PAW FriwaMini 6401410, FriwaMini 6401415 Installation And Operation Instructions Manual

PAW GmbH & Co. KG
FriwaMini
FriwaMini with circulation
Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu
Installation and Operation Instructions
FriwaMini - DN 15
FriwaMini with circulation - DN 15
2017/07 99640141x-mub-en - V02 1
1
General Information
Item no. 99640141x-mub-en - Version V02 - Issued 2017/07
Translation of the original instructions
We reserve the right to make technical changes without notice!
Printed in Germany – Copyright by PAW GmbH & Co. KG
2 99640141x-mub-en - V02 2017/07
PAW GmbH & Co. KG
Böcklerstraße 11
D-31789 Hameln, Germany
1
CONTENTS
1 General Information ......................................................................................................... 4
2 Safety instructions ........................................................................................................... 6
3 Product description .......................................................................................................... 7
4 Dimensioning and planning .............................................................................................. 8
5 Circulation mode ........................................................................................................... 10
6 Assembly and installation [specialist] .............................................................................. 11
7 Commissioning [specialist] ............................................................................................. 14
8 Maintenance [specialist] ................................................................................................. 21
9 Spare parts [specialist] .................................................................................................. 22
10 Technical data ............................................................................................................... 25
11 Commissioning report .................................................................................................... 27
General Information
1.1 Scope of these instructions .......................................................................................... 4
1.2 About this product ........................................................................................................ 5
1.3 Designated use ............................................................................................................ 5
4.1 Dimensioning of the tank .............................................................................................. 9
7.1 Filling the primary circuit ............................................................................................. 15
7.2 Commissioning of the controller ................................................................................. 16
7.3 Maximum withdrawal flow rate ................................................................................... 18
7.4 Adjustment of the temperature ................................................................................... 20
9.1 Spare parts controller and insulation .............................................................................. 22
9.2 Spare parts primary circuit.......................................................................................... 23
9.3 Spare parts secondary circuit ..................................................................................... 24
10.1 Dimensional drawing .................................................................................................. 26
10.2 Pressure drop characteristic curve ............................................................................. 26
2017/07 99640141x-mub-en - V02 3
1

1 General Information

1.1 Scope of these instructions

Station
Item
number
Controller
FC4.13
Pump
prim./sec.
Heat
exchanger
FriwaMini
6401410
FriwaMini
with circulation
6401415
General Information
Carefully read these instructions before installation and commissioning. Save these instructions in the vicinity of the installation for future reference.
These instructions describe the installation, commissioning, function and operation of the FriwaMini domestic hot water module. The chapters called [specialist] are intended for specialists only. For other components of the system, such as tanks, controllers or pumps, please observe the instructions of the corresponding manufacturer.
Prim: Grundfos
UPM3 15-75
50 plates
FlowEstimation
Prim: Grundfos
UPM3 15-75
FlowEstimation
Sec: Grundfos
50 plates
UPM3 15-70 CIL3
4 99640141x-mub-en - V02 2017/07
1

1.2 About this product

1.3 Designated use

General Information
The domestic hot water module is a premounted group of fittings checked for tightness and used to transfer the heat between the buffer tank and the domestic hot water circuit. It contains a preset controller and important fittings for the operation of the system:
Ball valves in the primary circuit
Piston valves in the secondary circuit
Pressure relief valve in the secondary circuit
Premounted controller
Temperature sensor at the cold water inlet
Temperature sensor in the heating circuit flow line
Flow meter at the domestic hot water outlet
Primary and circulation pump can be isolated
Manual vent valve for venting the heat exchanger
and the pump
The domestic hot water module must only be mounted in heating installations between the buffer tank and the domestic hot water circuit. Due to its design, the station must be mounted and operated in a vertical position! The technical limit values specified in these instructions must be observed.
Only use PAW accessories with the domestic hot water module.
Improper usage excludes any liability claims.
The wrapping materials are made of recyclable materials and can be disposed of with recyclable materials.
2017/07 99640141x-mub-en - V02 5
2

