PB Heat DE User Manual

DE
Boilers
Series
Gas
Installation, Operation & Maintenance Manual
USING THIS MANUAL 1
A. INSTALLATION SEQUENCE . . . . . . . . . . . . .1
B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .1
1. PREINSTALLATION 2
A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .2
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . .2
C. AIR FOR COMBUSTION AND
VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . .2
D. INSTALLATION SURVEY . . . . . . . . . . . . . . . .5
E. PLANNING THE LAYOUT . . . . . . . . . . . . . . . .5
2. BOILER SET-UP 6
3. WATER PIPING AND CONTROLS 7
A. BOILER SUPPLY AND RETURN . . . . . . . . . . .7
B. SAFETY RELIEF VALVE . . . . . . . . . . . . . . . . .8
C. PIPING FOR ZONED SYSTEMS . . . . . . . . . . .9
D. EXPANSION TANK . . . . . . . . . . . . . . . . . . . .10
E. INDIRECT-FIRED WATER HEATER . . . . . . .10
F. FREEZE PROTECTION . . . . . . . . . . . . . . . . .10
4. VENTING 11
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .11
B. CHIMNEY VENTING . . . . . . . . . . . . . . . . . . .11
C. DIRECT EXHAUST
HORIZONTAL VENTING- . . . . . . . . . . . . . . .11
D. DIRECT EXHAUST
VERTICAL VENTING . . . . . . . . . . . . . . . . . .14
E. BOILER REMOVAL FROM
COMMON VENTING SYSTEM . . . . . . . . . .15
5. GAS PIPING 16
6. ELECTRICAL 18
A. WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
B. ZONED SYSTEM WIRING . . . . . . . . . . . . . .18
C. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . .18
D. SEQUENCE OF OPERATION . . . . . . . . . . . .19
7. START-UP PROCEDURES 22
A. COMPLETING THE INSTALLATION . . . . . . .22
B. CONTROL DESCRIPTIONS . . . . . . . . . . . . .25
C. ADJUSTMENT OF GAS PRESSURE
REGULATOR . . . . . . . . . . . . . . . . . . . . . . . . .25
D. CHECKING BURNER INPUT . . . . . . . . . . . . .25
E. CHECK-OUT PROCEDURE . . . . . . . . . . . . . .26
8. TROUBLESHOOTING 28
A. SHUT-DOWN CAUSED BY PILOT OUTAGE,
PRESSURE SWITCH OR FLAME ROLL-OUT
SAFETY SHUT-OFF SWITCH . . . . . . . . . . . .28
B. TROUBLESHOOTING GUIDES . . . . . . . . . .28
C. MEASURING SUCTION PRESSURE . . . . . .28
9. MAINTENANCE 32
A. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .33
B. DAILY (WITH BOILER IN USE) . . . . . . . . . . .33
C. WEEKLY (WITH BOILER IN USE) . . . . . . . . .33
D. MONTHLY (WITH BOILER IN USE) . . . . . . .33
E. ANNUALLY (BEFORE START OF HEATING
SEASON) . . . . . . . . . . . . . . . . . . . . . . . . . . .34
10. BOILER DIMENSIONS & RATINGS 35
11. REPAIR PARTS 36
A. BLOCK/BASE/FLOOR PAN
JACKET/FLUE COLLECTOR . . . . . . . . . . . . .36
B. BASE/BURNERS/MANIFOLD . . . . . . . . . . . .37
TABLE OF CONTENTS
TABLE OF CONTENTS
1
A. INSTALLATION SEQUENCE
Follow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation.
B. SPECIAL ATTENTION BOXES
Throughout this manual you will see special attention boxes intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgment of PB Heat, LLC:
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
NOTICE
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
USING THIS MANUAL
USING THIS MANUAL
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
2
A. ACCESSIBILITY CLEARANCES
Install boiler not less than 24(610 mm) between the left side, top, and front of the boiler and adjacent wall or other appliance, when access is required for servicing.
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION
The design of this boiler is certified for closet installation with the following clearances:
1. 6(152 mm) between sides, rear and front and
combustible construction.
2. 24(610 mm)between top of jacket and
combustible construction.
3. 2(51 mm) between vent pipe and combustible
construction.
