Payne PH2PNB060000AA, PH2PNB030000AA, PH2PNB036000AA, PH2PNB042000AA Installation Guide

& Start-Up Instructions
PHI P, PH2P
Single-Packaged Heat Pump Units
NOTE: Read the entire instl_action manual before starting the installation
TABLE OF CONTENTS
SAFETY ( ONSIDERATIONS 2
INTRODUCTION .......................................................................................................................................................................................................... 2
RECEIVrNG AND INSTALLATION .......................................................................................................................................................................... 2
Check Equipment ..................................................................................................................................................................................................... 2
IDENTIFY UNIT ................................................................................................ 2
INSPECT SHIPMENT ............................................................................................ 3
Provide Lnit Support ................................................................................................. 3
ROOF CURB ...................................................................................................................................................................................................... 3
SLAB MOUNT ................................................................................................................................................................................................... 4
GROUND MOUNT ............................................................................................... 4
Provide Clearances ................................................................................................. 5
Rig and Place Unit ................................................................................................................................................................................................... 5
INSPE( TION ...................................................................................................................................................................................................... 5
INSTALLATION ................................................................................................................................................................................................ 5
Select and Install Ductwork ................................................................................................ 7
Provide fbr (ondensate Disposal ................................................................................... 9
Install Electrical Connections ....................................................................................... 11
HIGH-VOLTAGE ( ONNECTIONS ....................................................................................
PRE-START-L P ...................................................................................................... 17
START-UP ............................................................................................................... 18
(beck for Refi'igerant Leaks ........................................................................................ 18
Start-Up Adjustments .............................................................................................. 19
CHECKING (00LING AND HEATING
CONTROL OPERATION ........................................................................................... I9
REFRIGERANT CHARGE ........................................................................................... I9
NO CHARGE 19
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS 20 MAINTENANCE 21
Air Filter 22 Indoor blower and motor 22
OUTDOOR COIL, INDOOR (OIL, AND CONDENSATE DRAIN PAN 22
Outdoor fhn 23 Electrical controls and wiring 24
Refrigerant circuit 25
Indoor airflow ......................................................................................................................................................................................................... 25
Metering device ...................................................................................................................................................................................................... 25
Liquid line strainers ................................................................................................................................................................................................ 26
High Flow Valves .................................................................................................................................................................................................. 26
Time-delay relay 27 Loss of"charge switch 27
Check defiost them_ostat 27 Defi'ost Thermostat 27
Form: IM-PH1P-04 Cancels: tM-PHIP-03 Printed in U.S.A. 11-02 Catalog No. 53PH-1P7
TROUBLESHOOTING 27 START-UP ( HECKLIST 27
NOTE TO INSTALLER READ THESE INSTRU(TIONS (AREFULLY AND COMPLETELY befbre installing this unit. Also, make sure the Owner's Manual and Service Instl_/ctions are left with the unit after installation.
C99001
Fig. l--ModeJ PHIP/PH2P
SAFETY CONSIDERATIONS
Installation and servicing of air=conditioning equipment can be hazardous due to system pressure and electrical components Only trained and qualified personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance fkmctions of cleaning coils and filters. All other operations should be performed by tlained
service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for
all brazing operations.
Z_ WARNING: Improper installation, adjustment, aReration, service, maintenance, or use can cause explosion, fire,
electric shock, or other occurrences, which could cause serious injury or death or damage your property. ConsuR a qualified installer or service agency for information or assistance. The qualified installer or agency must use only factory-authorized
kits or accessories when modifying this product.
Recognize safety information. This is the safBty=alert symbolz_ x . When you see this symbol on the product or in instructions or manuals, be alert to the potential for personal iajury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. Danger identifies the most serious hazards, which will result in severe personal injury or death. Warning indicates a condition that could cause serious personal injury or death. Caution is used to identif)- unsafe
practices, which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result
in enhanced installation, reliability, or operation.
1. The power supply (volts, phase, and hertz) must cot_'espond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufEcient to handle toad imposed by this unit.
3. This installation must cont'orm with local building codes and with NEC (National Electrical Code). Refer to provincial and local plurnbing
or waste water codes and other applicable local codes.
Z_ WARNmNG: Before performing service or maintenance operations on system, turn off main power to unit. Turn off
accessory heater power switch if applicable. Electrical shock could cause severe injury or death.