2 Safety instructions

NOTICE
Material damage due to mineral oils!
NOTICE
Malfunction!
Safety instructions
The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist]. The following must be observed during installation and commissioning:
relevant local and national regulations
accident prevention regulations of the professional association
instructions and safety instructions of this manual
Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties get lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way.
It is imperative to avoid that EPDM gets in contact with substances containing mineral
oils.
Use a lubricant based on silicone or polyalkylene and free from mineral oils, such as
Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray.
The domestic hot water module must be integrated in the potential equalisation of the
electric installation. This can be guaranteed by establishing a potential equalisation connection to the main potential connection according to regulations or by the connected pipe system.
6 99640141x-mub-en - V02 2017/07
3

3 Product description

Primary circuit
Connections
1
2
3
4
5 Equipment primary circuit
A
B
C
D
E
F
Equipment secondary circuit
G
H
I
J
K Only for the protection of the station. Does not replace the pressure relief valve that has to be mounted on site!
L
M
Secondary circuit
Example: FriwaMini with circulation
Product description
Primary side/heating side: Return to the buffer tank
Primary side/heating side: Flow from the buffer tank
Secondary side/DHW side: Hot water supply, circulation
Secondary side/DHW side: Cold water supply
Secondary side/DHW side: Hot water outlet
Heat exchanger
Temperature sensor Pt1000
Ball valve
Ball valve with check valve
Primary pump
Manual vent valve
Piston valve with drain valve (cold water inlet)
Piston valve with drain valve (hot water outlet)
Analogue flow rate sensor, VFS 2-40 l/min
Temperature sensor Pt1000
Pressure relief valve 10 bars
2017/07 99640141x-mub-en - V02 7
Circulation pump
Piston valve with drain valve (circulation)
4

4 Dimensioning and planning

WARNING
Danger of scalding due to hot water!
Mounting example
Safety group according to DIN 1988
Dimensioning and planning
The FriwaMini is a domestic hot water module operating on the principle of a flow-type water heater.
The DHW module will only work flawlessly if the installation meets certain requirements. Please take some time to plan the installation.
Undesirable circulation of water in the primary circuit can cause the exit of water of up to 90 °C at the withdrawal point.
External pumps must not be installed between the domestic hot water
module and the buffer tank.
The domestic hot water module must not be connected to a distribution
manifold of a heating circuit.
FriwaMini circulation with optional return distribution (item no. 640425).
8 99640141x-mub-en - V02 2017/07
4

4.1 Dimensioning of the tank

Temperature in the buffer tank
Domestic hot water temperature set at the controller
Required tank volume
per litre of hot water
60 °C*
45 °C
0.9 litre
*Calculation example for the dimensioning of the buffer tank:
Dimensioning and planning
The following table helps you to calculate the approximately required volume of the buffer tank.
50 °C 45 °C 1.6 litres
50 °C 1.2 litres
55 °C 1.7 litre
50 °C 0.9 litre
70 °C
55 °C 1.1 litre
60 °C 1.3 litre
50 °C 0.7 litre
80 °C
55 °C 0.9 litre
60 °C 1.0 litre
Temperature of the buffer tank: 60 °C
Maximum withdrawal quantity needed: 20 l/min
Domestic hot water temperature set at the controller: 45 °C
How large must the tank be to allow for a continuous withdrawal during 20 minutes without post­heating?
20 l/min x 20 min = 400 l
400 l x 0.9 = 360 l
The heated part of the buffer tank must have a volume of 360 litres.
2017/07 99640141x-mub-en - V02 9
5

