Direct Current)
Both direct and alternating current
Conforms to relevant European Union directives.
Do not dispose of this clamp meter as unsorted municipal waste. Contact a qualified recycler for disposal.
SYMBOLS showed on the clamp meter or in this manual:
Page 3
EN 61010-2-032 CAT III 600V Pollution Degree 2
WARNING: If the flexible tester is used in a manner
Not specified by the manufacturer, the protection Provided by the clamp meter may be impaired.
Overvoltage Category I (CAT I):
Equipment for connection to circuits in which measures are taken to limit the transient overvoltages to an appropriate low level.
Overvoltage Category II (CAT II):
Energy-consuming equipment to be supplied from the fixed installation.
Overvoltage Category III (CAT III):
Equipment in fixed installations.
SAFETY INFORMATION: (Read First Before Operation)
Please follow the following instructions carefully for safe operation.
■ NEVER use the clamp meter for Voltages higher than 600V.
■ DO NOT hold the clamp meter beyond its tactile barrier.
■ DO NOT use the clamp meter and accessories if they look
damaged.
■ USE CAUTION when working with high voltages.
■ USE CAUTION when measuring the voltages higher than
30VAC rms or 60VDC. These voltages pose a shock hazard.
■ USE EXTREME CAUTION when working around bare
conductors or bus bars.
■ ALWAYS use the clamp meter as the instructions in the manual.
Page 4
TABLE OF CONTENTS
I. FEATURES ................................................................................................................ 1
II. PANEL DESCRIPTION ............................................................................................ 2
III. OPERATING INSTRUCTIONS .............................................................................. 4
III.1 Setup ................................................................................................................... 4
III.2 Measurement of RMS value, THD-F and Harmonics of ACV ....................... 13
III.3 Measurement of RMS value, THD-F and Harmonics of ACA ....................... 16
III.4 Waveforms of ACV and ACA with Phase Angle (φ) ........................................ 19
III.4.1 Waveform of ACV with Peak Value .......................................................... 20
III.4.2 Waveform of ACA with Peak Value .......................................................... 21
III.5 Measurement of Single Phase AC Power Quality .......................................... 22
III.5.1 True Power (W) and Power Factor (PF) .................................................. 23
III.5.2 Apparent Power (VA, KVA) and Reactive Power (VAR, KVAR) ............. 23
III.5.3 Maximum Demand (KW and KVA) .......................................................... 24
III.5.4. Energy (KWh, PFh, KVARh, and KVAh) ................................................. 24
III.5.5 Phasor Diagram ........................................................................................ 24
III.5.6 RMS values of Voltage and Current ......................................................... 25
III.6 Measurement of Balanced 3 Phase AC Power Quality ................................. 26
III.6.1 AC Watt (W) and Power Factor (PF) ........................................................ 26
III.6.2 Apparent Power (VA, KVA) and Reactive Power (VAR, KVAR) ............. 27
III.6.3 Maximum Demand (KW and KVA) .......................................................... 27
III.6.4 Energy (KWh, PFh, KVARh, and KVAh) .................................................. 27
III.6.5. Phasor Diagram ....................................................................................... 28
III.6.6. RMS values of Voltage and Current ........................................................ 28
IV. DATALOGGING OF VOLTAGE (RMS VALUE) AND HARMONICS ............... 29
IV.1 Scheduled Datalogging ............................................................................... 29
IV.2 Immediate Datalogging ................................................................................ 32
V. DATALOGGING OF CURRENT (RMS VALUE) AND HARMONICS ............... 33
V.1 Scheduled Datalogging ................................................................................ 33
V.2 Immediate Datalogging ................................................................................. 35
I
Page 5
VI. DATALOGGING OF VOLTAGE AND CURRENT WAVEFORMS ................... 36
VI.1 Datalogging of both Voltage and Current Waveforms ............................... 36
VI.2 Datalogging of Voltage Waveform .............................................................. 37
VI.3 Datalogging of Current Waveform .............................................................. 38
VII. DATALOGGING OF TRANSIENT DETECTION .............................................. 39
VIII. DATALOGGING OF AC POWER ..................................................................... 44
VIII.1 Scheduled Datalogging ............................................................................. 44
VIII.2 Immediate Datalogging ............................................................................. 46
IX. CLEAR DATA MEMORY ...................................................................................... 47
X. RS-232 INTERFACE PROTOCOL ....................................................................... 47
XI. SPECIFICATIONS (23C±5
XII. BATTERY REPLACEMENT ............................................................................... 52
XIII. MAINTENANCE & CLEANING ......................................................................... 54
C) ............................................................................ 48
II
Page 6
I. FEATURES
a. Power Quality Analysis for Single and Balanced Three Phase System. b. Harmonic Analysis of Voltage and Current (1 to 50th order). c. True RMS measurement of V with 0.5% of reading basic accuracy. d. True RMS measurement of A with 1% of reading basic accuracy e. Graphic Waveform of Voltage and Current f. Graphic Phasor Diagram g. Transient Detection and Logging of Swell, Dip, and Outage. h. Fast peak function (39μs for 50 Hz, 33μs for 60Hz). i. Active (W, KW, HP), reactive (VAR, KVAR) and apparent (VA, KVA) power j. Power factor (PF), phase angle (Φ), and energy (WH, KWH, KVARH, PFH). k. Measurement of balanced 3Φ Power Quality. l. Programmable VT ratio from 1 to 3000. m. Hold functions. n. Auto power off function in 15 minutes (selectable). o. Datalogging and Download to a PC. p. Optical isolated USB data connection. q. Unlimited datalogging facility on a PC.
