Payne PG9MAB024040, PG9MAB036060, PG9MAB036040, PG9MAB024060, PG9MAB048060 Installation Manual

...
Installation Manual
4-WAY MULTIPOISE FIXED-CAPACITY DUAL-VENT CONDENSING GAS FURNACE SIZES 040 THRU 140
As an ENERGY STAR® Partner, Payne Heating and Cooling has determined that this product meets the ENERGY STAR® guidelines for energy efficiency.
NOTE: Read the entire instruction manual before starting the installation. This symbol indicates a change since the last issue.
PG9MAB
Series A
INDEX
Page
SAFETY CONSIDERATIONS.....................................................................................................................................................................................2
CLEARANCES TO COMBUSTIBLES.......................................................................................................................................................................3
DIMENSIONAL DRAWING .......................................................................................................................................................................................4
CODES AND STANDARDS .......................................................................................................................................................................................6
INTRODUCTION..........................................................................................................................................................................................................8
APPLICATIONS ...........................................................................................................................................................................................................8
General......................................................................................................................................................................................................................8
Upflow Applications ................................................................................................................................................................................................9
Downflow Applications..........................................................................................................................................................................................10
Horizontal Left (Supply-Air Discharge) Applications..........................................................................................................................................12
Horizontal Right (Supply-Air Discharge) Applications........................................................................................................................................15
LOCATION .................................................................................................................................................................................................................17
General....................................................................................................................................................................................................................17
Furnace Location Relative to Cooling Equipment................................................................................................................................................18
Location with Respect to Combustion and Circulating Air Requirements..........................................................................................................18
Hazardous Locations..............................................................................................................................................................................................18
AIR FOR COMBUSTION AND VENTILATION....................................................................................................................................................20
INSTALLATION.........................................................................................................................................................................................................22
Leveling Legs (If Desired).....................................................................................................................................................................................22
Installation In Upflow or Downflow Applications ...............................................................................................................................................22
Installation In Horizontal Applications..................................................................................................................................................................23
Air Ducts ................................................................................................................................................................................................................23
General ..............................................................................................................................................................................................................23
Ductwork Acoustical Treatment.......................................................................................................................................................................23
Supply Air Connections....................................................................................................................................................................................25
Catalog No. IM-PG9MAB-01 Cancels: IM-PG9M-10 Printed in U.S.A. 8-05
Return Air Connections.....................................................................................................................................................................................25
Filter Arrangement ............................................................................................................................................................................................26
Bottom Closure Panel........................................................................................................................................................................................27
Gas Piping..........................................................................................................................................................................................................28
Electrical Connections............................................................................................................................................................................................28
115-v Wiring......................................................................................................................................................................................................29
24-v Wiring........................................................................................................................................................................................................31
Accessories ........................................................................................................................................................................................................31
Wiring Diagram.................................................................................................................................................................................................32
Removal of Existing Furnaces from Common Vent Systems..............................................................................................................................33
Combustion Air and Vent Pipe Systems ...............................................................................................................................................................33
Condensate Drain.........................................................................................................................................................................................................47
General....................................................................................................................................................................................................................47
Application..............................................................................................................................................................................................................47
Condensate Drain Protection..................................................................................................................................................................................48
START-UP, ADJUSTMENTS AND SAFETY CHECK...........................................................................................................................................48
General....................................................................................................................................................................................................................48
Prime Condensate Trap With Water......................................................................................................................................................................48
Purge Gas Lines......................................................................................................................................................................................................49
Sequence of Operation............................................................................................................................................................................................49
Heating Mode....................................................................................................................................................................................................49
Cooling Mode....................................................................................................................................................................................................50
Continuous Blower Mode .................................................................................................................................................................................50
Heat Pump Mode...............................................................................................................................................................................................50
Component Test.................................................................................................................................................................................................50
Adjustments.............................................................................................................................................................................................................51
Set Gas Input Rate ............................................................................................................................................................................................51
Set Temperature Rise........................................................................................................................................................................................58
Blower Off Delay (Heat Mode)........................................................................................................................................................................59
Set Thermostat Heat Anticipator ......................................................................................................................................................................59
Check Safety Controls.......................................................................................................................................................................................59
Check Primary Limit Control......................................................................................................................................................................60
Check Pressure Switch.................................................................................................................................................................................60
CHECKLIST................................................................................................................................................................................................................61
SAFETY CONSIDERATIONS
CAUTION: FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
WARNING: FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in electrical shock, fire, personal injury, or death. Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air
filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
—2—
This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 ft.
INSTALLATION
(0 - 2,135m). An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications. This furnace is for indoor installation in a building constructed on site. This furnace may be installed in a manufactured (mobile) home when stated on rating plate and using factory authorized kit.. This furnace may be installed on combustible flooring in alcove or closet at Minimum Inches Clearance To Combustible Construction as described below. This furnace requires a special venting system. Refer to the installation instructions for parts list and method of installation. This furnace is for use with schedule-40 PVC, PVC-DWV, CPVC, or ABS-DWV pipe, and must not be vented in common with other gas-fired appliances. Construction through which vent/air intake pipes may be installed is maximum 24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roofing materials).
Cette fournaise à air pulsé est équipée pour utilisation avec gaz naturel et altitudes comprises entre 0 - 3,050m (0 - 10,000 pi),excepté queles fournaises de 140 taille sont pour altitudes comprises entre 0 - 2,135m (0 - 7,000pi). Utiliser une trousse de conversion, fournie par le fabricant, pour passer au gaz propane ou pour certaines installations au gaz naturel. Cette fournaise à air pulsé est pour installation à l´intérieur dans un bâtiment construit sur place. Cette fournaise à air pulse peut être installée dans une maison préfabriquée (maison mobile) si prescrit par la plaque signalétique et si l' on utilise une trousse specifiée par le fabricant. Cette fournaise peut être installée sur un plancher combustible dans un enfoncement ou un placard en observant les Dégagement Minimum En Pouces Avec
Éléments De Construction Combustibles.
Cette fournaise nécessite un système d´évacuation spécial. La méthode d´installation et la liste des pièces nécessaires figurent dans les instructions d´installation. Cette fournaise doit s´utiliser avec la tuyauterie des nomenclatures 40 PVC, PVC-DWV, CPVC, ou ABS-DWV et elle ne peut pas être ventilée conjointment avec d´autres appareils à gaz. Épaisseur de la construction au travers de laquelle il est possible de faire passer les tuyaux d'aération (admission/évacuation): 24 po (600 mm) maximum, 3/4 po (19mm) minimum (y compris la toiture).
For upflow and downflow applications, furnace must be installed level, or pitched within 1/2" of level. For a horizontal application, the furnace must be pitched minimum 1/4" to maximum of 1/2" forward for proper drainage. See Installation Manual for IMPORTANT unit support details on horizontal applications.
Pour des applications de flux ascendant et descendant, la fournaise doit être installée de niveau ou inclinée à pas plus de 1/2" du niveau. Pour une application horizontale, la fournaise doit être inclinée entre minimum 1/4" et maximum 1/2" du niveau pour le drainage approprié. En cas d´installation en position horizontale, consulter les renseignements IMPORTANTS sur le support dans le manuel d´installation.
LEVEL (0") TO
1/2" MAX
UPFLOW OR DOWNFLOW
FRONT
MIN 1/4" TO 1/2" MAX
FRONT
HORIZONTAL
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
ALL POSITIONS:
Minimum front clearance for service 24 inches (610mm).
*
140 size furnaces require 1 inch back clearance to combustible materials.
DOWNFLOW POSITIONS:I
For installation on combustible floors only when installed on special base No. KGASB0201ALL, Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
HORIZONTAL POSITIONS::
Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket, and building joists, studs, or framing.
§
Clearance shown is for air inlet and air outlet ends. 120 and 140 size furnaces require 1 inch bottom clearance to combustible materials.
Ø
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS DE CONSTRUCTION COMBUSTIBLES
POUR TOUS LES POSITIONS:U
Dégagement avant minimum de 610mm (24 po) pour l´entretien.
*
Pour les fournaises de 140 taille, 1 po (25mm) dégagement des matériaux combustibles est
requis au-arriere.
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur le plancher combustible seulement quand on utilise la base spéciale, pièce nº KGASB0201ALL, l pièce nº KCAKC.
POUR LA POSITION HORIZONTALE:
Le contact n deuxcôtés de la chemise de la fournaise, et des solives, des montants ou de la charpente du bátiment. La distance indiquée concerne l
§
d
´
air.
Ø
Pour les fournaises de 120 et 140 taille, 1 po (25mm) dégagement des matériaux combusitbles est requis au-dessous.
´
ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de serpentin,
´
est permis qúentre les lignes formées par les intersections du dessus et des
´
extrémité du tuyau d´arrivée d´air et l´extrémité du tuyau de sortie
This furnace is approved for UPFLOW, DOWNFLOW and HORIZONTAL installations.
Cette fournaise est approuvée pour l´installation HORIZONTALE et la circulation d´air VERS LE HAUT et VERS LE BAS.
Clearance arrows do not change with furnace orientation.
0"
B
A
A
R
R
0"
§
Clearance in inches Dégagement (po).
C
K
I
E
R
E
E
D
S
I
S
E
T
O
C
1"
Les fléches de dégagement
ne change pas avec
l
générateur d´air chaud.
TOP/PLENUM
DESSUS/CHAMBRE D´AIR
E
C
E
A
S
N
I
R
A
U
N
F
R
T
U
N
O
FO
T
R
N
F
A
V
A
L
È
F
R
O
A
N
V
T
A
N
T
3"
BOTTOM
0"
Ø
DESSOUS
Vent clearance to combustibles 0".
0 (po) Dégagement
d´évent avec combustibles.
´
orientation de la
0"
E
D
S
I
S
E
T
O
C
S
E
R
N
V
I
T
R
C
E
T
I
E
328066-201 REV. B LIT TOP
§
E
*
N
24
MIN
A04110
Fig. 1—Clearances to Combustibles
These instructions cover the minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Wear safety glasses and work gloves. Have a fire extinguisher available during start-up and adjustment procedures and service calls.
CAUTION: CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand these signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
The PG9MAB Multipoise Condensing Gas-Fired Furnaces are CSA (formerly AGA and CGA) design-certified for natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A CSA listed gas conversion kit is required to convert furnace for use with propane gas.
See Fig. 1 for required clearances to combustibles.
—3—
A05103
"
1
8
"
16
"
16
13
5
"
8
5
7
39
1"
"
"
16
16
7
11
"
16
5
19"
"
22
4
OUTLET
1
"
16
26
15
"
2
26
1
28
A
AIRFLOW
"
16
9
13
13
"
16
/
D
"
16
/
TYP
2-IN. COMBUSTION-
TRAP LOCATION
CONDENSATE DRAIN
OUTLET
2-IN. DIA
1
GAS CONN
AIR CONN
(DOWNFLOW &
OR ALTERNATE
-IN. DIA GAS CONN
2
1
HORIZONTAL RIGHT)
8-IN. DIA
7
POWER CONN
2-IN. DIA
THERMOSTAT ENTRY
1
"
4
1
TYP
33
"
8
5
TYP
32
13
"
16
30
"
2
1
30
2-IN. VENT CONN
"
16
11
29
TYP
5
"
16
11
22
SIDE INLET
"
4
1
18
1
" TYP
4
22
"
16
3
24
(UPFLOW)
BOTTOM INLET
HANGING
CONDENSATE
DRAIN LOCATION
FOR HORIZONTAL
DIMPLE LOCATORS
"
16
/
11
INLET
E
"
16
/
11
-in. rectangle.
-in. rectangle.
/2
/4
1
1
x 19
x 23
/2
/2
x 12-in. rectangle.
1
1
/2
1
Dimensions (In.)
"
8
27
"
16
9
TYP
"
27
2
1
24
"
16
5
17
see flex duct manufacturer’s recommendations for equivalent diameters.
2. Minimum return-air opening at furnace:
literature for specific use of single side inlets. The use of both side inlets, a
b. For 1200 CFM–20-in. round or 14
c. For 1600 CFM–22-in. round or 14
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
a. For 800 CFM–16-in. round or 14
combination of 1 side and the bottom, or the bottom only will ensure adequate
return air openings for airflow requirements above 1800 CFM at 0.5” W.C. ESP.
Fig. 2—Dimensional Drawing
8-IN. DIA
7
POWER CONN
CONDENSATE
DRAIN TRAP
LOCATION
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL LEFT)
"
16
"
15
4
1
"
26
2
1
26
"
16
24
5
22
2-IN. COMBUSTION-
AIR CONN
2-IN. DIA
1
GAS CONN
2-IN. VENT CONN
8-IN. DIA
7
ACCESSORY
ENTRY
"
16
11
22
2-IN. DIA THERMOSTAT
1
(ALTERNATE
POWER ENTRY
UPFLOW)
SIDE INLET
"
2
1
4
TYP
"
16
7
TYP
CONDENSATE
DRAIN LOCATION
1
"
4
1
1
(UPFLOW)
" TYP
4
15
23
SIDE INLET
1"
9
" TYP
16
26
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
024040 17-1/2 15-7/8 16
036040 17-1/2 15-7/8 16
024060 17-1/2 15-7/8 16
036060 17-1/2 15-7/8 16
048060 17-1/2 15-7/8 16
036080 17-1/2 15-7/8 16
048080 17-1/2 15-7/8 16
060080 21 19-3/8 19-1/2
048100 21 19-3/8 19-1/2
060100 21 19-3/8 19-1/2
060120 24-1/2 22-7/8 23
UNIT SIZE A D E
060140 24-1/2 22-7/8 23
—4—
AIRFLOW
UPFLOW
HORIZONTAL
RIGHT
AIRFLOW
A93041
AIRFLOW
HORIZONTAL
LEFT
DOWNFLOW
AIRFLOW
Fig. 3—Multipoise Orientations
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5 or CK5, or when Coil Box Part No. KCAKC is used.
The PG9MAB 040 through 120 size units are CSA (formerly CGA and AGA) design-certified for use in manufactured (mobile) homes when factory accessory conversion kit is used. The 140 size unit is NOT design-certified for use in manufactured (mobile) homes. These furnaces are suitable for installation in a structure built on site or a manufactured building completed at final site. The design of this furnace line is NOT CSA design-certified for installation in recreation vehicles or outdoors.
This furnace is designed for continuous return-air minimum temperature of 60°F db or intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed 80°F db. Failure to follow these return-air limits may affect reliability of heat exchangers, motors and controls. (See Fig. 4.)
These furnaces are shipped with the drain and pressure tubes connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT, or HORIZONTAL LEFT (supply-air discharge direction) applications as shown in Fig. 3. See details in Applications section.
Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the Combustion Air and
Vent piping sections of these instructions. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all
connections as specified in the GAS PIPING section of these instructions. Always install the furnace to operate within the furnace’s intended rise range with a duct system which has an external static pressure within the
allowable range as specified in the SET TEMPERATURE RISE section of these instructions. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return
air shall also be handled by ducts sealed to the furnace casing and terminating outside the space containing the furnace. A gas-fired furnace for installation in a residential garage must be installed as specified in the Hazardous Locations section of these instructions. The furnace is not to be used for temporary heating of buildings or structures under construction unless the furnace installation and operation
complies with the first CAUTION in the LOCATION section of these instructions.
0
60
A05004
Fig. 4—Return-Air Temperature
—5—
This gas furnace may be used for construction heat provided that:
• The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
• The furnace is controlled by a thermostat. It may not be hot wiredto provide heat continuously to the structure without thermostatic control.
• Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
• The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
• The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
• The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
• The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
• After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
The furnace shall be installed so that the electrical components are protected by water. These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower
compartment.
Installer Packet includes:
Installation Manual Service Guide User’s Information Manual Warranty Certificate
Loose Parts Bag includes: Quantity
Pressure tube extension 1 Collector box or condensate trap extension tube 1 Inducer housing drain tube 1 1/2-in. CPVC street elbow 2 Drain tube coupling 1 Drain tube coupling grommet 1 Vent and combustion-air pipe support 2 Condensate trap hole filler plug 3 Vent and combustion-air intake hole filler plug 2 Combustion-air pipe perforated disk assembly 1
Vent Pipe Extension (ONLY supplied with some furnaces) 1
For accessory installation details, refer to accessory installation instructions.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
PROCEDURE 1—SAFETY
• US: National Fuel Gas Code (NFGC) NFPA 54-2002/ANSI Z223.1-2002 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC) CSA B149.1-05
PROCEDURE 2—GENERAL INSTALLATION
• US: NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada.
