Payne PY1PNB030060AAAA, PY1PNB036060AAAA, PY1PNB024040AAAA, PY1PNB024060AAAA, PY1PJB048090AAAA Installation Guide

CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1-5
I. General ................................... 1
RECEIVING AND INSTALLATION ................. 6 15
I. Step 1 -- Check Equipment .................. (3
II. Step 2 -- Provide Unit Support ............... (3
III. Step 3 -- Field Fabricate Ductwork ............ (3
V. Step 5 -- Rig and Place Unit ................. 6
VI. Step 6 -- Connect Condensate Drain .......... 9
VII. Step 7 -- Install Flue Hood ................... 9
VIII. Step 8 -- Install Gas Piping .................. 9
IX. Step 9 -- Install Duct Connections ........... 11
X. Step 10 -- Install Electrical Connections ...... 13
PRE-START-UP ................................. 1(3
START-UP .................................... 16 29
I. Check for Refrigerant Leaks ................. 1(3
II. Start-Up Heating Section and
Make Adjustments ......................... 17
III. Start-Up Cooling Section and
Make Adjustments ......................... 20
MAINTENANCE ................................ 3043
I. Air Filter .................................. 30
II. Unit Top Removal .......................... 30
III. Evaporator Blower and Motor ................ 30
IV. Flue Gas Passageways ..................... 31
V. Combustion-Air Blower ..................... 31
VI. Limit Switch .............................. 31
VII. Burner Ignition ............................ 31
VIII. Main Burners ............................. 32
IX. Condenser Coil, Evaporator Coil, and
Condensate Drain Pan ..................... 32
X. Condenser Fan ............................ 33
XI. Electrical Controls and Wiring ............... 33
Xll. Refrigerant Circuit ......................... 33
Xlll. Gas Input ................................. 33
XlV. Evaporator Airflow ......................... 33
XV. Metering Device -- Acutrol TM Device .......... 33
XVI. Liquid Line Strainer ........................ 33
TROUBLESHOOTING ........................... 34-3(;
START-UP CHECKLIST .......................... CL 1
Cancels: II PY1P 18 1 II PY1P 18 2
9/1/98
Fig. 1 -- Unit PY1P
Untrained personnel can perform basic maintenance flmc- tions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on
air conditioning equipment, observe precautions in the lit erature, tags and labels attached to the unit, and other safety
precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex- tinguisher available for all brazing operations.
NOTE TO INSTALLER -- Before the installation, READ
THESE INSTRUCTIONS CAREFULLY AND COMPLETELY.
Also, make sure the User's Manual and Replacement Guide are left with tile unit after installation. The furnace is NOT
to be used for temporary heating of buildings or structures under constrttction.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo
nents. Only trained and qualified personnel should install, repair, or service air conditioning equipment.
I. GENERAL
The PY1P units (see Fig. 1) are fidly self-contained, combi- nation Category I gas heating/electric cooling units designed
for outdoor installation. See Fig. 2 5 (pages 2 5) for unit di- mensions. All unit sizes have discharge openings for both hori
zontal and downflow configurations, and are factory shipped with all 4 duct openings covered. Units may be installed ei-
ther on a rooftop or a groundqevel cement slab. See Fig. 6 for roof curb dimensions.
- 4 13/16" ()22.2) 43 11116"
B/16 °
(312.?)
BLOWER ACCESS BURNER AND CONTROL 30X
PANEL RIGHT SIDE VIEW ACCESS PANEL
\
REQ'D CLEARANCES FOR SERVICING in (mm)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L in. (mm)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Flue panel ......................... 36 (914)
NEC REQ'D CLEARANCES in. (mm)
Between units, control box side ................ 42 (1067)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1067)
49 9116"
(1259.3)
4ll0B.B)
/-COND COIL
(281,4) I
l? l/1B'_
(433,9)
LOPT_ONAL SUPPLY
AIR OPENING
COIL
AIR OPENING
14 ?liB"
(365.9)
10 9116"
(263.R)
RETURN
(52,63
7/3" (22.2) BIA,
CONTROL ENTRY_
t (203.2)
UNIT
PYIP180040 PY1P024040 PYIP024060 PY1P030040
PYIP030060/080 PYIP036060/080 PYIP036100/120 PYIP042060/080
PYIP042100/120
I 1/8" (2B.6) DIA,
POWER ENTRY
\
_ (90.51 i
_-I 5/E _ 441,3) OIA.
i !
