PAW HeatBloC MC46 DN 25, HeatBloC MC46 DN 32 Installation And Operation Instructions Manual

PAW GmbH & Co. KG
Installation and Operation Instructions
HeatBloC MC46
DN 25 / DN 32
Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu
2017/02 99453x0333x-mub-en – V02 1
1
General Information
Item no. 99453x0333x-mub-en – Version V02 – Issued 2017/02
Translation of the original instructions
We reserve the right to make technical changes without notice!
Printed in Germany – Copyright by PAW GmbH & Co. KG
2 99453x0333x-mub-en – V02 2017/02
PAW GmbH & Co. KG
Böcklerstr. 11
D-31789 Hameln, Germany
1
General Information

Contents

1 General Information ......................................................................................................... 4
1.1 Scope of these instructions .......................................................................................... 4
1.2 Designated use ............................................................................................................ 4
2 Safety instructions ........................................................................................................... 5
3 Product description .......................................................................................................... 6
3.1.1 Equipment ............................................................................................................. 6
3.1.2 Function ................................................................................................................ 7
3.2 3-way mixing valve [specialist] ..................................................................................... 8
3.3 Pump [specialist] .......................................................................................................... 8
3.3.1 Pump settings ....................................................................................................... 8
3.3.2 Pump settings Grundfos UPM3 Hybrid .................................................................. 9
3.3.3 Pump settings Wilo-Yonos PARA RSTG ............................................................... 9
3.4 Check valve ............................................................................................................... 10
3.5 Actuator ...................................................................................................................... 11
4 Assembly and installation [specialist] .............................................................................. 12
4.1 Installation and commissioning of the HeatBloC ......................................................... 12
4.2 Cabling ....................................................................................................................... 14
4.3 Optional accessories .................................................................................................. 15
4.3.1 Cutting-ring compression fitting (not included in the scope of delivery) ................ 15
4.3.2 Wall bracket set for wall assembly (not included in the scope of delivery) ........... 16
5 Scope of delivery [specialist] .......................................................................................... 17
5.1 Insulation and controller DN 25 .................................................................................. 17
5.2 Hydraulics DN 25 ....................................................................................................... 18
5.3 Insulation and controller DN 32 .................................................................................. 19
5.4 Hydraulics DN 32 ....................................................................................................... 20
6 Technical data ............................................................................................................... 21
6.1 Dimensional drawing DN 25 ....................................................................................... 22
6.2 Dimensional drawing DN 32 ....................................................................................... 22
6.3 Pressure drop and pump characteristic curves DN 25 ................................................ 23
6.4 Pressure drop and pump characteristic curves DN 32 ................................................ 23
2017/02 99453x0333x-mub-en – V02 3
1
General Information

1 General Information

Carefully read these instructions before installation and commissioning. Save these instructions in the vicinity of the installation for future reference.

1.1 Scope of these instructions

These instructions describe the installation, commissioning, function and the operation of the HeatBloC MC46 in DN 25 and DN 32. For other components of the installation, such as the pump or the controller, please observe the instructions of the corresponding manufacturer. The chapters called [specialist] are intended for specialists only.

1.2 Designated use

The HeatBloC may only be used in heating circuits taking into consideration the technical limit values indicated in these instructions. The HeatBloC must
not be used in drinking water applications. Improper usage of the HeatBloC
excludes any liability claims.
Only use PAW accessories with the HeatBloC.
This product complies with the relevant directives and is therefore labelled with the CE mark. The Declaration of Conformity is available upon request. Please contact the manufacturer.
The wrapping materials are made of recyclable materials and can be disposed of with recyclable materials.
4 99453x0333x-mub-en – V02 2017/02
2
CAUTION
Personal injury and damage to property!
not
NOTICE
Material damage due to mineral oils!
Safety instructions

