PB Heat PSC-06, PSC-05, PSC-04, PSC-03 Installation, Operation & Maintenance Manual

PSC
Boilers
Series
Gas
Installation, Operation & Maintenance Manual
i
USING THIS MANUAL 1
A. INSTALLATION SEQUENCE . . . . . . . . . . . . .1
B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .1
1. PREINSTALLATION 2
A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .2
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . .2
C. INSTALLATION SURVEY . . . . . . . . . . . . . . . .2
D. PLANNING THE LAYOUT . . . . . . . . . . . . . . . .2
2. BOILER SET-UP 3
3. WATER PIPING AND CONTROLS 4
A. BOILER SUPPLY AND RETURN . . . . . . . . . . .4
B. SAFETY RELIEF VALVE . . . . . . . . . . . . . . . . .5
C. PIPING FOR ZONED SYSTEMS . . . . . . . . . . .6
D. EXPANSION TANK . . . . . . . . . . . . . . . . . . . . .7
E. INDIRECT-FIRED WATER HEATER . . . . . . . .7
F. FREEZE PROTECTION . . . . . . . . . . . . . . . . . .7
4. VENTING, VENTILATION AND AIR INLET 8
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
B. PSC WALL THIMBLE . . . . . . . . . . . . . . . . . . .8
C. ROOF TERMINATIONS . . . . . . . . . . . . . . . .10
D. VENT PIPE INSTALLATION . . . . . . . . . . . . .11
E. AIR INLET PIPE INSTALLATION . . . . . . . . .11
F. AIR FOR VENTILATION . . . . . . . . . . . . . . . .12
G. BOILER REMOVAL FROM COMMON
VENTING SYSTEM . . . . . . . . . . . . . . . . . . .12
5. GAS PIPING 13
6. ELECTRICAL 15
A. WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
B. ZONED SYSTEM WIRING . . . . . . . . . . . . . .15
C. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . .15
D. SEQUENCE OF OPERATION . . . . . . . . . . . .16
7. START-UP PROCEDURES 19
A. COMPLETING THE INSTALLATION . . . . . . .19
B. CONTROL DESCRIPTIONS . . . . . . . . . . . . .22
C. ADJUSTMENT OF GAS PRESSURE
REGULATOR . . . . . . . . . . . . . . . . . . . . . . . . .22
D. CHECKING BURNER INPUT . . . . . . . . . . . . .22
E. CHECK-OUT PROCEDURE . . . . . . . . . . . . . .22
8. TROUBLESHOOTING 24
A. SHUT-DOWN CAUSED BY PILOT OUTAGE,
PRESSURE SWITCH OR FLAME ROLL-OUT
SAFETY SHUT-OFF SWITCH . . . . . . . . . . . .24
B. TROUBLESHOOTING GUIDES . . . . . . . . . .24
C. MEASURING SUCTION PRESSURE . . . . . .24
9. MAINTENANCE 28
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .29
B. DAILY (WITH BOILER IN USE) . . . . . . . . . . .29
C. WEEKLY (WITH BOILER IN USE) . . . . . . . . .29
D. MONTHLY (WITH BOILER IN USE) . . . . . . .29
E. ANNUALLY (BEFORE START OF HEATING
SEASON) . . . . . . . . . . . . . . . . . . . . . . . . . . .30
10. BOILER DIMENSIONS & RATINGS 32
11. REPAIR PARTS 33
TABLE OF CONTENTS
1
USING THIS MANUAL
A. INSTALLATION SEQUENCE
Follow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation.
B. SPECIAL ATTENTION BOXES
Throughout this manual you will see special attention boxes intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgment of PB Heat, LLC:
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
NOTICE
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
USING THIS MANUAL
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
2
PREINSTALLATION
A. ACCESSIBILITY CLEARANCES
Install boiler not less than 24(610 mm) between the left side, top, and front of the boiler and adjacent wall or other appliance, when access is required for servicing.
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION
The design of this boiler is certified for closet installation with the following clearances:
1. 6(152 mm) between right side, front and combustible construction.
2. 12(305 mm) between top of jacket and combustible construction.
