Parker N2-45P, N2-20P, N2-55P, N2-65P, N2-60P User Manual

...
Page 1
Nitrogen Gas Generator
NITROSource N2-20P - N2-80P
Original Language
User Guide
aerospace climate control electromechanical
fluid & gas handling hydraulics pneumatics process control sealing & shielding
EN
Page 2
Page 3
CONTENTS - EN
1 Safety Information ..................................................................................................................................................................................3-EN
1.1 Markings and Symbols ..................................................................................................................................................................4-EN
1.2 Personnel Definitions.....................................................................................................................................................................4-EN
1.2.1 Generator Model Number Identification .................................................................................................................................5-EN
2 Description ..............................................................................................................................................................................................6-EN
2.1 Technical Specification..................................................................................................................................................................6-EN
2.2 Approvals and Compliance ...........................................................................................................................................................7-EN
2.2.1 Approvals ...............................................................................................................................................................................7-EN
2.2.2 Compliance ............................................................................................................................................................................7-EN
2.3 Weights and Dimensions ...............................................................................................................................................................8-EN
2.4 Materials of Construction ..............................................................................................................................................................8-EN
2.5 Receiving and Inspecting the Equipment ....................................................................................................................................9-EN
2.5.1 Storage...................................................................................................................................................................................9-EN
2.5.2 Unpacking ..............................................................................................................................................................................9-EN
2.6 Overview of the equipment..........................................................................................................................................................10-EN
3 Installation and Commissioning..........................................................................................................................................................11-EN
3.1 Recommended System Component Layout ..............................................................................................................................11-EN
3.1.1 Compressed air pre-treatment .............................................................................................................................................11-EN
3.2 Locating the Equipment...............................................................................................................................................................12-EN
3.2.1 Environment .........................................................................................................................................................................12-EN
3.2.2 Space Requirements............................................................................................................................................................12-EN
3.2.3 Air Inlet Quality.....................................................................................................................................................................12-EN
3.3 Mechanical Installation ................................................................................................................................................................13-EN
3.3.1 General Requirements .........................................................................................................................................................13-EN
3.3.2 Securing the Generator........................................................................................................................................................14-EN
3.3.3 Making the Connections.......................................................................................................................................................14-EN
3.4 Electrical Installation....................................................................................................................................................................15-EN
3.5 General Requirements .................................................................................................................................................................15-EN
3.6 Customer Connections ................................................................................................................................................................15-EN
3.6.1 Generator Mains Voltage Supply .........................................................................................................................................15-EN
3.6.2 Dryer Supply.........................................................................................................................................................................16-EN
3.6.3 Purge Economy....................................................................................................................................................................16-EN
3.6.4 Alarm Contacts.....................................................................................................................................................................16-EN
3.6.5 Remote Switching ................................................................................................................................................................16-EN
3.6.6 4–20mA Analogue Output....................................................................................................................................................17-EN
3.6.7 MODBUS..............................................................................................................................................................................17-EN
4 Operating the Generator ......................................................................................................................................................................18-EN
4.1 Overview of the Controls .............................................................................................................................................................18-EN
4.2 Starting the generator ..................................................................................................................................................................18-EN
4.3 Stopping the generator ................................................................................................................................................................19-EN
4.4 Menu Interface ..............................................................................................................................................................................19-EN
4.4.1 Hour Meters..........................................................................................................................................................................20-EN
4.4.2 Fault Log ..............................................................................................................................................................................20-EN
4.4.3 Customer Settings................................................................................................................................................................20-EN
4.5 Oxygen Content............................................................................................................................................................................22-EN
4.6 Economy Mode .............................................................................................................................................................................22-EN
4.7 Energy Saving Technology - EST ...............................................................................................................................................22-EN
4.8 Oxygen Sensor Calibrationn .......................................................................................................................................................23-EN
5 Preventative Maintenance....................................................................................................................................................................24-EN
5.1 Cleaning ........................................................................................................................................................................................24-EN
5.2 Maintenance Schedule........................................................................................................
.........................................................24-EN
5.3 Preventative Maintenance Kits....................................................................................................................................................25-EN
5.3.1 High Purity Generators (PPM)..............................................................................................................................................25-EN
5.3.2 Low Purity Generators (%)...................................................................................................................................................25-EN
5.3.3 Kit Contents..........................................................................................................................................................................26-EN
6 Troubleshooting....................................................................................................................................................................................27-EN
7 Declaration of Conformity....................................................................................................................................................................28-EN
8 Wiring Schematic..................................................................................................................................................................................29-EN
Page 4
Page 5
3 - EN
1 Safety Information
Important: Do not operate this equipment until the safety information and instructions in this user guide have been read and understood by all personnel concerned.
WARNING - USER RESPONSIBILITY
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker-Hannifin Corporation, its subsidiaries and authorized distributors provide product or system options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance, endurance, maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry standards, and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user, the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and reasonably foreseeable uses of the components or systems.
This equipment is intended to be operated indoors and is designed to produce high purity nitrogen gas from a supply of clean dry compressed air. Please refer to the technical specification for pressure, temperature, and compressed air requirements.
Do not connect liquids or gases or to the inlet port of this generator.
Use of the equipment in a manner not specified within this user guide may result in an unplanned release of pressure, which may cause serious personal injury or damage.
Only competent personnel trained, qualified, and approved by Parker domnick hunter should perform installation, commissioning, service and repair procedures.
When handling, installing or operating this equipment, personnel must employ safe engineering practices and observe all related regulations, health & safety procedures, and legal requirements for safety.
Ensure that the equipment is depressurised and electrically isolated, prior to carrying out any of the scheduled maintenance instructions specified within this user guide.
Note: Any interference with the calibration warning labels will invalidate the gas generator’s warranty and may incur costs for the re-calibration of the gas generator.
Parker domnick hunter can not anticipate every possible circumstance which may represent a potential hazard. The warnings in this manual cover the most known potential hazards, but by definition can not be all-inclusive. If the user employs an operating procedure, item of equipment or a method of working which is not specifically recommended by Parker domnick hunter the user must ensure that the equipment will not be damaged or become hazardous to persons or property.