GASENTRY
1/2 _ - 14 NPT
GASCONNECTION
REAR VIEW
ELECTRICAL
CHARACTERISTICS
208/230-1-60 208/230-1-60
208/230-1-60 208/230-1-60, 208/230-3-60 208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
i w (58.O)
! I
FLUE PANEL
FLUE HOOD
(29.6)
ALTERNATE LV ENTRY
EVAP COIL ACCESS
LEFT SIDE VIEW
UNIT WEIGHT
Ib kg
272 123 303 138 315 143 320 145
332 149 336 153 348 158 375 170
387 176
0 ?/3" 422.23)
I W4" (31.75)
_,ALTERNATE POWER ENTRY
I ?/16 -2 3/18"
(39.3) 455.6)
COMPRE330R ACCES5 PANEL
3/4" NPT (13,0)
DRAIN OUTLET
FRONT VIEW
CORNER WEIGHT UNIT HEIGHT
(Ib/kg) (in./mm)
A B C D E
81/37 82/28 78/35 53/24 24 1/813
97/44 43/20 123/56 40/18 241/813 100/45 46/21 128/57 43/20 241/813 100/45 47/21 128/57 47/21 241/813
103/46 50/22 129/58 50/23 24 1/813
86/39 76/35 111/50 63/29 24 1/813
89/40 79/36 114/52 66/30 24 1/613
95/43 86/39 119/54 75/34 28 1/714
98/45 89/40 122/55 78/35 28 1/714
UNIT
PYIP018040
PY1P024040 PY1P024060 PY1P030040
PY1P030060/080 PY1P036060/080 PY1P036100/120
PYIP042060/080 PY1P042100/120
F
in./mm
169½d420 7
209½d522 3
in./mm
18/5½6/481 0
X Y Z
2507/637 20.59/523 2707/688 23.35/593 2698/685 23.27/591 2671/678 23.46/598 10.85/278
2715/689 22.38/568 2750/698 22.48/571
CG -- Center of Gravity MAT'L -- Materiat COND -- Condenser NEC -- National Electrical Code
LV -- Low Voltage REQ'D -- Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.
2 Adequate clearance around air openings into combustion chamber must
be provided.
2740/696 22.44/570
CENTER OF GRAVITY in./mm
22/5½6/5826
2701/686 22.44/570 2694/684 22.44/570
127/321
Fig. 2 -- PYIP018-042 Without Base Rail, Unit Dimensions
--2--
LEGEND
SLOWER ACCESS
PANEL
RIGHT _IDE VIEW ACCESS PANEL
BURNER ANS CONTROL BOX
REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in (ram)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Ftue panel ......................... 36 (914)
NEC REQ'D CLEARANCES. in. (ram)
Between units, control box side ................ 42 (1067)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1067)
7/8" (22,2) OIA. I I/8" (28.6) GIA, C(:_ITROL ENTRY POWER ENTRY
FLUE HOOD
1 9/16"
52"
(1320_8)
EVAP COIL ACCESS
COND COIL (115E,7)
o
A/
3 5/1G_
1 1/4"
(84,1) I
ALTERNATE POWER ENTRY
(31,75)
-45 I/2"
43 11/16 °
(II08.B)
-OPTIONALSUPRLY
AIR OPENING
COMPRESSOR ACCESS PANEL
/ AIROPENING /
7"
GUPPLY 10 9/16"
_1 11/16" (48,2)
(43.21
OPTIONAL RETURN
(368.9)
T
(268, 9)
(52. S)
UNIT
PYIP018040 PYIP024040 PYIP024060 PYIP030040
PYIP030060/080 PYIP036060/080 PYIP036100/120 PYIP042060/080
PYIP042100/120
UNIT
PYIP018040
PY1P024040 PY1P024060 PY1P030040
PY1P030060/080 PY1P036060/080 PY1P036100/120
PYIP042060/080 PY1P042100/120
1A_/B:TR(41.3) OI A. /
I/2" - 14 NPT FLUE PANEL
GAS CONNECTION
REARVIEW
ELECTRICAL
CHARACTERISTICS
208/230-1-60 208/230-1-60 208/230-1-60
208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60 208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
F G
in./mm in./mm
25.04/636
26.90/683.3
26.82/681.2
19%/5048 22¼/5654
23%/6064 26¼/6668
26.57/674.9
26.93/684
27.31/693.7
27.23/691.6
26.87/682.5
26.81/681
K
18 I/
(458
(142.
