PB Heat 211A User Manual

211A
Boilers – Steam
Series
Gas
Installation, Operation & Maintenance Manual
A. FOLLOW THE PIPING GUIDELINES . . . . . . .1
B. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . .1
C. SPECIAL ATTENTION BOXES . . . . . . . . . . . .1
1. PREINSTALLATION 2
A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .2
B. COMBUSTIBLE CONSTRUCTION
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . .2
C. AIR FOR COMBUSTION & VENTILATION . . .2
D. CHIMNEY OR VENT . . . . . . . . . . . . . . . . . . . .5
E. BOILER SETTING . . . . . . . . . . . . . . . . . . . . . .7
F. WATER QUALITY AND MAKE-UP . . . . . . . . .7
G. INSTALLATION SURVEY . . . . . . . . . . . . . . . .7
2. ASSEMBLE THE BASE 9
A. BASE ASSEMBLY . . . . . . . . . . . . . . . . . . . . .9
B. INSTALL THE PILOT BURNERS . . . . . . . . . .10
3. PLACE THE BOILER SECTIONS 14
A. PREPARATION . . . . . . . . . . . . . . . . . . . . . . .14
B. PLACING THE SECTIONS . . . . . . . . . . . . . .14
C. HYDROSTATIC TEST THE BOILER . . . . . . .16
4. INSTALL THE FLUE COLLECTOR 17
5. PIPE THE BOILER 19
A. PREPARATION . . . . . . . . . . . . . . . . . . . . . . .19
B. SUPPLY PIPING . . . . . . . . . . . . . . . . . . . . . .19
C. RETURN PIPING . . . . . . . . . . . . . . . . . . . . . .19
D. MULTIPLE BOILER INSTALLATIONS . . . . . .21
6. INSTALL THE JACKET & DRAFT HOOD 23
A. PREPARE THE PARTS . . . . . . . . . . . . . . . . .23
B. APPLY CLEANOUT COVER PLATES . . . . . .23
C. APPLY JACKET END ASSEMBLIES . . . . . .23
D. 211A-04 THROUGH 211A-08 ONLY . . . . . .23
E. 211A-09 AND LARGER ONLY . . . . . . . . . . .23
F. APPLY JACKET TOP PANELS . . . . . . . . . . .24
G. APPLY LOWER END PANELS . . . . . . . . . . .24
H. APPLY PLATES AND LABELS . . . . . . . . . . .24
7. CONNECT GAS PIPING 29
A. INSTALL GAS TRAIN . . . . . . . . . . . . . . . . .29
B. CONNECT PILOT GAS TUBING . . . . . . . . . .29
C. INSTALL VENT AND BLEED PIPING . . . . . .29
D. INSTALL GAS SUPPLY PIPING . . . . . . . . . .30
E. TEST GAS SUPPLY PIPING . . . . . . . . . . . . .30
8. INSTALL CONTROLS AND TRIM 32
A. INSTALL SAFETY VALVE(S) . . . . . . . . . . . .32
B. INSTALL BLOWDOWN VALVES . . . . . . . . .32
C. INSTALL LOW WATER CUT-OFF(S) . . . . . .32
D. INSTALL PRESSURE CONTROLS . . . . . . . .32
9. WIRE THE BOILER 37
A. CONNECT SUPPLY WIRING . . . . . . . . . . . .37
B. PREPARE REMAINING CONTROLS . . . . . .37
C. INSTALL CONTROL WIRING . . . . . . . . . . . .37
10. STARTING THE BOILER 40
A. CHECK THE PIPING . . . . . . . . . . . . . . . . . . .40
B. FILL THE BOILER . . . . . . . . . . . . . . . . . . . . .40
C. STUDY LIGHTING INSTRUCTIONS . . . . . . .40
D. RUN PILOT CHECK-OUT . . . . . . . . . . . . . . .40
E. CHECK MAIN BURNER SYSTEM . . . . . . . .40
F. CHECK BOILER CONTROLS . . . . . . . . . . . .41
G. CLEAN THE BOILER . . . . . . . . . . . . . . . . . . .41
11. LIGHTING INSTRUCTIONS - TYPICAL 42
A. TO LIGHT THE BOILER . . . . . . . . . . . . . . . .42
B. TO SHUT DOWN THE BOILER . . . . . . . . . .42
C. PILOT FLAME FAILURE . . . . . . . . . . . . . . . .42
12. OPERATION & MAINTENANCE 43
A. PLACING BOILER IN OPERATION . . . . . . . .44
B. TO SHUT DOWN THE BOILER . . . . . . . . . .45
C. ANNUAL MAINTENANCE . . . . . . . . . . . . . .45
D. MONTHLY MAINTENANCE . . . . . . . . . . . . .45
E. WEEKLY MAINTENANCE . . . . . . . . . . . . . .45
F. DAILY MAINTENANCE . . . . . . . . . . . . . . . . .45
13. TROUBLESHOOTING - SERVICE TIPS 46
14. BOILER RATINGS & DIMENSIONS 48
15. REPAIR PARTS - SERIES 211A 52
TABLE OF CONTENTS
TABLE OF CONTENTS
1
USING THIS MANUAL
A. FOLLOW THE PIPING GUIDELINES
1. We have provided suggested piping diagrams which will cover most applications of this boiler.
2. Follow these guidelines to make sure the boiler will operate correctly.
B. CONTROLS
1. This manual provides wiring diagrams and lighting instructions for standard systems only.
2. Use the Lighting Instructions and Wiring Diagrams provided with the boiler to make sure they represent the controls provided.
