1. FEATURES
* Analysis for 3 phase multi-power system, 1P/2W,
1P/3W, 3P/3W, 3P/4W
* Voltage & Current are the True RMS value.
* True Power ( KW、MW、GW ) measurement.
* Apparent Power ( KVA、MVA、GVA ) measurement.
* Reactive Power ( KVAR MVAR、GVAR) measurement.
* Watt-Hour ( WH、SH、QH、PFH ).
* Power Factor( PF )、Phase Angle( Φ ).
* Voltage measurement range : 10 to 600 ACV
* Current measurement range: 0.2A to 1200 ACA.
* Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
* ACV input impedance is 10 Mega ohms.
* Safety Standard : IEC 1010, CAT III 600V
* Built-in clock and Calendar, real time data record with
SD memory card , sampling time set from 2 to 7200
seconds. Just slot in the SD card into the computer, it
can down load the all the measured value with the
time information ( year/month/data/
hour/minute/second ) to the Excel directly, then user
can make the further data analysis by themselves.
* Complete set with 4 PCs Test Leads, 4 PCs Alligator
clips, 3 PCs Clamp Probe, AC to DC 9V adapter,
2 G SD memory card and Carrying bag.
* Computer data output, can cooperate with USB Cable
/USB-01 RS232 cable/UPCB-02 and Data Acquisition
software, SOFT-LUT-USB.
1
Page 5
2. SPECIFICATIONS
2-1 General Specifications:
CircuitCustom one-chip of microprocessor LSI
circuit
Display* LCD Size :
81.4 X 61 mm ( 3.2 X 2.4 inch )
* Dot Matrix LCD (320 X 240 pixels )
with back light.
Measurement* ACV
* ACA
* AC WATT ( True Power )
AC WATT( Apparent Power )
AC WATT( Reactive Power )
* Power factor
* Phase angle
* Frequency
Wire 1P/2W, 1P/3W, 3P/3W, 3P/4W.
connections
Voltage ranges 10 ACV to 600 ACV, auto range.
Current ranges 0.2 ACA to 1200 ACA,
auto range/manual range.
SafetyIEC1010 CAT III 600 V.
standard
ACV input10 Mega ohms.
impedance
Range selectACVAuto range.
ACAAuto range & manual range.
Clamp 40 Hz to 1 KHz.
frequency
response
Spec. tested45 to 65 Hz.
frequency
Over loadACV720 ACV rms
protectionACA1300 ACA with clamp probe
CP-1200
2
Page 6
Over IndicatorShow " OL ".
Under Indicator Show " UR ".
Data HoldFreeze the display reading.
Data RecordSD Card Record.
Sampling Time Approx. 1 second.
Power ON/OFF Manual OFF by push button.
Real time* Real time data logger, saved the data
data loggerinto SD memory card and down load
the all the measured value with the
time information ( year/month/data/
hour/minute/second ) down load
to the Excel
* Integration time for data logger :
2 seconds to 7200 seconds, the during
of setting step are 2 seconds.
Data OutputRS232 computer serial interface :
USB/RS232* Connect the optional USB cable
* Computer
interface
USB-01 will get the USB plug.
* Connect the optional RS232 cable
UPCB-02 will get the RS232
plug.
Operating 0 to 50 ( 32 to 122 ).℃℉
Temperature
Operating Less than 80% R.H..
Humidity
Power Supply* DC 1.5V, AA ( UM-3 ) Battery X 8 PCs
(Alkaline or heavy-duty battery).
* AC to DC 9V power adapter.
Power * Meter : 300 DCmA.
Consumption* Clamp : 34 DCmA.
Clamp max.50 mm ( 2.0 inch ) Dia.
conductor
Size
3
Page 7
Weight* Meter : 948g ( includes batteries )
Instruction manual...............
Test Leads (TL88-4AT)...........
Clamp Probe ( CP-1200 ).........
AC to DC 9V adapter.................
Carrying bag.........................
