Payne PA3Z, PA3Z024, PA3Z030, PA3Z036, PA3Z042 Installation Instructions Manual

...
PA3Z
13 SEER SINGLE---PACKAGED AIR CONDITIONER SYSTEM
Installation Instructions
NOTE: Read the entire instruction manual before starting the
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 2.........................
INTRODUCTION 2...................................
RECEIVING AND INSTALLATION 2--6..................
Check Equipment 2..................................
Identify Unit 2....................................
Inspect Shipment 2.................................
Provide Unit Support 2...............................
Slab Mount 2.....................................
Ground Mount 2..................................
Provide Clearances 2.................................
Place Unit 2........................................
Select and Install Ductwork 2...........................
Configuring Units for Downflow (Vertical) Discharge 3....
Connect Condensate Drain 3...........................
Install Electrical Connections 6.........................
High--Voltage Connections 6.........................
Routing Power Leads Into Unit 6......................
Connecting Ground Lead to Unit Ground 6..............
Routing Control Power Wires 6......................
Accessory Electric Heat Wiring 6......................
PRE--START--UP 7....................................
START--UP 8--17......................................
Check for Refrigerant Leaks 8..........................
Start--Up Cooling and Make Adjustments 8................
Checking Cooling and Heating Control Operation 8.......
Refrigerant Charge 9...............................
No Charge 9......................................
Low Charge Cooling 9..............................
Indoor Airflow and Airflow Adjustments 10.............
Unit Controls 10...................................
High-- Pressure Relief Valve 10........................
Compressor Overload 10............................
Compressor Rotation 10.............................
Sequence of Operation 10...........................
Fan Operation 10..................................
W I T H R --- 2 2 R E F R I G E R A N T
SINGLE AND THREE PHASE
2 TO 5 NOMINAL TONS (SIZES 024 --- 060)
A05194
Fig. 1 -- Unit PA3Z
Cooling Operation 10, 17............................
Continuous Fan 17.................................
Electric Resistance Heating 17........................
MAINTENANCE 17--20................................
Air Filter 18........................................
Unit Top Removal 18.................................
Indoor Blower and Motor 18...........................
Outdoor Coil, Indoor Coil, and Condensate Drain Pan 19.....
Outdoor Fan 19.....................................
Electrical Controls and Wiring 19.......................
Refrigerant Circuit 20.................................
Indoor Airflow 20...................................
Metering Devices 20.................................
Liquid Line Strainers 20...............................
High Flow Valves 20.................................
TROUBLESHOOTING 20..............................
START--UP CHECKLIST 20............................
1
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit.
Recognize safety information. This is the safety-- alert symbol When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury
PA3Z
or death. WARNING signifies hazards which could result in per­sonal injury or death. CAUTION is used to identify unsafe practic­es which may result in minor personal injury or product and prop­erty damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
INTRODUCTION
The PA3Z packaged air conditioner is fully self--contained and designed for outdoor installation (See Fig. 1). Standard units are shipped in a horizontal-- discharge configuration for installation on a ground--level slab or directly on the ground if local codes permit. Standard units can be converted to downflow (vertical) discharge configurations for rooftop applications with a field supplied plenum.
RECEIVING AND INSTALLATION
Step 1 — Check Equipment
IDENTIFY UNIT The unit model number and serial number are printed on the unit
informative plate. Check this information against shipping papers. INSPECT SHIPMENT Inspect for shipping damage while unit is still on shipping pallet. If
unit appears to be damaged or is torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit. Check all items against shipping list. Immediately notify the nearest equipment distribution office if any item is missing. To prevent loss or damage, leave all parts in original packages until installation.
Step 2 — Provide Unit Support
For hurricane tie downs, contact distributor for details and PE (Professional Engineering) Certificate, if required.
SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4 in. (101.6 mm) thick with 2 in. (50.8 mm) above grade. The slab should extend approximately 2 in. (50.8 mm) beyond the casing on all 4 sides of the unit. Do not secure the unit to the slab except when required by local codes.
A 6-- in. (152.4 mm) wide gravel apron should be used around the flat surface to prevent airflow blockage by grass or shrubs. The unit should be level within 1/4 in. (6.4 mm). This is necessary for the unit drain to function properly.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the ground if local codes permit. Place the unit on level ground prepared with gravel for condensate discharge.
Step 3 — Provide Clearances
The required minimum service clearances are shown in Fig. 5.
.
Adequate ventilation and outdoor air must be provided.
The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm).
IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor--air inlet or the fan discharge may be detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab--mounted units should be at least 4 in. (101.6 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.
Step 4 — Place Unit
Unit can be moved with the rigging holds provided in the unit base. Refer to Table 1 for shipping weights. Use extreme caution to prevent damage when moving the unit. Unit must remain in an upright position during all moving operations. The unit must be level with in 1/4 in. (6.4 mm) for proper condensate drainage; the ground-- level pad must be level before setting the unit in place. When a field--fabricated support is used, be sure that the support is level and that it properly supports the unit.
Step 5 — Select and Install Ductwork
The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non--residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply--air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply-- and return--air openings on the side of the unit. See Fig. 5 for connection sizes and locations. The 14--in. (355.6 mm) round duct collars are shipped inside the unit attached to the base pan in the indoor blower compartment. They are field--installed and must be removed from the indoor blower compartment prior to start--up, even if they are not used for installation.
