CONTENTS
Page
SAFETY CONSIDERATIONS ...................... 1 4
I. General ................................... 1
RECEIVING AND INSTALLATION .................. 5-10
I. Step 1 -- Check Equipment .................. 5
II. Step 2 -- Provide Unit Support ............... 5
Ill. Step 3 -- Provide Clearances ................ 5
IV. Step 4 -- Place Unit ........................ 5
V. Step 5 -- Select and install Ductwork .......... 6
VI. Step 6 -- Provide for Condensate
Disposal .................................. 7
VII. Step 7 -- Install Electrical Connections ......... 7
PRE-START-UP ................................. 11
START-UP .................................... 11 14
I. Check for Refrigerant Leaks ................. 11
I1. Start-Up Cooling Section and
Make Adjustments ......................... 11
II1. Refrigerant Charge ......................... 11
IV. Indoor Airflow and Airflow Adjustments ....... 14
V. Unit Controls .............................. 14
VI. Sequence of Operation ..................... 14
MAINTENANCE ................................ 14 17
I. Air Filter .................................. 16
I1. Unit Top Removal (Condenser
Coil Side) ................................. 16
II1. Evaporator Blower and Motor ................ 16
IV. Condenser Coil, Evaporator Coil,
and Condensate Drain Pan .................. 16
V. Condenser Fan ............................ 17
VI. Electrical Controls and Wiring ............... 17
VII. Refrigerant Circuit ......................... 17
VIII. Evaporator Airflow ......................... 17
IX. Metering Devices .......................... 17
X. Liquid Line Strainer ........................ 17
TROUBLESHOOTING COOLING CHART ............ 18
START-UP CHECKLIST .......................... CL-1
NOTE TO INSTALLER -- Before the installation, READ
THESE INSTRUCTIONS CAREFULLY AND COMPLETELY.
Also, make sure the Owner's Manual and Sex-vice Instruc
tions are left with the unit after installation.
Cancels: New II PAIZ 24-1
11/15/97
Fig. 1 -- Unit PAIZ (Size 036 Shown)
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified workers should install,
repair, or service air-conditioning equipment.
Untrained workers can perform basic maintenance flmc-
tions of cleaning coils and filters. All other operations should
be performed by trained service people. When working on air-
conditioning equipment, pay attention to precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
I. GENERAL
The PA1Z cooling unit is flflly selficontained and designed
for outdoor installation, See Fig. 1. As shown in Fig. 2 4, units
are shipped in a horizontal discharge configuration fox"instal
lation on a ground level slab. All units can be field converted
to downflow discharge configurations for rooftop applications
with a field-supplied plenum.
247.6
[97R]
L,r
CONI_=NSER
O0_L
_294 0 _4080
[11.51] [16.N6]
0 " n
EVAPORATOR
REAR VIEW
[_O,NB)
3S6 DIA. DUCT OPENIN6S
[14,0]
t
il --y--
II
II
II
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L -- mm (in.)
Top of Unit ...................................... O
Duct Side of Unit .................................. O
Side Opposite Ducts ................................ 0
Bottom of Unit .................................... 0
NEC REQUIRED CLEARANCES -- mm (in.)
Between Units, Power Entry Side ............. 1066.8 (42.00)
Unit and Ungrounded Surfaces, Power
Entry Side ............................. 914.0 (36.00)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Power Entry Side ......... 1066.8 (42.09)
REQUIRED CLEARANCES FOR SERVICING -- mm (in.)
i
812.5
[31.RN|
Condenser Coil Access Side ................. 762.0 (30.00)
Power Entry Side ......................... 762.0 (30.00)
(Except for NEC Requirements)
Unit Top ................................ 914.0 (36.00)
Side Opposite Ducts ....................... 762.0 (30.00)
LEGEND
NEC -- National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recircuIation of air from
outdoor-fan discharge, with the exception of the condenser coil
(914 mm [36 in.]). A removable fence or barricade requires no
clearance.
2. Dimensions are in millimeters. Dimensions in ( ) are in inches.
BOTTOM
@.
i
LEFT SIDE VIEW
UNIT ELECTRICAL UNIT w'r
PAIZ CHARACTERISTICS Ib kg
024 208/230-1-60 222 10!
