Payne PG8J/M User Manual

PG8JAA PG8MAA
Installation, Start---up, Operating, and
SINGLE --- ST AGE DELUXE
INDUCED --- COMBUSTION
4-- -WAY MUL TIPOISE GAS FURNACE
Service and Maintenance Instructions Series 130/D
INTRODUCTION 3..................................
CODES AND STANDARDS 4..........................
Safety 4.........................................
General Installation 5...............................
Combustion and Ventilation Air 5.....................
Duct Systems 5...................................
Acoustical Lining and Fibrous Glass Duct 5.............
Gas Piping and Gas Pipe Pressure Testing 5.............
Electrical Connections 5............................
Venting 5........................................
LOCATION 6.......................................
AIR FOR COMBUSTION AND VENTILATION 8.........
INSTALLATION 11..................................
Bottom Return Air Inlet 11..........................
Side Return Air Inlet 11.............................
Leveling Legs (If Desired) 11........................
Bottom Return Air Inlet 12..........................
Suspended Furnace Support 12.......................
Platform Furnace Support 13.........................
Roll-- Out Protection 13.............................
Bottom Return Air Inlet 13..........................
Side Return Air Inlet 13.............................
General Requirements 14............................
Ductwork Acoustical Treatment 14....................
Supply Air Connections 14..........................
Return Air Connections 20..........................
START--UP, ADJUSTMENT, AND SAFETY CHECK 31.....
General 31.......................................
Start--Up Procedures 31.............................
Adjustments 34...................................
Check Safety Controls 37...........................
Checklist 38......................................
SERVICE AND MAINTENANCE PROCEDURES 46.......
Introduction 46...................................
Care and Maintenance 46...........................
Sequence of Operation 50...........................
Wiring Diagrams 51...............................
Troubleshooting 51................................
ama
ISO 9001:2000
CERTIFIED
REGISTERED
NOTE: Read the entire instruction manual before starting the installation.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1--2006E, with permission of Nation Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirely.
SAFETY CONSIDERATIONS
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory--authorized and listed kits or accessories when modifying this product.
PG8J/M
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CUT HAZARD
Failure to follow this caution may result in personal injury .
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the National Standards of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane Installation Codes, and Canadian Electrical Code CSA C22.1
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,and CAUTION. These words are used with the safety--alert symbol.
!
CAUTION
!
CAUTION
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as spe­cified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Con­nect this furnace to an approved vent system only, as spe­cified in the “Ve nting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
6. Always install furnace to operate within the furnace’s in­tended temperature--rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start--Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con­taining the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating out­side the space containing the furnace. See “Air Ducts” sec­tion.
8. A gas--fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these in­structions.
10. These Multipoise Gas--Fired Furnaces are CSA (formerly A.G.A. and C.G.A.) design--certified for use with natural and propane gases (see furnace rating plate) and for install­ation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) lis­ted accessory gas conversion kit is required to convert fur­nace for use with propane gas.
11. See Fig. 1 for required clearances to combustible construc­tion.
12. Maintain a 1 --in. (25 mm) clearance from combustible ma­terials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or loc­al code for further requirements.
13. These furnaces SHALL NOT be installed directly on car­peting, tile, or any other combustible material other than wood flooring. In downflow installations, factory access­ory floor base MUST be used when installed on combust­ible materials and wood flooring. Special base is not re­quired when this furnace is installed on manufacturer’s
.
Coil Assembly Part No. CNPV, CNRV, CAR or CAP or when Coil Box Part No. KCAKC is used. See Fig. 1 for clearance to combustible construction information.
