Mnstallation
Mnstructions
PH1Z024-060
Packaged Heat
Pump Units
7-03
NOTE: Read the entire instrt/ction manual before starting the installation.
TABLE OF CONTENTS
SAFETY ( ONSIDERATIONS 2
INTRODUCTION 2
RECEIVrNG AND INSTALLATION .......................................................................................................................................................................... 6
Check Equipment ..................................................................................................................................................................................................... 6
IDENTIFY UNIT ................................................................................................. 6
INSPECT SHIPMENT ........................................................................................................................................................................................ 6
Provide Unit Support ................................................................................................................................................................................................ 6
SLAB MOL_T ................................................................................................................................................................................................... 6
GROL ND MOUNT ............................................................................................... 6
Provide ( learances ................................................................................................. 6
Place Unit ................................................................................................................................................................................................................. 6
Select and Install Ductwork ..................................................................................................................................................................................... 6
INSTALL FLANGES FOR DUCTWORK CONNECTIONS (PH1Z060 ONLY) .......................................................................................... 6
CONVERTING HORIZONTAL DISCHARGE UNITS TO DOVv_'FLOW (VERTICAL) DISCHARGE ........................ 7
Provide fbr (ondensate Disposal ..................................................................................... 7
Install Electrical Connections ......................................................................................... 9
HIGH-VOLTAGE CONNECTIONS .................................................................................... 9
ROUTING POWER LEADS INT() UNIT ................................................................................. 9
CONNECTING GROUND LEAD TO E.KIT GROUND ............................................................ l0
ROUTING CONTROL POWER WIRES .............................................................................. 10
ACCESSORY ELECTRIC HEAT WIRING ............................................................................ l0
SPE(IAL PRO(EDURES FOR 208-V OPERATION ................................................................... I1
PRE-START-L P .................................................................................................... 11
START-UP .............................................................................................................. 12
(heck fbr Refi'igerant Leaks .......................................................................................... 12
LOCATE AND REPAIR REFRIGERANT LEAKS AND (HARGE THE UNIT AS FOLLOWS: ............................. 12
Start=L p Cooling Section and Make Adjustments ........................................................................ 12
CHECKING (OOLING CONTROL OPERATION .................................................................... 12
COMPRESSOR ROTATION ........................................................................................ 13
Refrigerant ( harge .................................................................................................. I3
NO CHARGE .................................................................................................................................................................................................... 13
LOW CHARGE COOLING ............................................................................................................................................................................. 13
T() USE THE COOLING CHARGING CHART ........................................................................................................................................... 13
HEATING MODE CHARGE .......................................................................................................................................................................... 13
Indoor Airflow and Airflow Adjustments ............................................................................................................................................................. 13
FOR 208/230-V ................................................................................................................................................................................................. 14
FOR 460-V MOTORS 14
Lnit Contlols 15
HIGH-PRESSURE RELIEF VALVE .............................................................................................................................................................. 15
LOSS OF CHARGE SWIT(H 15
COMPRESSOR OVERLOAD 15
Sequence of Operation 15
FAN OPERATION 15
(00LING 15
HEAT PUMP HEATING 15
DEFROST 17
ELECTRIC RESISTANCE HEATING 17
Form: tM-PHIZ-02 Cancets: IM-PH1Z-01 Printed in U.S.A. Catalog No. 53PH-1Z7
MAINTENANCE 17
Air Filter 19
tnit Top Removal (Outdooro(oilSide) 19
[ndool Blowel and Motor 19
Outdoor (oil, Indoor (oil, and Condensate Drain Pan 20
Outdoor Fan .......................................................................................................... 21
Electrical Controls and Wiring ............................................................................................................................................................................... 21
Refrigerant Circuit .................................................................................................................................................................................................. 22
Indoor Airflow ........................................................................................................................................................................................................ 22
Metering Devices .................................................................................................................................................................................................... 22
Lubrication ................................................................................................................................................................................................................
Liquid Line Strainer ................................................................................................................................................................................................ 22
High Flow Valves ................................................................................................................................................................................................... 22
TROUBLESHOOTING ............................................................................................................................................................................................... 26
START-UP CHECKLIST ............................................................................................................................................................................................ 27
NOTE TO INSTALLE_Before installation, READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. Also, make sure the
User's Manual and Replacement Guide are left with the unit after installation.