1
Page 7
II. PANEL DESCRIPTION
600V
COM
V
L1
L3
1. Jaw Assembly
2. Trigger Press the trigger to open the jaw assembly.
3. HOLD/CANCEL/BACK LIGHT Press this button to HOLD the display in LCD, or turn the backlight on or off. It is also used to delete harmonics in the harmonics configuration
4. Rotary Switch Select setup, measurement of current, voltage, transient detection, or power. Turn the unit on or off.
5. LCD This is a dot matrix LCD with backlight.
2
Page 8
6. + ► Button . Increment value by 1 . Move the reference axis up . Move the line cursor right to previous harmonics . Page up to next transient events
7. REC Press this button to start Datalogging. Press again to stop. Holding the button and turning the power on will clear the data memory. It is also used to add harmonics in the harmonics configuration.
8. - ◄ Button . Decrement value by 1 . Move the reference axis down . Move the line cursor left to next harmonics . Page down to next transient events
9. FUNC Button Press this button to select different display.
10. V Input Terminal This terminal is used as input for voltage.
11. COM Terminal This terminal is used as common voltage reference input.
12. RS-232 window and Battery Cover
3
Page 9
III. OPERATING INSTRUCTIONS
III.1 Setup
Move the rotary switch to the SETUP position. Users should setup the parameters
of the meter before use.
4
Page 10
CURRENT TIME: There is a calendar clock inside the meter. Users should setup the correct time.
HOUR
MINUTE
SAMPLE: Setup the sampling interval in seconds for Datalogging.
START TIME: schedule when to start datalogging
5
Page 11
HOUR
MINUTE
STOP TIME: schedule when to stop datalogging
HOUR
6
Page 12
MINUTE
VT: set the ratio of voltage transformer, normally 1.
V (reading) = Voltage * VT
MD: set the time interval form maximum demand in minutes (1 to 60 minutes),
normally 15.
7
Page 13
HZ: set the operating frequency to 50Hz, 60Hz, or Auto.
AUTO POWER OFF: enable (1) or disable (0) auto-power-off function.
TRANSIENT REFERENCE: set the nominal voltage and threshold (%) for
transient capture.
NOMINAL VOLTAGE
8
Page 14
TOLERANCE
9
Page 15
HARMONICS CONFIGURATION: select the harmonics to be logged.
NOTE: The unit will adjust the sampling time according to the amount of harmonics to be logged
10
Page 16
WAVEFORM CONFIGURATION: set the points to be logged for each cycle of
NOTE: The unit will adjust the sampling time according to the processing time
required to log waveform.
the waveform. There are four options, 32, 64, 128, and 256.
DATE: set the date of the internal calendar clock.
YEAR
11
Page 17
MONTH
DAY
12
Page 18
III.2 Measurement of RMS value, THD-F and Harmonics of ACV
L3
L1
V
COM
600V
NOTE: If the peak value of the input AC voltage is greater than the maximum value of the range, then symbol of OL will be displayed.
Voltage:
a. Set the rotary switch at V position. b. Insert the test leads into the input jack. Connect the test prods of the test
leads in PARALLEL to the circuit to be measured.