2 Safety instructions

The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist]. The following must be observed during installation and commissioning:
relevant local and national regulations
accident prevention regulations of the professional association
instructions and safety instructions of this manual
The HeatBloC must only be used in heating circuits filled with heating water according to VDI 2035 / Ö-Norm H 5195-1.
The HeatBloC must
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
It is imperative to avoid that EPDM gets in contact with substances containing mineral
oils.
Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as
Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.
be used in drinking water applications.
2017/02 99453x0333x-mub-en – V02 5
3
Product description

3 Product description

The HeatBloC MC is a preassembled group of fittings for heating circuits. The integrated pump can be isolated by means of ball valves and can thus be maintained without draining of the system.
The nominal value for the differential pressure between the flow and the return is adjusted at the controller. On this basis, the controller regulates the pump and an energy-saving operation of the pump is guaranteed at any time.

3.1.1 Equipment

A-1 Flow from the heat generator
A-2 Flow ball valve with temperature
sensor T
and thermometer
V
B Flow pipe
B -1 Check valve, can be opened
C 3-way mixing valve with actuator
C-1 Non-return valve, can be opened
C-2 Flow to the consumer circuit
C-3 Return from the consumer circuit
D Heating pump
E Design insulation according to
EnEV directive
F-1 Return to the heat generator
F-2 Return ball valve with temperature
sensor T
and thermometer
R
G Differential pressure sensor
H Controller MCom
6 99453x0333x-mub-en – V02 2017/02
3

MC46 - Boiler charging set with 3-way mixing valve

Application ranges:

HeatBloC
MC46
T
RE
TFL
PWM
p
Product description

3.1.2 Function

The boiler charging set prevents the temperature in the boiler from falling under the dew point, thus reducing the contamination of the boiler.
The return temperature to the heat generator is kept at the set temperature level by the integrated mixing valve. Hot water from the boiler and cold return water are mixed to reach the desired return temperature to the heat generator.
return flow temperature maintenance for
solid fuel boilers, wood firing and stove heating systems
for a constant flow rate in the heat generator
2017/02 99453x0333x-mub-en – V02 7
3
10
0
Product description

3.2 3-way mixing valve [specialist]

The mixing valve (C), driven by an electric actuator, adjusts the flow temperature of the consumer circuit to the required value by means of the flow sensor and the controller.
Position 10: Passage,
no mixing, return temperature consumer = return temperature boiler
Position 0: 100% mixing
flow temperature heat generator = return temperature heat generator

3.3 Pump [specialist]

Isolation of the pump

The pump can be completely isolated. It can be replaced and maintained without draining the HeatBloC.
1. Close the ball valves in the flow and the return (A-2, F-2).
2. Remove the actuator from the mixing valve.
3. Turn the rotary knob of the mixing valve such that the black nose is directed to "VL zu"
(flow closed). The mixing valve is now closed and drop tight.

3.3.1 Pump settings

The pump has been correctly adjusted at the factory. In the case of a breakdown of the control (no PWM signal), the pump runs at maximum rotation speed. To assure a proper functioning of the heating circuit, the pump must be set as follows:
PWM profile (heating)
8 99453x0333x-mub-en – V02 2017/02
3
Product description

3.3.2 Pump settings Grundfos UPM3 Hybrid

The following code must appear on the pump display. The code can be verified by briefly pressing the push button. Please observe the separate instructions of the pump!
Yellow
Off
Off
Yellow
Red

3.3.3 Pump settings Wilo-Yonos PARA RSTG

The rotary knob of the pump must be set to the following symbol. The LED ring is illuminated in orange. Please observe the separate instructions of the pump!
2017/02 99453x0333x-mub-en – V02 9
3
Operation Filling, draining, venting
Product description

3.4 Check valve

The HeatBloC is equipped with a check valve (B-1) in the flow pipe and with a non-return valve (C-1) in the mixing valve. The valves can be opened.
During operation, the marking must be directed to "Z".
The check valve is closed.
Flow only in the direction of the arrow.
For filling, draining and venting the installation, the marking must be directed to "A".
The check valve is open.
Flow in both directions.
10 99453x0333x-mub-en – V02 2017/02
3
Assembly of the actuator for mixing valves:
Product description