Most accidents that occur during the operation and maintenance of machinery are the result of failure to observe basic safety rules and procedures. Accidents can be avoided by recognising that any machinery is potentially hazardous.
Details of your nearest Parker domnick hunter sales office can be found at www.parker.com/dhfns
Retain this manual for future reference.
Page 6
4 - EN
1.1 Markings and Symbols
The following markings and international symbols are used on the equipment or within this manual:
1.2 Personnel Definitions
Operator - person operating equipment for its intended purpose. No access to the internal compartment of the generator.
Responsible Body - individuals or group responsible for the safe use and maintenance of equipment. Access into the internal compartment of
the generator is restricted to key holders only.
Service Personnel - individuals or group that have been trained, or are qualified and approved, by Parker domnick hunter to perform installation, commissioning, service and repair procedures.
Caution, Read the User Guide. Wear ear protection
Risk of electric shock. Pressurised components on the system
Highlights actions or procedures which, if not performed correctly, may lead to personal injury or death.
Remote control. The generator may start automatically without warning.
Highlights actions or procedures which, if not performed correctly, may lead to damage to this product.
Conformité Européenne
Highlights actions or procedures which, if not performed correctly, could lead to electric shock.
When disposing of old parts always follow local waste disposal regulations.
Use a fork lift truck to move the dryer.
If remote fault indication relay is used, the electrical enclosure will now contain more than one live circuit and in the event of the mains supply being disconnected, the fault relay connections will remain live.
NITROGEN (N2) NITROX DO NOT BREATHE Asphyxiant in high concentrations. No odour. Slightly lighter than air. Ensure adequate ventilation. Breathing 100% nitrogen will produce immediate unconsciousness and death due to lack of oxygen.
NON-FLAMMABLE COMPRESSED GAS
Waste electrical and electronic equipment should not be disposed of with municipal waste.
MAX PRESSURE
10barg (145psi)
NITROX
NITROGEN (N2)
GAS
NON-FLAMMABLE
DONOT BREATHE
COMPRESSED
USE ONLY WITH EQUIPMENT COMPATIBLE
WITH THIS PRESSURE
Asphyxiant in high concentrations. No odour Slightly lighter than air. Ensure adequate ventilation. Breathing 100% nitrogen will produce immediate unconsciousness and death due to lack of oxygen.
Page 7
5 - EN
1.2.1 Generator Model Number Identification
The model number can be found on the rating plate as illustrated.
Model No:
N2 8 0 P A L N
Model
20
25
35
45
55
60
65
75
80
Technology
P = Pressure Swing Adsorption
O2 Purity
X = Ultra High Purity (10 ppm)
A = High Purity (50 - 1000ppm)
B = Low Purity (0.5 - 5%)
Flow
L = Low Flow
M = Medium Flow
H = High Flow
Energy Saving Technology (EST)
N = No
Y = Yes
Page 8
6 - EN
2 Description
The NITROSource PSA range of nitrogen generators operate on the Pressure Swing Adsorption (PSA) principle to produce a continuous stream of nitrogen gas from clean dry compressed air.
Pairs of dual chamber extruded aluminium columns, filled with Carbon Molecular Sieve (CMS), are joined via an upper and lower manifold to produce a two bed system. Whilst one bed is online and removing oxygen from the process air the other is regenerated.
Clean, dry particulate free compressed air enters the bottom of the online bed and flows up through the CMS. Oxygen and other trace gases are preferentially adsorbed by the CMS, allowing nitrogen to pass through. At the end of this adsorption phase the inlet, outlet and exhaust valves close on both beds. The upper and lower equalisation valves open, allowing the pressure to equalise between the beds. This equalisation phase is designed to reduce energy consumption and enhance the overall performance of the generator.
Once equalised the bed entering regeneration is depressurised. The oxygen adsorbed during the adsorption phase is vented to atmosphere via an exhaust valve and silencer. A small proportion of the outlet nitrogen gas is also expanded into this bed to help the desorption of oxygen from the CMS.
The bed entering the adsorption phase is pressurised using a controlled flow of nitrogen gas from the nitrogen buffer vessel (Back Fill) and a controlled flow of clean, dry, particulate free compressed air (Front Fill).
