PCE Instruments PCE-GPA 50-ICA, PCE-GPA 50 Users guide

Page 1
© PCE Instruments
PCE-GPA 50 Power Analyser
User Manual
Last change: 4 September 2023
v1.0
English
Page 2
© PCE Instruments
Contents
1 Safety notes ........................................................................................... 1
2 Specifications ........................................................................................ 2
3 Delivery scope ....................................................................................... 3
4 System description ............................................................................... 3
4.1 Description of keys / switches........................................................................................... 4
5 Operation ............................................................................................... 4
5.1 Measurement preparation ................................................................................................ 4
5.2 Measurement ..................................................................................................................11
5.3 Logger function ...............................................................................................................20
5.4 Freezing the current measured values ............................................................................20
5.5 Backlight / Exit.................................................................................................................21
6 Read SD card ....................................................................................... 21
7 Battery replacement............................................................................ 21
8 Plug-in mains adapto .......................................................................... 21
9 RS232 interface ................................................................................... 22
10 Contact ................................................................................................. 23
11 Disposal ............................................................................................... 23
Page 3
© PCE Instruments
1
1 Safety notes
Please read this manual carefully and completely before you use the device for the first time. The device may only be used by qualified personnel and repaired by PCE Instruments personnel. Damage or injuries caused by non-observance of the manual are excluded from our liability and not covered by our warranty.
The device must only be used as described in this instruction manual. If used otherwise, this can cause dangerous situations for the user and damage to the meter.
The instrument may only be used if the environmental conditions (temperature, relative
humidity, …) are within the ranges stated in the technical specifications. Do not expose
the device to extreme temperatures, direct sunlight, extreme humidity or moisture.
Do not expose the device to shocks or strong vibrations.
The case should only be opened by qualified PCE Instruments personnel.
Never use the instrument when your hands are wet.
Never touch live components during the measurement. There is a danger to life.
Never touch the bare measuring tips, otherwise electric shocks may occur.
Before each measurement, make sure that the correct measurement function is set
and that the test leads are connected correctly.
Resistance, capacitance and temperature measurements as well as diode tests (if any) must only be carried out in a de-energised state.
Before replacing the batteries or the fuses, all test leads must be removed from the meter.
You must not make any technical changes to the device.
The appliance should only be cleaned with a damp cloth. Use only pH-neutral cleaner,
no abrasives or solvents.
The device must only be used with accessories from PCE Instruments or equivalent.
Before each use, inspect the case for visible damage. If any damage is visible, do not
use the device.
Do not use the instrument in explosive atmospheres.
The measurement range as stated in the specifications must not be exceeded under
any circumstances.