2
(FLUE COLLAR)
(
7/8" DI A
ACCESSORY
(664mm)
26-1/8"
(22mm)
5-15/16"
33-5/16"
(846mm)
(733mm)
28-7/8"
(641mm)
25-1/4"
22-9/16"
(573mm)
JUNCTION BOX LOCATION
1/2" DIA THERMOSTAT
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. ACCESSORY
24-7/8"
(632mm)
F
A
D
13/16"
(21mm)
4-13/16"
(122mm)
(217mm)
ALTERNA T E
JUNCTION BOX
LOCATIONS (TYP)
VENT OUTLE T
5 PLACES (TYP)
(140mm)
5-1/2"
8-9/16"
2-7/16" (62mm)
1-5/16" (33mm)
1-1/8"
(29mm)
AIRFLOW
19"
(483mm)
OUTLE T
1/2" DIA. K.O.THERMOSTA T WIRE ENTRY
7/8" DIA. K.O. WIRE ENTR Y
(22mm)
7/8" DIA. ACCESSORY
(22mm)
(13mm)
1-3/4" DIA.RIGHT HAND GAS ENTRY
(44mm)
13/16"
(21mm)
11/16"
(17mm)
14-7/8"
(378mm)
7-3/4"
(197mm)
9-5/8"
(244mm)
11-1/2"
(292mm)
11/16"
(17mm)
NOTES:
1. Two additional 7/8--- in. (22 mm) diameter holes are located in the top plate.
2. Minimum return ---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters. a. For 800 CFM --- 16--- in. (406 mm) round or 14 1/2 x 12 --- in. (368 x 305 mm) rectangle. b. For 1200 CFM --- 20--- in. (508 mm) round or 14 1/2 x 19 1/2 ---in. (368 x 495 mm) rectangle. c. For 1600 CFM --- 22--- in. (559 mm) round or 14 1/2 x 22 1/16 ---in. (368 x 560mm) r ectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Da ta literature for specific use of single side inlets. The use of both sideinlets,a combination of 1 side and the bottom, or the bottom only will ensure adequate r etu r n air openings for airflow requirements above 1800 CFM.
(549mm)
21-5/8"
BOTTOM INLE T
24"
CASING
610mm)
1-11/16" (43mm)
5-1/2"
(140mm)
E
11/16"
(17mm)
3-3/4"
(95mm)
1-1/2"
(560mm) 22-1/16"
SIDE INLE T
(38mm)
1-1/4"
(32mm)
1"
(25mm)
A04037
Fig. 1 --- Dimensional Drawing
INTRODUCTION
Series 130/D 4--way multipoise Category I fan--assisted furnace is CSA design-- certified. A Category I fan--assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory--shipped for use with natural gas. This furnace is not approved for
This furnace is designed for minimum continuous return--air temperature of 60_F(16_C) db or intermittent operation down to 55_F(13_C) db such as when used with a night setback thermostat. Return--air temperature must not exceed 85_F(29_C) db. Failure to follow these return-- air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 3.)
installation in mobile homes, recreational vehicles, or outdoors.
Table 1—Dimensions -- In. (mm)
FURNACE SIZE A
CABINET WIDTH
IN (mm)
045 --- 08/024045 14--- 3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 104 (47) 045 --- 12/036045 14--- 3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 107 (48) 070 --- 08/024070 14--- 3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 111 (50) 070 --- 12/036070 14--- 3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 115 (52) 070 --- 16/048070 17---1/2 (445) 15---7/8 (403) 16 (406) 11---9/16 (294) 4 (102) 126 (57) 090 --- 14/042090 17---1/2 (445) 15---7/8 (403) 16 (406) 11---9/16 (294) 4 (102) 127 (58) 090 --- 16/048090 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13---5/16 (338) 4 (102) 140 (64) 090 --- 20/060090 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13---5/16 (338) 4 (102) 146 (66) 110 --- 12/036110 17---1/2 (445) 15---7/8 (403) 16 (406) 11---9/16 (294) 4 (102) 135 (61) 110 --- 16/048110 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13---5/16 (338) 4 (102) 146 (66) 110 --- 22/066110 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13---5/16 (338) 4 (102) 152 (69) 135 --- 16/048135 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13---5/16 (338) 4 (102) 149 (68) 135 --- 22/066135 24---1/2 (622) 22---7/8 (581) 23 (584) 15---1/16 (383) 4 (102) 163 (74) 155 --- 20/060155 24---1/2 (622) 22---7/8 (581) 23 (584) 15---1/16 (383) 4 (102) 170 (77)
* 5---in. or 6--- in. (127 or 152 mm) vent connector may be required in some cases.