5 Circulation mode

Pulse-controlled operation
Time-dependent operation:
Temperature-dependent operation:
NOTICE
Damage to property!
Circulation mode
The domestic hot water module is equipped with a circulation pump.
For the operation of the circulation pump, three possible operation modes are stored in the controller (see controller instructions, page 21).
(depending on the demand / requirements):
The short actuation of a hot water tap (tap pulse: ~2 sec.) starts the circulation pump. The circulation pump will then run for several minutes (adjustable).
The operation of the circulation pump can be set on a week clock within freely selectable periods of time. In this operation mode, the circulation is activated at the beginning of the period of time chosen. The circulation will stop after the end of the chosen period of time.
In this operation mode, the circulation is only activated if the adjustable minimum temperature at the circulation temperature sensor is not reached during the chosen period of operation. The circulation stops after the required temperature has been reached or after the end of the chosen period of time.
The operating modes can be combined with each other as wished, f. ex. the time- and the temperature-dependent operating modes. The circulation is only activated if the temperature at the circulation temperature sensor falls below the required value and if the time window is active.
Outside the time slot, the circulation pump can be activated by a tap pulse if the pulse-controlled operation mode is additionally activated.
When the DHW module is delivered, the circulation is not activated (see controller instructions, page 15). During commissioning the operation mode must be selected and pre-set under all circumstances. The revolution speed of the circulation pump must be defined by the PWM signal (factory setting: 100 %).
10 99640141x-mub-en - V02 2017/07
6

6 Assembly and installation [specialist]

The domestic hot water connection must be carried out in accordance with the relevant norms (for example DIN 1988)!
NOTICE
Damage to property!
NOTICE
Damage to property!
module
Fittings
Drain valve
Pressure relief valve
Return valve (non-return valve)
Possibly pressure reducing valve
Test valve
Shut-off valve
Hot water
Cold water
Assembly and installation [specialist]
The domestic hot water module must only be connected with the storage tank by separate connections for the flow and return. External pumps must not be installed between the domestic hot water module and the buffer tank. The circulation of water causes considerable temperature fluctuations.
DHW
The pressure relief valve integrated in the station does not replace the safety groups of the potable water connection as per DIN 1988. The pressure relief valve only protects the module from overpressures in case of servicing.
If there are water supplies that may cause pressure surges (for example flush valves, washing machines or dishwashers), connected to the same mains as the domestic hot water module, we recommend the installation of water hammer arresters close to the place where these pressure surges may be caused.
For example the make Flexofit S of the Flamco GmbH company or the make WD of the Reflex Winkelmann GmbH company.
2017/07 99640141x-mub-en - V02 11
6
WARNING
Risk to life and limb due to electric shock!
NOTICE
Damage to property!
Assembly and installation [specialist]
Prior to commencing electrical work on the controller, pull the mains plug! Only after completing all installation work, plug the mains plug of the
controller into a socket. An unintentional start of the motors is thus avoided.
The location of installation must be dry, load-carrying, frost-proof and protected against ultraviolet radiation in order to prevent material damage of the installation.
1. Determine the mounting location of the
domestic hot water module near the buffer tank. The pipes in the heating circuit must not exceed a length of 4 m (for DN 20).
2. Copy the measures for the mounting holes
to the wall. You can find a corresponding drilling template (see on the right) on the paper board under the domestic hot water module.
3. Drill the holes and insert adequate wall
plugs into the holes.
4. Turn the screws into the wall plugs in such
a way that about 40 mm of each screw still stick out.
5. Remove the insulating front shell.
6. Hang the domestic hot water module onto
the screws. Tighten the screws, so that the sides of the insulation are flush to the wall.
12 99640141x-mub-en - V02 2017/07
6
1
Primary side:
recommended DN 25: 28 x 1.5 mm
2
Primary side:
recommended DN 25: 28 x 1.5 mm
3
Secondary side:
4
Secondary side:
5
Secondary side:
(primary) = 112 mm
Assembly and installation [specialist]
7. Connect the domestic hot water module
with the installation by using the piping according to the adjacent figure.
return to the buffer tank, connection: ¾" internal thread, pipes at least DN 20: 22 x 1 mm,
flow from the buffer tank, connection: ¾" internal thread, pipes at least DN 20: 22 x 1 mm,
Pipe distance to the wall (secondary) = 72 mm
hot water supply, circulation, connection: ¾" external thread, flat sealing
cold water inlet, connection: ¾" external thread, flat sealing
hot water outlet, connection: ¾" external thread, flat sealing
Pipe distance to the wall
2017/07 99640141x-mub-en - V02 13
7