C. SPECIAL ATTENTION BOXES
1. Throughout this manual you will see special attention boxes intended to supplement the instructions and make special notice of potential hazards. These categories mean, in the judgment of PB Heat, LLC:
USING THIS MANUAL
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
NOTICE
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
2
PREINSTALLATION
A. ACCESSIBILITY CLEARANCES
1. The following recommendations allow for reasonable access to the boiler. Local codes or special
conditions may require greater clearances.
a. For servicing the boiler: provide 48" (1219 mm)
between the control manifold and adjacent wall or other appliance.
b. For access to draft hood or passage to access the
boiler control manifold(s): provide 48" (1219 mm) between the side of the boiler and adjacent wall or other appliance.
c. See Figure 1.1. Clearances with an “S” are
minimum clearances for service accessibility.
B. COMBUSTIBLE CONSTRUCTION
CLEARANCES
1. This boiler is design certified for the following clearances to combustible construction.
24" (610 mm) between the front, top, sides and rear of the jacket.
6" (152 mm) from steam and hot water pipes
6" (152 mm) from vent connector
See Figure 1.1. Clearances with a “C” indicate
minimum clearances from combustible construction.
C. AIR FOR COMBUSTION AND
VENTILATION
1. Adequate combustion air and ventilation air must be provided for this appliance in accordance with the section of the National Fuel Gas Code entitled, “Air for Combustion and Ventilation” or applicable provisions of the local building code. Subsections 2 through 8 as follows are based on the National Fuel Gas Code requirements.
1. PREINSTALLATION
The equipment shall be installed with those installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the
National Fuel Gas Code
, ANSI Z223.1/NFPA 54 and/or
CAN/CGA B149 Installation Codes.
Where required by the authority having jurisdiction, the installation must conform to
American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers,
ASME CSD-1.
NOTICE
Read these instructions carefully before beginning the installation.
Study the control folder and consult drawings.
A shipping list is enclosed with each boiler, listing the items packed at the factory. Check the list as you unpack parts. If any parts are missing or damaged, report the problem to the delivering carrier immediately.
Figure 1.1: Clearance Requirements
3
PREINSTALLATION
2. Required Combustion Air Volume: The total required volume of indoor air is to be the sum of the required volumes for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed and through combustion air openings sized as indicated in Subsection 3 are considered part of the required volume. The required volume of indoor air is to be determined by one of two methods.
a. Standard Method: The minimum required
volume of indoor air (room volume) shall be 50 cubic feet per 1000 BTU/Hr (4.8 m
3
/kW). This method is to be used if the air infiltration rate is unknown or if the rate of air infiltration is known to be greater than 0.6 air changes per hour. As an option, this method may be used if the air infiltration rate is known to be between 0.6 and
0.4 air changes per hour. If the air infiltration rate is known to be below 0.4 then the Known Air Infiltration Rate Method must be used. If the building in which this appliance is to be installed is unusually tight, PB Heat recommends that the air infiltration rate be determined.
b. Known Air Infiltration Rate Method:
Where the air infiltration rate of a structure is known, the minimum required volume of indoor air for appliances other than fan assisted and for the Series 211A Boiler shall be determined as follows:
where:
I
other
= Input of appliances other than fan
assisted in Btu/hr
ACH = air change per hour (percent of the
volume of the space exchanged per hour, expressed as a decimal)
For fan assisted appliances, calculate the required volume of air using the following equation:
I
fan
= Input of the fan assisted appliances in
Btu/hr
Note: These calculations are not to be used for infiltration rates greater than 0.60 ACH.
3. Indoor Air Opening Size and Location:
Openings
connecting indoor spaces shall be sized and located as follows:
a. Combining spaces on the same floor:
Provide two permanent openings communicating with additional spaces that have a minimum free area of 1 in
2
per 1000 Btu/hr (22 cm2per 1000 W) of the total input rating of all gas fired equipment but not less than 100 in
2
(645 cm2). One opening is to begin within 12 inches (305 mm) from the top of the space and the other is to begin within 12 inches (305 mm) from the floor. The minimum dimension of either of these openings shall be 3 inches (76 mm). See Figure
1.2 for an illustration of this arrangement.
b. Combining spaces on different floors:
Provide one or more permanent openings communicating with additional spaces that have a total minimum free area of 2 in
2
per 1000
Btu/hr (44 cm
2
per 1000 W) of total input rating of all equipment. See Figure 1.3 for an illustration of this arrangement.
