Payne PYIP024060, PY1P024040, PYIP030060, PY1P030040, PYIP030080 Installation, Start-up And Service Instructions Manual

...
CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1-5
I. General ................................... 1
RECEIVING AND INSTALLATION ................. 6 15
I. Step 1 -- Check Equipment .................. (3
II. Step 2 -- Provide Unit Support ............... (3
III. Step 3 -- Field Fabricate Ductwork ............ (3
V. Step 5 -- Rig and Place Unit ................. 6
VI. Step 6 -- Connect Condensate Drain .......... 9
VII. Step 7 -- Install Flue Hood ................... 9
VIII. Step 8 -- Install Gas Piping .................. 9
IX. Step 9 -- Install Duct Connections ........... 11
X. Step 10 -- Install Electrical Connections ...... 13
PRE-START-UP ................................. 1(3
START-UP .................................... 16 29
I. Check for Refrigerant Leaks ................. 1(3
II. Start-Up Heating Section and
Make Adjustments ......................... 17
III. Start-Up Cooling Section and
Make Adjustments ......................... 20
MAINTENANCE ................................ 3043
I. Air Filter .................................. 30
II. Unit Top Removal .......................... 30
III. Evaporator Blower and Motor ................ 30
IV. Flue Gas Passageways ..................... 31
V. Combustion-Air Blower ..................... 31
VI. Limit Switch .............................. 31
VII. Burner Ignition ............................ 31
VIII. Main Burners ............................. 32
IX. Condenser Coil, Evaporator Coil, and
Condensate Drain Pan ..................... 32
X. Condenser Fan ............................ 33
XI. Electrical Controls and Wiring ............... 33
Xll. Refrigerant Circuit ......................... 33
Xlll. Gas Input ................................. 33
XlV. Evaporator Airflow ......................... 33
XV. Metering Device -- Acutrol TM Device .......... 33
XVI. Liquid Line Strainer ........................ 33
TROUBLESHOOTING ........................... 34-3(;
START-UP CHECKLIST .......................... CL 1
NOTE TO INSTALLER -- Before the installation, READ
THESE INSTRUCTIONS CAREFULLY AND COMPLETELY.
Also, make sure the User's Manual and Replacement Guide are left with tile unit after installation. The furnace is NOT
to be used for temporary heating of buildings or structures under constrttction.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical compo
nents. Only trained and qualified personnel should install, repair, or service air conditioning equipment.
Cancels: II PY1P 18 1 II PY1P 18 2
9/1/98
Fig. 1 -- Unit PY1P
Untrained personnel can perform basic maintenance flmc- tions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on
air conditioning equipment, observe precautions in the lit erature, tags and labels attached to the unit, and other safety
precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire ex- tinguisher available for all brazing operations.
I. GENERAL
The PY1P units (see Fig. 1) are fidly self-contained, combi- nation Category I gas heating/electric cooling units designed
for outdoor installation. See Fig. 2 5 (pages 2 5) for unit di- mensions. All unit sizes have discharge openings for both hori
zontal and downflow configurations, and are factory shipped with all 4 duct openings covered. Units may be installed ei-
ther on a rooftop or a groundqevel cement slab. See Fig. 6 for roof curb dimensions.
/-COND COIL
- 4 13/16" ()22.2) 43 11116"
4ll0B.B)
B/16 °
(312.?)
\
BLOWER ACCESS BURNER AND CONTROL 30X
PANEL RIGHT SIDE VIEW ACCESS PANEL
REQ'D CLEARANCES FOR SERVICING in (mm)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L in. (mm)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Flue panel ......................... 36 (914)
NEC REQ'D CLEARANCES in. (mm)
Between units, control box side ................ 42 (1067)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1067)
49 9116"
(1259.3)
COIL
RETURN
AIR OPENING
(281,4) I
l? l/1B'_
(433,9)
LOPT_ONAL SUPPLY
AIR OPENING
14 ?liB"
(365.9)
(52,63
10 9116"
(263.R)
7/3" (22.2) BIA,
CONTROL ENTRY_
\
t (203.2)
I 1/8" (2B.6) DIA,
POWER ENTRY
_ (90.51 i
i !
_-I 5/E _ 441,3) OIA.
GASENTRY
1/2 _ - 14 NPT
GASCONNECTION
REAR VIEW
i w (58.O)
! I
(29.6)
FLUE PANEL
FLUE HOOD
0 ?/3" 422.23)
ALTERNATE LV ENTRY
EVAP COIL ACCESS
LEFT SIDE VIEW
I W4" (31.75)
_,ALTERNATE POWER ENTRY
I ?/16 -2 3/18"
(39.3) 455.6)
COMPRE330R ACCES5 PANEL
3/4" NPT (13,0)
DRAIN OUTLET
FRONT VIEW
UNIT
PYIP180040 PY1P024040 PYIP024060 PY1P030040
PYIP030060/080 PYIP036060/080 PYIP036100/120 PYIP042060/080
PYIP042100/120
ELECTRICAL
CHARACTERISTICS
208/230-1-60 208/230-1-60
208/230-1-60 208/230-1-60, 208/230-3-60 208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
UNIT WEIGHT
Ib kg
272 123 303 138 315 143 320 145
332 149 336 153 348 158 375 170
387 176
CORNER WEIGHT UNIT HEIGHT
(Ib/kg) (in./mm)
A B C D E
81/37 82/28 78/35 53/24 24 1/813
97/44 43/20 123/56 40/18 241/813 100/45 46/21 128/57 43/20 241/813 100/45 47/21 128/57 47/21 241/813
103/46 50/22 129/58 50/23 24 1/813
86/39 76/35 111/50 63/29 24 1/813
89/40 79/36 114/52 66/30 24 1/613
95/43 86/39 119/54 75/34 28 1/714
98/45 89/40 122/55 78/35 28 1/714
UNIT
PYIP018040
PY1P024040 PY1P024060 PY1P030040
PY1P030060/080 PY1P036060/080 PY1P036100/120
PYIP042060/080 PY1P042100/120
F
in./mm
169½d420 7
209½d522 3
in./mm
18/5½6/481 0
22/5½6/5826
CENTER OF GRAVITY in./mm
X Y Z
2507/637 20.59/523 2707/688 23.35/593 2698/685 23.27/591 2671/678 23.46/598 10.85/278
2715/689 22.38/568 2750/698 22.48/571 2740/696 22.44/570
2701/686 22.44/570
127/321
2694/684 22.44/570
LEGEND
CG -- Center of Gravity MAT'L -- Materiat COND -- Condenser NEC -- National Electrical Code
LV -- Low Voltage REQ'D -- Required
NOTES:
1. Clearances must be maintained to prevent recirculation of airfrom outdoor- fan discharge.
2 Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 2 -- PYIP018-042 Without Base Rail, Unit Dimensions
--2--
SLOWER ACCESS
PANEL
BURNER ANS CONTROL BOX
RIGHT _IDE VIEW ACCESS PANEL
REQ'D CLEARANCES FOR SERVICING. in. (mm)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in (ram)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Ftue panel ......................... 36 (914)
NEC REQ'D CLEARANCES. in. (ram)
Between units, control box side ................ 42 (1067)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1067)
7/8" (22,2) OIA. I I/8" (28.6) GIA, C(:_ITROL ENTRY POWER ENTRY
1A_/B:TR(41.3) OI A. /
I/2" - 14 NPT FLUE PANEL
GAS CONNECTION
REARVIEW
FLUE HOOD
K
18 I/
(458
(142.
F
1 S/It
(29,S) (253.8)
o
1 9/16"
52"
(1320_8)
A/
-45 I/2"
COND COIL (115E,7)
43 11/16 °
(II08.B)
3 5/1G_
(84,1) I
1 1/4"
(31,75)
ALTERNATE POWER ENTRY
EVAP COIL ACCESS
OPTIONAL RETURN
/ AIROPENING /
7"
(368.9)
T
(52. S)
GUPPLY 10 9/16"
(268, 9)
_1 11/16" (48,2)
(43.21
-OPTIONALSUPRLY
AIR OPENING
COMPRESSOR ACCESS PANEL
(325.4)
1 3/4 ° NPT (19.0)
(34,S) SRAIN OUTLET
LEFT SIDE VIEW 2 3/16" FRONT VIEW
(SS.6)
UNIT
PYIP018040 PYIP024040 PYIP024060 PYIP030040
PYIP030060/080 PYIP036060/080 PYIP036100/120 PYIP042060/080
PYIP042100/120
ELECTRICAL
CHARACTERISTICS
208/230-1-60 208/230-1-60 208/230-1-60
208/230-1-60, 208/230-3-60
208/230-1-60, 208/230-3-60 208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60
UNIT WEIGHT
Ib kg
296 135 327 149 339 155 344 157
356 162 360 164 372 169 399 181
411 187
CORNER WEIGHT UNIT HEIGHT
(Ib/kg) (in,/rnm)
A B C D E
87/40 68/31 82/37 59/27 274/697 103/47 49/22 129/59 46/21 274/697 106/48 52/24 132/60 49/22 274/697 106/48 53/24 132/60 53/24 274/697
102/46 71/32 123/56 60/27 274/697
92/42 82/37 117/53 69/31 274/697
95/43 85/39 120/55 72/33 274/697 101/46 92/42 125/57 81/37 31.4/798
104/47 95/43 128/58 84/38 31.4/798
UNIT
PYIP018040
PY1P024040 PY1P024060 PY1P030040
PY1P030060/080 PY1P036060/080 PY1P036100/120
PYIP042060/080 PY1P042100/120
F G
in./mm in./mm
19%/5048 22¼/5654
23%/6064 26¼/6668
CENTER OF GRAVITY in./mm
X
25.04/636
26.90/683.3
26.82/681.2
26.57/674.9
26.93/684
27.31/693.7
27.23/691.6
26.87/682.5
26.81/681
Y Z
2272/577 2017/5123 2022/5136 201 /5093 13.16/334.3
211 /5354 210 /5326 210 /5331
210 /5331
14.96/380
210 /5337
LEGEND
CG -- Center of Gravity MAT'L -- Material COND -- Condenser NEC -- NationaI Electrical Code
LV -- Low Voltage REQ'D -- Required
NOTES:
1 Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge
2. Adequate clearance around air openings into combustion chamber must be provided
Fig. 3 -- PYIP018-042 With Optional Base Rail, Unit Dimensions
--3--
(19,0)
(55,B) DRAIN OUTLET
FRONT VIEW
RETURN
AIR OPENING
14 71IS"
(365.91
l _'2 1/lS"
(52,6)
10 9/16 °
(268,9)
FLUE HOOD
18 1/16
(458,8)
(E8,0)
t 3116 _
129.GI
0 7/8" (22.23) 1 1/4" (31.?51
ALTERNATELV ENTRY ALTERNATEPOWERENTRY
EVAPCOIL ACCESg
(292. I ) 1325.4) (36, 3)
(253,81
LEFTSIDE VIEW
REQ'D CLEARANCES FOR SERVICING. in (ram)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in (ram)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Flue panel ......................... 36 (914)
NEC REQ'D CLEARANCES. in (ram)
Between units, control box side ................ 42 (1067)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1867)
718" (22.2)DIA, I I18"(28.6)OIA. CONTROLENTRY POWERENTRY
28 15/16
1734 ' I I
1 5/9" (41.9) OIA,_-_
GAS ENTRY
I/2"- 14 NPT
GASOONNECT!0N
i
FLUE PANEL
UNIT
ELECTRICAL
CHARACTERISTICS
PY1PO48080 208/230-1-60, 208/230-3-60,460-3-60 PY1P048100/120/140 208/230-1-60, 208/230-3-60,460-3-80 PY1P060080 208/230-1-60, 208/230-3-60,460-3-80
PYIP060100/120/140 208/230-1-60, 208/230-3-60,460-3-80
UNIT
PYIP048080
PYIP048100/120/140 PYIP060O80 PYIP060100/120/140
CENTER OF GRAVITY (in./mm)
UNIT WEIGHT
Ib kg
414 188 426 193 453 206
465 211
A
107/49 110/50 117/53
120/55
CORNER WEIGHT
(Ib/kg)
B C
83/38 158/72 86/39 159/72 93/42 167/76
96/44 167/76
LEGEND
CG -- Center of Gravity MAT'L -- MateriaI
X Y
28.76/731 2346/596
28.42/722 2342/595
28.36/720 2327/591
27.95/710 2323/590
D 66/30 71/32 76/35
82/37
Z
1535/390 1535/390
1535/390 1535/390
COND -- Condenser NEC -- National Electrical Code
LV -- Low Voltage REQ'D -- Required NOTES:
1. Clearances must be maintained to prevent recircutation of air from outdoor- fan discharge.
2 Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 4 -- PYIP048,060 Without Base Rail, Unit Dimensions
--4--
GIG"
(23, B)
+45 1/2"
CON0 C0IL (115B,71
/
43 11/16"
1110B.8)
(281,4)
(433+a1
AIR OPENING
14 ?/16"
(355.9)
1,
t L2 1116"
(52,6)
10 BilE"
(268.91
5/B"
:39B,91
BLOWER ACCESS BURNER ANO CONTROL BOX
PANEL RIGHT SIDE VIEW ACCESS PANEL
ACCESB PANEL
13/15"
3/4" NPT {15.0)
DRAIN OUTLET
J 3115"
(55,B1 FRONT VIEW
FLUE HO00
1B 1/15
(458.8)
L__
B 518"
(142.9)
r-
1B/16: _lO "_
(29.5) (253.5)
I 114"
(31,7G3
ALTERNATE POWER ENTRY
EVAP COIL ACCEBB
\,
\
\
/16"
REQ'D CLEARANCES FOR SERVICING. in. (ram)
Duct panel ............................. 0
Unit top ........................... 36 (914)
Side opposite ducts ..................... 36 (914)
Compressor access ..................... 36 (914)
(Except for NEC requirements) REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in (ram)
Maximum extension of overhangs ............... 48 (1219)
Unit top ........................... 14 (356)
Duct side of unit ........................ 2 (51)
Side opposite ducts ..................... 14 (356)
Bottom of unit ........................... 0
Flue panel ......................... 36 (914)
NEC REQ'D CLEARANCES. in. (ram)
Between units, controt box side ................ 42 (1867)
Unit and ungrounded surfaces, control box side ......... 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side .................. 42 (1067)
2 1116"
(G2.3) _
?%Nf&2 NT ¢7
1 13116'
29 7/8"
32 1/4" (287.3)
,8,B.B)I
4_I t18" (2B.G) OIA+
POWER ENTRY
to
, /
1 B/B" (41=31 OIA.
GAS ENTRY
I/2" - 14 NPT FLUE PANEL
GAS CONNECTION
UNIT
ELECTRICAL
CHARACTERISTICS
PYIP048080 208/230-1-60,208/230-3-60,460-3-60 PY1P048100/120/140 208/230-1-60,208/230-3-60,460-3-60 PYIP060OBO 208/230-1-60,208/230-3-60,460-3-60
PYIP060100/120/140 208/230-1-60,208/230-3-60,460-3-60
UNIT WEIGHT
Ib kg
438 199 450 205 477 217
489 222
A 113/51 116/53
123/56 126/57
CORNER WEIGHT
(Ib/kg)
B C
89/40 164/75 92/42 165/75 99/45 173/79
182/46 173/79
D 72/33 77/35 82/37
88/40
UNIT
PY1P048080 PY1P048100/120/140
PY1P060080 PY1P060100/120/140
CENTER OF GRAVITY (in./mm)
X Y Z
28.54/7249 2000/508 1766/4486
28.22/7168 2005/5093 1766/4486
28.18/7156 2019/5128 1766/4486
27.79/7059 2023/5138 1766/4486
LEGEND
CG -- Center of Gravity MAT'L -- Material COND -- Condenser NEE -- National Electrical Code
LV -- Low Voltage REQ'D -- Required NOTES:
1.Clearances must be mahTtained to prevent redrculation of air from outdoor- fan discharge
2. Adequate clearance around air openings into combustion chamber must be provided.
Fig. 5 -- PYIP048,060 With Optional Base Rail, Unit Dimensions
--5--
RECEIVING AND INSTALLATION
I. STEP 1 -- CHECK EQUIPMENT
A. Identify Unit
The unit model nmnber and serial number are stamped on unit identification plate. Check this information against ship
ping papers and job data.
B. Inspect Shipment
Inspect for" shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose fl'om its
anchorage, have it examined by transportation inspectors be- fore removal. Fm_vard claim papers directly to transporta-
tion company. Manufacturer is not responsible for any darn age incnrred in transit.
Check all items against shipping list. hnmediately notify your representative if any item is missing.
To prevent loss or damage, leave all parts in original pack ages until installation.
II. STEP 2 -- PROVIDE UNIT SUPPORT
A. Roof Curb
Install accessory roof curb in accordance with instructions shipped with curb. See Fig. 6 for roof curb dimensions. In
stall insulation, cant strips, roofing, attd flashing. Ductwork must be attached to curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasketing material sup-
plied with the roof curb. hnproperly applied gasketing can also result in air leaks and poor" unit performance.
Curb should be level to within 1/4inch. This is necessa W for unit drain to flmction properly. Refer to accessory roof curb
installation instructions for additional information as required.
B. Slab Mount
Place the unit on a solid, level concrete pad that is a mini mmn of 4 in. thick with 2 in. above grade. The slab should be flush on the front of the unit (to allow condensate drain in-
stallation) and should extend 2 in. on the three remaining sides of the unit. See Fig. 7. Install a 6tin. gravel apron in
fl'ont of condenser air inlets to prevent obstrtiction of airflow by grass or shrubs. Do not secure the unit to the slab exc'u_t
when required by local codes.
C. Flush Mount
Place side of unit with duct panel flush against transition. On units with optional base rails, the skirt on duct-panel side of unit cat] be removed or relocated to allow unit to be mounted
flush against transitions that extend below basepan of trait, To move skirt, proceed as follows:
1. Remove 4 screws holding skirt to base rail. Retain screws.
2. Remove skirt or slide skirt inwards until alternate clear ance holes align with base rails.
3. Secure with screws removed in Step 1. Holes align with base rails.
To remove wood support under unit (with base rail only), loosen 4 screws above rigging holes and slide assembly out through
rectangular hole.
III. STEP 3 -- FIELD FABRICATE DUCTWORK
Secure all ducts to roof curb and building structure on verti- cal discharge units. Do [rot cczmect chlctwork to unit. For hori-
zontal applications, unit is provided with flanges on the hori zontal openings. All ductwork should be secured to the flanges.
Insulate attd weatherproof all external ductwork, joints, attd roof openings with counter flashing and inastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be in- sulated and covered with a vapor barrier.
If a plenmn return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork. Cabi- net return air static shall not exceed -.25 in. wg.
IV. STEP 4 -- PROVIDE CLEARANCES
The required n_inimunt operating and service clearances are shown in Fig. 2-5. Adequate combustion, ventilation, and cot]-
denser air must be provided, in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code ANSI (American National Standards Association) Z223.1
(in Canada, sections 7.2, 7.3 or 7.4 or Can/CGA [Canadian
Gas Association] B 149 Installation Codes), or applicable pro- visions of local building code.
The condenser fat] pushes air through the condenser coil and discharges it through the bank of louvers in the top cover,
the decorative grille on the right side of the unit, and the con> presser access panel. Be sure that the fan discharge does not
recirculate to the condenser coil. Do not locate the unit in ei- ther a corner or tinder an overhead obstruction. The mini-
mum clearance under a partial overhang (such as a normal house overhang) is 48-in. above the unit top. The maximunl
horizontal extension of a partial overhang must not exceed 48 inches.
Do not place the unit where water, ice, or snow fl'om an over- hang or roof will damage or flood the unit. Do not install the
unit on carpeting, tile, or other combustible materials. The unit may be installed on wood flooring or on Class A, B, or C
roof covering materials.
V. STEP 5 -- RIG AND PLACE UNIT
Use spreader bars or crate top when rigging the unit. The units must be rigged for lifting as shown in Fig. 8 and 9. Re-
fer to Table 1 for operating weight attd to Fig. 2 5 for" corner weights. U[se extreme c'ozlticzr to pz'eveirt ct_moge wheir mov
ing tire zmib U)rit must ['emoin in on zqJz'(ght [rositio:r dzlz'inq
oH ['{qgd/_,_ and moviz\_ OlreZ'ation.s. The unit Intist be level for
proper condensate drainage; therefore, the groundqevel pad or accessory roof curb must be level before setting the unit it]
place. When a field fabricated support is used, be sure that the support is level and properly supports the unit.
--6--
FLAT
CURB
PART NUMBER
CPRFCURB001A01 CPRFCURB002A01 CPRFCURB003A01
_A_
8" [203]
11" [279]
14" [356]
POWER AND
GAS ENTRY
6
"0
5UPPLY AIR
[SEE DETAIL "A "j
17!
[44E]
SUPPLY AIR
OPENING
RETURN AIR
OPENING
[279 (406]
3G 3/4".
[1010]
[13]
SCREW DLEARANOE
SEAL
(_PPLIED WITH CURB)
FOR UNITS WITH
BASE RAILS)
(FIELD SUPPLIED)
=FING FELT
(FIELD SUPPLIED)
(FIELD SUPPLIED)
MATERIAL
(FIELD SUPPLIED)
THIS BRACKET MUST BE REMOVED
BEFORE iNSTALLATION
\
MUST BE REMOVED
BEFORE INBTALLATION
IGIO INSULATION
(FIELD SUPPLIED)
DETAIL "A"
33 7/8"
[858]
NOTES:
1. Roof curb must be set up for unit being installed.
2. SeaI strip must be applied as required for unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7. [_ Direction of airflow.
8. Insulated panels: 1-in. thick fiberglass 1 Ib density.
Fig. 6 -- Roof Curb Dimensions
--7--
2,0'z,,
FLUSHWITHSLAB_ _F2. 0-
//i ! I
/ J
/ ,
/ b
// I I
/ I I
L. ...... J
, _
r "1
I I I i
I I
I t I t
L J
......U.......... ;_7.........20,,
CONCRETESLAB
Fig. 7 -- Slab Mounting Details
SEEDETAILA"_
SEAL STRIP MUST BE IN PLACE BEFORE PLACING
UNIT ON ROOF CURB "1
914-1371 / (36"- 54") /
_'_ DUCT END l\
/
SECURESCREW
AGAINSTBASEPAN
TO HOLDLIFTING
BRACKETINPLACE
DETAIL A
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in De- tail "A." Lifting brackets to be centered around the unit center of gravity. Use wooden top skid when rigging, to prevent rigging straps from dam- aging unit.
UNIT MAX A B C
PYIP WEIGHT
Size Ib kg in. mm in. mm in. mm
018 332 150 24.3 618 24.85 631 024 375 170 22.4 570 24.85 631 030 384 174 22.3 585 24.85 631 036 408 185 49.4 !255 22.0 559 24.85 631 042 447 203 22.5 571 28.85 733 048 486 220 21.0 533 34.85 885 060 525 238 21.5 545 34.85 885
Fig. 8 -- Suggested Rigging for Units Without
Base Rail
!
S 4-1371 UNIT ON ROOF CURB
BEE DETAIL A
NOTICE TO RIGGERS
Hook rigging shackles through holes in lifting brackets, as shown in De- tail "A." Lifting brackets to be centered around the unit center of gravity. Use wood top skid when rigging, to prevent rigging straps from damag- ing unit. Remove 4 screws to slide wood support through rectangular
hole in rail.
UNIT MAX PYIP WEIGHT
Size Ib kg
018 320 145
024 363 165 030 380 172 036 396 180 042 435 !97 048 474 215 060 5!3 233
A
in,
49.4
mm in.
24.4
22.6
22.5
1255 22.2
22.6 2! .2
21.6
mm
619 574 571 563 574 538 549
in, mm
28.2 715
28.2 715
28.2 715
28.2 715
32.2 816
38.2 969
38.2 969
Fig. 9 -- Suggested Rigging for Units With
Optional Base Rail
A. Units Without Base Rail
If accessory rigging brackets are to be used for rigging, in- stall them as follows:
1. Position brackets as close to the corners of unit as pos- sible. Be sure brackets are well outside of center of grav-
ity. See Fig. 2 and 4.
2. Position paint protectors and foam strips between screws and painted surface of unit. Tighten screws until they
make contact with the paint protectors.
3. Secure device or hook of sufficient strength to hole in bracket as shown in detail "A" of Fig. 8.
4. If wood top is available, use it for a spreader bar to pre-
vent straps fl'om damaging unit. If wood top is not avail-
able, use spreader bars of sufficient length.
--8--
B. Units With Optional Base Rail
Lifting holes are provided in optional base rail as shown in Fig. 9. Operating weights are shown in Table 1. Refer to rig-
ging instructions on unit. Protective wood support must be removed from unit before
unit is mounted to curb. Remove 4 screws that secure sup port above rigging holes in rails. Slide support out through
rectangular hole in rail. See Fig. 9.
Vl. STEP 6 -- CONNECT CONDENSATE DRAIN
NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Model PY1P disposes of condensate water through a 3/4 in. NPT fitting which exits through the compressor access panel.
See Fig. 2 5 for location. Condensate water can be drained directly onto the roof in roof
top installations (where permitted) or onto a gravel apron in groundqevel installations. Install a field-supplied conden-
sate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain pan condensate connection to pre
vent the pan fi'om overflowing. See Fig. 10. Prime the trap with water. When using a gravel apron, make sure it slopes
away fl'om the unit. If the installation requires draining the condensate water away
fi'om the unit, install a 2-in. trap at the condensate connec- tion to ensure proper drainage. See Fig. 10. Make sure that
the outlet of the trap is at least 1 in. lower than the drain- pan condensate connection to prevent the pax] fi'om overflow
ing. Prime the trap with water. Connect a drain tube using a minimum of 3/4 in. PVC or 3/4 in. copper pipe (all field
supplied) at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least
one in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks.
1" MIN,
t
Fig. 10 -- Condensate Trap
VIII, STEP 7 -- Install Flue Hood The flue hood assembly is shipped screwed to the control box
in the burner compartment. Remove the burner access panel to locate the assembly.
Fox" units being installed in California Air Quality Manage ment Districts which require NO x emissions of 40 nanograms/
joule or less, kit CRLOWNOX001A00 must be installed.
Install the flue hood as follows:
1. This installation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in Canada, CAN/CGA B149.1, and B149.2), or
NFPA (National Fire Protection Association) latest re vision. Refer to Provincial and local plumbing or waste-
water codes and other" applicable local codes.
2. Remove fl'om shipping location. Place vent cap assem bly over fine panel. Orient screw holes in vent cap with
holes in the fine panel.
3. Secure flue hood to flue panel by inserting a single screw on the right side, the left side, and the top of the hood.
VIII. STEP 8 -- INSTALL GAS PIPING
The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/d in.
