Payne PA13NR06000GAAAA, PA13NR042000AAAA, PA13NR04200GAAAA, PA13NR048000AAAA, PA13NR04800GAAAA Installation Guide

...
Installation Instructions
SAFETY CONSIDERATIONS
Improper installation, acljustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal iniury, or property damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety-alert symbol _X When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could
result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICALSHOCK HAZARD Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
INSPECT NEW UNIT
After un-crating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately
and file a concealed damage claim.
LOCATION
Check local codes for regulations concerning zoning, noise,
platforms, and other issues. Locate unit away from fresh air intakes, vents, or bedroom
windows. Noise may carry into the openings and disturb people inside.
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEARANCE
REQUIREMENT section of this document). Roof-top installation is acceptable providing the roof will support
the unit and provisions are made for water drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional information.
CLEARANCE REQUIREMENTS
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service.
Allow 24 in. (609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (45%2 mm) if no overhang within 12 ft. (3.66 m).
Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
NOTE: 18" (457.2 mm) clearance option described above is
approved for outdoor units with wire grille coil guard only. Units
with louver panels require 24" (609.6 mm) between units. On rooftop applications, locate unit at least 6 in. (152.4 mm) above
roof surface.
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal iniury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
UNIT SUPPORT
NOTE: Unit nmst be level _+ 2 degrees {3/8 inch rise or fall per foot of run (10 mm rise or fall per 305 mm of run) } or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid
construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure-treated timbers approved for ground contact. Soil conditions must be considered so that the
platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Fig. 1.
If beams or an open platform are used for support, it is recommended that the soil be treated or area be graveled to reduce
the growth of grasses and weeds. To minimize vibration or noise transmission, it is recommended
that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are
normally acceptable.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a fiat roof, locate unit minimum 6 inches (152 ram) above roof level.
Place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are self-supporting and span several load bearing walls. These suggestions are to
minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid locating the unit over
bedrooms or study. NOTE: When unit is to be installed on a bonded guaranteed roof,
a release must be obtained from the building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install tie down bolts
through the holes (see Fig. 1). Contact local distributor for hurricane hold-down details and the
P.E. (Professional Engineer) certification, when required.
3/8" (10mm) dia. Tie Down Knockouts
In Basepan (2 places)
I View From Top I
Base
Pan
Depth
oO
A
Base Pan Width
Inches (mm)
Base Pan
W x D
23 x 23
(584 x 584)
25-11/16 x
25-11/16
(652 x 652)
31-1/8 x
31-1/8
(791 x 791)
Tie Down
Knockouts
A
7- 6/4
(197)
9-1/16
(230)
B C
4-7/16 18
(113) (457)
4-7/16 21-1/4
(113) (540)
9-1/16 6-1/2 24-5/8
(230) (165) (625)
Minimum
Mounting Pad
Dimensions
23 x 23
(584 x 584)
26 x 26
(660 x 660)
31-1/2 x 61-1/2
(800x800)
Fig. 1 - Tie Down Knockouts
REFRIGERATION SYSTEM
EXPLOSION AND FIRE HAZARD
Failure to follow this caution could result in property damage, personal iniury and/or death.
This unit utilizes R-22 refrigerant. Use only R-22 refrigerant when servicing this unit.
DO NOT, under any circumstances, use R-410A refrigerant in this system.
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property
damage. Inadequate unit support may cause excessive vibration,
noise, and/or stress on the refrigerant lines, leading to refrigerant line failure.
A. COMPONENT MATCHES
Check to see that the proper system components are in place,
especially the indoor coil. R-22 outdoor units can only be used with R-22 specific indoor
coils. If there is a refrigerant ntis-match, consult the indoor coil manufacturer to deternfine if a refrigerant conversion kit is
available for the indoor coil.
This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device. If any other type of
metering device is installed on the indoor coil, consult the indoor coil manufacturer to deternfine if a TXV conversion kit is available
The compressors for these units are supplied with Polyol Ester (POE) Oil. If the existing line set and indoor coil has residual
nfineral oil (MO) there is no concern with percentage of oil nfixtures as both are nfiscible with the R-22. Mixtures of both oils
at any percentage will lubricate and return with the R-22.
