Recognize safety information. This is the safety--alert symbol.
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION
HAZARD
Failure to follow this warning could result in possible
damage to this equipment, personal injury, or death.
The ability to properly perform maintenance on this
equipment requires certain expertise, mechanical skills,
tools, and equipment. If you do not possess these, do not
attempt to perform any maintenance on this equipment
other than those procedures recommended in the User’s
Manual.
!
WARNING
!
WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, personal injury, death, or property
damage.
-- Before servicing, disconnect all electrical power to furnace.
--When servicing controls, label all wires prior to
disconnecting. Reconnect wires correctly.
-- Verify proper operation after servicing.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could property damage,
personal injury, or death.
Never store anything on, near, or in contact with the furnace,
such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum
cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning
compounds, plastic or plastic containers, gasoline, kerosene,
cigarette lighter fluid, dry cleaning fluids, or other volatile
fluids.
3. Paint thinners and other painting compounds, paper bags,
or other paper products.
1
Page 2
PG9MAB
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
furnace.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation.
GENERAL
This furnace can be installed as a direct vent (2--pipe) or non--direct
vent (1--pipe) condensing gas furnace. These instructions are
written as if the furnace is installed in an upflow application. An
upflow furnace application is where the blower is located below
the combustion and controls section of the furnace, and
conditioned air is discharged upward. Since this furnace can be
installed in any of the 4 positions shown in Fig. 2, you may need to
revise your orientation to component location accordingly.
AIRFLOW
UPFLOW
A05086
Fig. 1 -- Furnace in Upflow Orientation
ama
ISO 9001:2000
CERTIFIED
REGISTERED
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
service agency personnel should install, repair, or service
heating equipment. Untrained personnel can perform basic
maintenance functions described in User’s Information
Manual such as cleaning and replacing air filters. All other
operations must be performed by trained service personnel. When
working on heating equipment, observe precautions in the
literature, on tags, and on labels attached to or shipped with the
unit and other safety precautions that may apply.
Follow all safety codes including the National Fuel Gas Code
(NFGC) NFPA 54 -- 2006/ANSI Z223.1--2006 in the USA, CSA
B149.1--05 National Standard of Canada, Natural Gas and Propane
Installation Codes (NSCNGPIC) in Canada, and the Installation
Standards, Warm Air Heating and Air Conditioning Systems
(NFPA 90B) ANSI/NFPA 90B. Wear safety glasses and work
gloves. Have a fire extinguisher available during start--up and
adjustment procedures and service calls.
AIRFLOW
HORIZONTAL
LEFT
Fig. 2 -- Multipoise Orientation
DOWNFLOW
AIRFLOW
HORIZONTAL
RIGHT
AIRFLOW
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may damage furnace
components.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing
to protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These
precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control,
and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. DO NOT TOUCH
THE CONTROL OR ANY WIRE CONNECTED TO THE
CONTROL P RIOR TO DISCHARGING YOUR BODY’S
ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a
A93041
2
Page 3
person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used
AND new controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible furnace
failure, it is essential that maintenance be performed annually.
Consult your local dealer for maintenance and maintenance
contract availability.
!
WARNING
FILTER
SUPPORT
Fig. 3 -- Bottom Filter Arrangement
FILTER
FILTER
RETAINER
FILTER
FILTER
RETAINER
A08586
PG9MAB
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Turn off the gas and electrical supplies to the unit before
performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace.
The minimum maintenance that should be performed on this
equipment is as follows:
1. Check and clean or replace air filter each month as needed.
2. Check blower motor and wheel for cleanliness annually.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
4. Check for proper condensate drainage. Clean as necessary.
5. Check for blockages in combustion--air and vent pipes annually.
6. Check burners for cleanliness annually.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Be careful of sharp metal edges, etc. Use care and wear
protective clothing, gloves, and safety glasses when
removing parts.
Step 1 — Cleaning and/or Replacing Air Filter
The air filter arrangement may vary depending on the application
or orientation. See Table 1 for filter size and type.
A08587
Fig. 4 -- Filter Installed for Side Inlet
!
WARNING
FIRE, CARBON MONOXIDE POISONING
HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Never operate unit without a filter or with the blower access
panel removed. Operating a unit without a filter or with the
blower access door removed could cause damage to the
furnace blower motor. Dust and lint on internal parts of
furnace can cause a loss of efficiency.
NOTE: If the filter has an airflow direction arrow, the arrow must
point toward the blower.
To clean or replace filters, proceed as follows:
If filter is installed in filter cabinet adjacent to furnace:
4. If equipped with permanent, washable filter, clean filter by
spraying cold tap water through filter in opposite direction
of airflow. Rinse filter and let dry. Oiling or coating of the
filter is not recommended.
5. If equipped with factory specified disposable media filter,
replace only with a factory specified media filter of the same
size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
If filter is installed in furnace blower compartment:
Table 1 – Furnace Air Filter Table
FILTER QUANTITY AND SIZE *
BOTTOM RETURN*
IN (MM)
(1) 16 x 25 x 3/4
(406 x 635 x 19)
(1) 20 x 25 x 3/4
(508 x 635 x 19)
(1) 24 x 25 x 3/4
(610 x 635 x 19)
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Release filter retainer wire. (See Fig. 3 or 4.)