* Clamp ( includded cable ) : 467g
Dimension
Meter :
225 X 125 X 64 mm
( 8.86 X 4.92 X 2.52 inch )
Clamp :
210 X 64 X 33mm
( 8.3 X 2.5 X 1.3 inch )
Clamp Jaw : 86 mm (3.4 inch)- outside
Accessories*
Included*
* Alligator clips (TL88-4AC)1 Set (4 PCs)
*
*
* SD card ( 2 G ).................... 1 PC
*
1 PC
1 Set (4 PCs)
3 PCs
1 PC
1 PC
Optional* USB Cable , USB-01
Accessories* RS232 cable, UPCB-02
* Data Acquisition software,
SW-U811-WIN
2-2 Electrical Specifications:
ACV
RangeResolutionAccuracy
10.0V to 600.0V0.1V± (0.5%+0.5V)
* Phase to neutral line
10.0V to 600.0V
* Phase to phase
4
Page 8
ACA
RangeResolutionAccuracy
20A0.001A,
0.01A,
200A0.01A,
0.1A,
1200A0.1A,
1A,
< 10 A
10 A≧
< 100 A
100 A≧
< 1000 A
1000 A≧
± (0.5%+0.1A)
± (0.5%+0.5A)
± (0.5%+5A)
Power factor
RangeResolutionAccuracy
0.00 to 1.000.01± 0.04
Remark :
* PFH : Long term power factor
* PFΣ :
For 3Φ 4W, 3Φ 3W
PFΣ = ( PF1 + PF2 + PF3 )/3
For 1Φ 3W
PFΣ = ( PF1 + PF2 )/2
Φ ( Phase angle )
RangeResolutionAccuracy
-180° to 180°0.1°± 1°
* ACOS ( PF )
Frequency
RangeResolutionAccuracy
45 to 65 Hz0.1 Hz0.1 Hz
5
Page 9
Active (Real) Power
RangeResolutionAccuracy
0.000 to 9.999 KW*0.001/0.01/0.1 KW± (1%+0.008KW)
10.00 to 99.99 KW*0.01/0.1 KW± (1%+0.08KW)
100.0 to 999.9 KW 0.1 KW± (1%+0.8KW)
1.000 to 9.999 MW 0.001 MW± (1%+0.008MW)
* : The resolution is changed according the different ACA range.
Apparent Power
RangeResolutionAccuracy
0.000 to 9.999 KVA*0.001/0.01/0.1KVA± (1%+0.008KVA)
10.00 to 99.99 KVA*0.01/0.1 KVA± (1%+0.08KVA)
100.0 to 999.9 KVA 0.1 KVA± (1%+0.8KVA)
1.000 to 9.999 MVA 0.001 MVA± (1%+0.008MVA)
* : The resolution is changed according the different ACA range.
Reactive Power
RangeResolutionAccuracy
0.000 to 9.999 KVAR*0.001/0.01/0.1KVAR ± (1%+0.008 KVAR)
10.00 to 99.99 KVAR*0.01/0.1 KVAR± (1%+0.08 KVAR)
100.0 to 999.9 KVAR 0.1 KVAR± (1%+0.8 KVAR)
1.000 to 9.999 MVAR 0.001 MVAR± (1%+0.008 MVAR)
* : The resolution is changed according the different ACA range.