The CMS beds alternate between adsorption and regeneration modes to ensure continuous and uninterrupted nitrogen production.
2.1 Technical Specification
Product Selection
NITROSource PSA Performance @ 20 oC (68 oF)Ambient Air Temperature & 7 barg (101.5 psi g) Air inlet pressure
Model 5 ppm 10ppm 50ppm 100ppm 250ppm 500ppm 0.10% 0.40% 0.50% 1% 2% 3% 4% 5%
N2-20P
m3/hr
3.5 4.5 6.7 8.0 9.7 11. 1 12.4 16.7 17.7 21.3 25.3 29.8 30.9 33.7
CFM
2.1 2.6 3.9 4.7 5.7 6.5 7.3 9.8 10.4 12.5 14.9 17.5 18.2 19.8
N2-25P
m3/hr
5.3 6.8 10.1 12.0 14.6 16.7 18.6 25.1 26.6 32.0 38.0 44.7 46.4 50.6
CFM
3.1 4.0 5.9 7.1 8.6 9.8 10.9 14.8 15.7 18.8 22.4 26.3 27.3 29.8
N2-35P
m3/hr
7.0 9.0 13.4 16.0 19.4 22.2 24.8 33.4 35.4 42.6 50.6 59.6 61.8 67.4
CFM
4.1 5.3 7.9 9.4 11. 4 13.1 14.6 19.7 20.8 25.1 29.8 35.1 36.4 39.7
N2-45P
m3/hr
8.8 11. 3 16.8 20.0 24.3 27.8 31.0 41.8 44.3 53.3 63.3 74.5 77.3 84.3
CFM
5.2 6.7 9.9 11. 8 14.3 16.4 18.2 24.6 26.1 31.4 37.3 43.8 45.5 49.6
N2-55P
m3/hr
10.5 13.5 20.1 24.0 29.1 33.3 37.2 50.1 53.1 63.9 75.9 89.4 92.7 101.1
CFM
6.2 7.9 11 .8 14.1 17.1 19.6 21.9 29.5 31.3 37.6 44.7 52.6 54.6 59.5
N2-60P
m3/hr
11. 6 15.0 22.3 26.6 32.3 36.9 41.2 55.5 58.9 70.8 84.1 99.1 102.7 112 .1
CFM
6.8 8.8 13.1 15.7 19.0 21.7 24.2 32.7 34.7 41.7 49.5 58.3 60.4 66.0
N2-65P
m3/hr
13.3 17.1 25.5 30.4 36.9 42.2 47.1 63.5 67.3 80.9 96.1 113.2 117. 4 128.1
CFM
7.8 10.1 15.0 17.9 21.7 24.8 27.7 37.4 39.6 47.6 56.6 66.6 69.1 75.4
N2-75P
m3/hr
14.5 18.6 27.7 33.1 40.2 46.0 51.3 69.1 73.3 88.2 104.7 123.4 127.9 139.5
CFM
8.5 10.9 16.3 19.5 23.7 27.1 30.2 40.7 43.1 51.9 61.6 72.6 75.3 82.1
N2-80P
m3/hr
16.1 20.7 30.8 36.8 44.6 51.1 57.0 76.8 81.4 98.0 116.4 137.1 142.1 155.0
CFM
9.5 12.2 18.1 21.7 26.3 30.1 33.5 45.2 47.9 57.7 68.5 80.7 83.6 91.2
Air : N2
(N2-20 - N2-55)
9.3 7.2 5.1 4.6 4.1 3.7 3.4 2.9 2.8 2.6 2.3 2.2 2.2 2.1
Air : N2
(N2-60 - N2-65)
9.8 7.6 5.3 4.9 4.3 3.9 3.5 3.0 2.9 2.7 2.5 2.3 2.3 2.2
Air : N2
(N2-75 - N2-80)
10.1 7.8 5.5 5.0 4.4 4.0 3.7 3.1 3.0 2.8 2.5 2.4 2.4 2.3
Outlet
Bar g
6.0 6.0 6.0 6.0 5.9 5.9 5.8 5.8 5.7 5.7 5.6 5.5 5.4 5.4
Psi g
87.0 87.0 87.0 87.0 85.6 85.6 84.1 84.1 82.7 82.7 81.2 79.8 78.3 78.3
Page 9
7 - EN
2.2 Approvals and Compliance
2.2.1 Approvals
Directives
97/23/EC: Pressure Equipment Directive
2004/108/EC: Electromagnetic Compatibility Directive
2006/95/EC: Low Voltage Directive
Safety and Electromagnetic Compatibility Standards
This equipment has been tested and complies with the following European Standards:
EN 61326-1:2013 EMC - Electrical equipment for measurement, control and laboratory use. EMC requirements. (Equipment tested to: Emissions - Light, Immunity - Heavy)
BS EN 61000-3-2:2006+A2:2009 Electromagnetic compatibility (EMC). Limits for harmonic current emissions (equipment input current = 16 A per phase)
BS EN 61000-3-3:2013 Electromagnetic compatibility (EMC). Limits. Limitation of voltage changes, voltage fluctuations and flicker in public low­voltage supply systems, for equipment with rated current = 16 A per phase and not subject to conditional connection.
BS EN 61010-1:2010 Safety requirements for electrical equipment for measurement, control, and laboratory use. General requirements
General
Designed generally in accordance with ASME VIII DIVISION 1: EDITION 2010 2011a Addenda
2.2.2 Compliance
This gas generator is compliant with FDA and European Pharmacopeia Regulations for use as a medical gas generator.
Inlet Parameters
Port Connections
Environmental Parameters
Air Quality
ISO 8573-1: 2010 Class 2.2.2
(2.2.1 with high oil vapour content)
Pressure
5 –13 bar g (72.5 - 188.5) psi g
Temperature
5 – 50 oC (41 – 122 oF)
Purity
20.948% (wrt O2)
0.0314% (wrt CO2)
Air Inlet
G1”
N2 Outlet to Buffer
G1”
N2 Inlet from Buffer
G1/2”
N2 Outlet
G1/2”
Ambient Temperature
5 – 50 oC
(41 – 122
o
F)
Humidity
50% @ 40oC (80% @ MAX d 31oC)
IP Rating
IP20 / NEMA 1
Pollution Degree
2
Installation Category
II
Altitude
< 2000 m
(6562 ft)
Noise
<80 dB (A)
Electrical Parameters Packed Weights and Dimensions
Generator Supply
(1)
(1) The generator does not require adjustment when connecting to 115v and 230v
electrical supplies.
100 - 240 +/- 10% Vac 50/60Hz
Generator Power
(2)
(2) The power rating specified is for the generator alone and does not take in to
account any pre-treatment dryer connected to the dryer supply terminals of the generator.
55 W
Fuse
(3)
(3) (Anti Surge (T), 250v, 5 x 20mm HBC, Breaking Capacity 1500A @ 250v, IEC 60127,
UL R/C Fuse).
3.15 A
Max Dryer Power
(4)
(4) The dryer is fed directly from the generator supply.