Non-observance of the safety notes can cause damage to the device and injuries to the user.
We do not assume liability for printing errors or any other mistakes in this manual. We expressly point to our general guarantee terms which can be found in our general terms of
business.
Page 4
© PCE Instruments
2
2 Specifications
Measuring function
Measurement range
Resolution
Accuracy AC voltage
10 ... 600 V
0.1 V
±(0.5 % ... 3 digits)
AC V
peak-peak
0.1 V
±(5% ... 30 digits)
Alternating current
5 ... 2000 A <100 A: 0.01 A
<200 A: ±(1 %+ 0.5 A)
AC A
<1000 A: 0.1 A
>200 A: ±(1 % + 5 A)
peak-peak
>1000 A: 1 A
±(5 % + 30 digits)
Power factor (PF)
0 ... 1
0.001
± 0.04
Phase angle
-180 ° ... 180 °
0.1 °
± 1° x PF
Frequency
45 ... 65 Hz
0.1 Hz
± 0.2 Hz
Active, reactive & apparent power
0 ... 9.999 M (W / VA / VAR)
0.1 ... 0.001 M (W / VA / VAR)
±(1.5 % + 20 digits)
Active, reactive & apparent energy
0k ... 9.999 M (WH / VAH / VARH)
0.001k ... 0.001 M (WH / VAH / VARH)
±(1.5 % + 20 digits) Harmonics AC V
1. ... 20. order
0.1 V
±(2 % + 5 digits)
21. ... 50. order
0.1 V
±(4 % + 5 digits)
Harmonics AC A
1. ... 20. order
<100 A: 0.01 A
±(2 % + 5 digits) Alternating current
<1000 A: 0.1 A
21. ... 50. order
>1000 A: 1 A
±(4 % + 5 digits)
Harmonics AC V %
1. ... 20. order
0.10 %
±(2 % + 10 digits)
21. ... 50. order
0.10 %
±(4 % + 20 digits)
Harmonics AC A %
1. ... 20. order
0.10 %
±(2 % + 10 digits)
21. ... 50. order
0.10 %
±(4 % + 20 digits)
Absolute harmonic distortion
0 ... 20 %
0.10 %
±(2 % + 5 digits)
20.1 ... 100 %
0.10 %
±(6% + 10 digits)
Temperature K-type thermocouple
-100 ... 199.9 °C
0.1 °C
±(1 % + 1 °C)
200 ... 1300 °C
1 °C
±(1 % + 2 °C)
Display
graphic LCD
AC V input impedance
10 MOhm
Frequency range of current clamp
40 Hz ... 1 kHz
Calibrated frequency of current clamp
45 ... 65 Hz
Overload protection AC V: 720 V RMS
AC A: 2100 A
Data memory
micro SD card
Display refresh rate
1 second
Storage rate of data memory
2 ... 7200 s
Storage format
XLS
Interface
serial interface for live display on PC (SOFT-LUT-USB is required)
Power supply 2 x 1.5 V AA battery
9 V / 800 mA mains adaptor
Power consumption
60 mA DC
Clamp opening
50 mm
Operating conditions
0 ... 50 °C / 32 ... 122 °F, max. 80 % RH
Weight
approx. 595 g / 1.3 lbs
Dimensions
280 x 106 x 47 mm / 11 x 4.2 x 1.9 in
Page 5
© PCE Instruments
3
3 Delivery scope
1 x current clamp PCE-GPA 50 1 x set of test leads 2 x alligator clips 1 x micro SD memory card 1 x mains adaptor 9 V / 800 mA 2 x 1.5 V AA battery 1 x carrying bag 1 x user manual
4 System description
Measuring clamp
" key
Opening key for measuring clamp
“▼" key
Display
" key
FUNC" key
Rotary switch
HOLD" key
Socket RS232 interface
REC" key
Socket DC 9V mains adaptor
ENTER/SETUP" key
Sockets test leads
“▲" key
Battery compartment
EXIT" key
SD card slot in battery compartment
Page 6
© PCE Instruments
4
4.1 Description of keys / switches
Rotary switch Select the measuring function
Meter on / off
FUNC" key Select the display indication HOLD" key Freeze the current measured values REC" key Record the measured values on the SD card
"Setup" key Open the settings menu
Confirm a selection EXIT" key Exit the settings menu Backlight on / off
"▲" key Move cursor up in the settings menu "▼" key Move cursor down in the settings menu " key Move cursor to the left in the settings menu
Harmonic analysis to the left ▶" key Move the cursor to the right in the settings menu Harmonic analysis to the right
5 Operation
5.1 Measurement preparation
5.1.1 Inserting the battery and SD card
Loosen the two fastening screws of the battery compartment at the rear side.
Open the cover and insert two batteries (1.5 V AA) and a micro SD card.
Close the compartment and fasten the screws.
5.1.2 Switch meter on/off
Turn the rotary switch to the "3 phase" or "1 phase" position to switch on the meter.
The meter shows the following during the start-up phase:
After using the meter, turn the rotary switch back to the "OFF" position.
Page 7
© PCE Instruments
5
5.1.3 Start screen
The flashing "NO DISK" indicator at the bottom right indicates that the SD card is missing or not inserted correctly. During the brief display of "SD CHECK", it is read and checked.