FPT gas inlet on the manual shutoff or gas valve. Install a gas supply line that runs to the heating section. Re
fer to Table 2 and the NFGC for" gas pipe sizing. Do not zl.se ca.st iron pipe. It is recommended that a black iron pipe is
used. Check the local utility fox" recommendations concern- ing existing lines. Size gas supply piping fox" 0.5 in. wg maxi-
mum pressure drop. Never" zLse pipe _smaller than tire _/z-hr. FPT go_s hrlet on tire unit ga_s valve.
For natural gas applications, the gas pressure at unit gas cox]- nection must not be less than 4.0 in. wg or greater than
13 in. wg while the unit is operating. For propane applica-
tions, the gas pressure must not be less than 4.0 in. wg or greater than 13 in. wg at the unit connection.
An l/a-in. NPT plugged tapping accessible for test gage cox]- nection must be installed immediately upstream of the gas
supply connection to the furnace. When installing the gas supply line, observe local codes per
raining to gas pipe installations. Refer to the NFGC ANSI Z223.1-1988 NFPA latest edition (in Canada, CAN/CGA B 149.1,
(2) M86). In the absence of local building codes, adhere to the
following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe V4 inch in every 15 ft to prevent traps. Grade all hori-
zontal runs downward to risers. Use risers to connect to
heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropri-
ate straps, hangers, etc. Use a minimum of one hanger every 6 ft. Fox" pipe sizes larger than _?z in., follow rec
ommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to
male threads of joint when making pipe connections. Use
only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes.
Newt u_se Teflon talre.
4. Install sediment trap in riser" leading to heating section per Fig. 11. This drip leg functions as a trap for" dirt and
condensate.
5. Install an accessible, external, manual main shutoffvalve
in gas supply pipe within 6 ft of heating section.
6. Install groundOoint union close to heating section be- tween unit manual shutoff and external manual main
shutoff valve.
7. Pressure test all gas piping in accordance with local and
national plumbing and gas codes before connecting pip- ing to unit.
NOTE: Pressure test the gas supply system a/terthe gas sup- ply piping is connected to the gas valve. The supply piping
must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of
0.5 psig. Pressure test the gas supply piping system at pres- sures equal to or less than 0.5 psig. The unit heating section
must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the
groundOoint union.
--9--
Table I -- Physical Data -- Unit PYIP
UNIT SIZE PYIP
NOMINAL CAPACITY (ton) OPERATING WEIGHT (Ib)
Without Base Rail With Optional Base Rail
COMPRESSORS
Quantity
REFRIGERANT (R-22)
Charge (Ib)
REFRIGERANT METERING DEVICE
Orifice ID (in,)
CONDENSER COIL
Rows,..Fins/in, Face Area (sq ft)
CONDENSER FAN
Nominal Cfm Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows Fins/in. Face Area (sq ft)
EVAPORATOR FAN
Nominal Airflow (Cfm) Size (in.)
FURNACE SECTION*
Burner Orifice (Qty.,.drilt size)
Natural Gas
Burner Orifice (Qty._drill size)
Propane Gas
RETURN-AIR FILTERS (in.)t
Throwaway
018040 024040 024060 030040 030060 030080 036060
11/2 2 2 2//z 2 Y, 2i/, 3
036080
3
036100
3
036120
3
272 303 315 320 332 332 336 336 348 348 296 327 339 344 356 356 360 360 372 372
Rotary Reciprocating
1 1
i
260 2.75 2.75 3.40 I 3.40 340 430 430 4.30 430
m
Acutror M Device
.030 030 030 030 030 .030 .032 .032 032 .032
1.17 1..17 1..17 2..17 2..17 2.17 2.17 595 5.95 5.95 5.95 5.95 595 595
1700 1700 1700 1900 1900 1900 1900
18 18 18 18 18 18 18
1A(850) V_(850) V_(850) V8(850) V8(850) _A(850) ¼ (1050)
3.15 3..15 3..15 3..15 3..15 3.15 3.15 183 2.29 2.29 2.29 2.29 229 306
Direct Drive
600 800 800 1000 1000 1000 1200
10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10
1.32 1..32 2..32 1..32 2..32 2.32 2.32
1.41 1..41 2..47 1..41 2..47 2.42 2.47
20 x 20 20 x 20 20 x 20 20 x 24 20 x 24 20 x 24 20 x 24
2.17 595
1900
18
_(1050)
3.15 306
1200
10 x 10
2.32
2. 42
20 x 24
2..17
5.95
1900
18
1A(1050)
3..15
3.06
1200
10 x 10
2..32
2..40
20 x 24
2.17 595
1900
18
¼ (1050)
3.15 306
1200
10 x 10
3.32
3 .42
20 x 24
UNIT SIZE PYIP 042060 042080 042100 042120 048080 048100 048120 048140 060080 060100 060120 060140 NOMINAL CAPACITY (ton) 3 ½ 3½ 3 ½ 34½ 4 4 4 4 5 5 5 5
OPERATING WEIGHT (tb)
Without Base Rail 375 375 387 387 414 426 426 426 453 465 465 465 With Optional Base Rail 399 399 411 411 438 450 450 450 477 489 489 489
COMPRESSORS Reciprocating Hermetic Scroll
Quantity 1 1
REFR,GERANT(R-22,I I I I
Charge (Ib) 520 520 520 520 650 650 650 650 700 7.00 7.00 7.00
REFRIGERANT METERING Acutrot Device
DEVICE
Orifice ID (in.) .034 .034 .034 .034 .030 .030 .030 .030 .030 030 030 030
CONDENSER COIL
Rows...Fins/in. 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2...17 2..17 2..17 Face Area (sq ft) 704 704 704 704 867 867 867 867 867 8.67 8.67 8.67
CONDENSER FAN
Nominal Cfm 1900 1900 1900 1900 2400 2400 2400 2400 2400 2400 2400 2400 Diameter (in.) 18 18 18 18 20 20 20 20 20 20 20 20
Motor Hp (Rpm) (1050) (1050) (1050) (1050) % (1050) % (1050) % (1050) % (1050) % (1050) _/J(1050) _/J(1050) _/J (1050)
EVAPORATOR COIL
Rows Fins/in. 3.15 3.15 3.15 3.15 3..15 3..15 3..15 3..15 4..15 4..15 4..15 4..15 Face Area (sq ft) 333 333 333 333 444 444 444 4.44 4.44 4.44 4.44 4.44
EVAPORATOR FAN Direct Drive
Nominal Airflow (Cfm) 1400 1400 1400 1400 1600 1600 1600 1600 1995 1995 1995 1995
Size (in.) 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10
FURNACE SECTION*
Burner Orifice (Qty...drill size) 2.32 2.32 2.32 3.32 2.32 2.32 3.32 3..32 2..32 2..32 3..32 3..32
Natural Gas
Burner Orifice (Qty...drill size) 2.47 2.42 2.40 3.42 2.42 2.40 3.42 3..40 3..42 2..40 3..42 3..40
Propane Gas
RETURN-AIR FILTERS (in.)t
Throwaway 24 x 24 24 x 24 24 x 24 24 x 24 24 x 30 24 x 30 24 x 30 818"* 24 x 30 24 x 30 24 x 30 960**
*Based on altitude of 0-2000 feet.
tRequired filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated
cooling airflow or the heating airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity
type. For non-standard air filters, air filter pressure drop must not exceed 0.08 in. wg
**Sq inch Fitter is mounted external to unit.
--]0--
A. Configuring Units for Downflow (Vertical) Discharge
8. Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been
completed. Use soap-and-water solution (or method speci- fied by local codes and/or regulations).
IN
--] d_..1_ TEE
/ NtPPLE
_,_ CAP
Fig. 11 -- Sediment Trap
IX. STEP 9 -- INSTALL DUCT CONNECTIONS
The unit has duct flanges on the supply and return air open ings on the side and bottom of the unit. See Fig. 2 5 for con
nection sizes and locations.
1.
2.
Open all electrical disconnects before starting any serv
ice work.
Remove return duct covet" located on duct panel.
Figure 12 shows duct covet" removed. Save duct cover
and screws.
3. Locate lances in basepan insulation that are placed over the perimeter of the vertical duct opening covet"
(Fig. 13).
4. Using a straight edge and sharp knife, cut and remove the insulation around the perimeter of the cover. Re-
move and save 5 screws securing the cover to the base- pan and slide out the covet'. Discard the cover (Fig. 14).
5. Remove supply duct covet" located on duct panel.
Figure 12 shows duct cover removed. Save duct covet"
and screws. Remove and discard 2 screws which secure vertical dis
charge opening cover to basepan (Fig. 15). Slide covet" forward to disengage, then tilt and remove cover through
vertical discharge opening in bottom of unit. Discard
duct covet" (Fig. 16).
7. If unit ductwork is to be attached to vertical opening flanges on the unit basepan 0ackstand applications only),
do so at this time.
8. It is recommended that the basepan insulation around the perimeter of the vertical return air opening be se
cured to the basepan with aluminum tape. Applicable local codes may require aluminum tape to prevent ex-
posed fiberglass.
9. Covet" both horizontal duct openings with the duct coy ers fi'om Steps 2 and 5. Make sure opening is air- and
watertight.
10. After completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA for instal-
lation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B; and/or lo
cal codes and residence type, NFPA 90B; and/or local codes and ordinances.
--11--
Table 2 -- Maximum Gas Flow Capacity*
NOMINAL INTERNAL LENGTH OF PIPE, FTI"
IRON PIPE, DIAMETER
SIZE
(in.) (in.) 10 20 30 40 50 60 70 80 90 100 125 150 175 200
I/2 .622 175 120 97 82 73 66 61 57 53 50 44 40 -- --
3/4 .824 360 250 200 170 15! 138 125 118 !10 103 93 84 77 72
1 1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 !35
11/4 1.380 1400 950 770 600 580 530 490 460 430 400 360 325 300 280 11/2 1.610 2100 !460 1180 990 900 8!0 750 690 650 620 550 500 460 430
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on
a 0.60 specific gravity gas). Refer to Table C-4, National Fire Protection Association NFPA 54.
1-This length includes an ordinary number of fittings.
SUPPLY DUCT OPENING RETURN DUCT OPENING
Fig. 12 -- Supply and Return Duct Openings
Fig. 14 -- Vertical Duct Cover Removed
Fig. 13 -- Lance Location for Vertical Duct
Opening Cover
Fig. 15- Removal of Vertical Discharge
Opening Cover
--12--
-- X.STEP10 -- INSTALL ELECTRICAL CONNECTIONS
Fig. 16 -- Vertical Discharge Cover Removed
Adhere to the following criteria when selecting, sizing, and installing the duct system:
1. Units are shipped with all 4 duct openings covered. Re- move appropriate panels for intended installation.
2. Select and size ductwork, supply-air registers, and return-air grilles according to American Society of
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE) recmnmendations.
3. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may
be screwed or bolted to duct flanges. Use suitable gas kets to ensure weathertight and airtight seal.
4. All units must have field supplied filters or accesso W fil ter rack installed in the return air side of the unit. Rec
ommended sizes for filters are shown in Table 1.
5. Size all ductwork for maxinlmn required airflow (either heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be affected.
6. Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through uncon-
ditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Con
ditioning Contractors of America (ACCA) minimum in- stallation standards for heating and air conditioning
systems. Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in building structure in accordance with local codes and
good building practices.
1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes gov
erning such wiring. In Canada, all electrical connec- tions must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only coi)perconductor for connections between field supplied electrical disconnect switch and unit. DO NOT
USE ALUMINUM WIRE.
3. Be sure that high voltage power to unit is within oper ating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On
3 phase units, ensure phases are balanced within 2%. Consult local power company for correction of improper
voltage and/or phase imbalance.
A. High-Voltage Connections
The unit must have a separate electrical service with a field supplied, waterproof, disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate for maxL mum fllse/circuit breaker size and minimum circuit amps (am- pacity) for" wire sizing. See Table 3 for electrical data.
The field supplied disconnect switch box may be mounted on the unit over the high voltage inlet hole when tire standard
power and low-voltage entry points are used. See Fig. 2-5 for" acceptable location.
Standard Power Enti T Proceed as follows to complete the high-voltage connections
to the unit:
1. Connect ground lead to chassis ground connection when using separate ground wire.
2. Run high-voltage leads into unit control box.
3. Locate black and yellow wires connected to line side of
contactor.
4. Cut wires at partition where they exit control box.
5. Strip back leads and connect to high voltage leads. On 3 phase units, blue wire is provided stripped back and
ready to connect to high voltage lead. See unit wiring label and Fig. 17.
--13--
Table 3 -- Electrical Data -- Unit PYIP
UNIT VOLTAGE SIZE V-PH-Hz RANGE
PY1P Min Max
018 208/230-1-60 187 253
024 208/230-1-60 187 253
208/230-1-60 187 253
030
208/230-3-60 187 253 208/230-1-60 187 253
036 208/230-3-60 187 253
460-3-60 4!4 506
208/230-1-60 187 253
042 208/230-3-60 187 253
460-3-60 414 506
208/230-1-601- 187 253
208/230-1-60"* 187 253
048 208/230-3-601- 187 253
208/230-3-60"* 187 253
460-3-601- 414 506
460-3-60** 4!4 506
298/230-1-60 187 253
060 208/230-3-60 187 253
460-3-60 414 506
COMPRESSOR OUTDOOR-FAN
MOTOR
RLA LRA FLA
8.3 45.0 0.7
!2.4 6! .0 0.7
14.4 82.0 1.4
9.4 66.0 1.4
18.0 96.0 1.4
11.7 75.0 1.4
5.6 40.0 0.8
20.4 104.0 1.4
14.0 9! .0 1.4
6.4 42.0 0.8
21.8 124.0 2.!