NOTE: Filters shown in Fig. 3 and 4 can be in furnace blower
compartment or in filter cabinet, but not in both.
4. Slide filter out of furnace.
5. If equipped with permanent, washable filter(s), clean filter
by spraying cold tap water through filter in opposite direction of airflow.
6. Rinse filter and let dry. Oiling or coating filter is not recommended.
7. Slide filter into furnace.
8. Recapture filter retaining wire.
9. Replace blower access panel and main furnace door.
10. Turn on electrical supply to furnace.
Step 2 — Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean
accumulated dirt and grease from blower wheel and motor
annually.
The inducer and blower motors are pre--lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
The following items should be performed by a qualified service
technician.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
3. Disconnect wires
All factory wires can be left connected, but field thermostat
connections may need to be disconnected depending on
their length and routing.
4. Remove control box mounting screws, and position control
box, transformer, and door switch assembly to right side of
furnace casing.
A05110
5. If condensate trap is located in left-- or right--hand side of
furnace casing, proceed to item 6. Otherwise remove trap
and tubing as described below (See Fig. 5.):
a. Disconnect field drain connection from condensate trap.
b. Disconnect drain and relief port tubes from condensate
trap.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf
and slide blower assembly out of furnace. Detach ground
wire and disconnect blower motor harness plugs from
blower motor.
NOTE: Blower wheel is fragile. Use care.
7. Clean blower wheel and motor by using a vacuum with soft
brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades
as balance will be affected.
8. If greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
FILTER TYPE*SIDE RETURN*
3/4” (19 mm) thick washable
3/4” (19 mm) thick washable
3/4” (19 mm) thick washable
4
Page 5
a. Mark blower wheel location on shaft before disassembly
to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
c. Mark blower wheel orientation and cutoff plate location
to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing
and slide motor and mounts out of housing. Disconnect
capacitor and ground wire attached to blower housing
before removing motor. Motor mounts need not be
removed from motor.
f. Remove blower wheel from housing.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in noise or furnace
component failure.
The blower wheel should not be dropped or bent as balance
will be affected.
g. Clean wheel per instructions on degreaser cleaner. Do
not get degreaser in motor.
9. Reassemble motor and blower wheel by reversing items 8b
through 8f. Ensure wheel is positioned for proper rotation.
Be sure to reattach ground wire. Tighten setscrew to 140 to
160 in--lb torque.
NOTE: Be sure to attach ground wire and reconnect blower
harness plugs to blower motor.
10. Reinstall blower assembly in furnace.
11. Reinstall control box, transformer, and door switch assembly on blower shelf.
12. Reinstall condensate trap and tubing if previously removed.
a. Reinstall condensate trap in hole in blower shelf.
b. Connect condensate trap drain tubes. See Fig. 5 or
tubing diagram on main furnace door for proper tube
location.
NOTE: Ensure tubes are not kinked or pinched, as this will affect
operation.
(1.) Connect one tube (blue or blue and white striped)
from collector box.
(2.) Connect one tube (violet or unmarked) from in-
ducer housing.
(3.) Connect one tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
NOTE: Ensure tubes are not kinked or pinched, as this will affect
operation.
13. Reinstall control box, transformer, and door switch assembly on blower shelf.
14. Reconnect wires.
Refer to furnace wiring diagram and connect thermostat
leads if previously disconnected. (See Fig. 21.)
NOTE: Refer to Table one for motor speed lead reconnection if
leads were not identified before disconnection.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to adjust the heating speed may shorten heat
exchanger life.
Heating speed selection MUST be adjusted to provide
proper temperature rise as specified on the rating plate.
Table 2 – Speed Selection
COLORSPEED
BlackHighCool
Yellow (When Present)Medium HighSpare
BlueMedium LowHeat
RedLowFan
WhiteCommonCom
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access panel door switch opens 115--v power to
furnace control. No component operation can occur.
Caution must be taken when manually closing this
switch for service purposes.
15. Turn on electrical supply. Manually close blower access
panel door switch. Use a piece of tape to hold switch closed.
Check for proper rotation and speed changes between heating and cooling by jumpering R to G and R to Y/Y2 on
furnace control thermostat terminals. (See Fig. 15.)
16. If furnace is operating properly, release blower access panel
door switch, replace blower access panel, and replace main
furnace door.
CELL
PANEL
MANIFOLD
MOUNTING
SCREWS
GAS VALVE
REGULATOR
FITTING
GAS
CONTROL
VALV E
Fig. 6 -- Burner Box Assembly
FACTORY
ATTACHED TO
GASKET
MANIFOLD
A02312
PG9MAB
5
Page 6
Step3—CleaningBurners
The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from furnace gas control valve.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace
component damage.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation.
PG9MAB
5. Remove wires from gas valve. Note location for reassembly.
6. Remove burner box pressure tube from gas valve regulator
fitting.
7. Unplug igniter from harness.
8. Remove igniter leads from slot in manifold grommet.
9. Remove screws that secure manifold to burner box. (See
Fig. 6.)
NOTE: Do not remove burner box from cell panel.
10. Remove manifold, orifices, and gas valve as one assembly.
11. Remove screws attaching burner assembly in burner box.
NOTE: Use care when removing and reinstalling burners not to
strike the hot surface igniter.