C00155
Fig. 1--Unit PHIZ
SAFETY CONSIDERATIONS
h_stallation and servicing of airoconditioning equipment can be hazardous due to system pressure and electrical components Only trained and
qualified workers should install, repair, or service air-conditioning equipment
Untrained workers can peribnn basic maintenance fkmctions of cleaning coils and filters. All other operations should be performed by trained
service people. When working on air-conditioning equipment, pay attention to precautions in the literature, tags, and labels attached to the unit,
and other sai)ty precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth fbr unbrazing operations. Have fire extinguisher available for
all brazing operations.
z2x WARNmNG: Before performing service or maintenance operations on system, turn off main power to unit and install
lockout tag. Turn off accessory heater power switch if applicable. Electrical shock can cause serious injury or death.
Recognize sat)ty in%rmation. This is the sat_ty-alert symbol Z_. When you see this symbol in insm/ctions or manuals, be alert to the potential
fbr personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER
identities the most serious hazards which will resuh in severe personal injuo' or death. WARNING signifies a hazard which could result in personal
injury or death. CAUTION is used to identit_ unsafe practices which would result in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover n_inin_tnn requirements and conIbrm to existing national standards and safety codes. In some instances, these instructions
exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require
these instructions as a minimum for a safk installation.
BNTRODUGTmON
PH1Z heat pmnp units are fully self-contained and designed ibr outdoor installation (See Fig 1). As shown in Fig. 2°4, units are shipped in a
horizontalodischarge configuration fbr installation on a groundolevel slab. All units can be field-converted to downflow discharge configurations
for rooftop applications with a fieldosupplied plenum.
2
24_ 6
9 75]
('0_,1_
{OI -
P95'] 0 ......................... 408[ 6 06© ...................
REAR VIEW
..... 3S6 0 01A
1140}
DUCT OPENINGS
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT ......................................................................................... 0
DUCT SiDE OF UNIT ............................................................................. 0
SIDE OPPOSITE DUCTS ...................................................................... 0
BOTTOM OF UNIT ................................................................................. 0
NEC. REQUIRED CLEARANCES,
BETWEEN UNITS, POWER ENTRY SIDE .................................... 4200 11066 8I
UNITAND UNGROUNDED SURFACES, POWER ENTRY SIDE 3600 [914 0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 4200 11066 8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
CONDENSER COIL ACCESS SIDE .............................................. 30.00 [762 0]
POWER ENTRY SIDE ............................................................... 3000 [762 0]
(EXCEPT FOR NEC REQUIREMENTS)
U NIT TOP ...................................................................................... 48.00 [12192]
SIDE OPPOSITE DUCTS .............................................................. 3000 [762 0]
LEGEND
NEC - National Electrical Code
NOTES:
1 Clearances must be maintained to prevent recircuJation of air from outdoor-
fan discharge, with the exception of the condenser coil (3600 in [9140 mini A
removaNe fence or barricade requires no clearance.
2. Dimensions are in inches Dimensions irl I ] are in millimeters.
82
131 99J
wOO, ()F UN I
INCHES [mm}
INCHES [mini
INCHES [mini
I
LEFT SIDE VIEW
UNIT
PN1Z024
PN1Z030
BLC'_,[ R, COq 1!OI O'Z A1) / A_ ( O I
ACCESS P&NEL
FIELD ENTRY TO_
SERVICE PORTS _\
ELECTRICAL CNARACTERBSTICS
208/230-1-60
208/230-1-60,
208/230-3-60
Fig, 2--Unit Base Dimensions, PHIZ024o030
COMPRESSOR PANEL N
FRONT VIEW
\\\\\\
\\\\
UNIT WEIGHT
tb kg
232 106
254 116
26.772
[I.05403
I.D x 12.7 DEEP /
[1961]
RIGHT SIDE VIEW
CENTER OF GRAVITY IN. (MM)
X Y Z
14.0 (356) 19.0 (483) 12.0 (305)
14.0 (356) 19.0 (483) 12.0 (305)
635
[250]
C00156
3
29 0 _ 4080
Z222222222222ZZZZZZZZII_
241 6
CONDE 4SE_
(0{
.... o o
REAR VIEW
\
' 3560 )A
[4 o}
DUCT ©PES, NGS
REQUIRED CLEARANCETO DOMgUSTIBLE MATL.