6
Page 10
Watt Hour ( Active Power Hour) : WH
RangeResolutionAccuracy
0.000 to 9.999 KWH0.001 KWH± (2%+0.008 KWH)
10.00 to 99.99 KWH0.01 KWH± (2%+0.08 KWH)
100.0 to 999.9 KWH0.1 KWH± (2%+0.8 KWH)
1.000 to 9.999 MWH0.001 MWH± (2%+0.008 MWH)
VA Hour ( Apparent Power Hour ) : SH
RangeResolutionAccuracy
0.000 to 9.999 KVAH0.001 KVAH± (2%+0.008 KVAH)
10.00 to 99.99 KVAH0.01 KVAH± (2%+0.08 KVAH)
100.0 to 999.9 KVAH0.1 KVAH± (2%+0.8 KVAH)
1.000 to 9.999 MVAH0.001 MVAH± (2%+0.008 MVAH)
VAR Hour ( Reactive Power Hour ) : QH
RangeResolutionAccuracy
0.000 to 9.999 KVARH0.001 KVARH± (2%+0.008 KVARH)
10.00 to 99.99 KVARH0.01 KVARH± (2%+0.08 KVARH)
100.0 to 999.9 KVARH0.1 KVARH± (2%+0.8 KVARH)
1.000 to 9.999 MVARH0.001 MVARH± (2%+0.008 MVARH)
7
Page 11
3. FRONT PANEL DESCRIPTION
8
Page 12
3-1 Display
3-2 1Φ 3Φ ( Phase/wire ) key button
3-3 key button▲
3-4 key button▼
3-5 Hold key button
3-6 Backlight key button
3-7 Power key button
3-8 Exit key button
3-9 REC key button
3-10 A ( current ) range key button
3-11 Shift key button
3-12 Setup key button
3-13 Voltage input terminals
3-14 Current probe input sockets
3-15 SD card socket
3-16 RS232 socket
3-17 Reset button
3-18 DC 9V power adapter socket
3-19 Battery Cover/Battery compartment
3-20 Stand
3-21 Current Sense Jaw
3-22 Trigger
3-23 Plug of current probe
9
Page 13
4. MEASURING PREPARATION
1)
2)
4-1 The original screen
4-2 Entry the measurement Screen
The bottom right display of screen 1 will show as " SD
Check " along with blinking while inserting SD CARD
then disappears after several seconds that indicates the
data from SD CARD has been read completed.
The bottom right display of screen 2 will show as " NO
DISK " along with blinking when SD CARD is not
inserted.
10
Page 14
screen 1 ( 4-2 )
QΣ :
QΣ :
V12: 0.0 VV1: 0.0 VA1: 0.00 A
V23: 0.0 VV2: 0.0 VA2: 0.00 A
V31: 0.0 VV3: 0.0 VA3: 0.00 A
P1:-0.000 KWS1: 0.000KVAQ1: -0.000 KVAR
P2:-0.000 KWS2: 0.000KVAQ2: -0.000 KVAR
P3:-0.000 KWS3: 0.000KVAQ3: -0.000 KVAR
POWER KEY ( 3-7, Fig. 1 ) :
Press the key to turn the instrument ON/OFF.
1Φ 3Φ ( phase/wire ) KEY ( 3-2, Fig. 1 ) :
Press the key to select
(1P/2W、1P/3W、3P/3W、3P/4W) measurement
function mode.
A ( current ) RANGE KEY ( 3-10, Fig. 1 ) :
RANGE mode for current.
REC KEY ( 3-9, Fig. 1 ) :
The data record key for SD CARD.
HOLD KEY ( 3-5, Fig. 1 ) :
Press the key to freeze the display reading.
BACKLIGHT KEY ( 3-6, Fig. 1 ) :
Press the key to switch LCD backlight to ON/OFF.
SETUP KEY ( 3-12, Fig. 1 ) :
Press the key to setup the function before measuring.
EXIT KEY ( 3-8, Fig. 1 ) :
Press the key to exit setting screen.
SHIFT KEY ( 3-11, Fig. 1 )
Press the key to set the different functions in setting
screen.
10) UP () KEY ( 3-3, Fig. 1 ) :▲
Press the key to move the cursor up in setting
screen.
11) DOWN () KEY ( 3-4, Fig. 1 ) :▼
Press the key to move the cursor down in setting
screen.
12
Page 16
4-4 SETUP KEY description:
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Delet File:
0%SD Format:
0%Use Size:
388 KB
Decimal: Basic
screen 1 ( 4-4 )
Free Size:
1946 MB
Clamp Type: 1200A
Total Size:
1946 MB
RS232 Out Sel:
PT:
1 : 1
V1I1P1
CT:
1 : 1
S1Q1PF1
Beep:
ON
Φ1
WH
FREQ
Year
Month
Date
Hour
Minute
Second
2008
1205111518
File Name:
3P401001.XLS
SHIFT 2
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
Delet File:
0%SD Format:
0
%
screen 2 ( 4-4 )
Use Size:
388 KB
Decimal: Basic
Free Size:
1946 MB
Clamp Type: 1200A
Total Size:
1946 MB
RS232 Out Sel:
PT:
1 : 1
V1I1P1
CT:
1 : 1
S1Q1PF1
Beep:
ON
Φ1
WH
FREQ
Year
Month
Date
Hour
Minute
Second
2008
1205111518
4-4-1 SHIFT KEY
* SHIFT 1 : When the symbols " SETUP " and " SHIFT 1 "
are appeared on up right display of screen 1 in the
meantime, and then use the or to select the▲▼
expect item.