2
When designing and installing ductwork, consider the following:
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
When connecting ductwork to units, do not drill deeper than 3/4 in. (19.1 mm) in shaded area shown in Fig. 2 or coil may be damaged.
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DISCHARGE
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance operations on the system, turn off main power to unit and install lockout tag.
1. All units should have field-- supplied filters or accessory filter rack installed in the return--air side of the unit. Recommended sizes for filters are shown in Table 1.
2. Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24--in. (609.9 mm) from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum air quantity for proper electric heater operation is listed in Table 2. Heater limit switches may trip at air quantities below those recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof, and vibration--isolate duct openings in wall or roof according to good construction practices.
Fig. 6 shows a typical duct system with PA3Z unit installed.
19.17 in. (487 mm)
3.92 in.
(100 mm)
Units are dedicated side supply products. They are not convertible to vertical air supply. A field--supplied plenum must be used to convert to vertical air discharge.
Step 6 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Unit removes condensate through a 1--3/64--in. (26.6 mm) ID hole (using 3/4--in. (19.1 mm) OD piping or tubing) which is located at the end of the unit. See Fig. 5 for location of condensate connection.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field--supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. (25.4 mm) lower than the drain pan condensate connection to prevent the pan from overflowing (See Fig. 3 and 4). When using a gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from the unit, install a 2--in. (50.8 mm) trap using a 3/4--in. (19.1 mm) OD tubing or pipe. (See Fig. 3 and 4.) Make sure that the outlet of the trap is at least 1 in. (25.4 mm) lower than the unit drain--pan condensate connection to prevent the pan from overflowing. Prime the trap with water. Connect a drain tube using a minimum of 3/4-- in. PVC, 3/4--in. CPVC, or 3/4--in. copper pipe (all field supplied). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 in. (25.4 mm) for every 10 ft (3 m) of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the beginning of the cooling season start--up. Allowable glues for condensate trap connection are: Standard ABS, CPVC, or PVC cement..
1” (25 mm) MIN
.
TRAP OUTLET
PA3Z
Fig. 2 -- Area Not to be Drilled More Than 3/4 --in. (19.1 mm)
A08003
1" (25 mm) MIN
3
Fig. 3 -- Condensate Trap
TRAP OUTLET
.
Fig. 4 -- PVC Condensate Trap
2” (51 mm) MIN.
2" (51 mm) MIN
A08001
.
A08002
PA3Z
A07941
Fig. 5 -- Unit Base Dimensions, PA3Z024-- 060
4
RETURN AIR
INDOOR THERMOSTAT
TOP COVER
Power Wirin g
Control Wiring
Condenser Airflow
Evaporator Airflow
POWER AND LOW-VOLTAGE ENTRY
COMPOSITE RUST-PROOF BASEPAN
CONDENSATE DRAIN CONNECTION
FROM POWER SOURCE
DISCONNECT PER NEC (UNIT AND ELECTRIC HEATER)
A08207
Fig. 6 -- Typical Installation
Table 1 – Physical Data
UNIT SIZE 024 030 036 042 049 048 060 NOMINAL CAPACITY (ton) 2 2 --- 1 / 2 3 3 --- 1/2 4 4 5 SHIPPING WEIGHT (lb.)
(kg) Compressor Scroll Ultra Tech Scroll Refrigerant (R --22) Quantity (lb)
(kg)
REFRIGERANT METERING DEVICE AccuRatert TXV Orifice ID (in.) 0.067 0.067 0.082 0.086 CONDENSER COIL Copper Tubes, Aluminum Plate Fins RowsFins/in. 221 221 221 221 221 221 221 Face Area (sq. ft.) 11.1 12.7 15.8 15.8 13.3 13.3 15.8 CONDENSER FAN Propeller
Nominal Cfm 2600 2600 3200 3200 3200 3200 3300 Diameter (in.) 20 20 20 20 20 20 20 Motor HP (RPM) 1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (1100) 1/4 (1100) 1/4 (1100) 1/2 (1100)
EVAPORATOR COIL RowsFins/in. Face Area (sq. ft.)
298 135
6.8
3.0
329 149
9.5
4.3
382 173
9.5
4.3
394 179
11.1
5.0
386 175
10.0
4.5
389 176
10.7
4.9
438 199
12.5
5.7
Copper Tubes, Aluminum Plate Fins
317 417 417 417 417 417 417
4.3 4.9 4.9 6.1 4.9 4.9 6.1
PA3Z
Evaporator Blower Nominal Airflow (Cfm) Size (in.)
(mm)
Motor HP (RPM)
CONNECTING DUCT SIZES Supply Air (in.)
(mm)
Return Air (in.)
(mm)
Return--Air Filters Throwaway* (in.)
(mm)
800
10 x 8
254 x 203.2
1/2 (1050)
1000
10 x 8
254 x 203.2
1/2 (1050)
24 x 24
610 x 610
1200
11 x 9
279.4 x 228.6 3/4 (1050)
Direct Drive
1400
11 x 9
279.4 x 228.6 3/4 (1050)
Round
14
355.6 14
355.6
1600
11 x 10
279.4 x 254 1 (1050)
30 x 30
762 x 762
1600
11 x 10
279.4 x 254 1 (1050)
1875
11 x 10
279.4 x 254 1 (1050)
*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1 ---in . (25.4 mm) thick.
