Payne PA1P048, PA2P042, PA2P048, PA2P060, PA1P060 Installation & Start-up Instructions

...
& Start-Up
PAl P, PA2P Single Packaged Electric Cooling Units
Instructions
11-02
NOTE: Read the entire instl_action manual before starting the installation This symbol --> indicates a change since the tast issue,
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2 Introdnction 2 RECEIVING AND INSTALLATION 2
Check Equipment 2
IDENTIFY UNIT 2 INSPECT SHIPMENT 2
Provide Lnit Support ................................................................................................. 3
ROOF (LRB ................................................................................................. 3
SLAB MOUNT ................................................................................................ 4
GROL ND MOUNT ............................................................................................... 5
Provide Clearances ................................................................................................. 5
Field Fabricate Ductwork ......................................................................................................................................................................................... 7
Rig and Place Unit ................................................................................................................................................................................................... 7
INSPECTION ...................................................................................................................................................................................................... 7
INSTALLATION ................................................................................................................................................................................................ 7
Connect Condensate Drain ....................................................................................................................................................................................... 7
Instal! Duct (onnections .......................................................................................................................................................................................... 7
CONFIGURING UNITS FOR DO_\,L\'FLOW (VERTI(AL) DIS(HARGE ................................................ 7
Install Electrical ( onnection .......................................................................................... 11
HIGH=VOLTAGE CONNECTIONS ....................................................................................
SPECIAL PROCEDURES FOR 208-V OPERATION .................................................................. 11
CONTROL VOLTAGE CONNECTIONS ............................................................................. 11
STANDARD CONNE(TION ......................................................................................... 11
TRANSFORMER PROTE( TION ..................................................................................... 12
PRE=START=[ P ..................................................................................................... 15
START-UP ........................................................................................................... 15
CHE(K FOR REFRIGERANT LEAKS .................................................................................. 15
STAR7 UP (OOLING SECTION AND MAKE ADJUSTMENTS ..................................................... 15
CHECKING (OOLING CONTROL OPERATION ................................................................... 16
CHECKING AND ADJUSTING REFRIGERANT CHARGE ........................................................ 16
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS .............................................................. I6
Fm 208/230V ................................................................................................ 17
FOR 460-V GE MOTORS I8 (00LING SEQL EN(E OF OPERATION 20
MAINTENANCE 20
AIR FILTER 20 EVAPORATOR BLOWER AND MOTOR 22
(ONDENSER (OIL, EVAPORATOR COIL, AND (ONDENSATE DRAIN PAN 23 CONDENSER FAN 24
ELECTRICAL CONTROLS AND WIR]TNG 25 REFRIGERANT CIRCUIT 26
EVAPORATOR AIRFLOW 26 METERING DEVICE ACUTROL DEVICE 26
LIQUID LINE STRAINER 26
Troubleshooting 26 Start-Erp Checklist 26
Form: tM-PA1P-03 Cancels: tM-PA1P-02 Printed in U.S.A. Catalog No. 53PA-1P7
NOTE TO INSTALLER Bel:bre the installation, READ THESE INSTRU(TIONS (ARER LLY AND COMPLETELY. Also, make sure the
User's Manual and Replacement Guide are tei_ with the unit after installation.
SAFETY CONSIDERATIONS
[nstallation and servicing of air-conditioning equipment can be hazardous dz/e to system pressure and electrical components Only trained and qualified personnel should install, repair, or service air_conditioning equipment
Untrained personnel can perform basic maintenance fkmctions of cleaning coils and filters All other operations should be performed by trained
service personnel When working on air-conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply
Follow al! safe V codes. Wear safety glasses and work gloves Use quenching cloth _:br unbrazing operations. Have fire extinguisher available for
all brazing operations Consuk a qualified installer or service agency ibr information or assistance The qualified installer or agency must use only ihctory-authorized kits or accessories when modil_'ing this product.
C99062
Fig. l--Unit PAIP and PA2P
z_ WARNING: Before performing service or maintenance operations on system, turn off power to unit. Turn off
accessory heater power switch, if applicable. Emectrical shock can cause personal injury.
Recognize safety information. This is the safcty_alert symbolz_ x When you see this symbol in instructions or manuals, be alert to the potential
ibr personal irtiury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safcty_alert symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death. WARNfNG signifies a hazard which could result in personal injury or death. CAUTION is used to identii)* unsafe practices which would result in minor personal injury or product and property damage. NOTE
is used to highlight suggestions which will result in enhanced installation, reliability, or operation. These instructions cover minimum requirements and conibnn to existing national standards and safety codes. In some instances, these instl_actions
exceed certain local codes and ordinances, especially tl_ose that may not have kept up with changing residential construction practices. We require
these instructions as a minimum for a saf_ installation.
BNTRODUCTmON
The PA1P and PA2P units (see Fig. 1) are frilly self:containe& and designed _br outdoor installation. See Figs. 2 and 3 for unit dimensions. All
unit sizes have discharge openings ibr both horizontal and downflow configurations, and are _hcto_- shipped with all downflow dtlct openings
covered. Units may be installed either on a rooftop_ ground-level cement slab_ or directly on the ground if local codes permit (See Fig. 4 for roof curb dimensions)
RECEIVING AND INSTALLATION
PROCEDURE 1--CHECK EQUIPMENT
A. BDENTmFY UNIT
The unit model nmnber and serial nmnher are stamped on the unit identification plate Check this inJ:bm_ation against shipping papers
B. BNSPECT SHBPNENT
Inspect _br shipping damage while trait is still on shipping pallet. Ifnnit appears to be damaged o1"is torn loose from its anchorage, have it examined
by transportation inspectors beibre removal. Forward claim papers directly to transportation company. Manul:hcturer is not responsible ibr any
damage incurred in transit. (hock all items against shipping list. Immediately notify the nearest Payne Air (onditioning office if any item is
missing. To prevent toss or damage, leave all parts in original packages until installation.
2
DIMENSIONS 14 {] ARE
860
[3 39]
70 6
12 i'81
N N(IIES
406 4
[1600)
_798 5
131 44]
i i
5_03
[22 451
!
_831 0
{32 72) _DRA[N OUTLET
LEFT SIDEVIEW ]_22°_°olo_SJs."P_cP
/ EVAP01!AT01! COIL
I
I
5481
402 0 [1583]
!
117 7
[4 63]
TOPVIEW [! 48_
\
\
\
\ 1939
\ [4! 00]
23,\i
[C _1] [
i\
-i n__
I
12263 [48 281
FRONT ViEW
REQUIRED CLEARANCETO COMBUSTIBLE MATL
INCHES [mm]
TOP OF UNIT ................................................................................... 14.00 [355 6]
DUCT SIDE OF UNIT ......................................................................... 2.00 [508]
SIDE OPPOSITE DUCTS ................................................................ 14.00 [355 6]
BOTTOM OF UNiT ............................................................................. 0.50 [127]
ELECTRIC HEAT PANEL ................................................................. 36.00 [914 4]
NEC. REQUIRED CLEARANCES,
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [10668]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE 3600 [914 0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42,00 [10668]
/
249 6_550 5 [983]
RETJD
_'_249 6
[2! 677 [9 8_
REAR VIEW
44 5 [I )5] DIA I/0--_ _j_------_--- "
POWER ENTRY _\/
22 2 _0 88]C1_ HOLE-- _
#"'_j \\,,_x' I'lI I'
CONTROL ENTRY
L__ .... i " z
17, CJ
ip'/, -j
4 813
RIGHTSiDEViEW
50
[0 20]
REQUIRED CLEARANCE FOR OPERATIONAND SERVICING
INCHES [mm]
EVAP COIL ACCESS SiDE ............................................................ 3600 [914.0]
POWER ENTRY SiDE .................................................................... 4200 [1066 8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 4800 [12192]
SIDE OPPOSITE DUCTS .............................................................. 3600 [914.0]
DUCT PANEL ................................................................................. 1200 [304 8] _
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12 00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE
Note: Wire Grilles are a field installed option.
C99007
UNIT
PA1P018 PA1P024 PAIP030 PAIP036 PA1P042 PA2P024 PA2P030 PA2P036
PROCEDURE
ELECTRICAL CHARACTERISTICS
208/230-1-60 208/230-1o60
208/230-1-60, 208/230-1o60,
208/230-1-60, 208/230-1o60
208/230-1o60, 208/230o 1o60,
208/230-3-60 208/230-3-60, 460-3-60
208/230-3-60, 460°3-60
UNIT W%IGHT
208/230-3-60 208,230-3°60, 460-3-60
Fig. 2-- PAtP018-042 and PA2P024-036
lb. kg 254 jli52
260 ili7.9 258 [ii7.0
268 i21.6 294 ii33.3 270 i22.5 29i 132.0 299 i35.6
UNIT HEIGHT IN. (MM)
_A _
35.02 (889.5)
35.02 (889,5)
35.02 (889.5)
37.02 (940.3)
35.02 (889.5)
37.02 (940.3)
39.02 (991.1) 35,02 (889,5)
CENTER OF GRAVITY IN. (MM)
X Y
20.0 (508,0) 13.0 (330.2)
19.0 (482,6) 13.0 (330.2)
19.0 (482,6) 14.0 (355.6)
20.0 (508.0) 14.0 (355.6) i9.0 (482.6) i4.0 (355.6)
18.5 (469.9) 14.5 (368.3)
19.5 (495.3) 15.5 (393.7)
19.5 (495.3) 15.25 (387.4)
Unit Dimensions
2--PROVIDE UNIT SUPPORT
Z
i5.0 (381.0) i5.0 (381.0)
15.0 (381.0) i3.0 (330.2) i3.0 (330.2)
i6.0 (40&4)
i7.6 (447.0) i6.5 (419.i)
A. ROOF CURB
Install accessory roof curb in accordance with instructions shipped with curb (See Fig 4) Install insulation, cant strips, roofing, and flashing Ductwork must be attached to curh,
IMPORTANT: The gasketiag of the unit to the roof curb is critical for a watertight seal, Install gasketing material supplied with the roof curb, Improperly applied gasketing also can result in air leaks and poor unit performance,
3
r 2 ] RI WIN
1!6_00_
COMPREGSORIBLOWER,ELECTRIC IiEAT x
& ELECTRIC ACCESS \
_0006 [42 94]
?