100W
Model
Height (H) Width (W) Depth (D) Weight
mm ins mm ins mm ins Kg lbs
N2-20P
725.5 28.6
1994 78.5
1090 42.9 398.4 878.3
N2-25P
1260 49.6 495.4 1092.1
N2-35P
1430 56.3 580.4 1279.6
N2-45P
1600 63.0 686.4 1513.3
N2-55P
825.5 32.5
1770 69.7 782.4 1724.9
N2-60P
1935 76.2 897.4 1978.4
N2-65P
828.5 32.6 2100 82.7 997.4 2198.9
N2-75P
831.5 32.7
2275 89.6 1093.4 2410.5
N2-80P
2445 96.3 1186.4 2615.6
Page 10
8 - EN
2.3 Weights and Dimensions
2.4 Materials of Construction
Model
Dimension
Weight
H W D (a) (b) (c) (d) (e) (f) (g)
mm in s mm ins mm ins mm ins mm ins mm ins mm ins mm ins mm ins mm ins Kg lbs
N2-20P
1894 74.6 550 21.7 893 35.2 500 19.7 535.5 21.1 350 13.8 853.5 33.6 1007 39.6 1271 50 1739 68.5 299 659.2
N2-25P
1894 74.6 550 21.7 1062 41.8 500 19.7 704.5 27.7 350 13.8 853.5 33.6 1007 39.6 1271 50 1739 68.5 384 846.6
N2-35P
1894 74.6 550 21.7 1231 48.5 500 19.7 873.5 34.4 350 13.8 853.5 33.6 1007 39.6 1271 50 1739 68.5 469 1034.0
N2-45P
1894 74.6 550 21.7 1400 55.1 500 19.7 1042.5 41.0 350 13.8 853.5 33.6 1007 39. 6 1271 50 1739 68.5 553 1219.2
N2-55P
1894 74.6 550 21.7 1569 61.8 500 19.7 1211.5 47.7 350 13.8 853.5 33.6 1007 39. 6 1271 50 1739 68.5 638 1406.5
N2-60P
1894 74.6 550 21.7 1738 68.4 500 19.7 1380.5 54.4 350 13.8 853.5 33.6 1007 39. 6 1271 50 1739 68.5 722 1591.7
N2-65P
1894 74.6 550 21.7 1907 75.1 500 19.7 1549.5 61.0 350 13.8 853.5 33.6 1007 39. 6 1271 50 1739 68.5 807 1779.1
N2-75P
1894 74.6 550 21.7 2076 81.7 500 19.7 1718.5 67.7 350 13.8 853.5 33.6 1007 39. 6 1271 50 1739 68.5 892 1966.5
N2-80P
1894 74.6 550 21.7 2245 88.4 500 19.7 1887.5 74.3 350 13.8 853.5 33.6 1007 39. 6 1271 50 1739 68.5 976 2151.7
Silencer Baffle and End Cap
Aluminium
Columns, Manifolds and Exhaust Manifolds
Aluminium Extrusion EN AW-6063 T6
Manifold and Purge End Plates
Cast Machined EN AW-6082 T6
Inlet, Outlet and Equalisation Valve Plates
Machined EN AC-44100-F
Inlet and Exhaust Cylinders
Aluminium Alloy
Generator Feet
8MM Steel Plate
Dust Filter
Aluminium Housing
Fittings
Nickel Plated Brass and Nickle Plated Mild Steel
Pressure Gauges
Steel casing and dial, brass connector and movement
Adsorbant
Carbon Molecular Sieve (CMS)
Seal Materials
Nitrile, Viton, EPDM, PTFE (tape)
Paint
Epoxy coated
(b)
(a)
(d)
(c)
(e)
(f)
(g)
W
H
D
Page 11
9 - EN
2.5 Receiving and Inspecting the Equipment
The equipment is supplied in a sturdy wooden crate designed to be moved using a forklift truck or pallet truck. Refer to the technical specification for packed weights and dimensions. On delivery of the equipment check the crate and its contents for damage and verify that the following items have been included with the generator.
If there are any signs of damage to the crate, or there are any parts missing please inform the delivery company immediately and contact your local Parker domnick hunter office.
2.5.1 Storage
The equipment should be stored, within the packing crate, in a clean dry environment. If the crate is stored in an area where the environmental conditions fall outside of those specified in the technical specification, it should be moved to its final location (installation site) and left to stabilise prior to unpacking. Failure to do this could cause condensing humidity and potential failure of the equipment.
2.5.2 Unpacking
Remove the lid and all four sides of the packing crate. Unscrew the exhaust silencer from the generator and lift the generator on to it’s feet using suitable slings and an overhead crane as illustrated.
Remove the four wooden blocks from behind the shroud.
Once positioned in its final location refit the silencer to the generator.
Ref Description Qty
1 Pilot operated regulator 1
2 Pilot regulator 1
3 Dust filter 1
4 1/2” ball valve (N2 inlet from buffer vessel) 1
5 1” BSPP ball valve (N2 Outlet to buffer vessel) 1
6 1/2” 3-way ball valve (N2 Outlet) 1
7 1” BSPP ball valve (Compressed Air Inlet) 1
Page 12
10 - EN
2.6 Overview of the equipment
Key:
Note. The pressure gauges are for indication only. Items #1, #4, #5, and #6 are available on both sides of the generator.
Ref Description Ref Description
1 Outlet Port: To Buffer Vessel 7 User control interface with 20 x 2 line menu display
2 Cable glands 8 Exhaust silencer
3 Pressure gauges 9 Oxygen Dependant Switching (EST) Sensor (if fitted)
4 Inlet Port: From Buffer Vessel 10 Oxygen Sensor
5 Outlet Port: Nitrogen Outlet 11 4 - 20mA Cable gland
6 Inlet Port: Compressed Air Inlet with Pressure Regulator (supplied) 12 Calibration port
Page 13
11 - E N
3 Installation and Commissioning
3.1 Recommended System Component Layout
3.1.1 Compressed air pre-treatment
To achieve the maximum performance, reliability and service life, Parker domnick hunter strongly recommend the use of a Parker domnick hunter desiccant dryer based pre-treatment package.
A Parker domnick hunter Desiccant dryer pretreatment package provides a physical barrier to oil, ensures maximum generator efficiency by minimising Carbon Molecular Sieve (CMS) moisture loading and is in full compliance with the Parker 5 year warranty program.
Some applications such as pharmaceutical and food require nitrogen moisture contents that are only achievable with a desiccant dryer based pre-treatment package.
PPM generators must be operated with a Parker domnick hunter desiccant dryer based pre-treatment package.
This generator will operate with a refrigerant type dryer providing it is correctly maintained and achieves a constant pdp of +3°C, however this is the least preferred option as this type of dryer provides a inimal barrier to oil carry-over and should be strongly discouraged. It must be used in conjunction with an activated carbon Oil Vapour Removal (OVR) filter.
In certain circumstances it may also be necessary to install an OVR filter after the desiccant dryer pre-treatment package.
Note. Any contamination of the CMS due to oil or excess moisture loading will invalidate the warranty.
If in any doubt, consult your local Parker specialist for further information.
Installation should be performed by Service Personnel only.
Ref Description Ref Description
1
Compressor
(1)
(1) If using an oil lubricated compressor we recommend the use of oil vapour removal filtration.