5
Table 2 – Minimum Airflow for Safe
Electric Heater Operation
Unit Size
024 400 550 650 X X 030 450 600 800 850 X 036 450 600 800 850 900 042 450 600 800 850 900 049 450 600 800 850 900 048 450 600 800 850 900 060 450 600 800 850 900
5kW 7.5kW 10kW 15kW 20kW
Minimum Airflow (CFM)
Step 7 — Install Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
PA3Z
The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA ANSI/NFPA 70 American National Standards Institute/National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.
!
CAUTION
Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high-- voltage leads should be in a conduit until they enter the unit; conduit termination at the unit must be watertight. Run the high-- voltage leads through the hole on the control box side of the unit (See Fig. 7). When the leads are inside the unit, run leads to the control box (See Fig. 8). For single--phase units, connect leads to the black and yellow wires (See Fig. 9).
CONNECTING GROUND LEAD TO UNIT GROUND
Connect the ground lead to the chassis using the unit ground in the control box (See Fig. 8 and 9).
ROUTING CONTROL POWER WIRES (24--V) Form a drip--loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted hole provided in unit into unit control box (See Fig. 7). Connect thermostat leads and unit power leads as shown in Fig. 9, 10 and
11. Route thermostat wires through grommet providing a drip--loop at
the panel. Connect low--voltage leads to the thermostat as shown in Fig. 10 & 11.
The unit transformer supplies 24--v power for complete system including accessory electrical heater. Transformer is factory wired for 230-- v operation.
ACCESSORY ELECTRIC HEAT WIRING Refer to accessory electric heat installation instructions for
information on installing accessory electric heat. Accessory electric heat wiring is shown in Fig. 17 and 18.
HIGH-VOLTAGE POWER
WIRING ENTRY HOLE
LOW-VOLTAGE WIRING
ENTRY HOLE
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being installed.
1. Make all electrical connections in accordance with NEC ANSI/NFPA ANSI/NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field--supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that high--voltage power to unit is within operating voltage range indicated on unit rating plate. On 3--phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.
HIGH--VOLTAGE CONNECTIONS The unit must have a separate electrical service with a
field--supplied, waterproof disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over the high--voltage inlet hole when the standard power and low--voltage entry points are used. See Fig. 6 and 7 for acceptable location.
A05198
Fig. 7 -- Unit Electrical Connection
6
3-PHASE
Unit Control
Power
Thermostat
and subbase
G
Y
W2
W3
R
RED
GRN
YEL
C
BRN
WHT
VIO
Unit Control Power
Thermostat
and subbase
G
Y1
Y2
W2
R
RED
GRN
YEL
W3
PNK
BRN
C
WHT
VIO
CONNECTIONS TO DISCONNECT PER NEC
Fig. 9 -- Line Power Connections
Fig. 8 -- Control Box Wiring
GROUND
SINGLE-PHASE CONNECTIONS TO DISCONNECT PER NEC
LEAD
L
L
L
HEATER LOW VOLTAGE PLUG
A05388
UNIT GROUND
BLK
YEL
BLU
C00012
Fig. 11 -- Control Connections (Sizes 048 and 060)
PRE--START--UP
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage.
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Relieve and recover all refrigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals.
3. Never attempt to repair soldered connection while refrigerant system is under pressure.
4. Do not use torch to remove any component. System contains oil and refrigerant under pressure.
5. To remove a component, wear protective goggles and proceed as follows:
a. Shut off electrical power to unit and install
lockout tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to flame.
A05214
PA3Z
Fig. 10 -- Control Connections (Sizes 024--042 and 049)
A05213
Proceed as follows to inspect and prepare the unit for initial start--up:
1. Remove all access panels.
2. Read and follow instructions on all DANGER, WARNING, CAUTION, and INFORMATION labels attached to, or shipped with unit.
7
!
START--UP
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and
on unit base. Detecting oil generally indicates a refrigerant leak. Leak test all refrigerant tubing
PA3Z
connections using electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, see Check for Refrigerant Leaks section.
c. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions: a. Make sure that outdoor--fan blade is correctly positioned
in fan orifice. Top edge of blade should be 3.125 in. (79.4 mm) down from outdoor coil outlet grille (size 024--049, See Fig. 19) or hub should be 0.708--in. (18 mm) away from motor end bell (size 060, See Fig. 19). See Outdoor Fan Adjustment section.
b. Make sure that air filter is in place.
c. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
Step 1 — Check for Refrigerant Leaks
Proceed as follows to locate and repair a refrigerant leak and to charge the unit:
1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from both high-- and low--pressure ports.
2. Repair leak following accepted practices.
NOTE: Install a filter drier whenever the system has been opened for repair.
Step 2 — Start--Up Cooling and Make Adjust­ments
Complete the required procedures given in the Pre--Start--Up section before starting the unit. Do not jumper any safety devices when operating the unit. Do not operate the unit in cooling mode when the outdoor temperature is below 40°F(4.4°C) (unless accessory low--ambient kit is installed). Do not rapid cycle the compressor. Allow 5 min. between “on” cycles to prevent compressor damage.