D
SUPPLY--- AIR
WIDTH
IN (mm)
E
RETURN---AIR
WIDTH
IN (mm)
F
C.L. TOP AND
BOTTOM FLUE
COLLAR
IN (mm)
FLUE
COLLAR*
IN (mm)
SHIP WT
LB (KG)
PG8J/M
3
PG8J/M
Fig. 2 --- Clearances to Combustibles
60
Fig. 3 --- Return Air Temperature
For accessory installation details, refer to the applicable instruction literature.
80 / 27 C
/ 16 C
A06745
A08471
NOTE: Remove all shipping brackets and materials before operating the furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction. In the United States and Canada, follow all codes and standards for the following:
Step 1 Safety
US: National Fuel Gas Code (NFGC) NFPA
S
54--2006/ANSI Z223.1-- 2006 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: CSA B149.1--05 National Standard of
Canada Natural Gas and Propane Installation Codes (CAN/CSA--B149.1--05)
Step 2 General Installation
4
S US: Current edition of the NFGC and the NFPA 90B.
For copies, contact the National Fire Protection Associ­ation Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington, DC 20001 (www.AGA.org).
S CANADA: CAN/CSA-- B149.1 --05. For a copy, con-
tact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Step 3 Combustion and Ventilation Air
US: Section 9.3 of the NFGC, NFPA 54 / ANSI
S
Z223.1--2006 Air for Combustion and Ventilation
S CANADA: Part 8 of CAN/CSA--B149.1 --05, Venting
Systems and Air Supply for Appliances
Step 4 Duct Systems
US and CANADA: Air Conditioning Contractors As-
S
sociation (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refriger­ation, and Air Conditioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Step 5 Acoustical Lining and Fibrous Glass Duct
US and CANADA: current edition of SMACNA and
S
NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 Gas Piping and Gas Pipe Pressure Test in g
US: NFGC; NFPA 54 / ANSI Z223.1-- 2006 chapters 5,
S
6, 7 and 8 and National Plumbing Codes
S CANADA: CAN/CSA--B149.1--05 Parts 4, 5, and 6
and Appendices A, B, E, and H.
Step 7 Electrical Connections
US: National Electrical Code (NEC) ANSI/NFPA
S
70--2008
S CANADA: Canadian Electrical Cod e CSA C2 2.1
Step 8 Vent ing
US: NFGC NFPA 54 / ANSI Z223.1-- 2006; chapters
S
12 and 13
S CANADA: CAN/CSA--B149.1--05 Part 8 and Ap-
pendix C
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in furnace component damage.
Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the fur­nace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily dis­charged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch un­grounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
CAUTION
PG8J/M
5
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
PG8J/M
CONDITIONED AIR IS
DISCHARGED DOWNWARD
5. Use this procedure for installed and uninstalled (ungroun­ded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to pro­tect the control from damage. If the control is to be in­stalled in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the fur­nace. Put all used and new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
LOCATION
!
CARBON MONOXIDE POISONING AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death, and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
GENERAL
This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any of the four applications shown in Fig. 4.
This furnace must:
S be installed so the electrical components are protected
from water.
WARNING
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4 --- Multipoise Orientations
S not be installed directly on any combustible material
other than wood flooring (refer to SAFETY CONSIDERATIONS).
S be located as close to the chimney or vent and attached
to an air distribution system. Refer to Air Ducts section.
S be provided ample space for servicing and cleaning.