* SHIFT 2 : When the symbols " SETUP " and " SHIFT 2 "
are appeared on up right display of screen 2 in the
mean time, and then use the ▲ or ▼ to select ( 1P/2W、
1P/3W、3P/3W、3P/4W ) in File Name function.
Folder Name:WTA01SETUP
Folder Name:WTA01SETUP
13
Page 17
4-4-2 The Setting Function menu
* Folder Name : Set the expect folder name for SD CARD,
the range is between WTA01 and WTA10.
* File Name: Set the file name for SD CARD, It allows setting
50 filenames in this function.
* REC Date: Show the recorded time of existing files
( Year/Month/Date, Hour/Min./Sec. )
* Sampling Time : Set the sampling time from 2 to 7200 seconds.
* Delete File : To delete the existing data from SD CARD.
* SD Format : to Format SD CARD fast.
* PT : Set the potential transformer from 1 to 1000.
* CT : Set the current transformer from 1 to 600.
* Beep : Set to ON/OFF for buzzer.
* Clamp Type : Select the Clamp Type to 200A or 1200A.
* RS232 out Sel. : Set RS232 output function, maximum up
to nine items can be selected to output. screen 1 screen 2.
* Year : Set the year.
* Month : Set the month.
* Date : Set the date.
* Hour : Set the hour.
* Minute : Set the minute.
* Second : Set the second.
4-5 Setting function description before measuring
Press SETUP KEY to enter setting function screen, the
selected item will be displayed in highlight.
0 %
Use Size: 388 KBDecimal: Basic
Free Size: 1946 MBClamp Type: 1200A
Total Size:1946 MBRS232 Out Sel:
PT:1 : 1V1I1P1
CT: 1 : 1S1Q1PF1
Beep: ON Φ1WHFREQ
Year MonthDateHourMinuteSecond
20081205111434
15
Page 19
A : Folder Name range: WTA01 to WTA10.
Delet File:
SD Format:
B : Press or to select the expect folder number, the▲▼
number consists of " 01 to 10 " (as screen 1).
C : Press or continuously at least two seconds can▲▼
skip the numbers faster.
D : Press SHIFT KEY once, the symbol " SHIFT1" will
appear on up right display, and then press to entry next▼
setting function as screen 2 (Folder Name File Name).→
4-5-2 File Name: Set the file name for SD
A : The screen will show " NO File " indicator in REC Date
option when the selected file is new ( as screen 1 ).
B : The screen will show recording date and time in REC
Date option when the selected file has been recorded
as screen 2.
screen 1 ( 4-5-2 )
Folder Name:WTA03SETUP
File Name:3P401001.XLS
REC Date: NO File
Sampling Time: 2
0 %
0 %
Use Size: 388 KBDecimal: Basic
Free Size: 1946 MBClamp Type: 1200A
Total Size:1946 MBRS232 Out Sel:
PT:1 : 1V1I1P1
CT: 1 : 1S1Q1PF1
Beep: ON Φ1WHFREQ
Year MonthDateHourMinuteSecond
20081205151055
16
Page 20
screen 2 ( 4-5-2 )
Delet File:
SD Format:
Folder Name:WTA01SETUP
File Name:3P401001.XLS
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
0 %
0 %
Use Size: 388 KBDecimal: Basic
Free Size: 1946 MBClamp Type: 1200A
Total Size:1946 MBRS232 Out Sel:
PT:1 : 1V1I1P1
CT: 1 : 1S1Q1PF1
Beep: ON Φ1WHFREQ
Year MonthDateHourMinuteSecond
20081205111531
C : File Name description : press or in screen 2 to▲▼
select expect file number from 001 to 050.