• A manufactured (Mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part
3280, or when this standard is not applicable, the Standard for Manufactured Home Installation (Manufactured Home Sites, Communities, and Set-Ups), ANSI/NCS A225.1, and/or CAN/CSA-Z240, MH Series Mobile Homes
PROCEDURE 3—COMBUSTION AND VENTILATION AIR
• US: Section 8.3 of the NFGC, Air for Combustion and Ventilation
• CANADA: Part 7 of the NSCNGPIC, Venting Systems and Air Supply for Appliances
PROCEDURE 4—DUCT SYSTEMS
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34.
—6—
BLOWER SHELF
CONDENSATE TRAP (INSIDE)
ALTERNATE DRAIN TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
UPFLOW APPLICATIONS
FURNACE DOOR
FIELD
DRAIN
CONN
EXTERNAL UPFLOW APPLICATIONS
SLOT FOR SCREW
HORIZONTAL
APPLICATION
(OPTIONAL)
1
1
2
3
4
WIRE TIE GUIDES (WHEN USED)
CONDENSATE TRAP
FURNACE
SIDE
7
4
8
1
26
4
1
1
2
FURNACE DOOR
FIELD
DRAIN
CONN
FURNACE SIDE
4
3
5
4
4
1
26
4
3
5
3
4
SIDE VIEW FRONT VIEW END VIEW FRONT VIEW
DOWNFLOW AND ALTERNATE
1
7
8
3
1
4
7
8
1
2
4
1
4 OD COLLECTOR BOX TO TRAP RELIEF PORT
1
2 OD INDUCER HOUSING DRAIN CONNECTION
5
8 OD COLLECTOR BOX DRAIN CONNECTION
SCREW HOLE FOR UPFLOW OR DOWN­FLOW APPLICATIONS (OPTIONAL)
1
2-IN. PVC OR CPVC
HORIZONTAL
APPLICATIONS
4
FRONT VIEW SIDE VIEW
A93026
Fig. 5—Condensate Trap
PROCEDURE 5—ACOUSTICAL LINING AND FIBROUS GLASS DUCT
• US and CANADA: current edition of SMACNA, NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
PROCEDURE 6—GAS PIPING AND GAS PIPE PRESSURE TESTING
• US: NFGC; chapters 5, 6, 7, and 12 and national plumbing codes
• CANADA: NSCNGPIC Part 3, 4, 5, A, B, E, and H. NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
PROCEDURE 7—ELECTRICAL CONNECTIONS
• US: National Electrical Code (NEC) ANSI/NFPA 70-2002
• CANADA: Canadian Electrical Code CSA C22.1
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components. Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE
CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
—7—
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
CONDENSATE TRAP
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE
TRAP
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
FIELD-INSTALLED
FACTORY-SUPPLIED
1
2-IN. CPVC STREET
ELBOWS (2) FOR
LEFT DRAIN OPTION
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (RIGHT
DRAIN OPTION)
Fig. 6—Factory-Shipped Upflow Tube Configuration
(Shown With Blower Access Panel Removed)
A00288
INDUCER
HOUSING
DRAIN TUBE
(VIOLET)
A00289
Fig. 7—Alternate Upflow Tube Configuration and
Trap Location
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
INTRODUCTION
The model PG9MAB 4-way multipoise, Gas-Fired, Category IV, direct-vent and non-direct vent, condensing furnace is available in model sizes ranging in input capacities of 40,000 to 138,000 Btuh.
CAUTION: MINOR PROPERTY DAMAGE
Failure to follow this caution may result in minor property damage. Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
PROCEDURE 1—GENERAL
Some assembly and modifications are required for furnaces installed in any of the 4 applications shown in Fig. 3. All drain and pressure tubes are connected as shown in Fig. 6. See appropriate application instructions for these procedures.
APPLICATIONS
—8—
PROCEDURE 2—UPFLOW APPLICATIONS
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned air is discharged upwards.
A. Condensate Trap Location (Factory-Shipped Orientation)
The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications. A factory-supplied tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate Trap Tubing (Factory-Shipped Orientation) section for drain tube extension details. (See Fig. 5.)
B. Condensate Trap Tubing (Factory-Shipped Orientation) NOTE: See Fig. 6 or tube routing label on main furnace door to confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes
These tubes should be factory attached to condensate trap and pressure switch ready for use in UPFLOW applications. These tubes can be identified by their connection location and also by a color label on each tube. These tubes are identified as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube
The condensate trap drain connection must be extended for field attachment by doing the following: a. Determine location of field drain connection. (See Fig. 2 or 6.)
NOTE: If internal filter is used, drain tube should be located to opposite side of casing from return duct attachment to assist in filter removal.
b. Remove and discard casing drain hole plug button from desired side. c. Install drain tube coupling grommet (factory-supplied in loose parts bag) in selected casing hole. d. Slide drain tube coupling (factory-supplied in loose parts bag) through grommet ensuring long end of coupling faces blower. e. Cement 2 factory-supplied 1/2-in. street CPVC elbows to the rigid drain tube connection on the condensate trap. (See Fig. 6.) These
elbows must be cemented together and cemented to condensate trap drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink and prevent draining.
f. Connect larger diameter drain tube and clamp (factory-supplied in loose parts bag) to condensate trap and clamp securely. g. Route tube to coupling and cut to appropriate length. h. Attach tube to coupling and clamp securely.
C. Condensate Trap Location (Alternate Upflow Orientation)
An alternate location for the condensate trap is the left-hand side of casing. (See Fig. 2 and 7.) NOTE: If the alternate left-hand side of casing location is used, the factory-connected drain and relief port tubes must be disconnected and
modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment. To relocate condensate trap to the left-hand side, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap
into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
D. Condensate Trap Tubing (Alternate Upflow Orientation) NOTE: See Fig. 7 or tube routing label on main furnace door to confirm location of these tubes.
1. Collector Box Drain Tube
Connect collector box drain tube (blue label) to condensate trap.
NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks from occurring.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap. b. Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain
connection to the condensate trap. c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
—9—
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
Fig. 8—Downflow Tube Configuration
(Left-Hand Trap Installation)
A00262
DRAIN TUBE COUPLING
Fig. 9—Downflow Tube Configuration
(Right-Hand Trap Installation)
CAP COLLECTOR BOX
DRAIN TUBE (BLUE) COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX EXTENSION TUBE
INDUCER HOUSING DRAIN TUBE (VIOLET)
CONDENSATE TRAP
COLLECTOR BOX EXTENSION DRAIN TUBE
A00296
3. Relief Port Tube a. Connect relief port tube (green label) to condensate trap. b. Extend this tube (if required) by splicing to small diameter tube (factory-supplied in loose parts bag). c. Determine appropriate length, cut, and connect tube.
E. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
F. Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door to check for proper connections. G. Upper Collector Box and Inducer Housing (Unused) Drain Connections
UPPER COLLECTOR BOX DRAIN CONNECTION
Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door to check for proper connections.
UPPER INDUCER HOUSING DRAIN CONNECTION
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door to check for proper connections. H. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
PROCEDURE 3—DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2, 8, or 9.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
—10—
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap
into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B. Condensate Trap Tubing NOTE: See Fig. 8 or 9 or tube routing label on main furnace door to check for proper connections.
1. Collector Box Drain Tube
a. Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label). b. Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to condensate trap. c. Connect LOWER collector box drain connection to condensate trap.
Condensate Trap Located on Left Side of Casing (1.) Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.
(2.) Clamp tube to prevent any condensate leakage. Condensate Trap Located on Right Side of Casing (1.) Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue and white striped label) which
was previously plugged.
(2.) Connect larger diameter drain tube (factory-supplied in loose parts bag) to drain tube coupling, extending collector box drain tube
for connection to condensate trap. (3.) Route extended collector box drain tube directly from collector box drain to condensate trap as shown in Fig. 9. (4.) Determine appropriate length and cut. (5.) Connect to condensate trap. (6.) Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap. c. Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed. d. Use inducer housing drain tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain
connection to the condensate trap.
e. Connect inducer housing drain connection to condensate trap.
Condensate Trap Located on Left Side of Casing (1.) Determine appropriate length and cut.
(2.) Connect tube to condensate trap. (3.) Clamp tube to prevent any condensate leakage.
Condensate Trap Located on Right Side of Casing (1.) Route inducer housing drain tube (violet label) directly from inducer housing to condensate trap as shown in Fig. 9.
(2.) Determine appropriate length and cut. (3.) Connect tube to condensate trap. (4.) Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection procedure.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
—11—
NOTE: See Fig. 8 or 9 or tube routing label on main furnace door to check for proper connections. Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to remaining small diameter tube (factory-supplied in loose parts bag).
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
PROCEDURE 4—HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE) APPLICATIONS
A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.
NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 10.) See Electrical Connection section for J-Box relocation.
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 10.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B. Condensate Trap Tubing NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.
1. Collector Box Drain Tube a. Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected
to condensate trap.
b. Connect large diameter drain tube and clamp (factory-supplied in loose parts bag) to drain tube coupling, extending collector box drain
tube. c. Route extended tube (blue label) to condensate trap and cut to appropriate length. d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap. b. Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain
connection to the condensate trap. c. Determine appropriate length, cut, and connect tube. d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was previously connected to the condensate trap by splicing to small diameter tube
(factory-supplied in loose parts bag). b. Route extended collector box pressure tube to relief port connection on the condensate trap. c. Determine appropriate length, cut, and connect tube.
—12—
PLUG
AUXILIARY "J" BOX
CAP
COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED)
CONDENSATE
TRAP
COLLECTOR
BOX EXTENSION
DRAIN TUBE
COLLECTOR BOX
EXTENSION TUBE
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
040, 060, AND 080 HEATING INPUT FURNACES
COLLECTOR BOX TUBE (GREEN)
INDUCER HOUSING DRAIN TUBE (VIOLET)
COLLECTOR BOX DRAIN TUBE (BLUE)
A00215
Fig. 10—Horizontal Left Tube Configuration
d. Clamp tube to prevent any condensate leakage.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
D. Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications.
NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections. Modify tube as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.
3. Route extended tube:
a. Behind inducer housing. b. Between blower shelf and inducer housing. c. Behind inducer motor bracket. d. Between inducer motor and pressure switch.
4. Determine appropriate length, cut, and reconnect tube to pressure switch connection labeled COLLECTOR BOX.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
F. Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 2 and 11 or 12.)
CAUTION:
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
—13—
MANUAL
SHUTOFF
GAS VALVE
COMBUSTION – AIR
SEDIMENT TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
INTAKE
3
5
4
CONDENSATE TRAP
VENT
30 MIN WORK AREA
DRAIN
A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
ACCESS OPENING FOR TRAP
Fig. 11—Attic Location and Working Platform for Direct Vent Applications (All Sizes)
A93031
COMBUSTION–AIR
GAS VALVE
MANUAL
SHUTOFF
INTAKE
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
A 3-IN. MINIMUM CLEARANCE TO COMBUSTION-AIR INTAKE IS REQUIRED.
3
5
4
SEDIMENT TRAP
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
CONDENSATE TRAP
VENT
30-IN. MIN WORK AREA
DRAIN
A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
ACCESS OPENING FOR TRAP
Fig. 12—Attic Location and Working Platform for Non-Direct Vent Applications (Sizes 040 through 120 Only)
A96184
—14—
CAP
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX TUBE (PINK)
AUXILARY “J” BOX RELOCATED HERE
CONDENSATE TRAP
A00214
Fig. 13—Horizontal Right Tube Configuration
NOTE: Combustion-air and vent pipes are restricted to a minimum length of 5 ft. (See Table 11.) NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive
condensate droplets from exiting the vent pipe. (See Fig. 11, 12, or 40.)
NOTE: The 140 Size unit may not be installed in non-direct vent applications. PROCEDURE 5—HORIZONTAL RIGHT (SUPPLY-AIR DISCHARGE) APPLICATIONS
A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.
CAUTION: MINOR PROPERTY DAMAGE
Failure to follow this caution may result in minor property damage. Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes. NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 13.) See Electrical Connection section
for J-Box relocation.
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 13.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death. Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap
into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B. Condensate Trap Tubing NOTE: See Fig. 13 or tube routing label on main furnace door to check for proper connections.
1. Collector Box Drain Tube
a. Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).
—15—
b. Install removed clamp and plug into UPPER collector box drain tube (blue label) which was previously connected to condensate trap. c. Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut. d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove factory-installed cap and clamp from LOWER inducer housing drain connection. b. Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap. c. Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed. d. Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain
connection to condensate trap. e. Determine appropriate length, cut, and connect tube to condensate trap. f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection procedure.
C. Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
D. Pressure Switch Tubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications.
NOTE: See Fig. 13 or tube routing label on main furnace door to check for proper connections. Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory-supplied in loose parts bag).
3. Route extended collector box pressure tube behind inducer motor bracket then between inducer motor and pressure switch.
4. Connect collector box pressure tube (green label) to pressure switch connection labeled COLLECTOR BOX.
5. Use remaining smaller diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (pink label) which was previously connected to pressure switch.
6. Route this extended tube (pink label) to condensate trap relief port connection.
7. Determine appropriate length, cut, and connect tube.
8. Clamp tube to relief port connection.
E. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
F. Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 2 and 11 or 12.)
CAUTION:
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: Combustion-air and vent pipes are restricted to a minimum length of 5 ft. (See Table 9 or 11.) NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive
condensate droplets from exiting the vent pipe. (See Fig. 11, 12, and 40.) NOTE: The 140 Size unit may not be installed in non-direct vent applications.
—16—
LEVEL (0)
TO
1
2 MAX
UPFLOW OR DOWNFLOW HORIZONTAL
FRONT
MIN
TO
1
2 MAX
1
4
FRONT
A02146
Fig. 14—Furnace Location for Proper Condensate
Drainage
LOCATION
PROCEDURE 1—GENERAL
This furnace must
• be installed so the electrical components are protected from water.
• not be installed directly on any combustible material other than wood flooring (refer to SAFETY CONSIDERATIONS).
• be located so combustion-air and vent pipe maximum lengths are not exceeded. Refer to Table 11.
• be located where available electric power and gas supplies meet specifications on the furnace rating plate.
• be attached to an air distribution system and be located as close to the center of the distribution system as possible. Refer to Air Ducts section.
• be provided with ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown on the furnace clearance to combustibles label.
NOTE: For upflow/downflow applications install furnace so that it is level or pitched forward within 1/2-in. for proper furnace operation. For horizontal applications pitch 1/4-in. minimum to 1/2-in. maximum forward to ensure proper condensate drainage from secondary heat exchangers. (See Fig. 14.)
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to furnace casing and terminating outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space.
FRONT
B A C K
BACK
FRONT
A93043
Fig. 15—Prohibit Installation on Back
WARNING: FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in fire, property damage, personal injury, or death. Do not install furnace on its back. Safety control operation will be adversely affected. Never connect return-air ducts to back of furnace. (See Fig. 15.)
—17—
CAUTION: UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided that:
-The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be hot wiredto provide heat continuously to the structure without thermostatic control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed ot thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
-After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
PROCEDURE 2—FURNACE LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air shall prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless damper is in full-heat or full-cool position.
32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
A93058
Fig. 16—Freeze Protection
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or unit damage. If these furnaces are installed in an unconditioned space where ambient temperatures may be 32°F or lower, freeze protection measures must be taken. (See Fig. 16.)
PROCEDURE 3—LOCATION WITH RESPECT TO COMBUSTION AND CIRCULATING AIR REQUIREMENTS
WARNING:
FIRE, EXPLOSION, INJURY, OR DEATH HAZARD
Improper location or inadequate protection could result in fire or explosion. When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18-in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with NFGC or NSCNGPIC (See Fig. 17.)
PROCEDURE 4—HAZARDOUS LOCATIONS A. Direct Vent Applications
Furnace may be located in a confined space without special provisions for dilution or ventilation air.
—18—
DUCTS
OUTDOORS
TO
1 SQ IN. PER 4000 BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
12 MAX
1 SQ IN. PER 2000 BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
12 MAX
CIRCULA TING AIR DUCTS
*Minimum dimensions of 3 in.
NOTE:
Use any of the following combinations of openings: A & B C & D D & E F & G
B
CIRCULA TING
A
CLEARANCE IN FRONT
AIR DUCTS
OPENINGS SHALL BE
OF COMBUSTION AIR
D
VENT THROUGH ROOF
AT LEAST 3 IN.