F
1 S/It
(29,S) (253.8)
UNIT WEIGHT
Ib kg
296 135 327 149 339 155 344 157
356 162 360 164 372 169 399 181
411 187
CENTER OF GRAVITY in./mm
X
Y Z
2272/577 2017/5123 2022/5136 201 /5093 13.16/334.3
211 /5354 210 /5326 210 /5331
210 /5331 210 /5337
14.96/380
(325.4)
LEFT SIDE VIEW 2 3/16" FRONT VIEW
1 3/4 ° NPT (19.0)
(34,S) SRAIN OUTLET
(SS.6)
CORNER WEIGHT UNIT HEIGHT
(Ib/kg) (in,/rnm)
A B C D E
87/40 68/31 82/37 59/27 274/697 103/47 49/22 129/59 46/21 274/697 106/48 52/24 132/60 49/22 274/697 106/48 53/24 132/60 53/24 274/697
102/46 71/32 123/56 60/27 274/697
92/42 82/37 117/53 69/31 274/697
95/43 85/39 120/55 72/33 274/697 101/46 92/42 125/57 81/37 31.4/798
104/47 95/43 128/58 84/38 31.4/798
LEGEND
CG -- Center of Gravity MAT'L -- Material COND -- Condenser NEC -- NationaI Electrical Code
LV -- Low Voltage REQ'D -- Required
NOTES:
1 Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge
2. Adequate clearance around air openings into combustion chamber must be provided
Fig. 3 -- PYIP018-042 With Optional Base Rail, Unit Dimensions
--3--
AIR OPENING
14 71IS"
(365.91
RETURN
FLUE HOOD
18 1/16
(458,8)
0 7/8" (22.23) 1 1/4" (31.?51
ALTERNATELV ENTRY ALTERNATEPOWERENTRY
EVAPCOIL ACCESg
l _'2 1/lS"
10 9/16 °
(268,9)
(52,6)
t 3116 _
129.GI
(253,81
(292. I ) 1325.4) (36, 3)
LEFTSIDE VIEW
REQ'D CLEARANCES FOR SERVICING. in (ram)
(E8,0)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in (ram)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Flue panel ......................... 36 (914)
NEC REQ'D CLEARANCES. in (ram)
Between units, control box side ................ 42 (1067)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1867)
718" (22.2)DIA, I I18" (28.6)OIA. CONTROLENTRY POWERENTRY
(55,B) DRAIN OUTLET
FRONT VIEW
UNIT
(19,0)
ELECTRICAL
CHARACTERISTICS
PY1PO48080 208/230-1-60, 208/230-3-60,460-3-60 PY1P048100/120/140 208/230-1-60, 208/230-3-60,460-3-80 PY1P060080 208/230-1-60, 208/230-3-60,460-3-80
PYIP060100/120/140 208/230-1-60, 208/230-3-60,460-3-80
UNIT
PYIP048080
PYIP048100/120/140 PYIP060O80 PYIP060100/120/140
CENTER OF GRAVITY (in./mm)
X Y
28.76/731 2346/596
28.42/722 2342/595
28.36/720 2327/591
27.95/710 2323/590
1535/390 1535/390
1535/390 1535/390
Fig. 4 -- PYIP048,060 Without Base Rail, Unit Dimensions
28 15/16
UNIT WEIGHT
Ib kg
414 188 426 193 453 206
465 211
1734 ' I I
1 5/9" (41.9) OIA,_-_
GAS ENTRY
I/2"- 14 NPT
GASOONNECT!0N
CORNER WEIGHT
A
107/49 110/50 117/53
120/55
(Ib/kg)
B C
83/38 158/72 86/39 159/72 93/42 167/76
96/44 167/76
i
FLUE PANEL
D 66/30 71/32 76/35
82/37
LEGEND
Z
CG -- Center of Gravity MAT'L -- MateriaI COND -- Condenser NEC -- National Electrical Code
LV -- Low Voltage REQ'D -- Required NOTES:
1. Clearances must be maintained to prevent recircutation of air from outdoor- fan discharge.
2 Adequate clearance around air openings into combustion chamber must
be provided.