6 Dust filter
2 Wet air receiver complete with pressure relief valve and gauge 7 Buffer vessel
3 Water separator 8 Dust filter (supplied with the generator)
4 General purpose and dust filtration 9 Nitrogen generator
5 Compressed air dryer 10 Nitrogen Outlet to application
The system must be protected with a suitably rated thermal pressure relief valve upstream of the generator.
Page 14
12 - EN
3.2 Locating the Equipment
3.2.1 Environment
The equipment should be located indoors in an environment that protects it from direct sunlight, moisture, and dust. Changes in temperature, humidity, and airborne pollution will affect the environment in which the equipment is operating and may impair the safety and operation. It is the customers' responsibility to ensure that the environmental conditions specified for the equipment are maintained.
3.2.2 Space Requirements
The equipment should be mounted on a flat surface capable as a minimum of supporting its own weight plus the weight of all ancillary parts. The minimum footprint requirements are specified below, however there must be adequate space around the equipment to allow airflow and access for maintenance purposes and lifting equipment. A minimum spacing of approximately 500mm (20 ins) is recommended around all sides of the generator and 1000mm (39.4 ins) above it to allow service operations.
Do Not position the equipment so that it is difficult to operate or disconnect from the electrical supply.
3.2.3 Air Inlet Quality
ISO 8573-1:2010 is an international standard that specifies the purity classes of compressed air with respect to solid particulates, water and oil. The air inlet quality specified for this generator is ISO 8573-1:2010 class 2.2.2 and equates to the following:
Class 2 (Solid Particulate)
In each cubic metre of compressed air, not more than:
400,000 particles in the 0.1–0.5 micron size range are allowed.
6,000 particles in the 0.5–1 micron size range are allowed.
100 particles in the 1–5 micron size range are allowed.
Class 2 (Water)
A pressure dewpoint of -40
o
C/-40oF or better is required and no liquid is allowed.
Class 2 (Oil)
In each cubic metre of compressed air, not more than 0.1 mg of oil is allowed.
Note. This is the combined level for aerosol, liquid and vapour.
ISO 8573-1:2010 Class 2.2.2 can be achieved with the following combination of Parker purification products:
General Purpose filter Grade AO
High efficiency filter grade AA
ACS / OVR Adsorption Filter
General Purpose Dust removal Filter Grade AR
PNEUDRI -40
o
C/-40oF PDP dryer
Due to the nature of operation there is a possibility of oxygen enrichment surrounding the generator. Ensure that the area is adequately ventilated. Where the risk of oxygen enrichment is high, such as a confined space or poorly ventilated room, the use of oxygen monitoring equipment is advisable.
Page 15
13 - EN
3.3 Mechanical Installation
3.3.1 General Requirements
Please familiarise yourself with the local regulations before considering any pipe-work installation as standards and specifications for pipe-work systems can vary greatly from country to country. The information below is a guide based on installations performed within Europe.
Nitrogen, besides being inert, is also widely used because it is considered a clean dry gas.
Many of the processes that use nitrogen are of a critical nature and apart from contamination with oxygen, the removal of dirt particulate, oil and water vapour from the gas stream is also essential. Therefore the pipe-work system and material that will transfer the nitrogen to it’s destination should not add any unwanted contamination into the gas stream.
All components used within the system must be rated to at least the maximum operating pressure of the equipment. Buffer and nitrogen storage vessels should be clean and free from oil and grease, and fitted with a suitable pressure gauge and pressure relief valve.
If there is any possibility of particulate contamination then this can be removed by installing a suitable Oil-X Evolution filter as near to the point of use as possible. Ensure that each filter condensate drain is suitably piped away and any effluent is disposed of in accordance with local regulations.
The compressed air feed pipe-work to the pre-treatment package should be suitable for compressed air duty and of a size and construction to handle the maximum flow and pressures involved. Materials such as medium weight galvanized, Transair or similar are acceptable. As much cutting fluid, oil and grease as possible should be removed from the pipe-work and fittings prior to connecting.
From the pre-treatment onwards and for the nitrogen gas, the pipe-work needs to be clean and oil-free.
If using a modular pipe-work system such as Transair, oil and grease should be removed using a suitable cleaner (if necessary) from the surfaces that come into contact such as the pipe-work including fittings.
The most commonly used material for installing nitrogen pipe-work is table “X” de-greased copper. This should be silver soldered with a nitrogen purge where ever possible and for threaded interfaces general heavy duty (GHD) fittings should be used. For small bore pipe-work, it is sometimes acceptable to use compression type fittings or crimp type pipe-work systems. For food and pharmaceutical installations, welded or threaded stainless steel is often specified, especially where it enters the production environment. For these market sectors the inclusion of sterile filtration such as the “High Flow BIO-X” is advisable to ensure even the remote possibility of contamination from microorganisms is prevented.
In general flexible hoses should be avoided. They are almost certainly not suitable for high purity <100 ppm applications.
However, if they are to be used, ensure they are suitable for use with an inert gas. Certain materials such as nylon tubing can actually permeate oxygen from outside to inside and affect the purity of the nitrogen gas. PTFE flexible tubing is preferred.
When routing the pipes ensure that they are adequately supported to prevent damage and leaks in the system.
The diameter of the pipes must be sufficient to allow unrestricted inlet air supply to the equipment and outlet nitrogen supply to the application. The following table gives guidance on the maximum recommended flow rates for smooth bore pipe-work.
The system must be protected with a suitably rated thermal pressure relief valve upstream of the generator.
Pressure
4 bar g 58 psi 6 bar g 87 psi 8 bar g 116 psi 10 bar g 145 psi
Recommended Flowrate
m3/hour
cfm
m3/hour
cfm
m3/hour
cfm
m3/hour
cfm
Pipe size I/D (or Equivalent)
16mm
28.8 17.0 43.2 25.4 64.8 38.1 75.6 44.5
20mm
36.6 21.5 57.6 33.9 82.8 48.7 101.0 59.4
25mm
68.4 40.3 111 .0 65.3 155.0 91.2 194.0 114 .2
32mm
152.0 89.5 227.0 133.6 295.0 173.6 385.0 226.6
40mm
306.0 180.1 432.0 254.3 576.0 339.0 702.0 413.2
50mm
440.0 259.0 698.0 410.8 940.0 553.3 1213.0 713.9
63mm
824.0 485.0 1318.0 775.7 1771.0 1042.4 2326.0 1369.0
75mm
1296.0 762.8 2034.0 1197.2 2847.0 1675.7 3510.0 2065.9
90mm
2052.0 1207.8 3186.0 1875.2 4576.0 2693.3 5490.0 3231.3
110mm
3600.0 2118.9 5652.0 3326.6 7956.0 4682.7 9756.0 5742.2
Page 16
14 - EN
3.3.2 Securing the Generator
3.3.3 Making the Connections
Refer to the “Recommended System Component Layout” on page 11 for the desired system configuration.