TOP OF UNiT ......................................................................................... 0
DUCT StDE OF UNIT ............................................................................. 0
SIDE OPPOSITE DUCTS ...................................................................... 0
BOTTOM OF UNIT ................................................................................. O
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE .................................... 4200 I066 8]
UN T AND UNGROUNDED SURFACES, POWER ENTRY S DE ¸36¸00 9 40
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY S_DE......................... 42¸00 [1066 8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
CONDENSER COIL ACCESS SIDE .............................................. 3000 [762 0]
POWER ENTRY SIDE .................................................................... 3000 [762 0]
(EXCEPT FOR NBC REQUIREMENTS)
UNIT TOP ....................................................................................... 4800 [I 2192]
SIDE OPPOSITE DUCTS .............................................................. 3000 [762 0]
LEGEND
NEC - National Electrical Code
NOTE8:
1 Clearances must be maintained to prevent recircu[ation of air from outdoor-
fan discharge, with the exception of the condenser coil (3600 in [9140 mini A
removable fence or barricade requires no clearance
2 DimenRons are in inches Dimensions in [ ] are in millimeters
INCHES [mm]
INCHES [mrn]
INCHES [mini
i,
BLC,WER, CCNIROL BOX AND
E,_#PORAIOR COIL ACCESS PANEL
COMPRESSOR PANEL
LEFT SIDEVIEW FRONTVIEW _,o_o_
UNIT ELECTRICAL CHARACTERISTICS
PNlZ036 460-3-60 277 126 14.0 (356) 19.0 (483)
PNlZ042 460-3-60 295 134 14.0 (356) 19.0 (483)
PNlZ048 460-3-60 328 149 14.0 (356) 19.0 (483)
208/230-1-60, 208/230-3-60,
208/230_1-60, 208/230-3_60,
208/230_1-60, 208/230-3_60,
Fig. 3--Unit Base Dimensions, PBIZ036=048
\
..9
i
26 772 I D I 12 7 DEEP J [19 61] [250]
RIGHT SIDE VIEW
UNIT WEIGHT
Ib kg X Y
CENTER OF GRAVITY IN, (MM)
C00003
Z
15.0(381)
150 (381)
150 (381)
4
COND
1176
[463]
352.5
EIS.B8]
138.3
DIMENSIONS IN E] ARE IN INCHES
_3527
_352.8
[1389]
0 o
_537
[211]
REAR VIEW
12950
[5098]
BOTTOMOF UNIT
EVAP
[1389]
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT ......................................................................................... 0
DUCT SIDE OF UNIT ............................................................................ 0
SIDE OPPOSITE DUCTS ...................................................................... 0
BOTTOM OF UNIT ................................................................................. 0
NEC. REQUIRED CLEARANCES,
BETWEEN UNITS. POWER ENTRY SIDE .................................... 4200 [1066.8]
UNIT AND UNGROUNDED SURFACES. POWER ENTRY SIDE 3000 [914 O]
UNIT AND BLOCK OR CONCRETE W/ALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 4200 [1066 8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
706
[27 80]
CONDENSER COIL ACCESS SIDE .............................................. 3000 [762 0]
POWER ENTRY SIDE .................................................................. 3000 [762 O]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ...................................................................................... 4800 [1219 2]
SIDE OPPOSITE DUCTS .............................................................. 3000 [76201
r
889
[356]
LEGEND
NEC - National Electrical Code
NOTES:
I Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge, with the exception of the condenser coil (3600 in [9140 mm] A
removable fence or barricade requires no clearance
2 Dimensions are in inches Dimensions in [ ] are in millimeters
INCHES [mml
INCHES [mm}
INCHES [mm]
UNIT
PNIZ060
i
\\X
LEFT SIDE VIEW
ELECTRICAL CHARACTERBSTICS
208/230-1-60,208/230-3-60, 460-3-60 368 167 14.0 (356) 20.0 (508) 16.0 (406)
867.0
[B4.13]
8125
[BI99]
BOTTOMOF UNIT
_BLOWER, CONTROLBOXANDEVAP. COIL
ACCESSPANEL
FIELD NTRY TO
COMPRESSOR PANEL_
S RTS
\
o
z
/
_ " ? 1 "
FRONT VIEW
26772 I.D x 127 DEEr
[1OS4D] RIGHT SIDE VIEW
UNIT WEIGHT
tb kg
Fig. 4--Unit Base Dimensions, PHIZ060
44.5
DIA. DIA
E1.75]
751.8
E29.60
30.6
EI.2O] 1981
[O8B]
CENTER OF GRAVITY IN. (MM)
X Z
Y
E2161]
[1961]
254
[1OO]
C00158
5
RECEBVmNGANDINSTALLATION
PROCEDURE 1--CHECK EQUIPMENT
A. BDENTmFYUNmT
The unit model number and serial number are stamped on the unit identification plate. (heck this infbm_ation against shipping papers. -Veril}' that
unit voltage and amperage tisted on unit rating plate agree with power supplied tbr equipment.
