Payne PA2PNB036000AA Installation Guide

& Start-Up
Instructions
PAl P, PA2P Single Packaged Electric Cooling Units
11-02
NOTE: Read the entire instl_action manual before starting the installation This symbol --> indicates a change since the tast issue,
SAFETY CONSIDERATIONS 2 Introdnction 2 RECEIVING AND INSTALLATION 2
Check Equipment 2
IDENTIFY UNIT 2 INSPECT SHIPMENT 2
Provide Lnit Support ................................................................................................. 3
ROOF (LRB ................................................................................................. 3
SLAB MOUNT ................................................................................................ 4
GROL ND MOUNT ............................................................................................... 5
Provide Clearances ................................................................................................. 5
Field Fabricate Ductwork ......................................................................................................................................................................................... 7
Rig and Place Unit ................................................................................................................................................................................................... 7
INSPECTION ...................................................................................................................................................................................................... 7
INSTALLATION ................................................................................................................................................................................................ 7
Connect Condensate Drain ....................................................................................................................................................................................... 7
Instal! Duct (onnections .......................................................................................................................................................................................... 7
CONFIGURING UNITS FOR DO_\,L\'FLOW (VERTI(AL) DIS(HARGE ................................................ 7
Install Electrical ( onnection .......................................................................................... 11
HIGH=VOLTAGE CONNECTIONS ....................................................................................
SPECIAL PROCEDURES FOR 208-V OPERATION .................................................................. 11
CONTROL VOLTAGE CONNECTIONS ............................................................................. 11
STANDARD CONNE(TION ......................................................................................... 11
TRANSFORMER PROTE( TION ..................................................................................... 12
PRE=START=[ P ..................................................................................................... 15
START-UP ........................................................................................................... 15
CHE(K FOR REFRIGERANT LEAKS .................................................................................. 15
STAR7 UP (OOLING SECTION AND MAKE ADJUSTMENTS ..................................................... 15
CHECKING (OOLING CONTROL OPERATION ................................................................... 16
CHECKING AND ADJUSTING REFRIGERANT CHARGE ........................................................ 16
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS .............................................................. I6
Fm 208/230V ................................................................................................ 17
FOR 460-V GE MOTORS I8 (00LING SEQL EN(E OF OPERATION 20
MAINTENANCE 20
AIR FILTER 20 EVAPORATOR BLOWER AND MOTOR 22
(ONDENSER (OIL, EVAPORATOR COIL, AND (ONDENSATE DRAIN PAN 23 CONDENSER FAN 24
ELECTRICAL CONTROLS AND WIR]TNG 25 REFRIGERANT CIRCUIT 26
EVAPORATOR AIRFLOW 26 METERING DEVICE ACUTROL DEVICE 26
LIQUID LINE STRAINER 26
Troubleshooting 26 Start-Erp Checklist 26
Form: tM-PA1P-03 Cancels: tM-PA1P-02 Printed in U.S.A. Catalog No. 53PA-1P7
NOTE TO INSTALLER Bel:bre the installation, READ THESE INSTRU(TIONS (ARER LLY AND COMPLETELY. Also, make sure the
User's Manual and Replacement Guide are tei_ with the unit after installation.
SAFETY CONSIDERATIONS
[nstallation and servicing of air-conditioning equipment can be hazardous dz/e to system pressure and electrical components Only trained and qualified personnel should install, repair, or service air_conditioning equipment
Untrained personnel can perform basic maintenance fkmctions of cleaning coils and filters All other operations should be performed by trained
service personnel When working on air-conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply
Follow al! safe V codes. Wear safety glasses and work gloves Use quenching cloth _:br unbrazing operations. Have fire extinguisher available for
all brazing operations Consuk a qualified installer or service agency ibr information or assistance The qualified installer or agency must use only ihctory-authorized kits or accessories when modil_'ing this product.
C99062
Fig. l--Unit PAIP and PA2P
z_ WARNING: Before performing service or maintenance operations on system, turn off power to unit. Turn off
accessory heater power switch, if applicable. Emectrical shock can cause personal injury.
Recognize safety information. This is the safcty_alert symbolz_ x When you see this symbol in instructions or manuals, be alert to the potential
ibr personal irtiury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safcty_alert symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death. WARNfNG signifies a hazard which could result in personal injury or death. CAUTION is used to identii)* unsafe practices which would result in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced installation, reliability, or operation. These instructions cover minimum requirements and conibnn to existing national standards and safety codes. In some instances, these instl_actions
exceed certain local codes and ordinances, especially tl_ose that may not have kept up with changing residential construction practices. We require
these instructions as a minimum for a saf_ installation.
