pass & seymour CS500, CS1200, PWP2120, PWP2277, AR120/277 Installation Instructions Manual

...
Syracuse, NY 13221
800.223.4185
Installation Instructions
CS Series
360° PIR Occupancy Sensor
Specifications
Voltages . . . . . . . . . . . . . . . . . . . . .20–30VDC (24VDC Typical)
Time Adjustment . . . . . . . . . . . . . . . . .15 seconds–30 minutes
Sensitivity Adjustment . . . . . . . . . . . . . . .Minimum/Maximum
U.S. Patents:
4,757,204 • 4,787,722
Des360,842
DESCRIPTION
The CS Series sensor is a 24VDC Passive Infrared (PIR) occupancy sensor which controls lighting or HVAC systems based on occupancy in a given area.
PIR sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. PIR sensors must directly “see” motion of an occupant to detect them, so careful consideration must be given to sensor placement.
COVERAGE PATTERNS
The CS sensor has a multi-cell, multi-tier Fresnel lens with a field of view of 360°. The sensor has two lens pattern options. The Extended Range Lens will cover up to 1200 sq ft and 22 feet from the sensor when mounted at 8 feet. The High Density/Reduced Range Lens will cover up to 500 sq ft and 12 feet from the sensor when mounted at 8 feet.
Coverage shown in the diagrams below is maximum and represents coverage for half-step, walking motion, with no barriers or obstacles.
DRAWING NOT TO SCALE
8ft
12 ft 12 ft 3 ft 3 ft5ft 5ft7ft 7ft9ft 9ft0
Typical
desk-top
level
24 ft
Extended Range Lens (Standard) CS1200
High Density/Reduced Range Lens CS500
44 ft
8ft
22 ft 13 ft 7 ft 3 ft 0 3 ft 7 ft 13 ft 22 ft
Typical
desk-top
level
Visit our website at www.passandseymour.com
PLACEMENT
The effective coverage distances may be slightly less than the maximum sensing distance (see Coverage Patterns), depending upon obstacles such as furniture or partitions, and this must be considered when planning the number of sensors and their positioning. See the list below for approximate coverage distances for different types of motion.
Approximate coverage, for a mounting height of 8 feet: Lens option Walking motion Workstation (hand motion)
High Density up to 12 ft radius (500 sq ft) 9 ft radius (300 sq ft) Extended Range up to 22 ft radius (1200 sq ft) 12 ft radius (500 sq ft)
The CS sensor can be mounted at various heights. When mounting at heights other than 8 feet, be aware that as you decrease the mounting height, you will decrease the range and increase the sensitivity to smaller motions. Conversely, when you increase the height, you will increase the range and decrease the sensitivity to smaller motions. At heights of more than 12-14 feet, you may start to significantly reduce sensitivity.
Often the best location to install a CS sensor in a closed office is off-center (see fig.1). Avoid placing a sensor directly in line with an open door in which it has a clear view out, as the sensor may detect people walking by. For open office areas with partitions it is best to place sensors over intersections of four workstations (see fig. 2).
Also avoid placing the sensors close to air ducts, as rapid air currents or the differences in temperatures may cause false activations. For large areas of coverage use multiple sensors.
CS Sensor
36'
36'
12'
18'
CS Sensor
fig.1
fig. 2
Call 800.223.4185 for Technical Support