15. Reinsert the igniter wires in the slot in the manifold grommet, dressing the wires to ensure there is no tension on the
igniter itself. (See Fig. 7.)
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Igniter wires must be securely placed in slot in manifold
grommet or else they could become pinched or severed
and electrically shorted.
16. Reconnect wires to gas valve and igniter. Refer to furnace
wiring diagram for proper wire location.
17. Reinstall burner box pressure tube to gas valve regulator fitting.
18. Reinstall gas supply pipe to furnace gas control valve using
backup wrench on gas valve to prevent rotation and improper orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.
DO NOT use T eflon tape.
!
WARNING
FIRE, EXPLOSION, UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death, or property damage.
Gas valve switch MUST be facing forward or tilted
slightly.
19. Replace burner box cover.
20. Turn on gas and electrical supplies to furnace.
IGNIT ER WIRES MUST
BE PLACED IN THIS SLOT
A05074
Fig. 7 -- Igniter Wire Placement
12. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be
removed as one assembly.
13. Clean burners with soft brush and vacuum.
14. Reinstall manifold, orifice, and gas valve assembly in burner box. Ensure manifold seal grommet is installed properly
and burners fit over orifices.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
21. Check for gas leaks.
22. Replace main furnace door.
Step 4 — Cleaning Heat Exchangers
The following items should be performed by a qualified service
technician.
Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build--up of soot and carbon indicates
that a problem exists which needs to be corrected, such as improper
adjustment of manifold pressure, insufficient or poor quality
combustion air, improper vent termination, incorrect size or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
6
Page 7
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace
component damage.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and hazardous
operation.
3. Disconnect wires or connectors to flame rollout switch, gas
valve, igniter, and flame sensor.
4. Disconnect combustion--air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and
rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from furnace gas control valve.
8. Disconnect pressure tubing from gas valve.
9. Remove two screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell
panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
6.)
NOTE: Burner box, cover, manifold, gas valve, and burner
assembly should be removed as one assembly.
11. Clean heat exchanger openings with a vacuum and a soft
brush. (See Fig. 8.)
NOTE: After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
PRIMARY HX
INLET OPENINGS
12. Reverse items 3 through 10 for reassembly.
NOTE: Be sure burner box gasket is installed between burner box
and cell panel. (See Fig. 6.) If gasket is damaged, replace it.
NOTE: Inspect combustion--air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any
way, it must be repaired. To repair, remove damaged gasket
section, apply sealant releasing agent such as PAM cooking spray
or equivalent (must not contain corn nor canola oil, halogenated
hydrocarbons nor aromatic content, to prevent inadequate seal
from occurring) to burner box and apply a small bead of G.E. RTV
162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to edge
of combustion--air intake housing. (See Fig. 9.)
RTV
PG9MAB
PAM
A93087
Fig. 9 -- Combustion--Air Intake Housing
Gasket Repair
13. Refer to furnace wiring diagram and reconnect wires to
flame rollout switch, gas valve, igniter, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake
housing. Refer to tube routing label on main furnace door
for proper tube location. (See Fig. 10.) Be sure tubes are not
kinked.
15. Turn on gas and electrical supplies to furnace.
16. Check furnace operation through two complete heat operating cycles. Look through sight glass in burner enclosure to
check burners. Burner flames should be clear blue, almost
transparent. (See Fig. 11.)
17. Check for gas leaks.
Fig. 8 -- Cleaning Inlet Openings of Primary
Heat Exchangers
!
CAUTION
UNIT MAY NOT OPERATE
Failure to follow this caution may result in improper or
intermittent unit operation.
The ground wire from the gas valve MUST be attached to
the burner box attachment screw.
A96305
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections.
18. Replace main furnace door.
Secondary Heat Exchangers
NOTE: The condensing side (inside) of the secondary heat
exchangers CANNOT be serviced or inspected. A small numb er of
bottom outlet openings can be inspected by removing the inducer
assembly. See Flushing Collector Box and Drainage System
section for details on removing inducer assembly.
Step 5 — Flushing Collector Box and Drainage
System
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or connectors.
7
Page 8
PG9MAB
Condensate Trap; Facto ry Installed
(Blower access panel removed)
INDUCER HOUSING (MOLDED) DRAIN TUBE
(BEHIND COLLECTOR BOX DRAI N TUBE)
COLLECTOR BOX DRAIN TUBE
FIELD-INSTALL ED FACTORY-SUPPLIED
Condensate Trap on
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY
INDUCER HOUSING DRAIN T UBE (VIOLET)
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
COLLECTOR BOX EXTENSION DRAIN TUBE
NOTE:
1. All tubing must be connected securely and rout ed to avoid kinks and t raps.
2. Pressure tubing must always slope away from pressure switch to coll ector box connection as shown.
3. HORIZONTAL-LEFT installati ons requir e the collector box pressure tube to be rel ocated between the inducer housing and the blower shelf to
prevent a trap.Refer to the Installation Instructions for further details.