5.1.4 Settings menu
Folder Name Storage folder selection
You can choose between 10 storage folders: WTA01 ... WTA10 File Name File name selection
You can choose between 50 file names REC Date Date / time of last storage Sampling Time Memory interval Setting the memory interval between 2 and 7200 seconds Delete File Delete file Deleting saved files on the SD card SD Format Format SD card Format the SD card PT Voltage transformer setting 1:1 to 1000:1 Beep Control tone
Switching on/off the control tone MD Peak load interval Auto Power Off Automatic power off Enabling/disabling automatic power off Trans Ref Nominal voltage as reference for overvoltage detection SVDP Limit value setting for overvoltage detection Decimal Decimal Decimal point setting USA =. / Europe =, RS232 Out Sel RS232 interface output options Selection of the values transmitted through the interface (max. 9 of 67) Freq. Frequency Selection between 50 Hz, 60 Hz or Auto Temp. Unit Temperature unit Selection between °C and °F Start Time Start time recording Setting the start time of data storage Stop Time Stop time recording Setting the end time of recording Year Year Setting current year Month Month Setting current month
Page 8
© PCE Instruments
6
Day Day Setting current day Hour Hour Setting current hour Minute Minute Setting current minute Second Second Setting current second
5.1.5 Settings before the measurement
Press the "SETUP" key to enter the settings menu. The current adjustable parameter flashes.
5.1.5.1 Selection of memory location
Select "Folder Name" with the ▲ ▼ keys. "Folder Name" flashes.
Press the or key. "WTAxx" flashes.
Use the ▲ ▼ keys to select the desired memory location WTA01 ... WTA10.
Press the or key. "Folder Name" flashes.
Press the ▼ key to move to the next setting parameter or the key to move to the
previous setting parameter.
Page 9
© PCE Instruments
7
5.1.5.2 Memory number selection
Select "File Name" with the ▲ ▼ keys. "File Name" flashes.
Press the or key. Depending on the position of the rotary switch, one of the
following memory pre-numbers flashes.
o 1P201001 1P2 single-phase measurement o 3P301001 : 3P3 three-phase measurement o HAV01001 : HAV harmonic voltage measurement o HAA01001 : HAA harmonic .current measurement o SIN01001 : SIN waveform current and voltage o TRA01001 : TRA harmonic measurement o TMP01001 : TMP temperature measurement
Use the ▲ ▼ keys to select the desired memory number, e. g. 1P201001, 1P201050. Hold down the keys for fast scrolling. NO FILE below the memory number indicates a free memory number.
Press the or key. "File Name" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
5.1.5.3 Storage interval
Select "Sampling Time" with the ▲ ▼ keys. "Sampling Time" flashes.
Press the or key. The currently set storage interval flashes.
Use the ▲ ▼ keys to select the desired storage interval.
Press and hold the keys for fast scrolling. Press the or key. "Sampling Time" flashes.
Press the key to move to the next setting parameter or the key to move to the previous setting parameter.
5.1.5.4 Delete memory contents
Select "Delete File" with the ▲ ▼ keys. "Delete File" flashes.
Press and hold the or key for 2 seconds. "Y or N" is displayed. "N" flashes.
Use the ▲ ▼ keys to select "Y" to delete memory or "N" in order not to delete
memory.
Press the "SETUP / ENTER" key to confirm the selection. "Delete File" flashes. Or hold down the or key for 2 seconds. No action is performed and "Delete File" flashes again. Attention! If "Y" is selected, all data on the SD card will be deleted.
Press the ▼ key to move to the next setting parameter or the ▲ key to move to the previous setting parameter.
Page 10
© PCE Instruments
8
5.1.5.5 Format SD card
Select "SD Format" with the ▲ ▼ keys. "SD Format" flashes.
Press and hold the or key for 2 seconds. "Y or N" is displayed. "N" flashes.
Use the ▲ ▼ keys to select "Y" to format SD card or "N" in order not to format SD
card.
Press the "SETUP / ENTER" key to confirm the selection. "SD Format flashes. Or press and hold the or button for 2 seconds. No action is taken and "SD Format" flashes again. Caution! If "Y" is selected, all data on the SD card is deleted and the card is formatted.
Press the ▼ key to move to the next setting parameter or the ▲ key to move to the previous setting parameter.
5.1.5.6 Voltage transformer ratio setting
Select "PT" with the ▲ ▼ keys. "PT" flashes.
Press the or key. The currently set transformer ratio flashes.
Use the ▲ ▼ keys to select the transformer ratio.
Press and hold the keys for fast scrolling. Press the or key. "PT" flashes.