i
J
I
J
TOP VIEW
I}93 9 [47003
_2263
4 \\ [48 28]
[44 22} \\
\ DIIAII_ OUIL[I
190 [0¸?5) N PT
LEFT SIDE VIEW _2_0_08._ FRONT VIEW
DIMENSONS R {] ARE N NCHES
C01L
4000
880
[3 481
REAR VIEW
POWR ENTRY
202 [088] OIA HOLE
CON [ROL ENIR¥
I [ 21J
326 I _........ "%
[12 84]
[3 43]
[481 [0 20
RIGHT SIDE VIEW
REQUIRED CLEARANCE TO COMBUSTIBLE MATL
INCHES [mm]
TOP OF UNIT ................................................................................... 1400 [355 6]
DUCT SIDE OF UNIT ......................................................................... 200 [50.8]
SIDE OPPOSITE DUCTS ................................................................ 1400 [355 6]
BOTTOM OF UNIT ............................................................................. 050 [12.7]
ELECTRIC HEAT PANEL ................................................................. 3600 [914 4]
NEC: REQUIRED CLEARANCES,
INCHES [mini
BETWEEN UNITS, POWER ENTRY SIDE .................................... 42.00 [1066 8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0] UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE ......................... 42.00 [1066 8]
UNIT
PAIP048 PA1P060 PA2P042 PA2P048 PA2P060
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
INCHES [ram]
EVAR COIL ACCESS SIDE ............................................................ 36.00 [914.0]
POWER ENTRY SIDE .................................................................... 36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP ....................................................................................... 48.00 [1219 2]
SIDE OPPOSITE DUCTS .............................................................. 36.00 [914.0]
DUCT PANEL ................................................................................. 12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 3048 [12 00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE
Note: Wire Grilles are a field installed option.
C99006
ELECTRICAL CHARACTERISTICS
208/230-io60, 208/230o3o60, 460-3°60
208/230olo60, 208/230o3o60, 460°3°60
208/230-1o60, 208/230o3o60, 460-3°60
208/230olo60, 208/230o3o60, 460°3-60 208/230-1o60, 208/230o3o60, 460-3-60
UNIT WEIGHT
lb, k8 324 145
389 176 321 i46 326 148 399 i81
UNIT HEIGHT IN. (MM)
_A _
38.98 (9902)
38.98 (990.2)
38.98 (990.2)
38.98 (990.2)
42.98 (!091.i)
CENTER OF GRAVITY IN. (MM)
X Y
20.0 (508.0) 17.0 (432.0)
19.0 (482.6) 16.0 (406.0)
20.5 (520.7) 16.75 (425.5)
19.5 (495.3) 17.6 (447.6)
20.5 (520.7) i6.2 (412.8)
Z
17.0 (432.0)
17.0 (432.0)
16.6 (421.6)
18.0 (457.2)
17.6 (447.0)
Fig. 3-- PAl P048=060 and PA2P042-060 Unit Dimensions
CuIb should be level to within 1/4 in (See Fig. 5A) ]"his is necessary for unit drain to fhnction properly Refer to accessory roof curb installation instructions f_}r additional infbm_ation as required
g. SLAB MOUNT
Place d_e unit on a solid, level concrete pad that is a minimum of 4 in d_ick with 2 in above grade (See Fig. 5B) The slab should extend approximately 2 in beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes.
4
Roof Curb for Small Cabinet
Note A: When unit mounting screw is used,
retah_er bracket must also be used.
Roof Curb for Large Cabinet
Note A: When uNt mounting screw is used,
retainer bracket must also be used.
ReHm opeHrl0
{B X C)
deck pan
ong
/
,ul,oo_t
\
R/A
\
\
\
\
\
"--_-Gasket around_
duct
S/A
/2
insulated Gasket around deck pan outer edge ,.,
\,
C00076
UNIT SIZE
PAIP018-042
iPA1P048-060
PA2P024-036
PA2P042-060
NOTES: 1 Dimensions ]n ( ) are ]n millimeters.
2 Roof curb is made of 16-gage steel
ODS CATALOG NUMBER
CPRFCURB00dA00 CPRFCURB007A00 CPRFCURB008A00 CPRFCURB009A00
3 Table lists only the dimensions per part number that have changed 4 Insulated panels: 1-in thick fiberglass 1 Ib density.
A
IN. (MM)
8 (203)
14 (356)
8 (203)
14 (356)
B ]-N. (MM)
11(279) 11(279) 16-3/16 (411) 16-3/i6 (411)
c IN. (MM)
16-1,'2 (419) 16-1/2 (4!9) 17-3/8 (441) 17-3/8 (441)
D _N. (MM)
28-3/4 (730) 28-3/4 (730) 40-1/4 (1022) 40-1/4 (!022)
Fig. 4A-- Roof Curb Dimensions
C. GROUND MOUNT The unit may be installed either ou a slab or placed directly on the ground if local codes permit, Place the unit on level ground prepared with gravel
%r condensate discharge
PROCEDURE 3--PROMIDE CLEARANCES
_he required minimum service clearauces are shown in Fig. 2 & 3. Adequate ventilation and outdoor air must be provided. The outdoor _m drav,s air through the outdoor coil and discharges it through the top Jim grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not tocate the unit in either a come* or under an overhead obstruction. The minimum clearance under a partial ore*hang (such as a normal house
overhang) is 36 in above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in For extended overhangs, provide a minimum clearance of 48 in.
mMPORTANT: Do not restrict outdoor airflow, An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to compressor life,
5
1
Y
CORNER # PA 1P (In Pounds) PA2P (In Pounds)
018 024 030 036 042 048 060 024 030 036 042 048 060
1 58 60 59 62 76 69 84 76 84 85 71 78 85
2 47 50 48 50 50 45 54 49 60 60 55 56 66
3 55 56 56 58 71 88 106 57 6i 64 85 80 108
4 94 94 95 98 97 122 145 88 86 90 110 112 140 TOTAL WEIGHT 254 260 258 268 294 324 389 270 29i 299 32i 326 399
Fig. 4B--PAIP and PA2P Unit Corner Weights
C00071
.C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
1/4 1/4 1/4
Fig. 5A--Umt Leveling Tolerances
C99065
2 F_
±
m
EVAP COIL COND COIL
C99096
Fig, 5B--Slab Mounting Detail
Do not place the unit where water, ice, or snow t?om an ox'erhang or roof will damage or flood the unit Do not install the unit on carpeting or
other combustible materials Slab=mounted units should be at least 4 in above the highest expected water and runoff te_els Do not use unit if it
has been under water
6
PROCEDURE 4--F{ELD FABRBCATE DUCTWORK
Secure all ducts to roof curb and building structure on vertical discharge units, Do vot co_v¢ct d_lcmork to _mit.For horizontal applications, unit is provided with flanges on the horizontal openings All dnctwork should be secured to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit, the return should be ducted through the roof"deck to comply with applicable fire codes A mininmm clearance is not required around ductwork_
Cabinet retm'n=air static shall not exceed -.25 in wg
PROCEDURE 5--RIG AND PLACE UNIT
Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roo_s, elevated structures, etc.) Only trained, qualified crane operators and grotmd support staff should handle and install this equipment.
When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safkty precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work gloves.
/_ WARNING: Never stand beneath rigged units or lift over people.
/_ WARNING: Never exceed 200 Ibs. per bracket tilting force.
!_x WARNING: Accessory lifting kit is only to be used with Small Packaged units which have a composite base pan with
molded rigging holds.
A, [NSPECTBON
Prior to initial use. and at monthly intervals, all rigging brackets and straps should be visually inspected for any damage, evidence of wear, snucmral deibrmation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Brackets
or straps showing any kind of wear in these areas must not be used and should be discarded.
g. INSTALLATION
1. Position the lifting bracket assembly around the base of the unit. Leave the top shipping skid on the unit to act as a spreader bar. Be sure the strap does not twist.
2 Place each of the ibur (4) metal lifting brackets into the rigging holds in the composite pan 3_ Tighten the ratchet strap unit tight. Lit'ring brackets should be secure in the rigging holds.
4 Attach the clevis or hook of sufficient strength to hole in the lifting bracket (See Fig 6). 5 Attach safety stlaps directly to the field supplied rigging straps or clevis clip Do not attach the safety straps to the lifting brackets_
6 Use the top of the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood top is not available, use a spreader
bar of sufficient length to not damage the unit
z_ WARNING: Lifting point should be directly over the center of gravity for the unit,
PROCEDURE g--CONNECT CONDENSATE DRAIN NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions.
Models PA 1P and PA2P dispose of condensate water through a 3/4 in. NPT fitting which exits through the base on the evaporator coil access side See Fig. 2 & 3 for location.
Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground=level installations. Install a field=supplied condensate trap at end of condensate connection to ensure proper &ainage Make sure that the outlet of the
trap is at least 1 in. lower than the drainpan condensate connection to prevent the pan from overflowing (See Fig 7) When using a gravel apron, make sure it slopes away fi'om the unit. ( onnect a &ain tube using a minin_un_ of 3/4 -in PVC or 3/4 -in. copper pipe (all field-supplied) at the outlet end of the 2-in. trap. Do not undersize
the tube Pitch the &ain robe downward at a slope of at least 1-in for every 10 ft of horizontal 17.m Be sure to check the drain robe for leaks. Prime t_ap at the beginning of the cooling season start-up.
PROCEDURE 7--INSTALL DUCT CONNECTIONS
]_he unit has duct flanges on the supply- and return=air openings on the side and bottom of the unit For downshot applications the ductwork can be connected to the roof curb. See Fig. 2 & 3 ibr connection sizes and locations
IMPORTANT: Use flexible connectors between dtlctwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weathertight and airtight seal. When electric heat is installed, use fire proof canvas (or similar heat resistant material) connector between ductwork
and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) n-met extend 24°in. tiom the unit discharge connection flange into the ductwork.
A. CONFIGURING UNITS FOR DOWNFLOW (VERTICAL} DISCHARGE
A WARNING: Before performing service or maintenance operations on the system, turn off main power to unit and
install lockout tag or electrical shock could result.