4. Outdoor Combustion Air:
Outdoor combustion air is to be provided through one or two permanent openings. The minimum dimension of these air openings is 3 inches (76 mm).
a. Two Permanent Opening Method: Provide
two permanent openings. One opening is to begin within 12 inches (305 mm) of the top of the space and the other is to begin within 12 inches (305 mm) of the floor. The openings are to communicate directly or by ducts with the outdoors or with spaces that freely communicate with the outdoors. The size of the openings shall be determined as follows:
21 ft
3
I
other
ACH 1000
Btu
/
hr
Required Volume
other
=
⎛ ⎜ ⎝
Figure 1.2: Air Openings – All Air from Indoors
on the Same Floor
Figure 1.3: Air Openings – All Air from Indoors
on Different Floors
15 ft
3
I
fan
ACH 1000
Btu
/
hr
Required Volume
fan
=
⎛ ⎜ ⎝
4
i. Where communicating directly or through
vertical ducts with the outdoors each opening shall have a minimum free area of 1 in
2
per
4000 Btu/hr (22 cm
2
per 4000 W) of total input rating for all equipment in the space. See Figure 1.4 for openings directly communicating with the outdoors or Figure
1.5 for openings connected by ducts to the outdoors.
ii. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in
2
per 2000
Btu/hr (22 cm
2
per 2000 W) of total rated input for all appliances in the space. See Figure 1.6.
b. One Permanent Opening Method: Provide
one permanent opening beginning within 12 inches (305 mm) of the top of the space. The opening shall communicate directly with the outdoors, communicate through a vertical or horizontal duct, or communicate with a space that freely communicates with the outdoors. The opening shall have a minimum free area of 1 in
2
per 3000 Btu/hr of total rated input for all appliances in the space and not less than the sum of the cross-sectional areas of all vent connectors in the space. The gas-fired equipment shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance. See Figure 1.7 for this arrangement.
Figure 1.4: Air Openings – All Air Directly from
Outdoors
Figure 1.5: Air Openings – All Air from Outdoors
through Vertical Ducts
Figure 1.6: Air Openings – All Air from Outdoors
through Horizontal Ducts
Figure 1.7: Air Openings – All Air from Outdoors
through One Opening
PREINSTALLATION
5. Combination Indoor and Outdoor Combustion Air: If the required volume of indoor air exceeds the available indoor air volume, outdoor air openings or ducts may be used to supplement the available indoor air provided:
a. The size and location of the indoor openings
comply with Subsection 3.
b. The outdoor openings are to be located in
accordance with Subsection 4.
c. The size of the outdoor openings are to be sized
as follows:
where:
A
req
= minimum area of outdoor openings.
A
full
= full size of outdoor openings calculated
in accordance with Subsection 4.
V
avail
=available indoor air volume
V
req
= required indoor air volume
6. Engineer
ed Installations: Engineered combustion air installations shall provide an adequate supply of combustion, ventilation, and dilution air and shall be approved by the authority having jurisdiction.
7. Mechanical Combustion Air Supply
:
a. In installations where all combustion air is
provided by a mechanical air supply system, the combustion air shall be supplied from the outdoors at the minimum rate of 0.35 ft
3
/min per
1000 Btu/hr (0.034 m
3
/min per 1000 W) of the
total rated input of all appliances in the space.
b. In installations where exhaust fans are installed,
additional air shall be provided to replace the exhaust air.
c. Each of the appliances served shall be
interlocked to the mechanical air supply to prevent main burner operation when the mechanical air supply system is not in operation.
d. In buildings where the combustion air is provided
by the mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air.
8. Louvers & Grills:
a. The required size of openings for combustion,
ventilation, and dilution air shall be based on the net free area of each opening.
i. Where the free area through a louver or grille
is known, it shall be used in calculating the opening size required to provide the free area specified.
ii. Where the free area through a louver or grille
is not known, it shall be assumed that wooden louvers will have 25% free area and metal louvers and grilles will have 75% free area.
iii. Nonmotorized dampers shall be fixed in the
open position.
b. Motorized dampers shall be interlocked with the
equipment so that they are proven in the full open position prior to ignition and during operation of the main burner.
i. The interlock shall prevent the main burner
from igniting if the damper fails to open during burner startup.
ii. The interlock shall shut down the burner if
the damper closes during burner operation.
9. Combustion Air Ducts
a. Ducts shall be constructed of galvanized steel or
an equivalent corrosion- resistant material.
b. Ducts shall terminate in an unobstructed space,
allowing free movement of combustion air to the appliances.
c. Ducts shall serve a single space.
d. Ducts shall not serve both upper and lower
combustion air openings where both such openings are used. The separation between ducts serving upper and lower combustion air openings shall be maintained to the source of combustion air.
e. Ducts shall not be screened where terminating in
an attic space.
f. Horizontal upper combustion air ducts shall not
slope downward toward the source of the combustion air.
g. The remaining space surrounding a chimney
liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal, or factory built chimney shall not be used to supply combustion air.
h. Combustion air intake openings located on the
exterior of buildings shall have the lowest side of the combustion air intake opening at least 12 inches (305 mm) above grade.
D. CHIMNEY OR VENT
1. Inspect the existing chimney or vent system. Make sure it is in good condition. Inspect chimney liner and repair or replace if necessary.
2. The vent system and installation must be in accordance with the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, under “Venting of Equipment”, or CAN/CGA B149, Installation codes, under “Venting Systems and Air Supply for Appliances”, or applicable provisions of the local building codes.
5
PREINSTALLATION
V
avail
1 –
V
req
A
req
= A
full
⎛ ⎜ ⎝
PREINSTALLATION
3. Chimney/Vent Operation: The vent system must be sized and installed to provide the draft needed to remove all combustion products. If the vent system does not provide enough draft, combustion products will spill into the building from the draft hood relief opening. If spillage of combustion products occurs, check the vent system, the combustion and ventilation openings and make sure the boiler room is never under negative pressure.