Press the key to move to the next setting parameter or the key to move to the previous setting parameter.
5.1.5.7 Control tone
Select "Beep" with the ▲ ▼ keys. "Beep" flashes.
Press the or key. "ON" or "OFF" flashes.
Use the ▲ ▼ keys to select "OFF" to disable the control tome or "ON" to enable the
control tone.
Press the or key. "Beep" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
5.1.5.8 Peak load interval
Select "MD" with the ▲ ▼ keys. "MD" flashes.
Press the or key. The currently set interval time flashes.
Use the ▲ ▼ keys to select the desired interval time.
Press and hold the keys for fast scrolling. Press the or key. "MD" flashes.
Press the key to move to the next setting parameter or the key to move to the previous setting parameter.
Page 11
© PCE Instruments
9
5.1.5.9 Automatic power off
Select "Auto Power Off" with the ▲ ▼ keys. "Auto Power Off" flashes.
Press the or key. "Y" for Yes flashes.
Use the keys to choose between "Y" for Yes or "N" for No.
Attention! If Yes is selected, the meter is automatically switched off after 10 minutes to save battery power.
Press the or key. "Auto Power Off" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
5.1.5.10 Rated voltage overvoltage detection
Select "Trans Ref" with the ▲ ▼ keys. "Trans Ref" flashes.
Press the or key. The currently set nominal voltage value flashes.
Use the ▲ ▼ keys to select the desired nominal voltage value.
Press and hold the keys for fast scrolling. Press the or key. "Trans Ref" flashes.
Press the key to move to the next setting parameter or the key to move to the previous setting parameter.
5.1.5.11 Limit value setting overvoltage
Select "SDVP" with the ▲ ▼ keys. "SDVP" flashes.
Press the or key. The currently set percentage value flashes.
Use the ▲ ▼ keys to select the desired percentage value.
Deviation from the nominal voltage value in per cent
Press the or key. "SDVP" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
5.1.5.12 Decimal point
Select "Decimal" with the ▲ ▼ keys. "Decimal" flashes.
Press the or key. "Euro (,)" or "USA (.)" flashes.
Use the ▲ ▼ keys to select between "Euro (,)" or "USA (.)".
Attention! Adjust the setting to the country setting of your PC. If the setting is not correct, the data will be interpreted incorrectly by your PC.
Press the or key. "Auto Power Off" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
Page 12
© PCE Instruments
10
5.1.5.13 RS323 interface output options
Select "RS232 Out Sel" with the ▲ ▼ keys. "RS232 Out Sel" flashes.
Press and hold the or key for 2 seconds. 4 pages are available for you to select
the transferable parameters.
Use the ▲ ▼ ◀ ▶ keys to select the parameters to be output via the interface.
Press the "SETUP / ENTER" key to confirm the selection.
The selected parameters flash. The number of selected parameters is shown in the upper left corner of the display. When "Full" is displayed, the max. 9 transferable parameters have been exhausted.
By holding the key for 2 s, you can delete the complete selection.
To switch quickly between pages, press and hold the key for 2 s. The page number
flashes in the upper right corner. Use the ◀ ▶ keys to select the pages. Press and hold the key for 2 s to return to the standard selection mode.
Press and hold the key until "RS232 Out Sel" flashes. The selected parameters are displayed below "RS232 Out Sel".
Press the ▼ key to move to the next setting parameter or the ▲ key to move to the previous setting parameter.
5.1.5.14 Frequency
Select "Freq." with the ▲ ▼ keys. "Freq." flashes.
Press the or key. The set range flashes.
Use the ▲ ▼ keys to select the desired range.
Press the or key. "Freq." flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
5.1.5.15 Temperature unit
Select "Temp. Unit" with the ▲ ▼ keys. "Temp. unit" flashes.
Press the or key. The set temperature unit flashes.
Use the ▲ ▼ keys to select the desired temperature unit.
Press the or key. "Temp. unit" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
5.1.5.16 Recording time (time slot)
Select "Start Time" with the ▲ ▼ keys. "Start Time" flashes.
Press the or key. The hour entry (recording start time) flashes.
