Parmet GP-300, GP-500, GP-400, GP-750, GP800 Installation And Service Manual

...
1
1
INSTALLATION AND SERVICE MANUAL
PARMET GP300/500/900
Section Title Page
1 Introduction 2
2 Location 2
3 Positioning the Unit 2
4 Combustion and Ventilation Requirements ...2
5 Flues ...3
6 Gas Pipe Connection 4
7 Electrical Connections 4
8 Commissioning Instructions 5
9 Maintenance Instructions 5
10 Users Instructions 6
Appendix A- Wiring Diagrams
Appendix B Burner Data
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS AND THE REGULATIONS IN FORCE AND ONLY USED IN A SUITABLY VENTILATED LOCATION. READ THE INSTRUCTIONS FULLY BEFORE INSTALLING OR USING THIS APPLIANCE WHICH MUST BE INSTALLED BY A CORGI APPROVED ENGINEER
2
2
1. Introduction
The Parmet Range of Gas Fired Warm Air Heaters covers applications with outputs from 300,000 to 800,000 Btu/h.
The standard unit is the free -standing unit incorporating swivel type distribution heads. These units are available with inlet and outlets spigots suitable for connection to ductwork.
2.Location
The installation of a warm air heating system must conform with any fire regulations or insurance requirements especially wher e special risks are involved i.e. where there is paint spraying, etc. Attention must be paid where polyurethane based products are used in the premises as these can cause corrosion to the heat exchanger.
Installation of free blowing PARMET air heaters:-
Position the air heater taking into regard the position of the exhaust flue and avoid the heater being obstructed by pillars or shelving which could prevent the warm air from circulating. When more than one air heater is installed in the same room it is good practice to distribute the air in opposing directions. If air is to be ducted from the appliance all ducting should be made from non­combustible material. Where interjoist spaces are used as duct routes they should be suitably insulated to prevent excessive heat transfering to the
woodwork. A full unobstructed return air path should be provided to enable the air to return to the heater.
3. Positioning the Unit.
Free standing air heaters must be positioned on a level base that is capable of supporting the full weight of the unit.
Ensure that sufficient clearance is allowed for, and maintained, around the heater to facilitate easy access to the burner, main fan assembly and heat exchanger for servicing purposes and to allow unrestricted passage of the return air unless the system is ducted.
WARNING:­ Clearance should be allowed for the
pressure relief to operate.
4. Combustion and Ventilation Requirements.
Combustion Air
It is important to ensure that there is sufficient air for combustion, especially when a heater is positioned in an enclosed area i.e.plant room.
The air supply requirements shown relate to the total rated input of the heater(s). Size of air vent given is for air direct from outside and relates to the free area of the grill.
Loading...
+ 4 hidden pages