030 208/230-1-60 236 107
036 208/230-1-60, 208/230-3-60 250 114
OLOWER, CONTROL DOX AND [VAP COIL
ADDERS _ANRL
i
FRONT VIEW
26 57 I D -/
U.O4N] RIGHT SIDE VIEW
CONDENSATE DRAIN
CENTER OF GRAVITY -- mm (in.)
X Y Z
355.6 (14.00) 508.0 (20.00) 241.3 (9.50)
355.6 (14.00) 508.0 (20.00) 241.3 (9.50)
355.6 (!4.00) 508.0 (20.00) 241.3 (9.50)
Fig. 2 -- Base Unit Dimensions, PAIZ024-036
--2--
COIL
2476
C9,7S]
I
V
L,
_2940 _4080
[II,5?] [15,06]
REAR VIEW [14.ol
£
J295.0
t_O,98J
BOTTONI 0T UNIT
f\ 1
\
\
356.B UIA,
DUCTOPENINGS
t
812.5
131._9]
BOTTON OF UNIT
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L -- mm (in.)
Top of Unit ...................................... O
Duct Side of Unit .................................. O
Side Opposite Ducts ................................ 0
Bottom of Unit .................................... 0
NEC REQUIRED CLEARANCES -- mm (in.)
Between Units, Power Entry Side ............. 1066.8 (42.00)
Unit and Ungrounded Surfaces, Power
Entry Side ............................. 914.0 (36.00)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Power Entry Side ......... 1066.8 (42.09)
REQUIRED CLEARANCES FOR SERVICING -- mm (in.)
Condenser Coil Access Side ................. 762.0 (30.00)
Power Entry Side ......................... 762.0 (30.00)
(Except for NEC Requirements)
Unit Top ................................ 914.0 (36.00)
Side Opposite Ducts ....................... 762.0 (30.00)
LEGEND
NEC -- National Eiectrical Code
NOTES:
1. Clearances must be maintained to prevent recircuIation of air from
outdoor-fan discharge, with the exception of the condenser coil
(914 mm [36 in.]). A removable fence or barricade requires no
clearance.
2. Dimensions are in millimeters. Dimensions in ( ) are in inches.
LEFT SIDE VIEW
UNIT ELECTRICAL UNIT WT
PA1Z CHARACTERISTICS Ib kg
042 208/230-1-60, 208/230-3-60 297 135
048 208/230-1-60, 208/230-3-60 310 141
BLOWER, CONTROL BOX AND
EVAPORATORC01L ACCESS PANEL
COMPRESSOR PAH£
FI[L_ ZNTRY
SERVIC[ PORTS
FRONT VIEW
CENTER OF GRAVITY -- mm (in,)
X Y Z
355.6 (14.00) 508.0 (20.00) 304.8 (12.00)
355.6 (14.00) 508.0 (20.00) 304.8 (12.00)
Fig. 3 -- Base Unit Dimensions, PAIZ042,048
_R3.5
[2 S0}
--3--
117.B
[4.B3]
352.5
;.88)
.44]
1
_35Z8
H3.Sfl
" z
1
0
REARVIEW
O01LFVAPORATOR_ ._
_t
_352,r
_537
[5038!
[BSR]
[Lit3
-I
88,9 ]
(3.501
76G
IZ?
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L -- mm (in.)
Top of Unit ...................................... O
Duct Side of Unit .................................. O
Side Opposite Ducts ................................ 0
Bottom of Unit .................................... 0
NEC REQUIRED CLEARANCES -- mm (in.)
Between Units, Power Entry Side ............. 1066.8 (42.00)
Unit and Ungrounded Surfaces, Power
Entry Side ............................. 914.0 (36.00)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Power Entry Side ......... 1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING -- mm (in.)
Condenser Coil Access Side ................. 762.0 (30.00)
Power Entry Side ......................... 762.0 (30.00)
(Except for NEC Requirements)
Unit Top ................................ 914.0 (36.00)
Side Opposite Ducts ....................... 762.0 (30.00)
LEGEND
NEC -- National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge, with the exception of the condenser coil
(914 mm [36 in.]). A removable fence or barricade requires no
clearance.