3. 1(25 mm) between left side, rear and combustible construction.
4. 2(51 mm) between vent pipe and combustible construction.
5. Zero clearance between wall thimble and combustible construction.
6. This boiler is design certified for use on combustible flooring.
C. INSTALLATION SURVEY
For new and existing installations, a Water Installation Survey is available from PB Heat, LLC. The survey will provide information on how a hot water boiler works with your specific system and will provide an overview of hot water system operation in general.
You can also use this survey to locate system problems which will have to be corrected. To obtain copies of the Water Installation Survey, contact your PB Heat representative.
D. PLANNING THE LAYOUT
Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring. Review limitations on vent pipe, vent terminal, and air inlet pipe locations and ventilation air requirements in Section 4.
1. PREINSTALLATION
Read carefully, study these instructions before beginning work.
This boiler must be installed by a qualified contractor.
The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.
The equipment must be installed in accordance with those installation requirements of the authority having jurisdiction or, in the absence of such requirements,to the current edition of the
National Fuel Gas Code,
ANSI
Z223.1/NFPA 54 and/or CAN/CSA B49.1,
Natural Gas and Propane Installation Code
.
Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1.
NOTICE
Do not install this boiler on carpeting. Boiler installation on carpeting is a fire hazard. Install this boiler on non-combustible flooring or use a combustible floor pan to install this boiler on other non-carpeted flooring.
DANGER
Liquefied Petroleum (LP) is heavier than air and may collect or “pool” in a low area in the event of a leak from defective equipment.This gas may then ignite, resulting in a fire or explosion.
WARNING
3
BOILER SET-UP
1. Provide a sound, level foundation. Locate boiler as near to the outside wall as possible and centralized with respect to the heating system.
2. Locate boiler in front of installation position before removing crate.
4. Separate the wood shipping pallet from the boiler base by removing two (2) hold-down bolts at each end of the boiler base.
5. Move boiler into final position.
2. BOILER SET-UP
4
WATER PIPING AND CONTROLS
A. BOILER SUPPLY AND RETURN
1. Size the supply and return to suit the system. A typical piping arrangement is shown in Figure 3.1. Refer also to the Hydronics Institute Residential Hydronic Heating Installation Design Guide and the PB Heat Water Survey for additional guidance during water piping installation.
2. Return Piping: Pipe the outlet connection of the circulator to a tee,
provided with a drain valve, at the 1-1/4NPT return tapping near the bottom of the right section. Pipe the return to the inlet connection of the circulator.
3. Supply Piping: a. Pipe the supply to the 1-1/2NPT supply tapping
at the top of the boiler.
b. Provide clearance to venting system
(see Section 4).
4. When system return water temperature will be below
130°F (54°C), pipe the boiler with a bypass arrangement to blend the system return and hot supply to obtain at least 130°F (54°C)entering the boiler. For more information on bypass piping, consult the PB Heat Water Survey.
5. If desired, install the circulator in the alternate
location shown in Figure 3.1. Consult the PB Heat Water Survey for more information on circulator location.
3. WATER PIPING AND CONTROLS
Figure 3.1: Supply and Return Piping
5
WATER PIPING AND CONTROLS
6. Install this boiler so that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacements, etc.).
7. If this boiler and distribution system is used in conjunction with a refrigeration system, pipe the chilled medium in parallel with the boiler and install the proper valve to prevent the chilled medium from entering the boiler. A drawing illustrating this hook­up is provided in Figure 3.2.
8. When the boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, install flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
9. If this boiler is installed above radiation level, provide a low water cutoff device, either as a part of the boiler or at the time of boiler installation.
B. SAFETY RELIEF VALVE
1. Locate safety relief valve and fittings in bag assembly.
2. If air elimination is not required at the safety relief valve tapping, install valve and piping as shown in Figure 3.3.
3. For air elimination at the safety relief valve tapping, install valve and piping as shown in Figure 3.4.
Pipe the discharge of safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet.