13
Page 19
%THD-F: Total Harmonic Distortion with respect to Fundamental frequency %THD-F = (√(V22+ V32 + … +V492+ V502)) / V1) * 100 Where, V1: magnitude at the nominal frequency (eg.50 or 60 Hz) V2: magnitude at the second harmonics … V50: magnitude at the 50-th harmonics.
14
Page 20
NOTE: Frequency (Hz) is displayed in the second page (Harmonics order 25th to
50th order).
15
Page 21
III.3 Measurement of RMS value, THD-F and Harmonics of ACA
WARNING: Make sure that all the test leads are disconnected from the meter's
terminals for current measurement.
a. Set the rotary switch at A position. b. Clamp on to the conductor, and read the data from LCD display.
16
Page 22
%THD-F: Total Harmonic Distortion with respect to Fundamental frequency %THD-F = (√(V22+ V32 + … +V492+ V502)) / V1) * 100 Where, V1: magnitude at the nominal frequency (eg.50 or 60 Hz) V2: magnitude at the second harmonics … V50: magnitude at the 50-th harmonics.
17
Page 23
NOTE: Frequency (Hz) is displayed in the second page (Harmonics order 25th to 50th order).
18
Page 24
III.4 Waveforms of ACV and ACA with Phase Angle (φ)
19
Page 25
When users set the rotary switch at waveform position, the unit will display both voltage and current waveform with phase angle.
Users can press the +►or -◄ buttons to move the 0 reference axis of current up or down. So the waveforms of voltage and current can be easily distinguished as in the following figure.
III.4.1 Waveform of ACV with Peak Value
Press the FUNC button to select display of voltage waveform with RMS value and peak value
20
Page 26
III.4.2 Waveform of ACA with Peak Value
Press the FUNC button to select display of current waveform with RMS value and peak value
21
Page 27
III.5 Measurement of Single Phase AC Power Quality
NOTE: If the peak value of the input AC current or AC voltage is greater than the
maximum value of the range, then symbol of OL will be displayed.
NOTE: If the VT ratio is not 1, the readings of shown in LCD is equal to the W, VA, and VAR values measured by the tester multiplied by VT ratio (W
LCD
= W × VT,
VA
LCD
= VA × VT, VAR
LCD
= VAR × VT, WH
LCD
= WH × VT).
--
+
+
--
+
L3
L1
V
COM
600V
a. Set the rotary switch at the 1 Phase position b. Connect the test leads to the voltage source in parallel with the load. c. Clamp on one of the wire to the load. The current should flow from the front of
the tester to the side of the battery cover
d. Press FUNC to select following display.
22
Page 28
III.5.1 True Power (W) and Power Factor (PF)
III.5.2 Apparent Power (VA, KVA) and Reactive Power (VAR, KVAR)
23
Page 29
III.5.3 Maximum Demand (KW and KVA)
WARNING: Must disable auto-power-off for this measurement.
WARNING: Must disable auto-power-off for this measurement.
III.5.4. Energy (KWh, PFh, KVARh, and KVAh)
III.5.5 Phasor Diagram
24
Page 30
III.5.6 RMS values of Voltage and Current
25
Page 31
III.6 Measurement of Balanced 3 Phase AC Power Quality
L1
L3
L1 L2 L3
+
600V
COM
V
L1
L3
a. Set the rotary switch at the 3 Phase position b. Connect the test leads to the voltage source in parallel with the load. c. Clamp on one of the wire to the load. The current should flow from the
front of the tester to the side of the battery cover
d. Press
3φ
button for balanced
3φ
system measurement.
e. Press the FUNC button to select following displays
III.6.1 AC Watt (W) and Power Factor (PF)
26
Page 32
III.6.2 Apparent Power (VA, KVA) and Reactive Power (VAR, KVAR)
WARNING: Must disable auto-power-off for this measurement.
WARNING: Must disable auto-power-off for this measurement.
III.6.3 Maximum Demand (KW and KVA)
III.6.4 Energy (KWh, PFh, KVARh, and KVAh)
27
Page 33
III.6.5. Phasor Diagram
III.6.6. RMS values of Voltage and Current
28
Page 34
IV. DATALOGGING OF VOLTAGE (RMS VALUE) AND HARMONICS
NOTE: The true RMS value and the first harmonics are always logged.