7 Commissioning [specialist]

Note!
Slowly

Functioning check valve

45°
completely
Position 0°
Position 45°
Position 90°
flow only in flow direction.
flow in both directions.
no flow.
14
open the valves in the pipes and in the module, in order to prevent pressure surges.
The primary circuit is equipped with a check valve in the ball valve (D), in order to avoid unwanted gravity circulation.
For venting and flushing the installation, the check valve must be open. For this purpose, turn the ball
Commissioning [specialist]
valve into the position In this position, the check valve is not operating.
For the operation of the installation, all (ball) valves must be
.
open (position 0°).
Check valve is operating,
14 99640141x-mub-en - V02 2017/07
Check valve is not operating,
Ball valve closed,
7

7.1 Filling the primary circuit

WARNING
Danger of scalding due to hot water!
If the storage tank is (partly) filled
90°
45°
Primary circuit
*1.5 bars in the primary circuit = recommended minimum value The pressure depends on the individual system pressures and the components of the heating installation!
Commissioning [specialist]
The system is under pressure. By opening the vent valve, hot water with a temperature of up to 90 °C may exit and cause personal injury.
Open the vent valve slowly and with sufficient distance.
1. Slowly open the ball valve (C) by turning it into
position
.
2. Fill the storage tank using the fill valves available
on site until an operating pressure of about
1.5 bars* is reached. Use heating water compliant with the standards VDI 2035 / ÖNorm H5195-1.
3. Manipulate the vent valve (F) cautiously to let the
air escape.
4. Close the vent valve (F).
5.
Close the ball valve (C) by turning it into position
Slowly open the ball valve (D) by turning it into
6.
position
.
.
7. Manipulate the vent valve (F) cautiously to let the
air escape.
8. Close the vent valve (F).
9. Check the operating pressure of the storage tank
after the venting and increase the pressure if necessary.
10.
Open the ball valves (C) and (D) completely by turning them into position
.
2017/07 99640141x-mub-en - V02 15
7

7.2 Commissioning of the controller

WARNING
Risk to life and limb due to electric shock!
Primary circuit
Secondary circuit
Check if the sensors and pumps are properly connected to the controller
Commissioning [specialist]
and if the controller housing is closed.
Only under these circumstances, the mains plug of the controller can be plugged into a socket.
1. Connect the domestic hot water module to
the mains (230 V, 50 Hz) by using the premounted connection cable.
2. Select "Manual mode" in the main menu of
the controller and set the pump to "HE1" (PWM signal = 100 %), see controller manual page 27.
3. Let the pump run for several minutes to vent
the domestic hot water module.
4. When the air noises do not stop, carefully
manipulate the vent valve (F) while the pump is still running and let the air escape.
5. If the air noises have stopped, the pump can
be switched off.
6. To do so, select "Manual mode" in the main
menu of the controller and set the pump to "AUTO".
7. Slowly open the piston valves on the
secondary side (G and H).
16 99640141x-mub-en - V02 2017/07
7
Secondary circuit
Commissioning [specialist]
8. Open a withdrawal point for domestic hot
water (for example a tap) with a flow rate of at least 10 l/min and let the water run for about 2 minutes to vent the secondary circuit. Close all withdrawal points of the secondary circuit afterwards.
9. Make sure that the domestic hot water
module is correctly integrated into the potential equalisation of the installation.
10. Set the desired domestic hot water
temperature at the controller (see page 20).
11. The domestic hot water module is now ready
for operation.
2017/07 99640141x-mub-en - V02 17
7