CAUTION
Figure 3.4: Safety Relief Valve Hook-Up with
Air Elimination
Figure 3.3: Safety Relief Valve Hook-Up
Installation with Air Elimination in System Piping
Figure 3.2: Parallel Hook-up with Water Chiller
6
WATER PIPING AND CONTROLS
C. PIPING FOR ZONED SYSTEMS
1. See Figures 3.5 and 3.6 for basic zoned system layouts.
2. Run each zone pipe down then up to zone to prevent air accumulation in piping.
3. If required, provide means to isolate and drain each zone separately.
Figure 3.5: Zone Piping with Zone Valves
Figure 3.6: Zone Piping with Circulators
7
WATER PIPING AND CONTROLS
D. EXPANSION TANK
1. Consult the tank manufacturer’s instructions for specific information relating to tank installation. Size the expansion tank for the required system volume and capacity. See Table 10.2 in Section 10 for boiler water capacity.
2. Expansion tanks are available with built-in fill valves and check valves for reducing supply water pressure and maintaining minimum system pressure. Check the design features of the tank and provide valves as necessary.
Refer back to Figure 3.1 for typical expansion tank piping.
E. INDIRECT-FIRED WATER HEATER
If the boiler is to be used in conjunction with an indirect­fired water heater, refer to Figure 3.7 for typical piping. Follow the instructions provided by the water heater manufacturer. Pipe the water heater as a separate zone.
F. FREEZE PROTECTION
For new or existing systems that must be freeze­protected:
1. Glycol in hydronic applications is specially formulated for this purpose. It includes inhibitors which prevent the glycol from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level.
2. The glycol solution should be tested at least once a year and as recommended by the antifreeze manufacturer.
3. Glycol solutions expand more than water. For example, a 50% by volume solution expands 4.8% in volume for a temperature increase from 32°F (0°C) to 180°F (82°C) , while water expands 3% with the same temperature rise. Allowance must be made for this expansion in system design.
4. For more information, consult the PB Heat Water Installation Survey and the antifreeze manufacturer.
Figure 3.7: Typical Piping with Indirect-Fired Water Heater
Use only inhibited propylene glycol solutions of up to 50% by volume with water. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
WARNING
VENTING, VENTILATION AND AIR INLET
A. GENERAL
Install vent system in accordance with Venting of Equipment part of the National Fuel Gas Code, ANSI z223.1/NFPA 54 or sections 7.2, 7.3 or 7.4 of CAN/CSA B149.1, Natural Gas and Propane Installation Code.
B. PSC WALL THIMBLE (SIDEWALL
VENTING ONLY)
1. Determine vent cap (terminal) location. a. Must be within the maximum and minimum vent
and air intake lengths shown in Tables 4.1 and 4.2.
b. Maximum wall thickness for the 19-1/2(495 mm)
long PSC Wall Thimble (standard) is 11-1/2″ (292 mm). Maximum wall thickness for the optional 28(711 mm) long thimble is 20 (508 mm).
c. Provide 2(51 mm) clearance between vent pipe
and combustible construction. No clearance is required between Thimble and combustible construction.
d. Provide 3 feet (1 meter) clearance above any
forced air inlet within 10 feet (3 meters).
e. Provide 1 foot (0.3 meters) clearance below, 1 foot
(0.3 meters) beside, or 1 foot (0.3 meters) above any door, window, or gravity air inlet into any building.
f. Provide 1 foot (0.3 meters) clearance between
bottom of vent terminal and ground level and normal snow lines.
g. Provide 4 feet (1.2 meters) horizontal clearance
from from electric meters, gas meters, regulators and relief equipment. In Canada, this dimension must be 6 feet (2 meters).
h. Do not locate vent terminal over public walkways
where condensate could create a nuisance or hazard.
i. When adjacent to a public walkway, locate vent
terminal at least 7 feet (2.1 meters) above grade.
j. Do not locate directly under roof overhangs to
prevent icicles from forming.
2. Cut a 5-1/8(130 mm) square hole in sidewall to allow Peerless Wall Thimble to go through.
3. Insert Thimble from inside wall with 4(102 mm) diameter air inlet connection facing down. Extend Thimble 3-1/2(89 mm) past outside wall surface. The cut-out opening of thimble is pointed down.
