Parkray Inset Chevin 8 Installation And Operating Instructions Manual

JINCHI08 RevC 21/05/14
Inset Chevin 8
Multi-Fuel Inset Stove
Installation and Operating Instructions
JINCHI08 RevC 21/05/14
Inset Chevin 8
Technical Specification
This appliance is not for use in shared flue
This appliance is suitable for intermittent burning
This stove has been designed and assembled so that it may be used to burn wood logs in a Smoke Control Area. Find out if you are in a Smoke Control Area by contacting your Local Authority.
The Inset Chevin 8 has been fitted with a permanent bypass that prevents closure of the secondary air slider. Removal of this will lead to the appliance potentially causing smoke emissions. Without the permanent bypass in place the appliance is not an exempt appliance and so may leave the householder liable for a fine up to £1000.
INSET Chevin 8
Parkray Stoves, Trevilla Park,
Slaugtherbridge, Camelford, PL32 9TT
DSEN 13229 – Inset Wood Burning Stove
Stove Mass: 116.5 kg
NOMINAL OUTPUT: 6.0 KW
CO Emission at 13% O2: 0.18%
Mean Flue Gas Temperature: 326°C
EFFICIENCY: 75%
Flue Gas Mass Flow: 6.1 g/s
Minimum clearance to combustible material
At the sides of the stove:
In front of the stove (to furniture etc):
Above the stove:
200mm 700mm 275mm
This appliance is suitable for intermittent burning
This appliance is not suitable for use in a shared flue
Read and follow the operating instructions
Use only recommended fuels
13
JINCHI08 RevC 21/05/14
General Guidance
It is important that your stove is correctly installed as Hunter stoves cannot accept responsibility for any fault arising through incorrect use or installation. These instructions cover the basic principles to ensure satisfactory installation of the stove, although detail may need slight modification to suit particular local site conditions.
The installation must comply with current Building Regulations, national and European standards, Local Authority byelaws and other specifications or regulations as they affect the installation of the stove. The Building Regulations requirements may also be met by adopting the relevant recommendations in the current issues of British Standards BS 8303 and BS EN 15287-1.
COMPETENT PERSONS SCHEME
Hunter Stoves recommend that this stove is installed by a member of an accredited competent persons scheme e.g. HETAS. If the installer is not a member of a competent person’s scheme, it is a legal requirement to notify your local building control body in advance of any work starting.
CO ALARMS
Building regulations require that whenever a new or replacement fixed solid fuel or wood/biomass appliance is installed in a dwelling, a carbon monoxide alarm must be fitted in the same room as the appliance.
Further guidance on the installation of the carbon monoxide alarm is available in BS EN 50292:2002 and from the alarm manufacturer’s instructions.
Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular servicing and maintenance of the appliance and chimney system.
HEALTH AND SAFETY PRECAUTIONS
Special care must be taken when installing the stove such that the requirements of the Health and Safety at Work Act are met.
HANDLING
Adequate facilities must be available for loading, unloading and site handling.
FIRE CEMENT
Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In case of contact, wash immediately with plenty of water.
ASBESTOS
This stove contains no asbestos. If there is a possibility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective equipment.
METAL PARTS
When installing or servicing this stove, care should be taken to avoid the possibility of personal injury.
MODIFICATION
No unauthorized modification of this appliance should be carried out.
Safety
WARNING – This appliance will be hot when in operation and due care should be taken. The supplied gloves may be used to open the door and operate the air controls.
AEROSOLS
Do not use an aerosol spray on or near the stove when it is alight.
FIREGUARDS
Always use a fireguard in the presence of children, the elderly or the infirm. The fireguard should be manufactured in accordance with BS8423 – Fireguards for use with solid fuel appliances.
DO NOT OVER-FIRE
It is possible to fire the stove beyond its design capacity. This could damage the stove so watch for signs of over-firing. If any part of the stove starts to glow red, the stove is in an over-fire situation and the controls should be adjusted accordingly. Never leave the stove unattended for long periods without first adjusting the controls to a safe setting. Careful air supply control should be exercised at all times.
JINCHI08 RevC 21/05/14
FUME EMISSION
WARNING NOTE
Properly installed, operated and maintained, this appliance will not emit fumes into the dwelling. The appliance door(s) must be kept closed at all times, except for when de-ashing and refueling, during which occasional fumes may occur. However, Persistent fume emission is potentially dangerous and must not be tolerated. If fume emission does persist, then the following immediate action should be taken: -
1. Open doors and windows to ventilate the room
and then leave the premises.
2. Let the fire go out.
3. Check for flue or chimney blockage and clean if
required.
4. Do not attempt to re-light the fire until the cause
of the fume emission has been identified and corrected. If necessary, seek expert advice.
The most common cause of fume emission is flueway or chimney blockage. For your own safety these must be kept clean at all times.
Adverse weather In a small number of installations, occasional local weather conditions (e.g. wind from a particular direction) may cause downdraught in the flue and cause the stove to emit fumes. In these circumstances, the stove should not be used. A professional flue installer will be able to advise on solutions to this problem (e.g. anti-downdraught cowl).
CO ALARM
Your installer should have fitted a CO alarm in the same room as the appliance. If the alarm sounds unexpectedly, follow the instructions given under “Warning Note” above.