INTRODUCTmON
The PH1P and PH2P heat pumps are fully self-contained and designed for outdoor installation (See Fig. 1). Standard units are shipped in a
horizontal=discharge configuration _br installation on a ground=level slab. Units can be converted to downflow (vertical) discharge configurations
fbr rooftop applications.
RECEBMmNG AND INSTALLATION
PROCEDURE I--CHECK EQUBPMENT
A. BDENTIFY UNIT
The unit model number and serial number are stamped on the unit identification plate Check this inJ:bm_ation against shipping papers
2
CORNER4 L_
EVAPORA/OR CO_L
TOP VIEW
IlJllJllJitllllI]lllt
i tlJtIIIIJltlIItlIIIItL
l .............
4020 _15831
J i
117¸7 [463]
883 _ _ ......
_s4B_ REAR VIEW
.... OPEN NG
-5505 .................
!983) [21 6T} [9 83]
_UCT
REQUIRED CLEARANCES TO COMBUS_BLE MATL.
10P O_ UNII .......................... 3556 [14 OOJ
DUCT SIDE OF UNiT ......................................... 508 1200]
SIDE OPPOSITE DUCTS ........................ 3556 [140O]
BOTTOM OF UNIT ..................................... IRT [050]
EIECTRIC HEAT PANEl...................................... 9144 [3NDD]
NEC. REQUIRE) CLEARANCES.
BETWEEN UNITS, POWER [NTRT SIDE ............... lORD8 [4200]
UNIT AND UNGROUNDED SURFACES. POWER ENTRY SIDE .......... 9140 [3600]
UNIT AND DLOC_ OR CONCREIE WALLS AND OTIER
GROUNDED SURFACES, POWER ENTRY S!DE .................... _ODD8 [4200]
91!
MULIMETERS /IN]
MIILIMETERS IIN]
[47 00]
t
i]4j iJJ-JJiiiJ IIJlJii
IIIII IIIIIIIIIH
I_QUIP_) CLEARANCE FOR OP_A_ON AND SERV_INC
EVAP COIL ACCESS S_DE .................. 9F4 O [3600]
POWER ENTRY SiDE ........................................ 9[40 [360D]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ......................................... 9F4 O [3600]
SIDE OPPOSITE DUCTS ..................................... 9140 [BROO]
DUCI PANEL .................... 304 B IIROOD
,MINIMUM DISTANCES:IF UNIT IS PIACED LESS THAN 3048 !I?DO] FROM WAIL
SYSTEM,THEN SYSTEM PERFORMANCE MAYBE COMPROMISED
MILLIMETERS EJN1
DIMENSIONS IN [] ARE }N }NCHES
....iiii i11iil....
lilllilillillill
\.
Z
_2;6 3
{48 281
FRONT VIEW
UNIT WEIGHT UNiT HEIGHT
UNIT
[3272] _DRAIN 0UT[E]
LEFT SIDE VIEW _90 [0 ?S] N PT
220 [087] DP
ELECTRICAL CHARACTERBSTICS IN. (MM)
Ib kg "A"
PH1P018 PH1P024
PH1P030 PH1P036 PH1P042
PH2P024
PH2P030
PH2P03$
208/230-1-80, 208/230-3-60, 460-3-80 208/230-1-60, 208/230-3-60, 480-3-60
208/230-1-80, 208/230-3-80, 480-3-80
208/230-1-60 208/230-1-60
208/230-I-60, 208/230-3-60
208/230-1-60
208/230-1-60, 208/230-3-60
283 19.5 (495.3) 289 19.7 (500.4) 287 19.5 (495.3)
291 19.5 (495.3) 323 19.7 (500.4) 299 19.0 (482.6) 320 19.7 (500.4) 328 19.7 (500.4)
128.4 37.02 (940.3)
131.1 39.02 (991.1)
130.2 39.02 (991.1)
132.0 37.02 (940.3)
146.5 37.02 (940.3)
135.6 41.02 (1041.9)
145.2 37.02 (940.3)
148.8 37.02 (940.3)
Units shown with Optional Field installed Wire Griles
Fig. 2--PHIP018-042/PN2P024-036 Unit Dimensions
B. INSPECT SHIPMENT
Inspect %r shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose fi'om its anchorage, have it examined by transportation inspectors before removal Fmavard claim papers directly to transportation company Manuf_mtmer is not responsible [br any
damage incun'ed in transit. Check all items against shipping list. Immediately notif) the nearest Payne Air Conditioning office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
PROCEDURE 2--PROVIDE UNIT SUPPORT
A. ROOF CURB
Install accesso W roof curb in accordance with instructions shipped with curb (See Fig 5) Install insulation, cant strips, roofing, and flashing_ Ductwork must be attached to curb
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal, Install gasketing material supplied with the roof curb,
Improperly applied gasketing also can result in air leaks and poor unit performance.