2. Dimensions are in millimeters. Dimensions in ( ) are in inches.
il
ii
i _______________________
LEFT SIDEVIEW
COMPRESSOR
FIELD ENTRY
SERVICE PORTS
FRONT VIEW
8_2,5
[31.R9]
BOTTOH
CONTROL BOX AND EVkP. COIL
ACCESS PANEL
POWER ENTRY
(f:)s,°'"X
68.0 _ _549.G
[2.72] [21.GI]
[0 8B]
LOW VOLTAGE ENTRY
• \
22,2 DIA.
)_
_25.4
[I.00]
UNIT ELECTRICAL UNIT vv'r CENTER OF GRAVITY -- mm (in.)
PA1Z CHARACTERISTICS Ib kg X Y Z
060 230-1-60, 208/230-3-60, 460-3-60 350 159 355.6 (!4.00) 508.0 (20.00) 355.6 (14.00)
Fig. 4 -- Base Unit Dimensions, PAIZ060
--4--
RECEIVING AND INSTALLATION
I. STEP I--CHECK EQUIPMENT
A. Identify Unit
The unit model number and serial number are stamped on
the unit identification plate. Check this information against
shipping papers.
B. Inspect Shipment
Inspect fox" shipping damage while unit is still oi1 shipping
pallet. If unit appears to be damaged or is torn loose fi'om its
securing points, have it examined by transportation inspec
tars before removal. Fox,yard claim papers directly to trans
portation company. Manufacturer is not responsible for any
damage incurred in transit.
Check all items against stripping list. hmnediately notify yotxr
local representative if any item is missing.
To prevent loss or dan]age, leave all parts in original pack-
ages until installation.
II. STEP 2 -- PROVIDE UNIT SUPPORT
A. Slab Mount
Place the unit on a rigid, level surface, suitable to support
the unit weight. The flat surface should extend approxi
mately 2 in. beyond tire unit casing on the 2 sides. The duct
connection side and condensate drain connection sides should
be flush with the edge of the flat surface. A concrete pad or a
suitable fiberglass mounting pad is recommended.
A 6 in. wide gravel apron should be used around the flat sur-
face to prevent airflow blockage by grass or shrubs. Do not
secure the unit to the flat surface except where required by
local codes.
The unit should be level to within 1/a inch. This is necessary
for the unit drain to function properly.
III. STEP 3 -- PROVIDE CLEARANCES
The required minimum service clearances and clearances to
combustibles are shown in Fig. 2-4. Adequate ventilation and
condenser air must be provided.
The condenser fan pulls air through the condenser coil and
discharges it through tire fan on the top cover. Be sure that
the fan discharge does not recirculate to the condenser coil.
Do not locate the unit in either a corner or under an over-
head obstruction. The minimmn clearance under a partial over-
hang (such as a normal house overhang) is 48 in. above the
unit top. The maximum horizontal extension of a partial over-
hang must not exceed 48 inches.
Do not place the unit where water, ice, or snow from an
overhang or roof will damage or flood the unit. The unit may
be installed on wood flooring or on Class A, B, or C roof cov
ering materials.
IV. STEP 4 -- PLACE UNIT
Unit can be moved with tire handholds provided in the unit
basepan. Refer to Table 1 for operating weights. U:se extreme
caution m prevent (tamaqe when movJI\_ the unit. Unit mu_st
rolnaJi1 ill all u[)r_q]lt posJHoi1 duriil_ _1]] nlovillg oDer_lHolls.
The unit must be level for proper condensate drainage; the
ground level pad must be level before setting the unit in place.
When a field-fabricated support is used, be sure that the sup-
port is level and that it properly supports the unit.