OUTDOORS
E
C
12 MAX
DUCT
TO
F
1 SQ IN.
BTUH*
1 SQ IN.
BTUH*
G
1 SQ IN. PER 4000 BTUH*
12 MAX
PER 4000
OUTDOORS
PER
4000
12 MAX
A03174
Fig. 18—Air for Combustion, Ventilation, and Dilution for
Outdoors
12" MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with minimum dimensions of 3 in.
Minimum of 3 in. . when type-B1 vent is used.
UNCONFINED SPACE
6" MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL B E A T LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
12" MAX
A03175
Fig. 19—Air for Combustion, Ventilation, and Dilution from
Indoors
B. Non-Direct Vent Applications
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in intermittent unit operation. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met.
Refer to the Air for Combustion and Ventilation section for details.
18-IN. MINIMUM
TO BURNERS
Fig. 17—Installation in a Garage
—19—
A93044
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
U.S. Installations: Section 8.3 of the NFGC, Air for Combustion and Ventilation and applicable provisions of the local building codes.
Canadian Installations: Part 7 of the NSCNGPIC, Venting Systems and Air Supply for Appliances and all authorities having jurisdiction.
WARNING: FURNACE CORROSION HAZARD
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements may corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
The following types of furnace installations may require OUTDOOR AIR for combustion due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms, and
• Chemical storage areas If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials All fuel-burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the
equipment room or space. A positive seal must be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area and from draft safeguard opening.
WARNING: CARBON MONOXIDE POISONING HAZARD
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of make-up air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
• Spaces having less than 50 cubic feet per 1,000 Btuh require the OUTDOOR COMBUSTION AIR METHOD.
• Spaces having at least 50 cubic feet per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or KNOWN-AIR
INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 18 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air openings to the outdoors.
a. One opening MUST commence within 12(300 mm) of the ceiling and the second opening MUST commence within 12(300 mm) of
the floor.
b. Size openings and ducts per Fig. 18 and Table 1.
2
c. TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btuh (1,100 mm
/kW) of combined input for all gas
appliances in the space per Fig. 18 and Table 1.
2
d. TWO OPENINGS OR VERTICAL DUCTS require 1 square inch of free area per 4,000 Btuh (550 mm
/kW) for combined input of all
gas appliances in the space per Fig. 18 and Table 1.
—20—
Table 1—Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
TWO HORIZONTAL DUCTS
FURNACE
INPUT
(BTUH)
44,000 22 6 14.7 5 11 4 66,000 33 7 22 6 16.5 5
88,000 44 8 29.3 7 22 6 110,000 55 9 36.7 7 27.5 6 132,000 66 10 44 8 33 7 154,000 77 10 51.3 9 38.5 8
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq. In.)
Round Duct
(in. Dia)
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW)
Free Area of
Opening and Duct
(sq In.)
Round Duct
(in. Dia)
TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq In.)
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
Table 2—Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTED TOTAL
ACH
0.60 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300 3,850
0.50 1,260 1,680 2,100 1,320 1,980 2,640 3,300 3,960 4,620
0.40 1,575 2,100 2,625 1,650 2,475 3,300 4,125 4,950 5,775
0.30 2,100 2,800 3,500 2,200 3,300 4,400 5,500 6,600 7,700
0.20 3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900 11,550
0.10 6,300 8,400 10,500 6,600 9,900 13,200 16,500 19,800 23,100
0.00 NP NP NP NP NP NP NP NP NP
(1,000’S BTUH GAS INPUT RATE)
30 40 50 44 66 88 110 132 154
Space Volume (ft
3
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
)
Round Duct
(In. Dia)
3. ONE OUTDOOR OPENING requires:
2
a. 1 square inch of free area per 3,000 Btuh (734 mm
/kW) for combined input of all gas appliances in the space per Table 1 and
b. Not less than the sum of the areas of all vent connectors in the space.
The opening shall commence within 12(300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1(25 mm) from the sides and back and 6(150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air© NFPA & AGA Standard and Known-Air-Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Method is used.
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to supply outdoor air via grilles or ducts could result in death and/or personal injury. Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000 Btuh of the maximum input ratings for all gas appliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
—21—
Table 3-Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1-2002/NFPA 54-2002,8.3.2.2:
1. For other than fan-assisted appliances, such as a draft hood-equipped water heater:
3
Volume
Other
21ft
=
ACH
I
other
1000 Btu/hr
A04002
2. For fan-assisted appliances such as this furnace:
3
Volume
15ft
=
Fan
ACH
I
fan
1000 Btu/hr
A04003
If:
= combined input of all other than fan-assisted appliances in Btu/hr
I
other
I
= combined input of all fan-assisted appliances in Btu/hr
fan
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closable doors between rooms.
2
b. Combining spaces on same floor level. Each opening shall have free area of at least 1 in.
rating of all gas appliances in the space, but not less than 100 in.
2
(0.06 m2). One opening shall commence within 12(300 mm) of the
/1,000 Btuh (2,000 mm2/kW) of the total input
ceiling and the second opening shall commence within 12(300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Fig. 19.)
c. Combining space on different floor levels. The volumes of spaces on different floor levels shall be considered as communicating spaces
if connected by one or more permanent openings in doors or floors having free area of at least 2 in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1-in.
2
/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section.
Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a continuous, sealed vapor barrier. Openings are gasketed or sealed and b. Doors and openable windows are weatherstripped and c. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between
wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
NOTE: In determining the free area of an opening, the blocking effect of the louvers, grilles, and screens must be considered. If the free area of a louver or grille design is unknown, it may be assumed that wood louvers have a 20 percent free area, and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed.
When combustion air ducts are used, they must be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 in. (80mm).
PROCEDURE 1—LEVELING LEGS (IF DESIRED)
When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 20.) Install field-supplied, corrosion-resistant 5/16-in. machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1-1/2 in.
1. Position furnace on its back. Locate and drill a 5/16-in. diameter hole in each bottom corner of furnace. (See Fig. 20.) Holes in bottom closure panel may be used as guide locations.
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section. PROCEDURE 2—INSTALLATION IN UPFLOW OR DOWNFLOW APPLICATIONS NOTE: For downflow applications, this furnace is approved for use on combustible flooring when manufacturer’s accessory floor base Part No.
KGASB0201ALL is used. Manufacturer’s accessory floor base in not required when this furnace is installed on manufacturer’s Coil Assembly Part No. CD5, CK5, or Coil Box Part No. KCAKC is used.
INSTALLATION
—22—
5
16
5
16
1 3⁄4
3
4
1
5
16
5
16
1 3⁄4
1 3⁄4
A89014
Fig. 20—Leveling Legs
1. Determine application being installed from Table 3.
2. Construct hole in floor per dimensions specified in Table 3 and Fig. 21.
3. Construct plenum to dimensions specified in Table 3 and Fig. 21.
4. If downflow subbase (KGASB) is used, install as shown in Fig. 22.
If coil assembly CD5, CK5 or Coil Box KCAKC is used, install as shown in Fig. 23.
NOTE: Remove furnace perforated, discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated, discharge duct flange, use wide duct pliers or duct flange tool to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 24.)
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. Do not bend duct flanges inward as shown in Fig. 24. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210° as shown in Fig. 24.
NOTE: For 140 size unit when installed in downflow orientation, cut the white jumper wire off between terminals PL1-7 and PL1-9. Do not cut white jumper between terminals PL1-7 and PLI-11. Refer to Fig. 35 for location of jumper. Cut jumper close to connector and remove wire to avoid a short circuit.
PROCEDURE 3—INSTALLATION IN HORIZONTAL APPLICATIONS
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area.
These furnaces can be installed horizontally in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See Fig. 25 or 26.) Cut hanger bolts (4 each 3/8-in. all-thread rod) to desired length. Use 1 X 3/8-in. flat washers, 3/8-in. lockwashers, and 3/8-in. nuts on hanger rods as shown in Fig. 25 or 26. Dimples are provided for hole locations. (See Fig. 2.)
NOTE: The 140 Size unit may not be installed in non-direct vent applications. PROCEDURE 4—AIR DUCTS
A. General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design static pressure.
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
—23—
A
PLENUM
OPENING
B
C
FLOOR
OPENING
D
A96283
Fig. 21—Floor and Plenum Opening Dimensions
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Fig. 22—Furnace, Plenum, and Subbase
Installed on a Combustible Floor
FURNACE
CASING
WIDTH
Upflow Applications 16 24-1/8 16-5/8 24-3/4
Downflow Applications on Non-Combustible Flooring 15-7/8 19 16-1/2 19-5/8
17-1/2
21
24-1/2
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5, CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5, CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications 19-1/2 24-1/8 20-1/8 24-3/4
Downflow Applications on Non-Combustible Flooring 19-3/8 19 20 19-5/8
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5, CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5, CK5 Coil Assembly or KCAKC Coil Box
Upflow Applications 23 24-1/8 23-5/8 24-3/4
Downflow Applications on Non-Combustible Flooring 22-7/8 19 23-1/2 19-5/8
Downflow Applications on Combustible Flooring Using KGASB Subbase
Furnace with or without CD5, CK5 Coil Assembly or KCAKC Coil Box
Downflow Applications on Combustible Flooring NOT Using KGASB Subbase
Furnace with CD5, CK5 Coil Assembly or KCAKC Coil Box
Table 3—Opening Dimensions (In.)
APPLICATION
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A96284
Fig. 23—Furnace, Plenum, and Coil
Assembly or Coil Box Installed
on a Combustible Floor
PLENUM OPENING FLOOR OPENING
ABCD
15-1/8 19 16-3/4 20-3/8
15-1/2 19 16-1/2 20
18-5/8 19 20-1/4 20-3/8
19 19 20 20
22-1/8 19 23-3/4 20-3/8
22-1/2 19 23-1/2 20
—24—
PERFORATED DISCHARGE DUCT FLANGE
210° MIN
NO
YES
YES
Fig. 24—Duct Flanges
A93029
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements.
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
B. Ductwork Acoustical Treatment
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
C. Supply Air Connections
UPFLOW FURNACES
Connect supply-air duct to 3/4-in. flange on furnace supply-air outlet. The supply-air duct attachment must ONLY be connected to furnace supply-/outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
DOWNFLOW FURNACES
Connect supply-air duct to supply-air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material. When installed on combustible material, supply-air duct attachment must ONLY be connected to an accessory subbase or factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
HORIZONTAL FURNACES
Connect supply-air duct to supply air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
D. Return Air Connections
The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot affect another appliance’s combustion air supply or act to mix products of combustion with circulating air, and that the air circulating fan of the furnace, if installed in an enclosure communicating with another fuel-burning appliance not of the direct-vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return air plenum on ducts is in the closed position.
WARNING: FIRE HAZARD
A failure to follow this warning could result in fire, personal injury, or death. Never connect return-air ducts to the back of the furnace. Return-air duct connections on furnace side(s) permitted in upflow applications only.
UPFLOW FURNACES
The return-air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 2. Bypass humidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any portion of return-air duct to back of furnace casing.
—25—
3
8-IN. ROD
ANGLE IRON OR EQUIVALENT
(B)
(A) ROD LOCATION
USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION (B) ALTERNATE ROD LOCATION
(B)
(A)
3
/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
NOTES:
(A)
1. A 1 In. clearance minimum between top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
5
(B)
3
4
DRAIN
(A)
(B)
13
/16-IN. MAX ALTERNATE SUPPORT LOCATION FROM BACK
ALTERNATE SUPPORT LOCATION 4-IN. MIN 8-IN. MAX
A93304
Fig. 25—Crawlspace Location in Direct Vent Application (All Sizes)
DOWNFLOW AND HORIZONTAL FURNACES
The return-air duct must be connected to return-air opening provided as shown in Fig. 2. DO NOT cut into casing sides or back to attach any portion of return-air duct. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace.
E. Filter Arrangement
CAUTION: FIRE, CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in fire, personal injury, or death. Never operate a unit without a filter or with filter access door removed.
Factory-supplied washable framed filters are shipped in blower compartment. Determine location for filter and relocate filter retaining wire if necessary. See Table 4 to determine correct filter size for desired filter location. Table 4 indicates filter size, location, and quantity shipped with furnace. See Fig. 2 for location and size of bottom and side return-air openings.
CAUTION:
CUT HAZARD
Failure to follow this caution may result in minor personal injury. Use care when cutting support rods in filters to protect against flying pieces and sharp rod ends. Wear safety glasses, gloves, and appropriate protective clothing.
—26—
A 3-IN. MINIMUM
COMBUSTION-AIR INTAKE
CLEARANCE TO
IS REQUIRED.
COMBUSTION-AIR
INTAKE
VENT
3
8-IN. ROD
ANGLE IRON OR EQUIVALENT
(B)
(A) ROD LOCATION
USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION (B) ALTERNATE ROD LOCATION
(B)
(A)
3
/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
(A)
NOTES:
3
5
4
DRAIN
(A)
(B)
13
(B)
1. A 1 In. clearance minimum between top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
3. Bottom side combustion-air entry cannot be used when furnace is installed with hangers as shown.
/16-IN. MAX ALTERNATE SUPPORT LOCATION FROM BACK
ALTERNATE SUPPORT LOCATION 4-IN. MIN 8-IN. MAX
Fig. 26—Crawlspace Location in Non-Direct Vent Application (Sizes 040 through 120 Only)
Table 4—Filter Information
FURNACE CASING
WIDTH (IN.)
Side Return Bottom Return
17-1/2 (1) 16 X 25 X 1† (1) 16 X 25 X 1 Cleanable
21 (1) 16 X 25 X 1 (1) 20 X 25 X 1† Cleanable
24-1/2 (1 or 2) 16 X 25 X 1 (1) 24 X 25 X 1† Cleanable
* Filters can be field modified by cutting frame as marked and folding to desired size. Alternate sizes can be ordered from your distributor or dealer. † Factory-provided with furnace.
FILTER SIZE (IN.)*
FILTER TYPE
FRAMED
A96209
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
Bottom return-air opening may be used with all 4 orientations. Filter may need to be cut to fit some furnace widths. Install filter as shown in Fig.
27.
NOTE: Remove and discard bottom closure panel when bottom inlet is used. NOTE: Side return-air openings can ONLY be used in UPFLOW configurations. Install filter(s) as shown in Fig. 28.
F. Bottom Closure Panel
These furnaces are shipped with bottom enclosure panel installed in bottom return-air opening. This panel MUST be in place when side return air is used.
To remove bottom closure panel, perform following:
1. Tilt or raise furnace and remove 2 screws holding front filler panel. (See Fig. 29.)
2. Rotate front filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall front filler panel and screws.
—27—
Table 5—Maximum Capacity of Pipe*
NOMINAL IRON PIPE SIZE
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 9.2 NFPA 54-2002
(IN.)
1/2 0.622 175 120 97 82 73 3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285 1-1/4 1.380 1400 950 770 660 580 1-1/2 1.610 2100 1460 1180 990 900
INTERNAL DIAMETER
(IN.)
10 20 30 40 50
LENGTH OF PIPE (FT)
G. Gas Piping
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the United States. Canadian installations must be made in accordance with NSCNGPIC and all authorities having jurisdiction. Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 5 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in fire, explosion, personal injury, or death.
-Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls.
-Gas valve shutoff switch MUST be facing forward or tilted upward.
-Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
-Use proper length of pipe to avoid stress on gas control manifold.
-If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum of 2 in. outside furnace casing.
Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight-through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 30.) If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance.
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion could result causing property damage, personal injury or loss of life.
An accessible manual shutoff valve MUST be installed external to furnace casing and within 6 ft of furnace. A 1/8-in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual shutoff valve. NOTE: The gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas valve. (See Fig. 48.) Piping should be pressure and leak tested in accordance with NFGC in the United States or NSCNGPIC in Canada, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace. If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before pressure test. If test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on furnace gas valve and accessible manual shutoff valve before test. The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.
PROCEDURE 5—ELECTRICAL CONNECTIONS
See Fig. 31 for field wiring diagram showing typical field 115-v and 24-v wiring. Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63°F (35°C) rise.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in serious injury or death. Blower access panel door switch opens 115-v power to control center. No component operation can occur. Do not bypass or close switch with panel removed.
CAUTION: FURNACE MAY NOT OPERATE
Failure to follow this caution may result in furnace operation stopping and water pipes freezing during cold weather. Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
—28—
171⁄2-IN. WIDE CASINGS ONLY:
INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.