4. Exterior Vents
a. If the vent is outside, make sure it is insulated
sufficiently to ensure adequate draft.
5. Vent Sizing:
a. Individual vents: Use vent piping the same
diameter as the boiler vent connection. The minimum height is 10 feet (305 cm) above the bottom of the draft hood (relief opening). The vent must also extend above the roof or any obstructions as outlined in the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation Codes or as required by local codes.
b. Combined vent breeching:
The recommended sizing in Section 14, Boiler Ratings & Dimensions, in this Manual is based on a minimum chimney or vent height of 20 feet (610 cm) and a maximum horizontal run of 6 feet (183 cm) to the chimney with no more than one 90-degree standard elbow.
The minimum area of the chimney serving two or more appliances must be at least the area of the largest chimney connector plus 50% of the total area of all other appliance connectors.
The vent connector must be single wall steel or Type B double wall vent pipe. The vent connector must be Type B double wall if it is located in or passes through cold areas. The vent connector must extend into, but not beyond, the inside wall of the chimney.
6. Vent Connection to Boiler (Figure 1.8): a. Provide at least a 3 foot (91 cm) rise in the vent
connection on the boiler.
b. The vent system should provide a draft of at least
0.02" w.c. (5 Pa) measured at the vent connections.
c. Support the weight of the vent system
independently of the boiler draft hood. The draft hood is not designed to carry structural loading.
d. Provide support of the vent connector
(breeching) at maximum 12 foot (366 cm) intervals to prevent sagging and to provide a minimum upward slope of 1/4" per foot (21 mm per meter).
e. Do not connect the vent for this boiler into any
vent system which operates with positive pressure.
f. Use Type B double-wall pipe for vents which run
through unheated spaces.
7. Removing an existing boiler from a common vent:
At the time for removal of an existing boiler, the following steps shall be followed with each appliance connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common
venting system.
b. Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
c. Insofar as is practical, close all building doors
and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust the thermostat so appliance will operate continuously.
e. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
Failure to provide adequate venting can result in severe property damage, personal injury or death.
WARNING
Figure 1.8: Vent Connection
6
7
PREINSTALLATION
f. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
g. Any improper operation of the common venting
system should be corrected so the installation conforms with the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables located in the chapter Sizing of Category I Venting Systems in the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA B149, Installation Codes.
E. BOILER SETTING
1. Provide a good, level foundation for the boiler with the minimum dimensions given in Figure 1.9 and Table 1.1. The flooring and structural support system must be suitable for the operating weight of the boiler and any connected piping.
2. Do not operate the boiler until the foundation, if new concrete, has thoroughly cured. The high temperature under the burners could cause major damage to the concrete if it still contains moisture.
3. If the boiler is installed in a penthouse or if wiring of any sort is run underneath the boiler foundation, construct the foundation with provision for airflow underneath between the main floor and the top of the boiler foundation.
a. Concrete block aligned with the openings
connected continuously would serve this purpose, for example.
b. If the foundation must be a concrete slab, use an
air cell high temperature insulating board, at least 1/2 inch (13 mm) thick, with aluminum backing, aluminum side up. One-half inch (13 mm) Hi Temp millboard with aluminum backing would be acceptable as well. Place the insulating board on the slab inside the base.
F. WATER QUALITY AND MAKE-UP
1. Check the system to make sure there are no leaks or overfilling problems which might cause excessive make-up water to be added. Make-up water causes liming in the boiler and brings in oxygen. Oxygen can cause severe damage to the boiler through oxygen corrosion pitting.
2. Clean the boiler as described in this manual. Poor water quality will cause foaming, priming and overfilling of the system. Too much sediment in the water will cause build-up in the boiler and could result in cracked sections due to overheating.
3. If the condensate return time lag is too long, this boiler may not work correctly with gravity return or with a condensate return unit. Long time lags will cause make-up water to be added to the boiler, resulting in flooding of the boiler, carryover to the system and excessive make-up water addition. You will need to install a boiler feed system to prevent problems in such cases.
4. Do not use chemicals or substances in the
boiler or system which contain petroleum or its derivatives. This will damage the boiler seals.
G. INSTALLATION SURVEY
For new and existing installations, a Steam Installation Survey is available from PB Heat. The survey will provide information on how a steam boiler works with your specific system and will provide an overview of steam system operation in general.
You can also use this survey to locate system problems which will have to be corrected. To obtain copies of the Steam Installation Survey, contact your PB Heat representative or download from PeerlessBoilers.com.
Figure 1.9: Foundation Layout
Do not install this boiler on carpeting or any combustible flooring. A significant fire hazard could result, with potential for property damage, personal injury or death.