Furnace is shipped from factory in upflow configuration. Pressur e tube and drain tube routing MUST match the diagrams below.
in Blower Shelf
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX TUBE
(GREEN)
(BLUE)
FIELD-INSTALL ED
FACTORY-SUPPLIED DRAIN TUBE
COUPLING (LEFT DRAI N OPTION)
DRAIN TUBE
LEFT Side
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
Tube location when used on
HORIZONTAL - LEFT application
PLUG
CAP
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
Tube location when used in UPFLOW application
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX DRAIN
TUBE
(BLUE & WHITE STRIPED)
CONDENSATE TRAP
FIELD-INSTALL ED
FACTORY-SUPPLIED
DRAIN TUBE COUPLI NG
(RIGHT DRAIN OPT ION)
FIELD-INSTALL ED
FACTORY-SUPPLI ED 1/2-IN.
CPVC STREET ELBOWS (2)
FOR LEFT DRAIN OPTION
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE)
CONDENSATE TRAP
Tube location when used in DOWNFLOW application
COLLECTOR BOX
DRAIN TUBE (BLUE)
DRAIN TUBE
COUPLING
PLUGGED END
PLUG
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRI PED)
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER
SHELF AND INDUCER HOUSING FOR
040,060, AND 080 HEATING INPUT
FURNACES
DRAIN TUBE
(VIOLET)
COLLECTOR BOX DRAIN
TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING DRAIN
TUBE (VIOLET)
DRAIN TUBE COUPLING
DRAIN TUBES ROUTED IN
FRONT OF GAS VALVE
COLLECTOR BOX DRAIN TUBE
(BLUE)
PLUG
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
Tube location when used on
HORIZONTAL - RIGHT application
TUBE ROUTING
Condensate Trap on LEFT
Side Option al
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
CAP
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING DRAI N TUBE
Condensate Trap on
PLUG
CAP
COLLECTOR BOX DRAIN TUBE
(BLUE)
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX TUBE
(GREEN)
COLLECTOR BOX EXTENSION TUBE
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY
CONDENSATE TRAP
COLLECTOR BOX
EXTENSION DRAI N TUBE
GAS VALVE
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX TUBE (PINK)
INDUCER HOUSING DRAIN T UBE (VIOLET)
AUXILIARY "J" BOX RELOCATED HERE
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
324999-201 REV. C
(VIOLET)
RIGHT Side
Fig. 10 -- Furnace Pressure and Drain Tubing Diagram
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by
loosening coupling clamp on inducer outlet.
6. Disconnect drain tube from inducer housing. (See Fig. 10.)
NOTE: Ensure the drain tube disconnected from the inducer
housing is higher than the collector box opening or water will flow
out of tube.
7. Remove inducer housing assembly by removing 4 bolts attaching assembly to cell panel.
8. Flush inside of collector box with water until discharge
from condensate trap is clean and runs freely.
9. Inspect inside area of collector box for any pieces of foreign
materials and remove them if present.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace
component damage.
DO NOT use wire brush or other sharp object to inspect or
dislodge materials in secondary heat exchangers as cutting
of the secondary heat exchanger protective coating may
occur. Flush with water only.
A00308
10. Reassemble inducer assembly by reversing items 3--7.
Tighten the vent coupling clamp screw(s) to 15 in.--lb of
torque.
NOTE: If seal between the inducer housing and the collector box
is damaged in any way, it must be repaired. To repair, apply sealant
releasing agent such as PAM cooking spray or equivalent (must not
contain corn nor canola oil, halogenated hydrocarbons nor
aromatic content, to prevent inadequate seal from occurring) to
inducer housing. (See Fig. 12.) Apply a small bead of G.E. RTV
162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to groove
in collector box.
11. Refer to furnace wiring diagram and reconnect wires to inducer motor and pressure switches or connectors.
12. Reconnect pressure tubes to pressure switches. See diagram
on main furnace door for proper location of tubes. Be sure
tubes are not kinked. (See Fig. 10.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through two complete heat operating cycles. Check area below inducer housing, vent pipe,
and condensate trap to ensure no condensate leaks occur. If
leaks are found, correct the problem.
15. Check for gas leaks.
8
Page 9
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death or property damage.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections.
16. Replace main furnace door.
Step 6 — Servicing Hot Surface Igniter
The igniter does NOT require annual inspection. Check igniter
resistance before removal.
1. Turn off gas and electrical supplies to furnace.
!
CAUTION
BURN HAZARD
Failure to follow this caution may result in personal injury.
Allow igniter to cool before removal. Normal operating
temperatures exceed 2000_F (1093_C).
2. Remove main furnace door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. Igniter resistance is affected by
temperature. Only check resistance when the igniter is at
room temperature.
a. Using an ohm meter, check resistance across both ig-
niter leads in connector.
b. Cold reading should be between 40 ohms and 70 ohms.
5. Remove igniter assembly.
a. Remove burner box cover.
b. Remove igniter wires from slot in manifold grommet.
(See Fig. 7.)
c. Using a 1/4--in. driver, remove the single screw securing
the igniter bracket to the burner box bracket (See Fig.
13.) and carefully withdraw the igniter and bracket assembly through the front of the burner box without
striking the igniter on surrounding parts. Note that the
igniter bracket has a handle that extends to the front of
the burner box to aid in handling. (See Fig. 13.)
d. Inspect igniter for signs of damage or failure.
e. If replacement is required, replace igniter on igniter
bracket and then install assembly into burner box to
avoid damage to the igniter.