DO NOT FIT AN EXTRACTOR FAN IN THE SAME ROOM AS THIS APPLIANCE.
IN THE EVENT OF A CHIMNEY FIRE -
Raise the alarm Call the Fire Brigade Close appliance air controls Move furniture, ornaments etc away
Place a fireguard in front of stove Check the chimney breast for signs of excessive
heat.
If the wall is becoming excessively hot, move furniture away. Ensure the Fire Brigade can gain access to your roof space in order to check for fire spread.
Installation
APPLIANCE DIMENSIONS
FLUE OUTLET POSITION
The flue outlet angle is 30°. The effective centre dimension is shown below.
JINCHI08 RevC 21/05/14
AIR SUPPLY
The room or space containing this appliance should have purpose provided ventilation (where necessary) in accordance with Building Regulations.
Due consideration should be given to air requirements for any other appliance in the same room or space.
Any air opening must be kept clear from blockage or obstruction.
APPLIANCE OPENING
FLUE CONNECTION - All inset installations must have a
‘Throat Forming Lintel’, if a ‘Builders Opening Lintel is present then this will have to be modified for these units to be fitted.
This stove must be fitted on a hearth or base with adequate load-bearing capacity. The opening into which this stove is fitted should be constructed wholly from non-combustible materials. The dimensions of the opening should be at least those shown in the diagram.
This appliance will fit into a standard 16” fireplace
opening if the clay fireback is removed.
Any non-combustible walls within 50mm of this appliance should be at least 200mm thick and should extend at least 300mm above the top of the appliance and at least 1.2 metres above the hearth. Any walls more than 50mm from the appliance may be reduced to a thickness of 75mm. Ensure the inter­connecting flue pipe also has adequate clearances to combustible materials.
The walls surrounding the stove will become hot and should therefore be finished in a heat resistant plaster.
Do not hang pictures, plasma screen televisions or ornaments above the stove, as these could be damaged and could potentially create a fire hazard.
Please check the suitability of any fireplace/surround for closed solid fuel appliances before installation. Hunter Stoves cannot be held responsible for any fault arising through incorrect use or installation. Fire surround back panels suitable for solid fuel are usually in three sections and slabbed. Many fire surrounds are suitable only for use with gas and electric fires and therefore not suitable for solid fuel.
HEARTH REQUIREMENTS
A constructional hearth with a minimum thickness of 125mm should be provided. This constructional hearth should extend to at least 300mm in front of the stove and 150mm at the sides.
The constructional hearth should be made of solid non-combustible material and can include any solid non-combustible floor. The boundary of the hearth must be clearly marked. This can be done by adding a super-imposed hearth on top of the constructional hearth – e.g. a slate slab on top of a solid concrete floor.
FLUE REQUIREMENTS
The flue serving this appliance must be dry, free from cracks and obstructions and be in accordance with the designations shown in Table 1.
Table 1 Minimum Flue Designations
JINCHI08 RevC 21/05/14
The diameter of the flue should not be less than 150mm and not more than 200mm. If these requirements are not met the chimney should be lined by a suitable method. If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations Approved Document J or a twin-walled insulated stainless steel flue to BS EN 1856 can be used. These chimneys must be fitted in accordance with the
manufacturer’s instructions and Building
Regulations.
Table 1 – Minimum Flue Designations
The chimney/flue should have a vertical height of at least 4.5 metres and should terminate in accordance with Table 2.
If the chimney is believed to have previously served an open fire installation, it is possible that the higher flue gas temperature from the stove may loosen deposits that were previously firmly adhered, with the consequent risk of flue blockage. It is therefore recommended that the chimney is swept a second time within a month of regular use after installation.
If you have any doubts about the suitability of your chimney, consult your local dealer/stockist. Both the chimney and flue pipe must be accessible for cleaning and if ANY part of the chimney cannot be reached through the stove
(with baffle removed), a soot door must be fitted in a suitable position.
FLUE DRAUGHT
If the draught exceeds the recommended maximum, a draught stabiliser must be fitted so that the rate of burning can be controlled and to prevent over firing.
If the reading is less than the recommended minimum then the performance of the appliance will be compromised.
The flue draught should be checked under fire at high output.
Minimum Draught – 1.2mm Water Gauge Maximum Draught – 2.5mm Water Gauge
Flue Type
Minimum Designation
Masonry or flue block flue
with liner
T400 N2 D3 G
(BS EN 1443:2003)
Clay Flue Blocks
FB1 N2
(BS EN 1806:2006)
Clay/Ceramic Liners
B1 N2
(BS EN 1457:2009)
Concrete Liners
B2
(BS EN 1857:2003)
Factory Made Metal
Chimney
T400 N2 D3 G
(BS EN 1856-1:2003)
Position
Clearances to Flue
Outlet
a
At or within 600mm of the ridge
At least 600m above the ridge
b
Elsewhere on a roof (whether pitched or flat)
At least 2300mm horizontally from the nearest point on the weather surface and:
highest point of intersection of the chimney and the weather surface or
c
Below (on a pitched roof) or within 2300mm horizontally to an openable roof light, dormer window or other opening.
At least 1000mm above the top of the opening.
d
Within 2300mm of an adjoining or adjacent building, whether or not beyond the boundary.
At least 600mm above any part of the adjacent building within 2300mm
Table 2 – Flue Terminal Positions
Loading...
+ 12 hidden pages