Payne PA10 Series Product Data

MODEL PA10 10 SEER 3-PHASE AIR CONDITIONER
Product Data
FEATURES
AVAILABLE SIZES: Nominal sizes available (036, 048 and 060) to
ELECTRICAL RANGE: 208/230v, three phase in 036, 048 and 060
FAN MOTOR:
CABINET:
UNIT DESIGN:
meet the needs of light commercial applications.
All models are listed with UL, (U.S. and Can­ada), ARI, and CEC.
sizes; and 460v, three phase in 060 size.
The totally enclosed fan motor provides greater reliability under adverse conditions and depend­able performance for many years. The permanent split capacitor type motor was designed for opti­mum efficiency. The motor was then qualified under extreme conditions to help ensure a long, reliable life.
A weather protective cabinet of prepainted steel is protected underneath by a galvanized coating and treated with a layer of zinc phosphate for a finish that will last for many years. All screws on cabinet exterior are coated for a long-lasting, rust­resistant, quality appearance.
The copper tube, enhanced sine wave, aluminum fin coil is designed for optimum heat transfer. Ver­tical air discharge carries sound and hot con­denser air up and away from adjacent patio areas and foliage. The base pan is designed for easy removal of water, dirt, and leaves.
COMPRESSOR:
3-PHASE (SCROLL COMPRESSOR UNITS) MONITOR BOARD:
SERVICE VALVES: Control board that monitors the electrical phase
SERVICEABILITY: One panel provides access to electrical controls.
LIMITED WARRANTY:
Each compressor is protected with internal tem­perature- and current-sensitive overloads. An internal pressure relief valve provides high­pressure protection to the refrigerant system. For improved serviceability, all models are equipped with a compressor terminal plug.
Both service valves are brass, front seating type with sweat connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures.
and prevents compressor operation if wired incorrectly.
Removal of top gives access to fan motor, com­pressor, and condenser coil.
Standard 1-year limited warranty on parts and 5­year limited warranty on compressor.
E
SOUND POWER (dBA) (A-wtd., non-pure tone corrected.)
UNIT
SIZE
036-A 82 55.0 64.0 73.0 74.5 72.0 60.5 64.0
048-A 82 61.9 67.5 71.8 77.1 76.5 72.9 66.9
060-A 82 58.0 67.5 78.0 76.0 76.0 73.0 67.0
NOTE: Tested in accordance with ARI standard 270.95. (Not listed with ARI.)
SOUND
LEVEL
125 250 500 1000 2000 4000 8000
PA10
OCTAVE BAND CENTER FREQUENCY (Hz)
ISO 9001:2000
REGISTERED
Type of Unit
PA10 – Electric Air Conditioner
Electrical Supply P — 208/230-3-60
— 460-3
Refrigerant–R22
MODEL NUMBER NOMENCLATURE
PA10 P R
036 000 A A AA
Variations
Series
Variation
A — Standard Unit
Heating Capacity
Nominal Cooling Capacity 036 – 3.0 Tons 048 – 4.0 Tons 060 – 5.0 Tons
—2—
SQ
A
AIR DISCHARGE
-IN. DIA HOLE
8
/
-IN. DIA KNOCKOUT
8
/
3
-IN. DIA KNOCKOUT
8
/
-IN. DIA HOLE WITH
1
8
/
FIELD POWER SUPPLY CONN
7
AND 1
1
7
FIELD CONTROL SUPPLY
CONN
-IN. DIA LIQUID
8
/
LINE CONN
3
Pad Dim
Min Mounting
C
/8
7
2
/4
1
1
PA10
AIR DISCHARGE
AIR IN
M
DIA VAPOR LINE CONN
D
P
B
AIR IN
L
NOTES:
1. Allow 30 in. clearance to service side of
unit, 48 in. above unit, 6 in. on one side, 12 in.
on remaining side, and 24 in. between units for proper airflow.
2. Minimum outdoor operating ambient in cooling mode is
55°F, max. 125°F.
3. Series designation is the 14th position of the unit
model number.
4. Center of gravity .
DIMENSIONS (IN.)
K
J
AIR IN
H
G
F
E
N
/8-IN. DIA
AIR IN
TIEDOWN
3
(2) PLACES
KNOCKOUTS
AIR DISCHARGE
—3—
036 A 22-1/2 25-15/16 3-3/16 3/4 3-11/16 18-1/8 19-3/4 22-1/4 14-3/8 19-9/16 22-1/16 10-3/8 10-3/4 11 22-1/2 x 22-1/2
SIZE SERIES A B C D E F G H J K L M N P
UNIT
The data in this publication is displayed for all series, however, every series may not be available from manufacturer.