BNTRODUCTmON
The PA1P and PA2P units (see Fig. 1) are frilly self:containe& and designed _br outdoor installation. See Figs. 2 and 3 for unit dimensions. All
unit sizes have discharge openings ibr both horizontal and downflow configurations, and are _hcto_- shipped with all downflow dtlct openings
covered. Units may be installed either on a rooftop_ ground-level cement slab_ or directly on the ground if local codes permit (See Fig. 4 for roof curb dimensions)
RECEIVING AND INSTALLATION
PROCEDURE 1--CHECK EQUIPMENT
A. BDENTmFY UNIT
The unit model nmnber and serial nmnher are stamped on the unit identification plate Check this inJ:bm_ation against shipping papers
B. BNSPECT SHBPNENT
Inspect _br shipping damage while trait is still on shipping pallet. Ifnnit appears to be damaged o1"is torn loose from its anchorage, have it examined
by transportation inspectors beibre removal. Forward claim papers directly to transportation company. Manul:hcturer is not responsible ibr any
damage incurred in transit. (hock all items against shipping list. Immediately notify the nearest Payne Air (onditioning office if any item is
missing. To prevent toss or damage, leave all parts in original packages until installation.
2
DIMENSIONS 14 {] ARE
70 6
12 i'81
406 4
[1600)
860
[3 39]
N N(IIES
/ EVAP01!AT01! COIL
I
I
5481
402 0 [1583]
RETJD
!
_798 5
131 44]
\
\
\
\ 1939
\ [4! 00]
23,\i
[C _1] [
i\
-i n__
i i
5_03
[22 451
117 7
[4 63]
TOPVIEW [! 48_
44 5 [I )5] DIA I/0--_ _j_------_--- "
22 2 _0 88]C1_ HOLE-- _
/
249 6_550 5 [983]
REAR VIEW
POWER ENTRY _\/
CONTROL ENTRY
_'_249 6
[2! 677 [9 8_
#"'_j \\,,_x' I'lI I'
!
I
_831 0
{32 72) _DRA[N OUTLET
LEFT SIDEVIEW ]_22°_°olo_SJs."P_cP
REQUIRED CLEARANCETO COMBUSTIBLE MATL
TOP OF UNIT ................................................................................... 14.00 [355 6]
DUCT SIDE OF UNIT ......................................................................... 2.00 [508]
SIDE OPPOSITE DUCTS ................................................................ 14.00 [355 6]
BOTTOM OF UNiT ............................................................................. 0.50 [127]
ELECTRIC HEAT PANEL ................................................................. 36.00 [914 4]
NEC. REQUIRED CLEARANCES,
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [10668]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE 3600 [914 0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42,00 [10668]
UNIT
ELECTRICAL CHARACTERISTICS
12263 [48 281
FRONT ViEW
INCHES [mm]
INCHES [mm]
UNIT W%IGHT
REQUIRED CLEARANCE FOR OPERATIONAND SERVICING
EVAP COIL ACCESS SiDE ............................................................ 3600 [914.0]
POWER ENTRY SiDE .................................................................... 4200 [1066 8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 4800 [12192]
SIDE OPPOSITE DUCTS .............................................................. 3600 [914.0]
DUCT PANEL ................................................................................. 1200 [304 8] _
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12 00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE
Note: Wire Grilles are a field installed option.