Remark : When press or > 2 sec, the setting ▲▼
no. will change fast.
* 1P201001 : 1P2 means one phase by two wires, 01
means folder number, 001 means file number.
* 1P301001: 1P3 means one phase by three wires,
01 means folder number, 001 means file number.
* 3P301001 : 3P3 means three phases by three wires,
01 means folder number, 001 means file number.
* 3P401001 : 3P4 means three phases by four
wires, 01 means folder number, 001 means file
number.
D : The up right display will show " SHIFT1 " symbol
while pressing SHIFT KEY once in screen 2, and then
press to enter next setting function as screen 3▼
( File Name Sampling Time ).→
17
Page 21
E : The up right display will show " SHIFT2 " symbol
Delet File:
SD Format:
Delet File:
SD Format:
while pressing SHIFT KEY again in screen 4, at this time
press ▲ or ▼ to select 1P/2W(1P2)、1P/3W(1P3)、
3P/3W(3P3) and 3P/4W(3P4) as screen 4.
F: One by one to press SHIFT KEY to select different
functions circularly.
Folder Name:WTA01SETUP
File Name:3P401001.XLSSHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time: 2
0 %screen 3
0 %(4-5-2)
Use Size: 388 KBDecimal: Basic
Free Size: 1946 MBClamp Type: 1200A
Total Size:1946 MBRS232 Out Sel:
0 %
Use Size: 388 KBDecimal: Basic
Free Size: 1946 MBClamp Type: 1200A
Total Size:1946 MBRS232 Out Sel:
PT:1 : 1V1I1P1
CT: 1 : 1S1Q1PF1
Beep: ON Φ1WHFREQ
Year MonthDateHourMinuteSecond
20081205111518
18
Page 22
4-5-3 Sampling time: Set the data logger sampling time
screen 1 ( 4-5-3 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
SHIFT 1
REC Date: 2008-11-28 00:03:17
Sampling Time:
2
Delet File:
0%SD Format:
0%Use Size:
388 KB
Decimal: Basic
Free Size:
1946 MB
Clamp Type: 1200A
Total Size:
1946 MB
RS232 Out Sel:
PT:
1 : 1
V1I1P1
CT:
1 : 1
S1Q1PF1
Beep:
ON
Φ1
WH
FREQ
Year
Month
Date
Hour
Minute
Second
2008
1205111551
screen 2 ( 4-5-3 )
Folder Name:
WTA01
SETUP
File Name:
3P401001.XLS
REC Date: 2008-11-28 00:03:17
Sampling Time:
2
Delet File:
0%SD Format:
0%Use Size:
388 KB
Decimal: Basic
Free Size:
1946 MB
Clamp Type: 1200A
Total Size:
1946 MB
RS232 Out Sel:
PT:
1 : 1
V1I1P1
CT:
1 : 1
S1Q1PF1
Beep:
ON
Φ1
WH
FREQ
Year
Month
Date
Hour
Minute
Second
2008
1205111601
for SD
A : When press SHIFT KEY once, the symbol " SHIFT1 "
will disappear on up right display, at this time press
or to adjust expect sampling time as screen 2, ▲▼
adjusting numbers are from 2 to 7200 seconds.
Remark : When press or > 2 sec, the setting no. will change fast.▲▼
B : The up right display will show " SHIFT1 " symbol
while pressing SHIFT KEY again, and then press to▼
enter next setting function (Sampling Time Delete File)→
19
Page 23
4-5-4 Delete File: Delete the files for SD
SD Format:
A : The indicator " Y or N " will appear on right side
display of the option while pressing SHIFT KEY
continuously at least two seconds, and now press ▲
the display will show " Y " in highlight as screen 2,
press SETUP KEY again to confirm, the selected file (ex:
3P401001.XLS) will be erased then return to screen 1,
or else press SETUP KEY in " Y or N " option to
return to screen 1.