WARNING
8
PREINSTALLATION
Table 1.1: Boiler Foundation Layout
Boiler
Boiler Base Length Jacket Length Foundation Length
Model inches
mm inches mm inches mm
211A-04 22-1/2 572 28-1/8 714 40-1/8 1,019
211A-05 28-1/8 714 33-3/4 857 45-3/4 1,162
211A-06 33-3/4 857 39-3/8 1,000 51-3/8 1,305
211A-07 39-3/8 1,000 45 1,143 57 1,448
211A-08 45 1,143 50-5/8 1,286 62-5/8 1,591
211A-09 50-5/8 1,286 56-1/4 1,429 68-1/4 1,734
211A-10 56-1/4 1,429 61-7/8 1,572 73-7/8 1,876
211A-11 61-7/8 1,572 67-1/2 1,714 79-1/2 2,019
211A-12 67-1/2 1,714 73-1/8 1,857 85-1/8 2,162
211A-13 73-1/8 1,857 78-3/4 2,000 90-3/4 2,305
211A-14 78-3/4 2,000 84-3/8 2,143 96-3/8 2,448
211A-15 84-3/8 2,143 90 2,286 102 2,591
211A-16 90 2,286 95-5/8 2,429 107-5/8 2,734
211A-17 95-5/8 2,429 101-1/4 2,572 113-1/4 2,877
211A-18 101-1/4 2,572 106-7/8 2,715 118-7/8 3,019
211A-19 106-7/8 2,715 112-1/2 2,857 124-1/2 3,162
211A-20 112-1/2 2,857 118-1/8 3,000 130-1/8 3,305
211A-21 118-1/8 3,000 123-3/4 3,143 135-3/4 3,448
211A-22 123-3/4 3,143 129-3/8 3,286 141-3/8 3,591
211A-23 129-3/8 3,286 135 3,429 147 3,734
211A-24 135 3,429 140-5/8 3,572 152-5/8 3,877
211A-25 140-5/8 3,572 146-1/4 3,715 158-1/4 4,020
211A-26 146-1/4 3,715 151-7/8 3,858 163-7/8 4,162
211A-27 151-7/8 3,858 157-1/2 4,000 169-1/2 4,305
211A-28 157-1/2 4,000 163-1/8 4,143 175-1/8 4,448
211A-29 163-1/8 4,143 168-3/4 4,286 180-7/8 4,594
211A-30 168-3/4 4,286 174-3/8 4,429 186-3/8 4,734
211A-31 174-3/8 4,429 180 4,572 192 4,877
211A-32 180 4,572 185-5/8 4,715 197-5/8 5,020
211A-33 185-5/8 4,715 191-1/4 4,858 203-1/4 5,163
211A-34 191-1/4 4,858 196-7/8 5,001 208-7/8 5,305
211A-35 196-7/8 5,001 202-1/2 5,143 214-1/2 5,448
211A-36 202-1/2 5,143 208-1/8 5,286 220-1/8 5,591
211A-37 208-1/8 5,286 213-3/4 5,429 225-3/4 5,734
211A-38 213-3/4 5,429 219-3/8 5,572 231-3/8 5,877
211A-39 219-3/8 5,572 225 5,715 237 6,020
211A-40 225 5,715 230-5/8 5,858 242-5/8 6,163
211A-41 230-5/8 5,858 236-1/4 6,001 248-1/4 6,306
211A-42 236-1/4 6,001 241-7/8 6,144 253-7/8 6,448
211A-43 241-7/8 6,144 247-1/2 6,286 259-1/2 6,591
211A-44 247-1/2 6,286 253-1/8 6,429 265-1/8 6,734
211A-45 253-1/8 6,429 258-3/4 6,572 270-3/4 6,877
211A-46 258-3/4 6,572 264-3/8 6,715 276-3/8 7,020
9
ASSEMBLE THE BASE
A. BASE ASSEMBLY
1. Collect the crates containing the Base Assembly parts. Table 2.1 (on page 11) shows the quantity of each crate required. The crates contain the following parts:
2. Open crate number 2. Remove the End Panels and mount a Support Channel Clip toward the rear on each panel as shown in Figure 2.2 using 1/4"-20 x 1/2" (13 mm) long round head machine screws and 1/4" lock washers provided.
2. ASSEMBLE THE BASE
2
2AA
2BB
2CC
2DD
2EE
Crate
Right End Panel Sub-Assembly
Left End Panel Sub-Assembly
Burner Support Channel Clips (2)
Front Panel Sub-Assembly Back Panel Sub-Assembly
Burner Support Channel
Front Panel Support Bracket
Section Assembly Kit Front Panel Sub-Assembly Back Panel Sub-Assembly
Burner Support Channel
Angle Tie Brace
Front Panel Support Bracket
Section Assembly Kit Front Panel Sub-Assembly Back Panel Sub-Assembly
Burner Support Channel
Angle Tie Brace
Front Panel Support Bracket
Section Assembly Kit Front Panel Sub-Assembly Back Panel Sub-Assembly
Burner Support Channel
Angle Tie Brace
Front Panel Support Bracket
Section Assembly Kit Front Panel Sub-Assembly Back Panel Sub-Assembly
Burner Support Channel
Angle Tie Brace
Front Panel Support Bracket
Section Assembly Kit
Items
90338
90340
90341
90342
90343
90344
Sub-Assembly #
GG-2105 GG-2106 GG-2070 GG-2080 GG-2081 GG-2066 GG-2069
GG-1030 GG-2080-1 GG-2081-1 GG-2066-1
GG-2065
GG-2069
GG-1030 GG-2080-2 GG-2081-2 GG-2066-2
GG-2065
GG-2069 GG-1030-1 GG-2080-3 GG-2081-3 GG-2066-3
GG-2065
GG-2069 GG-1030-2 GG-2080-4 GG-2081-4 GG-2066-4
GG-2065
GG-2069 GG-1030-3
Par t #
Figure 2.2: Steel Base Assembly
Figure 2.1: Boiler Base Assembly
10
ASSEMBLE THE BASE
3. Attach the Front Panel and Back Panel (Figure 2.2) to the Left Hand End Panel using 5/16"-18 x 1" (25 mm) long cap screws and hex head nuts provided.