CHECKING COOLING AND HEATING CONTROL OPERATION
Start and check the unit for proper cooling control operation as follows:
1. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed in ON position and shuts down within 60 sec. (for 024--042 and 049) or 90 seconds (for 048 and 060) when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN switch in AUTO position. Set control below room temperature. Observe that compressor, outdoor fan, and indoor blower motors start. Observe that cooling cycle shuts down when control setting is satisfied.
3. If unit is equipped with electric heat, place system switch in HEAT position. Observe that indoor fan energizes. Set control above room temperature. Observe that heating cycle shuts down when control setting is satisfied.
4. When using an automatic changeover room thermostat, place both SYSTEM and FAN switches in AUTO positions. Observe that unit operates in Cooling mode when temperature control is set to call for Cooling (below room temperature), and unit operates in Heating mode when temperature control is set to call for Heating, if equipped with electric heat (above room temperature).
Model Size
024 --- 042 See “Required Liquid Line Termperature” Table
048 & 049 17.5 (9.7) 17 (9.4) 16.5 (9.2) 16 (8.9) 14 (7.8)
060 21 (11.7) 20.5 (11.4) 20 (11.1) 19 (10.6) 16 (8.9)
75 (24) 82 (28) 85 (29) 95 (35) 105 (41)
Table 3 – Required Subcooling
REQUIRED SUBCOOLING °F(°C)
Outdoor Ambient Temperature
8
Table 4 – Required Liquid Line Temperature
REQUIRED LIQUID LINE TEMPERATURE FOR A SPECIFIC SUBCOOLING (R --- 22)
Pressure PSIG
134 71 66 61 56 924 24 22 19 16 141 74 69 64 59 972 26 23 21 18 156 80 75 70 65 1075 30 27 24 21 163 83 78 73 68 1124 31 28 26 23 170 86 81 76 71 1172 33 30 27 24 177 89 84 79 74 1220 34 31 29 26 184 91 86 81 76 1268 36 33 30 27 191 94 89 84 79 1317 37 34 31 29 198 96 91 86 81 1365 38 36 33 30 205 98 93 88 83 1413 40 37 34 31 213 101 96 91 86 1468 41 38 36 33 221 104 99 94 89 1524 43 40 37 34 229 106 101 96 91 1579 44 41 38 36 237 108 103 98 93 1634 45 42 40 37 245 111 106 101 96 1689 47 44 41 38 253 113 108 103 98 1744 48 45 42 40 262 116 111 106 101 1806 49 46 44 41 271 118 113 108 103 1868 51 48 45 42 280 121 116 111 106 1930 52 49 46 44 289 123 118 113 108 1992 53 51 48 45 298 125 120 115 110 2054 55 52 49 46 307 128 123 118 113 2116 56 53 50 48 317 130 125 120 115 2185 57 54 52 49 327 132 127 122 117 2254 59 56 53 50 337 135 130 125 120 2323 60 57 54 52 347 137 132 127 122 2392 61 58 56 53 357 139 134 129 124 2461 62 60 57 54 367 142 137 132 127 2530 64 61 58 55 280 121 116 111 106 1930 52 49 46 44 289 123 118 113 108 1992 53 51 48 45 298 125 120 115 110 2054 55 52 49 46 307 128 123 118 113 2116 56 53 50 48 317 130 125 120 115 2185 57 54 52 49 327 132 127 122 117 2254 59 56 53 50 337 135 130 125 120 2323 60 57 54 52 347 137 132 127 122 2392 61 58 56 53 357 139 134 129 124 2461 62 60 57 54 367 142 137 132 127 2530 64 61 58 55
Required Subcooling (°F)
5 10 15 20 3 6 8 11
Pressure (kPa)
Required Subcooling (°C)
PA3Z
Step 3 — Refrigerant Charge
Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to Refrigerant Service Techniques Manual, Refrigerants section. Unit panels must be in place when unit is operating during charging procedure. Unit must operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Bryant Refrigerant Service Techniques. Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING 024--042 units:
1. Measure suction line pressure by attaching a gauge to the service port.
2. Measure the suction line temperature by attaching a temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor ambient doesn’t affect the reading.
4. Locate the measured suction line pressure in the top row of Table 6 and the measured outdoor ambient temperature in the left column of the table. Based on the two values, determine the required suction line temperature.
5. If the measured suction line temperature is greater than the tabulated temperature, add charge in the system.
048, 049 and 060 units:
1. Measure discharge line pressure by attaching a gauge to the service port.
2. Measure the liquid line temperature by attaching a temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor ambient doesn’t affect the reading.
4. Refer to the required subcooling in Tables 3 and 4 to find the required subcooling based on the model size and the outdoor ambient temperature.
5. Interpolate if the outdoor temperature lies in between the table values. Extrapolate if the temperature lies beyond the table range.
6. Find the pressure value corresponding to the measured pressure on the compressor discharge line.
7. Read across from the pressure reading to obtain the Liquid line temperature for a required subcooling.
8. Add charge if the measured temperature is higher than the liquid line temperature value in the table.
9
9. Add charge using the service connection on the suction line of the compressor.
Step 4 — Indoor Airflow and Airflow Adjust­ments
NOTE: For cooling operation, the recommended airflow is 350
to 450 cfm for each 12,000 Btuh of rated cooling capacity.