6. To replace igniter and bracket assembly, reverse items 5a
through 5c.
7. Reconnect igniter wire connection and insert the igniter
wires in the slot in the manifold grommet, dressing the igniter wires to ensure there is no tension on the igniter itself.
(See Fig.7.)
8. Reinstall burner box cover.
9. Turn on gas and electrical supplies to furnace.
10. Verify igniter operation by initiating control board self--test
feature or by cycling thermostat.
11. Replace main furnace door.
BURNER FLAME
BURNER
PG9MAB
MANIFOLD
A89020
Fig. 11 -- Burner Flame
PAM
RTV
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in premature
failure of the igniter.
The igniter is fragile. DO NOT allow it to hit burner box
parts while removing or replacing it.
A93081
Fig. 12 -- Gasket on Collector Box
9
Page 10
EXTENDED IGNITER
BRACKET HANDLE
IGNITER BRACKET
MOUNTING SCREW
Fig. 13 -- Igniter Bracket
IGNITER
BRACKET
PG9MAB
2-5/32˝
(55 mm)
Fig. 14 -- Igniter
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Igniter wires must be securely placed in slot in manifold
grommet or else they could become pinched or severed and
electrically shorted.
9/16˝
11/16˝
A05075
A04181
Step 7 — Electrical Controls and Wiring
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
There may be more than one electrical supply to the unit.
Check accessories and cooling unit for additional electrical
supplies.
The electrical ground and polarity for 115--v wiring must be
maintained properly. Refer to Fig. 15 for field wiring information
and to Fig. 21 for unit wiring information.
NOTE: If the polarity is not correct or furnace is not properly
grounded, the STATUS LED on the furnace control will flash
rapidly and prevent the furnace from operating. The control system
also requires an earth ground for proper operation of the furnace
control and flame sensor.
The 24--v circuit contains an automotive--type, 3--amp fuse located
on the furnace control. (See Fig. 16.) Any direct shorts of the 24 --v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size. The furnace control LED will flash status code 24
when fuse needs to be replaced.
With power to the unit disconnected, check all electrical
connections for tightness. Tighten all screws on electrical
connections. If any smoky or burned connections are found,
disassemble the connection, clean all parts, strip wire, and
reassemble properly and securely.
Reconnect electrical supply to unit and observe unit through one
complete operating cycle and check for proper operation.
In applications where the ambient temperature around the furnace
is 32_F(0_C) or lower, freeze protection measures are required. If
this application is where heat tape has been applied, check to
ensure it will operate when low temperatures are present.
NOTE: Heat tape, when used, should be wrapped around the
condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:
1. Check for signs of physical damage to heat tape such as
nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or
discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
10
Page 11
FIVE WIRE
THREE-WIRE
HEATING-ONLY
BLOWER DOOR SWITCH
BLK
WHT
115-V FIELD-
SUPPLIED
BLK
WHT
GND
AUXILIARY
J-BOX
DISCONNECT
GND
FURNACE
NOTE 2
W
C
R
O
N
T
G
R
O
COM
L
Y
24-V
TERMINAL
BLOCK
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
WCRGY
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
NOTE 1
CONDENSING
GND
UNIT
TWO
WIRE
NOTES:Connect Y-terminal in furnace as shown for proper blower operation.
1.
Some thermostats require a "C" terminal connection as shown.
2.
If any of the original wire, as supplied, must be replaced, use
3.
same type or equivalent wire.
Fig. 15 -- Field Wiring
PG9MAB
A02174
BLOWER OFF-DELAY
J2 JUMPER
24-V THERMOSTAT
TERMINALS
3-AMP FUSE
LED OPERATION &
DIAGNOSTIC LIGHT
115-VAC(L2)NEUTRAL
CONNECTIONS
COOL
HEAT
BLOWER SPEED
SELECTION TERMINALS
G Com W Y R
24V
STATUS CODE LED
COOL HEAT
SPARE-1
SPARE-2
J2
TEST/TWIN
0.5 AMP@24VAC
FUSE 3-AMP
SEC-2 SEC-1
EAC-2 L2
NUETRAL
BLW
SPARE-1 SPARE-2
BLOWER OFF-DELAY
90 150
120 180
PLT
HUM
PLT 1
EAC-1
(115-VAC 1.0 AMP MAX.)
TWINNING AND/OR
COMPONENT TEST
TERMINAL
1-AMP@
115VAC
PR-1
L1
PL2 1
115 VAC (L1) LINE
VOLTAGE CONNECTION
EAC-1 TERMINAL
Fig. 16 -- Control Center
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
TRANSFORMER 24-VAC
CONNECTIONS
PL1-LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL2-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A02100
11
Page 12
!
CAUTION
UNIT AND PROPERTY DAMAGE
Failure to follow this caution may result in furnace
component failures or water property damage.
Operating a unit without a filter or with the blower access
door removed could cause damage to the furnace blower
motor. Dust and lint on internal parts of furnace can cause a
loss of efficiency. If this furnace is to be operated in an
unconditioned space where the ambient temperatures may
be 32_F(0_C)or lower, freeze protection measures must be
taken. See CONDENSATE DRAIN PROTECTION section
of Installation, Start-- up, and Operating Instructions. (See
Fig. 17.)