--4--
(23, B)
CON0 C0IL (115B,71
/
+45 1/2"
43 11/16"
1110B.8)
AIR OPENING
FLUE HO00
EVAP COIL ACCEBB
\,
\
I 114"
ALTERNATE POWER ENTRY
(31,7G3
GIG"
(281,4)
(433+a1
5/B"
:39B,91
BLOWER ACCESS BURNER ANO CONTROL BOX
PANEL RIGHT SIDE VIEW ACCESS PANEL
ACCESB PANEL
14 ?/16"
(355.9)
10 BilE"
(268.91
13/15"
1,
t L2 1116"
\
1B 1/15
(458.8)
L__
B 518"
(142.9)
(52,6)
REQ'D CLEARANCES FOR SERVICING. in. (ram)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in (ram)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Flue panel ......................... 36 (914)
NEC REQ'D CLEARANCES. in. (ram)
Between units, controt box side ................ 42 (1867)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1067)
r-
1B/16: _lO "_
(29.5) (253.5)
2 1116"
(G2.3) _
?%Nf&2 NT ¢7
POWER ENTRY
4_I t18" (2B.G) OIA+
/16"
3/4" NPT {15.0)
J 3115"
UNIT
PYIP048080 208/230-1-60,208/230-3-60,460-3-60 PY1P048100/120/140 208/230-1-60,208/230-3-60,460-3-60 PYIP060OBO 208/230-1-60,208/230-3-60,460-3-60
PYIP060100/120/140 208/230-1-60,208/230-3-60,460-3-60
UNIT
PY1P048080 PY1P048100/120/140
PY1P060080 PY1P060100/120/140
DRAIN OUTLET
(55,B1 FRONT VIEW
ELECTRICAL
CHARACTERISTICS
CENTER OF GRAVITY (in./mm)
X Y Z
28.54/7249 2000/508 1766/4486
28.22/7168 2005/5093 1766/4486
28.18/7156 2019/5128 1766/4486
27.79/7059 2023/5138 1766/4486
to
1 13116'
29 7/8"
32 1/4" (287.3)
,8,B.B)I
1 B/B" (41=31 OIA.
, /
GAS ENTRY
I/2" - 14 NPT FLUE PANEL
GAS CONNECTION
UNIT WEIGHT
Ib kg
438 199 450 205 477 217
489 222
CG -- Center of Gravity MAT'L -- Material COND -- Condenser NEE -- National Electrical Code
LV -- Low Voltage REQ'D -- Required NOTES:
1.Clearances must be mahTtained to prevent redrculation of air from outdoor- fan discharge
2. Adequate clearance around air openings into combustion chamber must be provided.
A 113/51 116/53
123/56 126/57
CORNER WEIGHT
(Ib/kg)
B C
89/40 164/75 92/42 165/75 99/45 173/79
182/46 173/79
LEGEND
D 72/33 77/35 82/37
88/40
Fig. 5 -- PYIP048,060 With Optional Base Rail, Unit Dimensions
--5--
RECEIVING AND INSTALLATION
I. STEP 1 -- CHECK EQUIPMENT
A. Identify Unit
The unit model nmnber and serial number are stamped on unit identification plate. Check this information against ship
ping papers and job data.
B. Inspect Shipment
Inspect for" shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose fl'om its
anchorage, have it examined by transportation inspectors be- fore removal. Fm_vard claim papers directly to transporta-
tion company. Manufacturer is not responsible for any darn age incnrred in transit.
Check all items against shipping list. hnmediately notify your representative if any item is missing.
To prevent loss or damage, leave all parts in original pack ages until installation.
II. STEP 2 -- PROVIDE UNIT SUPPORT
A. Roof Curb
Install accessory roof curb in accordance with instructions shipped with curb. See Fig. 6 for roof curb dimensions. In
stall insulation, cant strips, roofing, attd flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material sup-
plied with the roof curb. hnproperly applied gasketing can also result in air leaks and poor" unit performance.
Curb should be level to within 1/4inch. This is necessa W for unit drain to flmction properly. Refer to accessory roof curb
installation instructions for additional information as required.
B. Slab Mount
Place the unit on a solid, level concrete pad that is a mini mmn of 4 in. thick with 2 in. above grade. The slab should be flush on the front of the unit (to allow condensate drain in-
stallation) and should extend 2 in. on the three remaining sides of the unit. See Fig. 7. Install a 6tin. gravel apron in
fl'ont of condenser air inlets to prevent obstrtiction of airflow by grass or shrubs. Do not secure the unit to the slab exc'u_t
when required by local codes.
C. Flush Mount
Place side of unit with duct panel flush against transition. On units with optional base rails, the skirt on duct-panel side of unit cat] be removed or relocated to allow unit to be mounted
flush against transitions that extend below basepan of trait, To move skirt, proceed as follows:
1. Remove 4 screws holding skirt to base rail. Retain screws.
2. Remove skirt or slide skirt inwards until alternate clear ance holes align with base rails.
3. Secure with screws removed in Step 1. Holes align with base rails.
To remove wood support under unit (with base rail only), loosen 4 screws above rigging holes and slide assembly out through
rectangular hole.
III. STEP 3 -- FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building structure on verti- cal discharge units. Do [rot cczmect chlctwork to unit. For hori-
zontal applications, unit is provided with flanges on the hori zontal openings. All ductwork should be secured to the flanges.
Insulate attd weatherproof all external ductwork, joints, attd roof openings with counter flashing and inastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in- sulated and covered with a vapor barrier.
If a plenmn return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabi- net return air static shall not exceed -.25 in. wg.