4. For 211A-04 through 211A-08 Only:
a. Complete the base assembly by attaching the
Right End Panel and setting the Burner Support Channel on the clips.
5. For 211A-09 through 211A-46 Only: a. Attach a Front Panel Support Bracket to each
Front Panel as shown in Figure 2.3.
6. Attach an Angle Tie Brace at each panel joint to
secure the front and back panels as shown in Figure
2.4 using 5/16"-18 x 1" (25 mm) long cap screws and hex head nuts.
7. Bolt remaining Front and Back Panels together using
5/16"-18 x 1" (25 mm) long cap screws and hex head nuts. See Table 2.1 for panels required. Place the panels in the positions shown in the table and Figure 2.1.
8. Complete the base assembly by attaching the Right
Hand End Panel using 5/16"-18 x 1" (25 mm) long cap screws and hex head nuts.
9. Set the Burner Support Channels in place as shown
in Figure 2.1.
B. INSTALL THE PILOT BURNERS
1. Check the location of the Burner Support Channels
in the Base Assembly. The dimensions should be:
a. Height above boiler foundation: 6-3/4" (171 mm)
b. Distance from back of Base: 3-3/4" (95 mm)
2. Remove the Gas Manifold and Pilot Line Assembly
from Box Number 7.
3. Place Manifold on front of Base. Bolt the hangers
using 5/16"-18 x 1" (25 mm) long long cap screws with 5/16" flat washers. See Figure 2.5.
Figure 2.3: Support Bracket Installation
Figure 2.4: Angle Tie Brace Installation
11
ASSEMBLE THE BASE
Table 2.1: Base Front and Back Panel Crates
Model
ABCDEFG
Number
211A-04 2AA ——————24-3/4" 629 211A-05 2BB ——————30-3/8" 771 211A-06 2CC ——————36"914 211A-07 2DD ——————41-5/8" 1,057 211A-08 2EE ——————47-1/4" 1,200 211A-09 2BB 2BB —————52-7/8" 1,343 211A-10 2CC 2BB —————58-1/2" 1,486 211A-11 2CC 2CC —————64-1/8" 1,629 211A-12 2DD 2CC —————69-3/4" 1,772 211A-13 2DD 2DD —————75-3/8" 1,915 211A-14 2EE 2DD —————81"2,057 211A-15 2EE 2EE —————86-5/8" 2,200 211A-16 2CC 2CC 2CC ————92-1/4" 2,343 211A-17 2DD 2CC 2CC ————97-7/8" 2,486 211A-18 2EE 2CC 2CC ————8'-7-1/2" 2,629 211A-19 2DD 2DD 2DD ————9'-1-1/8" 2,772 211A-20 2EE 2EE 2CC ————9'-6-3/4" 2,915 211A-21 2EE 2EE 2DD ————10'-0-3/8" 3,058 211A-22 2EE 2EE 2EE ————10'-6" 3,200 211A-23 2EE 2CC 2CC 2CC 10'-11-5/8" 3,343 211A-24 2DD 2DD 2DD 2CC 11'-5-1/4" 3,486 211A-25 2EE 2EE 2CC 2CC 11'-10-7/8" 3,629 211A-26 2EE 2EE 2EE 2BB 12'-4-1/2" 3,772 211A-27 2EE 2EE 2EE 2CC 12'-10-1/8" 3,915 211A-28 2EE 2EE 2EE 2DD 13'-3-3/4" 4,058 211A-29 2EE 2EE 2EE 2EE 13'-9-3/8" 4,201 211A-30 2DD 2DD 2DD 2DD 2CC 14'-3" 4,343 211A-31 2DD 2DD 2DD 2DD 2DD 14'-8-5/8" 4,486 211A-32 2EE 2DD 2DD 2DD 2DD 15'-2-1/4" 4,629 211A-33 2EE 2EE 2BB 2EE 2EE 15'-7-7/8" 4,772 211A-34 2EE 2EE 2EE 2EE 2CC 16'-1-1/2" 4,915 211A-35 2EE 2EE 2EE 2EE 2DD 16'-7-1/8" 5,058 211A-36 2EE 2EE 2EE 2EE 2EE 17'-0-3/4" 5,201 211A-37 2DD 2DD 2DD 2DD 2DD 2DD 17'-6-3/8" 5,344 211A-38 2EE 2DD 2DD 2DD 2DD 2DD 18'-0" 5,486 211A-39 2DD 2DD 2EE 2EE 2DD 2DD 18'-5-5/8" 5,629 211A-40 2BB 2EE 2EE 2EE 2EE 2EE 18'-11-1/4" 5,772 211A-41 2EE 2EE 2DD 2DD 2EE 2EE 19'-4-7/8" 5,915 211A-42 2DD 2EE 2EE 2EE 2EE 2EE 19'-10-1/2" 6,058 211A-43 2EE 2EE 2EE 2EE 2EE 2EE 20'-4-1/8" 6,201 211A-44 2EE 2BB 2EE 2EE 2EE 2BB 2EE 20'-9-3/4" 6,344 211A-45 2CC 2BB 2EE 2EE 2EE 2EE 2EE 21'-3-3/8" 6,487 211A-46 2CC 2CC 2EE 2EE 2EE 2EE 2EE 21'-9" 6,629
mm
feet/inches
Overall Length
12
ASSEMBLE THE BASE
4. Place only the Burners with pilots mounted in the locations given in Table 2.2. Install the Burners by slipping the opening on the front of the burner over the orifice adapter and slipping the pin on the end of the burner into the hole in the Burner Support Channel directly opposite the orifice.