Step 9 — Winterizing
PG9MAB
UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace
component damage.
Freezing condensate left in the furnace may damage the
furnace.
If the furnace will be off for an extended period of time in a
structure where the temperature will drop to 32_F(0_C)or below,
winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect upper inducer housing drain connection cap
4. Connect field--supplied 1/2--in. I.D. inducer housing tube to
5. Insert funnel in tube and pour one quart of antifreeze, pro-
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
Do not use ethylene glycol (Prestone II antifreeze/coolant or
equivalent automotive type).
6. Replace drain connection cap and clamp to inducer housing.
7. Replace main furnace door.
8. Propylene glycol need not be removed before restarting fur-
!
CAUTION
from inducer housing. (See Fig. 18.)
upper inducer housing drain connection.
pylene glycol (RV, swimming pool antifreeze, or equivalent) into funnel/tube until it is visible at point where condensate enters open drain. (See Fig. 19.)
!
CAUTION
nace.
A07911
Fig. 17 -- Freeze Protection
WIRING DIAGRAMS
See Fig. 21 for wiring diagram.
TROUBLESHOOTING
Use the troubleshooting guide, the status code LED on the furnace
control and the component test to isolate furnace operation
problems.
Status Codes
For an explanation of status codes, refer to service label located on
back of main furnace door or Fig. 20.
NOTE: Removing the blower access door will open the blower
access door switch and terminate 115--v power to the control.
To read current status code, remove main furnace door. The status
code LED can be viewed through the sight glass on the blower
access door.
NOTE: NO thermostat signals may be present at control and all
blower off delays must be completed to view previous codes.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
Make sure limit switch or flame rollout switch wire does
not contact any metal component, such as gas valve. If wire
is shorted, 3-- amp fuse on furnace control board will open
and unit will not operate.
To retrieve previous codes, remove one of the red main limit or
flame rollout switch wires for 1 to 4 sec until the LED light goes
out, then reconnect it. (Do not leave red wire disconnected for
longer periods of time as the control will assume an
overtemperature condition exists and will respond with blower
operation.) This places the control in the status recall mode and
displays the last code stored in memory.
Record the code. After the last code is displayed the control will
perform the component test, and then return to normal standby
mode.
12
Page 13
PG9MAB
A99118
Fig. 18 -- Inducer Housing Drain Tube
Component Test
NOTE:The furnace control component test allows all
components to run for a short time; except the gas valve and
humidifier terminal HUM are not energized for safety reasons. The
EAC--1 terminal is energized when the blower is energized. This
feature helps diagnose a system problem in case of a component
failure. The component test feature will not operate if any
thermostat signal is present at the control and not until all time
delays are completed.
NOTE: Record the status code BEFORE opening the blower
access door and before shutting off power to furnace. Opening the
blower access door will open the blower door switch and shut off
power within the furnace. When power to the furnace is shut off by
either method, the status code will be lost because the code is not
stored while power is removed for any reason.
To Begin Component Self--Test:
!
WARNING
ELECTRICAL SHOCK AND UNIT MAY NOT
OPERATE HAZARD
Failure to follow this warning could result in electrical shock,
personal injury, or death.
Blower access panel door switch opens 115--v power to
control board. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes.
1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace control
board.
3. Manually close blower door switch.
4. For approximately 2 sec, short (jumper) the COM--24v terminal on control to the TEST/TWIN 3/16 -- in. quick--connect terminal on control until LED turns off. Remove jumper from terminals. (See Fig. 16.)
NOTE: If TEST/TWIN and COM-- 24v terminals are jumpered
longer than 2 sec, LED will flash rapidly and ignore component
test request.
A99119
Fig. 19 -- Funnel in Drain Tube and Antifreeze
Running Through Trap
Component test sequence for single--stage furnace is as follows:
a. LED will display status code 11 four times.
b. Inducer motor starts and continues to run until Step f. of
component test sequence.
c. After 7 sec the hot surface igniter is energized for 15
sec, then off.
d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.
f. Inducer motor stops.
5. Reconnect R lead to furnace control board, remove tape
from blower door switch, and reinstall blower door.
6. Operate furnace per instruction on outer door.
7. Verify furnace shut down by lowering thermostat setting below room temperature.
8. Verify that furnace restarts by raising thermostat setting
above room temperature.
Use the Component Test to check furnace components for proper
operation. To initiate the component self--test sequence, shut off the
room thermostat or disconnect the “R” thermostat lead. Briefly
(approximately 2 sec) short the TWIN/TEST terminal to the COM
24V terminal. The status LED will turn off. The test sequence will
be as follows:
1. LED flashes last status code, or code 11, 4 times. Record
this status code for further troubleshooting.
2. The inducer will start and continue to run until test is over.
3. Hot surface igniter (HSI) is energized for 15 sec, then de-energized.
4. Blower operates on continuous FAN speed for 10 sec, then
turns off.
5. The blower motor operates on HEATING speed for 10 sec,
then turns off.
6. The blower motor operates on COOLING speed for 10 sec,
then turns off.
7. Inducer turns off.
8. The gas valve and humidifier terminal HUM are not energized for safety reasons.
13
Page 14
PG9MAB
SERVICE
If status code recall is needed, briefly remove then reconnect one main limit wire to display
stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After one status code recall is completed component test will occur.