B : Press in screen 1 to enter next setting function▼
0 %
Use Size: 388 KBDecimal: Basic
Free Size: 1946 MBClamp Type: 1200A
Total Size:1946 MBRS232 Out Sel:
PT:1 : 1V1I1P1
CT: 1 : 1S1Q1PF1
Beep: ON Φ1WHFREQ
Year MonthDateHourMinuteSecond
20081205111645
4-5-5 SD Format : Formatting function for SD CARD
A : The indicator " Y or N " will appear on right side
display of the option while pressing SHIFT KEY
continuously at least two seconds, and press the▲
display will show " Y " in highlight as screen 2,
press SETUP KEY again to confirm to format SD CARD
then return to screen 1, or else press SETUP KEY in
" Y OR N " option return to screen 1.
B : Press in screen 1 to enter next setting function ( SD▼
4-5-9 Decimal Type: set the Decimal type to
Basic ( .) or Euro ( , )
The numerical data structure of SD card
is default used the " . " as the decimal,
for example "20.6" "1000.53" . But in
certain countries ( Europe ...) is used
the " , " as the decimal point, for
example " 20,6 " "1000,53". Under such
situation, it should change the Decimal
character at first.
A : When press SHIFT KEY once the symbol " SHIFT1 " will
the Decimal type to " Basic " or " Euro ".
27
Page 31
* Basic type :
The numerical data structure of SD card
is default used the " . " as the decimal,
for example "20.6" "1000.53" .
* Euro type :
The numerical data structure of SD card
is default used the " , " as the decimal,
for example "20,6" "1000,53" .
B : Press SHIFT KEY once again will return to screen 1 then
press to enter next setting function ( Decimal type ▼→
A : When press SHIFT KEY continuously at least two
seconds as screen 2 and now press or to select▲▼
the item that intend to output, maximum up to nine
items, when the cursor stops on the selected item and
then press SHIFT KEY again, the selected item will be
displayed in highlight.
B : If the selected items are over nine, the low right
display will show indicator " full " as screen 3.
C : After the selecting is completed, press SHIFT KEY
continuously at least two seconds again will return to
screen 1 and show all the selected items at the same
time.
D : Press in screen 1 to enter next setting function▼
A : When press SHIFT KEY once the symbol " SHIFT1"
will disappear as screen 2, at this time press or ▲▼
to adjust expect numbers, and press or ▲▼
continuously at least two seconds can skip the
numbers faster.
B : Press in screen 1 to enter next setting function▼
( Year Month ).→
C : The settings about ( Month Date ), (Date →→
Hour ), (Hour Minute ), ( Minute Second ) are→→
same as above step A and step B.
D : In this setting function ( Year Minute ), press or→▲
in addition to adjust the numbers, and the setting▼
value will also be saved during the adjusting.
E : In the function of setting " second ", press or ▲▼
to adjust numbers. at this point the number of second
is at a standstill condition and then press setup key
that will save setting value and also start counting
function of " second ".
4-5-13 When all settings are completed, press EXIT
KEY to return measuring screen.
4-5-14 The descriptions about SD CARD memory
space
A : Use Size - To show the space data numbers that have
been used.
B : Free Size - To show the data numbers of balance space.
C : Total Size - To show the data numbers of total space.
D : Typical SD CARD and SDHC both can be used with the
instrument, except the SD CARD memory size is less
than 32MB.
4-5-15 RESET KEY : Press this key to reboot the
instrument
34
Page 38
5. MEASURING PROCEDURES
SCREEN 1 ( 5-1 )
5-1 1Φ 2W ( one phase by two wires ) measurement
A : Diagram
B : Operation Instructions:
B-1 : Power on the instrument by pressing POWER
KEY, and then press 1Φ 3Φ KEY to select the 1Φ 2W
system, the selected name of system will be
appeared on bottom left display of screen 2.
B-2 : Connect the line voltage L1, Vn ( Neutral ) to
V1 and N terminals of the instrument.
B-3: Place the conductor of CP-1200 (A1)to A1 as
screen 1.
B-4: Connect the output of clamp meter " CP-1200(A1) "
to A1 terminal of the instrument.
B-5: The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-11, page 49 ).