5. Cut and fit the 1/4" aluminum tubing provided from the pilot gas shut-off device(s) to the pilot burners.
6. Do not install the remaining burners until the Boiler Sections are installed.
Figure 2.5: Typical Gas Manifold and Pilot Line Assembly
Manifold Weldment
GG-4084 thru GG-4084-46
Imperial #68F
1/4" NPT x 3/8" O.D.
Tube Straight Connector
Orifice Spud
X-4026
Mounting Clamp
GG-3052 thru GG-3052-3
3/8" x 3/8" x 1/4" Tee
(2) 1/4" Street Elbow
3/8" Pipe Cap
Pipe Cap
Ignition Control & Relay
Mounting Box Assembly
(Standard HSP System, X-3011-3)
(Other panels mounted on
jacket front, left side)
1/4" x 1/8"
Hex Bushing
Imperial #69F Elbow
1/8" NPT x 1/4" O.D. Tubing
1/4" X 1-1/2"
(38 mm) long Nipple
PB-H91BG-2 or
H-V8046C
Pilot Gas Valve
Test Plug
3/8" Thermopilot
Valve(s) H17CA
(2) 5/16"-18 x 3/4" (19mm) long
Square Head Set Screw
3/8" x 1/4" Elbow
13
ASSEMBLE THE BASE
Table 2.2: Pilot Burner Locations – Numbered Right to Left (See Figure 2.1)
Total
Natural Gas Only Propane Gas Only
Model Number of Number Pilot Burner Locations Pilot Burner Locations
Number Pilots of (Positions Numbered Right to Left (Positions Numbered Right to Left
Burners
211A-04 1 6 5 5
211A-05 1 8 5 5
211A-06 1 10 5 5
211A-07 1 12 5 5
211A-08 1 14 5 5
211A-09 1 16 5 5
211A-10 1 18 5 7
211A-11 2 20 15 5 13 5
211A-12 2 22 15 5 13 5
211A-13 2 24 17 5 13 5
211A-14 2 26 17 5 9, 19
211A-15 2 28 19 5 9, 21
211A-16 3 30 25 5, 15 5, 15, 23
211A-17 3 32 25 5, 15 5, 15, 25
211A-18 3 34 25 5, 15 9, 19, 27
211A-19 3 36 29 5, 17 9, 21, 29
211A-20 3 38 35 5, 21 9, 21, 31
211A-21 3 40 37 5, 23 9, 23, 33
211A-22 3 42 19 5, 39 9, 23, 35
211A-23 3 44 19 5, 41 9, 23, 37
211A-24 3 46 21 5, 39 9, 23, 39
211A-25 3 48 25 5, 45 9, 23, 41
211A-26 4 50 19 5, 33, 47 9, 23, 33, 45
211A-27 4 52 21 5, 35, 49 9, 23, 35, 45
211A-28 4 54 23 5, 37, 51 9, 23, 35, 47
211A-29 4 56 27 5, 39, 53 9, 23, 39, 49
211A-30 4 58 29 5, 39, 51 9, 23, 39, 51
211A-31 4 60 31 5, 41, 53 9, 23, 39, 53
211A-32 4 62 33 5, 41, 59 9, 25, 41, 55
211A-33 4 64 35 5, 41, 61 9, 25, 41, 57
211A-34 5 66 35 5, 21, 49, 63 9, 23, 39, 51, 59
211A-35 5 68 37 5, 17, 51, 65 9, 23, 39, 51, 61
211A-36 5 70 37 5, 19, 53, 67 9, 23, 39, 51, 63
211A-37 5 72 37 5, 23, 47, 65 9, 23, 39, 51, 65
211A-38 5 74 25, 55 5, 43, 67
211A-39 5 76 23, 49 5, 35, 69
211A-40 5 78 25, 55 5, 33, 75
211A-41 6 80 19, 45 5, 33, 57, 77
211A-42 6 82 23, 51 5, 31, 65, 79
211A-43 6 84 23, 53 5, 33, 67, 81
211A-44 6 86 21, 55 5, 33, 67, 83
211A-45 6 88 23, 57 5, 37, 65, 85
211A-46 6 90 25, 59 5, 39, 67, 87
Electronic Pilots Standing Pilots Electronic Pilots Standing Pilots
(Spark Ignited) (Thermocouple) (Manually Lighted) Thermocouple
Models 211A-38 through 211A-46 Are Certified for Natural Gas Only
14
PLACE THE BOILER SECTIONS
A. PREPARATION
1. Check the level of the Boiler Base using a spirit level. Make sure the base is level and that the base panels are aligned within plus or minus 1/16" (2 mm).
2. Check the area around the Flow Ports (Figure 3.1). Use solvent and a clean cloth to thoroughly clean the flat surfaces and recesses. All foreign matter must be removed to assure a proper seal when the sections are drawn together.