LED CODE
CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned,
refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY
THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72
hours. On RED LED boards stored status codes can also be erased when power
(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90
seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens
during blower on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit or flame rollout switch is
open longer than 3 minutes.
- Control will auto reset after three hours. - Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve -Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for:
- Low inducer voltage (115VAC) - Defective pressure switch
- Inadequate combustion air supply - Restricted vent
- Disconnected or obstructed pressure tubing
- Low inlet gas pressure (if LGPS used)
If it opens during blower on-delay period, blower will come on for the selected
blower off-delay.
33 LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will
run for 4 minutes or until open switch remakes whichever is longer. If open
longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes
status code #33 continues to flash until blower shuts off. Flame rollout switch
requires manual reset. Check for: - Restricted vent
- Defective blower motor or capacitor. - Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE - Control will try three more times before lockout
#14 occurs. If flame signal lost during blower on-delay period, blower will come
on for the selected blower off-delay. Check for: - Control ground continuity
- Flame sensor must not be grounded
- Oxide buildup on flame sensor (clean with fine steel wool).
- Gas valve defective or gas valve turned off - Manual valve shut-off
- Defective Hot Surface Ignitor
- Low inlet gas pressure
- Inadequate flame carryover or rough ignition
- Green/Yellow wire MUST be connected to furnace sheet metal
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open - Flame sense circuit failure
- Software check error
Reset power to clear lockout. Replace control if status code repeats.
STATUS
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect
the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer
motor will run for the entire component test. The hot surface ignitor, blower motor
FAN speed (AMBER LED boards only) blower motor HEAT speed, and blower motor
COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier
will not be turned on.
Fig. 20 -- Service Label
14
327884-101 REV. B
A02270
Page 15
SCHEMATIC DIAGRAM
(NATURAL GAS & PROPANE)
L2
NOTE #2
TO 115VAC FIELD DISCONNECT
EQUIPMENT GROUND
GND
L1
L2
CAP-1
LO
SPARE-2
ILK
EAC-2
IDM
BLWM
START
OL
COM
HI
MED LO
MED HI
NOTE #10
COOL
HEAT
SPARE-1
HI/L O
HSIR
EAC-1
BLWR
L1
AUX
OL
M
1
3
HSI
2
1
PL3
2
1
PL2
115VAC
PR1
IDR
PL4
24VAC
TRAN
TEST/TWI N
LS
FRS
CAP - 2
2
6
SEC-2
SEC-1
NOTE #6
F U 1
PRINTED CIRCIUT BOARD
NOTE #3
GV
(WHEN USED)
NOTE #11
PRS
LGPS
2
8
PL1
C
328150-101 REV. A
M
5
4
10
GVR-1
CPU
FSE
7
3
9
1
11
PG9MAB
NOTE #5
PCB
R
W
HUM
G
Y
OM
24V
C
1. If any of the ori ginal equipment wire is replaced use wire rated for 105°C.
2. Use only copper wire between the disconnect switch and the furnace junction box (JB).
3. This wire must be co nnected to furnace sheet metal f or control to prove flame.
4. Symbols are electrical representation only.
NOTES:
optimum speed select ion.
auto-reset after three hours.
5. Solid lines inside PCB are printed circuit b oard conductors and are not included i n legend.
TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will
the
code recall. You can also recall the previous status code by momentarily shorting
control do not remove power or blower access panel before initiating status
Switch or Flame Rollout switch to display stored status code. On RED LED
To recall status code briefly remove and reconnect one RED wire from the Limit
voltage (24V) transformer phasing.
ing. If units are twinned, check for proper low-
Check for correct line voltage polarity and ground-
YES
pause?
Is LED status light blinking rapidly without a
NO
NO
Is LED status light blinking ON/OFF slowly
YES
with a combination of short and long flashes?
The HSI, b
T speed, and COOL speed will run f
After the control repeats the code 4 times, the
a brief component test sequence.
vious code.
un for the entire component test.
seconds each. Gas valve and humidifier will not be turned on.
(AMBER LED boards only) HEA
and r
control will go through
there was no pre
flash the previous status code or status code #11 (1 short and 1 long flash) if
and the second
The status code is a
t flashes
digit by the number of long flashes?
by the number of shor
2 digit number with the first digit determined
Determine status code.
other than #11?
Was there a previous status code
YES
was flashed.
Go to section below for the status code that
16
A05107
Page 17
igniter.
er or rough
yov
Auto-reset after 1 hour lockout due to:
- Flame circuit failure.
45 CONTROL CIRCUITRY LOCKOUT
minutes, inducer shuts off for 15 minutes
OR REOPENED – If open longer than 5
31 PRESSURE SWITCH DID NOT CLOSE
- Gas valve relay stuck open.
- Software check error.
delay period, blower will come on for the
before retry. If opens during blower on-
Reset power to clear lockout. Replace
control if code repeats.
- Proper vent sizing.
selected blower off-delay. Check for:
- Low inducer voltage (115V).
Check for continuity in the harness and
Replace furnace control.