C. AIR FOR COMBUSTION AND
VENTILATION
1. Adequate combustion air and ventilation air must be provided in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections 7.2,
7.3 or 7.4 of CAN/CSA B149.1, Natural Gas and Propane Installation Code or applicable provisions of the local building code. Subsections 2 through 8 as follows are based on the National Fuel Gas Code requirements.
2. Requir
ed Combustion Air Volume: The total required volume of indoor air is to be the sum of the required volumes for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed and through combustion air openings sized as indicated in Subsection 3 are considered part of the required volume. The required volume of indoor air is to be determined by one of two methods.
a. Standard Method: The minimum required
volume of indoor air (room volume) shall be 50 cubic feet per 1000 BTU/Hr (4.8 m3/kW). This method is to be used if the air infiltration rate is unknown or if the rate of air infiltration is known to be greater than 0.6 air changes per hour. As an option, this method may be used if the air infiltration rate is known to be between 0.6 and
0.4 air changes per hour. If the air infiltration rate is known to be below 0.4 then the Known Air Infiltration Rate Method must be used. If the building in which this appliance is to be installed is unusually tight, we recommend that the air infiltration rate be determined.
b. Known Air Infiltration Rate Method: Where
the air infiltration rate of a structure is known, the minimum required volume of indoor air for the Series DE Boiler and other fan assisted appliances shall be determined as follows:
PREINSTALLATION
1. PREINSTALLATION
Read carefully, study these instructions before beginning work.
This boiler must be installed by a qualified contractor.
The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.
The equipment must be installed in accordance with those installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the
National Fuel Gas Code
, ANSI
Z223.1/NFPA 54 and/or CAN/CSA B149.1,
Natural Gas and Propane Installation Code
.
Where required by the authority having jurisdiction, the installation must conform to
American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1.
NOTICE
Do not install this boiler on carpeting. Boiler installation on carpeting is a fire hazard. Install this boiler on non-combustible flooring or use a combustible floor pan to install this boiler on other non-carpeted flooring.
DANGER
Do not install this boiler on combustible flooring unless it is installed on a special combustible floor pan provided by PB Heat, LLC. Boiler installation on combustible flooring without the special pan is a fire hazard.
To order combustible floor pan, use the 5-digit stock codes listed in Section 11 of this manual.
DANGER
15 ft
3
I
fan
ACH 1000
Btu
/
hr
Required Volume
fan
=
⎛ ⎜ ⎝
3
where:
I
fan
= Input of the fan assisted appliances in
Btu/hr
ACH = air change per hour (percent of the
volume of the space exchanged per hour, expressed as a decimal)
For appliances other than fan assisted, calculate the required volume of air using the following equation:
I
other
= Input of appliances other than fan
assisted in Btu/hr
Note: These calculations are not to be used for infiltration rates greater than 0.60 ACH.
3. Indoor Air Opening Size and Location:
Openings connecting indoor spaces shall be sized and located as follows:
a. Combining spaces on the same floor:
Provide two permanent openings communicating with additional spaces that have a minimum free area of 1 in
2
per 1000 Btu/hr (22 cm2per 1000 W) of the total input rating of all gas fired equipment but not less than 100 in
2
(645 cm2). One opening is to begin within 12 inches (305 mm) from the top of the space and the other is to begin within 12 inches (305 mm) from the floor. The minimum dimension of either of these openings shall be 3 inches (76 mm). See Figure
1.1 for an illustration of this arrangement.
b. Combining spaces on different floors:
Provide one or more permanent openings communicating with additional spaces that have a total minimum free area of 2 in
2
per 1000
Btu/hr (44 cm
2
per 1000 W) of total input rating of all equipment. See Figure 1.2 for an illustration of this arrangement.
4. Outdoor Combustion Air:
Outdoor combustion air is to be provided through one or two permanent openings. The minimum dimension of these air openings is 3 inches (76 mm).
a. Two Permanent Opening Method: Provide
two permanent openings. One opening is to begin within 12 inches (305 mm) of the top of the space and the other is to begin within 12 inches (305 mm) of the floor. The openings are to communicate directly or by ducts with the outdoors or with spaces that freely communicate with the outdoors. The size of the openings shall be determined as follows:
i. Where communicating directly or through
vertical ducts with the outdoors each opening shall have a minimum free area of 1 in
2
per
4000 Btu/hr (22 cm
2
per 4000 W) of total input rating for all equipment in the space. See Figure 1.3 for openings directly communicating with the outdoors or Figure
1.4 for openings connected by ducts to the outdoors.