35
Page 39
Φ 1 :
**
CT: 1
PT: 1
screen 2 ( 5-1 )
V 1 :0.0V
A 1 :0.00A
P 1 : - 0.000KWP F 1:- 0.00
S 1 :0.000KVAP F H:0.00
Q 1 : -0.000KVAR
W H :0.000KWH
S H :0.000KVAH
Q H :0.000KVARHF R E Q : 50.1Hz
AUTO
20A1Φ 2WSEC: 2
:- 0.0°
1
1
5-2 1Φ 3W (one phase by three wires) measurement
A : Diagram
screen1 ( 5-2 )
36
Page 40
B : Operation Instructions:
50.0
CT: 1
PT: 1
B-1 : Power on the instrument by pressing POWER KEY,
and then press 1Φ 3Φ KEY to select the 1Φ 3W system,
the selected name of system will be appeared on bottom
left display of screen 2.
B-2 : Connect the line voltage L1, L2 and Vn (Neutral) to
V1, V2 and N terminals of the instrument.
B-3 : Place the conductor of CP-1200(A1), CP-1200(A2)
hook to A1 and A2 as screen 1.
B-4 : Connect the outputs of clamp meter
CP-1200(A1)、CP-1200(A2) to A1 and A2 terminals of
the instrument.
B-5 : The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-11, page 49 ).
screen 2 ( 5-2 )
V 1 :0.0VP 1 : -0.000KW
V 2 :0.0VP 2 : -0.000KW
A 1 :0.00AS 1 :0.000KVA
A 2 :0.00AS 2 :0.000KVA
Q 1 : -0.000KVAR
Q 2 : -0.000KVAR
, CP-1200(A2), CP-1200(A3) to A1, A2, A3 terminals
measurement
A : Diagram
screen 1 ( 5-3 )
B : Operation Instructions:
B-1 : Power on the instrument by pressing POWER KEY,
and then press 1Φ 3Φ KEY to select the 3Φ 3W system,
the selected name of system will be appeared on bottom
left display of screen 2.
B-2: Connect the line voltage L1, L2 and L3 to V1, V2
and V3 terminals of the instrument.
B-3: Place the conductor of CP-1200(A1), CP-1200(A2),
CP-1200(A3) hook to A1, A2 ,A3 as screen 1.
B-4 : Connect the outputs of clamp meter CP-1200(A1)
of the instrument.
B-5: The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-11, page 49 ).
38
Page 42
screen 2 ( 5-3 )
50.0
CT: 1
PT: 1
screen 1 ( 5-4 )
V 1 2 :0.0VA 1 :0.00A
V 2 3 :0.0VA 2 :0.00A
V 3 1 :0.0VA 3 :0.00A
P Σ:- 0.000 KW
S Σ:0.000 KVA
Q Σ :0.000 KVAR
PFΣ :0.00P F H : 0.00
WH:0.000 KWHSH:0.000 KVAH
QH:0.000 KVARHFREQ:
AUTO
20A3Φ 3WSEC: 2
Hz
1
5-4 3Φ 4W (three phases by four wires)
measurement
A : Diagram
1
39
Page 43
B: Operation Instructions:
PΣ :
CT: 1
PT: 1
B-1 : Power on the instrument by pressing POWER KEY,
and then press 1Φ 3Φ KEY to select the 3Φ 4W system,
the selected name of system will be appeared on bottom
left display of screen 2.
B-2 : Connect the line voltage L1, L2, L3 and Vn to
V1, V2, V3 and N terminals of the instrument.
B-3 : Place the conductor of CP-1200(A1), CP-1200(A2)、
CP-1200(A3) hook to A1, A2, A3 as screen 1.
B-4 : Connect the outputs of clamp meter
CP-1200(A1), CP-1200(A2), CP-1200(A3) to
A1、A2、A3 terminals of the instrument.
B-5 : The related measuring factors will be appeared
on display, about the instruction of factor please refer
appendix 1 ( 5-11, page 49 ).
B-1 : Power on the instrument by pressing POWER KEY,
and then press 1Φ 3Φ KEY to select the 3Φ 4W system,
the selected name of system will be appeared on bottom
left display of screen 2.