1 Open all electrical disconnects and install lockout tag before starting any smwice work.
2 Remove remm duct cover located on duct panel by breaking four (4) connecting tabs with screw&iver and a hammer. (Fig. 8 & 9)
7
>
DETAIL A
SCALE 0250
lIGHTEN STRAPPING SECURBk:Y
WITH TENSION SUCKLE
/
SEE DETAIL A
SIZE ! UNIT PAIP
018 276 024 282 030 280 036 290 042 316 048 346 060 411 UNIT PA2P 024 292 030 313 036 321 042 343 048 348 060 42i
INSTALL SAFETY STRAPS TO
RIGGING CkSVIS AT 4 RIGGING BRACKETS
PLACE RIGGING BRACKET ASSEMBLY IN 4 RIGGING HOLES AND INSTALL TIE DOWN STRAP AROUND PERIMETER OF UNIT AND THROUGH SPACE IN BRACKET ASSEMBLY
125.2 20 508.0 13 330.2
127.9 i9 482.6 i3 330.2
127.0 19 482.6 14 355.6
131.5 20 508.0 14 355.6
143.3 i9 482.6 i4 355.6
156.9 20 508 17 431.8
186.4 19 482.6 16 406.4
132.5 i8.5 469.9
142.5 19.5 495.3
145.6 19.5 495.3
155.6 20.5 520.7
157.9 i9.5 495.3
191.0 20.5 520.7
Fig. 6--Suggested Rigging
i4.50 368.3
15.50 393.7
15.25 387.4
16.75 425.5 i7.62 447.6
16.25 412.8
C99066
3. To remove supply duct cover, break front and right side connecting tabs with a screw&iver and a hammer. Push louver down to break rear and te_ side tabs (Fig, 8 & 9)
4. If unit ductwork is to be attached to vertical opening _:langes on the unit composite base (iackstand applications only), do so at this time Collect ALL screws that were removed. Do not leave screws on rooftop as permanent damage to the roof may occur.
5. [t is recommended that the unit base insulation around the perimeter of the vertical retnm-air opening be secured to the unit base with aluminum tape. Applicable local codes may require aluminum tape to prevent exposed fiberglass.
6. (over both horizontal duct openings with the duct covers from the accessory- duct cover kit. Ensure opening is air-and watertight.
7. Aker completing unit conversion, perform all safety checks and power up unit.
NOTE: The design and installation of the duct system must be in accordance with the standards of the NFPA _br installation of nonresidence-type air conditioning and ventilating systems, NFPA 90A or residence-type, NFPA 90B; and/or local codes and ordinances.
Adhere to d_e following criteria when selecting, sizing, and installing the duct system:
8. Units are shipped _br side shot installation.
9. Select and size ductwork, supply-air registers, and return=air grilles according to American Society" of Heating, Refiigeration and Air (onditioning Engineers (ASHRAE) recommendations,
10. Use flexible transition between rigid ductwork and unit to prevent transmission of vibration, The transition may be screwed or bolted to duct flanges "Use suitable gaskets to ensu*e weathertight and airtight seal,
11. All units must have field-supplied filters or accesso W filter rack installed in the return-air side of the unit Recommended sizes for filters are shown in Tables 1 and 2.
8
UNiT SIZE
NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb.)
COMPRESSOR
REFRIGERANT (R=22)
Quantity (lb.)
REFRIGERANT METERING DEVICE
Orifice ID {in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq, ft.)
CONDENSER FAN
NominN Cfm
Diameter
Motor Np (Rpm)
EVAPORATOR COiL
Rows...Fins/in.
Face Area (sq, ft,)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Hp (RPN)
RETURN-AIR FILTERS (in.)*
Throwaway
Required filter sizes shown arebased onthe larc
Table 1--Physical Data--Unit PAl P
018 024 042 048 0$0
1-1/2 2 3-1/2 4 5
254 260 294 324 389
Scroll Reciprocating
2.6 3.5 6.4 5.1 7.4
.034 .034 .034 .032 .030
1...17 1...17 1...17 1...17 2...17
6.1 9.1 9.1 12.3 12.3
2000 2400 3000 3600 3600
22 22 22 22 22
1/8 (825) 1/8 (825) 1/4 (I100) 1/4 (I100) 1/4 (1100)
2._15 2...15 4...15 3._15 4._15
3.1 3.1 3.06 4.7 4.7
600 800 1400 1600 2000
10x10 10x10 11x10 11x10 11x10
1/4 (825) 1/4 (1075) 3/4 (I075) 3/4 (I075) 1.0 (1100)
20x20 20x20 20x24 24x30 24x30
erof the ARI (Air Conditioningand Refrigeration Institute)ratedcooling airflow or the heating airflow velocity of 300 ft./min
for throwaway type or 450 ft/min for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
030 036
2-1/2 3
258 268
Reciprocating
3.65 4.4 Accurater
.034 .032
1._17 1._17
9.1 10.9
2400 3000
22 18
1/8 (825) 1/4 (I100)
2...15 3...15
3.7 3.06
1000 1200
10x10 11x10
1/4 (1075) 1/2 (1075)
20x20 20x24
UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSOR
REFRIGERANT (R°22)
Quantity (lb.)
REFRIGERANT METERING DEWCB
Orifice ID (in.)
CONDENSER COIL
Rows...Finsiin.
Face Area (sq. ft.)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Np (Rpm)
EVAPORATOR COIL
Rows...Finslin.
Face Area (sq. ft.)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor Np (RPM)
RETURN-AIR FILTERS (in.)*
Throwaway
Table 2--Physical Data--Unit PA2P
024 636 636 042 048 666
2 2-1/2 3 3-1/2 4 5
270 291 299 321 326 399
Scroll
3.7 4.4 5.2 7.6 8.3 8.1 Accurater
.034 .030 .032 .034 .034 .032
1._17 1...17 2._17 2...17 2...17 2._17
10.8 12.7 9.1 9.1 12.3 16.4
2350 2350 2350 3300 3300 3300
22 22 22 22 22 22
1/8 (825) 1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (I100) 1/4 (1100)
3...15 3._15 3._15 3...15 4._15 4._15
3.1 3.1 3.7 4.7 4.7 4.7
800 1000 1200 1400 1600
1750
10x10 10x10 1lx10 1lx10 11x10
11x10
1/4 1/4 1/2 3/4 3/4
1.0 (1040)
1/4 (1075) 1/4 (1075) 1/2 (1075) 3/4 (1075) 3/4 (1075)
20x20 20x20 20x24 20x30 24x30 24x30
Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft./min
for throwaway type or 450 ft/min for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
1" (25mm) MIN.
TRAP
OBTLET*,
2" (50ram) MIN.
Fig. 7--Condensate Trap
C99013
12 Size all ductwork %r maximum required airflow (either heating or cooling) %r unit being installed, Avoid abropt duct size increases or
decreases or performance may be affected
9
[
m
018 024 048 060 700 800 1600 2000
Table 3--Minimum Airflow for Safe Electric Heater
Operation (Cfm)
SBZE
030 036 042
1000 1200 1400
13. Adeqtlately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through unconditioned space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air (onditioning (ontractors National Association (SMA(NA) and Air
Conditioning (onhactors of America (A(CA) minimum installation standards for heating and air conditioning systems. Secure all ducts
to building stn_ctt_re.
14. Flash, weatherproof, and vibration-isolate all openings in building stlucmre in accordance with local codes and good building practices.
_ --,2
- /
/
//
SUPPLY RETURN DUCT DUCT
OPENING OPENING
Fig. 8--Supply and Return Duct Opening
C99011
DUCT COVERS REMOVED
Fig. 9--Verticam Duct Dover Removed
C99012
i0
PROCEDURE8--[NSTALLELECTRICALCONNECTION
z_ WARNING: The unit cabinet mast have an uninterrupted, unbroken electrical ground to minimize the possibility of
persona[ injury if an electrical faamt should occur. This ground may consist of an emectrica[ wire connected to the unit ground lag in the contro[ compartment, or conduit approved for electrica[ ground when instaImed in accordance with NEC (National
Electrical Code) ANSJ/NFPA (latest edition) and [oca[ emectrica[ codes, in Canada, follow Canadian Electrical Code CSA (Canadian Standards Association) 022.i and local electrical codes. Failure to adhere to this warning could result in personal
injury or death.
z_ CAUTION: Failure to follow these precautions could resa[t in damage to the unit being installed:
1. Make aH electrical connections in accordance with NEC ANS_/NFPA ([atest edition) and Ioca[ eiectrica[ codes governing such wiring, h Canada, aH emectrica[ connections must be in accordance with CSA standard D22.1 Canadian Electrical
Code Part I and applicable Boca[ codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between field-supplied electrica! disconnect switch and unit. DO NOT USE ALUMINUM WIRE.
3. Be sure that highovoltage power to unit is within operating voltage range indicated on unit rating plate.
4. Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase
imbalance.
A. HGNoVOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-st/pplied, waterproo£ disconnect switch mounted at, or within sight fi'om_ the trait. Refer [o the unit rating plate for n_axinmm rhea/circuit breaker size and n_ininlum circuit amps (ampacity) _br wire sizing. See Tables 4 and 5 _br
electlical data. The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage
entw- points are used. See Fig. 2 & 3 for acceptable location. See unit wiring label and Fig. 10 for re_rence when making high voltage connections. Proceed as follows to complete the high-voltage connections
to the unit. Single phase units:
1. Ron the high-voltage (L1, L2) and ground leads into the control box.
2. Connect ground lead to chassis ground connection.
3. Connect L1 to pressure lug connection 11 of the compressor contactor.
4. Connect L2 to pressure lug connection 23 of the compressor contactor.
Three phase units:
1. Run the high-vohage (L1, L2, L3) and ground leads into the contlol box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the lines side of tl-_e contactor_
4. Connect field L! to black wire on connection 11 of the compressor contactor.
5. Connec_ field wire L2 to yellow wire on connection 13 of the compressor contactor.
6. Connect field wire L3 to Blue wire fi'om compressor_
B. SPECIAL PROCEDURES FOR 208-V OPERATION
Z_ WARNBNG: Make sure that the power supply to the unit is switched OFF and lockout tag installed before making any
wiring changes. Electrical shock can cause serious injury or death.
C. CONTROL VOLTAGE CONNECTmONS NOTE: Do not use any type of power-stealing thermostat Unit control problems may resulL
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimun_) wires to make the conhoi voltage connections between the thermostat and the unit. If the themaostat is located more than 100 R. ti'om the unit (as measured along the conhol voltage wires), use no. 16 AWG
color-coded, insulated (35 C n_ininmm) wires.