Table 5 shows dry coil air delivery for horizontal discharge units. Tables 7 --9 show pressure drops.
NOTE: Be sure that all supply-- and return-- air grilles are open, free from obstructions, and adjusted properly.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power to the unit and install lockout tag before changing blower speed.
PA3Z
Airflow can be changed by changing the lead connections at the blower motor. To change motor speeds, reposition wire at fan motor speed terminals labeled 1--2--3--4 (refer to Fig. 12).
Remove the speed tap connector labeled 1 through 5 and the motor. While looking at the connector end that is inserted into the motor, gently pry the locking tab outward and remove the wire from the connector. Insert the wire into the desired tap until it locks into place. Be sure new airflow meets the range noted above and minimum electic heat CFM, if equipped. Refer to Table 2 and 5.
All model sizes are factory wired for rated airflow operation.
Fig. 12 -- Motor Speed Selection
FOR 208/230V BLOWER MOTORS
The motor lead speed connections are as follows:
SIZE RATED AIRFLOW HIGH AIRFLOW
024 Tap 1 Tap 3 030 Tap 2 Tap 4 036 Tap 1 Tap 3 042 Tap 2 Tap 4 049 Tap 3 Tap 4
RATED AIRFLOW HIGH AIRFLOW
SIZE
048 Ta p 1 Tap 3 Ta p 2 Ta p 4 060 Ta p 1 Tap 3 Ta p 2 Ta p 4
Low
Stage
High
Stage
Low
Stage
High
Stage
A08210
Step 5 — Unit Controls
All compressors have the following internal--protection controls.
HIGH--PRESSURE RELIEF VALVE This valve opens when the pressure differential between the low
and high side becomes excessive.
COMPRESSOR OVERLOAD This overload interrupts power to the compressor when either the
current or internal temperature become excessive, and automatically resets when the internal temperature drops to a safe level.
This overload may require up to 60 minutes (or longer) to reset; therefore, if the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester.
COMPRESSOR ROTATION On 3--Phase units it is important to be certain compressor is
rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start--up.
If the suction pressure does not drop and the discharge pressure does not rise to normal levels:
1. Turn off power to the unit and tag disconnect.
2. Reverse any two of the unit power leads.
3. Turn on power to the unit.
The suction and discharge pressure levels should now move to their normal start--up levels.
NOTE: When the compressor is rotation in the wrong direction, the unit makes an elevated level of noise and does not provide cooling.
Step 6 — Sequence of Operation
FAN O PER ATION The FAN switch on the thermostat controls indoor fan operation.
When the FAN switch is placed in the ON position, the IFR (indoor--fan relay) is energized through the G terminal on the thermostat. The normally--open contacts close, which then provide power to the indoor (evaporator) fan motor (IFM). The IFM will run continuously when the FAN switch is set to ON.
When the FAN switch is set to AUTO, the thermostat deenergizes the IFR (provided there is not a call for cooling). The contacts open and the IFM is deenergized. The IFM will be energized only when there is a call for cooling or if the unit is equipped with accessory electric heat.
NOTE: Some units are equipped with a time--delay relay. On these units, the indoor fan remains on for 30 seconds after G or Y is deenergized.
COOLING OPERATION (SIZES 024--042 and 049)
With a call for cooling (Y/Y2), the indoor fan energizes immediately whereas the contactor energizes after a 5 minute time delay (in case of initial start--up) starting the compressor and the outdoor fan motor. When the cooling demand is met, Y/Y2 de--energizes, shutting the compressor, indoor fan and the outdoor fan.
10
PA3Z
Fig. 13 -- Typical Single--Phase Unit Electrical Diagram (Sizes 024-- 042 and 049)
A07912
11
PA3Z
Fig. 14 -- Typical Single--Phase Unit Electrical Diagram (Sizes 048, 060)
A07896
12
PA3Z
Fig. 15 -- Typical Three--Phase Unit Electrical Diagram (Sizes 030--042 and 049)
A07913
13
PA3Z
Fig. 16 -- Typical Three--Phase Unit Electrical Diagram (Sizes 048 and 060)
A06337
14
Fig. 17 -- Single--Phase Accessory Electric Heater Wiring
PA3Z
A05209
Fig. 18 -- Three--Phase Accessory Electric Heater Wiring
A06327
15
Table 5 – Dry Coil Air Delivery* Horizontal Discharge
(Deduct 10 percent for 208 Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
UNIT
SIZE
024
030
036
042
PA3Z
049
048
060
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter a nd electric heater pressure drops to obtain static pressure available for ducting. NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occuratair­flows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
SPEED
TAP
1
2
2
3
1
2
3
4
3
4
1
2
3
4
1
2
3
4
AIR
DELIVERY
Watts 99 100 118 130 142
CFM 848 793 757 698 632
Watts 222 233 244 257 260
CFM 970 918 861 795 729
Watts 155 146 157 170
CFM 1108 995 951 884
Watts 261 275 286 291 315
CFM 1117 1053 1014 980 877
Watts 180 166 179 191 204 216
CFM 1344 1215 1172 1136 1095 1051
Watts 261 276 290 301 316 329 342
CFM 1343 1304 1272 1234 1190 1148 1100
Watts 269 283 305 321 336 349 360
CFM 1440 1404 1369 1333 1301 1273 1239
Watts 418 432 450 465 480 490 503 518
CFM 1572 1543 1504 1475 1441 1418 1380 1332
Watts 386 398 409 418 425 435 438 441 451
CFM 1680 1652 1625 1583 1555 1515 1477 1444 1403
Watts 440 448 457 462 469 477 480 485 486
CFM 1745 1717 1684 1651 1612 1573 1537 1508 1470
Watts 204 209 216 229 236 249
CFM 1129 1087 1027 994 932 881
Watts 233 245 254 266 276 289
CFM 1164 1122 1066 1025 954 906
Watts 386 398 409 418 425 435 438 441 451
CFM 1680 1652 1625 1583 1555 1515 1477 1444 1403
Watts 440 448 457 462 469 477 480 485 486
CFM 1745 1717 1684 1651 1612 1573 1537 1508 1470
Watts 224 235 251 266 277 291 298
CFM 1334 1288 1259 1224 1181 1157 1117
Watts 286 301 311 325 333 344 370
CFM 1333 1296 1261 1232 1199 1170 1062
Watts 608 626 643 660 668 685 697
CFM 1931 1900 1878 1844 1817 1789 1755
Watts 737 755 770 787 799 817 826 812 782
CFM 2093 2061 2028 2001 1971 1934 1899 1850 1757
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
EXTERNAL STATIC PRESSURE (IN. W.C.)