Always comply with minimum fire protection clear­ances shown on the furnace clearance to combustible label.
S The following types of furnace installations may re-
quire OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms, and S Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S W ater softening chemicals S De--icing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants S Cleaning solvents (such as perchloroethylene) S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid S Cements and glues S Antistatic fabric softeners for clothes dryers S Masonry acid washing materials
6
All fuel--burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return -- air duct to prevent pulling air from the burner area and from draft safeguard opening.
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC or CAN/CSA-- B149.1-- 05. (See Fig. 5.)
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in furnace component damage.
This gas furnace may be used for heating buildings under construction provided that:
--The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
-- The furnace is controlled by a thermostat. It may not be hot wired to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
-- Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
WARNING
!
CAUTION
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 --- Installation in a Garage
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace. (See Fig. 6.)
Fig. 6 --- Prohibit Installation on Back
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full--heat or full--cool position.
WARNING
A02054
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
S U.S. installations: Section 9.3 of the NFPA 54 / ANSI
Z223.1--2006, Air for Combustion and Ventilation, and applicable provisions of the local building codes.
S Canadian installations: Part 8 of CAN/CSA--
B149.1--05, Venting Systems and Air Supply for Ap­pliances, and all authorities having jurisdiction.
PG8J/M
7
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a
PG8J/M
NEGATIVE PRESSURE CONDITION at the furnace. Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make--up air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cu/ft. per 1,000 Btuh input rating for all gas appliances installed in the space.
WARNING
S Spaces having less than 50 cu/ft. per 1,000 Btuh re-
quire the OUTDOOR COMBUSTION AIR METHOD.
S Spaces having at least 50 cu/ft. per 1,000 Btuh may use
the INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combus­tion, ventilation, and dilution of flue gases using perman­ent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300
mm) of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
c. TWO HORIZONTAL DUCTS require 1 sq./in. of free
area per 2,000 Btuh (1,100 mm input for all gas appliances in the space per Fig. 7 and Tab le 2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq./in. of free area per 4,000 Btuh (550 mm combined input of all gas appliances in the space per Fig. 7 and Table 2.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch of free area per 3,000 Btuh (734
mm2/kW) for combined input of all gas appliances in the space per Table 2 and
b. Not less than the sum of the areas of all vent connect-
ors in the space.
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air NFPA & AGA Standard and Known--Air--Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known--Air--Infiltration Method is used.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
WARNING
2
/kW) of combined
2
/kW) for
8
Table 2—Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors
FURNACE
INPUT
(BTUH)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102) 66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127)
88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152) 110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152) 132,000 66 (42580) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178) 154,000 77 (49677) 10 (254) 51.3 (33096) 9 (229) 38.5 (24839) 8 (203)
TWO HOR IZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
Free Area of Opening
and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening
88,000
ACH
0.60
0.50
0.40
0.30
0.20
0.10
0.00
NP = Not Permitted
+ 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
Table 3—Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
30 40 50 44 66 88 110 132 154
1,050 (29.7)
1,260 (35.6)
1,575 (44.5)
2,100 (59.4)
3,150 (89.1)
6,300
(178.3)
NP NP NP NP NP NP NP NP NP
1,400 (39.6)
1,680 (47.5)
2,100 (59.4)
2,800 (79.2)
4,200
(118.9)
8,400
(237.8)
5,250 (148.6)
1,750 (49.5)
2,100
(59.4)
2,625
(74.3)
3,500
(99.1)
10,500
(297.3)
SpaceVolumeFt3(M3)
1,100 (31.1)
1,320 (37.3)
1,650 (46.7)
2,200 (62.2)
3,300 (93.4)
6,600
(186.8)
1,650
(46.7)
1,980 (56.0)
2,475 (70.0)
3,300 (93.4)
4,950
(140.1)
9,900
(280.3)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
2,200 (62.2)
2,640 (74.7)
3,300 (93.4)
4,400
(124.5)
6,600
(186.8)
13,200 (373.7)
2,750
(77.8)
3,300
(93.4)
4,125
(116.8)
5,500
(155.7)
8,250
(233.6)
16,500 (467.2)
3,300 (93.4)
3,960
(112.1)
4,950
(140.1)
6,600
(186.8)
9,900
(280.3)
19,800 (560.6)
3,850
(109.0)
4,620
(130.8)
5,775
(163.5)
7,700
(218.0)
11,550 (327.0)
23,100 (654.1)