D. STANDARD CONNECTION
Remove knockout hole located in the electric heat panel adjacent to the control access panel See Fig. 2 & 3_ Remove the rubber grommet from d-_e installer's packet (included wid-_ unit) and install grommet in the knockout opening. Provide a drip loop before running wire through panel
Run the tow-voltage leads t'rom the d_ermostat, through the inlet hole, and into unit tow-voltage splice box_ Locate five 18-gage wires leaving conkol box. These tow-voltage connection leads can be identified by the colors red, green, yellow, brown, and
white (See Fig. 10). Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Stripped yellow wire is located in connection box. Route leads through hole in bottom of control box and make tow-voltage connections (See Fig. 10)_
Secure all cut wires, so tl-_at they do not interfere with operation of uniL
11
UNIT PAIP
SIZE
018
024
O3O
036
O42
O48
060
V-PH-HZ
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
VOLTAGE
RANGE
Min Max
187 254
TaMe 4--Electrical Data--PAIP
COMPRESSOR OFM {FM ELECTRIC HEAT
RLA LRA FLA FLA Nominal Kw* FLA
187 254
187 254
187 254
187 254
187 254
414 508
187 254
187 254
414 508
187 254
187 254
414 508
187 254
187 254
460-3-60 414 508
(SeeEegend fo{Iow{ng ElectdcN Data charts)
4-
38/5.0
9 45 0.80 18
54/7.2
75/100
-/-
38/5.0
12.8 61 08 2 54/7.2
75/100
-/-
38/5.0
14.4 73 08 2 54/7.2
75/100
113/150
-/-
38/5.0
83 68 08 2
75/100
113/150
-/-
38/5.0
15.1 81 14 28 54/7.2
75/100
113/150
-/-
38/5.0
10.9 78 14 28
75/100
113/150
5
58 40 08 14
10 15
38/5.0 54/7.2
18.6 105 14 4
75/100 113/150 150/200
4-
38/5.0
10.7 85 14 4 75/100 113/150 150/199
5
53 42 08 2 10
15
20
38/5.0 54/7.2
25.3 131 21 5
75/100 113/150 15 0/20 0
4-
38/5.0
14.6 108 21 5 75/100 113/150 15 0/19 9
5
73 48 11 23 10
15
20
38/5.0 54/7.2
28.9 147 21 68
75/100 113/150 150/200
4-
38/5.0
18.6 125 21 68 75/100 113/150 15 0/19 9
5 10 15
20
4-
181/208 260/300 361/417
181/208
2/30
361/417
4-
181/208 260/300 361/417 542/625
4-
104/12 0 208/241 313/361
4-
181/208 260/300 361/417 542/625
4-
104/120 208/241 313/361
6 12 18
4-
181/208 260/300 361/41 7 542/625 722/833
104/120 208/241 31 3/361 41 6/480
6 12 18
241
4-
181/208 260/300 361/41 7 542/625 722/833
4-
104/120 208/241 313/361 41 6/480
6 12 18
241
4-
181/208 260/300 361/41 7 542/625 722/833
4-
104/120 208/241 31 3/361 41 6/480
6 12 18 24
MCA
POWER SUPPLY
Max Fuse orCkt Bkr MOCP
20/20 25/30 35/40 50/60 25/25
305/30
35/40 50/60
25/25 25/30 35/40 50/60
-- 80/90 20/20 20/20 30/35 45/50 30/30 30/30 40/45 50/60
80/90
25/25 25/25 30/35 45/50
15 15 20
25 35/35 35/35 40/45 60/60
-- 90/100
-- 100/110
25/25 25/25 35/40 45/60
-- 60/70
15
15
20
30
35 40/40 40/40 40/45 60/60
-- 90/100
-- 100/125
30/30 30/30 35/40 50/60
-- 60/70
15
15
20
30
35 60/60 60/60 45/50
-- 60/70
-- 90/100
-- 100/125
40/40 40/40 40/40 50/60
-- 70/70
20
20
20
30
35
85 66.5 11 32
13.9/139
24.8/283
34.7/398
47.4/543
18.8/188
25.1/285 35/40
47.6/546
20.8/208
25.1/285 35/40
47.6/546
70.2/806
13.2/132
15.5/175
28.6/326
41.8/476
23.1/231
26.1/295
36.0/41 0
48.6/556
71.2/81 6
17.8/178
16.5/185
29.6/336
42.6/486
9.5
9.5 168 243
28.7/287
28.7/31 0
37.5/425
50.1/571
72.7/831
95.3/1092
18.8/188
31.1/351
44.1/501
57.0/650
9.4 100 175 251 326
38.7/387
38.7/387
38.7/438
51.4/583
73.9/844
96.5/1104
25.4/254
25.4/254
32.3/363
45.3/51 4
58.2/662 125 125 179 254 329
45.0/450
45.0/450
41.0/460
53.8/606
76.2/866
98.8/1127
32.2/322
32.2/322
34.6/386
47.6/536
60.5/685 149 149 190 266 34 1
E. TRANSFORMER PROTECTION The tra_.@)m_Teris of the energyotimiting type, It is set to withstand a 30-second overload or shorted secondao' condition
12
UNIT PA2P
SiZE
024
O30
036
O42
048
O6O
V_PH_HZ
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
VOLTAGE
RANGE
MM Max
187 253
Table 5--Emectrical Data--PA2P
COMPRESSOR OFM IFM ELECTRIC HEAT RLA LRA FLA FLA Nominal Kw FLA
187 253
187 253
187 253
187 253
414 506
187 253
187 253
414 506
187 253
187 253
414 506
187 253
187 253
460-3-60 414 506
(See legend foHowing Electrical Data charts)
109 54.0 09 2.0
135 73.0 08 2.1
90 63.0 08 2.1
167 97.0 08 3.6
112 75.0 08 3.6
54 37.5 09 1.9
-/- 4- 3 8/5.0 181/208 54/7.2 260/300
7.5/10.0 361/417
-/- 4-
38/5.0 181/208 54/7.2 260/300
7.5/10.0 361/417
113/150 542/625
-/- 4-
38/5.0 104/120
7.5/10.0 208/241
113/150 313/361
-/- 4-
38/5.0 181/208 54/7.2 260/300
7.5/10.0 361/417
113/150 542/625
-/- 4-
38/5.0 104/120
7.5/10.0 208/241
113/150 313/361
5 6 10 12 15 18
-/- 4-
38/5.0 181/208 54/7.2 260/300
7.5/10.0 361/417 113/150 542/625 150/200 722/833
-/- 4-
38/5.0 104/120
179 1040 15 4.1
MCA
POWER SUPPLY
Max Fuse orCkt Bkr MOCP
20/20 30/30 35/40 50/60 25/25 30/30 40/50
50/60
-- 80/90
20/20 20/20 30/35
-- 80/90 30/30 30/35 40/45 50/60
-- 80/90 25/25 25/25 35/35 45/50
15 15 20
25 35/35 35/35 40/45 60/60
-- 90/100
-- 100/110 25/25 25/25 35/40 45/60
-- 60/70
15 15 20 30
35 45/45 45/45 45/45 60/60
-- 90/90
-- 100/110 30/30 30/30 35/40 45/60
-- 60/70
15 15 20 25
35 60/60 60/60 45/50 60/60
-- 90/100
-- 100/125 35/35 35/35 35/40 50/60
-- 60/70
20 20 20 30 35
124 88.0 15 4.1 7.5/10.0 208/241
113/150 313/361 150/200 417/481
4-
5 60
61 44.0 09 1.9 10 120
15 180
20 241
-/- 4-
38/5.0 181/208 54/7.2 260/300
234 1260 16 4.1
7.5/10.0 361/417 113/150 542/625 150/200 722/833
-/- 4-
38/5.0 104/120
130 93.0 16 4.1 7.5/10.0 208/241
113/150 313/361 150/200 417/481
4-
5 60
64 46.5 09 2.0 10 120
15 180
20 241
-/- 4-
38/5.0 181/208 54/7.2 260/300
288 1690 16 6.2
7.5/10.0 361/417 113/150 542/625 150/200 722/833
-/- 4-
38/5.0 104/120
173 1230 16 6.2 7.5/10.0 208/241
113/150 313/361 150/200 417/481
4-
5 60
90 62.0 09 3.2 10 120
15 180
20 241
165/165 251/285 350/400 476/546
198/198 252/287 351/401
478/547 722/826
142/142
157/177 287/327 703/808 253/253 271/305 370/420 496/566 722/826
184/184
184/195 306/346 436/496
96 99
174
249 281/281 281/31 2 376/426 503/572 728/833
954/109.3
21 2/21 2 21 2/21 2 31 2/352 442/502 572/653
105 105
175 251 326
349/349 349/349 376/426 503/572 728/833
954/109.3
21 9/21 9 21 9/21 9 31 2/352 442/502 572/653
108
108
174 249 324
438/438 438/438 402/453 529/598 754/859
980/111.9
294/294 294/294 338/378 468/529 599/679
154
154
190 266 341
13
LEGEND
FLA -- FullLoadAmps LRA -- LockedRotorAmps MCA-- MinimumCircuitAmps
MOCP-- MaximumOvercurrentProtection RLA -- RatedLoadAmps
CKTBKR--CircuitBreaker
US
NOTES:
1. tn compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. Canadian units may be
fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. tf other than 60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply 'Voltage
Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance. % Vottage imbalance
= 100 x max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60.
A B C AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
3
= 457
Determine maximum deviation from average 'voltage.
(AB) 457 452=5v (BC) 464 457=7v (AC) 457 455=2v
Maximum deviation is 7 v. Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x --
457
: 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: tf the supply voltage phase imbalance is more than 2%, contact your local electric utility company
immediately.
C99024
HIGHVOLTAGE
1
POWER LEADS <_o- - (SEE UNIT WIRING|
LABEL) L_- -
CONTROLBOX
LOW-VOLTAGE _ ......
POWER LEADS- (SEE UNIT
WIRING LABEL)
SPLICE BOX
o-i
J
_[:_,' - POWER
°[[suPPLY
FIELD-SUPPLIED FUSED DISCONNECT
YF--LL_L_ Q
RED_R±_.
BRN(C_)_
THERMOSTAT
(TYPICAL)
LEGEND
Field ControFVottage Wiring Field High-Voltage Wiring
NOTE: Use blue wire for 3-phase units only.