B. BNSPECT SHPMENT
Inspect fbr shipping damage while unit is still on shipping pallet. It"unit appears to be damaged or is torn loose fi'om its securing points, have it
examined by transportation inspectors beibre removal. Fop.yard claim papers directly to transportation company. Manu_tcturer is not responsible
fbr any damage incurred in tlansit.
(beck all items against shipping tist. Immediately notify the nearest Payne Air Conditioning ofi[lce if"any item is missing
To prevent loss or damage, 1cave all parts in original packages until installation
PROCEDURE 2--PROVmDE UNiT SUPPORT
A, SLAB MOUNT
Place the unit on a rigid, level surplice, suitable to support the unit weight. A concrete pad or a suitable fibe*glass mounting pad is recommended
The flat su*_hce should extend approximately 2=in beyond the unit casing on the 2 sides The duct connection side and condensate &ain connection
sides should be flush with the edge of the flat surface.
A 6-in. wide gravel apron should be used around the flat surfitce to prevent airflow blockage by grass or shrubs. Do not secure the unit to the flat
sur_tce except where required by local codes.
The unit should be level to within 1/4 inch. This is necessary fbr the unit &ain to fimction properly.
B. GROUND MOUNT
7he unit may also be installed directly on the ground if local codes pem_it. Place unit on level gronnd prepared with gravel for condensate
discharge.
PROCEDURE a--PROVIDE CLEARANCES
The required minimum sma'ice clearances and clearances to combustibles are shown in Fig. 2-4. Adequate ventilation and outdoor coil air must
be provided.
The outdoor fire pulls air through the outdoor coil and discharges it through the fan on the top cover. Be sure that the _hn discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial
overhang (such as a normal house ovmhang) is 48 in. above the unit top. The maxin-mm horizontal extension of a partial overhang must not exceed
48 inches.
Do not place the unit whine water, ice, or snow fiom an overhang or roof will damage or flood the unit The unit may be installed on wood flooring
or on Class A, B, or ( roof cove*lug materials.
A CAUTION: Do not restrict outdoor con airflow. An air restriction at either the outdoor-air inlet or the fan discharge can
be harmful to compressor life.
PROCEDURE 4--PLACE UNBT
Lnit can be moved with the rigging holds provided in the unit base Refer to Table 1%r operating weights. Use extreme cazltinn tn prevent dare, age
_hes_ mo_,is_g the _mit. Uvit m_/st remai_ i_ a_ _lzn'ig,ht fln,sitio'n d_frmg ale mo_mg ope_'ation,s. The unit must be level with in 1/4" for proper
condensate &ainage; the ground-level pad must be level befbre setting the unit in place. When a field-[Sbricated support is used, be sure that the
support is level and that it properly supports the unit.
PROCEDURE 5--SELECT AND mNSTALL DUCTWORK
7he design and installation of the duct system must be in accordance with:
the standards of the NFPA (National Fire Protection Association) [br installation of nonresidence-type air conditioning and ventilating systems
NFPA90A or residence-type, NFPA90B: and/or local codes and residence=type, NFPA 90B
and/or local codes and ordinances
Select and size ductwork, supply=air registers and return-air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air
Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply° and returnoair openings on the side of the unit. See Fig. 2-4 _br connection sizes and locations. The
14=in. round duct collars (size 024-048 units) are shipped inside t!-_eunit attached to the indoor blower. They are field-installed and must be
removed t'rom the indoor cavity prior to start-up, even if they are not used for installation.