WheninstallingaTXVonanindoorcoil,followtheinstructions providedwiththenewTXV.
AtypicalTXVinstallationisshowninFig.2.
EQUALIZER
TUBE
SENSING SUCTION BULB TUBE
LIQUID
TUBE
TXV
SENSING BULB
(EITHER SIDE)
STRAP
\
8 O'CLOCK 4 O'CLOCK
Fig. 2 - Typical TXV Installation
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation.
Refer to Long Line Guideline for line set sizing. NOTE: Total line set length must not exceed 200 feet (61 m). A crankcase heater must be used when the refrigerant line length
exceeds 80 feet (24.4 m). If vertical separation between indoor and outdoor units is greater
than 30 ft (9.14 m), refer to the Long Line Guideline. If it is necessary to add refrigerant line in the field, use dehydrated
or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can "kink" easily, and if this occurs, the entire length of tubing must be
replaced.
UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit
operation. Do not leave system open to atmosphere any longer than
absolutely required for installation. Internal system components - especially refrigerant oils - are extremely susceptible to moisture contamination. Keep ends of tubing sealed during installation until the last possible moment.
C. ROUTING AND SUSPENDING REFRIGERANT LINES
Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when routed through an attic or
when routed through an underground raceway. When routing refrigerant lines through a foundation or wall, do not
allow refrigerant lines to come in direct contact with the building
structure. Make openings large enough so that lines can be wrapped with
extra insulation. Fill all gaps with RTV caulk. This will prevent noise transmission between the tubing and the foundation or wall.
Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water pipes, or ductwork. Use
insulated or suspension type hangers. Metal straps must be at least
1" (25 mm) wide to avoid cutting into the tube insulation. Keep the
liquid and suction lines separate. Refer to Fig. 3.
OUTDOORWALL--X '"DOORWALy
CAU LK_ _J
_/_'_ ' _[ r LLIQUIDTUBE
---el ---4 m/_[ _---SUCTIONTUBE
_-'-INSU LATION
THROUGH THE WALL
HANGER STRAP
(AROUND SUCTION _ --
TUBE_N
1" (25.4 mm_ _
MIN _-- LIQUID TUBE
SUSPENSION
Fig. 3 - Routing and Suspending Refrigerant Lines
_/---JOIST
/ _ INSULATION
/SUCTION TUBE
A07588
PERSONAL INJURY HAZARD Failure to follow this warning could result in personal iniury
and/or death.
Relieve pressure and recover all refrigerant before servicing existing equipment, and before final unit disposal. Use all service ports and open all flow-control devices, including
solenoid valves.
UNIT OPERATION HAZARD Failure to follow this caution may result in improper
product operation. Do not bury more than 36" (1 m) of line set underground.
Refrigerant may migrate to cooler buried section during extended periods of unit shut-down, causing refrigerant slugging and possible compressor damage at start-up.
If ANY section of the line set is buried underground, provide a minimum 6" (152 mm) vertical rise at the service
valve.
D.OUTDOORUNITHIGHERTHANINDOORUNIT
Properoilreturntothecompressorshouldbemaintainedwith suctiongasvelocity.Ifvelocitiesdropbelow1500fpm(feetper
minute),oilreturnwillbedecreased.Tomaintainsuctiongas
velocity, do not upsize vertical suction risers.
E. LIQUID LINE FILTER-DRIER
NOTE: It is required that an approved filter drier (XH-6 with 25% activated alumina / 75% molecular sieve desiccants) be
installed in the liquid line due to the POE oil. Leave the plugs in the tube ends until the filter-drier is installed.
The optimal location for the filter-drier is close to the indoor coil. Install the filter-drier with the arrow pointing towards the indoor coil. Refer to Fig. 4.
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and contacts brazing torch. Make sure the refrigerant charge is properly removed from both the high and low sides of the system before brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush. Remove any grit or debris.
Insert line set tube ends into service valve tube stubs. Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material such as a wet cloth.
Braze joints using a Sil-Fos or Phos-copper alloy.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component damage. Service valves must be wrapped while brazing in a heat
sink material, such as a wet cloth.