B. PLACING THE SECTIONS
1. Begin by placing the Left Hand End Section on the left end of the base. The upper flow port goes toward the front of the boiler as shown in Figure 3.2.
2. Slide the section to the back of the base until the cast lug on the bottom of the section under the lower flow port is against the base back panel. Keep the section upright by a supporting prop or other means.
3. Align the parting line of the section with the seam between the Base End panel and the Base Front Panel as shown in Figure 3.3.
4. Apply Hi-Temp rope seal by spreading a thin coat of spray adhesive in the grooves on each end of the section. Place the rope in the grooves. Do not stretch the rope. The longer rope goes in the front groove. NOTE: The ends of each rope must extend 1/2" (13 mm) beyond the top and bottom.
5. Place the Flow Port Gaskets in the recesses provided (see Figure 3.1). Do not use adhesive.
6. The following steps must be followed to insure that no damage is done to the tie rod lugs. A 0-100 ft.-lbs. (0-136 N
·
m) torque wrench is required.
a. Place an Intermediate Section on the base and
slide it carefully against the Left Hand End Section.
b. Align the flow ports from front to back, as close
as possible.
c. Insert a tie rod into each of the lugs on each
section and apply a nut and washer to each end of the tie rod.
d. Before tightening, check the vertical alignment of
the sections using a spirit level (see Figure 3.4). Make sure they are square with the Base.
3. PLACE THE BOILER SECTIONS
Gaskets will be damaged by petroleum or its derivatives. Completely remove all solvent residue before placing gaskets.
Do not use petroleum based compounds in the boiler.
CAUTION
The sections are heavy and must be supported securely.
WARNING
Figure 3.1: Flow Port Machining & Gasket
Figure 3.2: Placing the First Section on Base
15
Figure 3.3: Assembling Sections on Base
PLACE THE BOILER SECTIONS
16
e. Draw sections together evenly, alternating
between top lug and bottom lug in increments of 20 ft.-lbs. (27 N
·
m). Continue until both top and
bottom lugs are tightened to 60 ft.-lbs. (81 N
·
m).
DO NOT EXCEED 60 FT.-LBS (81 N
·
m).
f. Check the level while tightening to make sure
alignment stays true. Also make sure sections remain square with the Base from front to back as the tie rods are tightened and as additional sections are installed.
g. If the sections tend to run out of plumb, this will
usually be at the bottom front. Loosen the upper nuts slightly and tighten the lower ones to adjust.
7. Assemble the remaining sections in the same way for a finished assembly as shown in Figure 3.3.
8. Some of the Intermediate Sections have tappings for installing additional steam risers from the boiler. These Tapped Intermediate Sections must be installed as shown in Figure 3.5A. The placement order is left to right (Figure 3.5).
C. HYDROSTATIC TEST THE BOILER
1. The supply and return piping can be permanently erected before applying the Boiler Jacket if the pipe nipples applied to the boiler tappings are long enough to clear the jacket.
2. Install a drain cock in the tapping provided at the bottom rear of each end section.
3. Provide a water supply line to the boiler.
4. Plug all open tappings in the boiler.
5. Provide a means to vent air as the boiler fills.
6. Fill the boiler with water, venting air as water level rises.
7. Pressurize boiler to 45 psig (310 kPa). Do not exceed this pressure.
a. Maintain pressure while checking all joints and
fittings for leaks.
b. After inspection is complete, drain the boiler and
remove plugs from tappings that are to be used.
Figure 3.4: Align Sections Vertically
Figure 3.5: Section Positioning Numbering
Boiler Model Number
Place Tapped Intermediate Sections
as Positions (numbered Left to Right)
211A-18 10 211A-19 10 211A-20 11 211A-21 11 211A-22 8, 16 211A-23 8, 16 211A-24 9, 17 211A-25 7, 13, 19 211A-26 7, 13, 20 211A-27 7, 12, 17, 22 211A-28 5, 11, 17, 23 211A-29 5, 10, 15, 20, 25 211A-30 6, 11, 16, 21, 26 211A-31 6, 10, 14, 18, 22, 26 211A-32 6, 11, 15, 19, 23, 27 211A-33 5, 9, 13, 17, 21, 25, 29 211A-34 5, 9, 13, 17, 22, 26, 30 211A-35 5, 9, 13, 18, 23, 27, 31 211A-36 5, 9, 13, 17, 21, 25, 29, 33 211A-37 5, 9, 13, 17, 21, 25, 29, 33 211A-38 4, 8, 12, 17, 22, 27, 31, 35 211A-39 4, 8, 12, 16, 20, 24, 28, 32, 36 211A-40 4, 8, 12, 16, 21, 25, 29, 33, 37 211A-41 4, 8, 12, 16, 19, 23, 26, 30, 34, 38 211A-42 4, 8, 12, 16, 20, 23, 27, 31, 35, 39 211A-43 4, 7, 11, 14, 18, 22, 26, 30, 33, 37, 40 211A-44 4, 8, 12, 16, 19, 23, 26, 29, 33, 37, 41 211A-45 4, 7, 11, 14, 18, 21, 25, 28, 32, 35, 39, 42 211A-46 4, 7, 11, 14, 18, 22, 25, 29, 33, 36, 40, 43
Figure 3.5A: Section Position Numbering
PLACE THE BOILER SECTIONS
Loading...
+ 41 hidden pages