Fig, 10--High- and Control-Voltage Connections
C99010
]4
PRE-STAR%UP
z_ WARNING: Failure to observe the following warnings could result in serious personal injury:
1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured.
3. Do not remove compressor terminam cover until all emectrical sources are disconnected.
4. Relieve and recover aH refrigerant from system before touching or disturbing anything inside terminal box if refrigerant
Beak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while refrigerant system is under pressure.
6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component,
wear protective goggles and proceed as folmows: a. Shut off electrical power to unit.
b. Relieve and reclaim aim refrigerant from system using both high- and low-pressure ports.
c. Cut component connecting tubing with tubing cutter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oim can ignite when exposed to torch flame.
Proceed as fbllows to inspect and prepare the unit fbr initial starmp:
1 Remove access panel
2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, uniL
3. Make the following inspections: a. Inspect fbr shipping and handling damages such as broken lines, loose parts, disconnected wires, etc.
b. Inspect fbr oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak test all
refi'igerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. If a refi'igerant leak is detected, see
(?beck for Refi'igerant Leaks section. c. Inspect all field- and fhctoryowiring connections. Be sure that connections are completed and tight. d. Ensure electrical wiring does not contact refrigerant tubes or sharp metal edges. e. Inspect coil fins. If damaged during shipping and handling, careffdly straighten fins with a fin comb.
Verif) the fbllowing conditions:
a. Make sure that condenser-fan blade is correctly positioned in fhn orifice. Leading edge of condenser-fan blade should be 1/2 in.
naaxinmm from fan orifice (See Fig. 1i)_
b. Make sure that air filter(s) is in place. c. Make sure that condensate drain tlap is filled with water to ensure proper &ainage. d. Make sure that all tools and miscellaneous loose parts have been removed.
START-UP
F. CHECK FOR REFRIGERANT LEAKS Proceed as fbllows to locate and repair a refi'igerant leak and to charge the unit:
1 Locate leak and make sure d-_atrefi'igerant system pressure has been relieved and reclaimed fiom both high- and tow-pressure ports
G,
MOTORANDFANHUB
MOTOR SHAFT
C99009
Fig. ll--Fan Blade Clearance
2 Repair leak following accepted practices. NOTE: Install a filter drier whenever tl-le system has been opened for repair. 3 Add a small charge of Ro22 refrigerant vapor to system and leakotest unit.
4. Recover refl'igerant f?om refi'igerant system and evacuate to 500 microns if no additional leaks are not found.
5. (;barge unit with R-22 ref?igerant, using a volumetric-charging cylinder or accurate scale_ R@_' lo zmit rating p/ate/br _'eqz_il'ed cha_ve. Be sure to add extra refi'igerant to compensate for internal volume of filter drier.
START UP COOLmNG SECTmON AND MAKE ADJUSTMENTS
Z_ CAUTION: Complete the required procedures given in the Pre-Starto Up section before starting the unit. Do not jumper
any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature is below 40°F (unless accessory Iowoambient kit is installed). Do not rapid-cycle the compressor. AHow 5 minutes between "on" cycles to
prevent compressor damage.
15
H. CHECKINGCOOLINGCONTROLOPERATION
Start and check the unit %r proper cooling control operation as %llows:
1. Place room thermostat SYSTEM switch in OFF position Obsela'e that blower motor starts when FAN" switch is placed in ON position and shuts down after 30 second _hn time delay expires when FAN switch is placed in AUTO position.
2. Place SYSTEM switch in COOL position and FAN" switch in AUTO position. Set cooling control below room ternperamre. Observe that compressor, condenser fan, and evaporator blower motors start. Observe that compressor and outdoor fan shut down when contIol setting
is satisfied and that indoor blower shuts down afier 30 second fire time delay expires.
3. When using an auto-changeover room thel_nostat, place both SYSTEM and FAN' switches in AUTO positions. Obsela-e that unit operates in heating mode when temperature conhol is set to "call for heating" (above room temperature) and operates in cooling mode when
temperature control is set to "call fbr cooling" (below room temperature).
IMPORTANT: Three-phase, scroll compressor units (PA1P048, PA2P030-060) are direction-oriented. These units must be checked to ensure
proper compressor 3-phase power lead orientation. If not corrected within 5 minutes, the internal protector will shut off the compressor. The
3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, scroll compressors emit elevated noise levels, and
the difference between compressor suction and discharge pressures may be &amatically lower than nom_al.
I. CHECKING AND ADJUSTING REFRBGERANT CHARGE
_fhe refi'igerant system is fldly charged with R-22 refrigerant, tested, and ihctory-sealed. NOTE: Adjustment of the refrigerant charge is not required unless the unit is suspected of not having the proper R-22 charge.
A superheat charging chart is attached to the outside of the service access panel. The chart includes the required suction line temperature at given
suction line pressures and outdoor ambient temperatures (See Fig. 15 27).
An accurate superheat, thermocouple- or thermistor-type thermometer, a sling psychrometer, and a gauge manifold are required when using the
superheat charging method fbr evaluating the unit charge. Do 1rot _*.seme_'c_¢_?"or .sma/[ dia/-Ope thermometer:_' beca_¢se th<_"are not a&,q_¢ate for thi.v _379e q/ sneas_lreme_t
NOTE: Allow system to operate in the cooling mode for a minimum of 10 minutes before checking or adjusting refi'igerant charge.
Z_X CAUTION: When evaluating the refrigerant charge, an indicated adjustment to the specified factory charge must
always be very minimal If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coim or both coils.
Proceed as %llows:
1. Remove caps fi'om low- and high-pressure service fittings
2. Using hoses with valve core depressors, attach tow- and high-pressure gauge hoses to low- and high-pressure service fittings, respectively
3. Start unit in Cooling mode and let unit run until system pressures stabilize
4. Measure and record the following: a. Outdoor arnhient-air temperature (_>F db).
b. Evaporator inlet-air ternperamre (_'F wb).
c. Suction-tube tenlperatme (_'F) at low-side service fitting. d. Suction (!ow-side) pressure (psig).
5. Using "Cooling Charging Cha_s" compare outdoor-air temperature (°F dfb) with the suction tine pressure (psig) to determine desired system operating suction line temperature. See Fig. 15-27.
6. Compare actual suction-robe temperature with desired suction-tube temperature. Using a tolerance of ÷3°F, add refi'igerant if actual
temperatt_re is more than 3_>Fhigher than proper suction-robe temperature, or remove refrigerant if acttml temperature is more than 3_>Flower than required suction-tube temperature.
NOTE: If the problem causing the inaccurate readings is a refi'igerant leak, refer to Check for Refl'igerant Leaks section.
J. INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
Z_ CAUTION: For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling
capacity.
Tables 8 and 9 show cooling airt)ows at various external static pressures. Refer to these tables to detem_ine the airflow _br the system being installed.
NOTE: Be sure that all supply- and return-air grilles are open, free from obstructions, and adjusted properly.
Z_ WARNmNG: Disconnect electrical power to the unit and install lockout tag before changing blower speed. Electrical
shock can cause serious injury or death.
Airflow can be changed by changing the lead connections of the blower motor Unit PAIP two- or three-speed motors (except size 030) are f3ctory wired for tow speed operation Unit PAIP030 is factoD" wired fbr rnediurn
speed
16
ACCESSORY ELECTRIC NEAT_
--!
COMMON
_127 BRN
R4V SPLICE BOX
UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN SECTION
@RESSOR ]TION
COMP
C S
INDOORFAN
SECTIONsoGsoGoONLY
50GXO42060
CONIROL UOX AREA
-EQUIP
GND
DISCONNECT
REL
-- RDN POWER ENTRY
LEGEND
z_, FIELD SPLICE C CONTACTOR o TERMINAL (MARKED) CAP CAPACITOR
o TERMINAL (UNMARKED) COMP COMPRESSOR MOTOR
SPLICE EQUIP EQUIPMENT
o SPLICE (MARKED) FU FUSE
FACTORY WIRING GND GROUND FIELD CONTROL WIRING FIR NEATER RELAY
---FIELD POWER WIRING NTR NEATER
=H ACCESSORY OR OPTIONALIFM INDOOR FAN MOTOR
WIRING IP INTERNAL PROTECTOR
--TO INDICATE COMMON OFM OUTDOOR FAN MOTOR POTENTIAL ONLY: QT QUADRUPLE TERMINAL
NOT TO REPRESENT SB SLOW BLOW FUSE WIRING ST TNERMISTOR START
TC TNERMOSTAT COOLING TDR TIME DELAY RELAY
TN TNERMOSTAT NEATING TRAN TRANSFORMER
NOTES:
I,IF ANY OF TNE ORIGINAL WIRES FURNISNED ARE REPLACED,
IT MUST BE REPLACED WlTN TYPE 90 DEGREE C WIRE OR IT'S EQUIVALENT
2SEE PRICE PAGES FOR TNERMOSTAT AND SUBBASES 5USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION
4,FOR NIGN SPEED IFM,DISCONNECT RED
WIRE FROM TDR;3 AND CONNECT BLK WIRE FROM IFM
FOR MEDIUM SPEED,DISCONNECT RED WIRE FROM TDR;S AND CONNECT BLU WIRE FROM IFM
TDR II_) FARSEQUENCE
D T T+30 6 6
ENERGIZED DE NNNNDIZND
C99003
Fig. 12--Wiring Diagram {208/230o60ol)
All PA2P units are facto O" wired %r tow speed and may need to be wired %r medium or high speed in the field
K. For 2081230V
For color coding on the 208 _0Vq_ motor leads, see Table 6,
17
NEAT SCNEMATIC
I
R ON G
AUTO Slg
TCI
°
AUTO
,IEA 0FF
TH_o
300L M _I
AUTO _ _c--_@_
HEAT TH2
OFF
W2
SEE NOTE#2
COMMON
136 YEL
RED_
YEL
WI55 BLK
YEL PRIMARY
WI56 460V
TRANI @.W25
i
WI21 RED
Wl6 GRN
WlI5 YEL
Z_- W72 WNT
Wl63 PNK
WlD2 VlO
I
I
WI66 GRA I
WI53 BRN
3"
W127 BRN
CAP2 YEL OFM
@_BFIN
060 ONLY
LI
WIg7 YEL COMP
L5
GRN YEL _W26 GRN YEL
I
/
GRN YEL OF/N YEL
IFM
WII BRN
ORN
BRN
WIIBRN
WIO BFIN
BRN
ACCESSORY ELECTRIC klEAT_
W7O BRN
153 BRN
NRI (5 KW)_k BRN
NRI & 2 (IO KW)_w7o BRN
NRI,R & 3 (15 KW)__------_4_j BRNBRN
@1,2,3 & 4 (20 KW)
24V SPLICE BOX
UNIT COMPONENT ARRANGEMENT
3UTDOOR FAN
SECTION
COMPFIE_SOFI INDOOR FAN CONTROL BOX AREA
SECTION SECTION
COMP
c 8
R
50GXO42 OGO
ilNGLE PT
iCONNECTION iFOR iELECTHEAT
iSEE HEATER J
/EQUIP
6ND
r--i
I
24_ POWER ENTRY
LEGEND
FIELD SPLICE C CONTACTOR TERMINAL (MARKED) CAP CAPACITOR
o TERMINAL (UNMARKED) COMP COMPRESSOR MOTOR
o SPLICE EQUIP EQUIPMENT
c_SPLICE (MARKED) GND GROUND
FACTORY WIRING NR PLEATER RELAY FIELD CONTROL WIRING IFM INDOOR FAN MOTOR
--_ FIELD POWER WIRING IP INTERNAL PROTECTOR
--- ACCESSORY OR OPTIONALOFM OUTDOOR FAN MOTOR WIRING QT QUADRUPLE TERMINAL
--TO INDICATE COMMON TC TNERMOSTAT COOLING POTENTIAL ONLY: TDR TIME DELAY RELAY
NOT TO REPRESENT TN TNERMOSTAT NEATING WIRING TRAN TRANSFORMER
NOTES:
TDR[13) FAN SEQUENCE
0 T T+_O G G
ENEIIGIZED DEENERGIZED
IIF ANY OF TNE ORIGINAL WIRES FURNISNED ARE REPLACED,
IT MUST BE REPLACED WITN TYPE go DEGREE C WIRE OR IT'S EQUIVALENT
2SEE PRICE PAGES FOR TNERMOSTAT AND SUBBASES
3,USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION,
4,FOR NION SPEED IFM,DISCONNECT RED
WIRE FROM TDR;3 AND CONNECT BLK WIRE FROM IFM FOR MEDIUM SPEED,DISCONNECT RED WIRE
FROM TDR;# AND CONNECT BLU WIRE FROM IFM
C99004
Fig, 13--Wiring Diagram (208!230o60o3)
To change the speed of the indoor £aa motor (IFM), remove the Jim motor speed leg lead [?om the time delay relay (TDR). This wire is attached
to temainal 3 of TDR for singleophase and 3ophase units To change the speed, remove and replace with lead for desired blower motor speed Ins_date t,/Te removed lead to moid contact _ith chassis pat%.