3
1
24
/2″
1
21-IN. WIDE CASINGS ONLY:
SUPPORT RODS (3) EXTEND 1/4" ON EACH SIDE OF FILTER AND REST ON CASING FLANGE
WASHABLE FILTER
A00217
Fig. 28—Filter Installed for Side Inlet
FILTER SUPPORT
FILTER RETAINER
Fig. 27—Bottom Filter Arrangement
GAS SUPPLY
MANUAL SHUTOFF VALVE (REQUIRED)
SEDIMENT TRAP
Fig. 30—Typical Gas Pipe Arrangement
A00290
UNION
BOTTOM CLOSURE PANEL
FRONT FILLER PANEL
Fig. 29—Removing Bottom Closure Panel
A93047
A93324
A. 115-v Wiring
Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on unit rating plate. Check to be sure that service provided by power supply is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 6 for equipment electrical specifications.
—29—
FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
115-V FIELD-
SUPPLIED
DISCONNECT
GND
BLK
WHT
AUXILIARY J-BOX
GND
FURNACE
NOTE 2
W
C
R
O
N T
G
R
O
COM
L
Y
24-V
TERMINAL
BLOCK
WCR GY
NOTE 1
NOTES: Connect Y-terminal in furnace as shown for proper blower operation.
1.
2.
3.
THERMOSTAT TERMINALS
CONDENSING UNIT
TWO WIRE
Some thermostats require a "C" terminal connection as shown. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
FIELD-SUPPLIED DISCONNECT
GND
208/230- OR 460-V THREE PHASE
208/230-V SINGLE PHASE
A02174
Fig. 31—Heating and Cooling Application Wiring Diagram
Table 6—Electrical Data
UNIT SIZE
VOLTS— HERTZ—
PHASE
024040 115—60—1 127 104 6.1 8.4 14 44 15 036040 115—60—1 127 104 7.3 10.0 14 37 15 024060 115—60—1 127 104 6.1 8.4 14 44 15 036060 115—60—1 127 104 7.1 9.8 14 38 15 048060 115—60—1 127 104 9.5 12.8 14 29 15 036080 115—60—1 127 104 7.6 10.4 14 36 15 048080 115—60—1 127 104 10.0 13.4 14 28 15 060080 115—60—1 127 104 14.1 18.4 12 31 20 048100 115—60—1 127 104 10.2 13.5 14 27 15 060100 115—60—1 127 104 14.8 19.3 12 30 20 060120 115—60—1 127 104 14.6 19.1 12 30 20 060140 115—60—1 127 104 14.3 18.8 12 30 20
* Permissible limits of voltage range at which unit will operate satisfactorily. † Unit ampacity = 125 percent of full load amps of largest operating component plus 100 percent of full load amps of all other potential operating components (EAC,
humidifier, etc.). ‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended.
OPERATING
VOLTAGE RANGE
Max* Min*
MAX UNIT
AMPS
UNIT
AMPACITY†
MIN
WIRE
GAUGE
MAX WIRE
LENGTH
(FT)‡
MAX FUSE
OR CKT BKR
AMPS**
Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2002 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.
ELECTRIC
DISCONNECT
SWITCH
COPPER
WIRE ONLY
ALUMINUM
WIRE
Fig. 32—Disconnect Switch and Furnace
—30—
A93033
ALTERNATE
FIELD
LOCATION
FACTORY INSTALLED LOCATION
A00212
Fig. 33—Relocating J-Box
WARNING: FIRE HAZARD
Failure to follow this warning could result in serious injury, death, or property damage. Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 32.)
Use a separate, fused branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 6 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control center LED status indicator light will flash rapidly and furnace will NOT operate.
WARNING: ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in serious injury, death, or property damage. The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2002 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground.
J-BOX RELOCATION
1. Remove 2 screws holding auxiliary J-box. (See Fig. 33.)
2. Rotate J-box 180° and attach box to right side, using holes provided.
WARNING:
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in serious injury, death, or property damage. If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.
B. 24-v Wiring
Make field 24-v thermostat connections at 24-v terminal block on furnace control center. For proper cooling operation, Y wire from thermostat MUST be connected to Y terminal on control center, as shown in Fig. 31. The 24-v terminal block is marked for easy connection of field wiring. (See Fig. 34.) The 24-v circuit contains a 3-amp, automotive-type fuse located on furnace control center. (See Fig. 35.) Any electrical shorts of 24-v wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (3 amp) and type. The control will flash code 24 when fuse needs replacement.
NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire. C. Accessories
1. Electronic Air Cleaner (EAC) Two quick-connect terminals marked EAC-1 and EAC-2 are provided for EAC connection. (See Fig. 35.) These terminals are energized
with 115v (1.0-amp maximum) during blower motor operation.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage. DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat™, Zone Controller or similar device. See Thermidistat™, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
—31—
SCHEMATIC DIAGRAM
(NAT UR AL G AS & PRO PANE)
L2
NOTE #2
TO 115VAC FIELD DISCONNECT
GND
L1
L2
CAP-1
LO
EQUIPMENT GROUND
SPARE-2
ILK
EAC-2
IDM
BLWM
START
OL
COM
HI
MED LO
MED HI
NOTE #10
COOL
HEAT
SPARE-1
HI/LO
L1
HSIR
EAC-1
BLWR
AUX
OL
M
1
3
HSI
2
1
PL3
2
1
PL2
115VAC
PR1
IDR
PL4
24VAC
TRAN
TEST/TWIN
LS
FRS
CAP - 2
2
6
SEC-2
SEC-1
NOTE #6
F U 1
PRINTED CIRCIUT BOARD
NOTE #3
GV
(WHEN USED)
NOTE #11
PRS
LGPS
C
328150-101 REV. A
M
FSE
A02271
7
3
9
1
5
2
8
PL1
R
W
4
10
GVR-1
CPU
G
HUM
Y
11
NOTE #5
PCB
OM
24V
C
NOTES:
2. Use only copper wire between the disconnect sw itch and the furnac e junc tion box (JB ).
3. This wire must be connected to furnace sheet metal for control to prove flame.
4. Symbols are electrical representation only.
1. If any of the original equipment wire is replaced use wire rated for 105°C.
optimum speed selection.
auto-r e s e t after three h ours.
5. Solid lines inside PCB are printed circuit board conductors and are not included in legend.
6. Replace only with a 3 amp fuse.
7. Inducer (IDM) and blower (BLW M) motors contain internal auto-reset thermal overload sw itches (O L).
8. Neutral connections are interchangeable within the NEUTRAL connector block.
9. Blower motor speed selections are for average conditions, see installation instructions for details on
10. YELLOW lead no t on all m otors.
11. Factory connected when LGP S is not u se d.
90 seconds or 5 seconds when J2 is cut.
12. Ig nition-lockout will occ ur after four consecutive unsucce ssful trials-f o r- ignition. Co ntrol will
13. Blower-on delay: gas heating 60 seconds, cooling or heat pump 2 seconds.
14. Blower-off delay: gas heating selections are 90, 120, 150 or 180 seconds, cooling or heat pump
LGPS
(WHEN USED)
NOTE #11
PRS
ORN
PCB
120
90
BLOWER OFF DELAY
150
JUMPER SELECT
J2
G
PRINTED CIRCIUT BOARD
YEL
GRN/YEL
GV
C
NOTE #3
M
BLU
FRS
GRN/YEL
RED
RED
LS
RED
ORN
BLU
180
J1
HUM
TEST/TWIN
om
Y
R
W
24V
C
FU1
NOTE #6
WHT
11
WHT
BLK
CAP -2
TRAN
WHT
BLU
RED
RED
RED
GRN/YEL
WHT
L2
SEC-1
LED 1
EAC-2
SEC-2
IDM
BRN
AUX
M
BRN
WHT
GRN/YEL
3
2
PL4
FSE
YEL
WHT
GRN/YEL
PL1
12345678910
NEUTRAL
BLW
NOTE #8
HSI
WHT
OL
2
1
PL3
BLK
WHT
BLK
1
BLK
BLK
1
PL2
2
EAC-1
SPAR E 2
L1
BHT/CLR BLWR
COOL
HEAT
SPA RE 1
FUSED OR CIRCUIT BREAKER
WHT
BLK
WHT (COM)
PR1
BLWM
BLK (HI)
WHT
(COM )
L1
NEUTRAL
NOTE #2
FU2
BLK
WHT
DISCONNECT SWITCH (WHEN REQ’D)
JB
GRN/YEL
BRN
YEL
(MED HI)
GND
TEMPERATURE SWITCH (N.C.)
JUNCTION
UNMARKED TERMINAL
PCB CONTROL TERMINAL
FACTOR Y WIRING (115V AC)
FACTOR Y WIRING (24V AC)
FIELD WIRING (115VAC)
FIELD WIRING (24VAC)
CONDUCTOR ON CONTROL PCB
FIELD WIRING SCREW TERMINAL
FIELD EARTH GROUND
EQUIPMENT GROUND
FIELD SPLICE
PLUG RECEPTACLE
Fig. 34—Wiring Diagram
OL AUTO-RESET INTERNAL MOTOR OVERLOAD
PCB PR INTED CIRCUIT BOARD CONTROL
PL1 11-CIRCUIT PCB CONNECTOR
PL2 2-CIRCUIT CONNECTOR
PL3 2-CIRCUIT HSI, CONNECTOR
PL4 3-CIRCUIT IDM EXTENSION CONNECTOR
PRS PRESSURE SWITCH, SPST-(N.O.)
TEST/TWIN COMPONENT TEST & TWIN TERMINAL
TRAN TRANSFORMER-115VAC/24VAC
ILK
BLK
WHT
CAP -1
BRN
STAR T
OL
(FIELD INSTALLED & SUPPLIED)
FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME-PROVING ELECTRODE
FU 1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FU 2 FUSE OR CIRC UIT B REAK ER CURRENT INTERRUPT DEVICE
GND EQUIPMENT GROUND
GV GAS VALVE-REDUNDANT
GVR 1, 2 GAS VALVE RELAY, DPST-(N.O.)
HSI HOT SURFACE IGNITER (115 V AC)
HSIR HOT SURFACE IGNITER RELAY, SPST-(N.O.)
HUM 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.)
IDM INDUCED DRAFT MOTOR, PSC
IDR INDUCED DRAFT MOTOR RELAY, SPST-(N.O.)
ILK BLO WER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.)
J1 BLOWER - OFF DELAY JUMPER SELECTOR
J2 COOLING - OFF DELAY JUMPER
JB JUNCTION BOX
LED LIGHT-EMITTING DIODE FOR STATUS CODES - RED
LGPS LOW GAS PRESSURE SWITCH, SPST -(N.O .)
LS LIMIT SWITCH, AUTO-RESET, SPST (N.C.)
D
NOTE #10
RED (LO)
BLU
(MED L O )
BHT/CLR BLOWER MOTOR SPEED CHANGE RELAY, SPDT
BLWR BLOWER MOTOR RELAY, SPST-(N.O.)
BLWM BLOWER MOTOR, PERMANENT-SPLIT-CAPACITOR
CAP 1,2 CAPACITOR
CPU MICROPROCESSOR AND CIRCUITRY
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.)
EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON)
LEGEN
—32—
2. Humidifier (HUM) A quick-connect terminal (HUM) and screw terminal (C
OM 24v) are provided for 24-v humidifier connection. (See Fig. 35.) HUM terminal
is energized with 24v (0.5-amp maximum) when gas valve is energized.
NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.
PROCEDURE 6—REMOVAL OF EXISTING FURNACES FROM COMMON VENT SYSTEMS
When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the remaining attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, spillage of combustion products into the living space, etc.
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, asrequired in the NationalFuel Gas Code,ANSI Z223.1-2002/NFPA 54-2002 or the CSA B149.1, Natural Gasand Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1-2002/NFPA 54-2002 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired appliance to their previous conditions of use.
Vent system or vent connectors may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSCNGPIC.
PROCEDURE 7—COMBUSTION AIR AND VENT PIPE SYSTEMS A. General
Vent system or vent connectors may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSCNGPIC.
The PG9MAB can be vented as either a direct vent (all sizes) or as a non-direct vent (except for 140 size) application. A direct vent system shall be installed in accordance with the direct vent procedures (2-pipe) in the following Combustion Air and Vent Pipe Systems section. For non-direct vent (1-pipe) applications, refer to the non-direct vent (1-pipe) procedures in the same section.
B. Direct Vent/2-Pipe System (All Sizes)
In a direct-vent (2-pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. A factory accessory vent termination kit MUST be used in a direct vent (2-pipe) system.
—33—
Table 7—Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials
ASTM SPECIFICATION
(MARKED ON MATERIAL)
D1527 ABS Pipe Schedule-40 D1785 PVC Pipe Schedule-40
D2235 For ABS D2241 PVC Pipe SDR-21 & SDR-26
D2466 PVC Fittings Schedule-40 D2468 ABS Fittings Schedule-40
D2564 For PVC D2661 ABS Pipe Fittings DWV at Schedule-40 IPS sizes
D2665 PVC Pipe Fittings DWV
F438 CPVC Fittings Schedule-40 F441 CPVC Pipe Schedule-40 F442 CPVC Pipe SDR
F493 For CPVC F628 ABS Pipe Cellular Core DWV at Schedule-40 IPS sizes
F656 For PVC Primer For PVC F891 PVC Pipe Cellular Core Schedule-40 & DWV
C. Non-Direct Vent/1-Pipe System Sizes 040 Through 120 Only)
MATERIAL PIPE FITTINGS SOLVENT CEMENT AND PRIMERS DESCRIPTION
Solvent
Cement
Solvent
Cement
Solvent
Cement
For ABS
For PVC
For CPVC
In a non-direct vent (1-pipe) system, all air for combustion is taken from the area adjacent to furnace, and all flue products are discharged to outdoor atmosphere. A factory-supplied perforated disk assembly (in loose parts bag) MUST be used in combustion-air pipe elbow.
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, asrequired in the NationalFuel Gas Code,ANSI Z223.1-2002/NFPA 54-2002 or the CSA B149.1, Natural Gasand Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1-2002/NFPA 54-2002 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
D. Materials
Combustion-air and vent pipe, fittings, primers, and solvents must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards. See Table 7 for approved materials for use in the U.S.A.
WARNING: FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in fire, property damage, personal injury, or death. Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well-ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes.
In Canada, construct all combustion-air and vent pipes for this unit of CSA or ULC listed schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in Canada.
In direct vent (2-pipe) systems, combustion air and vent pipes must terminate together in same atmospheric pressure zone, either through roof or sidewall (roof termination preferred), using accessory termination kit. See Table 8 for required clearances.
—34—
BLOWER OFF-DELAY
J2 JUMPER
24-V THERMOST AT
TERMINALS
G Com W Y R
24V
BLOWER OFF-DELAY
90 150
J2
120 180
TWINNING AND/OR COMPONENT TEST
TERMINAL
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
3-AMP FUSE
LED OPERATION &
DIAGNOSTIC LIGHT
115-VAC(L2)NEUTRAL
CONNECTIONS
COOL
HEAT
BLOWER SPEED
SELECTION TERMINALS
STATUS CODE LED
NUETRAL
BLW
COOL HEAT
SPARE-1
SPARE-2
TEST/TWIN
0.5 AMP@24VAC
FUSE 3-AMP
SEC-2 SEC-1
EAC-2 L2
SPARE-1 SPARE-2
PLT
HUM
PLT 1
1-AMP@
EAC-1
115VAC
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
Fig. 35—Control Center
L1
PR-1
PL2 1
115 VAC (L1) LINE
VOLTAGE CONNECTION
TRANSFORMER 24-VAC
CONNECTIONS
PL1-LOW VOLTAGE MAIN HARNESS CONNECTOR
PL2-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A02100
In non-direct vent (1-pipe) system, vent pipe termination must be installed with adequate clearances to building openings and equipment to comply
with national and local codes. See Table 9 for required clearances.
WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in property damage, personal injury, or death. All combustion-air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 40 for direct vnet (2-pipe) system and Fig. 41 for non-direct vent (1-pipe) system.
An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion-air (when applicable) and vent pipes.
Each furnace must have its own set of combustion-air and vent pipes and be terminated individually, as shown in Fig. 40 for Direct Vent (2-Pipe) system and Fig. 41 for Non-Direct Vent (1-Pipe) system.
Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer’s installation instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.
CAUTION:
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 10 with Armaflex-type insulation.