UNIT HEIGHT IN. (MM)
_A _
35.02 (889.5)
35.02 (889,5)
35.02 (889.5)
37.02 (940.3)
35.02 (889.5)
37.02 (940.3)
39.02 (991.1) 35,02 (889,5)
PA1P018 PA1P024 PAIP030 PAIP036 PA1P042 PA2P024 PA2P030 PA2P036
208/230-1-60 208/230-1o60
208/230-1-60, 208/230-1o60,
208/230-1-60, 208/230-1o60
208/230-1o60, 208/230o 1o60,
208/230-3-60 208/230-3-60, 460-3-60
208/230-3-60, 460°3-60
208/230-3-60 208,230-3°60, 460-3-60
lb. kg 254 jli52
260 ili7.9 258 [ii7.0
268 i21.6 294 ii33.3 270 i22.5 29i 132.0 299 i35.6
Fig. 2-- PAtP018-042 and PA2P024-036
PROCEDURE A. ROOF CURB
Install accessory roof curb in accordance with instructions shipped with curb (See Fig 4) Install insulation, cant strips, roofing, and flashing Ductwork must be attached to curh,
IMPORTANT: The gasketiag of the unit to the roof curb is critical for a watertight seal, Install gasketing material supplied with the roof curb, Improperly applied gasketing also can result in air leaks and poor unit performance,
2--PROVIDE UNIT SUPPORT
3
L__ .... i " z
17, CJ
ip'/, -j
4 813
CENTER OF GRAVITY IN. (MM)
X Y
20.0 (508,0) 13.0 (330.2)
19.0 (482,6) 13.0 (330.2)
19.0 (482,6) 14.0 (355.6)
20.0 (508.0) 14.0 (355.6) i9.0 (482.6) i4.0 (355.6)
18.5 (469.9) 14.5 (368.3)
19.5 (495.3) 15.5 (393.7)
19.5 (495.3) 15.25 (387.4)
Unit Dimensions
RIGHTSiDEViEW
50
[0 20]
INCHES [mm]
Z
i5.0 (381.0) i5.0 (381.0)
15.0 (381.0) i3.0 (330.2) i3.0 (330.2)
i6.0 (40&4)
i7.6 (447.0) i6.5 (419.i)
C99007
r 2 ] RI WIN
1!6_00_
COMPREGSORIBLOWER,ELECTRIC IiEAT x
_0006 [42 94]
& ELECTRIC ACCESS \
TOP VIEW
I}93 9 [47003
C01L
4000
880
[3 481
DIMENSONS R {] ARE N NCHES
REAR VIEW
POWR ENTRY
?
i
J
I
J
[44 22} \\
LEFT SIDE VIEW _2_0_08._ FRONT VIEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATL
TOP OF UNIT ................................................................................... 1400 [355 6]
DUCT SIDE OF UNIT ......................................................................... 200 [50.8]
SIDE OPPOSITE DUCTS ................................................................ 1400 [355 6]
BOTTOM OF UNIT ............................................................................. 050 [12.7]
ELECTRIC HEAT PANEL ................................................................. 3600 [914 4]
NEC: REQUIRED CLEARANCES,
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [1066 8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00 [1066 8]
UNIT
PAIP048 PA1P060 PA2P042 PA2P048 PA2P060
ELECTRICAL CHARACTERISTICS
208/230-io60, 208/230o3o60, 460-3°60
208/230olo60, 208/230o3o60, 460°3°60
208/230-1o60, 208/230o3o60, 460-3°60
208/230olo60, 208/230o3o60, 460°3-60 208/230-1o60, 208/230o3o60, 460-3-60
4 \\ [48 28] \ DIIAII_ OUIL[I
190 [0¸?5) N PT
INCHES [mm]
INCHES [mini
UNIT WEIGHT
lb, k8 324 145
389 176 321 i46 326 148 399 i81
_2263
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAR COIL ACCESS SIDE ............................................................ 36.00 [914.0]
POWER ENTRY SIDE .................................................................... 36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 48.00 [1219 2]
SIDE OPPOSITE DUCTS .............................................................. 36.00 [914.0]
DUCT PANEL ................................................................................. 12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 3048 [12 00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE
Note: Wire Grilles are a field installed option.
UNIT HEIGHT IN. (MM)
_A _
38.98 (9902)
38.98 (990.2)
38.98 (990.2)
38.98 (990.2)
42.98 (!091.i)
202 [088] OIA HOLE
CON [ROL ENIR¥
I [ 21J
326 I _........ "%
[12 84]
[3 43]
[481 [0 20
CENTER OF GRAVITY IN. (MM)
X Y
20.0 (508.0) 17.0 (432.0)
19.0 (482.6) 16.0 (406.0)
20.5 (520.7) 16.75 (425.5)
19.5 (495.3) 17.6 (447.6)
20.5 (520.7) i6.2 (412.8)
RIGHT SIDE VIEW
INCHES [ram]
C99006
Z
17.0 (432.0)
17.0 (432.0)
16.6 (421.6)
18.0 (457.2)
17.6 (447.0)
Fig. 3-- PAl P048=060 and PA2P042-060 Unit Dimensions
CuIb should be level to within 1/4 in (See Fig. 5A) ]"his is necessary for unit drain to fhnction properly Refer to accessory roof curb installation instructions f_}r additional infbm_ation as required
g. SLAB MOUNT
Place d_e unit on a solid, level concrete pad that is a minimum of 4 in d_ick with 2 in above grade (See Fig. 5B) The slab should extend approximately 2 in beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes.
