PCE-EMD 5, PCE-EMD 10 Large Display
User Manual
Last change: 27 May 2024
v1.0
English
Page 2
© PCE Instruments
Contents
1 Safety notes ........................................................................................... 1
2 Specifications ........................................................................................ 2
3 Delivery scope ....................................................................................... 3
4 Display dimensions .............................................................................. 3
5 Sensor dimensions ............................................................................... 4
6 Wiring diagram for 4 ... 20 mA sensors on the display ..................... 6
7 Sensor connection diagram to PCE-EMD series (display) ............... 7
7.1 Wiring diagram sensor (insulated) .................................................................................... 8
7.2 Wiring diagram sensor (standard) .................................................................................... 9
7.3 Instructions ....................................................................................................................... 9
8 Calibration ........................................................................................... 10
9 Contact ................................................................................................. 11
10 Disposal ............................................................................................... 11
Page 3
© PCE Instruments
1
1 Safety notes
Please read this manual carefully and completely before you use the device for the first time. The device may only be used by qualified personnel and repaired by PCE Instruments personnel. Damage or injuries caused by non-observance of the manual are excluded from our liability and not covered by our warranty.
The device must only be used as described in this instruction manual. If used otherwise, this can cause dangerous situations for the user and damage to the meter.
The instrument may only be used if the environmental conditions (temperature, relative
humidity, …) are within the ranges stated in the technical specifications. Do not expose
the device to extreme temperatures, direct sunlight, extreme humidity or moisture.
Do not expose the device to shocks or strong vibrations.
The case should only be opened by qualified PCE Instruments personnel.
Never use the instrument when your hands are wet.
You must not make any technical changes to the device.
The appliance should only be cleaned with a damp cloth. Use only pH-neutral cleaner,
no abrasives or solvents.
The device must only be used with accessories from PCE Instruments or equivalent.
Before each use, inspect the case for visible damage. If any damage is visible, do not
use the device.
Do not use the instrument in explosive atmospheres.
The measurement range as stated in the specifications must not be exceeded under
any circumstances.
Non-observance of the safety notes can cause damage to the device and injuries to the user.
We do not assume liability for printing errors or any other mistakes in this manual. We expressly point to our general guarantee terms which can be found in our general terms of
business.
Page 4
© PCE Instruments
2
2 Specifications
Temperature PCE-EMD 5
Measurement range
0 ... 50 °C
Resolution
0,1 °C
Accuracy
±0,5 °C
Temperature PCE-EMD 10
Measurement range
32 ... 122 °F
Resolution
0,1 °F
Accuracy
±0,9 °F
Humidity
Measurement range
0 ... 99.9 % RH
Resolution
0.1 % RH
Accuracy
±3 % RH
Further specifications
Response time
<15 seconds
Number of usable sensors
4
Digit height
100 mm / 3.9"
Digit colour
white
Sensor supply voltage
12 and 24 V DC
Maximum sensor supply current
100 mA
Impedance current input
<200 Ω
Display housing material
Black lacquered aluminium housing
Display protection
Anti-reflective methacrylate
Sensor housing material
ABS
Display protection class
IP20
Sensor protection class
IP30
Power supply
110 ... 220 V AC 50 / 60 Hz
Maximum power consumption
18 W
Display mounting
flat on a surface via a monitor stand (75 x 75 mm / 2.95 x 2.95")
Sensor mounting
flat on a surface
Cable cross-section of terminal strip power supply
0.5 ... 2.5 mm² (AWG 14) rigid cable
0.5 ... 1.5 mm² (AWG 15) flexible cable
Cable cross-section of terminal strip sensor connection
0.14 ... 0.15 mm² (AWG 18) rigid cable
0.15 ... 1 mm² (AWG16) flexible cable
Terminal strip torque
1.2 Nm
Terminal strip screw length
<12 mm / 0.47"
Display dimensions
535 x 327 x 53 mm / 21.0 x 12.8 x 2.0"
Sensor dimensions
80 x 80 x 35 mm / 3.1 x 3.1 x 1.3"
Operating conditions
-10 ... 60 ºC, 5 ... 95 % RH, non-condensing
Storage conditions
-20 ... 70 ºC, 5 ... 95 % RH, non-condensing
Display weight
4579 g / 161.5 oz
Sensor weight
66 g / 2.3 oz
Page 5
© PCE Instruments
3
3 Delivery scope
1 x large display PCE-EMD series (depending on model) 2 x brackets for wall mounting 1 x user manual
4 Display dimensions
Page 6
© PCE Instruments
4
5 Sensor dimensions
Page 7
© PCE Instruments
5
Page 8
© PCE Instruments
6
6 Wiring diagram for 4 ... 20 mA sensors on the display
Page 9
© PCE Instruments
7
7 Sensor connection diagram to PCE-EMD series (display)
Designation
Meaning
24 V
Supply voltage 24 V
12 V
Supply voltage 12 V
Hx
Connection for humidity
Tx
Connection for temperature
GND
Dimensions
Page 10
© PCE Instruments
8
7.1 Wiring diagram sensor (insulated)
Page 11
© PCE Instruments
9
7.2 Wiring diagram sensor (standard)
7.3 Instructions
To use the display, between one and four sensors must be connected to it. As there are no keys on the display, no operation is required. The display works completely automatically.