A05178
Fig. 4 - Liquid Line Filter Drier Installed at Indoor Unit
F. SERVICE VALVES
Service valves are closed and tube stubs are plugged from the factory. Outdoor units are shipped with a dry nitrogen holding
charge sealed in the unit. Leave the service valves closed until all other refrigerant system work is complete or the charge will be
lost. Leave the plugs in place until line set tubing is ready to be inserted.
Service valve bodies are brass and tube stubs are copper.
G. BRAZING CONNECTIONS
NOTE: Remove valve core from schrader port on both Service Valves BEFORE brazing. This helps prevent overheating and
damage to valve seals (refer to Fig. 5). Replace valve core when brazing is completed.
VALVE SERVICE
CORE
Fig. 5 - Service Valve
H. OPENING SERVICE VALVES
Outdoor units are shipped with a dry nitrogen holding charge
sealed in the unit. Opening the service valves releases this charge into the system.
NOTE: Open the Suction service valve first. If the Liquid service valve is opened first, oil from the compressor may be drawn into the indoor coil TXV, restricting refrigerant flow and affecting operation of the system.
Remove Suction service valve cap and insert a hex wrench into the valve stem. Hold the valve body steady with an end-wrench and
back out the stem by turning the hex wrench counterclockwise. Turn the stem until it just contacts the rolled lip of the valve body.
After the nitrogen charge has bled into the system, open the Liquid service valve.
NOTE: These are not back-seating valves. It is not necessary to force the stem tightly against the rolled lip.
The service valve cap is a primary seal for the valve and must be properly tightened to prevent leaks. Make sure cap is clean and
apply refrigerant oil to threads and sealing surface on inside of cap.
Tighten cap finger tight and then tighten additional 1/6 of a turn (1 wrench flat) to properly seat the sealing surfaces.
nitrogen pressure from the system before attaching vacuum
I NOTE: Using the service ports (or gauge set), release the I
pump.
I. EVACUATINGCONDENSER,LINE SET, AND
INDOORCOIL
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage.
Never use the outdoor unit compressor as a vacuum pump. Doing so may damage the compressor.
Condenser, line set, and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. If deep
vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure.
If vacuum must be interrupted during the evacuation procedure, always break vacuum with dry nitrogen.
UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit
operation.. This unit is filled with a Nitrogen charge. Prior to starting
this unit, evacuate to 500 microns and charge with refrigerant listed on rating label. Purge nitrogen before connection to vacuum pump.
Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of
pulling a vacuum to 500 microns and a vacuum gauge capable of accurately measuring this vacuum level. The deep vacuum method
is the most positive way of assuring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down. The response of the gauge is an indicator of the condition of the system
(refer to Fig. 6). With no leaks in the system, allow the vacuum pump to run for 30
minutes minimum at the deep vacuum level.
5000 4500 4000
ff18500 g aooo
_2500
m
2000
1500- VACUUM TIGHT 1000
500 TIGHT
0 1 2 3 4 5 6 7
MINUTES
Fig. 6 - Deep Vacuum Gauge Response
and System Conditions
TOO WET
DRY SYSTEM
A95424
Triple Evacuation Method The triple evacuation method should only be used when system
does not contain any water in liquid form and vacuum pump is only capable of pulling down to 28 inches of mercury (711 mm Hg). Refer to Fig. 8 and proceed is as follows:
1. Pull system down to 28 inches of mercury (711 mm Hg) and allow pump to continue operating for an additional 15
minutes.
2. Close manifold valves or valve at vacuum pump and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and fill
with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 7.
6. After the final evacuate sequence, confirm there are no leaks in the system. If a leak is found, repeat the entire process
after repair is made.
IEVAOUATE I
IBREAKVACUUMWITH DRY NITROGEN I
r- Tq
IEVACUATEI
IBREAKVACUUMWITHDRYNITROGEN I
IEVACUATEI
ICHECKFORTIGHT'DRYSYSTEMI(IF IT HOLDS DEEP VACUUM)
I CHARGESYSTEMI
A95425
Fig. 7 - Triple Evacuation Sequence
J. GAUGE PORTS
Check for leaks at the schrader ports and tighten valve cores if
necessary. Install plastic caps finger tight.