Furnace combustion air and vent pipe connections are sized for 2-in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe. The transition has to be made as close to the furnce as reasonably possible.
—35—
Table 8—Direct Vent Termination Clearance
A05009
—36—
Table 9—Other than Direct Vent Termination Clearance
A05013
—37—
Table 10—Maximum Allowable Exposed Vent Pipe Length (ft) With and Without Insulation in Winter Design Temperature
Ambient*
FURNACE
SIZE
040
060
080
100
120
140
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 10. † Insulation thickness based on R value of 3.5 per in.
WINTER DESIGN
TEMPERATURE
(°F)
20 1.5 51 70
0 1.5 28 70
-20 1.5 16 70 20 2 45 70
0 2 22 70
-20 2 10 58 20 2 65 70
0 2 35 70
-20 2 20 70 20 2 55 55
0 2 48 55
-20 2 30 55 20 2.5 70 70
0 2.5 47 70
-20 2.5 28 70 20 2.5 40 40
0 2.5 40 40
-20 2.5 38 40 20 3 70 70
0 3 50 70
-20 3 28 70 20 3 70 70
0 3 61 70
-20 3 37 70 20 4 70 70
0 4 48 70
-20 4 23 70 20 3 60 60
0 3 60 60
-20 3 44 60 20 4 70 70
0 4 57 70
-20 4 30 70
MAX PIPE
DIAMETER
(IN.)
WITHOUT
INSULATION
WITH 3/8–IN. OR
THICKER INSULATION†
E. Combustion Air Pipe
GENERAL
Furnace combustion-air connection must be attached as shown in Fig. 35. Combustion-air intake housing plug may need to be relocated in some applications.
For Non-Direct Vent (1-Pipe) system, combustion-air must terminate outside of furnace casing with 1 elbow. Orient elbow so that its opening faces down for upflow or downflow applications. Orient elbow so that its opening faces sideways (left or right) for horizontal left or horizontal right applications (See Fig. 36.) Maintain a 3-in minimum clearance between the opening of the combustion-air inlet pipe and any object.
CAUTION: UNIT CORROSION HAZARD
Excessive exposure to contaminated combustion air may result in safety and performance related problems. Combustion air must not be taken from inside structure because inside air is frequently contaminated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion-air inlet as far as possible from swimming pool and swimming pool pump house.
NOTE: All pipe joints must have cemented attachment of combustion-air inlet pipe to inlet housing connection, since it may be necessary to remove pipe for servicing.
ASSEMBLY OF COMBUSTION AIR PIPE (NON-DIRECT VENT/1-PIPE SYSTEM ONLY)
1. Permanently install perforated disk assembly (factory-supplied in loose parts bag) in combustion-air elbow using RTV or by cementing, as shown in Fig. 36. For 120,000 Btuh size units only: separate the 2 halves of perforated disk assembly and use only the shouldered disk half.
2. Determine the length of straight portion of combustion-air inlet pipe from Fig. 36.
3. Cut field-supplied 2-in. diameter PVC pipe to length as determined per Fig. 36.
—38—
NOTE: Select 1 vent pipe connection and
Select 1 vent pipe connection and 1 combustion-air pipe connection.
AIR
AIR
FLOW
COMBUSTION-
COMBUSTION-
VENT
*
AIR
VENT
NOTE:
1 combustion-air pipe connection.
VENT
VENT
*
COMBUSTION-
AIR
UPFLOW DOWNFLOW
COMBUSTION-
AIR
VENT
**
AIR
FLOW
HORIZONTAL-LEFT DISCHARGE HORIZONTAL-RIGHT DISCHARGE
* For Non-Direct Vent (1-Pipe) system, orient elbow so that its
opening faces down.
** For Non-Direct Vent (1-Pipe) system, orient elbow so that its
opening faces sideways.
† An external trap kit (see furnace product data sheet) must be used.
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. Make sure there is adequate clearance (3-in. minimum) to any fixed or loose objects in order to ensure an adequate combustion-air supply.
Fig. 36—Combustion-Air and Vent Pipe Connections
COMBUSTION-
AIR
FLOW
COMBUSTION-
AIR
VENT
AIR
FIELD-SUPPLIED
**
AIR
FLOW
2-IN. DIAMETER PVC 90° ELBOW
FIELD-SUPPLIED 2-IN. DIAMETER PVC PIPE
A
COMBUSTION-AIR DISC (FACTORY-SUPPLIED IN
A96188
LOOSE PARTS BAG)
Length of Straight Pipe Portion of
Combustion-Air Inlet Pipe Assembly (In.)
CASING WIDTH A
17-1/2 8-1/2 ± 1/2
21 10-1/2 ± 1/2
24-1/2 12 ± 1/2
Fig. 37—Combustion-Air Inlet Pipe Assembly
4. Permanently attach elbow/perforated disk assembly to straight portion of pipe using RTV or by cementing as shown in Fig. 36.
ASSEMBLY OF COMBUSTION AIR PIPE (DIRECT VENT-2-PIPE SYSTEM ONLY)
1. Using Table 11, determine the smallest combustion air diameter permitted. Pick the larger diameter and use it for both combustion and vent
pipe.
NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 40 for Direct Vent/2-Pipe system, and Fig. 41 for Non-Direct Vent/1-Pipe system.
A96211
CAUTION:
UNIT MAY NOT OPERATE
Failure to follow this caution may result in incomplete combusiton, flame disturbance, or flame sense lockout. When installing combusiton air and vent system of short pipe length, the smallest allowable pipe diameter must be used.
NOTE: A 2-in. diameter pipe must be used within furnace casing. Make all pipe diameter transitions outside furnacec casing per Fig. 37.
2. If required per Table 11, insert perforated disk assembly (factory-supplied in loose parts bag) in intake housing where combustion air pipe
will be connected. If half disk set is required, install only shouldered disk half.
ATTACHMENT OF COMBUSTION AIR PIPE
1. Determine location of combustion air intake pipe connection to combustion air intake housing as shown in Fig. 35 for application.
2. Reposition combustion air intake housing plug fitting in appropriate unused intake housing connection.
3. Install pipe support (factory-supplied in loose parts bag) into selected furnace casing combustion-air pipe hole. Pipe support should be
positioned at bottom of casing hole.
4. Insert assembled combustion air inlet pipe into intake housing as shown in Fig. 35.
5. Drill a 1/8-in. hole in 2-in, combustion air pipe using the hole in intake housing as a guide.
—39—
ALTITUDE (FT)
0 to 2000
ALTITUDE (FT)
2001 to 3000
ALTITUDE (FT)
3001 to 4000
See notes at end of table
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
140,000
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
140,000
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
140,000
Table 11—Maximum Allowable Vent Pipe Length (Ft)
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
4† no disk 4† no disk 4† no disk 70 70 70 70 70 70
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1 1 5 NANANANANA
1-1/2 1-1/2 70 70 65 60 60 55
2 2 70 70 70 70 70 70
1-1/2 1-1/2 20 15 10 5 NA NA
2 2 70 70 70 70 70 70
1-1/2 1-1/2 10 NA NA NA NA NA
2 2 55 50 35 30 30 20
2-1/2 2-1/2 70 70 70 70 70 70
2 2 5 NANANANANA
2-1/2 2-1/2 40 30 20 20 10 NA
3 3 70 70 70 70 70 70
2-1/2 one disk 2-1/2 10 NA NA NA NA NA
3† NA 45 40 35 30 25 20
3† no disk 3† 70 70 70 70 70 70
2-1/2 one disk NA 5 NA NA NA NA NA
3† one disk NA 40 35 30 25 20 15
3† no disk NA 60 56 52 48 44 40 4† no disk NA 70 70 70 70 70 70
PIPE DIA
(IN.)*
1-1/2 1-1/2 67 62 57 52 52 47
2 2 70 70 70 70 70 70
1-1/2 1-1/2 17 12 7 NA NA NA
2 2 70 67 66 61 61 61
2 2 49 44 30 25 25 15 2-1/2 2-1/2 70 70 70 70 70 70 2-1/2 2-1/2 35 26 16 16 6 NA
3 3 70 70 70 70 66 61
3 NA 14 9 NA NA NA NA
NA 3† 63 62 62 61 61 61 3† no disk NA 70 70 63 56 50 43 4† no disk 4† no disk 70 70 70 70 70 70
3† one disk NA 20 15 10 5 NA NA
3† no disk NA 39 35 31 27 23 19 4† no disk NA 70 70 70 70 70 70
PIPE DIA
(IN)*
1-1/2 1-1/2 64 59 54 49 48 43
2 2 70 70 70 70 70 70
1-1/2 1-1/2 16 11 6 NA NA NA
2 2 68 63 62 57 57 56
2 2 46 41 28 23 22 13 2-1/2 2-1/2 70 70 70 70 70 70 2-1/2 2-1/2 33 24 15 14 5 NA
3 3 70 70 70 66 61 56
3† no disk NA 65 58 51 44 38 31
NA 3† 59 59 58 57 57 56
3† one disk NA 11 6 NA NA NA NA
3† no disk NA 30 26 22 18 14 10 4† no disk NA 70 70 70 70 70 70
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
123456
NUMBER OF 90° ELBOWS
123456
NUMBER OF 90° ELBOWS
123456
—40—
ALTITUDE (FT)
4001 to 5000‡
ALTITUDE (FT)
5001 to 6000‡
ALTITUDE (FT)
6001 to 7000‡
See notes at end of table
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
140,000
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
140,000
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
140,000
Table 11—Maximum Allowable Vent Pipe Length (Ft) (Continued)
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1-1/2 1-1/2 60 55 50 45 44 39
2 2 70 70 70 70 70 70
1-1/2 1-1/2 15 10 5 NA NA NA
2 2 64 59 58 53 52 52
2 2 44 39 26 21 20 11 2-1/2 2-1/2 70 70 70 70 70 70 2-1/2 2-1/2 31 22 13 12 NA NA
3 3 70 70 67 62 57 52
3† no disk NA 53 46 40 33 26 20
NA 3† 56 55 54 53 52 52 4† no disk 4† no disk 70 70 70 70 70 70 3† no disk NA 21 17 13 9 5 NA 4† no disk NA 69 64 59 54 49 44
PIPE DIA
(IN.)*
1-1/2 1-1/2 57 52 47 42 40 35
2 2 70 70 70 70 70 70
1-1/2 1-1/2 14 9 NA NA NA NA
2 2 60 55 54 49 48 47
2 2 41 36 23 18 17 8 2-1/2 2-1/2 70 70 70 70 70 70 2-1/2 2-1/2 29 21 12 11 NA NA
3 3 70 67 62 57 52 47
3† no disk NA 42 35 29 22 15 9
NA 3† 53 52 50 49 48 47 4† no disk 4† no disk 70 70 70 70 70 70 3† no disk NA 12 8 NA NA NA NA 4† no disk NA 42 37 32 27 22 17
PIPE DIA
(IN)*
1-1/2 1-1/2 53 48 43 38 37 32
2 2 70 70 68 67 66 64
1-1/2 1-1/2 13 8 NA NA NA NA
2 2 57 52 50 45 44 43
2 2 38 33 21 16 15 6 2-1/2 2-1/2 70 70 68 67 66 64 2-1/2 2-1/2 27 19 10 9 NA NA
3 3 68 63 58 53 48 43
3† no disk NA 31 24 18 11 NA NA
NA 3† 49 48 47 45 44 43
4† no disk 4† no disk 70 70 70 70 67 62 4† no disk NA 17 12 7 NA NA NA
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN)*
NUMBER OF 90° ELBOWS
123456
NUMBER OF 90° ELBOWS
123456
NUMBER OF 90° ELBOWS
123456
—41—
ALTITUDE (FT)
UNIT SIZE
(BTUH)
40,000
60,000
80,000
7001 to 8000‡
100,000
120,000
Table 11—Maximum Allowable Vent Pipe Length (Ft) (Continued)
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1-1/2 1-1/2 49 44 39 34 33 28
2 2 66 65 63 62 60 59
1-1/2 1-1/2 12 7 NA NA NA NA
2 2 53 48 46 41 40 38
2 2 36 31 19 14 12 NA 2-1/2 2-1/2 66 65 63 62 60 59 2-1/2 2-1/2 25 17 8 7 NA NA
3 3 63 58 53 48 43 38
3† no disk NA 20 13 7 NA NA NA
NA 3† 46 44 43 41 40 38
4† no disk 4† no disk 61 56 51 46 41 36
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
123456
140,000 NA
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
123456
ALTITUDE (FT)
8001 to 9000‡
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1-1/2 1-1/2 46 41 36 31 29 24
2 2 62 60 58 56 55 53 1-1/2 1-1/2 11 6 NA NA NA NA
2 2 49 44 42 37 35 34
2 2 33 28 17 12 10 NA 2-1/2 2-1/2 62 60 58 56 55 53 2-1/2 2-1/2 23 15 7 5 NA NA
3 3 59 54 49 44 39 34
3† no disk NA 10 NA NA NA NA NA
NA 3† 43 41 39 37 35 34
4† no disk 4† no disk 35 30 25 20 15 10
140,000 NA
NON-DIRECT VENT
(1-PIPE) ONLY
PIPE DIA
(IN.)*
NUMBER OF 90° ELBOWS
123456
ALTITUDE (FT)
9001 to 10,000‡
UNIT SIZE
(BTUH)
40,000
60,000
80,000
100,000
120,000
DIRECT VENT (2-PIPE) ONLY
TERMINATION
TYPE
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 2-in
Concentric
2 Pipe or 3-in
Concentric
2 Pipe or 3-in.
Concentric
PIPE DIA
(IN.)*
1-1/2 1-1/2 42 37 32 27 25 20
2 2 57 55 53 51 49 47
2 2 45 40 38 33 31 29
2 2 30 25 14 9 7 NA 2-1/2 2-1/2 57 55 53 51 49 47 2-1/2 2-1/2 21 13 5 NA NA NA
3 3 54 49 44 39 34 29
NA 3† 39 37 35 33 31 29
4† no disk 4† no disk 10 5 NA NA NA NA
140,000 NA
*Disk usage-Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag). If one disk is stated, separate 2 halves of perforated disk assembly and use shouldered disk half. When using shouldered disk half, install screen side toward inlet box. †Wide radius elbow. ‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA-Not Allowed; pressure switch will not make.
NOTES:
1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.
3. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
6. Use 3-in. diameter vent termination kit for installations requiring 4-in diameter pipe.
—42—
3/8
3/16
DRILL
TRAP
HOUSING
PLUG
ID TUBE
4
MIN
TO OPEN
DRAIN
Fig. 39—Intake Housing Plug Fitting Drain
COMBUSTION–AIR INTAKE HOUSING
BURNER BOX
COMBUSTION– AIR PIPE
A96190
FURNACE
NOT IN HORIZONTAL SECTION
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
Fig. 38—Vent Pipe Diameter Transition Location
and Elbow Configuration
6. Install a field-supplied No. 6 or No. 8 sheet metal screw into combustion air pipe.
7. Install casing hole filler cap (factory-supplied in loose parts bag) in unused combustion air pipe casing hole.
NOTE: Do not attach combustion air intake pipe permanently to combustion air intake housing since it may be necessary to remove pipe for service of igniter or flame sensor.
ATTACHMENT OF COMBUSTION AIR INTAKE HOUSING PLUG FITTING
The combustion-air intake plug fitting must be installled in unused combustion air intake housing. This fitting must be attached by using RTV sealant, or by drilling a 1/8-in. hole in fitting, using hole in intake housing as a guide. Install a field-supplied No. 6 or No. 8 sheet metal screw.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur. A plugged drain connection has been provided on this fitting for use when moisture is found in combustion air intake pipe and combustion box.
If use of this drain connection is desired, drill out fitting’s tap plug with 3/16-in. drill and connect a field-supplied 3/8-in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped, as shown in Fig. 38.
NOTE: (Direct Vent/2-Pipe System ONLY). Moisture in combustion air intake may be a result of improper termination. Ensure combustion air pipe termination is similar to those as shown in Fig. 40 so that it will not be susceptible to area where light snow or others sources of moisture could be pulled in.
F. Vent Pipe
GENERAL
Furnace vent connection must be attached as shown in Fig. 35.
A93034
WARNING: CARBON MONOXIDE POISONING AND PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property damage, personal injury, or death. Vent pipes must be airtight.
NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing per Fig. 37. The minimum vent pipe length for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge condensate droplets. These condensate droplets
may be undesirable. A 12-in. minimum offset pipe section is recommended to reduce excessive condensate droplets from exiting vent pipe outlet. (See Fig. 40)
ATTACHMENT OF VENT PIPE
1. Determine vent pipe diameter and maximum pipe lengths using Table 11.
NOTE: (Direct Vent/2-Pipe) vent pipe system has the same diameter and same length as combustion air pipe as mentioned in section Assembly of Combustion Air Pipe (Direct Vent/2-Pipe system ONLY).
NOTE: Do not count elbows or pipe sections in terminations or within furnace, as indicated as shaded areas in Fig. 40 for Direct Vent/2-Pipe system, and Fig. 41 for Non-Direct Vent/1-Pipe system.
2. Determine location of vent pipe connection to inducer housing as shown in Fig. 35 for application.
3. Reposition elastomeric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing connection. Tighten clamp.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage. Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage.
4. Install pipe support (factory-supplied in loose parts bag) into selected furnace casing vent pipe hole. Pipe support should be positioned at bottom of casing hole.
—43—
reduce excessive condensate droplets from exiting the vent pipe.
COMBUSTION AIR
P
PIPE (NON-DIRECT
VENT/1-PIPE)
VENT PIPE
HORIZONTAL TO ROOF HORIZONTAL TO SIDEWALL
COMBUSTION AIR
IPE (NON-DIRECT
VENT/1-PIPE)
12 MIN
COMBUSTION AIR PIPE (DIRECT VENT /2-PIPE)
COMBUSTION AIR PIPE (DIRECT VENT /2-PIPE)
COMBUSTION AIR
PIPE (NON-DIRECT
VENT/1-PIPE)
VENT PIPE
VENT PIPE
COMBUSTION AIR
PIPE (NON-DIRECT
VENT/1-PIPE)
12 MIN
COMBUSTION AIR PIPE (DIRECT VENT /2-PIPE)
12 MIN
COMBUSTION AIR PIPE (DIRECT VENT/2-PIPE)
12 MIN
VERTICAL TO SIDEWALLVERTICAL TO ROOF
NOTE: A 12-In. minimum offset pipe section is recommended with
short (5-ft. to 8-ft) vent systems. This recommendation is to
VENT PIPE
A05094
Fig. 40—Short Vent (5 to 8 Ft) System
5. Be certain that mating surfaces of inducer housing connection elastomeric (rubber) coupling, and 2-in. diameter vent pipe are clean and dry. Assemble the elastomeric (rubber) vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2-in. diameter vent pipe through the elastomeric (rubber) coupling and fully into inducer housing connection until it touches a stop inside the inducer housing outlet. Tighten the screws on both clamps to 15-in-lb. of torque. pipe to inducer housing. Tighten the clamp screws to 15 in.-lb. of torque.
NOTE: Starting at furnace, slope vent pipe a minimum of 1/4-in. per linear ft with no sags between hangers.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage. Vent pipe must be installed and fully seated against inducer housing internalstop. Clamp must betightened to preventany condensate leakage.
6. Install casing hole filler cap (factory-supplied in loose parts bag) in unused vent pipe casing hole.
ATTACHMENT OF VENT EXTENSION PIPE
Furnaces with 100,00 Btuh and larger input are supplied with a PVC vent extension pipe (2-in. diameter by 12-in. long). This pipe has a built-in channel to assist vent condensate disposal. When this vent extension pipe is supplied, it MUST be used to connect the field vent pipe to furnace inducer housing on ALL upflow and downflow applications.
NOTE: See label on vent extension pipe for proper installation. This pipe may be shortened if an elbow is used to connect vent extension tube to field-installed vent pipe.
INSTALLATION GUIDELINES FOR COMBUSTION AIR PIPE AND VENT PIPE
It is recommended that all pipes be cut, prepared, and pre-assembled before permanently cementing any joint.
1. Attach combustion air pipe and vent pipe per instructions in sections Combustion Air Pipeand Vent Pipe.
2. Working from furnace to outside, cut pipe to required length(s).
3. Deburr inside and outside of pipe.
4. Chamfer outside edge of pipe for better distribution of primer and cement.
5. Clean and dry all surfaces to be joined.
6. Check dry fit of pipe and mark insertion depth on pipe.
—44—
Roof Termination (Preferred)
ve
r
Vertical separation between combustion air and vent 8 3/4 in. for 3 in. kit 6 3/4 in. for 2 in. kit
Maintain 12 in. min. clearance above highest anticipated snow level Maximum of 24 in. above roof
18 in. maximum
Note: "A" denotes 0 to < 2 in.
90°
At least 36 in.
At least 36 in
Concentric Vent and Combustion Air
A
Abandoned masonry used as raceway (per code)
12 in. min from
overhang or roof
12
in. separation
between bottom of
A
.
combustion air and bottom of vent
Maintain 12 min. clearance above highest anticipated snow level or grade whichever is greater
At least 36 in.
in.
Roof Termination (preferred)
A
Side wall termination
of less than 12
36 in.
A
Maintain 12 in. min. clearance above highest anticipated snow level, maximum of 24 in. above roof
1 in. maximum (type)
12 in. minimum from overhang or roof
A
t lea
3
st
6
in.
Concentric Vent and Combustion - Air Side Termination
A
Maintain 12 min. clearance abo highest anticipated snow level or grade whichever is greate
in.
At least
in.
Fig. 41—Combustion Air and Vent Pipe Termination
for Direct Vent (2-Pipe) System (All Sizes)
Roof Termination (Preferred)
Vent
Maintain 12 in.
minimum clearance
above highest anticipated
snow level maximum of
24 in. above roof.
Abandoned masonry used as raceway (per code)
12 in. min. from overhang or roof
Sidewall Termination
with Straight Pipe (preferred)
Maintain 12 in. minimum clearance above highest anticipated snow level or grade whichever is greater
6 in. minimum clearance
between wall and end of vent pipe.
10 in. maximum pipe length
12 in. min. from
overhang or roof
90°
Maintain 12 in. minimum clearance above highest anticipated snow level or grade
Side wall termination with 2 elbows (preferred)
whichever is greater.
Fig. 42—Vent Pipe Termination for Non-Direct
Vent (1-pipe) System (Sizes 040 Through 120 Only)
7. After pipes have been cut and preassembled, apply generous layer of cement primer to pipe fitting socket and end of pipe to insertion mark.
Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.
8. While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.
9. Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.
A05090
A05091
—45—
10. Handle pipe joints carefully until cement sets.
11. Support combustion air piping (if applicable) and vent piping a minimum of every 5 ft (3 ft for SDR-21 or -26 PVC) using perforated metal hanging strap.
12. Slope combustion air piping (if applicable) and vent piping downward towards furnace a minimum of 1/4 in. per linear ft with no sags between hangers.
13. Use appropriate methods to seal openings where combustion air pipe (if applicable) and vent pipe pass through roof or sidewall.
EXAMPLE: An 080-12 size furnace located in Indianapolis, elevation 650 ft above sea level, could be installed as either a direct vent/2-pipe system that requires 3 elbows and 32 ft of vent pipe, along with 5 elbows and 34 ft of combustion-air pipe OR a non-direct vent/1-pipe system that requires 3 elbows and 32 ft vent pipe. For a direct vent/2-pipe system, Table 11 indicates this application would allow a 2-in. diameter vent pipe, but require a 2-1/2 in. diameter combustion air pipe. According to Table 11, 2-in. diameter pipe is good for 35 ft with 3 elbows, but only 30 ft with 5 elbows. Therefore, 2-1/2 in. diameter pipe must be used for both vent and combustion-air pipes since larger required diameter must always be used for both pipes. For a non-direct vent/1-pipe system, Table 11 indicates that this application would allow a 2-in. diameter vent pipe. If same installations were in Albuquerque, elevation 5250 ft above sea level: For a direct vent/2-pipe system, Table 11 indicates that 2-1/2 in. diameter vent pipe and combustion-air pipe are required. For a non-direct vent/1-pipe system, Table 11 indicates that 2-1/2-in. diameter vent pipe is required. If same applications are to be installed at 5001- to 6000 ft elevation: For a direct vent/2-pipe system, 2-in. pipe is only good for 23 ft (with 3 elbows) and 17 ft (with 5 elbows). Therefore, 2-1/2 in. diameter combustion air and vent pipe must be used. For a non-direct vent/1-pipe system, a 2-in. diameter pipe is only good for 23 ft with 3 elbows. A 2-1/2-in. diameter vent pipe must be used.
G. Vent Termination
GENERAL
Combustion-air (direct vent/2-pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof. For vent termination clearance, refer to Table 8 for Direct Vent/2-Pipe system and Table 9 for Non-direct Vent/1-Pipe system. For exterior piping arrangements, refer to Fig. 40 for Direct Vent/2-Pipe system and Fig. 41 for Non-Direct/1-Pipe system.
Roof termination is preferred since it is less susceptible to damage or contamination, and it has less visible vent vapors. Sidewall termination require sealing or shielding of building surfaces with a corrosive resistance material due to corrosive combustion products of vent system.
NOTE: (Direct Vent/2-Pipe system ONLY). A factory accessory termination kit MUST be used. See section Vent Termination Kit (Direct Vent/2-Pipe System Only)in this instruction.
When determining appropriate location for termination, consider the following guidelines:
1. Comply with all clearance requirements stated in Table 8 or Table 9 per application.
2. Termination or termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment.
3. Termination or termination kit should be positioned so that it will not be affected by wind eddy, such as inside building corners, nor by recirculation of flue gases, airborne leaves, or light snow.
4. Termination or termination kit should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.
5. Termination or termination kit should be positioned where vent vapors are not objectionable.
EXTENDED EXPOSED SIDEWALL PIPES
Sidewall combustion air pipe termination (direct vent/2-pipe system only) and vent pipe termination may be extended beyond area shown in Fig. 40 or in Fig. 41 per application in outside ambient by insulating pipe as indicated in Table 10.
1. Determine combustion air pipe diameter (direct vent/2-pipe system only) and vent pipe diameter, as stated above, using total pipe length and number of elbows.
2. Using winter design temperature (used in load calculations), find appropriate temperature for your application and furnace model.
3. Determine required insulation thickness for exposed pipe length(s).
NOTE: Pipe length(ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 8.
VENT TERMINATION KIT (DIRECT VENT/2-PIPE SYSTEM ONLY)
NOTE: Always refer to the instructions in termination kit for the latest version. Combustion air and vent pipes MUST terminate outside structure. A factory accessory termination kit must be installed as shown in Table 12.
There are four options of vent/combustion air termination kits available as shown in Table 12. NOTE: Combustion air pipe must have the same diameter as vent pipe.
CONCENTRIC VENT/COMBUSTION AIR TERMINATION KIT
Determine an appropriate location for termination kit using the guidelines provided in section Vent Termination: Generalin this instruction.
1. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in. diameter hole for 3-in. kit.
2. Loosely assemble concentric vent/combustion air termination components together using instructions in kit.
—46—
DIRECT VENT (2-PIPE) TERMINATION KIT TERMINATION SYSTEM 2-in. Concentric Vent Kit Single Penetration of Wall or Roof 1, 1-1/2, 2, or 2-1/2
3-in. Concentric Vent Kit Single Penetration of Wall or Roof 2-1/2, 3 or 4 2-in. Termination Bracket Kit 2-Pipe Termination System 1, 1-1/2 or 2 3-in. Termination Bracket Kit 2-Pipe Termination System 2-1/2, 3 or 4
Table 12—Vent Termination Kit for Direct Vent/2-Pipe System
DIAM. OF COMBUSTION AIR AND VENT PIPES (IN INCHES)
3. Slide assembled kit with rain shield REMOVED through hole.
NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.
Roof terminations—Locate assembly through roof to appropriate height as shown in Fig. 40. Sidewall terminations—Locate assembly through sidewall with rain shield positioned no more than 1-in. from wall as shown in Fig. 40.
4. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
5. Check required dimensions as shown in Fig. 40.
TWO-PIPE TERMINATION KIT
Determine an appropriate location for termination kit using the guidelines provided in section Vent Termination: Generalin this instruction.
1. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.
2. Loosely install elbow in bracket and place assembly on combustion-air pipe.
Roof terminations—Loosely install pipe coupling on properly cut vent pipe. Coupling must be positioned so bracket will mount as shown in Fig. 40.
For applications using combustion-air pipe option, indicated by dashed lines in Fig. 40, install 90° street elbow into 90° elbow, making a U-fitting. A 180° U-fitting may be used.
Sidewall terminations—Install bracket as shown in Fig. 40. For applications using vent pipe option indicated by dashed lines in Fig. 40, rotate vent elbow 90° from position shown in Fig. 40.
3. Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.
4. Check required dimensions as shown in Fig. 40.
MULTIVENTING AND VENT TERMINATIONS
When 2 or more PG9MAB Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent PG9MAB furnaces. (Direct Vent/2-Pipe System ONLY)-When 2 or more PG9MAB furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 40, but next vent termination must be at least 36 in. away from first 2 terminations. It is important that vent terminations be made as shown in Fig. 40 to avoid recirculation of flue gases.
PROCEDURE 8—CONDENSATE DRAIN A. General
Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications.
Condensate trap MUST be used for all applications. An external trap is not required when connecting the field drain to this condensate trap. The field drain connection (condensate trap or drain tube coupling) is sized for 1/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID tube connection. Drain pipe and fittings must conform to ANSI standards and ASTM D1785, D2466 or D2846. CPVC or PVC cement must conform to ASTM
D2564 or F493. Primer must conform to ASTM F656. In Canada, use CSA or ULC listed schedule 40 CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid condensate spillage, select a pump with an overflow switch.
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. Unit must not be installed, operated, and then turned off and left in an unconditioned structure during cold weather when temperature drops to 32°F and below unless drain trap and drain line have adequate freeze protection. See Service and Maintenance Instructions for winterizing procedures. (See Fig. 16.)
Furnace condensate is mildly acidic, typically in the pH range of 3.2 to 4.5. Due to corrosive nature of this condensate, a condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required.
B. Application
The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field-supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment’s drain.
—47—
OPEN STAND
PIPE FOR
A/C OR
HUMIDIFIER
DRAIN
TEE
CONDENSATE TRAP
WIRE TIE(S)
TO OPEN DRAIN
Fig. 43—Example of Field Drain Attachment
(3 WRAPS MINIMUM)
A94054
HEAT TAPE
A93036
Fig. 44—Condensate Trap Heat Tape
See Fig. 43 for example of possible field drain attachment using 1/2-in. CPVC or PVC tee for vent and A/C or humidifier drain connection. Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.
WARNING: PERSONAL INJURY HAZARD
Caution should be taken to prevent draining where slippery conditions could cause personal injuries. Excessive condensate draining may cause saturated soil conditions which could result in damage to plants.
C. Condensate Drain Protection
Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft at 120v and 40°F self-regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer’s recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
2. Locate heat tape between sides of condensate trap back. (See Fig. 44.)
3. Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig. 44.)
4. Wrap field drain pipe with remaining heat tape, approximately 1 wrap per ft.
5. When using field-supplied heat tape, follow heat tape manufacturer’s instructions for all other installation guidelines.
START-UP, ADJUSTMENTS AND SAFETY CHECK
PROCEDURE 1—GENERAL
1. Furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation.
NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control center LED status light will flash rapidly and furnace will not operate.
2. Thermostat wire connections at terminals R, W, G, and Y must be made at 24-v terminal block on furnace control.
3. Natural gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc).
4. Blower access panel must be in place to complete 115-v electrical circuit to furnace.
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. These furnaces are equipped with a manual reset limit switch in burner box. This switch will open and shut off power to gas control valve if an overheat condition (flame rollout)occurs inburner enclosure.Correct inadequate combustion-air supply or improper venting condition and reset switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset switch for continuity. If necessary, press button to reset switch.
PROCEDURE 2—PRIME CONDENSATE TRAP WITH WATER
CAUTION: UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent unit operation. Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has 2 internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
—48—
A94208
Fig. 45—Inducer Housing Drain Cap
Fig. 46—Filling Condensate Trap
1. Remove upper inducer housing drain connection cap. (See Fig. 45.)
2. Connect field-supplied 1/2-in. ID tube to upper inducer housing drain connection.
3. Insert field-supplied funnel into tube.
4. Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain.
(See Fig. 46.)
5. Remove funnel and tube from inducer housing and replace drain connection cap and clamp.
PROCEDURE 3—PURGE GAS LINES
A94209
WARNING:
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in a fire, explosion, personal injury, or death. Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
If not previously done, purge lines after all connections have been made and check for leaks.