L FOR 460oV G_= MOTORS
For color coding on the 460ox GE motor leads, see Table 7
18
MAXIMUM WIRE SIZE 2 AWG
USED WlTN ACCESSORY
ELECTHEAT OPTION ONLY
USED WITN NEATER OPTIONS
5,10 & 15 KW MAXIMUM WIRE
SIZE 2 AWG
USED WITN ACCESSORY
ELECTNEAT OPTION ONLY,
USED WITN NEATER OPTIONS
20 KW (ONLY) MAXIMUM WIRE
SIZE 2/0 AWG
ON G
THI
COMMON
SEE NOTE#Z
_- Wl6 GRN
G WlI3 YEL
Z_Z W72 WNT
Wl63 PNK
W162 VlO
I Wl64 GRA
E
_J_ Wl55 BRN
WI27 BRN
Z4V SPLICE BOX
UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN
SECTION
CONTROLBOXAREA
SINGLEPTi
CONNECTION
FOR
ELECTHEAT
.....
p; p,CE_
COMPRESSOR INDOOR FAN SECTION SECTION
c S
R
COMP
506X042 060
Wll BRN WlO BRN
BRN
ACCESSORY ELECTRIC klEAT_
_,,,, I I _ _WYO BRN
NRI (5 ,,,_,___ R ,)CD_wls5 BRN
NR, NR I,DKWl "-" BRN
NRI,2 & 3 (15KW)_ k
NRI,Z,3 & 4 (20 KW) ___ Dr_
_ %-J_,J%=J
I I
LEGEND
-EQUIP
ORB
-- 24V POWER ENTRY
FIELD SPLICE C CONTACTOR
<:D TERMINAL (MARKED) CAP CAPACITOR
o TERMINAL (UNMARKED) COMP COMPFIESSOFIMOTOR o SPLICE EQUIP EQUIPMENT
<3, SPLICE (MARKED) FU FUSE
FACTORY WIFIING GND GROUND
FIELD CONTROL WlFIING NR NEATEFI FIELAY
--- FIELD POWERWlFIING NTR PLEATER
=H ACCESSORY OR OPTIONALII_M INDOOFI FAN MOTOFI
INTERNAL PROTECTOR
WIRING OFM OUTDOOR FAN MOTOR
--TO INDICATE COMMON POTENTIAL ONLY: QT QUADRUPLE TERMINAL
NOT TO REPRESENT S,B, SLOW BLOW FUSE
WIRING TC TNERMOSTAT COOLING
TDR TIME DELAY RELAY TN TNERMOSTAT PLEATING
TRAN TRANSFORMER
NOTES:
IIF ANY OF TNE ORIGINAL WIRES FURNISNED ARE REPLACED,
IT MUST BE REPLACED WlTN TYPE 90 DEGREE C WIRE OR IT'S EQUIVALENT
2SEE PRICE PAGES FOR TNERMOSTAT AND SUBBASES 5USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION,
4,FOR NIGN SPEED IFM,DISCONNECT RED
WIRE FROM TDR;3 AND CONNECT BLK WIRE FROM IFM
FOR MEDIUM SPEED,DISCONNECT RED WIRE FROM TDR;3 AND CONNECT BLU WIRE FROM IFM
TDR(13} FANSEQUENCE
0 T T+30 G
ENEROIZED DE ENERGIZED
C99005
Fig, 14--Wiring Diagram (460o60o3)
To change the speed of the indoor fan motor (IFM), remove fun motor speed lead from the time delay relay (TDR) and replace with the lead %r the desired blower motor spee& The motor speed lead is attached to terminal 3 of TDR_ For low and medim_n speeds black must be connected
to the jumper wire./n.sz#ate remuled lead end to mE)id contact _,Jt,/l C,I_a.S.SR.SparXx. To select high speed on 460_v GE motors, separate the black female quick connect (QC) flora the jumper lead male quick connect (QC) and connect the black lead to the BR. ]nsz#clte thejzm_psr to moid
conlact _ith an}: chas,sis pro%'.
19
f
Table 6--Color Coding for 208/230=V Motor Leads
3-SPEED 2-SPEED
Nack = high speed black = high speed
blue = medium speed
red = low speed red = low speed
Table 7--Color Coding for 460-V GE Motor Leads
3-SPEED
Nack = high
violet = jumper
orange = medium
red = low
2-SPEED
black = high
blue = jumper
red = low
M. COOLING SEQUENCE OF OPERATmON
With [l_eroom thermostat SYSTEM switch in the (eel position and the FAN switch in the AUTO position, the cooling sequence of operation
is as fPllows:
When the room temperatnre rises to a point that is slightly above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G These completed circuits through the thermostat connect contactor coil (C) (through unit wire
Y) and time delay relay (TDR) (through unit wire G) ac*oss the 24ov seconda W of transformer (TRAN).
The normally open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fire motor (OFM). Both motors start instantly.
The set of normally open contacts of energized relay TDR close and complete the circuit through evaporator blower (indoor) fhn motor (IFM) NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapse& The cooling cycle remains _on" until the room temperature drops to a point that is slightly below the cooling control setting ot'the roonr thermostat.
At this point, the tl'lcrmostat "breaks" the circuit between thermostat terminal R to terminals Y and G These open circuits deenergize contactor
coil C and relay coil TDR The condenser and compressor motors stop After a 30-second delay, the blowe* motor stops The unit is in a %tandhy" condition, waiting for the next "call for cooling" fi'om the room thermostat.
MAINTENANCE
To ensure continuing high performance_ and to minimize &e possibility of premature equipment _hilure_periodic maintenance must be perfPrmed on this equipment. This cooling unit should be inspected at 1east once each year by a qualified service person To troubleshoot heating or cooling
of units, refer to tables at the back of the book.
NOTE TO EQUIPMENT OVv_'ER: Consult your local dealer about the availability of a maintenance contract.
z_ WARNING: The abHRy to propedy perform maintenance on this equipment requires certain expertise, mechanical
skills, tooJs, and equipment, ffyou do not possess these, do not attempt to perform any maintenance on this equipment other
than those procedures recommended in the User's Manual FAILURE TO HEED THS WARNmNG COULD RESULT IN SERIOUS
PERSONAL [NJURY AND POSSIBLE DAMAGE TO THIS EQUmPMENT.
Z_ WARNmNG: Failure to follow these warnings could resuR in serious persona[ injury:
1. Turn off electrica[ power to the unit and install Bockout tag before performing any maintenance or service on the unit.
2. Use extreme caution when removing panems and parts. As with any mechanical equipment, persona[ injury can result from sharp edges, etc.
3. Never place anything combustible either on, or in contact with, the unit.
Z_ CAUTION: Errors made when reconnecting wires may cause improper and dangerous operation. Labem all wires prior
to disconnection when servicing.
The minimum maintenance requirements %r this equipment are as %llows:
1. Inspect air filter(s) each month Clean or replace when necessa_-
2. Inspect indoor coil, &ain pan, and condensate &ain at least each cooling season for cleanliness. Clean when necessaw.
3. Inspect blower motor and wheel for cleanliness and check lubrication each heating and cooling season. Clean when necessary.
4. (heck electrical connections fk_r tightness and controls t'or proper operation each heating and cooling season. Service when necessao,-.