Use the ▲ ▼ ◀ ▶ keys to select the start time in hours and minutes.
Press and hold the ▲ ▼ keys for fast scrolling.
Press the or key. "Start Time" flashes.
Press the ▼ key to enter the time for the end of recording. "Stop Time" flashes.
Press the or key. The hour entry (end of recording) flashes.
Use the ▲ ▼ ◀ ▶ keys to select the time in hours and minutes.
Press and hold the ▲ ▼ keys for fast scrolling.
Press the or key. "Stop Time" flashes.
Press the key to move to the next setting parameter or the key to move to the
previous setting parameter.
Page 13
© PCE Instruments
11
5.1.5.17 Date / Time
Select "Year" with the ▲ ▼ keys. "Year" flashes.
Press the or key. The year flashes.
Use the ▲ ▼ keys to select the current year.
Press and hold the ▲ ▼ keys for fast scrolling.
Press the or key. "Year" flashes.
Press the ▼ key to enter the month. "Month" flashes.
Press the or key. The month number flashes.
Use the ▲ ▼ keys to select the current month.
Press and hold the ▲ ▼ keys for fast scrolling.
Press the or key. "Month" flashes.
Press the ▼ key to go to the day entry. "Date" flashes.
When entering the number of the day, hour, minute and second, proceed in the same
way as when entering the year and month.
Press the ▼ key to move to the next setting parameter or the ▲ key to move to the previous setting parameter.
You can exit the settings menu from any position with the "EXIT" key.
5.2 Measurement
5.2.1 Single-phase measurement
Turn the rotary switch to the position "1 phase".
Use the test leads to contact the L1 and N conductors as described in the connection
diagramme.
Enclose the conductor L1 with the measuring clamp.
Wiring diagramme
With the "FUNC" key you can call up 4 pages with the following measured values.
Disable automatic power off for longer lasting measurements.
Page 14
© PCE Instruments
12
Page 1 Voltage (V), current (A), power factor (PF) active power (KW).
Page 2 Active power (KW) and apparent power (KVA) from the peak load interval (left side). The current apparent power (KVA) and the current reactive power (KVAR).
Page 3 Energy measurement (PFh, kWh, KVAh, kvarh)
Page 4 Graphical representation
Page 15
© PCE Instruments
13
5.2.2 3-phase measurement symmetrical network
Turn the rotary switch to position "3 phase".
Use the test leads to contact the conductors L1 and L3 as described in the wiring
diagramme.
Enclose the conductor L2 with the measuring clamp.
Wiring diagramme
With the "FUNC" key you can call up 4 pages with the following measured values.
Disable automatic power off for longer lasting measurements.
Page 16
© PCE Instruments
14
Page 1 Voltage (V), current (A), power factor (PF) Active power (KW).
Page 2 Active power (KW) and apparent power (KVA) from the peak load interval (left side). The current apparent power (KVA) and the current reactive power (KVAR)
Page 3 Energy measurement (PFh, kWh, KVAh, kvarh)
Page 4 Graphical representation
Page 17
© PCE Instruments
15
5.2.3 Reset peak load value
Call up the following page in measuring mode with the "FUNC" key. Press and hold the "EXIT" key for more than 6 seconds.
5.2.4 Reset hourly output
Call up the following page in measuring mode with the "FUNC" key. Press and hold the "EXIT" key for more than 6 seconds.
Page 18
© PCE Instruments
16
5.2.5 Measurement of voltage harmonics
Turn the rotary switch to position " ".
Use the test leads to contact the L1 and N conductors as described in the wiring
diagramme.
Wiring diagram
With the "FUNC" key you can call up the following 2 pages. Voltage harmonics with and without display of the waveform.
Page 19
© PCE Instruments
17
Press and hold the key for more than 2 s to switch between the voltage harmonic 1 ... 25 and 26 ... 50 ranges.
Use the and keys to select between the individual voltage harmonics.
5.2.6 Measurement of current harmonics
Turn the rotary switch to position " ".
Enclose the conductor to be measured with the measuring clamp.
Please ensure the correct frequency setting in the settings menu 5.1.5.14 or contact L1
and N with the test leads.