PG8J/M
9
1 SQ IN.
E
12 ″ MAX
(305mm)
PER 4000 BTUH*
F
G
1 SQ IN. PER 4000 BTUH*
DUCTS
TO
O UTDOORS
(305mm)
12 ″ MAX
1 SQ IN. PER 2000 BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
(305mm)
PG8J/M
12 ″ MAX
CIRCULA TING AIR DUCT S
*Minimum dimensions of 3--- in. (76 mm).
NOTE: Use any of the following combinations of openings:
A&BC&DD&EF&G
B
AIR DUCTS
C IRCULA TING
A
OF COMB USTION AIR
CLEARANCE IN FRONT
D
VENT THR OUGH R OOF
(76mm)
AT LEAST 3 IN .
OPENINGS SHALL BE
C
DUCT
TO
OUTDOORS
Fig. 7 --- Air for Combustion, Ventilation, and Dilution for
Outdoors
12 MAX
1 SQ IN .
PER
4000
BTUH*
OUTDOORS
1 SQ IN .
PER 4000
BTUH*
12 MAX
(305mm)
(305mm)
A03174
CIRCULATING AIR
DUCTS
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. (64516 sq. mm)with minimum dimensions of3in.(76mm) †Minimumof3in.(76mm)whentype-B1ventisused.
VENT THROUGH ROOF
12" MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
(152mm)
6" MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
12" MA X
(305mm)
Ü
(305mm)
A03175
Fig. 8 --- Air for Combustion, Ventilation, and Dilution from
Indoors
The Standard Method:
1. The space has no less volume than 50 cu/ft. per 1,000 Btuh of the maximum input ratings for all gas appliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
Table 3--Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1--2006/NFPA 54--2006, 9.3.2.2:
1. For other than fan--assisted appliances, such as a draft hood--equipped water heater:
Volume
Other
=
21ft ACH
3
I
other
1000 Btu/hr
A04002
2. For fan--assisted appliances such as this furnace:
Volume
Fan
=
15ft ACH
3
I
fan
1000 Btu/hr
A04003
If:
I
other = combined input of all other than fan--assisted
appliances in Btuh/hr
I
fan = combined input of all fan--assisted appliances in Btuh/hr ACH = air changes per hour (ACH shall not exceed 0.60.) The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening
shall have free area of at least 1 in.
2
/kW) of the total input rating of all gas appliances
mm in the space, but not less than 100 in.
2
/1,000 Btuh (2,000
2
(0.06 m2). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm).(SeeFig.8.)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in.
2
/kW) of total input rating of all gas appliances.
mm
2
/1,000 Btuh (4,400
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to out­doors having free area of at least 1--in.
2
/4,000 Btuh of total
input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, in­filtration should be adequate to provide air for combus­tion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods de­scribedintheOutdoor Combustion Air Method section.
10
Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a con-
tinuous, sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include
joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combus- tion Air Method below and,
2. Outdoor openings shall be located as required in the Out- door Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided
by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The min­imum dimension of air openings shall be not less than 3in.(80mm).
INSTALLATION
UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
A02098
Fig. 9 --- Removing Bottom Closure Panel
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when only side return air is used.
NOTE: Side return--air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side return-- air openings in DOWNFLOW configuration.
In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field--supplied, 5/16 x 1--1/2 in. (8 x
38 mm) (max) corrosion--resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item 1. in Bottom Return Air Inlet section.