16
Table6–CoolingChargingChart
SUCTION LINE TEMPERATURE (°F)
Suction Line Pressure (PSIG)
OD Temp.
(°F)
45 51 55 60 64 69 55 53 57 62 66 70 65 53 57 62 66 71 75 75 56 61 66 71 76 85 53 58 63 67 72
95 50 54 58 62 66 105 50 53 57 60 64 115 49 52 55 58 61 125 50 53 56 59
OD Temp.
(°C)
7 11 13 15 18 21 13 12 14 16 19 21 18 12 14 17 19 21 24 24 13 16 19 22 24 29 12 14 17 20 22 35 10 12 14 17 19 41 10 12 14 16 18 46 9 11 13 14 16 52 10 11 13 15
52 54 56 59 61 64 67 70 73 76 79 82 85 89 92
SUCTION LINE TEMPERATURE (°C)
Suction Line Pressure (kPa)
361 370 387
40
423 442 462 482 502 523 544 566 589 612 636
5
PA3Z
COOLING OPERATION (SIZES 048 AND 060)
These units utilize a 2 stage indoor thermostat. With a first stage call for cooling (Y1), the indoor fan (low stage) energizes immediately whereas the contactor energizes after a 5 minute time delay (in case of an initial start--up) starting the compressor (low stage) and the outdoor fan motor. If the low stage operation cannot satisfy the cooling demand, the second stage cooling (Y2) energizes switching the compressor into high stage cooling through energizing an internal solenoid valve inside the scroll compressor and switching the indoor fan into high stage. When second stage cooling is satisfied, Y2 de--energizes switching the compressor and the indoor fan into low stage cooling. When the low stage cooling demand is met, Y1 de--energizes shutting the compressor, indoor fan and the outdoor fan.
CONTINUOUS FAN With the continuous Indoor fan option selected on the thermostat,
G is continuously energized. In case of 024--042 and 049 units, the selected airflow setting is provided. In case of 048 and 060 units, the system runs low stage (Y1) airflow for continuous fan operation.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, the thermostat energizes W which energizes the heater relay and in turn energizes the electric heaters. The IFR is energized which starts the indoor--fan motor. If the heaters are staged, W2 is energized when the second stage of heating is required. When the need for heating is satisfied, the heater and IFM are de--energized.
MAINTENANCE
To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This cooling unit should be inspected at least once each year by a qualified service person. T o troubleshoot unit, refer to Troubleshooting Chart in back of book.
NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.
!
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and possible unit component damage.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner’s Manual.
The minimum maintenance requirements for this equipment are as follows:
1. Inspect air filter(s) each month. Clean or replace when necessary.
2. Inspect indoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness each cooling season. Clean when necessary.
4. Check electrical connections for tightness and controls for proper operation each cooling season. Service when necessary.
5. Ensure electric wires are not in contact with refrigerant tubing or sharp metal edges.
17
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow these warnings could result in personal injury or death:
1. Turn off electrical power and install lockout tag to the unit before performing any maintenance or service on this unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact with the unit.
Step 1 — Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system. Always replace the filter with the same dimensional size and type as originally installed. See T able 1 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway-- type) or clean (cleanable-- type) at least twice during
PA3Z
each cooling season and twice during the heating season if electric heat is installed, or whenever the filter becomes clogged with dust and lint.
Step 2 — Unit Top Removal (Outdoor--Coil Side)
NOTE: When performing maintenance or service procedures that
require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top removal, including coil inspection and cleaning, and condensate drain pan inspection and cleaning.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power, and install lockout tag to the unit before removing top.
Only qualified service personnel should perform maintenance and service procedures that require unit top removal.
Refer to the following top removal procedures:
1. Remove screws on unit top cover surface. (Save all screws.)
2. Remove screws on unit top cover flange. (Save all screws.)
3. Lift top from unit carefully. Set top on edge and make sure that top is supported by unit side that is opposite duct (or plenum) side.