Wiring diagramme
Page 20
© PCE Instruments
18
With the "FUNC" key you can call up the following 2 pages: Current harmonic with and without display of the waveform.
Press and hold the key for more than 2 s to switch between the current harmonic ranges 1 ...25 and 26 ... 50.
Use the and keys to select between the individual current harmonics.
5.2.7 Voltage and current waveform graph
Turn the rotary switch to the " " position.
Enclose the conductor to be measured with the measuring clamp.
Contact L1 and N with the test leads.
With the "FUNC" key you can call up the following 2 pages:
Page 21
© PCE Instruments
19
5.2.8 Overvoltage measurement
Turn the rotary switch to the "Transient" position.
Use the test leads to contact the L1 and N conductors.
If the set limit values are met, "DIP" is displayed. If the set limit values are exceeded, "SWELL" is displayed. At a voltage 40.0V, "DIP-OUTAGE" is displayed. Any change, exceeded limit value or voltage 40.0V is saved with date and time.
5.2.9 Temperature measurement
Connect the optionally available temperature sensor to the sockets for the test leads, observing correct polarity.
Turn the rotary switch to the "Temp" position.
If necessary, change the temperature unit as described in item 5.1.5.15.
Page 22
© PCE Instruments
20
5.3 Logger function
5.3.1 Logging without a time slot
In the settings menu under item 5.1.5.16, no start and stop time must be set.
Press the "REC" key to start or stop the logging function.
The data will be saved in the interval set under item 5.1.5.3. The enabled logging function is shown on the display at the bottom left by the indication "REC". If there are more than 30000 records, a new file with a new storage name is automatically created.
5.3.2 Logging with time slot preset
In the settings menu under item 5.1.5.16, set a start and stop time.
Press the "REC" key to start or stop the logging function.
The meter starts the logging function with the interval given in item 5.1.5.3 when the start time is reached and ends the function when the stop time is reached. The logging function records the data daily at the set time by pressing the "REC" key meter it is switched off. When the logging function is switched on, "REC" is shown at the bottom left of the display.
By holding down the "REC" key, you can also end the logging function during the active log phase.
If there are more than 30000 records, a new file with a new storage name is automatically created.
5.3.3 Spontaneous logging with time slot preset
If the logging function is enabled, disable it by pressing the "REC" key.
Press and hold the "REC" key for 2 seconds to start the logging function.
The meter starts the logging function with the interval set under item 5.1.5.3 directly and stops the function when the set stop time is reached. The logging function records the data daily at the set time by pressing the "REC" key until the meter is switched off. When the logging function is enabled, "REC" is shown at the bottom left of the display.
>By holding down the "REC" key, you can also end the logging function during the active log phase.
If there are more than 30000 records, a new file with a new storage name is automatically created. If "ChangeSD" is shown at the bottom left of the display, the SD card memory is exhausted or the
SD card has an error. If "NO DISK" is shown at the bottom right of the display after pressing the "REC" button, insert an SD card or check that it is correctly inserted.
5.4 Freezing the current measured values
Press the "HOLD" key to freeze the currently displayed values.
Press the "HOLD" key again to return to the current reading.
The enabled hold function is displayed at the bottom left by the indication "Hold".
Page 23
© PCE Instruments
21
5.4.1 Saving the frozen display view
Press the "REC" key while the hold function is activated.
You can occupy a maximum of 50 memory locations. The display view is saved 1:1 as an image (BMP file).
5.5 Backlight / Exit
Press the "EXIT" key during the measurement to switch the backlight on or off.
Press the "EXIT" key during the settings in the settings menu to return to measuring
mode.
6 Read SD card
Open the battery compartment on the back of the meter.
Disconnect all test leads and the measuring clamp from the connected conductors
before opening. Proceed as described in item 5.1.1.
Remove the SD card and insert it directly or with the help of an adapter into the slot on the PC.
Start the spreadsheet programme and open the file with the extension "XLS".
Make sure that the decimal point is set correctly for your region as described in item. Failure to do so may result in incorrect display of the measured values. The saved values can also be displayed as a graph in the spreadsheet programme. Please refer to the help section or the instructions of your spreadsheet programme.