5/
16
(8mm)
(8mm)
5/
16
1 3 / 4 ″
(44mm)
3
1
/ 4 ″
(44mm)
(8mm)
5
/
16
(8mm)
5/
16
1
(44mm)
3/
4 ″
3/
1
4 ″
(44mm)
Fig. 10 --- Leveling Legs
Leveling Legs (If Desired)
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
DOWNFLOW INSTALLA
TION
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3 accessories are used:
S Special Base, KGASB S Cased Coil Assembly Part No. CNPV, CNRV, CAR,
or CAP
S Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and Fig. 11.
4. If downflow subbase, KGASB is used, install as shown in Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAR, or CAP or Coil Box Part No. KCAKC is used, install as shown in Fig. 13.
11
PG8J/M
A89014
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
A
PLENUM
OPENING
B
OPENING
D
FLOOR
C
PG8J/M
Fig. 11 --- Floor and Plenum Opening Dimensions
NOTE: It is recommended that the perforated supply--air duct
flanges be completely folded over or removed from furnace when installing the furnace on a factory--supplied cased coil or coil box. To remove the supply-- air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 14.)
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
A96283
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A08556
Fig. 13 --- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLA
!
WARNING
TION
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Fig. 12 --- Furnace, Plenum, and Subbase Installed on a
Combustible Floor
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawl space on either the left-- hand (LH) or right--hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non-- combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Fig. 15 and
16.) Secure angle iron to bottom of furnace as shown. Heavy--gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4--in. (19 mm) screws into the side and 2 #8 x 3/4--in. (19 mm) screws in the bottom of the furnace casing for each strap. (See Fig. 15 and 16.)
12
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in. (25 mm) clearance requirement on side, set furnace on non-­combustible blocks, bricks or angle iron. For crawl space installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
Roll-- Out Protection
Provide a minimum 17--3/4 in. x 22 in. (451 x 559 mm) piece of sheet metal for flame roll--out protection in front of burner area for furnaces closer than 12 inches (305 mm) above the combustible deck or suspended furnaces closer than 12 inches (305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. (25 mm) with the door removed.
The bottom closure panel on furnaces of widths 17--1/2 in. (445 mm) and larger may be used for flame roll--out protection when bottom of furnace is used for return air connection. See Fig. 17 for proper orientation of roll-- out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air inlet(s) is used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.)
FILTER
There are no provisions for an internal filter rack in these furnaces.
Refer to the instructions supplied with Media Cabinet for assembly and installation options.
A field--supplied accessory external filter rack is required. This furnace requires KGAFR030ALL 1 in. (25 mm) external
filter rack or a suitable field--supplied substitute, such as the media cabinet.
Refer to the instructions supplied with external filter rack for assembly and installation options.
ARRANGEMENT
!
CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage. Never operate a furnace without a filter or with filter access door removed.