3.5 Actuator

blue
1. Turn the rotary knob of the
mixing valve into position 10.
2. Set the actuator to manual
mode by turning the selector
Stop bolt
switch.
3. Turn the rotary knob of the
actuator to the left to the position shown on the adjacent figure.
4. Put the actuator on the
adjusting knob of the mixing valve and the two stop bolts.
5. Set the actuator to automatic
mode.
2017/02 99453x0333x-mub-en – V02 11
4
NOTICE
Damage to property!
NOTICE
Assembly and installation [specialist]

4 Assembly and installation [specialist]

The HeatBloC MC can be mounted directly to the wall or on a wall bracket set.
The location of installation must be dry, load-carrying, frost-proof and protected against ultraviolet radiation in order to prevent material damage of the installation.

4.1 Installation and commissioning of the HeatBloC

Verify if the grounding cable holds securely in place at the differential pressure sensor!
The ground lug points in the direction of the banderole.
1. Remove the station from the packaging.
2. Determine the location of installation.
3. Drill two holes. They must have a distance of
45 mm.
4. Insert appropriate wall plugs. Please note that the
enclosed wall plugs are only adapted for full brick masonry.
5. Screw the stair bolts in such that exactly 25 mm
of the bolts stick out of the wall (see figure on the left).
6. Push the enclosed spacer (K) onto the stair bolt.
7. Push the HeatBloC onto the stair bolt.
8. Fix the HeatBloC on the stair bolts with the
enclosed washers and nuts.
12 99453x0333x-mub-en – V02 2017/02
4
Assembly and installation [specialist]
9. Take off the thermometer handles.
10. Remove the actuator.
11. Note regarding HeatBloC with Wilo pump:
Dismount the insulating front shell of the controller and push the insulating back shell backwards.
12. Take off the insulating front shells.
13. Push the insulating back shell backwards.
14. Connect the HeatBloC to the installation by using the
pipes. The installation to the piping must be carried out without any tension.
15. Fill and vent the installation.
16. Carry out a pressure test and check all thread
connections.
17. Check the position of the check valve: during
operation, the marking must be directed to "Z" (see page 10).
18. Connect the power supply of the pump to the boiler
control.
19. Mount the insulating back shell.
20. Run first the cable of the actuator through the
insulating element of the mixing valve backwards. Mount the insulating element. Mount the actuator (see page 11) and pull the actuator cable backwards at the same time.
21. Mount the insulating front elements.
2017/02 99453x0333x-mub-en – V02 13
4

4.2 Cabling

Assembly and installation [specialist]
1. Loosen the screws of the controller
insulation.
2. Dismount the insulating front shell of the
controller.
3. Connect the wall power supply to the
socket X6.2 (see below) at the controller.
X1 X2 X3 X4 X5 X6.1 X6.2
X1 Signal of the actuator X4 Temperature sensor TV, flow, red
marking
X2 PWM signal of the pump X5 Differential pressure sensor
X3 Temperature sensor TR, return,
blue marking
X6.1
X6.2
Supply voltage or bus line (connected in parallel and therefore interchangeable)
4. Carry out the electrical commissioning of
the controller (see controller instructions).
5. Mount the insulating front shell of the
controller.
6. Screw the screws in the controller
insulation.
14 99453x0333x-mub-en – V02 2017/02
4
Assembly and installation [specialist]
7. Please fill in the enclosed insert and fix
it on the insulation:
Type: Type of the heating circuit, f. ex.
MC46
MC46
Name: Type of application,
f. ex. return flow temperature
Return flow temperature
maintenance
1
No.: Number of the heating circuit
according to the controller instructions, f. ex. 1