IV.1 Scheduled Datalogging
Set the rotary switch at the V position and press the REC button ONCE. If users see the following display and press the REC button, the true RMS value of voltage and selected harmonics set in the configuration will be logged at specified sampling interval. The START TIME and STOP TIME is set in the SETUP.
29
Page 35
30 31
Page 36
When the REC button is pressed, users will see the following display.
Users always have 8 seconds to cancel Datalogging by pressing the HOLD button for about 2 seconds. If users do not press HOLD/CANCEL button, the unit starts Datalogging, and the LED next to the REC button starts blinking.
Page 37
IV.2 Immediate Datalogging
Press the REC button TWICE START TIME will be changed to next minute. STOP TIME will be changed to current time tomorrow.
Please refer to HARMONICS CONFIGURATION of SETUP for selecting harmonics.
32
Page 38
V. DATALOGGING OF CURRENT (RMS VALUE) AND HARMONICS
V.1 Scheduled Datalogging
Set the rotary switch at the A position and press the REC button ONCE. The true RMS value of current and selected harmonics set in the configuration will be logged at specified sampling interval. The START TIME and STOP TIME is set in the SETUP.
33
Page 39
When the REC button is pressed, users will see the following display.
Users always have 8 seconds to cancel datalogging by pressing the HOLD button for about 2 seconds. If users do not press HOLD/CANCEL button, the unit starts datalogging, and the LED at the bottom starts blinking.
34
Page 40
Please refer to HARMONICS CONFIGURATION of SETUP for selecting
NOTE: The true RMS value and the first harmonics are always logged.
harmonics.
V.2 Immediate Datalogging
Press the REC button TWICE, the unit start Datalogging in the next minute. START TIME will be changed to next minute. STOP TIME will be changed to current time tomorrow.
35
Page 41
VI. DATALOGGING OF VOLTAGE AND CURRENT WAVEFORMS
NOTE: Users can specify how many points per cycle in the WAVEFORM
CONFIGURATION of SETUP.
VI.1 Datalogging of both Voltage and Current Waveforms
Set the rotary switch at the VA waveform, and press the FUNC to select display of both voltage and current waveforms. Press the REC button once to do scheduled Datalogging. Both voltage and current waveforms will be logged.
36
Page 42
VI.2 Datalogging of Voltage Waveform
NOTE: Users can specify how many points per cycle in the WAVEFORM
CONFIGURATION of SETUP.
Set the rotary switch at the VA waveform and press the FUNC to select display of voltage waveform. Press the REC button once to do scheduled Datalogging. Voltage waveform will be logged.
37
Page 43
VI.3 Datalogging of Current Waveform
NOTE: Users can specify how many points per cycle to be logged in the
WAVEFORM CONFIGURATION of SETUP.
Set the rotary switch at the VA waveform and press the FUNC to select display of current waveform. Press the REC button once to do scheduled Datalogging. Current waveform will be logged.
38
Page 44
VII. DATALOGGING OF TRANSIENT DETECTION
NOTE: Maximum 32000 events
Set the rotary switch to the Transient position, the following display is shown.
It shows the reference voltage is AC 110.0V (TRANS REF), and the threshold is 5%. If the voltage exceeds 115.5V (SWELL) or is less than 104.5V (DIP), or is less the 40.0V (OUTAGE), one transient event will be logged.
39
Page 45
Press the FUNC button to start transient detection.
40
Page 46
After users press the FUNC button, the LCD will become blank and the LED at the bottom starts to flash.
41
Page 47
To stop transient detection and review events, press the FUNC button again. Press the +►or -◄ buttons to review events.
42
Page 48
43
Page 49
VIII. DATALOGGING OF AC POWER
VIII.1 Scheduled Datalogging
Press the REC button ONCE
Users can press the REC button once to start scheduled datalogging. The START TIME and STOP TIME is set in the SETUP.
44
Page 50
When the REC button is pressed, users will see the following display.
Users always have 8 seconds to cancel Datalogging by pressing the HOLD button for about 2 seconds. If users do not press HOLD/CANCEL button, the unit starts Datalogging, and the LED next to the REC button starts blinking.
45
Page 51
The unit will log 50,000 records of (Date/Time, VA, W, VAR, PF, KVAH, KWH, KVARH, PFH, AD(VA), AD(W), MD(VA), MD(W), Phase, HP).
VIII.2 Immediate Datalogging
Press the REC button TWICE START TIME will be changed to next minute. STOP TIME will be changed to current time tomorrow.