4. Carefully replace and secure unit top to unit, using screws removed in Steps 1 and 2, when maintenance and/or service procedures are completed.
Step 3 — Indoor Blower and Motor
For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical power, and install lockout tag to the unit before cleaning and lubricating the blower motor and wheel.
To clean the blower wheel:
1. Remove the blower housing:
a. Remove the screws on the external side of the duct
panel that fasten the housing to the duct panel assembly.
b. Remove the side access panel and unscrew the
mounting bracket that fastens the blower housing to the internal partition panel fo the control box assembly.
c. Make sure that the blower housing is supported by hand
before completely removing the mounting bracket.
d. Slide the blower housing from the rails of the duct panel
and place it outside the unit.
2. Remove the blower wheel from the housing:
a. Loosen the set screw which secures the wheel to the
motor shaft.
b. Loosen the three mounting legs of the motor by
removing the bolts that fasten themounting legs to the housing.
c. Slide out the motor assembly (motor, belly band and the
3 mounting legs) from the hub of the wheel.
d. Remove the filler panel at the discharge end of the
blower housing by removing the two screws that fasten it to the housing.
e. Remove the wheel form the housing.
3. Remove the caked on dirt from the wheel and the motor using a brush.
4. Remove lint and dirt accumulations from the wheel and housing with a vacuum cleaner, using a soft brush attachment.
5. Remove grease and oil with a mild solvent.
6. Reassemble
a. Slip the wheel back in the housing with the hub set
screw parented in the correct direction.
b. Install the filler panel.
c. Reinsert the motor assembly in the wheel hub and align
the mounting legs with the housing mounting hold locations.
d. Tighten the mounting bolts to fasten the motor assembly
with the housing.
18
Table 7 – Wet Coil Pressure Drop
UNIT
SIZE
024 .027 .034 040 .047 .053 -- -- -- -- -- -- -- -- -- -­030 -- .036 .042 .050 .055 .063 .072 .081 -- -- -- -- -- -- -­036 -- -- -- .050 .055 .063 .072 .081 .090 .097 -- -- -- -- -­042 -- -- -- -- .042 .049 .052 .059 .065 .071 .078 .085 .091 -- -­049 -- -- -- -- -- -- .072 .081 .090 .097 .108 .120 .129 .139 -­048 -- -- -- -- -- -- .072 .081 .090 .097 .108 .120 .129 .139 -­060 -- -- -- -- -- -- -- -- -- .071 .078 .085 .091 .098 .114
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
STANDARD CFM (S.C.F.M.)
Table 8 – Filter Pressure Drop (IN. W.C.)
UNIT SIZE
024--- 036
042--- 060
FILTER SIZE in.
(mm)
24 x 24
(610 x 610)
30 x 30
(762 x 762)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
0.06 0.07 0.08 0.08 0.09 0.09 0.09 0.10 0.11 0.12 0.14 0.15
0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
CFM
Table 9 – Accessory Electric Heat Pressure Drop (IN. W.C.)
HEATER kW
5--20 0.06 0.08 0.10 0.13 0.15 0.18 0.20 0.23 0.25
600 800 1000 1200 1400 1600 1800 2000 2200
CFM
PA3Z
e. Center the wheel in the housing by sliding it, align the
flat end of the shaft with the set screw and tighten the set screw.
f. Slide back the blower housing into the mounting rails in
the duct panel and install the mounting bracket back in its position.
g. Install the screws on the external side of the duct panel
to fasten duct panel with the housing.
h. Replace the side access panel.
Step 4 — Outdoor Coil, Indoor Coil, and Condensate Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.
Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a “plumbers snake” or similar probe device.
Step 5 — Outdoor Fan
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit components.
Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of unit.
1. Shut off unit power supply and install lockout tag.
2. Remove outdoor--fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly onto unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 19.
5. Tighten setscrews.
6. Replace outdoor--fan assembly.
Fig. 19 -- Outdoor Fan Adjustment
CAUTION
15/32-in. (12 mm)
A08004
Step 6 — Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring. Check all electrical connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble the connection, clean all the parts, re-- strip the wire end and reassemble the connection properly and securely.
19
Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate from tubing and sheet metal edges.
After inspecting the electrical controls and wiring, replace all the panels. Start the unit, and observe at least one complete cooling cycle to ensure proper operation. If discrepancies are observed in operating cycle, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. Refer to the unit wiring label when making these checks.
Step 7 — Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil accumulation annually. Detecting oil generally indicates a refrigerant leak.
If oil is detected or if low performance is suspected, leak test all refrigerant tubing using an electronic leak detector, or liquid--soap solution. If a refrigerant leak is detected, refer to Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected, refer to Checking and Adjusting Refrigerant Charge section.
Step 8 — Indoor Airflow
PA3Z
The airflow does not require checking unless improper performance is suspected. If a problem exists, be sure that all
supply-- and return--air grilles are open and free from obstructions, and that the air filter is clean.
Step 9 — Metering Devices
Refrigerant cooling metering device is an AccuRater (024--042) or TXV (048--060) located upstream of the indoor coil distributor assembly.