3
{1087]
BT_
[3¸43}
122 2 _4 B!l
RIGHT SIDE VIEW
CENTER OF GRAVITY
IN. (MM)
X
13.7 (348.0)
13.9 (353.1)
13.7 (348.0)
13.7 (348.0)
14.0 (355.6)
13.7 (348.0)
14.0 (355.6)
14.0 (355.6)
{o 2o}
C00137
¥
Z
15.0 (381.0)
15.0 (381.0)
15.0 (381.0)
13.0 (330.2)
13.0 (330.2)
16.0 (406.4)
17.6 (447.0)
16.5 (419.1)
.........lITIl 'ffTT
IIIIIlllIllllllIl
SUPPL? RETURN
7
DQCT DUCT
4020
[15631
OPENING OPENING
J
UNIT
PN1P048
PN1P060
PN2P042
PN2P048
PN2P0$0
t TOP VIEW
REtiRED CLEARAr_ES TO COMBJSTIBLE MATL
TOP OF UNIT ............................................. 355¸0 [1400]
DUCT SIDE OF UNIT .... S0 8 [200]
S!DE OPPOSITE OUCIS ..................................... 355¸0 [1400]
BOTTOM OF UNIT ........................... {27 (050]
ELECTRIC _EAT PANEL ...................................... 9[4¸4 [30001
NEC. REQUIRED CLEARANCE&
BETWEEN UNITS, POWER ENTRY SIDE ........... 10668 I4E00]
UNIT AND UNGROUNOED SURFACES, POWER ENTRY SlOE .......... 914¸0 [3600]
UNIT AND BLOCK OR CONCRETE WALLS AND OTNER
GROUNDED SURFACES, POWER ENTRY SIDE .................. 1066¸8 [4200]
1090 6
[42 94/
F£LD ENTRY_
SERVICE PORTS
h
]
MIllIMETERS [IN]
M_LLiMEEERS [IN]
{47 00]
.....T
I IItlllllIIIlIIIIll
z
__LL_____ ±
.......................................... 1{234 ............................................... _ 148 28]
[44 22] \_
LEFT SIDE VIEW ,,,o_o,.D, FRONT VIEW
\ORAIN OUTLET
_90 [075] NPT
_=LECTRBCAL CNARACTr=R_STICS
208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 208/230-3-60, 460-3-60 208/230-1-60, 206/230-3-60, 460-3-60
Units shown with Optional Field Installed Wire Grilles
Fig, 3--PNIP048-060/PHEP042-060 Unit Dimensions
12Z_ 3
UNIT WEIGNT
Ib kg
353 160.1 418 189.6
350 158.8 315 170.1 428 194.1
[4 631
88 5 {3 48}
[13 831 {13 6/] [13 8_]
REAR VIEW
REQUIRE_ CLEARANCE FOR OPERATION AND SERVICING
EVAP COIL ACCESS SIDE .................................. 9140 [36001
POWER ENTRY SIDE .............. 914 0 [36 001
{EXCEPT FOR NEC REOUIREMENIS}
UNIT TOP ............................. 9140 [36001
SIDE OPPOSITE DUCTS .................................... 9140 [3600]
OUCT PANEL .............................................. 3048 [1200],
,M]N!M_M D_STANBES;W UNI[ IS PLACED LESS IHAN 3048 [IRO0] FROM WALL
DIMENSIONS IN [1 ARE IN INCHES
STSTEM,TREN SYSTEM PERFORMANCE MAYBE COMPROMISED¸
445
POWER
222 [o 88] O{A ilOL[_
CONTROL EN#RY
•%
13 431 _222 _"
[48}]
...... 50
MILLIMETERS [IN1
{020}
RIGHT SIDE VIEW
UNIT HEIGHT
IN. {MM)
_A_
38.98 (990.2)
38.98 (990.2)
40.98 (1040.9)
40.98 (I040.9)
42.98 (1091.7)
19.9 (505.5)
19.9 (505.5)
19.9 (505.5)
19.9 (505.5)
19.9 (505.5)
CENTER OF GRAVITY
IN.(NM)
X
15.7 (398.8)
15.7 (398.8)
15.7 (398.8)
15.7 (398.8)
15.7 (398.8)
Y
C00136
Z
17.0 (431.8)
17.0 (431.8)
16.6 (421.6)
18.0 (457.2)
17.6 (447.0)
Curb should be level to within 1/4 in. (See Fig. 6). This isnecessary %r unit drain to _hnction properly. Refer to accessory- roof curb installation instructions fbr additional infbrmation as required
B. SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of" 4 in tl-gick with 2 in. above grade (See Fig. 7) The slab should extend approximately 2 in beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes.