7 Battery replacement
Replace the battery as soon as the icon (battery voltage low) appears at the top left of the display. Disconnect all test leads and the measuring clamp from the connected conductors before opening. Proceed as described in item 5.1.1.
8 Plug-in mains adapto
Always use the plug-in mains adaptor for measurements with the logging function. This will prevent the measurement from being interrupted due to exhausted batteries. As soon as you connect the plug-in mains adaptor to the PCE-GPA 50, the battery supply is switched off. In the event of a power failure, the batteries serve as a backup.
Page 24
© PCE Instruments
22
9 RS232 interface
Via the RS232 interface, the parameters described in item 5.1.5.13 can be transferred directly to a PC. A special cable with 3.5 mm jack plug and USB converter is required for this. (PCE part number: SOFT-LUT-USB) The software is made available for download after the purchase of the data cable.
The meter has an RS232 interface via a 3.5 mm socket. The output is a 16-digit data string that can be set up according to user-specific requirements. An RS232 cable with the following features is required to connect the meter to a PC:
The 16-digit data string is displayed in the following format: D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
The numbers stand for the following parameters:
Page 25
© PCE Instruments
23
10 Contact
If you have any questions, suggestions or technical problems, please do not hesitate to contact us. You will find the relevant contact information at the end of this user manual.
11 Disposal
For the disposal of batteries in the EU, the 2006/66/EC directive of the European Parliament applies. Due to the contained pollutants, batteries must not be disposed of as household waste. They must be given to collection points designed for that purpose.
In order to comply with the EU directive 2012/19/EU we take our devices back. We either re-use them or give them to a recycling company which disposes of the devices in line with law.
For countries outside the EU, batteries and devices should be disposed of in accordance with your local waste regulations.
If you have any questions, please contact PCE Instruments.
Page 26
© PCE Instruments
24
PCE Instruments contact information
Germany France Spain
PCE Deutschland GmbH PCE Instruments France EURL PCE Ibérica S.L. Im Langel 26 23, rue de Strasbourg Calle Mula, 8 D-59872 Meschede 67250 Soultz-Sous-Forets 02500 Tobarra (Albacete) Deutschland France España Tel.: +49 (0) 2903 976 99 0 Téléphone: +33 (0) 972 3537 17 Tel. : +34 967 543 548 Fax: +49 (0) 2903 976 99 29 Numéro de fax: +33 (0) 972 3537 18 Fax: +34 967 543 542 info@pce-instruments.com info@pce-france.fr info@pce-iberica.es www.pce-instruments.com/deutsch www.pce-instruments.com/french www.pce-instruments.com/espanol
United Kingdom Italy Turkey
PCE Instruments UK Ltd PCE Italia s.r.l. PCE Teknik Cihazları Ltd.Şti. Trafford House Via Pesciatina 878 / B-Interno 6 Halkalı Merkez Mah. Chester Rd, Old Trafford 55010 Loc. Gragnano Pehlivan Sok. No.6/C Manchester M32 0RS Capannori (Lucca) 34303 Küçükçekmece - İstanbul United Kingdom Italia Türkiye Tel: +44 (0) 161 464902 0 Telefono: +39 0583 975 114 Tel: 0212 471 11 47 Fax: +44 (0) 161 464902 9 Fax: +39 0583 974 824 Faks: 0212 705 53 93 info@pce-instruments.co.uk info@pce-italia.it info@pce-cihazlari.com.tr www.pce-instruments.com/english www.pce-instruments.com/italiano www.pce-instruments.com/turkish
The Netherlands United States of America Denmark
PCE Brookhuis B.V. PCE Americas Inc. PCE Instruments Denmark ApS Institutenweg 15 1201 Jupiter Park Drive, Suite 8 Birk Centerpark 40 7521 PH Enschede Jupiter / Palm Beach 7400 Herning Nederland 33458 FL Denmark Telefoon: +31 (0)53 737 01 92 USA Tel.: +45 70 30 53 08 info@pcebenelux.nl Tel: +1 (561) 320-9162 kontakt@pce-instruments.com www.pce-instruments.com/dutch Fax: +1 (561) 320-9176 www.pce-instruments.com/dansk info@pce-americas.com www.pce-instruments.com/us
Loading...