The display works as follows:
Number of sensors
Display
0
99.9 °C / °F and 99.9 % RH
1
Measured values
2 or more
Average of all sensors
Page 12
© PCE Instruments
10
8 Calibration
To perform a calibration, there is a row of switches on the inside of the sensor. These switches can be used to change the temperature signal. The measured value can be added and subtracted by turning these switches on and off. It is not recommended to change these switches as the sensor is already set appropriately at the factory.
Position 1
Position 2
Position 3
Position 4
Correction
- - - - 0
On - - - 0.2 - On - -
0.4
On
On - -
0.6 - -
On - 0.8
On - On - 1.0 - On
On - 1.2
On
On
On - 1.4
Calibration switch Signal outputs
Page 13
© PCE Instruments
11
9 Contact
If you have any questions, suggestions or technical problems, please do not hesitate to contact us. You will find the relevant contact information at the end of this user manual.
10 Disposal
For the disposal of batteries in the EU, the 2006/66/EC directive of the European Parliament applies. Due to the contained pollutants, batteries must not be disposed of as household waste. They must be given to collection points designed for that purpose.
In order to comply with the EU directive 2012/19/EU we take our devices back. We either re-use them or give them to a recycling company which disposes of the devices in line with law.
For countries outside the EU, batteries and devices should be disposed of in accordance with your local waste regulations.
If you have any questions, please contact PCE Instruments.
Page 14
© PCE Instruments
12
PCE Instruments contact information
Germany France Spain
PCE Deutschland GmbH PCE Instruments France EURL PCE Ibérica S.L. Im Langel 26 23, rue de Strasbourg Calle Mula, 8 D-59872 Meschede 67250 Soultz-Sous-Forets 02500 Tobarra (Albacete) Deutschland France España Tel.: +49 (0) 2903 976 99 0 Téléphone: +33 (0) 972 3537 17 Tel. : +34 967 543 548 Fax: +49 (0) 2903 976 99 29 Numéro de fax: +33 (0) 972 3537 18 Fax: +34 967 543 542 info@pce-instruments.com info@pce-france.fr info@pce-iberica.es www.pce-instruments.com/deutsch www.pce-instruments.com/french www.pce-instruments.com/espanol
United Kingdom Italy Turkey
PCE Instruments UK Ltd PCE Italia s.r.l. PCE Teknik Cihazları Ltd.Şti. Trafford House Via Pesciatina 878 / B-Interno 6 Halkalı Merkez Mah. Chester Rd, Old Trafford 55010 Loc. Gragnano Pehlivan Sok. No.6/C Manchester M32 0RS Capannori (Lucca) 34303 Küçükçekmece - İstanbul United Kingdom Italia Türkiye Tel: +44 (0) 161 464902 0 Telefono: +39 0583 975 114 Tel: 0212 471 11 47 Fax: +44 (0) 161 464902 9 Fax: +39 0583 974 824 Faks: 0212 705 53 93 info@pce-instruments.co.uk info@pce-italia.it info@pce-cihazlari.com.tr www.pce-instruments.com/english www.pce-instruments.com/italiano www.pce-instruments.com/turkish
The Netherlands United States of America Denmark
PCE Brookhuis B.V. PCE Americas Inc. PCE Instruments Denmark ApS Institutenweg 15 1201 Jupiter Park Drive, Suite 8 Birk Centerpark 40 7521 PH Enschede Jupiter / Palm Beach 7400 Herning Nederland 33458 FL Denmark Telefoon: +31 (0)53 737 01 92 USA Tel.: +45 70 30 53 08 info@pcebenelux.nl Tel: +1 (561) 320-9162 kontakt@pce-instruments.com www.pce-instruments.com/dutch Fax: +1 (561) 320-9176 www.pce-instruments.com/dansk info@pce-americas.com www.pce-instruments.com/us
Loading...