C. GROUND MOUNT
The unit may be installed either on a slab or placed directly on the ground if total codes permit Place the unit on tevel ground prepared with gravel fbr condensate discharge, 4
1 2
Y
4 x 3
C00071
CORNER WEIGHTS (SMALL CABINET)
Unit 18 24 30 36 42
Total Weight 283 289 287 291 323 Corner Weight 1 65 67 66 67 83 Corner Weight 2 53 56 54 55 55
o
Corner Weight 3 61 62 62 63 78 Corner Weight 4 103 104 105 106 107
i
Corner Weiqht 1 63 63 64 -- -- Corner Weight 2 62 74 76 -- --
o
Corner Weight 3 56 56 58 -- -- Corner Weight 4 118 127 130 -- --
PROCEDURE 3--PROVIDE CLEARANCES
The required minimum service clearances are shown in Figs. 2 and 3. Adequate ventilation and outdoor air must be provided. The outdoor fire &aws air through the outdoor coil and discharges it through the top fun grille. Be sure that the fan discharge does not recirculate to the outdoor
coil. Do not locate the unit in either a comer or under an overhead obstruction. The minimum clearance under a partial overhang (such as a no*real house overhang) is 36 in. above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. For extended
overhangs, provide a minimum clearance of 48 in mMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to
compressor life. Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or
other comhustible materials. Slab-mounted units should be at least 4 in. above the highest expected water and runoff levels. Do not use unit if it has been under water.
PROCEDURE 4--RIG AND PLACE UNmT Rigging and handling of d_is equipment can be hazardous %r many reasons due to the installation location (roofs, elevated structures, etc.)
Only trained, qualified crane operators and ground support staff should handle and install this equipment When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other
safety precautions that might apply. Follow all applicable safety codes. Wear safety shoes and work gloves.
A. mNSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets and straps should be visually inspected for any damagQ evidence of wear, structural defbm_atiom or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets
or straps showing any kind of wear in these areas must not be used and should be discarded.
B. mNSTALLATION
1. Remove unit from shipping carton Leave top shipping skid on the malt as a spreader bar to prevent the rigging straps from damaging the unit If the wood skid is not available, use a spreader bar of sufficient length to protect unit f?om damage.
2 Position the lifting bracket assembly around the base of the unit. Be sure the strap does not twist 3 Place each of the 4 metal lifting brackets into the rigging holds in the composite pan
CORNER WEIGHTS {Small Cabinet_
Yota_ Weidht 999 320 32_ -- --
Fig. 4--Corner Weights
5
c_ Corner Weight 1 76 90
"O
:_ Corner Weight 3 96 114
o_ Yet_t W_ir_ht 350 375 428
oJ
!
m. Corner Weiaht 1 75 81 92 _ Corner Weight 2 49 52 60
:_ Corner Weight 3 95 102 116
in Pounds)
CORNER WEIGHTS (LARGE CABINET)
Unit 48 60
Total Weig ht 353 418
O
Corner Weight 2 49 58
Corner Weight 4 132 156
CORNER WEIGHTS (Lame Cabinet_
_tnit 47 4,_ 60
O
Corner Weight 4 131 140 160
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used
(/125 5mrr)
\ /
\
\\ /
R/A
\ _ Gasket around_,
\
Insulated Gasket around deck pan outer edge \
UNIT SIZE
PH1P018-042 PH2P024-036
PH1P048-060 PH2P042-060
NOTES: 1 Roof curb must be set up for unit being installed.