Port connections are provided on both sides of the generator. Connect the ball valves supplied to the ports, using PTFE tape on the threads to provide a leak free seal.
Assemble the inlet pressure regulator as illustrated below taking note of the flow directions marked on the underside of the pilot operated regulator.
Use PTFE tape on the threads to provide a leak free seal.
Note. Fittings are not supplied.
When installing the 3-way ball valve to the Nitrogen Outlet port ensure that it is positioned in a vertical position and so that there is unrestricted access to the centre port for the connection of a flow meter.
Install the pipe-work ready for connection to the buffer vessel and compressed air supply. We recommend that additional ball valves are connected to the buffer vessel ports to allow it to be isolated during maintenance activities.
Setting the inlet Pressure Regulator
The inlet pressure must be set prior to running the generator.
1 Adjust the internal Inlet / Outlet pressure ball valve to the Inlet
Pressure position (pointing down).
2 Power up the generator and navigate to menu 3.5. The inlet
compressed air pressure will be displayed.
3 Check the rating plate for the required set pressure then adjust the regulator until the required set pressure is displayed on menu 3.5.
4 Tighten the lock nut on the regulator adjustment handle to prevent inadvertent adjustment.
5 Reposition the internal Inlet / Outlet pressure ball valve to the Outlet Pressure position (pointing upwards).
The generator MUST be fixed in position using suitable M20x40mm Rawl bolts (or equivalent). Mounting holes are provided in the feet of the generator.
1
Mounting holes
2
Inlet Port: Compressed Air Inlet (1” BSPP ball valve)
3
Inlet Pressure Regulator
4
Outlet Port: Nitrogen Outlet (1/2” 3-way ball valve)
5
Inlet Port: From Buffer Vessel (1/2” ball valve)
6
Outlet Port: To Buffer Vessel (1” BSPP ball valve)
7
Internal inlet / outlet pressure ball valve
1” BSPP
1/4” BSPP
Page 17
15 - EN
3.4 Electrical Installation
3.5 General Requirements
In order to maintain the IP rating of the generator, all cables entering the electrical enclosure must do so through the dedicated cable glands located on the side of the generator. All cables used must be sized such that the voltage drop between the supply and the load does not exceed 5% of the nominal voltage under normal conditions. All cables external to the generator must be adequately supported and protected against physical damage.
When connecting to terminal blocks always ensure that the conductors are fully inserted into the terminal, and the terminal screws are firmly secured. We recommend that individual conductors are cable tied together so that, in the event of on conductor coming loose, they cannot touch other parts.
3.6 Customer Connections
Please refer to the wiring schematic at the rear of this guide for wiring details.
3.6.1 Generator Mains Voltage Supply
The generator requires a 100 - 240Vac single phase electrical supply in accordance with local wiring regulations. Refer to the technical specification for voltage and frequency tolerances.
Connection to the electrical supply should be made through a switch or circuit breaker rated at 250VAC, 6A with a minimum short circuit rating of 10KA. All of the current carrying conductors should be disconnected by this device. This protection should be selected in accordance with local and national code regulations.
The device chosen should be clearly and indelibly marked as the disconnecting device for the equipment and be located in close proximity to the equipment and within easy reach for the operator.
Over current protection must be fitted as part of the building installation. This protection should be selected in accordance with local and national code regulations with a minimum short circuit rating of 10KA.
The protective earth conductor should be longer than the associated phase conductors so that in the event of the cable slipping in the cable gland, the earth will be the last to take the strain.
Note. If using flexible cable please ensure that it conforms to the requirements of IEC60227 or IEC60245.
A fully qualified electrical engineer must undertake all field wiring and electrical work in accordance with local regulations.
Ter mi nal s Description
Minimum Conductor Size
Cable size
TB1 - L1
Fuse terminal for the phase conductor
1mm
2
8 - 12mm
TB1 - N
Neutral conductor
TB1 -
Earth conductor
1 Cable Entry Glands
2 Generator Supply Terminals
3 Dryer Supply Terminals
4 Purge Economy Terminals (JP17)
5 Alarm Contact Terminals
6 Remote Switching Terminals
6mm
0.2ins
Page 18
16 - EN
3.6.2 Dryer Supply
If a Parker domnick hunter pre-treatment air dryer is used, it should be connected to the generator at the dedicated DIN rail terminals. Refer the documentation provided with your dryer for additional information on installation requirements.
3.6.3 Purge Economy
If the pre-treatment dryer is fitted with a purge economy feature, it may be controlled using the volt free relay contacts on JP17. The relay is energised only when the generator enters standby mode. Refer to the documentation provided with your dryer for details on purge economy.
3.6.4 Alarm Contacts
Each generator is fitted with a set of volt free relay contacts designed for remote alarm indication and are rated 1A max @ 250Vac (1A @ 30Vdc). Under normal operation the relay will be energised and the alarm circuit will be open. When a fault occurs, e.g. power failure, the relay will de­energise causing the alarm circuit to be complete.
3.6.5 Remote Switching
The generator may be controlled remotely by connecting a remote start / stop circuit to digital input #4 on the control board. When the circuit is open the generator should remain in standby mode, closing the circuit should initiate a start command.
To enable the remote switching function refer to 4.4.3 of this guide. Once the remote switching function has been enabled the local start control will no longer function.
Ter mi nal s Description Cable size
TB1 - L1
Live conductor
3 - 7mm
TB1 - N
Neutral conductor
TB1 -
Earth conductor
Do Not connect mains electricity to the Purge Economy Terminals.