26.4 129.0 2.1 !2.8 93.0 2.!
15.0 99.0 2.1
6.4 46.5 ! .1
8.2 50.0 1.!
32.1 169.0 2.! !9.3 123.0 2.!
19.0 62.0 ! .1
INDOOR-FAN POWER SUPPLY
MOTOR
FLA MCA MOCP*
1.8 12.9 15
2.0 18.2 30
2.3 2! .4 30
2.0 15.1 25
2.8 28.7 40
2.8 18.8 30
1.4 9.2 10
4.0 30.9 50
4.0 22.9 35
2.0 10.8 15
5.0 40.1 60
5.0 40.1 69
5.0 25.9 40
5.0 25.9 49
2.3 !3.7 29
2.3 13.7 20
6.8 49.0 60
6.8 33.0 50
3.2 !6.8 25
AWG 60 C
MIN WIRE
SIZE
14 12 10 12 10 12 14
8 10 14
8
6 10 10 !4 14
6
8 !2
MAX WIRE
LENGTH (ft)
75 8O
100
8O 9O
85 100 100
85 100 100 100
75
75
100 100 100
9O 100
LEGEND
AWG -- American Wire Gage
FLA -- Full Load Amps HACR -- Heating, Air Conditioning and
Refrigeration
LRA -- Locked Rotor Amps MCA -- Minimum CircuitAmps
MOCP -- Maximum Overcurrent Protection RLA -- Rated Load Amps
*Fuse or HACR Breaker.
1-Carrier Scroll Compressor. **CopeIand Scroll Compressor.
0Q°s
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CGA (Canadian Gas Associa- tion) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, deter-
mine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance.
% Voltage imbalance
= !00 x max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
A a C AB = 452 v
BC = 464 v
(_ AC = 455 v
Average Voltage =
452 + 464 + 455
3
= 1371
3
= 457
Determine maximum deviation from average voltage. (AB) 457 - 452 = 5 v (BC) 464 - 457 = 7 v (AC) 457 - 455 = 2 v
Maximum deviation is 7 v. Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x --
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi- mum allowable 2%.
o
IMPORTANT: If the supply voltage phase imbalance is more than 2 Yo, contact your local electric utility company immediately.
--14--
THERMOSTAT (TYPICAL)
1,¢o,,¢,¢91
t S J g, g
_-I _jI Z Cl I Z z I wl rr I m I r¢l
/
2-
I SPLICE BOX
GND LOW-VOLTAGE POWER LEADS (SEE UNIT
WIRING LABEL)
__%K[
_-4L..U-E
]""- "_ _ '-- POWER
]_ --._q ._TI SUPPLY
----1"--S--- FIELD-SUPPLIED
FUSED DISCONNECT
LEGEND
.... Field Control-Voltage Wiring
.... Field High-Voltage Wiring
NOTE: Use blue wire for 3-phase units only.
Fig. 17 -- High- and Control-Voltage Connections
Alternate Power Entry
1. Remove knockouts in fixed compressor panel located on duct panel side of unit.
2. Route high-voltage leads into high-voltage terminal box.
3. Connect ground wire to green yellow wire using field supplied splice.
4. Connect power wires to unit high-voltage leads.
5. On 3 phase units, locate blue wire projecting fi'om corn pressor junction box. Cut wire at partition and route into
high voltage junction box through grommet in back of
junction box.
6. On 3-phase units, strip back blue lead and connect to third leg of the power wires.
B. Special Procedures for 208-v Operation
1. Disconnect the orange transformer-primary lead from the contactor. See unit wiring label.
2. Remove the tape and wirenut fi'om the terminal on the end of the red transformer-prhnm T lead.
3. Save the wirenut.
4. Connect the red lead to the contactor terminal fi'om which the orange lead was disconnected.
5. Using the wirenut removed fi'om the red lead, insulate the loose terminal on the orange lead.
6. Wrap the cover with electrical tape so that the metal terminal cannot be seen.
C. Control Voltage Connections
Locate the roon] thermostat on an inside wall in the space to be conditioned, where it will not be subjected to either a cool-
ing or heating source or direct exposure to sunlight. Mount tire thermostat 4 to 5 ft above the floor.
NOTE: Do not use any type of power stealing thermostat. Unit control problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insu- lated (35 C mininmm) wires to make the control voltage con-
nections between the thermostat and the unit. If the thermo- stat is located more thai] 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color" coded,
insulated (35 C minimum) wires. Standard Connection
Remove knockout hole located in the flue panel adjacent to the control access panel. See Fig. 2-5. Remove the rubber groin
met fl'om the installer's packet (included with unit) and in- stall grommet in the knockout opening. Provide a drip loop
before running wire through panel. Run the low voltage leads from the thermostat, through the
inlet hole, and into unit low-voltage splice box. Locate five 18-gage wires leaving control box. These low-
voltage connection leads can be identified by the colors red, green, yellow, brown, and white. (See Fig. 17.) Ensure the leads
are long enough to be routed into the low-voltage splice box
(located below right side of control box). Stripped yellow wire
is located in connection box. Route leads through hole in bot- tom of control box and make low voltage connections as shown
in Fig. 17. Secure all cut wires, so that they do not interfere with operation of unit.
Alternate Connection Remove knockout in compressor fixed panel located below high
voltage knockout. Remove the rubber grommet fl'om the in staller's packet (included with unit) and install grommet in
the knockout opening. Route thermostat wires through grom- met providing drip loop at panel, Connect low voltage leads
as shown in Fig. 17.
D. Heat Anticipator Setting
The rooin thei'nmstat heat anticipator nmst be properly ad-
justed to ensure proper heating performance. Set the heat
anticipator, using an ammeter between the W and R termi nals to determine the exact required setting.
NOTE: For thermostat selection purposes, use 0.18 amp for" the approximate required setting.
Failure to make a proper heat anticipator adjustment will result in improper operation, discomfort to the occupants of
the conditioned space, and inefficient energy utilization; how- ever, the required setting may be changed slightly to provide
a greater degree of comfort for a particular installation.
E. Transformer Protection
The unit transformer protection may be one of 2 types.
The ill-st t,"on_sfoFmez"(ype may contain an auto. reset over
current protector for control circuit protection. If this device trips, it may reset without warning, starting the heating or
cooling section of this product. Use caution when servicing; if overcurrent protector continues to trip, there is a problem in
the low voltage electrical circuit, such as an electrical short, ground, or transformer overload. Disconnect power, correct
the condition, and check for normal unit operation.
The _seconct rfon_stbrmel" type is of the energy limiting type. It
is set to withstand a 30 second overload or shorted second ary condition.
--15--
PRE-START-UP
Proceed as follows to inspect and prepare the unit for initial start up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU- TION, and INFORMATION labels attached to, or shipped
with, unit.
3. Make the following inspections: a. Inspect for shipping and handling dan]ages such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refi'igerant tubing connections
and on unit base. Detecting oil generally indicates a refi'igerant leak. Leak-test all refrigerant tubing con
nections using electronic leak detector, halide torch, or liquid soap solution. If a refi'igerant leak is de-
tected, see Check for Refi'igerant Leaks section on this page.
c. Inspect all field and factm T wiring connections. [3e
sure that connections are completed and tight.
d. Inspect coilfins. Ifdamaged during shipping and han-
dling, carefiflly straighten fins with a fin comb.
4. Verify the following conditions:
a. Before lighting the unit for the first time, perform
the following: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is
recommended that the ground joint union be loos- ened, and the supply line be allowed to purge until
the odor of gas is detected. Never purge gas lines into a combustion chamber, hnmediately upon detection
of gas odor, retighten the union. Allow 5 minutes to elapse, then light unit.
b. Make sure that condenser-fan blade is correctly po-
sitioned in fan orifice. Leading edge of condenser fan blade should be '/z in. maximum fl'om plastic fan ori
rice (see Fig. 18).
c. Make sure that air filter(s) is in place. d. Make sure that condensate drain trap is filled with
water to ensure proper drainage.
e. Make sure that all tools and miscellaneous loose parts
have been removed.
_i_ -,-1/2 IN, MAX
\l
]_ / MOTOR SHAFT
Fig. 18 -- Fan Blade Clearance
START-UP
I. CHECK FOR REFRIGERANT LEAKS
Proceed as follows to locate and repair a refrigerant leak and to charge the unit:
f. Locate leak and make sure that refrigerant system pres-
sure has been relieved and reclaimed fi'om both high and low pressure ports.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair.
3. Add a small charge of R 22 refi'igerant vapor to system and leak test unit.
4. Evacuate and reclaim refrigerant from refrigerant sys- tem if additional leaks are not found.
5. Charge unit with R-22 refi'igerant, using a volumetric charging cylinder or accurate scale. Re[ki" to tlnit Foth\q
piote [bF r'_quiF_(t c'hofge. Be sure to add extra refriger-
ant to compensate for internal volume of filter drier.
--16--
II. START UP HEATING SECTION AND MAKE ADJUSTMENTS
Do not jumper any safety devices when operating the unit. Make sure that burner orifices are properly aligned. Un
stable operation may occur when the burner orifices in the manifold are misaligned.
Follow the lighting instructions on the heating section opera tion label (located inside the burner or blower access door) to
start the heating section.
NOTE: Make sure that gas supply has been purged, and that all gas piping has been checked for leaks.
A. Check Heating Control
Start and check the unit for proper heating control operation as follows. (See furnace lighting instructions located inside
burner or blower access panel.)
1. Place the room thermostat SYSTEM switch in the HEAT position and the fan switch in the AUTO. position.
2. Set the heating temperature control of the thermostat above rooIn temperature.
3. The induced-draft motor will start.
4. After a call for heating, the main burner should light within 5 seconds. If the burners do not light, there is a
22 second delay before another 5 second try. If the burn- ers still do not light, this sequence is repeated. If the
burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break
the 24 v power to W.
5. The evaporator fan will turn on 45 seconds after the flame has been established. The evaporator fan will turn off
45 seconds after the thermostat has been satisfied.
B. Check Gas Input
Check gas input and manifold pressure after unit start-up (see Table 4). If adjustment is required proceed as follows.
The rated gas inputs shown in Table 4 are for altitudes from sea level to 2000 ft above sea level. These inputs are based
on natural gas with a heating value of 1050 Btu/ft :_ at 0.65 specific gravity, or propane gas with a heating value of
2500 Btu/ft :_ at 1.5 specific gravity. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level. When
the gas supply being used has a different heating value or specific gravity, refer to national and local codes, or contact
your distributor to determine the required orifice size.
C. Adjust Gas Input
The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure.
Measuring the gas flow at the meter is recommended for natu- ral gas units. The manifold pressure must be measured to
determine the input of propane gas units. Measure Gas Flow (Natural Gas Units)
Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be main
rained between 3.4 and 3.6 in. wg. If larger adjustments are required, change main burner orifices following the recom
mendations of national and local codes. NOTE: All other appliances that use the same meter must
be turned off when gas flow is measured at the meter. Proceed as follows:
1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (see Fig. 19), then con- nect manometer at this point. Turn on gas to unit.
3. Record number of seconds for gas meter test dial to make one revolution.
4. Divide number of seconds in Step 3 into 3600 (number of seconds in one hour).
5. Multiply result of Step 4 by the number of cuft shown for one revolution of test dial to obtain cuft of gas flow
per hour.
6. Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value
with heating input shown in Table 4. Consult the local gas supplier if the heating value of gas is not known.
EXAMPLE: Assume that the size of test dial is 1 cuft, one revolution takes 30 seconds, and the heating value of the gas
is 1050 Btu/ft:L Proceed as follows:
1. 30 seconds to complete one revolution.
2. 3600 + 30 = 120.
3. 120 x 1 = 120 ft:*of gas flow/hr.
4. 120 x 1050 = 126,000 Btuh input.
If the desired gas input is 120,000 Btuh, only a minor change in the manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas input:
1. Remove covet" screw over regulator adjustment screw on gas valve.
2. Turn regulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counter
clockwise to decrease input. Manifold pressure must be between 3.4 and 3.6 in. wg.
3. Replace cover screw cap on gas valve.
4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn
on gas to unit and check for leaks.
--17--
Table 4 -- Rated Gas Inputs at Indicated Manifold Pressures
UNIT PY1P
018040, 024040, 030040 024060, 030060, 036060, 042060 030080, 036080, 042080,
048080, 060080
036100, 042100, 048100, 060100 036120, 042120, 048120, 060120 048140, 060140
NUMBER
OF
ORIFICES
1
2 2 2
3 3
GAS SUPPLY PRESSURE
(in. wg)
Natural Propane
Min Max Min Max
4.0 13.0 4.0 !3.0
4.0 13.0 4.0 !3.0
4.0 13.0 4.0 !3.0
4.0 13.0 4.0 !3.0
4.0 13.0 4.0 13.0
4.0 13.0 4.0 !3.0
MANIFOLD
NATURAL GAS PROPANE*
PRESSURE
(in, wg)
Natural Propane
3.5 3.1
3.5 3.3
3.5 3.4
3.5 3.7
3.5 3.5
3.5 3.4
Orifice Heating
Drill Input
Size (Btuh)t
32 40,000 32 58,000
32 80,000 32 95,000
32 120,000 32 138,000
Orifice
Drill
Size
41 47
42 4O
42 4O
Heating
Input
(Btuh)t
40,000 54,000
80,000 95,000
115,000
!33,000
*When a unit is converted to propane, different size orifices must be used. See separate natural-to-propane conversion kit
instructions.