4. Use a minimum 2-1/2 foot (762 mm) piece of 3 (76 mm) diameter AL29-4C stainless steel vent pipe for insertion through Wall Thimble. See Vent Pipe section below for vent pipe requirements.
4. VENTING
Figure 4.1: PSC Wall Thimble
This vent system will operate with a positive pressure in the vent pipe. Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure.
Flue gases will condense as they exit the vent termination.This condensate can freeze on exterior building surfaces which may cause discoloration of these surfaces.
NOTICE
WARNING
WARNING
All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products into the living space.
8
VENTING, VENTILATION AND AIR INLET
5. Slide Stainless Steel Collar over vent pipe and slide 3(76 mm) diameter hose clamp and collar to vent pipe.
6. Insert pipe with collar through Outside Vent Cap and slide 3(76 mm) diameter hose clamp and collar to vent pipe.
7. Leave at least 2(51 mm) of vent pipe protruding beyond face of Vent Cap and secure hose clamp and collar to vent pipe.
8. Place Outside Vent Cap over Wall Thimble with air openings in Vent Cap facing down. Secure Cap to Thimble with #10 sheet metal screws.
9. Place 3(76 mm) diameter hose clamp over pipe protruding through inside of Wall Thimble.
10. Place Inside Thimble Cap and Collar onto Wall Thimble. Access hose clamp through 4(102 mm) diameter collar on bottom of Thimble and secure hose clamp over collar and vent pipe as per step 7 above.
11. Secure Inside Thimble cap to Wall Thimble with #10 screws. Seal Thimble Cap perimeter with silicone.
12. Seal all openings between Wall and Thimble and around the 3(76 mm) diameter stainless steel vent pipe that protrudes through inside and outside of Wall Thimble.
13. Add any bracing that may be needed to support Wall Thimble on inside of wall structure.
14. Secure Outside Vent Cap to exterior wall with four #10 sheet metal screws provided.
15. Attach Z-Flex #2SVSTPF03 terminal to protruding vent pipe. Refer to Figure 4.2. To attach to HEAT­FAB pipe, insert into pipe end and fold over tabs to secure. Otherwise, silicone terminal to vent pipe.
Figure 4.2: Side Wall Venting System
9
10
VENTING, VENTILATION AND AIR INLET
C. ROOF TERMINATIONS (VERTICAL
VENTING)
1. Vent pipe and air inlet terminations must be within the maximum and minimum vent and air intake lengths shown in Tables 4.1 and 4.2.
2. Vent pipe and air inlet pipe must terminate 12" (305 mm) above expected snow lines. Vent pipe must be a minimum 12" (305 mm) above and 12" (305 mm) horizontally from air inlet pipe. See Figure
4.3.
3. Attach a vent manufacturer's listed rain cap to both the vent pipe and air inlet pipe.
4. Provide 2" (51 mm) clearance between vent pipe and combustible construction. No clearance is required between air inlet pipe and combustible construction.
5. See vertical venting section in vent manufacturer's instructions for recommendations for penetration through roof.
52 feet (15.5 m) 52 feet (15.5 m) 45 feet (13.5 m) 45 feet (13.5 m)
PSC-03 PSC-04 PSC-05 PSC-06
Boiler Model
8 feet (2.5 m) 8 feet (2.5 m) 8 feet (2.5 m) 8 feet (2.5 m)
Table 4.1:
*Equivalent Length of 3(76 mm) Diameter
Stainless Steel Vent Pipe
Minimum Vent Length
Maximum Vent Length
70 feet (21.0 m) 70 feet (21.0 m) 63 feet (19.0 m) 63 feet (19.0 m)
PSC-03 PSC-04 PSC-05 PSC-06
Boiler Model
12 feet (4.0 m) 12 feet (4.0 m) 12 feet (4.0 m) 12 feet (4.0 m)
Table 4.2:
*Equivalent Length of 4(102 mm) Diameter
Aluminum/Galvanized Air Inlet Pipe
Minimum Length
Maximum Length
*Each 90° elbow equals 5 feet (1.5 meters) of equivalent length.
Figure 4.3: Vertical Venting System
Loading...
+ 27 hidden pages