IV. STEP 4 -- PROVIDE CLEARANCES
The required n_inimunt operating and service clearances are shown in Fig. 2-5. Adequate combustion, ventilation, and cot]-
denser air must be provided, in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code ANSI (American National Standards Association) Z223.1
(in Canada, sections 7.2, 7.3 or 7.4 or Can/CGA [Canadian
Gas Association] B 149 Installation Codes), or applicable pro- visions of local building code.
The condenser fat] pushes air through the condenser coil and discharges it through the bank of louvers in the top cover,
the decorative grille on the right side of the unit, and the con> presser access panel. Be sure that the fan discharge does not
recirculate to the condenser coil. Do not locate the unit in ei- ther a corner or tinder an overhead obstruction. The mini-
mum clearance under a partial overhang (such as a normal house overhang) is 48-in. above the unit top. The maximunl
horizontal extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow fl'om an over- hang or roof will damage or flood the unit. Do not install the
unit on carpeting, tile, or other combustible materials. The unit may be installed on wood flooring or on Class A, B, or C
roof covering materials.
V. STEP 5 -- RIG AND PLACE UNIT
Use spreader bars or crate top when rigging the unit. The units must be rigged for lifting as shown in Fig. 8 and 9. Re-
fer to Table 1 for operating weight attd to Fig. 2 5 for" corner weights. U[se extreme c'ozlticzr to pz'eveirt ct_moge wheir mov
ing tire zmib U)rit must ['emoin in on zqJz'(ght [rositio:r dzlz'inq
oH ['{qgd/_,_ and moviz\_ OlreZ'ation.s. The unit Intist be level for
proper condensate drainage; therefore, the groundqevel pad or accessory roof curb must be level before setting the unit it]
place. When a field fabricated support is used, be sure that the support is level and properly supports the unit.
--6--
FLAT
CURB
PART NUMBER
CPRFCURB001A01 CPRFCURB002A01 CPRFCURB003A01
_A_
8" [203]
11" [279]
14" [356]
POWER AND
GAS ENTRY
SEAL
(_PPLIED WITH CURB)
5UPPLY AIR
[SEE DETAIL "A "j
BASE RAILS)
(FIELD SUPPLIED)
=FING FELT
(FIELD SUPPLIED)
(FIELD SUPPLIED)
(FIELD SUPPLIED)
IGIO INSULATION
(FIELD SUPPLIED)
DETAIL "A"
FOR UNITS WITH
MATERIAL
6
"0
THIS BRACKET MUST BE REMOVED
BEFORE iNSTALLATION
17!
[44E]
\
SUPPLY AIR
OPENING
[279 (406]
RETURN AIR
OPENING
3G 3/4".
[1010]
BEFORE INBTALLATION
MUST BE REMOVED
33 7/8"
[858]
[13]
SCREW DLEARANOE
NOTES:
1. Roof curb must be set up for unit being installed.
2. SeaI strip must be applied as required for unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7. [_ Direction of airflow.
8. Insulated panels: 1-in. thick fiberglass 1 Ib density.
Fig. 6 -- Roof Curb Dimensions
--7--
2,0'z,,
FLUSHWITHSLAB_ _F2. 0-
/ J
//i ! I
/ ,
/ b
// I I
/ I I
, _
L. ...... J
r "1
I I I i
I I
I t I t
L J
!
S 4-1371 UNIT ON ROOF CURB
BEE DETAIL A
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in De- tail "A." Lifting brackets to be centered around the unit center of gravity. Use wood top skid when rigging, to prevent rigging straps from damag- ing unit. Remove 4 screws to slide wood support through rectangular
hole in rail.
......U.......... ;_7.........20,,
CONCRETESLAB
Fig. 7 -- Slab Mounting Details
SEAL STRIP MUST BE IN PLACE BEFORE PLACING
UNIT ON ROOF CURB "1
914-1371 / (36"- 54") /
SECURESCREW
AGAINSTBASEPAN
TO HOLDLIFTING
_'_ DUCT END l\
/
BRACKETINPLACE
DETAIL A
SEEDETAILA"_
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in De- tail "A." Lifting brackets to be centered around the unit center of gravity. Use wooden top skid when rigging, to prevent rigging straps from dam- aging unit.
UNIT MAX A B C
PYIP WEIGHT
Size Ib kg in. mm in. mm in. mm
018 332 150 24.3 618 24.85 631 024 375 170 22.4 570 24.85 631 030 384 174 22.3 585 24.85 631 036 408 185 49.4 !255 22.0 559 24.85 631 042 447 203 22.5 571 28.85 733 048 486 220 21.0 533 34.85 885 060 525 238 21.5 545 34.85 885
Fig. 8 -- Suggested Rigging for Units Without
Base Rail
UNIT MAX PYIP WEIGHT
Size Ib kg
018 320 145
024 363 165 030 380 172 036 396 180 042 435 !97 048 474 215 060 5!3 233
in,
49.4
A
mm in.