2 Seal strip must be applied, as required, to unit being installed. 3 Dimensions in ( ) are in millimeters
4 Roof curb is made of 16-gage steel.
5 Table lists only the dimensions, per part number, that have changed. 6 Attach ductwork to curb (flanges of duct rest on curb) 7 Insulated panels: i-in thick fiberglass 1 Ib density
8 Dimensions are in inches 9 When unit mounting screw is used (see Note A), a retainer bracket must be used as well This bracket must also be used when required by code for hurricane or seismic
conditions This bracket is available through Micrometl.
4. Thread lifting bracket strapping around bottom perimeter of unit as %ltows: a Open lever of tension buckle (ratchet type)
b. Feed strapping through tension buckle as shown in Fig 8
c Pull strapping through tension buckle unit taut. d. Snap lever down to lock strap in tension buckle To release strapping, squeeze safety latch, lift lever, and pull webbing outward.
5. Tighten the tension buckle until it is taut Lifting brackets must be secure in the rigging holds.
d. Attach fieldosupplied clevis or hook of sufficient strength to hole in the lifting bracket (See Fig. 9).
ODS CATALOG NUMBER
CPRFCURB006A00 CPRFCURB007A00 CPRFCURB098A00
CPRFCURB009A00
Fig. 5--Roof Curb Dimensions
A
IN. (MN)
8 (203)
14 (356)
8 (203)
14 (356)
d
B
IN. {MM)
11(279)
11(279) 16 3/16 (411) 16 3/16 (411)
duct
\\\
C
IN. (MM)
161/2 (419)
161/2 (419) 17 3/8 (441) 17 3/8 (441)
S/A
/2
C00076
D
IN. (NM)
28-3/4 (730)
28-3/4 (730) 40-1/4 (1022) 40-1/4 (1022)
2" I
±I
I- IIIII I lllll
I lllll I
L
Fig. 6--Unit Leveling Tolerances
EVAP.COIL
COND. COIL
Fig. 7--Slab Mounting Detail
C
MAXIMUM ALLOWABLE
DIFFERENCE (in)
A-B B-C A-C
1/4 1/4 1/4
C99065
C99096
HANDHOLD
/
/
/
HOOK _ ....
FEED m_I_
C99067
Fig. 8--Threading Belt
7 Attach the 2 safety straps directly to the clevis or hook at the 4 rigging brackets DO NOT attach the safety straps to the
lifting brackets (See Fig. 9)
g Position lifting point directly over the unit's center of gravity
9. Lift unit. When unit is directly over the roof curb, remove the 2 safety straps. Lower the equipment onto the roof curb.
PROCEDURE 5--SELECT AND BNSTALL DUCTWORK
The design and installation of the &/ct system must be in accordance with the standards of [l_e NFPA [br installation of non-residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply=air registers, and remm air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply- and return-air openings on the side of the unit. When designing and installing ¢lt/ctwork_ consider the following:
z_ WARNING: For vertical supply and return units, tools or parts could drop into ductwork and cause serious injury or
death. Install a 90 degree turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the
conditioned space. Units with electric heaters require 90 degree elbow in supply duct.
1. All units shonld have field=supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes %r filters are sho_xn in Tables 1 and 2
2. A_oid abla/pt duct size increases and reductions. Abrupt change in duct size adversdy affects air performance.
7
DETAIL A
SCALE 0250
TIGHTEN STRAPPING SECURBL:Y
WITH TENSION SUCKLE
INSTALL SAFETY STRAPS TO
RIGGING CLEVIS AT 4 RIGGING BRACKETS
/
SEE DETAIL A
UNiT A B
MAXIMUM WEIGHT
{INCLUDES SHIPPING SKID)
PLACE RIGGING BRACKET ASSEMBLY IN 4 RIGGING HOLES AND INSTALL TIE DOWN STRAP AROUND PERIMETER OF UNIT AND THROUGH SPACE IN BRACKET ASSEMBLY
C99075
Size Ib kg in. mm. in. mm.