1-Based on altitudes from sea level to 2000 ft above sea level. For altitudes above 2000 ft, reduce input rating 4% for each
additional 1000 ft above sea level. In Canada, from 2000 ft above sea level to 4500 ft above sea level, derate the unit
10%.
MANIFOLD PIPE PLUG
Fig. 19- Burner Assembly
Measure Manifold Pressure (Propane Units) The main burner orifices on a propane gas unit are sized for
the unit rated input when the manifold pressure reading matches tire level specified in Table 4.
Proceed as follows to adjust gas input on a propane gas unit:
1. Turn off gas to unit.
2. Remove pipe plug on manifold (see Fig. 19), then con nect manometer at this point.
3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw on
gas valve.
5. Adjust regulator adjustment screw to the correct mani fold pressure, as specified in Table 4. Turn adjusting
screw clockwise to increase manifold pressure, or turn adjusting screw counterclockwise to decrease manifold
pressure.
6. Replace cover screw.
7. Turn offgas to unit. Remove manometer fl'om pressure
tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks.
D. Check Burner Flame
With burner access panel removed, observe tire unit heating operation. Watch the burner flames to see if they are light
blue and soft in appearance, and that the flames are approxi- mately tire same for each burner. Propane will have blue flame
with yellow tips. See Fig. 20. Refer to Maintenance section for" information on burner removal.
E. Airflow and Temperature Rise
The heating section for" each size unit is designed and ap proved for heating operation within the temperature-rise range
stamped on the unit rating plate. Table 5 shows the approved temperature rise range for each
heating input, and the air delivery cfln at various tempera ture rises. The heating operation airflow must produce a tem-
perature rise that falls within the approved range. Refer" to Evaporator Airflow and Airflow Adjustments section
on page 24 to adjust heating airflow when required.
--18--
Table 5 -- Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input
HEATING TEMPERATURE RISE °F
INPUT (Btuh) 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
40,000 1389 1111 926 794 694 617 556 ........
56,000 2083 1667 1389 1190 1042 926 833 758 .......
80,000 2778 2222 1852 1587 1389 1235 1111 1010 926 855 794 ....
95,000 3472 2778 2315 1984 1736 1543 1389 1263 1157 1068 992 926 868 -- -- 120,000 4167 3333 2778 2381 2083 !852 1667 1515 1389 1282 1190 1111 1042 980 928 136,000 5037 4029 3358 2878 25!8 2238 20!4 1831 1679 1549 1439 1343 !259 1185 !119
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.
P
BURNERFLAME
°°
Fig. 20 -- Monoport Burners
F. Heating Sequence of Operation See Fig. 21-23 and unit wiring label.
On a call for heating, terminal "W" of the thermostat is en- ergized, starting the induced draft motor. When the hall
effect sensor on the induced draft motor senses that it has reached the required speed, the burner sequence begins. This
flmction is performed by the integrated gas control (IGC). The evaporator-fan motor is energized 45 seconds after flame is
established. When the thermostat is satisfied and "W" is deen ergized, tire burners stop firing and the evaporator fan motor
shuts off after" a 45 second time off delay. A LED (light-emitting diode) indicator is provided on the con-
trol board to monitor operation. The control board is located by removing the burner access panel. During normal opera tion, the LED is continuously on. See Table 6 for error codes.
Table 6 -- LED Indications
ERROR CODE LED INDICATION
Normal Operation On Hardware Failure Off
Fan On/Off Delay Modified 1 Flash Limit Switch Fault 2 Flashes
Flame Sense Fault 3 Flashes Four Consecutive Limit Switch Faults 4 Flashes
Ignition Lockout Fault 5 Flashes Induced-Draft Motor Fault 8 Flashes
RolIout Switch Fault 7 Flashes
Internal Control Fault 8 Flashes
NOTES:
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will be displayed in numerical sequence.
3. This chart is on the wiring diagram located inside the burner access panel.
G. Limit Switches
Normally-closed limit switch (LS) completes the control cir- cuit through the thermostat R circuit. Should the leaving-air
temperature rise above the maximum allowable tempera- ture, the limit switch opens and the R control circuit "breaks."
Any interruption in the R control circuit instantly closes the gas valve and stops gas flow to the burners and pilot. The
blower motor continues to run until LS resets. When the air temperature at the limit switch drops to the
low-temperature setting of the limit switch, the switch closes and completes tire R control circuit. The electric-spark igni
tion system cycles and the unit returns to normal heating operation.
H. Auxiliary Limit Switch -- Rollout
The function of the switch is to close the main gas valve in the event of flame rollout. The switch is located above the
main burners. When the temperature at the auxiliary switch reaches the maximum allowable temperatm'e, the R control
circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and in
duced draft motor continue to run tmtil switch is reset.
--19--
III. START UP COOLING SECTION AND MAKE ADJUSTMENTS
A superheat charging label is attached to the inside of the compressor access door. The label includes a "Superheat Charg-
ing Table" and a "Required Suction-Tube (F) Temperature" chart.
An accurate superheat, thermocouple, or thermistor type ther monmter, a sling psychrometer, and a gage manifold are re
quired when using the superheat charging method for evalu ating the unit charge. Do not u,se me['c'rHy or small Hial-(ype
themlome_ers bec'ouse they ore not oclequa_e _bz"this _ype of
measzmemenb
A. Checking Cooling Control Operation
Start and check the unit for" proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF posL tion. Observe that blower motor starts when FAN switch
is placed in ON position and shuts down when FAN switch is placed in AUTO, position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO. position. Set cooling control below room tem-
perature. Obsexwe that compressor, condenser fan, and evaporator blower motors start. Observe that cooling
cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for"30 seconds.
3. When using an auto. changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions.
Observe that unit operates in heating mode when tern perature control is set to "call for heating" (above room
temperature) and operates in cooling mode when tem- perature control is set to "call for" cooling" (below room
temperature).
IMPORTANT: Three phase, scroll compressor units (sizes 048,060) are direction-oriented. These units must be checked to ensure proper compressor 3-phase power lead orientation.
If not corrected within 5 minutes, the internal protector will shut off the compressor. The 3 phase power leads to the unit
must be reversed to correct rotation. When turning back
wards, scroll compressors emit elevated noise levels, and the
difference between compressor suction and discharge pres- sures may be dramatically lower than normal.
B. Checking and Adjustment Refrigerant Charge
The refrigerant system is fully charged with R-22 refriger- ant, tested, and factory sealed.
NOTE: Adjustment of the refl'igerant charge is not required unless the unit is suspected of not having the proper" R-22
charge.
Proceed as follows:
1. Remove caps fl'om low and high pressure service fittings.
2. Using hoses with valve core depressors, attach low- and high-pressure gage hoses to low- and high-pressure serw
ice fittings, respectively.
3. Start unit in cooling mode and let unit run until system
pressures stabilize.
4. Measure and record the following: a. Outdoor ambient air temperature (F db).
b. Evaporator inlet-air temperature (F wb). c. Suction tube temperature (F) at low side service
fitting.
d. Suction (low-side) pressure (psig).
5. Using "Superheat Charging Table," compare the out- door entering air temperature with indoor air tempera- rare to determine desired system operating superheat
temperature. See Tables 7A 7H.
6. Using "Required Suction-Tube (F) Temperature" table, compare desired superheat temperature with suction (lmw side) operating pressure (psig) to determine proper suction-
tube temperature. See Table 8.
7. Compare actual suction-tube temperature with proper suction-tube temperature. Using a tolerance of _+3° F, add refl'igerant if actual temperature is more than 3 ° F
higher than proper suction tube temperature, or re move refrigerant if actual temperature is more than
3° F lower than required suction-tube temperature.
NOTE: If the problem causing the inaccurate readings is a refl'igerant leak, refer to Check for" Refl'igerant Leaks section
on page 16.
2O
VOLT OPERATIONREVERSEREDANDGRN LEADSONTRANSFORMER.
\
COOLINGFANLOGIC
BR I
I I I
0 T T+30 6 6
ENERGIZED DE'ENERGIZED
HEATING FAN LOGIC
BR
I I I I
!
o 45 T T÷3O
W BR W BR
ENERGIZEDENERGIZEDI_'-Eh_R61ZEDDE-ENERGIZED
SINGLE STAGE HEAT _ 5Iit;LE STAGE
COOL THERMOSTAT ¢TYP)
RE_D RED_BRN i
I
)ISCONNEO COMPONENT
L
! --" I
Irnl
CAP I g 2
L
J_ I
_NATE
YEL BR I
I
c
24V
)TRAN
)
c
AWG
BR
C CAP
CH COMP CR EQUIP
FL FS
FU GND GVR
HS HV TRAN --
I
IDM IFM IGC
IP
LS
MGV
NEC
OFM
LEGEND
American Wire Gage PWR --
Btower ReIay QT -- Contactor RS --
Capacitor TRAN -- Crankcase Heater
Compressor Motor Combustion Relay
Equipment Fuse Link 4_ Flame Sensor
Fuse O Ground
Gas Valve Relay Hall Effect Sensor
High-Voltage Transformer Ignitor
Induced-Draft Motor Indoor-Fan Motor
Integrated Gas Control internal Protector Limit Switch
Main Gas Vatve National Electrical Code Outdoor-Fan Motor
Power
Quadruple Terminal
Rollout Switch
Transformer
Field Sptice
Terminal (Marked) Terminal (Unmarked) Splice
Splice (Marked)
Factory Wiring Field Control Wiring Field Power Wiring
Accessory or Optionat Wiring To Indicate Common Potential Onty, Not to Represent Wiring
NOTES:
1 If any of the original wire furnished must be replaced, it must be replaced
with type 90 C wire or its equivalent
2 Use copper conductors onty
Fig. 21 -- 208/230-1-60 Wiring Diagram, Units PYIP018-060
--2]--
MAXIMUM WIRE } ,_UP-I_,_Y----a_-,,--YEL
S,ZE2AWG -- U
EQUIP 6ND
230 VOLT OPERATION A5 SHOWN. FOR 20B
VOLT OPERATION REVERSE RED AND ORN
LEADSON TRANSFORMER.
CO(_..INOFAN LOGIC
BR I I ..... i
I I I
0 T T+30 G 6
ENERGIZED DE-ENERGIZED
HEATING FAN LOGIC
BR
I I I I
I
O 45 T T+30
W BR W BR
ENERGIZEDENERGIZEO_-ENEROIZED BE-ENERGIZED
r-
i i
FAN -- --
I I _ I
I R
" "3
If
SINGLE5TA_ ItEATg 5INGLESTAGE I
COOLTHERMOSTAT(TYP)
CONNON
RED
I
-- WHT'
-- GRN
-- RED
_ --YEL-
_ - BRN-
24V SPLICE
BOX
I COMPONENT
ARRANGEMENT
24v GAS SECTION
IGC
ALTERNA_
__BRN--
YEL BRN--
I BRN--
BRN--
LEGEND
AWG -- Amedcae Wire Gage PWR -- BR -- Blower Relay QT --
C -- Contactor RS -- CAP -- Capacitor TRAN --
CH -- Crankcase Heater COMP -- Compressor Motor _[[_
CR -- Combustion Relay
EQUIP -- Equipment FL -- Fuse Link <_ FS -- FIame Sensor
FU -- Fuse 0 GND -- Ground
GVR -- Gas Valve Relay HS -- Hail Effect Sensor
HV TRAN -- High-Voltage Transformer
I -- Ignitor
IDM -- Induced-Draft Motor IFM -- Indoor-Fan Motor
IGC -- Integrated Gas Control IP -- Internal Protector
LS -- Limit Switch MGV -- Main Gas Valve NEC -- National Electrical Code i
OFM -- Outdoor-Fan Motor
Power Quadruple Terminal
Roltout Switch Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice
Splice (Marked)
Factory Wiring Field Control Wiring Field Power Wiring
24V
TRAN
Accessory or Optional Wiring To Indicate Common Potential Only, Not to Represent Wiring
NOTES:
1 If any of the original wire furnished must be replaced, it must be replaced
with type 90 C wire or its equivalent
2 Use copper conductors only.
Fig. 22 -- 208/230-3-60 Wiring Diagram, Units PYIP030-060
--22--
L?_-_p
EQUIP GND
COOLING FAN LOGIC
BR I
I I I
0 T T+3O G G
ENERGIZED DE-ENERGIZED
HEATING FAN LOGIC
BR
l
i I I I
i
0 45 T T+3O
W BR W BR
ENERGIZEDENERGIZEDI_E-ENERGIZEOOE-ENERGIZED
BLK. BLK,_--- l
_---YELTL
BLK
LBLU
BLK,
BLK
(G.E.
,BLK
YED OFM
CAP2
BLI_ COMP
YEL
JGH (036 & 042 ONLY)
CAP
J2
--vIo _VIO--
f_L GVR
_,t1-11-.
I
I o
IFM
_LU--------7
3L_
R5
2LN I :
6RN-YEL--------_
NtN_
_P GROUNDED THRU STANDOFF
YEL BRN--W
t--BRN--d
i BRN--
IDM
BRN-- C
C
24V TRAN
?G
QT -- Quadruple Terminal RS -- Rollout Switch
TRAN -- Transformer
Field Splice
LEGEND
AWG -- American Wire Gage BR -- Blower Relay
C -- Contactor CAP -- Capacitor
CH -- Crankcase Heater
COMP -- Compressor Motor CR -- Combustion ReIay
EQUIP -- Equipment FS -- Flame Sensor
FU -- Fuse GND -- Ground
GVR -- Gas Valve Relay HS -- HalI Effect Sensor
HV TRAN -- High-VoItage Transformer 1 -- Ignitor
IDM -- Induced-Draft Motor IFM -- Indoor-Fan Motor
IGC -- Integrated Gas Controt LS -- Limit Switch
MGV -- Main Gas Valve NEC -- NationaI Electrical Code
OFM -- Outdoor-Fan Motor PWR -- Power
4_ TerminaI (Marked)
O Terminal (Unmarked)
Splice Splice (Marked)
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring
To Indicate Common PotentiaI Only, Not to Represent Wiring
NOTES:
1 If any of the original wire furnished must be replaced, it must be replaced
with type 90 C wire or its equivalent
2 Use copper conductors onty
Fig. 23 --460-3-60 Wiring Diagram, Units PYIP036-060
--23--
C.Evaporator Airflow and Airflow Adjustments
Table 5 shows the temperature rise at various airflow rates. Tables 9 and 10 show both heating and cooling airflows at
various external static pressures. Refer to these tables to de-
termine the airflow for the system being installed. See Table 11 for wet coil pressure drop.