PREINSTALLATION
Figure 1.1: Air Openings – All Air from Indoors
on the Same Floor
Figure 1.2: Air Openings – All Air from Indoors
on Different Floors
21 ft
3
I
other
ACH 1000
Btu
/
hr
Required Volume
other
=
⎛ ⎜ ⎝
Figure 1.3: Air Openings – All Air Directly from
Outdoors
4
ii. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in
2
per 2000
Btu/hr (22 cm
2
per 2000 W) of total rated input for all appliances in the space. See Figure 1.5.
b. One Permanent Opening Method: Provide
one permanent opening beginning within 12 inches (305 mm) of the top of the space. The opening shall communicate directly with the outdoors, communicate through a vertical or horizontal duct, or communicate with a space that freely communicates with the outdoors. The openings shall have a minimum free area of 1 in
2
per 3000 Btu/hr of total rated input for all appliances in the space and not less than the sum of the cross-sectional areas of all vent connectors in the space. The gas fired equipment shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance. See Figure 1.6 for this arrangement.
5. Combination Indoor and Outdoor Combustion Air: If the required volume of indoor air exceeds the available indoor air volume, outdoor air openings or ducts may be used to supplement the available indoor air provided:
a. The size and location of the indoor openings
comply with Subsection 3.
b. The outdoor openings are to be located in
accordance with Subsection 4.
c. The size of the outdoor openings are to be sized
as follows:
where:
A
req
= minimum area of outdoor openings.
A
full
= full size of outdoor openings calculated
in accordance with Subsection 4.
V
avail
= available indoor air volume
V
req
= required indoor air volume
6. Engineer
ed Installations: Engineered combustion air installations shall provide an adequate supply of combustion, ventilation, and dilution air and shall be approved by the authority having jurisdiction.
7. Mechanical Combustion Air Supply
:
a. In installations where all combustion air is
provided by a mechanical air supply system, the combustion air shall be supplied from the outdoors at the minimum rate of 0.35 ft
3
/min per
1000 Btu/hr (0.034 m
3
/min per 1000 W) of the
total rated input of all appliances in the space.
b. In installations where exhaust fans are installed,
additional air shall be provided to replace the exhaust air.
V
avail
1 –
V
req
A
req
= A
full
x
⎛ ⎜ ⎝
Figure 1.5: Air Openings – All Air from Outdoors
through Horizontal Ducts
Figure 1.6: Air Openings – All Air from Outdoors
through One Opening
Figure 1.4: Air Openings – All Air from Outdoors
through Vertical Ducts
PREINSTALLATION
5
c. Each of the appliances served shall be
interlocked to the mechanical air supply to prevent main burner operation where the mechanical air supply system is not in operation.
d. In buildings where the combustion air is provided
by the mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air.
8. Louvers & Grills:
a. The required size of openings for combustion,
ventilation, and dilution air shall be based on the net free area of each opening.
i. Where the free area through a louver or grille
is known, it shall be used in calculating the opening size required to provide the free area specified.
ii. Where the free area through a louver or grille
is not known, it shall be assumed that wooden louvers will have 25% free area and metal louvers and grilles will have 75% free area.
iii. Nonmotorized dampers shall be fixed in the
open position.
b. Motorized dampers shall be interlocked with the
equipment so that they are proven in the full open position prior to ignition and during operation of the main burner.
i. The interlock shall prevent the main burner
from igniting if the damper fails to open during burner startup.
ii. The interlock shall shut down the burner if
the damper closes during burner operation.