Ter mi nal s Description Cable size
JP17 - 2
Common
3 - 7mm
JP17 - 3
Normally Open
Ter mi nal s Description Cable size
JP18 - 1
Normally closed
3 - 7mm
JP18 - 2
Common
JP18 - 3
Normally open
If remote fault indication relay is used, the electrical enclosure will now contain more than one live circuit and in the event of the mains supply being disconnected, the fault relay connections will remain live.
Ter mi nal s Description Cable size
JP19 - 7
Common
3 - 7mm
JP19 - 8
Normally Open
When the remote switching function is enabled the generator can start without warning.
Page 19
17 - EN
3.6.6 4–20mA Analogue Output
The oxygen content detected by the generators internal analyser may be re-transmitted to external peripherals using the 4-20mA linear analogue output. The output is a linear current source, with 10 bit resolution, which increases from 4mA (Zero Oxygen) to 20mA (Full Scale Deflection). The FSD of the internal analyser is factory set to a default value of twice the generators specified purity. For % purity generators the maximum FSD is set to 6%. The oxygen purity setting of the generator is marked on the rating plate. The table below shows the correlation between the purity settings of the generator and the output current.
It is recommended that the cable used for the 4-20mA Analogue Output is screened twisted pair. Ferrites should be added to the cable, using 1 turn, either side of the shroud cable gland. It is recommended that the cable used does not exceed 30m in length. Suitable ferrites are available from Wurth Electronics (P/N. 74271633S).
3.6.7 MODBUS
The generator’s controller is capable of supporting direct Modbus communication via its integral RS485 connection. This industry standard connection allows multiple generators to communicate with a remote Modbus master on a network up to 30m in length. The generator can be programmed with its own unique address, to allow multiple generators to be connected to an existing network.
Ter mi nal s Description Cable size
Analyser - #6
Positive
3 - 7mm
Analyser - #7
Negative
Generator Purity
Full Scale Deflection
Resolution
4mA - 20mA
5ppm 0 - 10ppm 1ppm = 1.6mA
10ppm 0 - 20ppm 1ppm = 0.8mA
50ppm 0 - 100ppm 1ppm = 0.16mA
100ppm 0 - 200ppm 1ppm = 0.08mA
250ppm 0 - 500ppm 1ppm = 0.032mA
500ppm 0 - 1000ppm 1ppm = 0.016mA
0.1% 0 - 0.2% 0.01% = 0.8mA
0.4% 0 - 0.8% 0.01% = 0.2mA
0.5% 0 - 1% 0.01% = 0.16mA
1% 0 - 2% 0.01% = 0.08mA
2% 0 - 4% 0.01% = 0.04mA
3% 0 - 6% 0.01% = 0.026mA
4% 0 - 6% 0.01% = 0.026mA
5% 0 - 6% 0.01% = 0.026mA
Ter mi nal s Description Cable size
RS485 MODBUS - A
For MODBUS communication setup details refer to dh publication 176500120
3 - 7mm
RS485 MODBUS - A
Page 20
18 - EN
4 Operating the Generator
4.1 Overview of the Controls
4.2 Starting the generator
1 Inspect all of the system connection points and verify that they are secure.
2 With both the inlet and outlet ball valves of the buffer vessel closed, open the ball valve on the air inlet port to allow the compressed air into
the generator.
3 Switch the electrical power on to the generator and wait whilst it runs through the controller initialisation routine.
4 If the generator was in standby mode when the electrical power was removed it will default to standby
mode on completion of the initialisation routine.
5 Press to initiate the start up routine.
If the start clean up option is enabled the generator will run through the Rapid Cycle before opening the buffer valve and the N2 outlet valve. The clean up cycle, which takes approximately 160 seconds, is designed to clean the CMS bed of impurities, bring the generator up to production purity more rapidly, and prevent poor quality gas flowing into the buffer.
If the generator was running when the electrical power was removed (e.g. power failure) it will automatically run through a start up cycle (if enabled) and then commence normal operation. Wait until this cycle is complete and the menu displays “Running”. This may take several minutes for ppm generators.
6 Partially open the ball valve on the inlet to the buffer vessel to allow it to pressurise slowly. When the pressure gauge on the buffer vessel
reads within 0.5 barg (7psig) of the inlet pressure, check for leaks in the buffer vessel inlet piping and then fully open the ball valve.
7 Open the ball valve on the outlet of the buffer vessel and check for leaks in the piping between the vessel and the generator.
8 Open the ball valve on the Nitrogen outlet.
Note: If the purity of the gas is not within specification it will be vented to atmosphere through a vent solenoid within the generator and not
delivered to the application. When the required purity is achieved the gas will be delivered to the application.
O2 = 5.00% Shutting Down
Standby Standby
O2 = 5.00% O2 = 5.00% Rapid Cycle Rapid Cycle
1
Star t K ey
2
Stop Key
3
Menu navigation keys
4
Enter key
5
Operating status indicator
Green = Running, Yellow = Starting up / Shutting down Red - Standby
6
Economy / EST status indicator
Green = Economy or EST Mode
7
Service / Fault indicator
Yellow = Service due Red = Fault
8
LCD Display
Page 21
19 - EN
4.3 Stopping the generator
1 Close the ball valve on the N2 Outlet port.
2 Press to initiate the shutting down sequence.
The generator will complete the current cycle and then exhaust both beds. This may take several minutes particularly on ppm generators.
3 When the generator is depressurised it will revert to standby mode.
4.4 Menu Interface
All of the operational parameters and data are accessed through the menu driven interface..
The interface will automatically default back to the main operating menu if no key activity has been detected for one minute.
Note: After an additional two minutes of inactivity the display will darken. To brighten the display press .