4
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retah_er bracket must also be used.
Roof Curb for Large Cabinet
Note A: When uNt mounting screw is used,
retainer bracket must also be used.
\
R/A
\
"--_-Gasket around_
\
\
\
/
\
duct
S/A
/2
,ul,oo_t
deck pan
ReHm opeHrl0
{B X C)
UNIT SIZE
PAIP018-042
PA2P024-036
ODS CATALOG NUMBER
CPRFCURB00dA00 CPRFCURB007A00
iPA1P048-060
PA2P042-060
CPRFCURB008A00 CPRFCURB009A00
NOTES: 1 Dimensions ]n ( ) are ]n millimeters.
2 Roof curb is made of 16-gage steel 3 Table lists only the dimensions per part number that have changed 4 Insulated panels: 1-in thick fiberglass 1 Ib density.
C. GROUND MOUNT The unit may be installed either ou a slab or placed directly on the ground if local codes permit, Place the unit on level ground prepared with gravel
%r condensate discharge
PROCEDURE 3--PROMIDE CLEARANCES
_he required minimum service clearauces are shown in Fig. 2 & 3. Adequate ventilation and outdoor air must be provided. The outdoor _m drav,s air through the outdoor coil and discharges it through the top Jim grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not tocate the unit in either a come* or under an overhead obstruction. The minimum clearance under a partial ore*hang (such as a normal house
overhang) is 36 in above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in For extended overhangs, provide a minimum clearance of 48 in.
mMPORTANT: Do not restrict outdoor airflow, An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to compressor life,
ong
A
IN. (MM)
8 (203)
14 (356)
8 (203)
14 (356)
Fig. 4A-- Roof Curb Dimensions
5
insulated Gasket around deck pan outer edge ,.,
B ]-N. (MM)
11(279) 11(279) 16-3/16 (411) 16-3/i6 (411)
c IN. (MM)
16-1,'2 (419) 16-1/2 (4!9) 17-3/8 (441) 17-3/8 (441)
\,
C00076
D _N. (MM)
28-3/4 (730) 28-3/4 (730) 40-1/4 (1022) 40-1/4 (!022)
1
Y
CORNER # PA 1P (In Pounds) PA2P (In Pounds)
018 024 030 036 042 048 060 024 030 036 042 048 060
1 58 60 59 62 76 69 84 76 84 85 71 78 85
2 47 50 48 50 50 45 54 49 60 60 55 56 66
3 55 56 56 58 71 88 106 57 6i 64 85 80 108
4 94 94 95 98 97 122 145 88 86 90 110 112 140 TOTAL WEIGHT 254 260 258 268 294 324 389 270 29i 299 32i 326 399
Fig. 4B--PAIP and PA2P Unit Corner Weights
C00071
.C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
C99065
Fig. 5A--Umt Leveling Tolerances
2 F_
±
m
EVAP COIL COND COIL
C99096
Fig, 5B--Slab Mounting Detail
Do not place the unit where water, ice, or snow t?om an ox'erhang or roof will damage or flood the unit Do not install the unit on carpeting or
other combustible materials Slab=mounted units should be at least 4 in above the highest expected water and runoff te_els Do not use unit if it
has been under water
6
PROCEDURE 4--F{ELD FABRBCATE DUCTWORK
Secure all ducts to roof curb and building structure on vertical discharge units, Do vot co_v¢ct d_lcmork to _mit.For horizontal applications, unit is provided with flanges on the horizontal openings All dnctwork should be secured to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit, the return should be ducted through the roof"deck to comply with applicable fire codes A mininmm clearance is not required around ductwork_
Cabinet retm'n=air static shall not exceed -.25 in wg
PROCEDURE 5--RIG AND PLACE UNIT
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roo_s, elevated structures, etc.) Only trained, qualified crane operators and grotmd support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safkty precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work gloves.
/_ WARNING: Never stand beneath rigged units or lift over people.
/_ WARNING: Never exceed 200 Ibs. per bracket tilting force.
!_x WARNING: Accessory lifting kit is only to be used with Small Packaged units which have a composite base pan with
molded rigging holds.