B-2 : Connect the line voltage L1, L2, L3 and Vn to V1,
, V3 and N terminals of the instrument.
B-3 : Place the conductor of CP-1200(A1), CP-1200(A2),
CP-1200(A3) hook to A1, A2 , A3 as screen 1.
B-4: Connect the outputs of clamp meter CP-1200(A1),
CP-1200(A2), CP-1200(A3) to A1, A2, A3 terminals
of the instrument.
B-5: The related measuring factors will be appeared on
display, about the instruction of factor please refer
appendix 1 ( 5-11, page 49 ).
If reset the " Exit key button " ( 3-8, Fig. 1 ) continuously
and > 6 seconds, the measurement value of " WH ", " SH ",
" QH " will reset to Zero value.
42
Page 46
5-7 Data Logger Function
PΣ :
CT: 1
PT: 1
A : Press REC KEY once to start the data record function.
A-1 : If the bottom right shows as " Change Card ", it
indicates the memory space is already full either or the
SD CARD exist some wrong.
A-2 : If the SD CARD is normal, the data logger function
will start to be executed.
B : The bottom right display will show the recorded data
points.
B-1 : Each file can record up to 30,000 data points as
screen 1 when the record points exceed 30,000 points,
system will create a new file automatically. (For example,
WTA01001.XLS will be replaced by WTA01002.XLS)
B-2 : While pressing REC KEY twice, the data logger
function will stop to execute, the record points will
disappear on bottom right display as screen 2.
A: During the measurement, press HOLD KEY once, the
bottom right display will show “ HOLD symbol as screen 1.
B: Press the HOLD KEY twice will disable the Data HOLD
function and the “ HOLD” symbol will disappear in the
meantime
45
Page 49
5-9 BACKLIGHT KEY
PΣ :
CT: 1
PT: 1
screen 1 ( 5-9 )
Control the backlight function of LCD to ON/OFF
5-10 A ( Current ) RANGE KEY function
Change AUTO RANGE to MANUAL RANGE
A : One by one to press A RANGE KEY will entry to
different ranges as following screens in sequence. Range
200A (as show on bottom left display of screen 1) to
1200A (as screen 2) to 20A (as screen 3)
B : When hold A RANGE KEY down at least for 2 seconds
will change MANUAL to AUTO as show on bottom left
display of screen 4.
D9Decimal Point(DP), position from right to the left
0 = No DP, 1= 1 DP, 2 = 2 DP, 3 = 3 DP
D8 to D1Display reading, D1 = LSD, D8 = MSD
For example :
If the display reading is 1234, then D8 to D1 is :
00001234
D0End Word
RS232 setting
Baud rate9600
ParityNo parity
Data bit no. 8 Data bits
Stop bit1 Stop bit
52
Page 56
8. Download the saving data from the
1)
2)
3)
software screen ( for example as following EXCEL data
SD card to the computer ( EXCEL
software )
After execute the Data Logger function, take away the
SD card out from the " SD card socket " ( 3-15, Fig. 1 ).
Plug in the SD card into the Computer's SD card slot
( if your computer build in this installation ) or
insert the SD card into the " SD card adapter ". then
connect the " SD card adapter " into the computer.
Power ON the computer and run the " EXCEL software ".
Down load the saving data file ( for example the file
name : 3P401001.XLS, 1P201001.XLS, 1P301001.XLS,
3P301001.XLS........) from the SD card to the
computer. The saving data will present into the EXCEL
screens ) , then user can use those EXCEL data to make
the further Data or Graphic analysis usefully.
EXCEL data screen 1 ( for example )
53
Page 57
EXCEL data screen 2 ( for example )
EXCEL data screen 3 ( for example )
EXCEL data screen 4 ( for example )
54
Page 58
EXCEL data screen 5 ( for example )
EXCEL data screen 6 ( for example )
EXCEL graphic screen 1 ( for example )
55
Page 59
EXCEL graphic screen 2 ( for example )
EXCEL graphic screen 3 ( for example )
56
Page 60
EXCEL graphic screen 4 ( for example )
EXCEL graphic screen 5 ( for example )