Step 10 — High Flow Valves
High flow valves are located on the compressor hot gas and suction tubes. Large black plastic caps distinguish these valves with O--rings located inside the caps. These valves can not be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur.
TROUBLESHOOTING
Refer to the Troubleshooting Chart (Table 10) for troubleshooting information.
START--UP CHECKLIST
Use the Start--Up Checklist at the back of this manual.
20
Table 10 – Troubleshooting Chart
SYMPTOM CAUSE REMEDY
Power failure Call power company
Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker
Defective contactor, transformer, control relay, or
Compressor and outdoor fan will not start
Compressor will not start but condenser fan runs
Three-- phase scroll compressor (size 030--
060 unit) has a low pressure differential 3--phase power leads to the unit
Compressor cycles (other than normally sat­isfying) cooling/heating calls
Compressor operates continuously
Excessive head pressure
Head pressure too low
Excessive suction pressure
Suction pressure too low
high--pressure, or low--pressure switch
Insufficient line voltage Determine cause and correct
Incorrect or faulty wiring Check wiring diagram and rewire correctly
Thermostat setting too low/too high Reset thermostat setting
Faulty wiring or circuit Loose connections in compressor
Compressor motor burned out, seized, or Determine cause
internal overload open Replace compressor
Defective run capacitor, overload, or PTC (positive temperature coefficient) thermistor
One leg of 3-- phase power dead
Low input voltage (20 percent low) Determine cause and correct
Scroll compressor is rotating in the wrong direction
Refrigerant overcharge or undercharge
Defective compressor Replace and determine cause
Insufficient line voltage Determine cause and correct
Blocked outdoor coil Determine cause and correct
Defective run/start capacitor, overload or start relay Determine cause and replace
Faulty outdoor fan motor or capacitor Replace
Restriction in refrigerant system Locate restriction and remove
Dirty air filter Replace filter
Unit undersized for load Decrease load or increase unit size
Thermostat temperature set too low Reset thermostat setting
Low refrigerant charge Locate leak, repair, and recharge
Air in system
Outdoor coil dirty or restricted Clean coil or remove restriction
Dirty air filter Replace filter
Dirty indoor or outdoor coil Clean coil
Refrigerant overcharged Recover excess refrigerant
Air in system
Indoor or outdoor air restricted or air short-- cycling Determine cause and correct
Low refrigerant charge Check for leaks, repair and recharge Restriction in liquid tube Remove restriction High Heat load Check for source and eliminate Reversing valve hung up or leaking internally Replace valve Refrigerant overcharged Recover excess refrigerant Dirty air filter Replace filter Low refrigerant charge Check for leaks, repair and recharge Metering device or low side restricted Remove source of restriction Insufficient coil airflow Check filter–replace if necessary Temperature too low in conditioned area Reset thermostat setting Outdoor ambient below 55°F(13°C) Install low--ambient kit Filter drier restricted Replace
Replace component
Check wiring and repair or replace
Determine cause and replace
Replace fuse or reset circuit breaker Determine cause
Correct the direction of rotation by reversing the
Recover refrigerant, evacuate system, and re­charge to capacities shown on rating plate
Recover refrigerant, evacuate system, and re­charge
Recover refrigerant, evacuate system, and re­charge
PA3Z
21
START--UP CHECKLIST
(REMOVE AND STORE IN JOB FILE)
I. PRELIMINARY INFORMATION
Model No ............................................................................................................................................................
Serial No .............................................................................................................................................................
Date .....................................................................................................................................................................
Technician ..........................................................................................................................................................
Customer Information(Name/Address) .....................................................................................................................
II. PRE -- START-- UP
____ Verify that all packing materials have been removed from unit. ____ Verify that condensate connection is installed per installation instructions. ____ Check all electrical connections and terminals for tightness. ____ Check wire proximity to refrigerant tubes and sheet metal edges. ____ Check that indoor (indoor) air filter is clean and in place. ____ Verify that unit installation is level. ____ Check fan wheel propeller for location in housing and setscrew tightness.
III. START--UP
Supply Voltage: L1--L2 __________ L2--L3 __________ L3 --L1 __________ Compressor Amps: L1(C) __________ L2(S) __________ L3(R) __________
PA3Z
Indoor Fan Amps: __________ Outdoor Fan Amps: __________
TEMPERATURE--Cooling Mode
Outdoor Air Temperature: __________ DB ____________WB Return--Air Temperature: __________ DB __________ WB Cooling Supply Air: __________DB___________WB
PRESSURES-- Cooling Mode
Refrigerant Suction __________ psig ___________kPa Suction Line Temp* ___________ Refrigerant Discharge __________ psig ___________kPa Discharge Temp{__________
TEMPERATURE--Heating Mode
Outdoor Air Temperature: __________ DB ____________WB Return--Air Temperature: __________ DB __________ WB Cooling Supply Air: __________DB___________WB
PRESSURES--Heating Mode
Refrigerant Suction __________ psig ___________kPa Suction Line Temp* ___________ Refrigerant Discharge __________ psig ___________kPa Discharge Temp{__________ ____ Verify Refrigerant charge using charging tables
*Measured at suction inlet to compressor
{Measured at liquid line leaving outdoor coil
E2008 Payne Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
C a t a l o g N o : I M --- PA 3 Z --- 0 4
R e p lac e s : I M --- PA 3 Z --- 0 3