46
Page 52
IX. CLEAR DATA MEMORY
To clear the memory of data logger, hold the REC button and turn the power on. The following display will be shown in LCD. Users press the HOLD button to confirm the clearance of memory. The unit is turned off after the memory is cleared.
If users do not press the HOLD button in 8 seconds, the memory is not clear. This timer could avoid users accidentally clear the memory.
X. RS-232 INTERFACE PROTOCOL
Baud Rate: 9600 Data Bits: 8 Stop Bit: 1 Parity: None Format: ASCII
47
Page 53
XI. SPECIFICATIONS (23C±5C)
Range (0 to 1500A)
Resolution
Accuracy of Readings1
> 20 V and > 20A
< 20V or < 20A
10.0 – 999.9 W
0.1W
±1% ±20dgts
±2% ±40dgts
1.000 – 9.999 KW
0.001 KW
±1% ±20dgts
±2% ±40dgts
10.00 – 99.99 KW
0.01 KW
±1% ±20dgts
±2% ±40dgts
100.0 – 999.9 KW
0.1 KW
±1% ±20dgts
±2% ±40dgts
1000 – 9999 KW
1 KW
±1% ±20dgts
±2% ±40dgts
Range (0 to 1500A)
Resolution
Accuracy of Readings1
> 20 V and > 20A
< 20V or < 20A
10.0 – 999.9 VA
0.1VA
±1% ±20dgts
±2% ±40dgts
1.000 – 9.999 KVA
0.001 KVA
±1% ±20dgts
±2% ±40dgts
10.00 – 99.99 KVA
0.01 KVA
±1% ±20dgts
±2% ±40dgts
100.0 – 999.9 KVA
0.1 KVA
±1% ±20dgts
±2% ±40dgts
1000 – 9999 KVA
1 KVA
±1% ±20dgts
±2% ±40dgts
Range (0 to 1500A)
Resolution
Accuracy of Readings1
> 20 V and > 20A
< 20V or < 20A
10.0 – 999.9 VAR
0.1VAR
±2% ±30dgts
±3% ±40dgts
1.000 – 9.999 KVAR
0.001 KVAR
±2% ±30dgts
±3% ±40dgts
10.00 – 99.99 KVAR
0.01 KVAR
±2% ±30dgts
±3% ±40dgts
100.0 – 999.9 KVAR
0.1 KVAR
±2% ±30dgts
±3% ±40dgts
1000 – 9999 KVAR
1 KVAR
±2% ±30dgts
±3% ±40dgts
AC Watt (50 or 60 Hz, PF 0.5 to 1.0, VT = 1, Voltage > 5V AC, Current > 5A AC for A range, and continuous waveform)
1
For VT ≠1, the accuracy in percentage is the same (±1%). But the additional
wattage should be multiplied by the VT ratio.
For example, ±0.2W becomes ±0.2W * VT ratio
AC Apparent Power (VA, from 0.000VA to 9999 KVA, PF 0.5 to 1)
1
For VT ≠1, the accuracy in percentage is the same (±1%). But the additional
wattage should be multiplied by the VT ratio.
For example, ±0.2VA becomes ±0.2VA * VT ratio
AC Reactive Power (VAR, from 0.000 VAR to 9999 KVAR)
1
For VT ≠1, the accuracy in percentage is the same (±2%). But the additional
wattage should be multiplied by the VT ratio.
For example, ±0.2VAR becomes ± 0.2VAR * VT ratio
48
Page 54
Range
Resolution
Accuracy of Readings
4.0 – 1500.0 A
0.01 A
±1.0% ± 5dgts
Range
Resolution
Accuracy of Readings1
4.0 V – 600.0 V
0.1 V
±0.5% ± 5dgts
Range
Resolution
Accuracy
1 – 20th
0.1%
±2%
21 – 50th
0.1%
4% of reading ±2.0%
Range
Resolution
Accuracy
1 – 20th
0.1%
±2% ± 0.5V
21 – 50th
0.1%
4% of reading ±0.5V
Range of VT (Voltage Transformer) Ratio: 1 to 3000
AC Active Energy (WH, or KWH, from 0 WH to 999,999 KWH) WH = W * Time (in hours)
AC Current (50 or 60 Hz, Auto Range, True RMS, Crest Factor < 4, Overload
Protection AC 2000A)
AC Voltage (50 or 60 Hz, Auto Range, True RMS, Crest Factor < 4, VT=1, Input Impedance 10 MΩ, Overload Protection AC 800V)
1
For VT ≠1, the accuracy in percentage is the same (±0.5%). But the
additional digits should be multiplied by the VT ratio.