A. BNSTALL FLANGES FOR DUCTWORK CONNECTIONS (PHIZ060 ONLY)
The PH1Z060 units are shipped with _'langes which must be field=installed on the unit.
To install unit flanges:
1. Five pieces of flange are shipped on the return=air opening of the unit Remove the flanges fiom the shipping position (See Fig. 5). Screws
are field°supplied.
2. One piece of flange is used as it is shipped (stlaight) Bend the other 4 pieces at right angles
3. Install the stlaight flange on the right side of the return°air opening in holes provided. (See Fig 6). Flanges should stick out from unit to
allow for connection of dnctwork.
6
4 Install2 hando%m_ed flanges onto return air opening in holes provided to %m_ a rectangle aronnd the remm air opening
5 Install remaining 2 handoformed flanges around discharge air opening in holes provided
6. Ductwork can now be attached to flanges.
When designing and installing ductwork, consider the following:
L,_ CAUTION: When connecting ductwork to units, do not drii[ deeper than 3/4 inch in shaded area shown in Fig. 7 or coi[
may be damaged.
* All units should have field-supplied filters installed in the returnoair side of the unit. Recommended sizes %r filters are shown in Table 1.
Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air per_bm_ance.
mMPORTANT: Use flexible connectors between dnctwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure
weathertight and airtight seal. When electric heat is installed, use fire proof canvas (or similar heat resistant material) connector between ductwork
and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve)
must ectend 24 in. fi'om d_e unit discharge connection flange into the dt/ctwork.
* Size ductwork tbr cooling air quantity (cfm). The mininmm air quanti w for proper electric heater operation is listed in Table 2. Heater limit
switches may trip at air quantities below those recommended.
* Insulate and weatherproof all external dnctwork. Insulate and cover with a vapor barrier all ductwork passing through conditioned spaces.
Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association
(A(CA) minin-mm installation standards for residential heating and air conditioning systems.
* Secure all dt_cts to building structure. Flash, weatherproofS, and vibration-isolate duct openings in wall or roof according to good construction
practices.
Figure 8 shows a typical duct system with PH1Z unit installed.
FIVE PIECES OF DUCT
FLANGE ATTACHED
HERE FOR SHIPMENT
C00005
Fig. 5--Shipping Location of Duct Ftanges
(Size 060 Only)
B. CONVERTING HORIZONTAL DISCHARGE UNITS TO BOWNFLOW {VERTICAL) DISCHARGE
A WARNBNG: Before performing service or maintenance operations on system, turn off main power to unit and install
lockout tag. Turn off accessory heater power switch if applicabme. Emectrical shock can cause serious injury or death.
Lnits are dedicated side supply products. They are not convertible to vertical air supply A fieldosupplied plenum must be used to convert to vertical
air discharge.
PROCEDURE g--PROVIDE FOR CONDENSATE DISPOSAL
NOTE: Be sure that condensate-water disposal methods comply with local codes, restrictions, and practices.
Unit removes condensate through a 1 3id4oin. ID hole (using 3/4oin. OD piping or tubing) which is located at the end of the unit. See Fig. 2=4
for location of condensate connection.
Condensate water can be drained directly onto the roof in rooftop installations (where pei_aitted) or onto a gravel apron in groundotevel
installations. Install a fieldosupplied condensate tlap at end of condensate connection to ensure proper &ainage. Make sure that the outlet of the
trap is at least 1 in. lower dtan the &ain-pan condensate connection to prevent the pan fi'orn overflowing. Prime the trap with water. When using
a gravel apron, make sure it slopes away fi'om the unit.
7
HAND FORM
STRAIGHT PIECE
Fig. 6--gJanges Bnstalmed on PHIZ060 Units
Fig. 7--Area Not to Be DriJJed More Than 3/4°in.
C00006
C00007
If the installation requires draining the condensate water away fi'om the unit, install a 2°in trap using a 3/4-in. OD robing or pipe. (See Fig 9 and
10.) Make sure that the outlet of the trap is at least 1 in lower than d-_eunit &ain-pan condensate connection to prevent the pan fiom overflowing.
Prime the trap with water. Connect a drain robe using a n_inimum of 3/4-in. PVC, 3/4-in. CPVC, or 3/4-in. copper pipe (all field supplied). Do
not undersize the robe. Pitch the drain robe downward at a slope of at least 1 in. t'or every 10 t't of horizontal run. Be sure to check the drain tube
_br leaks. Prime trap at the beginning of the cooling season start-up. Allowable glues for condensate trap connection are: Standard ABS, (PVC,
or PVC cement.