7.3 Maximum withdrawal flow rate

hot water temperature of 45 °C
Withdrawal flow rate [l/min]
Power [kW]
Domestic hot water temperature: 45 °C
Boundary conditions:
Example 1
Example 2
FriwaMi
Temperature of the buffer tank
Example 2
Example 1
Commissioning [specialist]
The following diagram illustrates the maximum withdrawal flow rate depending on the tank temperature with a preset avoids temperature drops as long as the maximum flow rate is not exceeded.
at the tap. The integrated control
Cold water temperature: 10 °C
Maximum pressure drop on the domestic hot water side of the DHW module: 1000 mbars
The following examples illustrate the correlation between the domestic hot water temperature, the withdrawal flow rate and the temperature of the buffer tank and show their impact on the heat transfer capacity of the DHW module.
Domestic hot water temperature at the withdrawal point: 45 °C
Temperature in the buffer tank: 50 °C
DHW module: max. withdrawal flow rate: 18 l/min, heat transfer capacity: 41 kW
Domestic hot water temperature at the withdrawal point: 45 °C
Maximum withdrawal flow rate: 27 l/min
DHW module: temperature in the buffer tank: 60 °C, heat transfer capacity: 67 kW
18 99640141x-mub-en - V02 2017/07
7
hot water temperature
is of 60 °C
Withdrawal flow rate [l/min]
Power [kW]
Domestic hot water temperature: 45 °C, after heating to 60 °C and addition of cold water (10 °C)
Boundary conditions:
Example 1
Example 2
FriwaMini
Temperature of the buffer tank
Example 1
Example 2
Commissioning [specialist]
The following diagram illustrates the maximum withdrawal flow rate at a domestic hot water temperature of 45 °C at the tap, after the addition of cold water of 10 °C.
The domestic
Cold water temperature: 10 °C
set at the controller
.
Domestic hot water temperature at the controller: 60 °C
Temperature in the buffer tank: 70 °C
DHW module: max. withdrawal flow rate: 31 l/min, heat transfer capacity: 77 kW
Domestic hot water temperature at the controller: 60 °C
Maximum withdrawal flow rate: 21 l/min
DHW module: temperature in the buffer tank: ~65 °C, heat transfer capacity: 53 kW
2017/07 99640141x-mub-en - V02 19
7

7.4 Adjustment of the temperature

WARNING
Danger of scalding due to hot water!
60 °C

Primary side

Secondary side

Commissioning [specialist]
Set the desired (maximum) domestic hot water temperature at the controller under "Main menu / Hot water / T HW nom." (see controller instructions, page 19).
In order to avoid scalding at the tap, the maximum domestic hot water temperature set at the controller must not exceed
.
The required temperature on the primary side in the buffer tank depends on the desired domestic hot water temperature and on the required tap quantity. The temperature in the buffer tank must be at least 5 K above the desired domestic hot water temperature.
The possible withdrawal flow rate [l/min] at the tap depends on the domestic hot water temperature adjusted at the controller and on the temperature available in the buffer tank.
The recommended maximum domestic hot water flow rate through the domestic hot water module is ~42 l/min.
The following table illustrates the correlation between the storage tank temperature and the maximum withdrawal flow rate at a water temperature of 45 °C at the tap (f. ex. single lever tap). If the domestic hot water temperature set at the controller is above 45 °C, the tap flow rate consists of a mixture of hot and cold water.
The indicated heat transfer capacity is necessary to heat up the water quantity of the withdrawal flow rate [l/min] from 10 °C to 45 °C.
20 99640141x-mub-en - V02 2017/07
8
Temperature in the
buffer tank
Domestic hot water
temperature set at the
controller
Maximum flow rate from
the DHW module with the
set hot water temperature
Maximum withdrawal
flow rate at the tap for a
domestic hot water
temperature of 45 °C
Heat transfer capacity of
the DHW module
FriwaMini
FriwaMini
FriwaMini
50 °C
60 °C
70 °C
80 °C