NO
YES
iod?
second per
the control. Was 115V present for the 15
for 115V between pin 1 and NEUTRAL-L2 on
another component test sequence. Check
Unplug igniter harness from control and initiate
(if LGPS used).
ucted pressure
ustion air supply.
gas pressure
isconnected or obstr
efective pressure switch.
efective inducer motor.
tubing.
- Excessive wind.
-D
-D
-D
- Inadequate comb
- Low inlet
Check connections. If OK, replace control.
Replace defective component.
NO
Reconnect the R thermostat lead and set
Blower
open.
is
LT – Indicates the
icted vent.
estr
limit or flame rollout switch
-R
33 LIMIT CIRCUIT FAU
ve.
al
Replace v
Check that all gas valves are turned on.
connections. Does gas valve
lve
e 24V?
mostat to call for heat. Connect voltmeter
receiv
across gas va
ther
h
itc
ver is longer. If open
longer than 3 minutes, code changes to
remakes whiche
will run for 4 minutes or until open sw
Inadequate flame carr
-
Check for:
NO
YES
e open and allow gas to flow?
Does gas valv
requires manual reset. Check for:
blower shuts off. Flame rollout switch
status code #33 continues to flash until
lockout #13. If open less than 3 min.
ignition.
YES
lower wheel.
- Dirty filter or restricted duct system.
- Loose b
- Proper firing rate.
- Low inlet gas pressure.
NO
Do the main burners ignite?
e blower motor or capacitor.
efectiv
-D
- Defective switch or connections.
er to come on and repeat test to
k connections and retry. If current is
Chec
check for intermittent operation.
Allow blow
YES
urners stay on?
Do the main b
estricted vent.
-R
- Blower motor on incorrect speed tap.
- Excessive wind.
- Proper vent sizing.
NO
or heat and check flame sensor
Repeat call f
nace set too high.
- Input rate to fur
YES
witch open).
(flame rollout s
Inadequate combustion air supply
-
value (4.0-6.0 nominal) and
burners will not stay on, replace control.
near typical
NO
YES
ow 0.5?
ing trial for ignition period. Is the
DC microamps bel
current dur
NO
out
flame
ck
or ignition
the control will repeat the ignition
iod,
GNITION PROVING FAILURE – If
sequence 3 more times before lo
per
is not sensed during the trial f
34 I
microamps.
recheck current. Nominal current is 4.0 to 6.0
Clean flame sensor with fine steel wool and
YES
l
MUST be connected
wire
reen/Yellow
to furnace sheet metal.
-G
- Gas valve turned off.
proceeding to the next step.
Check the following items first before
come on for the selected blower off-delay.
the blower on-delay period, blower wil
#14 occurs. If flame signal is lost during
- Manual shut-off valve.
Replace electrode.
NO
Is current near typical value?
- Flame sensor must not be grounded.
Replace furnace control.
NO
YES
urners ignite and stay on?
Will main b
k the igniter. First
igniter, or flame sensor the
the control and initiate the component
remove the R thermostat connection from
test mode to chec
system can be operated in the component
the gas valve,
To determine whether the problem is in
YES
ed.
Fix
warm-up period?
orange/white by the end of the 15 second
test sequence. Does the igniter glow
PG9MAB
e
WER UP –
check system.
upted. Run system through a
heating or cooling cycle to
is interr
erased whenever power (115V or 24V)
boards stored status codes can also be
are erased after 72 hours. On RED LED
NO PREVIOUS CODE – Stored codes
11
uns for 90 seconds, if unit is
er r
WER ON AFTER PO
ow
blower on-delay period.
closed) or when (R-W opens) during th
powered up during a call for heat (R-W
Bl
(115V OR 24V) – Normal operation.
12 BLO
13 LIMIT CIRCUIT LOCKOUT – Lockout
occurs if the limit or flame rollout switch is
open longer than 3 minutes. Control will
.
See code 33
eset after 3 hours.
auto-r
attempts.
See status code 34.
Control will auto-reset after 3 hours.
ignite gas and prove flame in 4
14 IGNITION LOCKOUT – System failed to
n off
21 GAS HEATING LOCKOUT – Tur
17
Check for:
SECONDARY VOLTAGE FUSE IS OPEN
24
ltage (24V)
vo
t circuit in secondary
wiring including thermostat leads.
-Shor
isconnect thermostat leads to isolate
short circuit.
D
A05096
on control.
k for:
Chec
power and wait 5 minutes to retry.
VING SIGNAL
k for:
Inducer will run until fault is
ed.
- Pressure switch stuck closed.
- Obstructed pressure tube.
- Stuck open or leaky gas valve.
cleared. Chec
energiz
- Miswire or short to gas valve wire.
- Stuck closed gas valve relay
Flame is proved while gas valve is de-
22 ABNORMAL FLAME-PRO
Check for:
23 PRESSURE SWITCH DID NOT OPEN
Page 18
PG9MAB
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your
knowledge of the equipment discussed in this manual, including:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available, using popular
video-based formats and materials. All include video and/or slides, plus companion
book.
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
A94328
E2008 Payne Heating & Cooling Systems D7310 W. Morris St. D Indianapolis, IN 46231Printed in U.S.A.Edition Date: 12/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
18
C a t a l o g N o : S G --- P G 9 M A B --- 0 3
R e p l a c e s : S G --- PG 9 M A B --- 0 2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.