5. Ensure electric wires are not in contact with refiigerant robing or sharp metal edges.
N. AIR FILTER
2O
Tab[e8--WetCoilAirDelivery(Deduct!0 percentfor208v)*
HorizontalandDownflowDischarge
UnitPAIP018o060
230AND4G0VOLT
ExternalStaticPressure(in.wg)
Unit
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
227 212 196 177 165 153
1000 915 825 710 530 340
018
287 275 266
1150 1032 963
280 275 270
880 825 765
380 375 365 335 312
024
1136 1085 1010 495 360
485 475 470 430 415 385
1415 1332 1266 780 480 256
280 275 270
880 825 765
380 375 365
030
1136 1085 1010
485 475 470
1415 1332 1266
576 566 556
1385 1297 1220
680 671 660 496
036
1572 1460 1375 730
810 800 790 627
1685 1620 1560 800
675 660
1387 1326
886 855 700
042 1458 1406 870
833
1005
727
1640
853
048 1860
979
2090
1033 949
2050 2000
1084 1054
060
2248 2179
Motor
Speed
Low
Med High
Low
Med High
Low
Med High
Low
Med High
Low
Med High
Low
Med High
Low Med High
Watts
Cfm
Watts
Cfm
Watts 253 242 234 226
Cfm 807 698 503 250
Watts 267 264 262 260
Cfm 693 600 450 281
Watts 360 355 350 344
Cfm 946 865 787 650
Watts 460 455 445 437
Cfm 1180 1100 1000 900
Watts 267 264 262 260
Cfm 693 600 450 281
Watts 360 355 350 344
Cfm 946 865 787 650
Watts 460 455 445 437
Cfm 1180 1100 1000 900
Watts 538 512 497 481
Cfm 1165 1090 995 905
Watts 624 604 620 602
Cfm 1305 1286 1192 1125
Watts 782 766 742 723
Cfm 1486 1389 1322 1284
Watts 650 640 630 620
Cfm 1275 1204 1142 1081
Watts 825 795 778 765
Cfm 1350 1285 1224 1163
Watts 1000 950 925 910
Cfm 1488 1424 1360 1296
Watts 712 700 688 666 644
Cfm 1600 1575 1505 1450 1390
Watts 836 821 807 782 756
Cfm 1830 1770 1700 1642 1565
Watts 959 943 927 897 868
Cfm 2048 1997 1922 1845 1750
Watts 864 836 822 808 772
Cfm 1945 1905 1880 1820 1775
Watts 1024 994 971 955 928
Cfm 2110 2058 2000 1932 1885
Watts 1184 1152 1120 1102 1084
Cfm 2278 2207 2124 2041 2000
335 312 495 360 430 415 385 780 480 256 466 450 435
846 715 609 558 534 512
1046 891 800
709 688 661
1170 1000 897
610 595 580 995 918 850 750 735 718
1091 1013 932
890 875 855
1233 1148 1071
622 595 569
1300 1205 1145
730 699 667
1482 1385 1290
838 802 766
1600 1550 1425
737 705 674
1695 1627 1530
897 867 835 1829 1740 1638 1056 1029 997
1960 1856 1748
640
1210
730
1380
642
1480
803
1569
965
1645
Air delivery values are based on operating vo{tage of 230v or 460v, wet coil, without Nter or electric heater Deduct fi{ter and electric heater pressure drops to obtain static
pressure available for ducting NOTES:
1 Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point
2 Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended
Z_ CAUTION: Never operate the unit without a suitable air filter in the returnoair duct system. Always replace the filter with
the same dimensional size and type as originally installed. See TaMes 1 and 2 for recommended filter sizes.
Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanableotype) at least twice &_ring each heating and cooling season or whenever the filter(s) becomes clogged with dr/st and lint,
21
Table 9--Wet Coit Air Delivery (Deduct 10 percent for 208v)*
Horizontal and Downflow Discharge
Unit PA2P024o060
230 AND 460 VOLT
Motor External Static Pressure (in. wg)
Unit
Speed 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 281 282 281 278 276
Low
Cfm 833 776 702 638 554
Watts 375 370 363 357 352
024 Med
Cfm 894 800 754 636 518
Watts 468 457 444 431 423
High Cfm 884 802 697 467 397
Watts 246 244 243 241
Low
Cfm 910 806 749 680
Watts 343 339 336 332 328 322 317
030 Med
Cfm 1148 1104 1028 958 850 782 645
Watts 441 432 421 410 400
High Cfm 1102 988 896 783 529
Watts 470 458 445 430 415 399 384
Low
Cfm 1352 1257 1240 1199 1107 1015 924
Watts 514 501 487 471 455 438 422
03G Med
Cfm 1338 1295 1288 1181 1111 968 813
Watts 646 636 626 614 602 589
High Cfm 1385 1268 1196 1159 1032 948
Watts 625 614 605 593 574 549 518 485 454
Low
Cfm 1540 1510 1473 1396 1348 1288 1192 1124 1037
Watts 726 695 661 625 591 561 540
042 Med
Cfm 1648 1593 1530 1446 1352 1237 1114
Watts 790 766 7421 713
High Cfm 1616 1492 1394 1283
Watts 588 577 572 566 556 539 517 491
Low
Cfm 1514 1543 1467 1408 1374 1324 1237 1161
Watts 756 738 719 699 676 650 623 596 572 555
048 Med
Cfm 1785 1765 1706 1628 1577 1503 1421 1357 1298 1253
Watts 896 862 829 800 775 752 728
High Cfm 1880 1804 1704 1547 1565 1406 1367
Watts 903 898 873 842 814 792 777 764 743 701 618
Low
Cfm 2190 2158 2081 2026 1958 1866 1822 1744 1678 1535 1377
Watts 1002 978 960 941 914 880 839 798 764 750
060 Med
Cfm 2389 2291 2216 2120 2020 1952 1852 1727 1617 1549
Watts 1080 1080 1066 1041 1008 972 938
High Cfm 2316 2181 2122 2101 2000 1802 1672
Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static
pressure available for ducting. NOTES:
1 Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity Evaporator ceil frosting may occur at airflows below
this point.
2 Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended. O. EVAPORATOR BLOWER AND MOTOR
NOTE: All motors are prelubricate& Do not attempt to lubricate these motors
For longer lit'c, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.
Z_ WARNmNG: Disconnect and tag electrical power to the unit before cleaning the blower motor and wheel Faiture to
adhere to this warning coumd cause personal injury or death.
To clean the blower motor and wheel:
1. Remove and disassemble blower assembly as %llows: a Remove unit access panel
b. Disconnect motor lead t?om time delay relay (TDR). Disconnect yellow lead t?om terminal L2 of the contactor.
c. On all units remove blower assembly t'rom unit. Remove screws securing blower to blower partition and slide assembly out. Be carefid
not to tear insulation in blower compartment. d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing befbre disassembly. e. Loosen setscrew(s) that secures wheel to motor shaR, remove screws that secure motor mount brackets to housing, and slide motor and
motor mount out of housing.
22
30 40 SO BO 70 80
SUCTION LINE rEMPERATURE (oF)
I I I I I I
4 10 18 21 27
SUCTION LINE TEMPERATURE {"C)
9O
I
32
C99037
30 40 50 80 70 80 90
SUCTION LINE TEMPERATURE {_F)
I I I I I I I
4 10 16 21 27 32
SUCTION LINE TEMPERATURE (_C)
Fig, 17--Cooling Charging Chart, PAIP030 Units
2 Remo_e and clean blov, er wheel as follows:
a. Ensure prope* reassembly by marking xsheel o*ientation
30 40 50 SO
SUCTION LINE rEHPERATURE
I I I I
4 10 16
5UOTION LINE TEMPERATURE
: o_?ooR:TP
Z 115 48
105 41
96 35 85 29
76 24
65 18 55 13
70 80 90
(°F)
I I I
21 27 32
("CI
_. 16--CoDlin{
7581 I10
6891 100
A us
<_ 82 I 90
o E <c m
£ 5521_o
trl u i tr_ cc lus
cc_
us 4831 _ FO w us
c_ Iz
u z z
4n41_o6o
z iS
co I_
o_ 3451 So D
crj
2761 40
3O
30 40 SO 80 70
SUCTION LINE TEMPERATURE {"F)
I I I I I I I
4 10 18 21 27 32
SUCT]ON LINE TEMPERATURE (°C)
PAl P024 Unit_ 99039
E 4E
,S 41 IS 35
IS 29
'S 24 ;5 18
;5 13
5 7
iIIIl
80 80
Fig. 18--Cooling Charging Chart, PAIP036 Units c99040
b Lift wheel flora housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel
vanes,
c. Remove caked=on dirt fi'om wheel and housing with a brush. Remove lint and/or dirt accumulations flora wheel and housing with vacuum
cleaner, using soft brush attachment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing. e, Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of' shaft.
fi Reinstall unit access panel
3. Restore electrical power to unit. Start unit and check £br proper blower rotation and motor speeds during heating and cooling cycles.
P. CONDENSER COIL, EVAPORATOR COIL, AND CONDENSATE DRAIN PAN
Inspect the condensei coil, evaporator coil, and condensate drain pan at least once each year
The coils are easily cleaned when du-; therefore, inspect and clean the coils either betk_re or after each cooling season, Remove all obsm/ctions,
including weeds and shrubs, that interfere with the airflow through the condenser coil.
23
30 40 50 50 ?0 80 90
SUCTION LINE TEMPERATURE (_F}
I I I I I I I
4 10 18 21 27 32
SUCTION LINE TEMPERATURE ('C)
7581 I 1 0
6891 100
621 90
< m
o_ Is
ss21_0
crl w I m cd I_
W Is
Iz
w
z414 zSO
z I_
o ID
Lr_
o 3451 50
2761 40
OUTDOORTEI4P
F C
115 46 105 41
95 35 85 29
75 24 65 18
55 13
45 7
3O
30 40 SO BO 70 80 90
SUCTION LINE TEHPERATURE (°F}
I I I I I I I
4 10 18 21 27 32
SUOTION L]NE rEMPERATURE ("C)
!9--Coolinc PAl P042 Units O99041 20--CoDlin( PAl P048 Unit_ 99042
(024) 60HZ CHARGING CHART
30 40 SO 80 70 80 90 30 40 50 50 70 80 90
SUCTION LINE TEMPERATURE ((F} SUCTION LINE TEMPERArURE {°F)
I I I I I I I I I I I I I I
4 10 I 5 21 27 32 4 I 0 16 2/ 27 32
SUCTION LINE rEkIPERATURE ("C) SUCHON LINE TENPERATURE ('C)
Fig. 22--Cooling Charging Chart, PA2P024 Un[t_ 99044
Straighten bent fins with a fin comb. It" coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft blT_/sh attachment. Be card:'ul
not to bend the fins. If coated with oil or grease, clean the coils with a mild detergentoand-water solution. Rinse coils with clear water, using a
garden hose. Be card:'ul not to splash water on motors, insulation, wiring, or air _ter(s). For best results, spray condenser coil fins fi'om inside
to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris fiom the unit base
Inspect the &ain pan and condensate drain line when inspecting the coils Clean the &ain pan and condensate drain by removing all foreign matter fiom the pan. Flush the pan and drain robe with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube
is restricted, clear it with a "plumbers snake" or similar probe device Ensure that the auxiliary &ain port above the drain tube is also clear
Q. CONDENSER FAN
Fig. 21--Cooling Charging Chart, PAIP060 Units
A CAUTION: Keep the condenser fan free from al! obstructions to ensure proper cooling operation. Never place articles
on top of the unit. Damage to unit may result.