9. Combustion Air Ducts
a. Ducts shall be constructed of galvanized steel or
an equivalent corrosion- resistant material.
b. Ducts shall terminate in an unobstructed space,
allowing free movement of combustion air to the appliances.
c. Ducts shall serve a single space.
d. Ducts shall not serve both upper and lower
combustion air openings where both such openings are used. The separation between ducts serving upper and lower combustion air openings shall be maintained to the source of combustion air.
e. Ducts shall not be screened where terminating in
an attic space.
f. Horizontal upper combustion air ducts shall not
slope downward toward the source of the combustion air.
g. The remaining space surrounding a chimney
liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal, or factory built chimney shall not be used to supply combustion air.
h. Combustion air intake openings located on the
exterior of buildings shall have the lowest side of the combustion air intake opening at least 12 inches (305 mm) above grade.
D. INSTALLATION SURVEY
For new and existing installations, a Water Installation Survey is available from PB Heat, LLC. The survey will provide information on how a hot water boiler works with your specific system and will provide an overview of hot water system operation in general.
You can also use this survey to locate system problems which will have to be corrected. To obtain copies of the Water Installation Survey, contact your Peerless representative or download it from PeerlessBoilers.com.
E. PLANNING THE LAYOUT
Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring.
Liquefied Petroleum (LP) is heavier than air and may collect or “pool” in a low area in the event of a leak from defective equipment. This gas may then ignite, resulting in a fire or explosion.
WARNING
PREINSTALLATION
6
BOILER SET-UP
1. Provide a sound, level foundation. Locate boiler as near to the chimney or outside wall as possible and centralized with respect to the heating system.
2. Locate boiler in front of installation position before removing crate.
3. If using combustible floor pan, position pan on foundation or flooring.
4. Separate the wood shipping pallet from the boiler base by removing two (2) hold-down bolts at each end of the boiler base.
5. Move boiler into final position. If using combustible floor pan, install boiler on pan as outlined in the instructions included with the pan.
2. BOILER SET-UP
7
A. BOILER SUPPLY AND RETURN
1. Size the supply and return to suit the system. A typical piping arrangement is shown in Figure 3.1. Refer also to the I=B=R Guide to Residential Hydronic Heating Installation/Design and the PB Heat, LLC Water Survey for additional guidance during water piping installation.
2. Return Piping:
a. Pipe the outlet connection of the circulator to a
tee, provided with a drain valve, at the 1-1/4 NPT return tapping near the bottom of the left section. Pipe the return to the inlet connection of the circulator.
3. Supply Piping: Pipe the supply to the 1-1/2 NPT supply tapping at the top of the boiler.
4. When system return water temperature will be below 130°F (54°C), pipe the boiler with a bypass arrangement to blend the system return and hot supply to obtain at least 130°F (54°C) entering the boiler. For more information on bypass piping, consult the PB Heat, LLC Water Survey.
5. If desired, install the circulator in the alternate location shown in Figure 3.1. Consult the PB Heat, LLC Water Survey for more information on circulator location.
3. WATER PIPING AND CONTROLS
Figure 3.1: Supply and Return Piping
WATER PIPING AND CONTROLS
8
6. Install this boiler so that the gas ignition system components are protected from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacements, etc.).
7. If this boiler and distribution system is used in conjunction with a refrigeration system, pipe the chilled medium in parallel with the boiler and install the proper valve to prevent the chilled medium from entering the boiler. A drawing illustrating this hook­up is provided in Figure 3.2.
8. When the boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, install flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
9. If this boiler is installed above radiation level, provide a low water cutoff device, either as a part of the boiler or at the time of boiler installation.
B. SAFETY RELIEF VALVE
1. Locate safety relief valve and fittings in bag assembly.
2. If air elimination is not required at the safety relief valve tapping, install valve and piping as shown in Figure 3.3.
3. For air elimination at the safety relief valve tapping, install valve and piping as shown in Figure 3.4.
Pipe the discharge of safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet.
CAUTION
Figure 3.4: Safety Relief Valve Hook-Up with
Air Elimination
Figure 3.3: Safety Relief Valve Hook-Up
Installation with Air Elimination in System Piping
Figure 3.2: Parallel Hook-up with Water Chiller
WATER PIPING AND CONTROLS
9
C. PIPING FOR ZONED SYSTEMS
1. See Figures 3.5 and 3.6 for basic zoned system layouts.
2. Run each zone pipe down then up to zone to prevent air accumulation in piping.
3. If required, provide means to isolate and drain each zone separately.
Figure 3.5: Zone Piping with Zone Valves
Figure 3.6: Zone Piping with Circulators
WATER PIPING AND CONTROLS
10
D. EXPANSION TANK
1. Consult the tank manufacturer’s instructions for specific information relating to tank installation. Size the expansion tank for the required system volume and capacity. See Table 10.2 in Section 10 for boiler water capacity.