NOTE: Be sure that all supply and return-air grilles are open, free from obstructions, and adjusted properly.
Airflow can be changed by changing the lead connections of the blower motor.
Unit PYIP two- or 3-speed motors (except size 030) are fac- tory wired for low speed operation. Unit PY1P is factory wired
for medium speed. For 208/230-v and A.O. Smith 460-v Blower Motors
The motor leads are color-coded as follows:
3 SPEED 2 SPEED
black = high speed black = high speed blue = medium speed red = low speed
red = low speed
To change the speed of the blower motor, remove the fan mo- tor speed leg lead fl'om the blower relay (BR). This wire is
attached to terminal BM for single-phase and 3-phase units. To change the speed, remove and replace with lead for de-
sired blower motor speed. In_sulare tire remowH leaH m avoicl
c'onract with c'hassis /raz'r_s.
For 460-v GE Motors The motor leads are color coded as follows:
3 SPEED 2 SPEED
black = high black = high blue = jumper blue = jumper orange = medium red = low red = low
To change the speed of the blower motor, remove fan motor speed lead from the blower relay (BR) and replace with the
lead for the desired blower motor speed. The motor speed lead is attached to terminal BM. [n.sul_r_ remov_ct leact end ro avoid
contact with c'ha.ssLs Darts. On 3-speed motors only, connect
orange lead to terminal BM of BR. To select high speed on 460 v GE motors, separate the black (female QC) fi'om the blue lead (male QC) and connect the black lead to the BR.
[n_sulare tire blue leact go avoiH contact with ar_y c'hasMs parr&
D. Cooling Sequence of Operation
With the room thermostat SYSTEM switch in the COOL po- sition and the FAN switch in the AUTO. position, the cooling
sequence of operation is as follows: When the room temperature rises to a point that is slightly
above the cooling control setting of the thermostat, the ther mostat completes the circuit between thermostat terminal R
to terminals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y)
and blower relay coil (BR) (through unit wire G) across the 24 v secondary of transformer (TRAN).
The normally-open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP)
to condenser (outdoor) fan motor (OFM). Both motors start instantly.
The set of normally-open contacts of energized relay BR close and complete the circuit through evaporator blower (indoor)
fan motor (IFM). The blower motor starts instantly. NOTE: Once the compressor has started and then has stopped,
it should not be started again until 5 minutes have elapsed. The cooling cycle remains "on" until the room temperature
drops to point that is slightly below the cooling control set ting of the room thermostat. At this point, the thermostat
"breaks" the circuit between thermostat terminal R to termb nals Y and G. These open circuits deenergize contactor coil C
and relay coil BR. The condenser and compressor motors stop. After a 30-second delay, the blower motor stops. The unit is
in a "standby" condition, waiting for the next "call for cool ing" fl'om the room thermostat.
24
TEMP (F)
OUTDOOR ENTERING
AIR 54
65 SPH 17.3 70 SPH 13.8
75 SPH 10.2 80 SPH 8.2
85 SPH 8.1 90 SPH *
95 SPH *
100 SPH * 105 SPH *
110 SPH * 115 SPH *
LEGEND
Ewb -- Entering Wet Bulb
Table 7A- Superheat Charging Table, PY1P018
INDOOR AIR -- CFM
600
Indoor Air -- Ewb (F)
56 58 60 62 64 66 68 70 72 74 76
!8.5 19.6 20.8 24.2 27.7 28.5 29.3 29.3 29.3 29.3 29.3 !4.9 16.1 !7.3 20.7 24.1 25.7 27.3 27.3 27.3 27.3 27.3
!1.4 12.5 !3.7 17.! 20.6 22.9 25.2 25.2 25.2 25.2 25.2
8.8 9.5 10.2 13.6 17.0 20.1 23.1 23.9 24.1 25.4 26.1
6.2 6.5 6.6 10.0 13.5 17.3 21.1 22.6 24.1 25.6 27.1 * * 5.0 8.1 11.4 15.2 19.0 20.5 22.0 23.5 25.0
* * * 6.2 9.4 13.2 17.0 18.5 20.0 21.5 23.0 * * * 7.3 1! .1 14.9 17.2 !9.5 21.7 24.0
* * * 5.3 9.1 12.9 15.9 18.9 21.9 24.9 * * * 6.7 10.8 13.8 16.8 19.8 22.8
* * * 8.8 1! .8 14.8 !7.8 20.8
*Do not attempt to charge system under these conditions -- refrigerant
slugging may occur.
SPH -- Superheat at Compressor (F)
TEMP (F)
OUTDOOR ENTERING
AIR 54
65 SPH 18.2 70 SPH 17.1
75 SPH 16.0 80 SPH 14.8
85 SPH 13.7 90 SPH 1! .1
95 SPH 8.5
100 SPH 7.3
105 SPH 6.2 110 SPH *
115 SPH *
LEGEND
Ewb -- Entering Wet Bulb
Table 7B -- Superheat Charging Table, PYIP024
INDOOR AIR -- CFM
800
Indoor Air -- Ewb (F)
56 58 60 62 64 66 68 70 72 74 76
!9.0 19.9 20.7 22.5 24.2 25.! 25.9 26.6 27.2 27.9 28.6 !7.6 18.1 !8.6 20.4 22.1 23.0 23.9 24.9 26.0 27.1 28.1
16.2 16.4 !6.6 18.3 20.1 21.0 2! .8 23.3 24.8 26.2 27.7
14.7 14.6 !4.5 16.3 18.0 19.7 2!.3 22.4 23.5 24.6 25.8 !3.3 12.9 !2.5 14.3 16.0 18.4 20.7 21.5 22.3 23.1 23.8
!0.9 10.7 !0.4 12.2 13.9 16.3 18.7 !9.9 21.0 22.2 23.4
8.4 8.4 8.4 10.1 11.9 14.3 16.6 18.2 !9.8 21.4 23.0
7.5 7.7 7.9 8.9 9.9 12.2 14.6 16.6 !8.6 20.6 22.6
6.6 6.9 7.3 7.6 7.8 10.2 12.5 14.9 17.3 19.7 22.1 * * 5.3 5.5 5.8 8.1 10.5 13.3 16.1 18.9 21.7
* * 6.1 8.4 1! .6 14.9 !8.1 21.3
*Do not attempt to charge system under these conditions -- refrigerant
slugging may occur.
SPH -- Superheat at Compressor (F)
TEMP (F)
OUTDOOR ENTERING
AIR 54
65 SPH 14.2 70 SPH 13.6 75 SPH 13.0
80 SPH 10.9 85 SPH 8.9
90 SPH 8.3 95 SPH 7.8
100 SPH 7.3
105 SPH 6.7 110 SPH
115 SPH
LEGEND
Ewb -- Entering Wet Bulb
Table 70 -- Superheat Charging Table, PYIP030
INDOOR AIR -- CFM
1000
Indoor Air -- Ewb (F)
56 58 60 62 64 65 68 70 72 74 76
!5.1 16.1 !7.1 19.2 2!.3 23.3 24.7 25.9 27.2 27.8 28.5 !4.1 14.6 !5.0 17.! 19.2 21.3 22.8 24.2 25.7 26.3 26.9 !3.0 13.0 !3.0 15.! 17.2 19.2 20.9 22.6 24.2 24.8 25.4
!1.0 11.0 !0.9 13.6 16.1 18.7 20.1 21.4 22.7 23.6 24.4
8.9 8.9 8.9 12.0 15.! 18.2 19.2 20.2 21.2 22.4 23.5
8.4 8.4 8.3 10.9 13.6 16.2 17.7 19.2 20.8 21.6 22.5
7.8 7.8 7.8 9.9 12.0 14.1 16.! 18.2 20.2 20.9 21.7
7.3 7.3 7.3 9.3 11.4 13.6 15.6 17.6 !9.7 20.2 20.7
6.7 6.7 6.7 8.8 10.9 13.0 15.0 17.1 !9.1 19.4 19.8
6.7 8.9 10.9 13.0 15.0 17.1 !8.0 18.9 * 6.8 8.9 10.9 13.0 15.0 16.5 !8.0
*Do not attempt to charge system under these conditions -- refrigerant
slugging may occur.
SPH -- Superheat at Compressor (F)
--25--
Table 7D -- Superheat Charging Table, PYIP036
INDOOR AIR -- CFM
1200
Indoor Air -- Ewb (F)
TEMP (F)
OUTDOOR ENTERING
AIR 54 56 58 60 62 64 66 68 70 72 74 76 65 SPH 8.4 8.4 8.4 8.4 12.5 16.7 18.7 20.7 22.0 23.4 24.8 26.1 70 SPH 5.0 5.0 5.0 5.0 9.0 13.! 15.9 18.6 20.0 21.3 22.7 24.0
75 SPH * * 5.4 9.6 13.! 16.6 17.9 19.3 20.6 22.0
80 SPH * * 6.0 10.3 14.5 15.9 17.3 !8.6 20.0 85 SPH * * * 7.5 12.5 13.9 !5.2 16.5 17.9
90 SPH * * * 5.4 10.4 12.5 !4.6 16.8 18.8 95 SPH * * * 8.4 11.3 14.1 17.0 19.8
100 SPH * * * 6.4 10.0 13.5 17.1 20.7
105 SPH .... 8.7 13.0 17.3 21.7
110 SPH .... 9.3 12.4 15.6 18.7
115 SPH .... 10.0 11.9 13.8 15.8
LEGEND *Do not attempt to charge system under these conditions -- refrigerant
Ewb -- Entering Wet Bulb slugging may occur.
SPH -- Superheat at Compressor (F)
Table 7E -- Superheat Charging Table, PYIP042
TEMP (F) INDOOR AIR -- CFM
OUTDOOR 1400 ENTERING Indoor Air -- Ewb (F)
AIR 54 56 58 60 62 64 66 68 70 72 74 76 65 SPH 11.O 1! .0 11 .O !4.0 17.0 20.0 22.0 24.0 26.0 26.0 27.7 28.6 70 SPH 7.5 7.5 7.5 !0.4 13.4 16.4 18.9 21.4 24.0 25.0 26.1 27.1
75 SPH * * 6.9 9.9 12.9 15.9 18.9 21.9 232 24.4 25.7 80 SPH * * 5.9 8.4 10.8 13.8 16.8 19.8 21.3 22.8 24.9
85 SPH * * 5.0 6.9 8.8 1! .8 !4.8 17.8 19.5 21.1 22.8
90 SPH * * 6.0 6.8 10.2 !3.7 17.3 18.6 20.0 2!.4 95 SPH * * * 5.0 8.7 !2.7 16.7 17.8 18.9 20.0
100 SPH * * * 6.5 10.5 14.6 16.4 !8.2 20.0
105 SPH .... 8.4 12.6 15.1 17.6 20.0
110 SPH .... 8.0 12.0 14.2 16.4 18.6
115 SPH .... 7.7 11.5 13.4 15.3 17.2
LEGEND *Do not attempt to charge system under these conditions -- refrigerant
Ewb -- Entering Wet Bulb slugging may occur.
SPH -- Superheat at Compressor (F)
Table 7F -- Superheat Charging Table, PYIP048 (Carrier Scroll Compressor)
TEMP (F) INDOOR AIR -- CFM
OUTDOOR 1600 ENTERING Indoor Air -- Ewb (F)
AIR 54 56 58 60 62 64 66 68 70 72 74 76
65 SPH 15.5 15.5 15.6 15.6 17.6 19.6 21.6 22.8 24.0 25.2 25.2 25.3 70 SPH 11.7 1!.8 11.8 1!.8 13.9 16.0 !8.0 20.1 22.2 24.3 24.3 24.3 75 SPH 8.0 8.0 8.0 8.0 10.2 12.3 !4.5 17.4 20.4 23.3 23.3 23.3
80 SPH 6.0 6.0 6.0 6.0 8.7 11.3 13.9 16.3 !8.6 20.9 21.5 22.0 85 SPH 7.2 10.3 13.4 15.1 !6.8 18.5 19.7 20.8
90 SPH 5.6 7.7 9.9 12.4 !5.0 17.6 18.7 19.8 95 SPH * 5.2 6.3 9.8 13.2 16.7 17.7 18.8
100 SPH * * 5.8 9.1 12.5 15.8 17.! 18.4 105 SPH * * 5.2 8.4 11.7 14.9 16.5 18.!
110 SPH * * 6.2 8.8 11.4 14.0 15.9 17.8 115 SPH * * 7.1 9.1 11.1 13.1 15.3 17.5
LEGEND
Ewb -- Entering Wet Bulb
SPH -- Superheat at Compressor (F)
*Do not attempt to charge system under these conditions -- refrigerant
slugging may occur.