A, [NSPECTBON
Prior to initial use. and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence of wear, snucmral deibrmation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets
or straps showing any kind of wear in these areas must not be used and should be discarded.
g. INSTALLATION
1. Position the lifting bracket assembly around the base of the unit. Leave the top shipping skid on the unit to act as a spreader bar. Be sure the strap does not twist.
2 Place each of the ibur (4) metal lifting brackets into the rigging holds in the composite pan 3_ Tighten the ratchet strap unit tight. Lit'ring brackets should be secure in the rigging holds.
4 Attach the clevis or hook of sufficient strength to hole in the lifting bracket (See Fig 6). 5 Attach safety stlaps directly to the field supplied rigging straps or clevis clip Do not attach the safety straps to the lifting brackets_
6 Use the top of the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood top is not available, use a spreader
bar of sufficient length to not damage the unit
z_ WARNING: Lifting point should be directly over the center of gravity for the unit,
PROCEDURE g--CONNECT CONDENSATE DRAIN NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Models PA 1P and PA2P dispose of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side See Fig. 2 & 3 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground=level installations. Install a field=supplied condensate trap at end of condensate connection to ensure proper &ainage Make sure that the outlet of the
trap is at least 1 in. lower than the drainpan condensate connection to prevent the pan from overflowing (See Fig 7) When using a gravel apron, make sure it slopes away fi'om the unit. ( onnect a &ain tube using a minin_un_ of 3/4 -in PVC or 3/4 -in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not undersize
the tube Pitch the &ain robe downward at a slope of at least 1-in for every 10 ft of horizontal 17.m Be sure to check the drain robe for leaks. Prime t_ap at the beginning of the cooling season start-up.
PROCEDURE 7--INSTALL DUCT CONNECTIONS
]_he unit has duct flanges on the supply- and return=air openings on the side and bottom of the unit For downshot applications the ductwork can be connected to the roof curb. See Fig. 2 & 3 ibr connection sizes and locations
IMPORTANT: Use flexible connectors between dtlctwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weathertight and airtight seal. When electric heat is installed, use fire proof canvas (or similar heat resistant material) connector between ductwork
and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) n-met extend 24°in. tiom the unit discharge connection flange into the ductwork.
A. CONFIGURING UNITS FOR DOWNFLOW (VERTICAL} DISCHARGE
A WARNING: Before performing service or maintenance operations on the system, turn off main power to unit and
install lockout tag or electrical shock could result.
1 Open all electrical disconnects and install lockout tag before starting any smwice work.
2 Remove remm duct cover located on duct panel by breaking four (4) connecting tabs with screw&iver and a hammer. (Fig. 8 & 9)
7
>
DETAIL A
SCALE 0250
lIGHTEN STRAPPING SECURBk:Y
WITH TENSION SUCKLE
INSTALL SAFETY STRAPS TO
RIGGING CkSVIS AT 4 RIGGING BRACKETS
/
SEE DETAIL A
SIZE ! UNIT PAIP
018 276 024 282 030 280 036 290 042 316 048 346 060 411 UNIT PA2P 024 292 030 313 036 321 042 343 048 348 060 42i
3. To remove supply duct cover, break front and right side connecting tabs with a screw&iver and a hammer. Push louver down to break rear and te_ side tabs (Fig, 8 & 9)
4. If unit ductwork is to be attached to vertical opening _:langes on the unit composite base (iackstand applications only), do so at this time Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
5. [t is recommended that the unit base insulation around the perimeter of the vertical retnm-air opening be secured to the unit base with aluminum tape. Applicable local codes may require aluminum tape to prevent exposed fiberglass.
6. (over both horizontal duct openings with the duct covers from the accessory- duct cover kit. Ensure opening is air-and watertight.
7. Aker completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA _br installation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and ordinances.
Adhere to d_e following criteria when selecting, sizing, and installing the duct system:
8. Units are shipped _br side shot installation.
9. Select and size ductwork, supply-air registers, and return=air grilles according to American Society" of Heating, Refiigeration and Air (onditioning Engineers (ASHRAE) recommendations,
10. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration, The transition may be screwed or bolted to duct flanges "Use suitable gaskets to ensu*e weathertight and airtight seal,
11. All units must have field-supplied filters or accesso W filter rack installed in the return-air side of the unit Recommended sizes for filters are shown in Tables 1 and 2.