1. Remove 6 screws holding condenser grille and motor to top cover.
2. Turn motor grille assembly upside doN',n on top cover to expose the f_n blade.
24
(030) 60HZ CHARGING CHART
30 40 80 B0 70 80 90
5UOT]ON LINE TEMPERATURE (_F]
I I I I I I I
4 10 18 21 27 32
5UCTION LiNE rEMRERATURE ('C)
(036) 60HZ CHARGING CHART
30 40 80 BO 70 80 90
8UOT]ON LINE TEMPERATURE (_F}
I I I I I I I
4 10 16 21 27 32
5UCTION LiNE rEMRERATURE ('C)
23--Coolinc PA2P030 Unit C99046 , 24--Coolin_
(042) 60HZ CHARGING CHART
PA2P0S6 Unit C99045
(048) 6OHZ CHARGING CHART
30 40 80 BO 70 80 BO 30 40 80 BO 70 80 90
SUOT]ON LINE TEMPERATURE (°F} SUOT]ON LINE TEMPERATURE (°F}
I I I I I I I I I I I I I I
4 10 16 21 27 32 4 10 16 21 27 32
5UCTION LiNE rEMPERATURE ('C) 5UCTION LiNE rEMPERATURE (_C)
Fig. 25--Cooling Charging Chart, PA2P042 Units
3 Inspect the £'anblades [or cl"acks or bends.
Fig. 26--Cooling Charging Chart, PA2P048 UPdt c99048
4. If fan needs to be ren_oved, loosen the setscrew and slide the tim off the motor shaft. 5 When replacing I:hn blade, position blade so that the hub is 1/8 in away fl'on_ the n_otor end (i/8 in of'motto" shaft will be visible).
6 Ensure that setscrew engages the fiat area on the n_otor shaft when tightening 7 Replace grille
R. ELECTRmCAL CONTROLS AND WIRING
Inspect and check the electrical contl"ols and wil"ing annually. Bc .s_'c to t_w off 1/7ee[ecmicct[ !_one_' to the m_it _md i_.st_/l [oc_'o_t tag,. Remove access panel to locate all the electrical controls and wiring. Check all electlical connections t'or tighmess. Tighten all screw connections.
I["any 8n_oky or burned connections are noticed, disassemble the connection, clean all the parts, restdp the wire end and reassen-,ble the connection pl"operly and securely
After inspecting the electrical controls and wiring, *'eplace the access panel. Start the unit, and observe at 1east one complete heating cycle and one con_plete cooling cycle to ensure proper opmation. If discl"epancie8 are observed in either or both operating cycles, or if a suspected n_alt'unction
}*asoccmTed, check each electrical component with the proper electl"ical instrun_entation. RefEr to the unit wiring label when making these checkouts.
25
(060) 60HZ CHARGING CHART
30 40 50 B0 70 80 90
5UOT]0N LINE TEMPERATURE (°F]
I I I I I I I
4 10 16 21 27 32
SUCTION LINE rEMPERATURE ('C)
C99049
Fig. 27--Cooling Charging Chart, PA2P060 Units
NOTE: Refkr to the heating aador cooling sequence of operation in this publication as an aid in determining proper control operation
S. REFRIGERANT CIRCUIT
Inspect all rd'rigeraat robing connections and the trait base _br oil accumulations annually Detecting oil generally indicates a refiigerant leak.
Z_ WARNING: System under pressure. Relieve pressure and recover all refrigerant before system repair or final unit
disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.
If oil is detected or if low cooling performance is suspected, leak-test all refi'igerant robing using an electronic teakodetector, halide torch, or liquid-soap solution. If a refi'igeraat leak is detected, refer to Check for Ref?igerant Leaks section.
If no refl'igerant leaks are found and tow cooling perfbrmance is suspected, refer to (becking and Adiusting Refl'igerant Charge section.
T. EVAPORATOR A_RFLOW
_he heating and/or cooling air-flow does not require checking unless improper performance is suspected_ [f'ct/_'ob/_m e._%'tx, be xz_t'e thE,# a[!
suppll- as_d return-air grilles are opes_ and /7"ee.fi'om o/_strzzctions, and that 117eair fi/ter is c/eas_. When necessary, refer to Indoor Airflow and
Airflow Adjustments section to check the system airflow.
U, METERING DEVICE -- ACUTROL DEVICE This metering device is a fixed orifice and is located in the header to the evaporator coil.
V. LIQUID LINE STRAINER
_he liquid line strainer (to protect metering device) is made of wire mesh and located in the liquid line on the inlet side of the metering device.
TROUBLESHOOTING
Lse the 7>o_lb!e,shooth_gCoo/i*_g guide (see Table 10) if problems occur with these units
START-UP CHECKUST
Lse the StartoL p checklist to ensure proper startoup procedures are %llowed
26
Table 10--Trou b[eshooting--Coo[ing
SYMPTOM
Compressor and condenser fan wiil not start.
Compressor will not start but condenser fan
runs.
CAUSE
Power Failure
Fuse blown or circuit breaker tripped
Defective thermostat, contractor, transformer, or
control relay
Insufficient line voltage
Incorrect or faulty wiring
Thermostat setting too high
Faulty wiring or loose connections in compressor
circuit
Compressor motor burned out, seized, or internal
overload open
Defective run/start capacitor, overload, start relay
One leg of 3-phase power dead
Three-phase scroll compressor (PAl P048,
PA2P030o060} makes excessive noise, and Scroll compressor is rotating
there may be a low pressure differential inthe wrong direction
Compressor cycles
(other than normally satisfying thermostat),
Compressor operates continuously.
Excessive head pressure.
Head pressure too low.
Excessive suction pressure,
Suction pressure too low.
Refrigerant overcharge or undercharge
Defective compressor
Insufficient line voltage
Blocked condenser
Defective run/start capacitor, overload or start
relay
Defective thermostat
Faulty condenser-fan motor or capacitor
Restriction h_refrigerant system
Dirty air filter
Unit undersized for load
Thermostat set too low
Low refrigerant charge
Leaking valves in compressor
Air in system
Condenser coil dirty or restricted
Dirty air filter
Dirty condenser coil
Refrigerant overcharged
Air in system
Condenser air restricted or air short-cycling
Low refrigerant charge
Compressor valves leaking
Restriction in liquid tube
High heat load
Compressor valves leaking
Refrigerant overcharged
Dirty air filter
Low refrigerant charge
Metering device or low side restricted
Insufficient evaporator airflow
Temperature too low in conditioned area
Outdoor ambient below 40°F
Field-installed filter-drier restricted
REMEDY
Call power company
Replace fuse or reset circuit breaker
Replace component
Determine cause and correct
Check wiring diagram and rewire correctly
Lower thermostat setting below
room temperature
Check wiring and repair or replace
Determine cause
Replace compressor
Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause
Correct the direction of rotation by reversing the 3-phase power leads to the unit Shut down unit
to allow pressures to equalize.
Recover refrigerant, evacuate system, and re-
charge to capacities shown on nameplate
Replace and determine cause
Determine cause and correct Determine cause and correct
Determine cause and replace
Replace thermostat
Replace
Locate restriction and remove
Replace filter
Decrease load or increase unit size
Reset thermostat
Locate leak, repair, and recharge
Replace compressor
Recover refrigerant, evacuate system, and re-
charge
Clean coil or remove restriction
Replace filter
Clean coil
Recover excess refrigerant
Recover refrigerant, evacuate system, and re-
charge
Determine cause and correct
Check for leaks repair and recharge
Replace compressor
Remove restriction
Check for source and eliminate
Replace compressor
Recover excess refrigerant
Replace Filter
Check for leaks, repair, and recharge
Remove source of restriction
Increase air quantity
Check filter- replace if necessary
Reset thermostat
Install low-ambient kit
Replace
2?
START-UP CHECKLIST
(REMOVE AND STORE mNJOB FILE)
I. PRELIMINARY ]NFORMATION
Model No .............................................................................................................................................................
Serial No ..............................................................................................................................................................
Date .....................................................................................................................................................................
Technician ...........................................................................................................................................................
Job/Location ...............................................................................................................................................
II. PRE-START-UP
Verify that all packing materials have been removed tiom unit Verify that condensate connection is installed per installation instructions Check all electrical connections and tcm_inals for tightness Check that indoor (evaporator) air filter is clean and in place Verify that unit installation is level Check f_tnwheel propeller fbr location in housing and setscrew tightness
IIL START-UP
Supply Voltage: LIoL2(CoS) L2oL3(S-R) L3oLI(R-C) Compressor Amps: LI(C) L2(S) L3(R) Indoor (Evaporator) Fan Amps:
TEMPERATURE
Outdoor (Condenser) Air Temperature: DB RemrnoAir Temperature: DB WB Cooling Supply Air: DB WB
PRESSURES
Retiigerant Suction psig Suction Line Temp* Refiigerant Discharge psig
Discharge Tempi
Verify Refi-igerant charge using charging rubles Verify that 3-phase scroll compressor (PA1P048 and PA2P030 060) is rotating in correct direction.
* Measlued at suction inle_ to comp_essol
* Measmed at Iiquid lille leavil_g cond_nsel
Form: IM-PA1P-03 Cancels: IM-PA1P-02 Printed in U.S.A. Page 28 2002 Payne Heating & Cooling Catalog No. 53PA-1P7
Loading...