ELECTRICAL WIRING
ELECTRICALSHOCK HAZARD Failure to follow this warning could result in personal iniury
or death. Before installing, modifying, or servicing system, main
electrical disconnect switch nmst be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
The supply voltage must be 208/230 volts (197 volt minimum to 253 volts naaxinmm) 60 Hz single phase.
Outdoor units are approved for use with copper conductors only. Do not use alunfinum wire.
Refer to unit rating plate for minimum circuit ampacity and circuit protection requirements.
Grounding Permanently ground unit in accordance with the National Electrical
Code and local codes or ordinances. Use a copper conductor of the correct size from the grounding lug in control box to a grounded
connection in the service panel or a properly driven and electrically grounded ground rod.
ELECTRICALSHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupted or unbroken ground to nfininfize personal iniury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes.
Wiring Connections Make all outdoor electrical supply (Line Voltage) connections with
rain-tight conduit and fittings. Most codes require a disconnect switch outdoors within sight of the unit. Consult local codes for
special requirements. Route electrical supply (Line Voltage) wiring through knockout
hole in bottom of Control Box. Connect wires to Contactor and
Ground Lug according to Wiring Diagram on unit. Also refer to
Fig. 8. Route thermostat wiring through rubber grommet in bottom of
Control Box. Low voltage lead wires are provided in the control
box for connection to thermostat wires (use wire nuts). Refer to Wiring Diagram on unit and Fig. 9 for low voltage wiring examples.
All wiring must be NEC Class 2 and must be separated from inconfing power leads.
NOTE: Use No. 18 AWG (American Wire Gage) color-coded, insulated (35 °C nfininmm) wire. If thermostat is located more than
100 feet (31 m) from unit as measured along the control voltage wires, use No. 16 AWG color-coded wires to avoid excessive voltage drop.
DISCONNECT
PER NEC AND/OR
LOCAL CODES
1
FIELD POWER
WIRING
FIELD GROUND
WIRING ] GROUND
Fig. 8 - Electrical Supply (Line Voltage) Connections
L.1 @ _- ®
CONTACTOR
[ 23 or 13
-g)
LUG
A10476
A/C Typical
THERMOSTAT FURNACE
24VACHOTE}"------Q 24VACCOM[D'------E]--
HEATSTAGE1....-El
COOLSTAGE1...."42]"'
,NDOORFANEl--------El
AIR
CONDITIONER
LEGEND
24-V FACTORY WIRING
24-V FIELD WIRING
C_ FIELD SPLICE CONNECTION
CONTACTOR
Fig. 9 - Typical Thermostat Connections
(See Thermostat Installation Instruction
for specific unit combinations)
A/C Typical AIR
THERMOSTAT FAN COIL CONDITIONER
24 MAC HOT [_,
24 MAC COM D"
HEAT STAGE 1 [_
COOL STAGE 1 [_
INDOOR FAN [_'
A97368
_,a4B
A02326
START-UP PROCEDURE
1. Set indoor thermostat selector switch to OFF.
2. Turn ON all electrical disconnect devices.
3. If unit has a crankcase heater, energize the heater and wait
24 hours before proceeding.
4. Set indoor thermostat at desired temperature. Be sure set-
point is below indoor ambient temperature or thermostat will not call for cooling.
5. Set indoor thermostat selector switch to COOL. Operate
unit for minimum 15 nfinutes, then check system refrigerant charge.
REFRIGERANT CHARGE
Table 1 shows the suggested refrigerant charge quantities for a 15 foot (4.6 m) lineset. If shorter or longer refrigerant lines or a
different indoor coil are used, the charge will have to be adjusted. For different line lengths, add or remove charge based on 0.6
ounces (17 g) charge per foot (305 ram) of difference. For example, a 25 foot (7.6 m) line set is 10 feet (3 m) longer than the
specified 15 feet (4.6 m). Add 0.6 ounces (17 g) charge for each of the extra 10 feet (3 m):
10 x 0.6 = 6.0 ounces additional charge (3 m x 17 g = 51 g additional charge)
The initial charge should be weighed into the system per Table 1 and the additional amount for the length of line set. Then check
subcooling. This outdoor unit is designed for use only with indoor coils that
utilize a TXV refrigerant metering device. With an indoor TXV, use the subcooling method to make final charge adjustments:
NOTE: Only use subcooling charging method when the following is true:
outdoor ambient temperature is between 70°F and 100°F
(21°C and 38°C)
indoor temperature is between 70 ° and 80°F (21 °C and 27°C)
line set is less than 80 feet (24.4 m).