PLACE RIGGING BRACKET ASSEMBLY IN 4 RIGGING HOLES AND INSTALL TIE DOWN STRAP AROUND PERIMETER OF UNIT AND THROUGH SPACE IN BRACKET ASSEMBLY
125.2 20 508.0 13 330.2
127.9 i9 482.6 i3 330.2
127.0 19 482.6 14 355.6
131.5 20 508.0 14 355.6
143.3 i9 482.6 i4 355.6
156.9 20 508 17 431.8
186.4 19 482.6 16 406.4
132.5 i8.5 469.9
142.5 19.5 495.3
145.6 19.5 495.3
155.6 20.5 520.7
157.9 i9.5 495.3
191.0 20.5 520.7
Fig. 6--Suggested Rigging
8
i4.50 368.3
15.50 393.7
15.25 387.4
16.75 425.5 i7.62 447.6
16.25 412.8
C99066
Table 1--Physical Data--Unit PAl P
UNiT SIZE
NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb.)
COMPRESSOR
REFRIGERANT (R=22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Orifice ID {in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq, ft.)
CONDENSER FAN
NominN Cfm
Diameter
Motor Np (Rpm)
EVAPORATOR COiL
Rows...Fins/in.
Face Area (sq, ft,)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Hp (RPN)
RETURN-AIR FILTERS (in.)*
Required filter sizes shown arebased onthe larc
for throwaway type or 450 ft/min for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
Throwaway
018 024 042 048 0$0
1-1/2 2 3-1/2 4 5
254 260 294 324 389
2.6 3.5 6.4 5.1 7.4
.034 .034 .034 .032 .030
1...17 1...17 1...17 1...17 2...17
6.1 9.1 9.1 12.3 12.3
2000 2400 3000 3600 3600
22 22 22 22 22
1/8 (825) 1/8 (825) 1/4 (I100) 1/4 (I100) 1/4 (1100)
2._15 2...15 4...15 3._15 4._15
3.1 3.1 3.06 4.7 4.7
600 800 1400 1600 2000
10x10 10x10 11x10 11x10 11x10
1/4 (825) 1/4 (1075) 3/4 (I075) 3/4 (I075) 1.0 (1100)
20x20 20x20 20x24 24x30 24x30
erof the ARI (Air Conditioningand Refrigeration Institute)ratedcooling airflow or the heating airflow velocity of 300 ft./min
030 036
2-1/2 3
258 268
Reciprocating
3.65 4.4 Accurater
.034 .032
1._17 1._17
9.1 10.9
2400 3000
22 18
1/8 (825) 1/4 (I100)
2...15 3...15
3.7 3.06
1000 1200
10x10 11x10
1/4 (1075) 1/2 (1075)
20x20 20x24
Scroll Reciprocating
Table 2--Physical Data--Unit PA2P
UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSOR
REFRIGERANT (R°22)
Quantity (lb.)
REFRIGERANT METERING DEWCB
Orifice ID (in.)
CONDENSER COIL
Rows...Finsiin.
Face Area (sq. ft.)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Np (Rpm)
EVAPORATOR COIL
Rows...Finslin.
Face Area (sq. ft.)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Np (RPM)
RETURN-AIR FILTERS (in.)*
Throwaway
Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft./min
for throwaway type or 450 ft/min for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
1" (25mm) MIN.
024 636 636 042 048 666
2 2-1/2 3 3-1/2 4 5
270 291 299 321 326 399
Scroll
3.7 4.4 5.2 7.6 8.3 8.1 Accurater
.034 .030 .032 .034 .034 .032
1._17 1...17 2._17 2...17 2...17 2._17
10.8 12.7 9.1 9.1 12.3 16.4
2350 2350 2350 3300 3300 3300
22 22 22 22 22 22
1/8 (825) 1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (I100) 1/4 (1100)
3...15 3._15 3._15 3...15 4._15 4._15
3.1 3.1 3.7 4.7 4.7 4.7
800 1000 1200 1400 1600
10x10 10x10 1lx10 1lx10 11x10
1/4 1/4 1/2 3/4 3/4
1/4 (1075) 1/4 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075)
20x20 20x20 20x24 20x30 24x30 24x30
TRAP
1750
11x10
1.0 (1040)
OBTLET*,
Fig. 7--Condensate Trap
12 Size all ductwork %r maximum required airflow (either heating or cooling) %r unit being installed, Avoid abropt duct size increases or
decreases or performance may be affected
9
2" (50ram) MIN.
C99013
Loading...
+ 19 hidden pages