2. Expansion tanks are available with built-in fill valves and check valves for reducing supply water pressure and maintaining minimum system pressure. Check the design features of the tank and provide valves as necessary.
Refer back to Figure 3.1 for typical expansion tank piping.
E. INDIRECT-FIRED WATER HEATER
If the boiler is to be used in conjunction with an indirect­fired water heater, refer to Figure 3.7 for typical piping. Follow the instructions provided by the water heater manufacturer. Pipe the water heater as a separate zone.
F. FREEZE PROTECTION
For new or existing systems that must be freeze­protected:
1. Glycol in hydronic applications is specially formulated for this purpose. It includes inhibitors which prevent the glycol from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level.
2. The antifreeze solution should be tested at least once a year and as recommended by the antifreeze manufacturer.
3. Antifreeze solutions expand more than water. For example, a 50% by volume solution expands 4.8% in volume for a temperature increase from 32°F (0°C) to 180°F (82°C), while water expands 3% with the same temperature rise. Allowance must be made for this expansion in system design.
4. For more information, consult the PB Heat LLC Water Installation Survey and the antifreeze manufacturer.
Figure 3.7: Typical Piping with Indirect-Fired Water Heater
WATER PIPING AND CONTROLS
Use only inhibited propylene glycol solutions of up to 50% by volume with water. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
WARNING
11
A. GENERAL
1. Install vent system in accordance with the "Venting of Equipment" Chapter of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the "Venting Systems and Air Supply for Appliances" Section of the CAN/CSA B149.1, Natural Gas and Propane Installation Code. or applicable provisions of the local building codes.
2. Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure.
3. Refer to the following venting options to determine which method is applicable.
ON –
B. CHIMNEY VENTING
If venting into a masonry chimney; chimney must be lined with a fire clay tile liner or corrosion resistant metal liner. Type B vent may also be used as a lining system or as a stand alone chimney vent.
1. The vent system, when installed per the following instructions, will operate with a negative pressure (draft).
2. Horizontal portions of the venting system shall slope upward at least 1/4” per lineal foot (21 mm per meter) between boiler and chimney. The vent pipe shall be supported to prevent sagging; using metal strapping or equivalent means at no more than 4 ft. (1.2 meter) intervals.
3. Locate fan adapter, silicone, hardware and fan adapter gasket in boiler miscellaneous parts box and attach to blower outlet flange. Refer to Fig. 4.1 for details.
4. Apply 1/4” (6 mm) bead of silicone around fan adapter and slip increaser over the fan adapter. Refer to Table 4.1 for increaser and chimney sizes.
Increaser to be provided by installer.
5. Single wall vent pipe should be furnished between increaser and chimney. If the vent connector shall be located in or pass through a cold area, the vent connector shall be type B material.
C. DIRECT EXHAUST; HORIZONTAL
VENTING
1. This vent system will operate with a positive pressure in the vent pipe. Follow vent pipe manufacturers instructions for proper assembly of vent pipe and fittings.
4. VENTING
Figure 4.1: Chimney Venting
VENTING
Table 4.1: Increaser & Chimney Size
Boiler Model
Increaser Size
Vent Size Diameter
Chimney
Height
DE-03 DE-04 DE-05 DE-06
3" to 4" (7.6 to 10.2 cm)
3" to 5" (7.6 to 12.7 cm) 3" to 5" (7.6 to 12.7 cm) 3" to 5" (7.6 to 12.7 cm)
4" (10.2 cm) 5" (12.7 cm) 5" (12.7 cm) 5" (12.7 cm)
15' (4.5 m) 15' (4.5 m) 15' (4.5 m) 15' (4.5 m)
All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products into the living space.
WARNING
Flue gases will condense as they exit the vent termination. This condensate can freeze on exterior building surfaces which may cause discoloration of these surfaces.
NOTICE
Loading...
+ 30 hidden pages