Paxton 2A User Manual

28/06/2012
Ins-30098 2A/12V DC boxed power supply
Technical Support
01273 811011 support@paxton.co.uk
Technical help is available: Monday - Friday from 07:00 - 19:00 (GMT)
Saturday from 09:00 - 13:00 (GMT)
Documentation on all Paxton products can be found on our website - http://www.paxton.co.uk/
Layout
12V DC Outputs
Paxton
V21
V21
V21
V0
USP
V0
V0
V0
Tamper Switch
Mains Failure
Monitoring
Back-up battery
Battery
INPUT AC 100-240V 50 / 60 Hz
1.2A OUTPUT DC 13.8V 2A
Ratings Label
PSU
elbaegrahceRdelaeS
MAINS POWER
hA7V21
Green
Red
Status Lights
This LED is on when the input supply is healthy.
This LED is on when the input supply has failed - Power is being supplied by the battery.
116mm
25mm
Fitting
1. Screws and wall plugs are provided in a tting
kit. With reference to the diagrams, determine where the top, central mounting position is required and drill a hole suitable for a No 8 wall plug.
2. Tap in one of the wall plugs.
320mm
Metal Cabinet
68mm
AC Mains Connection
232mm
268mm
68mm
3. Put in one of the long screws, leaving a suitable gap to the wall surface and slide the cabinet over it.
4. Mark the hole positions for the lower 2 screws.
5. Remove the cabinet and drill the additional holes.
6. Tap in the 2 wall plugs and hang the cabinet back onto the top screw.
7. Secure the cabinet with the 2 lower screws.
8. Tighten the top screw.
This product is not suitable for retail sale. All warranties are invalid if this product is not installed by a competent person.
118mm
18mm
A detachable gure 8 power cable is
provided with the unit. This is pre-stripped at one end for connection to a fused spur.
Anchor points are supplied inside the case to secure the incoming mains cable. (cable tidy/ties are provided) There are also 'knock-outs' in the case to allow convenient access for the cable.
Ensure that the supplied compression gland is used when passing the mains cable through any holes in the cabinet.
The power supply is double insulated and requires no additional earth connection.
The PSU's battery function will not
work until this unit has rst been
connected to the mains supply. It is the loss of this supply that switches the unit to battery power.
Plastic Cabinet
98mm
320mm
284mm
98mm
236mm
Statement of Conformity
The Low Voltage (LVD) Directive - 2006/95/EC The Electro-Magnetic Compatibility (EMC) Directive - 2004/108/EC The Restriction of Hazardous Substances (RoHS) Directive - 2002/95/EC
Loading...
+ 1 hidden pages