1255 22.2
24.4
22.6
22.5
22.6 2! .2
21.6
mm
619 574 571 563 574 538 549
in, mm
28.2 715
28.2 715
28.2 715
28.2 715
32.2 816
38.2 969
38.2 969
Fig. 9 -- Suggested Rigging for Units With
Optional Base Rail
A. Units Without Base Rail
If accessory rigging brackets are to be used for rigging, in- stall them as follows:
1. Position brackets as close to the corners of unit as pos- sible. Be sure brackets are well outside of center of grav-
ity. See Fig. 2 and 4.
2. Position paint protectors and foam strips between screws and painted surface of unit. Tighten screws until they
make contact with the paint protectors.
3. Secure device or hook of sufficient strength to hole in bracket as shown in detail "A" of Fig. 8.
4. If wood top is available, use it for a spreader bar to pre-
vent straps fl'om damaging unit. If wood top is not avail-
able, use spreader bars of sufficient length.
--8--
B. Units With Optional Base Rail
Lifting holes are provided in optional base rail as shown in Fig. 9. Operating weights are shown in Table 1. Refer to rig-
ging instructions on unit. Protective wood support must be removed from unit before
unit is mounted to curb. Remove 4 screws that secure sup port above rigging holes in rails. Slide support out through
rectangular hole in rail. See Fig. 9.
Vl. STEP 6 -- CONNECT CONDENSATE DRAIN
NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Model PY1P disposes of condensate water through a 3/4 in. NPT fitting which exits through the compressor access panel.
See Fig. 2 5 for location. Condensate water can be drained directly onto the roof in roof
top installations (where permitted) or onto a gravel apron in groundqevel installations. Install a field-supplied conden-
sate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain pan condensate connection to pre
vent the pan fi'om overflowing. See Fig. 10. Prime the trap with water. When using a gravel apron, make sure it slopes
away fl'om the unit. If the installation requires draining the condensate water away
fi'om the unit, install a 2-in. trap at the condensate connec- tion to ensure proper drainage. See Fig. 10. Make sure that
the outlet of the trap is at least 1 in. lower than the drain- pan condensate connection to prevent the pax] fi'om overflow
ing. Prime the trap with water. Connect a drain tube using a minimum of 3/4 in. PVC or 3/4 in. copper pipe (all field
supplied) at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least
one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.
1" MIN,
t
Fig. 10 -- Condensate Trap
VIII, STEP 7 -- Install Flue Hood The flue hood assembly is shipped screwed to the control box
in the burner compartment. Remove the burner access panel to locate the assembly.
Fox" units being installed in California Air Quality Manage ment Districts which require NO x emissions of 40 nanograms/
joule or less, kit CRLOWNOX001A00 must be installed.
Install the flue hood as follows:
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in Canada, CAN/CGA B149.1, and B149.2), or
NFPA (National Fire Protection Association) latest re vision. Refer to Provincial and local plumbing or waste-
water codes and other" applicable local codes.
2. Remove fl'om shipping location. Place vent cap assem bly over fine panel. Orient screw holes in vent cap with
holes in the fine panel.
3. Secure flue hood to flue panel by inserting a single screw on the right side, the left side, and the top of the hood.
VIII. STEP 8 -- INSTALL GAS PIPING
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/d in.
FPT gas inlet on the manual shutoff or gas valve. Install a gas supply line that runs to the heating section. Re
fer to Table 2 and the NFGC for" gas pipe sizing. Do not zl.se ca.st iron pipe. It is recommended that a black iron pipe is
used. Check the local utility fox" recommendations concern- ing existing lines. Size gas supply piping fox" 0.5 in. wg maxi-
mum pressure drop. Never" zLse pipe _smaller than tire _/z-hr. FPT go_s hrlet on tire unit ga_s valve.
For natural gas applications, the gas pressure at unit gas cox]- nection must not be less than 4.0 in. wg or greater than
13 in. wg while the unit is operating. For propane applica-
tions, the gas pressure must not be less than 4.0 in. wg or greater than 13 in. wg at the unit connection.