PROCEDURE 4—SEQUENCE OF OPERATION
CAUTION: FURNACE MAY NOT OPERATE
Failure to follow this caution may result in furnace operation stopping and water pipes freezing during cold weather. Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
Using schematic diagram, follow sequence of operation through different modes. (See Fig. 34.) Read and follow wiring diagram carefully. NOTE: If 115-v power supply to furnace or blower access panel switch is interrupted during a call for heat, blower operates for 90 sec when power
is restored before heating cycle is resumed.
A. Heating Mode
(See Fig. 31 for thermostat connections.)
The wall thermostat calls for heat, closing the R to W circuit. The furnace control performs a self-check, verifies the pressure switch contacts PRS are open, and starts the inducer motor IDM.
a. Inducer Prepurge Period- As the inducer motor IDM comes up to speed, the pressure switch contacts PRS close, 24 vac power is
supplied for a field installed humidifier at the HUM terminal and the control begins a 15-second prepurge period.
—49—
b. Igniter Warm-Up- At the end of the prepurge period, the Hot-Surface Igniter HSI is energized for a 17-second igniter warm-up period. c. Trial-for-Ignition Sequence- When the igniter warm-up period is completed the main gas valve relay contacts GVR close to energize
the gas valve GV, the gas valve opens. The gas valve GV permits gas flow to the burners where it is ignited by the Hot Surface Igniter HSI. Five seconds after the GVR closes, a 2-second flame period begins. The HSI igniter will remain energized until the flame is sensed or until the 2-second flame proving period begins.
d. Flame-Proving- When the burner flame is proved at the flame-proving sensor electrode FSE, the furnace control CPU begins the
blower-ON delay period and continues to hold the gas valve GV open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV, and the control CPU will repeat the ignition sequence for up to three more Trials-For-Ignition before going to Ignition-Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W, G, R, etc.)
If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode and operate the inducer motor IDM until flame is no longer proved.
e. Blower-On Delay- If the burner flame is proven, the blower motor is energized on HEAT speed 66 seconds (040 through 120 sizes) or
45 seconds (140 size) after the gas valve GV is energized. Simultaneously, the electronic air cleaner terminal EAC-1 is energized and remains energized as long as the blower motor BLWM is energized.
f. Blower-Off Delay- When the thermostat is satisfied, the R-to-W circuit is opened, de-energizing the gas valve GV, stopping gas flow
to the burners, and de-energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a 15-second (040 through 120 sizes) or 5-second (140 size) post-purge period. The blower motor BLWM and air cleaner terminal EAC-1 will remain energized for 90, 120, 150, or 180 seconds (depending on the blower-OFF delay selection). The furnace control CPU is factory-set for a 120-second blower-OFF delay.
B. Cooling Mode
(See Fig. 31 for thermostat connections) The thermostat closes the R-to-G-and-Y circuits. The R-to-Y circuit starts the outdoor unit, and the R-to-G and-Y circuits start the furnace blower
motor BLWM on COOL speed. The electronic air cleaner terminal EAC-1 is energized with 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R-to-G-and-Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating on the COOL speed for an additional 90 seconds. Cut jumper J2 to reduce the cooling off-delay to 5 seconds. (See Fig. 35.)
C. Continuous Blower Mode
When the R-to-G circuit is closed by the thermostat, the blower motor BLWM will operate on continuous-blower speed (same as HEAT speed). Terminal EAC-1 is energized as long as the blower motor BLWM is energized. During a call for heat,the blower BLWM will stop during igniter warm-up (17 seconds), ignition (7 seconds), and blower-ON delay (66 or 45 seconds for 040 through 120 sizes or for 140 size), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower-ON delay period at HEAT speed. In heating, the furnace control CPU will continue running the blower motor BLWM at HEAT speed after the selected blower-OFF delay period is completed. When the thermostat calls for cooling, the blower motor BLWM will operate at COOL speed. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds on COOL speed before reverting back to HEAT speed. Jumper J2 can be cut to reduce the cooling off-delay to 5 seconds. (See Fig. 35.)
6. Insert 2-in. diameter pipe into inducer housing through neoprene coupling and clamp in inducer housing. Tighten clamp. When the R-to-G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
D. Heat Pump Mode
When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. When the R-to-W-and-Y or R-to-W-and-Y-and-G circuits are energized the furnace control CPU will continue to turn on the blower motor BLWM at HEAT speed, and begin a heating cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 seconds then come back on at HEAT speed. When the W input signal disappears, the furnace control begins a normal inducer post-purge period and the blower switches to COOL speed after a 3 second delay. If the R-to-W-and-Y-and-G signals disappear at the same time, the blower motor BLWM will remain on for the selected blower-OFF delay period. If the R-to-W-and-Y signals disappear, leaving the G signal, the blower motor BLWM will continue running the blower motor BLWM at HEAT speed after the selected blower-OFF delay period is completed.
Control initiates a 90-sec blower only on period before starting another heat pump cycle if there is a power interruption. Anytime control senses false flame, control locks out of heating mode. This reaction occurs because control ignores W input due to false flame signal and, as a result, sees only Y input and goes into cooling mode blower off delay. All other control functions remain in standard format.
E. Component Test NOTE: The furnace control component test allows all components to run for a short time; except the gas valve and humidifier terminal HUM
are not energized for safety reasons. The EAC-1 terminal is energized when the blower is energized. This feature helps diagnose a system problem in case of a component failure. The component test feature will not operate if any thermostat signal is present ant the control and not until all time delays are completed.
NOTE: Record the status code BEFORE opening the blower access door and before shutting off power to the furnace. Opening the blower access door will open the blower door switch and shut off power within the furnace. When power to the furnace is shut off by either method, the status code will be lost because the code is not stored while power is removed for any reason.
—50—
To Begin Component Self-Test:
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in electrical shock, personal injury, or death. Blower access panel door switch opens 115-v power to control center. No component operation can occur. Caution must be taken when manually closing this switch for service purposes.
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control.
3. Manually close blower door switch.
4. For approximately 2 sec, short (jumper) the C
OM-24v terminal on control to the TEST/TWIN 3/16-inch quick-connect terminal on control
until the LED goes out. Remover jumper from terminals. (See Fig. 35.)
NOTE: If TEST/TWIN and C
OM-24v terminals are jumpered longer than 2 sec, LED will flash rapidly and ignore component test status code
retrieval request. Component test sequence is as follows:
a. LED will display previous status code 4 times. b. Inducer motor starts and continues to run until Step f of component test sequence. c. After 7 seconds the hot surface igniter is energized for 15 sec, then off. d. Blower motor operates on HEAT speed for 10 sec. e. Blower motor operates on COOL speed for 10 sec. f. Inducer motor stops.
5. Reconnect R lead to furnace control, remove tape from blower door switch, and re-install blower door.
6. Operate furnace per instruction on outer door.
7. Verify furnace shut down by lowering thermostat setting below room temperature.
8. Verify that furnace restarts by raising thermostat setting above room temperature.
PROCEDURE 5—ADJUSTMENTS A. Set Gas Input Rate
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. In the U.S.A., the input ratings for altitudes above 2000 ft must be reduced by 2 percent for each 1000 ft above sea level. In Canada, the input ratings must be derated by 5 percent for altitudes of 2000 ft to 4500 ft above sea level. Furnace input rate must be within ±2 percent of input on furnace rating plate adjusted for altitude.
1. Determine natural gas orifice size and manifold pressure for correct input.
a. Obtain average gas heat value (at installed altitude) from local gas supplier. b. Obtain average gas specific gravity from local gas supplier. c. Verify furnace model and size. Table 13 can only be used for model PG9MAB furnaces with heating sizes of 040 through 120. Table
14 can only be used for model PG9MAB furnaces with heating size of 140.
d. Find installation altitude in Table 13 or 14.
NOTE: For Canada altitudes of 2001 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 13 or 14.
e. Find closest natural gas heat value and specific gravity in Table 13 or 14. f. Followheat value and specific gravity lines to point of intersection to find orifice size and manifold pressure settings for proper operation.
EXAMPLE: (0—2000 ft altitude using Table 13) Heating value = 1050 Btu/cu ft Specific gravity = 0.62 Therefore: Orifice No. 45
Manifold pressure 3.6-in. wc * Furnace is shipped with No. 45 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain the proper input rate.
Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE; ALWAYS CHECK AND VERIFY.
2. Adjust manifold pressure to obtain input rate.
NOTE: Manifold pressure must always be measured with burner enclosure front REMOVED. Gas meter must always be clocked with burner enclosure front INSTALLED.
a. Remove burner enclosure front. b. Remove cap that conceals adjustment screw for gas valve regulator. (See Fig. 48.) c. Jumper R and W thermostat connections on control to start furnace operation.
—51—
Table 13—Model PG9MAB Orifice Size and Manifold Pressure for Correct Input
For Use With 040 Through 120 Size Furnaces Only
(Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)*
ALTITUDE
RANGE
(FT)
0 925 44 3.5 44 3.7 44 3.8 43 3.4 43 3.5
to 975 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6
2000 1025 45 3.5 45 3.6 45 3.7 44 3.2 44 3.3
U.S.A. and Canada
0% 1075 45 3.2 45 3.3 45 3.4 45 3.5 45 3.6
derate 1100 47 3.6 47 3.7 45 3.2 45 3.4 45 3.5
ALTITUDE
RANGE
(FT)
U.S.A. 775 43 3.8 42 3.2 42 3.3 42 3.4 42 3.5
Altitudes 800 43 3.5 43 3.7 43 3.8 42 3.2 42 3.3
2001 to 825 44 3.8 43 3.4 43 3.6 43 3.7 43 3.8
3000 850 44 3.6 44 3.7 44 3.8 43 3.5 43 3.6
or 875 44 3.4 44 3.5 44 3.6 44 3.7 43 3.4
Canada 900 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6
Altitudes 925 45 3.7 45 3.8 44 3.2 44 3.3 44 3.4
2001 to 950 45 3.5 45 3.6 45 3.7 45 3.8 44 3.3
U.S.A. and Canada
4500 975 45 3.3 45 3.4 45 3.5 45 3.6 45 3.8
5% 1000 45 3.1 45 3.2 45 3.4 45 3.5 45 3.6
derate 1025 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
ALTITUDE
RANGE
(FT)
3001 825 44 3.5 44 3.6 44 3.8 43 3.4 43 3.5
to 875 45 3.8 44 3.2 44 3.3 44 3.5 44 3.6
U.S.A. Only
4000 925 45 3.4 45 3.5 45 3.6 45 3.7 44 3.2
7% 975 45 3.0 45 3.2 45 3.3 45 3.4 45 3.5
derate 1000 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
* Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
850 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 875 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2 900 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7
950 44 3.4 44 3.5 44 3.6 44 3.7 44 3.8
1000 45 3.7 45 3.8 44 3.2 44 3.4 44 3.5
1050 45 3.3 45 3.4 45 3.6 45 3.7 45 3.8
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
750 43 3.7 43 3.8 42 3.3 42 3.4 42 3.5 775 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2 800 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7
850 44 3.3 44 3.4 44 3.5 44 3.7 44 3.8
900 45 3.6 45 3.7 45 3.8 44 3.3 44 3.4
950 45 3.2 45 3.3 45 3.4 45 3.5 45 3.7
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—52—
Table 13—Model PG9MAB Orifice Size and Manifold Pressure for Correct Input (Continued)
For Use With 040 Through 120 Size Furnaces Only
(Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
4001 800 44 3.5 44 3.6 44 3.7 44 3.8 43 3.4
to 850 45 3.7 45 3.8 44 3.3 44 3.4 44 3.5
U.S.A. Only
5000 900 45 3.3 45 3.4 45 3.5 45 3.6 45 3.8
9% 925 45 3.1 45 3.2 45 3.3 45 3.4 45 3.6
derate 950 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
ALTITUDE
RANGE
(FT)
5001 800 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6
to 850 45 3.4 45 3.5 45 3.6 45 3.8 44 3.2
U.S.A. Only
6000 900 45 3.0 45 3.1 45 3.3 45 3.4 45 3.5
11% 950 45 2.7 45 2.8 45 2.9 45 3.0 45 3.1
derate 975 45 2.6 45 2.7 45 2.8 45 2.9 45 2.9
ALTITUDE
RANGE
(FT)
6001 725 44 3.6 44 3.7 44 3.8 43 3.4 43 3.5
to 775 45 3.8 44 3.2 44 3.3 44 3.4 44 3.5
U.S.A. Only
7000 825 45 3.3 45 3.4 45 3.6 45 3.7 45 3.8
13% 850 45 3.1 45 3.2 45 3.4 45 3.5 45 3.6
derate 875 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
* Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4 750 43 3.4 43 3.5 43 3.7 43 3.8 42 3.2 775 44 3.7 44 3.8 43 3.4 43 3.5 43 3.7
825 44 3.2 44 3.4 44 3.5 44 3.6 44 3.7
875 45 3.5 45 3.6 45 3.7 44 3.2 44 3.3
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
700 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4 725 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8 750 44 3.6 44 3.7 43 3.4 43 3.5 43 3.6 775 44 3.4 44 3.5 44 3.6 44 3.7 43 3.4
825 45 3.6 45 3.7 44 3.2 44 3.3 44 3.4
875 45 3.2 45 3.3 45 3.4 45 3.6 45 3.7
925 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
1000 45 2.5 45 2.5 45 2.6 45 2.7 45 2.8
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
650 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6 675 43 3.6 43 3.7 43 3.8 42 3.2 42 3.3 700 44 3.8 43 3.4 43 3.6 43 3.7 43 3.8
750 44 3.3 44 3.4 44 3.6 44 3.7 44 3.8
800 45 3.5 45 3.7 45 3.8 44 3.2 44 3.3
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—53—
Table 13—Model PG9MAB Orifice Size and Manifold Pressure for Correct Input (Continued)
For Use With 040 Through 120 Size Furnaces Only
(Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
7001 700 44 3.5 44 3.6 44 3.8 43 3.4 43 3.5
to 750 45 3.7 45 3.8 44 3.3 44 3.4 44 3.5
U.S.A. Only
8000 800 45 3.3 45 3.4 45 3.5 45 3.6 45 3.7
15% 825 45 3.1 45 3.2 45 3.3 45 3.4 45 3.5
derate 850 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
ALTITUDE
RANGE
(FT)
8001 650 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7
to 700 44 3.2 44 3.3 44 3.4 44 3.6 44 3.7
U.S.A. Only
9000 750 45 3.4 45 3.5 45 3.6 45 3.8 44 3.2
17% 775 45 3.2 45 3.3 45 3.4 45 3.5 45 3.6
derate 800 45 3.0 45 3.1 45 3.2 45 3.3 45 3.4
ALTITUDE
RANGE
(FT)
9001 625 44 3.7 44 3.8 43 3.5 43 3.6 43 3.7
to 675 45 3.8 44 3.3 44 3.4 44 3.5 44 3.6
U.S.A. Only
10,000 725 45 3.3 45 3.4 45 3.6 45 3.7 45 3.8
19% 750 45 3.1 45 3.2 45 3.3 45 3.4 45 3.5
derate 775 45 2.9 45 3.0 45 3.1 45 3.2 45 3.3
* Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
625 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6 650 43 3.5 43 3.7 43 3.8 42 3.2 42 3.3 675 44 3.8 43 3.4 43 3.5 43 3.6 43 3.7
725 44 3.3 44 3.4 44 3.5 44 3.6 44 3.7
775 45 3.5 45 3.6 45 3.7 45 3.8 44 3.3
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
600 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6 625 43 3.5 43 3.6 43 3.8 42 3.2 42 3.3
675 44 3.5 44 3.6 44 3.7 44 3.8 43 3.4
725 45 3.6 45 3.8 44 3.2 44 3.3 44 3.4
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
575 43 3.8 42 3.2 42 3.3 42 3.5 42 3.6 600 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3
650 44 3.4 44 3.5 44 3.7 44 3.8 43 3.4
700 45 3.6 45 3.7 45 3.8 44 3.3 44 3.4
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—54—
Table 14—Model PG9MAB Orifice Size and Manifold Pressure for Correct Input
For Use with 140 Size Furnaces Only
(Tabulated Data Based on 23,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level) *
ALTITUDE
RANGE
(FT)
0 925 42 3.4 42 3.5 42 3.6 42 3.7 42 3.8
to 975 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
2000 1025 43 3.3 43 3.4 43 3.6 43 3.7 43 3.8
U.S.A. and Canada
0% 1050 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
derate 1075 44 3.5 44 3.6 43 3.2 43 3.3 43 3.4
ALTITUDE
RANGE
(FT)
U.S.A. 775 41 3.7 41 3.8 40 3.6 40 3.7 39 3.6
Altitudes 800 42 3.8 41 3.6 41 3.7 41 3.8 40 3.6
2001 to 825 42 3.6 42 3.7 41 3.5 41 3.6 41 3.7
3000 850 42 3.4 42 3.5 42 3.6 42 3.7 41 3.5
or 875 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6
Canade 900 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
Altitudes 925 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3
2001 to 950 43 3.3 43 3.4 43 3.5 43 3.7 43 3.8
U.S.A. and Canada
4500 975 43 3.1 43 3.3 43 3.4 43 3.5 43 3.6
5% 1000 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
derate 1025 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
ALTITUDE
RANGE
(FT)
3001 825 42 3.3 42 3.4 42 3.6 42 3.7 42 3.8
to 875 43 3.6 43 3.7 42 3.2 42 3.3 42 3.4
U.S.A. Only
4000 925 43 3.2 43 3.3 43 3.5 43 3.6 43 3.7
7% 975 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
derate 1000 43 2.8 43 2.9 43 3.0 43 3.0 43 3.1
* Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
850 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8 875 42 3.8 41 3.5 41 3.6 41 3.7 41 3.8 900 42 3.5 42 3.7 42 3.8 41 3.5 41 3.6
950 42 3.2 42 3.3 42 3.4 42 3.5 42 3.6
1000 43 3.5 43 3.6 43 3.7 42 3.2 42 3.3
1100 44 3.3 44 3.4 44 3.5 43 3.2 43 3.3
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
750 41 3.6 41 3.8 40 3.6 40 3.7 40 3.8 775 42 3.8 41 3.5 41 3.6 41 3.7 40 3.6 800 42 3.5 42 3.7 42 3.8 41 3.5 41 3.6
850 43 3.8 42 3.2 42 3.4 42 3.5 42 3.6
900 43 3.4 43 3.5 43 3.6 43 3.8 42 3.2
950 43 3.1 43 3.2 43 3.3 43 3.4 43 3.5
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—55—
Table 14—Model PG9MAB Orifice Size and Manifold Pressure for Correct Input (Continued)
For Use with 140 Size Furnaces Only
(Tabulated Data Based on 23,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
4001 775 42 3.5 42 3.6 42 3.7 42 3.8 41 3.6
to 825 43 3.7 42 3.2 42 3.3 42 3.4 42 3.5
5000 875 43 3.3 43 3.4 43 3.6 43 3.7 43 3.8
U.S.A. Only
9% 925 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
derate 950 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
ALTITUDE
RANGE
(FT)
5001 800 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
to 850 43 3.3 43 3.4 43 3.5 43 3.6 43 3.7
U.S.A. Only
6000 900 43 2.9 43 3.0 43 3.1 43 3.2 43 3.3
11% 950 43 2.6 43 2.7 43 2.8 43 2.9 43 3.0
derate 975 43 2.5 43 2.6 43 2.6 43 2.7 43 2.8
ALTITUDE
RANGE
(FT)
6001 700 42 3.6 42 3.7 41 3.5 41 3.6 41 3.7
to 750 43 3.8 42 3.3 42 3.4 42 3.5 42 3.6
7000 800 43 3.4 43 3.5 43 3.6 43 3.7 43 3.8
U.S.A. Only
13% 850 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
derate 875 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
* Orifice numbers shown in BOLD are factory installed. Percents of derate are based on midpoints of U.S. altitude ranges.