WARNING
PG8J/M
13
Table 4—Opening Dimensions -- In. (mm)
PG8J/M
FURNACE
CASING
WIDTH
14–3/16
(360)
17–1/2
(445)
21
(533)
24---1/2
(622)
APPLICATION
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring (KGASB sub-
base required)
Downflow Applications on Combustible Flooring with CNPV,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring (KGASB sub-
base required)
Downflow Applications on Combustible Flooring with CNPV ,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on combustible flooring (KGASB sub-
base required)
Downflow Applications on Combustible Flooring with CNPV ,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible Floor-
ing (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring (KGASB
subbase not required)
Downflow applications on Combustible flooring (KGASB sub-
base required)
Downflow Applications on Combustible Flooring with CNPV ,
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box
(KGASB subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
12---11/16
(322)
12---9/16
(319)
11---13/16
(284)
12---5/16
(319)
16
(406)
15---7/8
(403)
15---1/8
(384)
15---1/2
(394)
19---1/2
(495)
19---3/8
(492)
18---5/8
(473)
19
(483)
23
(584)
22---7/8
(581)
22---1/8
(562)
22---1/2
(572)
21---5/8
(549)
19
(483)
19
(483)
19
(483)
21---5/8
(549)
19
(483)
19
(483)
19
(483)
21---5/8
(549)
19
(483)
19
(483)
19
(483)
21---1/8
(537)
19
(483)
19
(483)
19
(483)
13---5/16
(338)
13---3/16
(335)
13---7/16
(341)
13---5/16
(338)
16---5/8
(422)
16---1/2
(419)
16---3/4
(425)
16---1/2
(419)
20---1/8
(511)
20
(508)
20---1/4
(514)
20
(508)
23---5/8
(600)
23---1/2
(597)
23---3/4
(603)
23---1/2
(597)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
22---1/4
(565)
19---5/8
(498)
20---5/8
(600)
20
(508)
AIR DUCTS
General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 5--AIR DELIVERY--CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated and sealed to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft. (3 M) of main duct to the first branch take-- off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
14
Table 5—Air Delivery -- CFM (with Filter)*
FURNACE
SIZE
045 --- 08 /
024045
045 --- 12 /
036045
070 --- 08 /
024070
070 --- 12 /
036070
070 --- 16 /
048070
090 --- 14 /
042090
090 --- 16 /
048090
090 --- 20 /
060090
110 --- 12 /
036110
110 --- 16 /
048110
110 --- 22 /
066110
* A filter is required for each return --- air inlet. Airflow performance included 3/4 ---in. (19 mm) washable filter media such as contained in factory--- a u th o r i z ed a c -
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
RETURN---AIR
INLET
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Both Sides or 1
Side & Bottom
1Side Only
Bottom or
Side(s)
Bottom or
Side(s)
Bottom Only
Bottom Sides
or 1 Side & Bot-
tom
1Side Only
SPEED
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1085
920 820
1440 1360 1250
1030
835 725
1425 1320 1200
1805 1630 1460
1650 1515 1385
2060 1790 1505
2405 2225 2020
2530 2285 1995
2475 2260 1950
1625 1510 1360
2035 1745 1530
2530 2230 1920
--- --­2235 1920
2540 2125
--- ---
1035
875 775
1375 1300 1210
1010
815 700
1375 1280 1175
1740 1585 1420
1600 1485 1360
1985 1765 1505
2310 2155 1955
2450 2215 1945
2395 2190 1910
1575 1470 1335
1965 1710 1515
2470 2205 1900
--- ---
220
1900 2495
2120 1795
EXTERNAL STATIC PRESSURE (IN. WC)
975 830 730
1305 1240 1160
980 790 675
1320 1240 1145
1670 1530 1385
1535 1440 1320
1915 1715 1480
2220 2080 1880
2365 2150 1900
2300 2110 1855
1515 1415 1295
1880 1650 1470