For example, ±5digits becomes ± 5digits * VT ratio
Harmonics of AC Voltage in Percentage( 1 to 50th order, minimum voltage at 50
or 60 Hz > AC 80V. If the voltage is 0 at 50 or 60 Hz, all the percentage (%) display is 0.)
Harmonics of AC Voltage in Magnitude (1 to 50th order, minimum voltage at 50 or 60 Hz > AC 80V, VT=1)
49
Page 55
Harmonics of AC Current in Percentage (1 to 50th order, minimum current at 50
Range
Resolution
Accuracy
1 – 20th
0.1%
±2%
21 – 50th
0.1%
4% of reading ±2.0%
Range
Resolution
Accuracy
1 – 20th
0.1%
±2% of reading ±0.4A
21 – 50th
0.1%
±4% of reading ±0.4A
Range
Resolution
Accuracy
> 20V and > 20A
< 20V or < 20A
0.000 – 1.000
0.001
± 0.04
±0.1
Range
Resolution
Accuracy
-180° to 180°
0.1°
± 1°
0° to 360°
0.1°
± 1°
Range
Resolution
Accuracy
0.0 – 20%
0.1%
± 2%
20.1 – 100%
0.1%
± 6% of reading ± 1%
100.1 – 999.9 %
0.1%
± 10% of reading ± 1%
Range
Sampling Time
Accuracy of Reading
50 Hz
39 μs
± 5% ± 50 digits
60 Hz
33 μs
± 5% ± 50 digits
or 60 Hz > 20 A. If the current is 0 at 50 or 60 Hz, all the percentage (%) display is 0.)
Harmonics of AC Current in Magnitude (1 to 50th order, minimum current at 50 or 60 Hz > 20A)
Power Factor (PF)
Phase Angle (Φ)
Total Harmonic Distortion (THD-F with respect to the 50 or 60 Hz, min. value at 50
or 60 Hz > 80V and > 20 A, 1 to 50th Harmonics. If the voltage or current is 0 at 50 or 60 Hz, all the percentage (%) display is 0)
Peak Value of AC Voltage (peak value > 10V) or AC Current (peak value > 20A)
50
Page 56
Frequency (RMS value > 20V) or ACA (RMS value > 30A)
Range
Resolution
Accuracy
46 – 65
0.1
± 0.3Hz
Indoors Use Conductor Size: 55mm (approx.), 65 x 24mm (bus bar) Battery Type: two 1.5V SUM-3 Display: 128 X 64 dot matrix LCD with backlight Range Selection: Auto Overload Indication: OL Power Consumption: 10 mA(approx.) Auto-Power-Off: 15 minutes after power-on Update Time: 2 times/second (display) No. Of Samples per Period 512 (voltage or current) 256 (power) Operating Temperature: -10C to 50C Operating Humidity: less than 85% relative Altitude: up to 2000M Storage Temperature: -20C to 60C Storage Humidity: less than 75% relative Dimension: 271mm (L) x 112mm (W) x 46mm (H)
10.7" (L) x 4.4" (W) x 1.8" (H) Weight: 647g / 22.8 oz (battery included) Accessories: Test leads Carrying bag x 1 Users manual x 1 Software users manual x 1 Software CD x 1
Batteries 1.5V x 2 Alligator clips RS232 to USB bridge x 1
51
Page 57
XII. BATTERY REPLACEMENT
When the battery voltage low is shown in LCD, A. Turn the power off and remove the test leads from the box. B. Remove the screw of the battery compartment. C. Lift and remove the battery compartment. D. Remove the old batteries E. Press the FUNC button for 2 seconds to discharge. F. Insert two new 1.5V SUM-3 batteries. G. Replace the battery compartment and secure the screw.
52
Page 58
53
Page 59
XIII. MAINTENANCE & CLEANING
Servicing not covered in this manual should only be performed by qualified personnel. Repairs should only be performed by qualified personnel. Periodically wipe the case with a damp cloth and detergent; do not use abrasives or solvents.
Address of Agent, Distributor, Importer, or Manufacturer
54
Loading...