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8 750 42 3.7 42 3.8 41 3.6 41 3.7 41 3.8
800 42 3.3 42 3.4 42 3.5 42 3.6 42 3.7
850 43 3.5 43 3.6 43 3.8 42 3.2 42 3.3
900 43 3.1 43 3.3 43 3.4 43 3.5 43 3.6
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
700 41 3.5 41 3.7 41 3.8 40 3.6 40 3.7 725 42 3.7 42 3.8 41 3.5 41 3.6 41 3.8 750 42 3.4 42 3.5 42 3.7 42 3.8 41 3.5 775 42 3.2 42 3.3 42 3.4 42 3.5 42 3.7
825 43 3.5 43 3.6 43 3.7 43 3.8 42 3.2
875 43 3.1 43 3.2 43 3.3 43 3.4 43 3.5
925 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
1000 43 2.3 43 2.4 43 2.5 43 2.6 43 2.7
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
650 41 3.8 40 3.6 40 3.7 40 3.8 39 3.7 675 41 3.5 41 3.6 41 3.7 40 3.6 40 3.7
725 42 3.4 42 3.5 42 3.6 42 3.7 42 3.8
775 43 3.6 43 3.7 43 3.8 42 3.3 42 3.4
825 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
0.58 0.60 0.62 0.64 0.66
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
0.58 0.60 0.62 0.64 0.66
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
SPECIFIC GRAVITY OF NATURAL GAS
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
Orifice
No.
Orifice
No.
Orifice
No.
Manifold
Pressure
Manifold
Pressure
Manifold
Pressure
—56—
BURNER
ORIFICE
Fig. 47—Burner Orifice
A93059
d. Turn adjusting screw, counterclockwise (out) to decrease manifold pressure or clockwise (in) to increase manifold pressure.
NOTE: This furnace has been approved for a manifold pressure of 3.2 in. wc to 3.8 in. wc when installed at altitudes up to 2000 ft. For altitudes above 2000 ft, the manifold pressure can be adjusted from 2.0 in. wc to 3.8 in. wc. If manifold pressure is outside of this range, change burner orifice to obtain pressure in this range.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life. DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulatedmanifold pressure and result in excess overfire and heat exchanger failures.
NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in component damage due to flame impingement of burners and heat exchangers. DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flames. (See Fig. 47.)
e. Replace gas valve regulator adjustment screw cap. f. Replace burner enclosure front and verify adjusted gas input rate using method outlined in item 3. g. Look through sight glass in burner enclosure and check burner flame. Burner flame should be clear blue, almost transparent. (See Fig.
49.)
h. Remove jumper from R and W.
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas meter.
a. Calculate high-altitude adjustment (if required).
UNITED STATES At altitudes above 2000 ft, this furnace has been approved for a 2% derate for each 1000 ft above sea level. See Table 15 for derate
multiplier factor.
EXAMPLE: 100,000 Btuh input furnace installed at 4300 ft.
FURNACE INPUT RATE
AT SEA LEVEL
100,000 X 0.91 = 91,000
X DERATE MULTIPLIER FACTOR =
CANADA At installation altitudes from 2001 to 4500 ft, this furnace must be derated 5% by an authorized Gas Conversion Station or Dealer. To
determine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor. b. Reinstall burner box cover. c. Gas valve regulator seal cap MUST be installed. d. Turn off all other gas appliances and pilots. e. Start furnace and let operate for 3 minutes. f. Measure time (in sec) for gas meter test dial to complete 1 revolution.
FURNACE INPUT RATE
AT INSTALLATION ALTITUDE
—57—
REGULATOR SEAL CAP
REGULATOR ADJUSTMENT SCREW
ON/OFF SWITCH
REGULATOR SPRING (PROPANE - WHITE, 6 TURNS NATURAL - SILVER, 10 TURNS)
GAS PRESSURE REGULATOR
INLET PRESSURE T AP
ADJUSTMENT
MANIFOLD PRESSURE T AP
Fig. 48—Redundant Automatic Gas Valve
Table 15—Altitude Derate Multiplier for U.S.A.
ALTITUDE (FT) % OF DERATE DERATE MULTIPLIER FACTOR*
0—2000 0 1.00 2001—3000 4—6 0.95 3001—4000 6—8 0.93 4001—5000 8—10 0.91 5001—6000 10—12 0.89 6001—7000 12—14 0.87 7001—8000 14—16 0.85 8001—9000 16—18 0.83
9001—10,000 18—20 0.81
* Derate multiplier factor is based on midpoint altitude for altitude range.
A03142
BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 49—Burner Flame
g. Refer to Table 16 for cu ft of gas per hr. h. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft) using natural gas heating value from local gas utility/supplier.
EXAMPLE: (0—2000 ft altitude) Furnace input from rating plate is 100,000 Btuh. Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 975 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 70 sec Gas rate = 103 cu ft/hr (from Table 15) Btu heating input = 103 X 975 = 100,425 Btuh In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.
B. Set Temperature Rise
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate. Temperature rise must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise range or above.
Determine and adjust air temperature rise as follows:
1. Placethermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.
—58—
Table 16—Gas Rate (Cu Ft/Hr)
SECONDS FOR 1 REVOLUTION
10 11 12 13 14
15 16 17 18 19
20 21 22 23 24
25 26 27 28 29
30 31 32 33 34
35 36 37 38 39
40 41 42 43 44
45 46 47 48 49
1 cu ft
360 327 300 277 257
240 225 212 200 189
180 171 164 157 150
144 138 133 129 124
120 116 113 109 106
103 100 97 95 92
90 88 86 84 82
80 78 76 75 73
SIZE OF TEST DIAL
2 cu ft
720 655 600 555 514
480 450 424 400 379
360 343 327 313 300
288 277 267 257 248
240 232 225 218 212
206 200 195 189 185
180 176 172 167 164
160 157 153 150 147
5 cu ft
1800 1636 1500 1385 1286
1200 1125 1059 1000 947
900 857 818 783 750
720 692 667 643 621
600 581 563 545 529
514 500 486 474 462
450 439 429 419 409
400 391 383 375 367
SECONDS FOR 1 REVOLUTION
50 51 52 53 54
55 56 57 58 59
60 62 64 66 68
70 72 74 76 78
80 82 84 86 88
90 92 94 96 98
100 102 104 106 108
110 112 116 120 124
1 cu ft
72 71 69 68 67
65 64 63 62 61
60 58 56 54 53
51 50 48 47 46
45 44 43 42 41
40 39 38 38 37
36 35 35 34 33
33 32 31 30 29
SIZE OF TEST DIAL
2 cu ft
144 141 138 136 133
131 129 126 124 122
120 116 112 109 106
103 100 97 95 92
90 88 86 84 82
80 78 76 75 74
72 71 69 68 67
65 64 62 60 58
5 cu ft
360 355 346 340 333
327 321 316 310 305
300 290 281 273 265
257 250 243 237 231
225 220 214 209 205
200 196 192 188 184
180 178 173 170 167
164 161 155 150 145
3. Adjust temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase
temperature rise.
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death. Disconnect 115-v electrical power before changing speed tap.
4. To change blower motor speed selections for heating mode, remove blower motor lead from control center HEAT terminal. (See Fig. 35.)
Select desired blower motor speed lead from 1 of the other motor leads and relocate it to HEAT terminal. See Table 18 for lead color identification. Reconnect original lead on SPARE terminal.
Follow this same procedure for proper selection of COOL speed selection.
C. Blower Off Delay (Heat Mode)
The blower off delay has 4 adjustable settings from 90 sec to 180 sec. (See Table 18.) The blower off delay jumpers are located on the furnace control board (See Fig. 35). To change the blower off delay setting, move the jumper from one set of pins on the control board to the pins used for the desired blower off delay. Factory blower off delay setting is 120 sec.
D. Set Thermostat Heat Anticipator
When using a nonelectronic thermostat, the thermostat heat anticipator must be set to match amp draw of the electrical components in R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 50 illustrates an easy method of obtaining actual amp draw. The amp reading should be taken after blower motor has started and furnace is heating. Connect ammeter wires as shown in Fig. 50. The thermostat anticipator should NOT be in the circuit while measuring current. If thermometer has no subbase, the thermostat must be disconnected from R and W wires during current measurement. See thermostat manufacturer’s instructions for adjusting heat anticipator and for varying heating cycle length. For an electronic thermostat, set cycle rate for 3 cycles per hour.
PROCEDURE 6—CHECK SAFETY CONTROLS
This section covers the safety controls that must be checked before installation is complete. The flame sensor, gas valve, and pressure switch were all checked in the Start-up procedure section as part of normal operation.
—59—
Table 17—Speed Selector
COLOR SPEED Black High Cool
Yellow (When Present) Medium High Spare Blue Medium Low Heat Red Low Spare White Common Com
FACTORY-SHIPPED CONNECTION
Table 18—Blower Off Delay Setup Position
PINS 1 AND 2 2 AND 3 3 AND 4 4 AND 5
Time (in sec) 90 120 150 180
THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED
HOOK-AROUND
VOLT/AMMETER
R Y W G
10 TURNS
FROM UNIT 24-VOLT TERMINAL BLOCK
EXAMPLE:
5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201
Fig. 50—Amp Draw Check with Ammeter
A. Check Primary Limit Control
This control shuts off gas control system and energizes air-circulating blower motor if furnace overheats. Recommended method of checking this limit control is to gradually block off return air after furnace has been operating for a period of at least 5 minutes. As soon as limit control has shut off burners, return-air opening should be unblocked to permit normal air circulation. By using this method to check limit control, it can be established that limit is functioning properly and operates if there is a restricted return-air duct or motor failure. If limit control does not function during this test, cause must be determined and corrected.
B. Check Pressure Switch
This control proves operation of draft inducer. Check switch operation as follows:
1. Turn off 115-v power to furnace.
2. Remove main furnace door and disconnect inducer motor lead wires from wire harness.
3. Turn on 115-v power to furnace.
4. Set thermostat to call for heat and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow, and control status code LED light flashes a Status Code 31. If hot surface igniter glows when inducer motor is disconnected, shut furnace down immediately. Determine reason pressure switch did not function properly and correct condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor leads, reinstall main furnace door, and turn on 115-v power supply.
—60—
CHECKLIST
1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Verify that blower and main access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Guide with owner.
7. Leave literature packet near furnace.
—61—
CHECKLIST—DIRECT VENT INSTALLATIONS
LOAD CALCULATION ____________ Heating Load (Btuh) ____________ Cooling Load (Btuh) ____________ Furnace Model Selection COMBUSTION AIR AND VENT PIPING Termination Location ________ Roof or Sidewall ________ Termination Kit — 2 Pipe or Concentric ________ Combustion-Air Pipe Length ________ Combustion-Air Pipe Elbow Quantity ________ Vent Pipe Length ________ Vent Pipe Elbow Quantity ________ Pipe Diameter Determined from Sizing Table ________ Pipe Sloped To Furnace Pipe Insulation ________ Over Ceilings ________ Low-Ambient Exposed Pipes Condensate Drain ________ Unit Level or Pitched Forward ________ Internal Tubing Connections Free of Kinks and Traps ________ External Drain Connection Leak Tight and Sloped ________ Condensate Trap Primed before Start-Up ________ Heat Tape Installed if Required CHECKLIST—START-UP ________ Gas Input Rate (Set Within 2 percent of Rating Plate) ________ Temperature Rise Adjusted Thermostat Anticipator ________ Anticipator Setting Adjusted ________ Cycle Rate (3 Cycles per Hr) Selected Safety Controls Check Operation ________ Primary Limit ________ Pressure Switch
or
—62—
CHECKLIST—NON-DIRECT VENT INSTALLATIONS
LOAD CALCULATION ____________ Heating Load (Btuh) ____________ Cooling Load (Btuh) ____________ Furnace Model Selection VENT PIPING Termination Location ________ Roof or Sidewall ________ Vent Pipe Length ________ Vent Pipe Elbow Quantity ________ Pipe Diameter Determined from Sizing Table ________ Pipe Sloped To Furnace Pipe Insulation ________ Over Ceilings ________ Low-Ambient Exposed Pipes Condensate Drain ________ Unit Level or Pitched Forward ________ Internal Tubing Connections Free of Kinks and Traps ________ External Drain Connection Leak Tight and Sloped ________ Condensate Trap Primed before Start-Up ________ Heat Tape Installed if Required CHECKLIST—START-UP ________ Gas Input Rate (Set Within 2 percent of Rating Plate) ________ Temperature Rise Adjusted Thermostat Anticipator ________ Anticipator Setting Adjusted ________ Cycle Rate (3 Cycles per Hr) Selected Safety Controls Check Operation ________ Primary Limit ________ Pressure Switch
or
—63—
© 2005 Payne Heating & Cooling 7310 W. Morris St., Indianapolis, IN 46231
—64—
impg9mab01 Catalog No. IM-PG9MAB-01
Loading...