2400 2165 1880
2415 2155 1880
2430 2105 1790
915 770 680
1240 1175 1100
945 760 645
1265 1205 1105
1600 1470 1325
1465 1380 1260
1820 1645 1440
2130 1995 1805
2270 2075 1840
2200 2035 1795
1445 1355 1250
1790 1560 1400
2320 2110 1845
2350 2100 1845
2355 2060 1765
845 710 620
1160 1115 1040
900 720 600
1200 1140 1050
1530 1405 1280
1385 1300 1195
1720 1560 1375
2025 1895 1730
2165 1985 1770
2090 1940 1730
1355 1285 1180
1680 1450 1310
2220 2035 1795
2250 2040 1795
2265 2010 1720
770 640 555
1070 1040
965 845
675 555
1125 1075
990
1445 1330 1220
1285 1220 1120
1610 1470 1300
1920 1785 1630
2065 1890 1685
1985 1845 1650
1260 1185 1100
1495 1340 1215
2115 1950 1730
2145 1955 1730
2175 1940 1650
675 555 470
975 950 885
775 610 475
1035
995 920
1360 1255 1155
1175 1115 1025
1490 1345 1190
1790 1675 1535
1940 1780 1600
1865 1735 1555
1165 1070
985
1365 1205 1095
2000 1855 1650
2015 1850 1650
2065 1840 1585
565 440 360
870 850 790
680 490 390
940 905 840
1280 1170 1080
1055
990 915
1340 1195 1045
1660 1565 1420
1805 1660 1480
1730 1620 1445
990 890 810
1215 1090
990
1865 1740 1555
1875 1740 1555
1935 1730 1500
390 250 190
730 725 670
490 375 300
830 790 725
1180 1080
995 895
830 710
1135 1010
890
1530 1420 1275
1670 1525 1350
1585 1475 1310
785 725
--- ---
1075
955 830
1730 1615 1460
1715 1595 1460
1785 1615 1390
195
--- ---
--- ---
560 575 520
335 265
--- ---
655 620 555
1075
990 910
645 600 565
925 820 740
1350 1260 1135
1505 1360 1180
1425 1325 1150
--- ---
--- ---
--- ---
875 750 670
1590 1485 1340
1560 1470 1340
1650 1485 1280
PG8J/M
15
Table 5 Air Delivery -- CFM (with Filter)* (Continued)
FURNACE
SIZE
048135
066135
060155
PG8J/M
* A filter is required for each return --- air inlet. Airflow performance included 3/4 ---in. (19 mm) washable filter media such as contained in factory--- a u th o r i z ed a c -
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
RETURN---AIR
INLET
Bottom or
Side(s)
Bottom Only
Bottom, Sides
or 1 Side & Bot-
tom
1SideOnly
Bottom Only
Both Sides Or 1
Side & Bottom
1Side Only
UPFLO
SPEED
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
High
M e d --- H i g h
M e d --- L o w
W OWNFLOW
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2090 1790 1545
2485 2195 1880
--- ---
“2180
1880
--- --­2135 1880
2465 2115 1800
--- --­2155 1800
--- --­2140 1800
2010 1755 1525
2400 2150 1850
--- --­2145 1850
--- --­2085 1850
2430 2105 1790
--- --­2135 1790
--- --­2095 1790
D
EXTERNAL STATIC PRESSURE (IN. WC)
1930 1705 1500
2310 2090 1820
2385 2060 1820
2245 2035 1820
2375 2075 1770
2375 2095 1770
2260 2040 1770
1835 1640 1450
2215 2000 1780
2305 2010 1780
2155 1975 1780
2305 2030 1735
2285 2040 1735
2180 1975 1735
1710 1550 1380
2110 1920 1715
2195 1945 1715
2055 1895 1715
2230 1980 1695
2200 1975 1695
2085 1890 1695
1590 1465 1315
2000 1825 1635
2085 1865 1635
1940 1795 1635
2110 1910 1640
2105 1895 1640
1975 1810 1640
HORIZONTAL
1470 1360 1215
1880 1720 1540
1960 1765 1540
1825 1685 1540
2000 1830 1570
1995 1790 1570
1865 1705 1570
1335 1210 1005
1725 1565 1415
1825 1660 1415
1695 1565 1415
1865 1725 1465
1870 1685 1465
1740 1595 1465
1025
945 855
1535 1405 1290
1670 1515 1290
1555 1445 1290
1725 1590 1345
1730 1550 1345
1605 1480 1345
835 785 670
1355 1255 1160
1465 1325 1160
1385 1265 1160
1545 1425 1225
1570 1400 1225
1455 1325 1225
90˚
120˚
MIN
YES
YES
NOT RECOMMENDED
120˚
MIN
Fig. 14 --- Duct Flanges
YES
YES
NOT RECOMMENDED
90˚
120˚ MIN
YES
YES
NOT RECOMMENDED
A02329
16
Loading...
+ 36 hidden pages