--26--
Table 7G -- Superheat Charging Table, PYIP048 (Copeland Scroll Compressor)
INDOOR AIR -- CFM
1600
Indoor Air -- Ewb (F)
58 60 62 64 66 68 70 72 74 76
19.0 !9.0 21.7 24.3 26.0 27.7 27.9 28.2 28.4 28.8
15.4 !5.4 18.! 20.8 22.5 24.1 25.1 28.1 27.1 28.1
11.9 !1.9 14.6 17.2 18.9 20.6 22.3 24.0 25.8 27.5
8.4 8.4 11.0 13.7 15.4 17.0 19.5 22.0 24.5 27.0
5.0 5.0 7.5 10.! 11.8 13.5 16.7 20.0 23.2 28.4 * * 6.6 9.0 11.4 14.7 17.9 21.1 24.4
* * 6.2 9.4 12.6 15.9 !9.1 22.3 * * 7.3 10.6 13.8 !7.0 20.3
* * 5.3 8.5 !1.8 15.0 !8.2 * * 6.9 !1.2 15.5 !9.8
* * 5.3 10.6 !6.0 21.3
*Do not attempt to charge system under these conditions -- refrigerant
slugging may occur.
TEMP (F)
OUTDOOR ENTERING
AIR 54 56 65 SPH 19.0 !9.0 70 SPH 15.4 !5.4
75 SPH 1! .9 !1.9 80 SPH 8.4 8.4
85 SPH 5.0 5.0 90 SPH * *
95 SPH * *
100 SPH * * 105 SPH * *
110 SPH * * 115 SPH * *
LEGEND
Ewb -- Entering Wet Bulb
8PB -- Superheat at Compressor (F)
TEMP (F)
OUTDOOR ENTERING
AIR 54
65 SPH 20.1 70 SPH 16.5
75 SPH 13.0 80 SPH 10.9
85 SPH 8.9 90 SPH 6.9
95 SPH 5.0
100 SPH * 105 SPH *
110 SPH * 115 SPH *
LEGEND
Ewb -- Entering Wet Bulb
Table 7H -- Superheat Charging Table, PYIP060
INDOOR AIR -- CFM
1995
Indoor Air -- Ewb (F)
56 58 60 62 64 66 68 70 72 74 76
20.1 20.1 20.1 20.1 20.1 22.6 25.2 25.6 26.1 26.6 27.0
16.5 16.5 !6.5 17.3 18.0 20.6 23.1 24.0 24.8 25.6 26.5
13.0 13.0 !3.0 14.5 16.0 18.5 2!.1 22.3 23.5 24.7 25.9 !0.9 10.9 !0.9 12.4 13.9 16.5 19.0 20.6 22.2 23.8 25.4
8.9 8.9 8.9 10.4 11.9 14.4 17.0 18.9 20.9 22.9 24.9
6.9 6.9 6.9 8.4 9.9 12.4 14.9 17.3 !9.6 22.0 24.3
5.0 5.0 5.0 6.3 7.8 10.3 12.9 15.6 !8.3 21.1 23.8 * * * 5.8 8.3 10.8 13.9 !7.0 20.1 23.2
* * * 6.2 8.8 12.3 15.7 19.2 22.7 * * * 6.7 10.6 14.4 18.3 22.2
* * * 8.9 13.1 !7.4 21.6
*Do not attempt to charge system under these conditions -- refrigerant
slugging may occur.
SPH -- Superheat at Compressor (F)
--27--
Table 8 -- Required Suction-Tube Temperature (F)*
SUPERHEAT SUCTION PRESSURE AT SERVICE PORT (psig)
TEMP (F) 61.6 64.2 67.1 70,0 73.0 76.0 79,2 82.4 86.7
0 35 37 39 4! 43 45 47 49 51
2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 5! 53 55 6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 6! 63 14 49 51 53 55 57 59 61 63 65 16 5! 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69
20 55 57 59 8! 83 65 67 89 71 22 57 59 61 83 85 67 69 71 73 24 59 61 63 85 87 69 7! 73 75 26 81 63 65 87 89 71 73 75 77 28 83 65 67 89 71 73 75 77 79 30 85 67 69 71 73 75 77 79 81 32 87 69 71 73 75 77 79 81 83 34 89 71 73 75 77 79 8! 83 85 36 7! 73 75 77 79 81 83 85 87 38 73 75 77 79 81 83 85 87 89 40 75 77 79 8! 83 85 87 89 91
*Temperature at su_ion service valve.
Table 9 -- Dry-Coil Air Delivery* -- Horizontal Discharge at 230 and 460 V -- Unit PYIP
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT MOTOR AIR EXTERNAL STATIC PRESSURE (in. wg) PY1 P SPEED DELIVERY 0,0 0.1 0.2 0.3 0.4 0.6 0.6 0,7 0.8 0.9 1.0
Watts 230 225 220 210 195 170 t _ _ _ t
Low
Cfm 760 745 725 695 640 540 t t t t t
018
Watts t t t t 270 235 200 t t t t
High Cfm t ? t ? 850 700 450 t ? t ?
Watts 275 275 273 269 260 257 249 ? ? ? ?
Low
Cfm 857 835 802 782 745 717 663 t ? _ ?
024, Med Watts 371 368 360 349 345 326 319 304 293 ? 030 Cfm 1079 1063 1027 996 978 919 865 783 726 _
Watts 5!4 493 476 460 443 425 40! 378 344 _
High Cfm !409 1383 1324 1282 1223 1!56 1068 984 857 _
Watts 473 447 427 418 395 367 346 337 323 _
Low
Cfm !253 1253 1172 1130 1047 946 865 829 768 _
Watts 5!9 500 478 459 439 410 377 357 340 _
036 Med
Cfm !414 1366 1287 1234 1162 !074 920 829 743 _
Watts 667 634 609 593 564 541 506 469 436 422
High Cfm 1734 1639 1563 1461 1370 !292 1157 960 829 743
Watts 678 635 604 580 550 520 493 455 430 _
Low
Cfm !540 15!5 1475 1430 1375 !280 1225 1128 1020 _
042
Watts t 820 785 750 700 680 649 612 570 _
High Cfm t 1825 1750 1685 1610 1525 1485 !355 12!5 _
Watts t t 854 786 744 706 64! 606 557 511
Low
Cfm t t 2026 1905 1830 1752 1603 !513 1367 1228
048
Watts t t _ 905 846 824 804 748 683 637
High Cfm t t _ 2025 1905 1830 1752 1603 1398 1228
Watts !104 !093 1072 1029 986 938 89! 830 769 733 697
Low
Cfm !876 1865 !840 1803 1765 1710 1641 !533 1425 !345 1264
Watts 1351 !295 1245 1197 1148 1096 1053 994 936 871 812
060 Med
Cfm 2249 2209 2157 2097 2036 1959 1882 !781 1679 1542 1405
Watts t t 1391 1343 1296 1247 1!91 !129 !067 1002 936
High Cfm t t 2299 2231 2152 2060 !975 1859 !746 1591 1441
*Air delivery values are without air filter and are for dry coil. See
Table 1! for wet coil pressure drop. Deduct field-supplied air filter pres-
sure drop and wet coil pressure drop to obtain external static pressure available for ducting.
tUnit air delivery is outside of operating range.
NOTE: Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil icing may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
--28--
Table 10 -- Dry-Coil Air Delivery* -- Downflow Discharge at 230 and 460 V -- Unit PYIP
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT MOTOR AIR EXTERNAL STATIC PRESSURE (in. wg) PYIP SPEED DELIVERY 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0,7 0.8 0.9 1.0
Watts t 295 251 223 201 176 149 !24 t t
Low
Cfm t 821 817 753 665 536 343 164 t t
018
Watts 401 376 346 322 294 272 250 229 219 t
High Cfm !334 1253 1128 996 816 658 461 246 167 t
Watts t 285 284 282 278 274 270 261 251 244 230
Low
Cfm t 798 76! 727 682 634 581 525 450 37! 304
024, Med Watts t 378 371 368 362 357 343 332 315 301 283 030 Cfm t !01! 982 948 906 858 771 703 597 492 387
Wafts t 520 51! 487 472 451 431 411 385 362 341
High Cfm t 1342 !309 1237 1181 1106 1007 892 745 610 471
Wafts t 460 439 423 398 379 349 322 297 270 246
Low
Cfm t !19! 1136 1081 !005 907 795 687 579 47! 349
Watt t 511 492 470 450 420 392 364 332 308 275
036 Med
Cfm t 1316 1244 !178 1104 1005 891 784 657 535 389
Watts _ 655 631 603 584 552 522 492 459 433 398
High Cfm ? !54! 1458 !367 1292 1178 1053 920 806 662 509
Wafts _ 637 612 587 560 526 493 455 t t t
Low
Cfm _ !500 1450 1405 1350 1290 1200 1105 t t t
042
Wafts _ 790 750 700 679 639 608 574 547 t t
High Cfm _ 1750 1675 !604 1509 1421 1323 1221 1094 t t
Watts _ 847 784 746 708 646 609 563 516 t t
Low
Cfm _ 1995 1901 !822 1730 1580 1477 1319 1!78 t t
048
Watts _ t 909 852 820 801 751 687 639 t t
High Cfm _ t 2018 !896 18!4 1729 1582 1380 1270 t t
Wafts _ 983 950 923 885 845 804 751 697 665 633
Low
Cfm _ 1838 1808 1755 1702 !628 1553 1446 1339 1257 1175
Wafts ? 1115 1083 !045 1006 964 921 872 823 783 742
060 Med
Cfm ? 2067 2023 !957 1891 !807 1723 1612 150! 1392 !282
Watts ? 1284 1201 1166 !131 !092 1053 1001 950 907 864
High Cfm ? 2167 2108 2038 1968 1882 1796 1676 1555 1437 !318
*Air delivery values are without air filter and are for dry coil. See
Table 11 for wet coil pressure drop. Deduct field-supplied air filter pressure drop and wet coiI pressure drop to obtain external static
pressure available for ducting.
1-Unit air delivery is outside of operating range.
NOTE: Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
Table 11 -- Wet Coil Pressure Drop
UNIT SIZE PYIP
018
024
030
036
042
O48
060
AIRFLOW(cfm)
600 700
8OO 900
600 700 8OO
900 900
1000 1200
1000 1200
1400 1600
1000 1200
1400 1600 1400
1600 1800
1700
1900 2100 2300
PRESSURE DROP (in. wg)
0.069
0.082
0.102
0.116
0.039
0.058
0.075
0.088
0.088
0.095
0.123
0.068
0.088
0.108
0.123
0.048
0.069
0.088
0.102
0.068
0.075
0.088
0.082
0.095
0.108
0.123
--29--
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic mainte-
nance must be performed on this equipment. This combina tion heating/cooling unit should be inspected at least once each
year by a qualified service person. To troubleshoot heating or
cooling of units, refer to tables at the back of the book. NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
The minimum maintenance requirements for"this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season fox"cleanliness. Clean when necessary.
3. Inspect blower motor and wheel fox"cleanliness and check lubrication each heating and cooling season. Clean and
lubricate (if required) when necessary. For" first heating season, inspect blower wheel bimonthly to determine
proper cleaning fi'equency.
4. Check electrical connections for tighmess and controls fox"proper operation each heating and cooling season.
Service when necessary.
5. Check and inspect heating section before each heating season. Clean and adjust when necessm T.
6, Check flue hood screen and remove any obstructions if
necessary.
7. Check vent screen and clean if necessary.
I. AIR FILTER
Inspect air filter(s) at least once each month and replace
(throwaway type) or clean (cleanable type) at least twice dur
ing each heating and cooling season or whenever the filter(s) becomes clogged with dust and lint.
II. UNIT TOP REMOVAL NOTE: When performing maintenance or service procedures
that require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top re-
moval, including: inspection of the heat exchanger area, coil inspection and cleaning, and condensate drain pan inspec
tion and cleaning. Only qualified service personnel should perform mainte-
nance and service procedures that require unit top removal. Refer to the following top removal procedures:
1. Turn off gas supply, then turn off electric power to unit.
2. Remove all screws that secure unit top, including screws around 4 sides and those on top that screw into internal
divider panels. Save all screws.
3. Lift top fi'om unit carefully. Set top on edge.
4. Carefully replace and secure unit top to unit, using screws removed in Step 2, when maintenance and/or service pro
cedures are completed. (Be sure to use original screws that have rubber washers to seal out water when secur
ing top to internal divider panels.)
III. EVAPORATOR BLOWER AND MOTOR NOTE: Motors without oilers are prelubricated. Do not at-
tempt to lubricate these motors. For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and motor annually.
Lubricate the motor every 5 years if the motor is used inter mittently (thermostat FAN switch in AUTO. position), or ev
eW 2 years if the motor is used continuously (thermostat FAN switch in ON position).
To clean and lubricate the blower motor and wheel:
1. Remove and disassemble blower assembly as follows: a. Remove blower access door.
b. Disconnect motor lead fi'om blower relay (BR). Dis-
connect yellow lead fi'om terminal L2 of the contactor.
--30--
c. Remove blower assembly fl'om unit. Remove screws
securing blower to gas partition and slide assembly out. Be carefld not to teal" insulation in blower
compartment.
d. Ensure proper reassembly by marking blower wheel
and motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
relnove screws that secure ii-!otor inoun{ brackets to housing, and slide motor and motor mount out of
housing.
2. Lubricate motor as follows: a. Thoroughly clean all accumulations of dirt or grease
from motor housing.
b. Remove dust caps or plugs from oil ports located at
each end of motor.
c. Use a good grade of SAE 20 nondetergent motor oil
and put one teaspoon (3/,_ oz. or 16 to 25 drops) in each oil port.
d. Allow time for oil to be absorbed by each bearing, then
wipe excess oil fl'om motor housing.
e. Replace dust caps or plugs in oil ports.