1. Operate unit a minimum of 15 nfinutes before checking charge.
NOTE: If outdoor unit has a 2-speed fan motor, motor will operate in low speed when outdoor ambient temperature is
below 82°F (28°C). Pull one of the yellow low voltage wires off the fan control and the unit will default to high
speed fan for servicing. Reconnect wire after servicing.
2. Measure liquid service valve pressure by attaching an accurate gauge to service port.
3. Measure liquid line temperature by attaching an accurate thernfistor type sensor or electronic thermometer to liquid
line near outdoor coil.
4. Refer to unit rating plate for required subcooling temperat- ure.
5. Refer to Table 2. Find the required liquid line temperature
where the rating plate subcooling temperature intersects
measured liquid service valve pressure.
6. If the measured liquid line temperature is higher than the chart number, add refrigerant to lower the measured temper-
ature. NOTE: When adding refrigerant, charge in liquid form, using a flow restricting device, into the suction port.
If the measured liquid line temperature is lower than the chart number, reclaim refrigerant to raise the measured
temperature. Tolerance is _+3 °F (_+ 1.7 °C).
Table 1--Suggested Refrigerant Charge Quantity
for 15 foot (4.6 m) Lineset
Model Number Ibs. (kg)
PA13NR018 3.56 (1.62) PA13NR024 4.08 (1.85)
PA13NR030 4.11 (1.87) PA13NR036 5.35 (2.43) PA13NR042 7.01 (3.19) PA13NR048 8.88 (4.04)
PA13NR080 10.52 (4.79)
Measured Liquid
Pressure (psig)
183 171 179 187
198
205 214 223
233 243 253 284 274
285 297 309
oF
83 86 89 92
95
98 101 104
107 110 113 116 119
122 125 128
Table 2--Required Liquid Line Temperature
Rating Plate (required) Subcooling Temperature ° F C)
oF oF
5
10 15
oF 20
R-22 Required Liquid Line Temperature ° F C)
78 81 84 87
90 93 96 99
102 105 108 111 114
117 120 123
73 76 79 82
85 88 91 94
97 1O0 103 106 109
112 115 118
68 71 74 77
80 83 86 89
92 95
98 101 104
107 110
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_i_!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_i!_!_i_i_
113
SEQUENCE OF OPERATION
With power supplied to indoor and outdoor units, transformer is energized.
On a call for cooling, the thermostat makes circuits R-Y and R-G. Circuit R-Y energizes contactor, starting outdoor fan motor and compressor. Circuit R-G energizes indoor unit blower relay,
starting indoor blower motor. When thermostat is satisfied, its contacts open, de-energizing
contactor and blower relay. Compressor and motors stop. NOTE: If indoor unit is equipped with a time-delay relay circuit,
the blower runs an additional length of time to increase system efficiency.
MAINTENANCE
Condensate Drain
During the cooling season, check monthly for free flow of drainage
and clean if necessary. Cleanliness
These tips will help keep the air conditioner looking better and working more efficiently:
1. Free flow of air is essential. Keep fences, shrubs, trash cans, and other obstructions at least 18 inches (0.5 m) from all
coil inlets.
2. Keep the coil free of grass clippings, leaves, weeds, and other debris.
NOTE: Coil may occasionally require cleaning with a liquid solution. The coil nmst be cold when cleaning. Use
an alkaline based cleaner only. Cleaning a hot coil or using an acid based cleaner will remove the paint from the fins
and may clog the coil.
3. Never use a weather cover over the outdoor unit unless it is a ventilated type or made of breathable fabric that will allow
moisture to evaporate rapidly. A cover that holds moisture in the unit will cause more rust build-up and damage than normal exposure to weather.
Copyright 2014 CAC/BDR 7310 W. Morris St. Indianapolis, IN 46231 edition date: 07/14
Manufacturer reserves the right to change, at any time, specification8 and design8 without notice and without obligations,
Catalog No: IM-PA13NR-06
Replaces: IM- PAl 3NR- 05
Loading...