8
Table I -- Physical Data
UNiT PHIZ 024 030 036 048 060
OPERATING WEBGNT (_bs) 232 254 277 328 368
COMPRESSOR TYPE
REFRIGERANT Charge (tb)
REFRBGERANT METERBNG DEVICE
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR-FAN MOTOR CFM
Nomina_ Rpm
Motor Np
Diameter (in.)
INDOOR COBL
Rows...Fins/in.
Face Area (sq ft)
INDOOR FAN MOTOR
B_ower Motor Size (in.)
Nominal Cfm
Rpm Range
Number of Speeds
Factory Speed Setting
Motor Np
CONNECTING DUCT SBZES
SupNy Air (in.)
Return Air (in.)
FIELD-SUPPLBED RETURN-AIR FILTERt
460-v motors are 2-speed or 3-speed
fRequired filter sizes shownare based onthe ARI (Air Conditioning and Refrigeration Institute) ratedairflow at avelocity of 300 ft/min for throwaway type or 450 ft/min for
high capacity type Recommended filters are 1-in thick.
PROCEDURE 7--BNSTALL ELECTRICAL CONNECTIONS
Throwaway (in.)
3.7 I 5.8 I 5.9 I 6.6 I 9.1 I 9.7
AcutroF M System
Copper Tubes, Aluminum Plate Fins
1...17 2...17 2...17 2...17
7.9 6.7 11.1 12.7
1800 2000
825 1100
1/8 1/4
20 20
2._15 3...15 4...15 4...15
3.1 3.1 4.4 4.9
10x8
8OO
550-1000
3
Low
1/4
24 x 24 24 x 24 24 x 24 24 x 24 24 x 30 24 x 30
10x8
1000
550-1000
3
Med
1/4
1._17 2...17
11.1 9.3
Pro _etter
2600 2600
1100 1100
1/4 1/4
20 20
Copper Tubes, Aluminum Plate Fins
3._15 3._15
4.0 4.0
Direct Drive
10x9
1200
800-1050
3
Low
1/2
Round
14
14
Scroll
R-22
042
295
10 x 9
1400
800-1050
3
Med
1/2
26OO
1100
1/4
2O
10x9
1600
1000-1100
2
Low
3/4
32OO
1100
1/2
2O
10 x 10
2000
950-1100
3
Low
1
Square
13.9 x 13.9
13.9 x 27.8
Z_ WARNING: The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of
persona[ injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground
in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC (Nationam
Electrical Code), ANSI (American National Standards mnstitute)/NFPA (latest edition) (in Canada, Canadian Electrical Code
CSA C22.1) and local electrical codes. Failure to adhere to this warning could result in serious injury or death.
z_ CAUTION: Failure to follow these precautions could result in damage to the unit being installed:
1. Make aH electrical connections in accordance with NEC ANSl!NFPA (matest edition) and Bocat electricam codes governing
such wiring. Bn Canada, aH electricam connections must be in accordance with CSA standard 022.1 Canadian Electrical
Code Part 1 and applicable Bocal codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-supplied electrica! disconnect switch and unit. DO NOT USE ALUMINUM
WIRE.
3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.
4. Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are run in same conduit as
high-voltage wires.
5. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On 3-phase units,
ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase
imbalance.
A, HGHoVOLTAGE CONNECTIONS
The unit must have a separate electlical service with a field-supplied, waterproof disconnect switch mounted at, or within sight fiom the uniL Refer
to the unit rating plate for maximum/i_seicircuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 3 for electrical data.
The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole. See Fig. 2-4.
Z_ CAUTION: Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect
warranty.
B. ROUTING POWER LEADS BNTO UNBT
Lse only copper wire between disconnect and enit The high-voltage leads shouM be in a conduit until they enter the unit; conduit te_]aination
at the unit must be watertight. Run the highovoltage leads through the hole on the contlol box side of the unit (see Fig. 11 for location). When
the leads are inside _he unit, run leads to the conhol box (Fig. 12). For single-phase units, connect leads to the black and yellow wires; for 3-phase
units, connect the leads to the black, yellow, and blue wires (see Fig. 13).
g