3. Remove and clean blower wheel as follows: a. Ensure proper reassembly by marking wheel
orientation.
b. Lift wheel fl'om housing. When handling and/or clean-
ing blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with
a brush. Remove lint and/or dirt accumulations from
wheel and housing with vacuum cleaner, using soft
brush attachment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing. e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft fiats and not on round part of shaft.
f. Reinstall blower access door.
4. Restore electrical power, then gas supply to unit. Start unit and check for proper blower rotation and motor speeds
during heating and cooling cycles,
IV. FLUE GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the heat exchanger:
1. Remove the combustion blower wheel and motor assem bly according to directions in Combustion Air Blower sec
tion on this page.
2. Remove tile 3 screws holding the blower housing to the title collector box cover (see Fig. 24).
3. Remove the 12 screws holding the title collector box cover
(Fig. 24) to the heat exchanger assembly. Inspect the heat
exchangers.
4. Clean all surfaces as required using the wire brush.
FLUE COLLECTOR BOX
INDUCED DRAFT MOTOR MOUNTING PLATE
BLOWER HOUSING
BURNER RACK
MOUNTING SCREW
Fig. 24 -- Blower Housing and Flue Collector Box
V. COMBUSTION-AIR BLOWER
Clean periodically to assure proper airflow and heating effi- ciency. Inspect blower wheel every fall and periodically dur
ing heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning fl'equency.
To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is re
quired, remove motor and wheel as follows:
1. Remove burner access panel. (See Fig. 25.)
2. Remove the 7 screws that attach induced-draft motor mounting plate to blower housing. (See Fig. 24.)
3. Slide the motor and blower wheel assembly out of the
blower housing. (See Fig. 26.) Clean the blower wheel.
If additional cleaning is required, continue with Steps 4
and 5.
4. To remove blower, remove 2 setscrews. See Fig. 26.
5. To remove motor, remove 4 screws that hold blower hous- ing to mounting plate. Remove the motor cooling fan by removing one setscrew. Remove nuts that hold motor to
mounting plate.
6. To reinstall, reverse the procedure outlined above.
Vl. LIMIT SWITCH
Remove blower panel. Limit switch is located on the gas partition.
VII. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout system. Ignition module is located in the control box. Module
contains a selfdiagnostic LED. During servicing, refer to la- bel diagram for LED interpretation.
If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit, or turning selector switch
to OFF position at the thermostat.
--31--
ONkN_EOFTHU_PA_L
BURNER
""_""_ACCESS
PANEL
Fig. 25 -- Burner Access Panel
BLOWER HOUSING
2 SETSCREWS (HIDDEN)
Fig. 26 -- Removal of Motor and Blower Wheel
VIII. MAIN BURNERS
At the beginning of each heating season, inspect for deterio- ration or blockage due to corrosion or other causes. Observe
the main burner flames and adjust if necessary.
A. Removal of Gas Train
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Remove burner access panel. (See Fig. 25.)
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner rack to the basepan. (See Fig. 24.)
8. Slide the burner rack out of the unit. (See Fig. 24 and 27.)
9. To reinstall, reverse the procedure outlined above.
Fig. 27 -- Burner Rack Removed
IX. CONDENSER COIL, EVAPORATOR COIL, AND CONDEN- SATE DRAIN PAN
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year. Proper inspection and clean-
ing requires the removal of the unit top. See Unit Top Re moval section on page 30.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Re- move all obstructions, including weeds and shrubs, that in
terfere with the airflow through the condenser coil. Straighten bent fins with a fin comb. If coated with dirt or lint, clean the
coils with a vacuum cleaner, using the soft brush attach- ment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent and water solu tion. Rinse coils with clear water, using a garden hose. Be
careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from
inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to
flush all dirt and debris fl'om the unit base. Inspect the drain pan and condensate drain line when in-
specting the coils. Clean the drain pan and condensate drain by removing all foreign matter fi'om the pan. Flush the pan
and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is
restricted, clear" it with a "plumbers snake" or similar probe device. Ensure that the auxiliary drain port above the drain
tube is also clear.
--32--
X. CONDENSER FAN
1. Remove 2 screws at bottom and 2 screws along sides of condenser air intake grille and remove plastic grille.
2. Inspect the fan blades for cracks or bends.
3. If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft.
4. When replacing fan blade, position blade so that lead- ing edge is 1/z in. in front of fan orifice. See Fig. 18.
5. Ensure that setscrew engages the fiat area on the me tar shaft when tightening.
6. Replace grille.
XI. ELECTRICAL CONTROLS AND WIRING
Inspect and check the electrical controls and wiring annu ally. Be _szlr'ere turn off'the ga_s _supIrl_ and then tire electrical
power re tire zmfr.
Remove the control, blower, and compressor compartment ac- cess panels to locate all the electrical controls and wiring. Check
all electrical connections fox"tightness. Tighten all screw con nections. If any smoky or burned connections are noticed, dis-
assemble the connection, clean all the parts, restrip the wire end, and reassemble the connection properly and securel N
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete
heating cycle and one complete cooling cycle to ensure proper operation. If discrepancies are observed in either or both op-
erating cycles, or if a suspected malflmction has occurred, check each electrical component with the proper electrical instru
mentation. Refer to the unit wiring label when making these checkouts.
NOTE: Refer to the heating and/or cooling sequence of op eration in this publication as an aid in determining proper control operation.
XII. REFRIGERANT CIRCUIT
Inspect all refrigerant tubing connections and the unit base fox"oil accumulations annually. Detecting oil generally indi
cares a refl'igerant leak. If oil is detected or if low cooling performance is suspected,
leak-test all refrigerant tubing using an electronic leak- detector, halide torch, or liquid soap solution. If a refrigerant
leak is detected, refer to Check for Refl'igerant Leaks section on page 16.
If no refrigerant leaks are found and low cooling perfor- mance is suspected, refer to Checking and Adjusting Refrig-
erant Charge section on page 20.
XIII. GAS INPUT
The gas input does not require checking unless improper heat- ing performance is suspected. If a problem exists, refer to
Start Up section on page 16.
XIV. EVAPORATOR AIRFLOW
The heating and/or cooling airflow does not require checking unless improper performance is suspected. [ta problem ex-
isr_s, be sure that oH _sUi)lrlF- and retzmn-ah" gz'illes are open
and bee O'om ob.stfuctions, and that tire oh" i/ire1"ZscJean.When necessary, refer to Evaporator Airflow and Airflow Adjust
ments section on page 24 to check the system airflow.
XV, METERING DEVICE- ACUTROL TM DEVICE
This metering device is a fixed orifice and is located in the header to the evaporator coil.
XVI. LIQUID LINE STRAINER
The liquid line strainer (to protect metering device) is made of wire mesh and located in the liquid line on the inlet side of
the metering device.
33
TROUBLESHOOTING
Cooling
SYMPTOM CAUSE REMEDY
Compressor and Power failure Call power company. condenser fan will Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker.
not start.
Defective thermostat, contactor, transformer, Replace component. or control relay
Insufficient line voltage Determine cause and correct. Incorrect or faulty wiring Check wiring diagram and rewire correctly.
Thermostat setting too high Lower thermostat setting below room temperature.
Compressor will not Faulty wiring or loose connections in Check wiring and repair or replace. start but condenser compressor circuit
fan runs. Compressor motor burned out, seized, or Determine cause. Replace compressor.
internal overload open Defective run/start capacitor, overload, Determine cause and replace.
start relay One leg of 3-phase power dead
Three-phase scroll compressor (Unit sizes 048,060 only)
makes excessive noise, and there
may be a low pres- sure differential.
Compressor cycles (other than normally satisfying
thermostat).
Scroll compressor is rotating in the wrong direction
Replace fuse or reset circuit breaker. Determine cause.
Correct the direction of rotation by reversing the 3-phase power leads to the unit. Shut down unit to allow pressures to equalize.
Refrigerant overcharge or undercharge Recover refrigerant, evacuate system, and
recharge to capacities shown on nameplate.
Defective compressor Replace and determine cause.
Insufficient line voltage Determine cause and correct.
Blocked condenser Determine cause and correct. Defective run/start capacitor, overload Determine cause and replace.
or start relay Defective thermostat Replace thermostat.
Faulty condenser-fan motor or capacitor Replace. Restriction in refrigerant system Locate restriction and remove.
Compressor Dirty air filter Replace filter. operates Unit undersized for load Decrease load or increase unit size.
continuously. Thermostat set too low Reset thermostat.
Low refrigerant charge Locate leak, repair, and recharge. Leaking valves in compressor Replace compressor.
Air in system Recover refrigerant, evacuate system, and recharge.
Condenser coil dirty or restricted Clean coil or remove restriction. Excessive head Dirty air filter Replace filter. pressure. Dirty condenser coil Clean coil.
Refrigerant overcharged Recover excess refrigerant. Air in system Recover refrigerant, evacuate system, and recharge. Condenser air restricted or air short-cycling Determine cause and correct.
Head pressure too Low refrigerant charge Check for leaks, repair and recharge. low. Compressor valves leaking Replace compressor.
Restriction in liquid tube Remove restriction.
Excessive suction High heat load Check for source and eliminate. pressure. Compressor valves leaking Replace compressor.
Refrigerant overcharged Recover excess refrigerant.
Suction pressure Dirty air filter Replace filter. too low. Low refrigerant charge Check for leaks, repair and recharge.
Metering device or low side restricted Remove source of restriction.
Insufficient evaporator airflow increase air quantity. Check filter -- replace if
necessary. Temperature too low in conditioned area Reset thermostat. Outdoor ambient below 40 F install low-ambient kit.
Field-installed filter-drier restricted Replace.
--34--
SYMPTOM
Burners will not ignite.
Inadequate heating.
Poor flame characteristics.
Heating
CAUSE
Water in gas line
No power to furnace No 24-v power supply to control
circuit
Miswired or loose connections Burned-out heat anticipator in
thermostat
Broken thermostat wire Misaligned spark electrodes
No gas at main burners
Dirty air filter
Gas input to furnace too low
Unit undersized for application Restricted airflow
Blower speed too low
Limit switch cycles main burners
incomplete combustion results in:
Aldehyde odors, carbon monox-
ide, sooting flame, floating flame
REMEDY
Drain. install drip leg. Check power supply fuses, wiring, or circuit breaker.
Check transformer. NOTE: Some transformers have internal overcurrent protection that requires a cool-down period to reset.
Check all wiring and wirenut connections.
Replace thermostat.
Run continuity check. Replace wire if necessary.
Check flame ignition and sense electrode positioning. Adjust as necessary.
1. Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least
5 minutes for any gas to dissipate before attempt- ing to light unit.
2. Check gas valve. Clean or replace filter as necessary. Check gas pressure at manifold. Match with that on
unit nameplate.
Replace with proper unit or add additional unit. Clean or replace filter. Remove any restriction. Use faster speed tap if available, or install alternate
motor. Check rotation of blower, thermostat heat antic-
ipator settings, temperature rise of unit. Adjust as necessary.
1. Tighten all screws around burner compartment.
2. Cracked heat exchanger. Replace.
3. Unit overfired. Reduce input (change orifices or
adjust gas line or manifold pressure).
4. Check burner alignment.
--35--
LED Troubleshooting -- Error Code
SYMPTOM CAUSE REMEDY
Hardware failure. Loss of power to control module Check 5 amp fuse on IGC, power to unit, 24-v circuit (LED OFF) (IGC). breaker, and transformer. Units without a 24-v circuit
breaker have an internal overload in the 24-v trans- former. If the overload trips, allow 10 minutes for au-
tomatic reset.
Limit switch fault. High temperature limit switch is Check the operation of the indoor (evaporator) fan (LED 2 flashes) open. motor. Ensure that the supply-air temperature rise is
in accordance with the range on the unit nameplate.
Flame sense fault. The IGC sensed flame that Reset unit. If problem persists, replace control board. (LED 3 flashes) should not be present.
4 consecutive limit switch Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and
faults, that supply-air temperature rise agrees with range on
(LED 4 flashes) unit nameplate information. Ignition lockout. Unit unsuccessfully attempted Check ignitor and flame sensor electrode spacing,
(LED 5 flashes) ignition for 15 minutes, gaps, etc. Ensure that flame sense and ignition wires
are properly terminated. Verify that unit is obtaining proper amount of gas.
Induced-draft motor fault. IGC does not sense that induced- Check for proper voltage. If motor is operating, check (LED 6 flashes) draft motor is operating, the speed sensor plug/IGC Terminal J2 connection.
Proper connection: PiN 1 -- White, PIN 2 -- Red, PIN 3 -- Black.
Rollout switch fault. Rollout switch has opened. Rollout switch will automatically reset, but IGC will (LED 7 flashes) continue to lockout unit. Check gas valve operation.
Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect.
Internal control fault. Microprocessor has sensed an If error code is not cleared by resetting unit power, (LED 8 flashes) error in the software or hardware, replace the IGC.
IMPORTANT: Refer to Heating troubleshooting chart for additional troubleshooting analysis.
LEGEND
IGC -- Integrated Gas Unit Controller LED -- Light-Emitting Diode
--36--
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your kalowledge of the equipment discussed in this manual. Product progralns cover:
Unit Familiarization Maintenance
Installation Overview Operating Sequence
A large selection of product, theory, and skills programs is available. All pro m'ams include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
--37--
Copyright 1998 Payne Heating & Cooling CATALOG NO. 53PY-1P6
Loading...