PH1P018 305 138.4 19.5 495.3 16.75 425.5 PH1P024 311 141.1 18.5 469.9 16.75 425.5
PH1P030 309 140.2 19.5 495.3 17.50 444.5 PH1P036 313 142.0 19.5 495.3 17.75 459.9 PH1P042 345 156.4 19.5 495.3 17.75 450.9 PH1 P048 375 170.1 20.5 520.7 20.62 523.8
PH1P0$0 440 199.6 19.5 495.3 19.75 501.7 PH2P024 321 145.6 19.0 482.6 18.25 463.6 PH2P030 342 155.2 20.0 508 19.25 489 PH2P036 350 158.8 20.0 508 19.0 482.6
PH2P042 372 168.8 21.0 533.4 20.5 520.7 PN2P048 377 171.0 20.0 508 21.25 539.8 PN2P0g0 450 204.2 21.0 533.4 20.0 508.0
Fig. 9--Suggested Rigging
mNPORTANT: /se flexible connectors between ductwork and m_it to prevent tlansmission of vibration./se s_/itable gaskets to ensure weather
tight and airtight seal When electric heat is installe& use fireproof canvas (or similar heat resistant material) connector between ductwork and unit
discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in. from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum air quantity' %r proper electric heater operation is listed in Tables 3 and 4. Heater limit switches may trip at air quantities below those recommended.
4. Seal, insulate, and weatherproof all external ductworlc Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air ( onditioning
Contractors Association (AC(A) minimum installation standards for residential heating and air conditioning systems.
5. Secure all ducts to building stlucmre. Flash, weatherproo£ and vibration-isolate duct openings in wall or roof according to good construction
practices.
A, CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE UNITS
Z_ WARNING: Before performing service or maintenance operations on system, turn off main power to unit and install
lockout tag. Turn off accessory heater power switch if applicable. Electrical shock could cause serious injury or death.
1. Open all electrical disconnects and install lockout tag be%re starting any service work.
2. Remove side duct covers to access bottom return and supply knock outs.
NOTE: These panels are held in place with tabs similar to an electrical knockont.
3. Use a screw&iver and hammer to remove the panels in the bottom of the composite unit base
4. Ensure the side duct covers are in place to block off the horizontal air openings.
8
Fig.10--TypicalInstallation
NOTE:Avoidab_/ptductsizeincreasesandreductions,Abruptchangeinductsizeadveiselya_:_ctsairper%m_ance PROCEDURE6--PROVBDEFORCONDENSATEDISPOSAL NOTE:Ensurethatcondensate-waterdisposallllethodscomplywithlocalcodes,restrictions,andpractices.
C00139
Horizontal Duct Covers
C99030
Fig, 11--PH2P with Duct Covers On
The units dispose of condensate through a 3/4 in. NPT female fitting that exits on the compressor end of the unit Condensate water can be &ained directly onto the roof in toot'top installations (where permitted) or onto a gravel apron in ground level installations. Install a field=supplied
condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the &ain-pan condensate connection to prevent the pan l:i'om overflowing. Prime the a'ap with water. When using a gravel apron, make sure it slopes
away fi'om the unit. If the installation requires draining the condensate water away fi'om the unit. install a field=supplied 2=in. tIap at the condensate connection to
ensure proper drainage. (ondensate trap is available as an accessoE¢ or is field-supplied. Make sure that the outlet of the trap is at least 1 in. lower than the unit &ain-pan condensate connection to prevent the pan t'rom overflowing. Connect a drain trough using a mininmna of field=supplied 3/4
-in. PVC or field-supplied 3/4 -in. copper pipe at outlet end of the 2 =in. trap (See Fig. 12). Do not undersize the robe. Pitch the drain trough downward at a slope of at least 1 in. ever}' 10 it. of horizontal run. Be sure to check the &ain trough for leaks. Prime the tIap at the beginning
of the cooling season start-up.
1" (25ram) MIN.
TRAP
2" (50ram) MIN.
C99013
Fig. 12--Condensate Trap
9
Table l--Physical Data
UNIT SIZE PH1PO18 PH1PO24 PH1PO3O PH1P036 PH1PO42 PN1PO48 PH1POG0
NOMINAL CAPACITY (ton) 1-1/2 2 2-1/2 3 3-1/2 4 5
OPERATBNG WEBGBT (_b.) 283 289 287 291 323 353 418
COMPRESSOR QUANTITY 1
TYPE RECIPROCATING COMPRESSOR SCROLL COMPRESSOR
REFRIGERANT R-22
REFRIGERANT METERING DEVICE AccuRater@
Refrigerant {R-22) Quantity (_b.) 6.5 5.3 5.6 7.6 8.0 7.85 9.3
ORIFICE ID (in.) 0.053 0.061 0.068 0.078 0.078 0.088 0.093
ORBFIOE OD (in.) 0.040 0.035 (2) 0.042 (2) 0.046 (2) 0.052 (2) 0.057 (2) 0.061 (2)
OUTDOOR COBL
Rows... Fins/in.