048 A 22-1/2 33-15/16 3-1/4 7/8 3-11/16 18-1/8 19-13/16 22-1/4 14-3/8 19-9/16 22-1/16 10-3/8 10-3/4 15-1/2 22-1/2 x 22-1/2
060 A 30 29-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-3/4 20 27-1/16 29-9/16 15-1/2 14 15 30 x 30
NOTE:
METERING DEVICE
UNIT SIZE-SERIES
036-A 70
048-A 82
060-A 93
* Piston listed is for any approved coil non-capillary tube combination. Piston is shipped with outdoor unit and must be installed in an approved indoor coil.
UNIT SIZE 036
SERIES A A A A
PA10
Operating Weight (Lb) 122 154 214 Shipping Weight (Lb) 141 175 236
ELECTRICAL
Unit Volts—Hertz—Phase 208/230-60-3 208/230-60-3 208/230-60-3 460-60-3 Operating Voltage Range* 187-253 187-253 187-253 414-506 Compressor—Rated Load Amps 10.0 12.8 16.0 8.0
Locked Rotor Amps 70.0 91.0 125.0 66.5 Condenser Fan Motor—Full Load Amps 1.4 1.4 1.4 0.8 Min Unit Ampacity for Wire Sizing 13.9 17.4 21.4 10.8 Min Wire Size (60°C/75°F Copper) AWG† 14/14 14/14 12/12 14/14 Max Wire Length (60°C/75°F) (Ft)‡ 65/62 52/49 66/63 165/157 Max Branch Circuit Fuse Size** 20 30 30 15
COMPRESSOR & REFRIGERANT
Compressor—Type Reciprocating Scroll Temperature and Current Protection Internal Line Break Refrigerant—Type and Amount (Lbs) R-22 5.00 R-22 6.25 R-22 8.31 Refrigerant Tubes (In. OD)
Vapor and Liquid (Up to 50 Ft) 3/4 and 3/8 7/8 and 3/8 1-1/8 and 3/8
CONDENSER COIL & FAN
Coil Face Area (Sq Ft) 9.1 12.4 18.5 Fan Motor—HP, Type, and RPM 1/4 PSC and 1100 1/4 PSC and 1100 Volts—Hertz—Phase 208/230—60—1 208-230—60—1 460—60—1 Condenser Airflow (CFM) 2500 2500 3400
OPTIONAL EQUIPMENT
Cycle Protector KSACY0101AAA Low-Pressure Switch KAALP0101LPS High-Pressure Switch KSAHI0101HPS Time-Delay Relay KAATD0101TDR Winter Start Control KAAWS0101AAA Evaporator Freeze Thermostat KAAFT0101AAA Compressor Crankcase Heater KAACH1001AAA KAACH1201AAA KAACH1301AAA Liquid Line Solenoid Valve KAALS0101LLS KAALS0101LLS Filter Drier P502-8083S P502-8163S MotorMaster® Control 32LT660004 32LT660005 Ball Bearing Fan Motor HC40GE232 HC40GE462 Low-Ambient Pressure Switch Kit KSALA0201R22 Compressor Sound Hood KSASH1201COP KSASH2001CYL TXV (Hard Shutoff) KSATX0601HSO KSATX0701HSO KSATX1001HSO Thermostat, Manual Changeover,
Non-Programmable, °F/°C, 1-Stage Heat, 1-Stage Cool‡‡ TSTATPPBAC01-B
Thermostat, Manual Changeover,
5-2-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool TSTATPPSAC01-B Backplate for Standard Thermostat TSTATXXBBP01 Backplate for Programmable Thermostat TSTATXXPBP01 Outdoor Air Temperature Sensor TSTATXXSEN01-B
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.
‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time-delay fuse or circuit breaker.
‡‡ Furnace model numbers P08UA, P08LA, and PG8HA are not compatible with this thermostat.
N/A—Not applicable in this application.
NOTES: 1. Control circuit is 24v on all units and requires external power source.
2. All motors/compressors contain internal overload protection.
3. Copper wire must be used from service disconnect to unit.
IDENTIFICATION NO.
PISTON*
SPECIFICATIONS
—4—
CHARGING SUBCOOLING
(TXV-TYPE EXPANSION DEVICE*)
UNIT SIZE
036 15
048 15
060 15
048 060
REQUIRED SUBCOOLING
(°F)