Table 1 -- Physical Data
UNIT PAIZ 024 030 036 042 048 060
OPERATING WEIGHT (Ibs) 222 236 250 297 310 350
COMPRESSOR TYPE Reciprocating
REFRIGERANT R-22
Charge (Ibs) 2.8 [ 3.9 4.7 [ 4.4 I 6.1 I 7.5
REFRIGERANT METERING DEVICE Acutrol TM System
CONDENSER COIL "opper Tubes, Aluminum Plate Fins
Rows,,.Fins/in. 1...!7 1...!7 2...17 1...17 2...!7 2...17
Total Face Area (sq ft) 6.7 7.9 6.2 11.1 8.6 10.7
CONDENSER-FAN MOTOR Pro )elier
CFM 1600 2000 2000 2600 2600 2800
Nominal Rpm 825 1!00 1100 1100 1!00 1100
Motor Hp 7_ ¼ ¼ _¼ ¼ ¼
Diameter (in.) 20 20 20 20 20 20
EVAPORATOR COIL _opper Tubes, Aluminum Plate Fins
Rows,,.Fins/in. 2...15 3...!5 3...15 3...15 3...!5 4...15
Total Face Area (sq ft) 2.8 2.8 3.1 3.9 4.3 4.9
EVAPORATOR-FAN MOTOR Direct Drive
Blower Motor Size (in.) 10 x 8 10 x 8 10 x 8 10 x 9 10 x 9 10 x 10
Nominal Cfm 800 1000 !200 1400 1600 2000
Rpm Range 550-1000 550-1000 800-1050 800-1050 !000-1100 950-1100
Number of Speeds 3 3 3 3 2 3*
Factory Speed Setting Low Med Low Med Low Low
Motor Hp ¼ ¼ ½ _½ % 1
CONNECTING DUCT SIZES Round Square
Supply Air (in.) 14 !3.9 x !3.9
Return Air (in.) 14 !3.9 x 27.8
FIELD-SUPPLIED RETURN AIR FILTER1"
Throwaway (in.) 24 x 24 24 x 24 24 x 24 24 x 24 24 x 30 24 x 30
"460-v motors are 2-speed only.
1-Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity
of 300 ft!min for throwaway type or 450 ft/min for high capacity type. Recommended filters are 1-in. thick,
--5--
V. STEP 5 -- SELECT AND INSTALL DUCTWORK
The design and installation of the duct system must be in
accordance with:
• the standards of the NFPA (National Fire Protection
Association) for installation of nonresidence type air con
ditioning and ventilating systems;
• NFPA 90A or residence-type, NFPA 90B; and/or local codes
and residence-type, NFPA 90B;
• and/or local codes and ordinances.
Select and size ductwork, supply-air registers and
return air grilles according to ASHRAE (American Society of
Heating, Refrigeration, and Air Conditioning Engineers) rec-
ommendations.
Use the duct flanges provided on the supply and return air
openings on the side of the unit. See Fig. 2 4 for connection
sizes and locations. The 14tin. round duct collars (size 024-
048 units) are shipped inside the unit attached to the indoor
blower. They are field-installed and must be removed fl'om
the indoor cavity prior" to start up, even if they are not used
for"installation.
A. Install Flanges for Ductwork Connections (PAIZ060 Only)
The PA1Z060 units are shipped with flanges which must be
field-installed on the unit.
To install unit flanges:
1. Five pieces of flange are shipped on the return air open
ing of the unit. Remove the flanges from the shipping
position. See Fig. 5. Screws are field-supplied.
2. One piece of flange is used as it is shipped (straight).
Bend the other 4 pieces at right angles.
3. Install the straight flange on the right side of the
return air opening in holes provided. See Fig. 6. Flanges
should stick out from unit to allow for connection of
ductwork.
4. Install 2 hand formed flanges onto return air opening
in holes provided to form a rectangle around the return
air opening.
5. Install remaining 2 hand-formed flanges around dis-
charge air opening in holes provided.
6. Ductwork can now be attached to flanges.
When designing and installing ductwork, consider the
following:
• All units should have field-supplied filters installed in the
return-air side of the unit. Recommended sizes fox"filters
are shown in Table 1.
• Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gas-
kets to ensure weathertight and airtight seal.
• Size ductwork for cooling air quantity (cfln). The mini-
mum air quantity for proper electric heater operation is
listed in Table 2. Heater limit switches may trip at air quan-
tities below those recommended.
HAND FORM
STRAIGHT PIECE
Fig. 6 -- Flanges Installed on PAIZ060 Units
/
FIVE PIECES OF DUCT
FLANGE ATTACHED
HERE FOR SHIPMENT
Fig. 5 -- Shipping Location of Duct Flanges
(Size 060 Only)
/
/
Fig. 7 -- Area Not to be Drilled More than 3/4-in.
--6--