4.3 Optional accessories

4.3.1 Cutting-ring compression fitting (not included in the scope of delivery)

1. Push the union nut ② and the cutting ring ③ onto the
copper pipe ①. The pipe must protrude at least 3 mm
from the cutting ring in order to ensure the force transmission and the sealing.
2. Insert the support sleeve ④ into the copper pipe.
3 mm
Not included in the scope of
delivery!
3. Insert the copper pipe with the plugged-on individual
parts (②, ③ and ④) as far as possible into the housing of the compression fitting ⑤.
4. First, screw the union nut ② manually.
5. Tighten the union nut ② by rotating one full turn.
Secure the housing of the compression fitting ⑤
against distort, in order to avoid damaging the sealing ring.
2017/02 99453x0333x-mub-en – V02 15
4
Description
Item no.
Assembly and installation [specialist]

4.3.2 Wall bracket set for wall assembly (not included in the scope of delivery)

Wall bracket set DN 25 3422SET
Wall bracket set DN 32 3722SET
16 99453x0333x-mub-en – V02 2017/02
5
NOTICE
Scope of delivery [specialist]

5 Scope of delivery [specialist]

Complaints and requests/orders of spare parts will only be processed with information on the serial number! The serial number is placed on the flow pipe of the heating circuit.

5.1 Insulation and controller DN 25

2017/02 99453x0333x-mub-en – V02 17
5
Item
Item number
Pump
EEI

5.2 Hydraulics DN 25

Scope of delivery [specialist]
Sealing set for mixing valve 34013
Grundfos UPM3 Hybrid 25-70
Wilo-Yonos PARA RSTG 25/1-7.5
18 99453x0333x-mub-en – V02 2017/02
E1212465F < 0.20
E1236247 < 0.21
5
Insulation
Item no.
Scope of delivery [specialist]

5.3 Insulation and controller DN 32

HeatBloC with Grundfos pump
HeatBloC with Wilo pump
E171593
B 1715933
2017/02 99453x0333x-mub-en – V02 19
5
Item
Item number
Pump
EEI

5.4 Hydraulics DN 32

Scope of delivery [specialist]
Sealing set for mixing valve 37013
Grundfos UPM3 Hybrid 32-70
Wilo-Yonos PARA RSTG 30/1-7.5
20 99453x0333x-mub-en – V02 2017/02
E1212565F < 0.20
E1236257 < 0.21
6
DN 25 (1")
DN 32 (1¼")
Dimensions
Connections
Technical data
Materials
Hydraulics
Technical data

6 Technical data

Centre distance 125 mm 125 mm
Width insulation 250 mm 250 mm
Height insulation 500 mm 557 mm
Installation length 340 mm 400 mm
Connection generator 1½" external threads,
flat-sealing
2" external thread,
flat-sealing
Connection consumer 1" internal thread 1¼" internal thread
Opening pressure check valve 200 mm wc, can be opened
Valves and fittings Brass
Gaskets AFM34 / EPDM
Insulation EPP, EnEV conform
Maximum pressure 6 bars
Maximum temperature 110 °C
KVS value [m3/h] 6.0 10.1
2017/02 99453x0333x-mub-en – V02 21
6

6.1 Dimensional drawing DN 25

Technical data

6.2 Dimensional drawing DN 32

22 99453x0333x-mub-en – V02 2017/02
6
Differential pressure [m wc]
Differential pressure [kPa]
Differential pressure [m wc]
Differential pressure [kPa]
Technical data

6.3 Pressure drop and pump characteristic curves DN 25

Flow rate [l/h]

6.4 Pressure drop and pump characteristic curves DN 32

Flow rate [l/h]
2017/02 99453x0333x-mub-en – V02 23
PAW GmbH & Co. KG
Böcklerstraße 11
D-31789 Hameln, Germany
99453x0333x-mub-en – V02 2017/02
Phone: +49 (0) 5151 9856 - 0
Fax: +49 (0) 5151 9856 - 98
www.paw.eu