An l/a-in. NPT plugged tapping accessible for test gage cox]- nection must be installed immediately upstream of the gas
supply connection to the furnace. When installing the gas supply line, observe local codes per
raining to gas pipe installations. Refer to the NFGC ANSI Z223.1-1988 NFPA latest edition (in Canada, CAN/CGA B 149.1,
(2) M86). In the absence of local building codes, adhere to the
following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe V4 inch in every 15 ft to prevent traps. Grade all hori-
zontal runs downward to risers. Use risers to connect to
heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropri-
ate straps, hangers, etc. Use a minimum of one hanger every 6 ft. Fox" pipe sizes larger than _?z in., follow rec
ommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes.
Newt u_se Teflon talre.
4. Install sediment trap in riser" leading to heating section per Fig. 11. This drip leg functions as a trap for" dirt and
condensate.
5. Install an accessible, external, manual main shutoffvalve
in gas supply pipe within 6 ft of heating section.
6. Install groundOoint union close to heating section be- tween unit manual shutoff and external manual main
shutoff valve.
7. Pressure test all gas piping in accordance with local and
national plumbing and gas codes before connecting pip- ing to unit.
NOTE: Pressure test the gas supply system a/terthe gas sup- ply piping is connected to the gas valve. The supply piping
must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of
0.5 psig. Pressure test the gas supply piping system at pres- sures equal to or less than 0.5 psig. The unit heating section
must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the
groundOoint union.
--9--
Table I -- Physical Data -- Unit PYIP
UNIT SIZE PYIP
NOMINAL CAPACITY (ton) OPERATING WEIGHT (Ib)
Without Base Rail With Optional Base Rail
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Charge (Ib)
REFRIGERANT METERING DEVICE
Orifice ID (in,)
CONDENSER COIL
Rows,..Fins/in, Face Area (sq ft)
CONDENSER FAN
Nominal Cfm Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows Fins/in. Face Area (sq ft)
EVAPORATOR FAN
Nominal Airflow (Cfm) Size (in.)
FURNACE SECTION*
Burner Orifice (Qty.,.drilt size)
Natural Gas
Burner Orifice (Qty._drill size)
Propane Gas
RETURN-AIR FILTERS (in.)t
Throwaway
018040 024040 024060 030040 030060 030080 036060
11/2 2 2 2//z 2 Y, 2i/, 3
272 303 315 320 332 332 336 336 348 348 296 327 339 344 356 356 360 360 372 372
Rotary Reciprocating
1 1
260 2.75 2.75 3.40 I 3.40 340 430 430 4.30 430
i
m
Acutror M Device
036080
3
036100
3
.030 030 030 030 030 .030 .032 .032 032 .032
1.17 1..17 1..17 2..17 2..17 2.17 2.17 595 5.95 5.95 5.95 5.95 595 595
1700 1700 1700 1900 1900 1900 1900
18 18 18 18 18 18 18
1A(850) V_(850) V_(850) V8(850) V8(850) _A(850) ¼ (1050)
3.15 3..15 3..15 3..15 3..15 3.15 3.15 183 2.29 2.29 2.29 2.29 229 306
600 800 800 1000 1000 1000 1200
10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10
Direct Drive
1.32 1..32 2..32 1..32 2..32 2.32 2.32
1.41 1..41 2..47 1..41 2..47 2.42 2.47
20 x 20 20 x 20 20 x 20 20 x 24 20 x 24 20 x 24 20 x 24
2.17 595
1900
18
_(1050)
3.15 306
1200
10 x 10
2.32
2. 42
20 x 24
2..17
5.95
1900
18
1A(1050)
3..15
3.06
1200
10 x 10
2..32
2..40
20 x 24
036120
3
2.17 595
1900
18
¼ (1050)
3.15 306
1200
10 x 10
3.32
3 .42
20 x 24
UNIT SIZE PYIP 042060 042080 042100 042120 048080 048100 048120 048140 060080 060100 060120 060140 NOMINAL CAPACITY (ton) 3 ½ 3½ 3 ½ 34½ 4 4 4 4 5 5 5 5
OPERATING WEIGHT (tb)
Without Base Rail 375 375 387 387 414 426 426 426 453 465 465 465 With Optional Base Rail 399 399 411 411 438 450 450 450 477 489 489 489
COMPRESSORS Reciprocating Hermetic Scroll
Quantity 1 1
REFR,GERANT(R-22,I I I I
Charge (Ib) 520 520 520 520 650 650 650 650 700 7.00 7.00 7.00
REFRIGERANT METERING Acutrot Device
DEVICE
Orifice ID (in.) .034 .034 .034 .034 .030 .030 .030 .030 .030 030 030 030
CONDENSER COIL
Rows...Fins/in. 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2...17 2..17 2..17 Face Area (sq ft) 704 704 704 704 867 867 867 867 867 8.67 8.67 8.67
CONDENSER FAN
Nominal Cfm 1900 1900 1900 1900 2400 2400 2400 2400 2400 2400 2400 2400 Diameter (in.) 18 18 18 18 20 20 20 20 20 20 20 20