8 Maintenance [specialist]

Maintenance [specialist]
45 °C 18 l/min 18 l/min 44 kW
45 °C 31 l/min 31 l/min 76 kW
50 °C 24 l/min 27 l/min 67 kW
55 °C 17 l/min 21 l/min 53 kW
45 °C 39 l/min* 39 l/min 95 kW
50 °C 32 l/min 36 l/min 89 kW
55 °C 27 l/min 34 l/min 85 kW
60 °C 22 l/min 31 l/min 77 kW
45 °C 42 l/min* 42 l/min 102 kW
50 °C 40 l/min* 45 l/min 112 kW
55 °C 34 l/min 43 l/min 107 kW
60 °C 29 l/min 41 l/min 101 kW
at a cold water temperature of 10 °C, reheating not considered
*maximum flow rate: 42 l/min, with pressure drop of the DHW module of 1000 mbars (for hydraulic reasons, higher values are only partly possible, measuring limit of the flow rate sensor ~42 l/min)
In order to guarantee an optimal control, no additional hydraulic pressure losses should occur on the primary side (f. ex. due to the installation of a mud strainer, a strainer or a mixing valve).
2017/07 99640141x-mub-en - V02 21
9

9 Spare parts [specialist]

NOTICE

9.1 Spare parts controller and insulation

Spare parts [specialist]
Complaints and requests/orders of spare parts will only be processed with information on the serial number! The serial number is placed in the lower right corner of the support sheet of the station.
22 99640141x-mub-en - V02 2017/07
9

9.2 Spare parts primary circuit

Spare parts [specialist]
2017/07 99640141x-mub-en - V02 23
9

9.3 Spare parts secondary circuit

*
Spare parts [specialist]
*only included in the scope of delivery of 6401415
24 99640141x-mub-en - V02 2017/07
10

10 Technical data

Dimensions
FriwaMini
FriwaMini with circulation
Height (with insulation)
539 mm
Width
306 mm
344 mm
Depth (with insulation)
314 mm
Centre distance prim./sec.
90 mm
Pipe connections
Primary circuit (storage tank circuit)
¾" internal thread
Secondary circuit (DHW circuit)
¾" external thread, flat sealing
flat sealing
Operating data
Max. admissible pressure
primary: 3 bars, secondary: 10 bars
Operating temperature
2 – 95 °C
Kvs value primary
3.1
Kvs value secondary
2.4
Equipment
Check valve
1 x 400 mm wc
Primary pump
HE pump with PWM control, 2-60 W
PWM control, 2-52 W
Heat exchanger
50 plates
Flow rate sensor
1 x VFS 2-40 l/min
Temperature sensor
2 x Pt1000, rapid
Materials
Valves and fittings
Brass
Gaskets: o-rings
EPDM
Flat sealings
AFM 34, asbestos-free
Plate heat exchanger
Stainless steel 1.4401 / solder: 99.99% Cu
Insulation
EPP
Check valve
Hostaform
Technical data
Secondary circuit (circulation)
Secondary pump
¾" external thread,
HE pump with
2017/07 99640141x-mub-en - V02 25
10

10.1 Dimensional drawing

10.2 Pressure drop characteristic curve

Technical data
Pressure [m wc]
Pressure [kPa]
Flow rate [l/h]
26 99640141x-mub-en - V02 2017/07
11

11 Commissioning report

Commissioning report
Installation operator
Location of installation
Serial numbers:
DHW module
Flow rate sensor
Controllers
Software version
Pipes primary
Pipes secondary
Pipes circulation
Other additionally installed components
Have both circuits been flushed and vented correctly? (no air noises in the pump) Vented
Are all shut-off valves open in the cold water line? Open
Is there a pressure of at least 1.5 bars on the primary side? Checked
Is there a pressure of at least 2.5 bars on the secondary side? Checked
Is the potential equalisation processed according to regulations? Checked
Is there an error message on the display? No message
=
=
=
Return distribution set Miscellaneous
mm l = m
mm l = m
mm l = m
Plumbing company Date, signature
2017/07 99640141x-mub-en - V02 27