Face Area (sq. ft.)
OUTDOOR FAN
Nomina_ Airflow (CFM) 22 22 22 22 22 22 22
Diameter
Motor HP (RPM)
INDOOR COiL
Rows... Fins/in.
Face Area (sq. ft.)
iNDOOR BLOWER
Nomina_ Airflow (CFM) 10X10 10X10 10X10 11X10 11X10 11X1O 11X10
Size (in.) 1/8 (1075) 1/4 (1075) 1/4 (1075) 1/2 (1075) 3/4 (t075) 3/4 (I075) 1 (1100)
Motor NP (RPM)
RETURN-AIR FBLTERS (in.) 20X20Xl 20X20X1 20X20X1 20X24X1 24X30X1 24X30Xt 24X30X1
throwaway
1...17 1...17 1...17 2._17 2._17 2._17 2._17
10.2 12.0 12.0 10.3 10.3 11.6 11.6
2400 2400 2400 2800 2400 3300 3300
1/8 (825) 1/8 (825) 1/8 (825) 1/4 (1100) 1/8 (825) 1/4 (I100) 1/4 (1100)
2._15 2._15 3...15 3._15 4...15 3...15 4...15
3.7 3.7 3.7 3.7 3.7 4.7 4.7
700 800 1000 1200 1250 1600 2000
Tabme 2--Physical Data
UNiT SIZE PN2P024 PN2P030 PH2P036 PH2P042 PN2P648 PN2P660
NOMINAL CAPACBTY (ton) 2 2-1/2 3 3-1/2 4 5
OPERATING WEIGHT (_b.) 299 320 328 350 375 428
COMPRESSOR QUANTITY
TYPE SCROLL COMPRESSOR
REFRIGERANT R-22
REFRIGERANT METERING DEVBCE AccuRater®
Refrigerant {R-22} Quantity (lb.) 5.1 6.4 7.0 10.8 10.1 12.3
ORBFICE ID (in,) 0.065 0.073 0.076 0.080 0.088 0.093
ORBFICE OD (in.) 0.037 (2) 0.043 (2) 0.040 (2) 0.052 (2) 0.057 (2) 0.063 (2)
OUTDOOR COIL
Rows... Fins/in.
Face Area (sq. ft.)
OUTDOOR FAN
Nominal Airflow (CFM) 22 22 22 22 22 22
Diameter
Motor BP (RPM}
INDOOR CO_L
Rows... Finstin.
Face Area (sq. ft.)
iNDOOR BLOWER
Nominal Airflow (CFM) 1OX1O 1OX1O 10XI0 11X10 11X1O 11X1O
Size (in.)
Motor HP (RPM) 1/4 (1075) 1/4 (1075) 1/2 (1075) 1/2 (1075) 1/2 (1075) 1 (1040)
RETURN-AIR FILTERS (in.) 20X2OX1 20X2OX1 20X24X1 24X30X1 24X30X1 24X30X1
throwaway
NOTE: Air filter pressure drop for non-standard filters must not exceed 008 in wg.
1._17 2...17 2._17 2._17 2._17 2...17
13.7 10.3 10.3 13.7 13.7 15.7
2350 2350 2800 2800 3300 3300
1/8 (825) 1/8 (825) 1/4 (1100) 1/8 (825) 1/4 (1100) 1/4 (1100)
3...15 3...15 4...15 4._15 4...15 4...15
3.7 3.7 3.7 4.7 4.7 5.7
800 1600 1200 1400 1450 1750
Table 3--Minimum Airflow for Reliable Electric Heater Operation (Cfm)
AIRFLOW(CFM)I 660 600 1000" 1206 I 1400 I 1600 I 20OO
The 030 size models must be run on medium or high speed when used in conjunctionwith 15 kw electric heat accessory
]0
Loading...
+ 22 hidden pages