Motor Hp (Rpm) (1050) (1050) (1050) (1050) % (1050) % (1050) % (1050) % (1050) % (1050) _/J(1050) _/J(1050) _/J (1050)
EVAPORATOR COIL
Rows Fins/in. 3.15 3.15 3.15 3.15 3..15 3..15 3..15 3..15 4..15 4..15 4..15 4..15 Face Area (sq ft) 333 333 333 333 444 444 444 4.44 4.44 4.44 4.44 4.44
EVAPORATOR FAN Direct Drive
Nominal Airflow (Cfm) 1400 1400 1400 1400 1600 1600 1600 1600 1995 1995 1995 1995
Size (in.) 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10
FURNACE SECTION*
Burner Orifice (Qty...drill size) 2.32 2.32 2.32 3.32 2.32 2.32 3.32 3..32 2..32 2..32 3..32 3..32
Natural Gas
Burner Orifice (Qty...drill size) 2.47 2.42 2.40 3.42 2.42 2.40 3.42 3..40 3..42 2..40 3..42 3..40
Propane Gas
RETURN-AIR FILTERS (in.)t
Throwaway 24 x 24 24 x 24 24 x 24 24 x 24 24 x 30 24 x 30 24 x 30 818"* 24 x 30 24 x 30 24 x 30 960**
*Based on altitude of 0-2000 feet.
tRequired filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated
cooling airflow or the heating airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity
type. For non-standard air filters, air filter pressure drop must not exceed 0.08 in. wg
**Sq inch Fitter is mounted external to unit.
--]0--
8. Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been
completed. Use soap-and-water solution (or method speci- fied by local codes and/or regulations).
IN
A. Configuring Units for Downflow (Vertical) Discharge
1.
Open all electrical disconnects before starting any serv
ice work.
2.
Remove return duct covet" located on duct panel.
Figure 12 shows duct covet" removed. Save duct cover
and screws.
3. Locate lances in basepan insulation that are placed over the perimeter of the vertical duct opening covet"
(Fig. 13).
4. Using a straight edge and sharp knife, cut and remove the insulation around the perimeter of the cover. Re-
move and save 5 screws securing the cover to the base- pan and slide out the covet'. Discard the cover (Fig. 14).
5. Remove supply duct covet" located on duct panel.
Figure 12 shows duct cover removed. Save duct covet"
and screws. Remove and discard 2 screws which secure vertical dis
charge opening cover to basepan (Fig. 15). Slide covet" forward to disengage, then tilt and remove cover through
vertical discharge opening in bottom of unit. Discard
duct covet" (Fig. 16).
--] d_..1_ TEE
/ NtPPLE
_,_ CAP
Fig. 11 -- Sediment Trap
IX. STEP 9 -- INSTALL DUCT CONNECTIONS
The unit has duct flanges on the supply and return air open ings on the side and bottom of the unit. See Fig. 2 5 for con
nection sizes and locations.
7. If unit ductwork is to be attached to vertical opening flanges on the unit basepan 0ackstand applications only),
do so at this time.
8. It is recommended that the basepan insulation around the perimeter of the vertical return air opening be se
cured to the basepan with aluminum tape. Applicable local codes may require aluminum tape to prevent ex-
posed fiberglass.
9. Covet" both horizontal duct openings with the duct coy ers fi'om Steps 2 and 5. Make sure opening is air- and
watertight.
10. After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for instal-
lation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B; and/or lo
cal codes and residence type, NFPA 90B; and/or local codes and ordinances.
--11--
Table 2 -- Maximum Gas Flow Capacity*
NOMINAL INTERNAL LENGTH OF PIPE, FTI"
IRON PIPE, DIAMETER
SIZE
(in.) (in.) 10 20 30 40 50 60 70 80 90 100 125 150 175 200
I/2 .622 175 120 97 82 73 66 61 57 53 50 44 40 -- --
3/4 .824 360 250 200 170 15! 138 125 118 !10 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 !35
11/4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280 11/2 1.610 2100 !460 1180 990 900 8!0 750 690 650 620 550 500 460 430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on
a 0.60 specific gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.
1-This length includes an ordinary number of fittings.
SUPPLY DUCT OPENING RETURN DUCT OPENING
Fig. 12 -- Supply and Return Duct Openings
Fig. 14 -- Vertical Duct Cover Removed
Fig. 13 -- Lance Location for Vertical Duct
Opening Cover
Fig. 15- Removal of Vertical Discharge
Opening Cover
--12--
Loading...
+ 26 hidden pages