O2 = 5.00% O2 = 5.00% Shutting Down Shutting Down
Shutting Down Shutting Down
Standby Standby
O2 = 5.00%
O2 = 5.00%
Shutting Down
Shutting Down
1. Hour meters
1. Hour meters
2. Fault log
2. Fault log
2.1 Fault 10:
2.1 Fault 10:
[---]
[---]
2.1 Fault 1: Active
2.1 Fault 1: Active
C1 at 5234h
C1 at 5234h
3. Customer
3. Customer
settings
settings
3.16 EST enable
3.16 EST enable
= 0
= 0
3.15 Modbus parity
3.15 Modbus parity
= Even
= Even
3.14 Remote control
3.14 Remote control
= 1
= 1
3.13 Machine number
3.13 Machine number
= 1
= 1
3.12 Fault relay
3.12 Fault relay
On Stop =1
On Stop =1
3.11 Economy enable
3.11 Economy enable
= 1
= 1
3.10 Start cycle
3.10 Start cycle
enable = 1
enable = 1
3.9 Oxygen Analogue
3.9 Oxygen Analogue
FSD =6%
FSD =6%
3.8 Oxygen alarm
3.8 Oxygen alarm
delay = 60s
delay = 60s
3.7 Oxygen alarm
3.7 Oxygen alarm
level =15ppm
level =15ppm
3.6 Pressure units
3.6 Pressure units
= Bar
= Bar
3.5 Pressure reading
3.5 Pressure reading
= 9Bar
= 9Bar
3.4 Calibrate EST
3.4 Calibrate EST
sensor
sensor
3.3 Calibrate outlet
3.3 Calibrate outlet
sensor
sensor
3.2 Oxygen Alarm
3.2 Oxygen Alarm
Over-ride =0
Over-ride =0
3.1 Password enable
3.1 Password enable
= 0
= 0
1.4 Hours EST
1.4 Hours EST
4h
4h
1.3 Hours economy
1.3 Hours economy
25h
25h
1.2 Service due at
1.2 Service due at
8000h
8000h
1.1 Hours Run
1.1 Hours Run
5234h
5234h
+
+
Page 22
20 - EN
4.4.1 Hour Meters
There are four hour meters available for viewing:
4.4.2 Fault Log
The fault log menu allows the user to access the 10 most recent fault messages.
Refer to “Fault Codes” on page 27 for a full listing of fault codes.
4.4.3 Customer Settings
To prevent unauthorised access to the configurable parameters, the customers setting menu has optional password protection. This is disabled by default and can be enabled in menu 3.1
To gain access in to this menu, when password has been enabled:
Press and hold both the and keys for approximately 5 seconds until the menu changes to the password prompt as shown.
The flashing cursor will be positioned over the first digit. Using the key change the first digit of the code and press . The cursor will move to the next digit.
Repeat the process and enter the following password 1 2 1 _ _ . When the password has been entered correctly the Hour Meters menu will be displayed. Use the key to navigate to page 3 “Customer Settings” menu and press .
The time in hours that the generator has been producing gas.
The time in operating hours that the generator can produce gas before a service is required.
The time in hours that the generator has been operating in Economy mode.
The time in hours that the generator has been operating in EST mode.
Each fault is represented by a fault code and is displayed along with the run hours at which the fault occurred. If a fault is active the fault code displayed will flash. Any faults that are active when the power is switched off, and are still active when the power is re-applied, will cause a new entry to be added into the fault log.
When enabled the end user is required to enter a password to gain access to the customer configuration menu.
0 = Disabled, 1 = Enabled
When enabled the Oxygen alarm is over-ridden. 0 = Over-ride disabled, 1 = Override Enabled [OVR]
Outlet oxygen sensor calibration menu.
Refer to section 4.8 for details on calibration.
EST oxygen sensor calibration menu.
Refer to section 4.8 for details on calibration.
Displays the outlet pressure in real time.
Also used for the inlet pressure set up.
Sets the units of measure for the outlet pressure. Units available are Bar / Psi / Mpa
1.1 Hours run 1.1 Hours run 5234h 5234h
1.2 Service due at 1.2 Service due at 8000h 8000h
1.3 Hours economy 1.3 Hours economy 25h 25h
1.4 Hours EST 1.4 Hours EST 4h 4h
2.1 Fault 1: Active2.1 Fault 1: Active C1 at 5234h C1 at 5234h
1121
3.1 Password enable3.1 Password enable = 0 = 0
3.2 Oxygen alarm 3.2 Oxygen alarm over-ride =0 over-ride =0
3.3 Calibrate outlet3.3 Calibrate outlet sensor = 5.00% sensor = 5.00%
3.4 Calibrate EST3.4 Calibrate EST sensor = 5.00% sensor = 5.00%
3.5 Pressure reading 3.5 Pressure reading = 8Bar = 8Bar
3.6 Pressure units 3.6 Pressure units = Bar = Bar
Page 23
21 - EN
Changing Parameters
Use the and keys to scroll through to the desired menu and press .
The flashing cursor should be positioned over the “=” sign to indicate that the parameter may be changed.
Use the / keys to change the parameter.
Press to accept the changes or press and simultaneously to cancel the changes.
Press and simultaneously to return to the customer settings menu and then again to return to the main operating menu.
Sets the purity level at which an oxygen fault is initiated. Default Settings: % Generators - 0.05% above the selected production purity. ppm Generators - 5ppm above the selected production purity.
If the purity level exceeds the oxygen alarm level for a period longer than the alarm delay, the oxygen alarm will be activated and the gas will be vented to atmosphere.
Delay Range = 0 – 600 Seconds, Default = 60 Seconds
Sets the Full Scale Deflection value for the 4 – 20mA Analogue Output of the Oxygen sensor(s).
When enabled the bed cleaning cycles will run whenever the generator is powered up, comes out of standby mode and economy mode.
0 = Disabled, 1 = Enabled
Enables the economy mode.
0 = Disabled, 1 = Enabled
When enabled the actuation of the Stop control will generate an alarm.
0 = Disabled, 1 = Enabled
Sets the address for the generator when communicating on a network via the RS485 MODBUS port.
Address range is 1 – 247
Sets the mode of control for the generator
1 = Local Start / Stop control, 2 = Remote Start / Stop control via the digital input, 3= Remote communication
Sets the parity for Modbus communication.
Even, Odd, None2, None1
Note. None2 and None1 refer to no parity with two or one stop bits.
Enables the EST mode.
0 = Disabled, 1 = Enabled
3.7 Oxygen alarm 3.7 Oxygen alarm level =15ppm level =15ppm
3.8 Oxygen alarm 3.8 Oxygen alarm delay = 60s delay = 60s
3.9 Oxygen Analogue3.9 Oxygen Analogue FSD = 6.0% FSD = 6.0%
3.10 Start cycle 3.10 Start cycle enable = 1 enable = 1
3.11 Economy enable 3.11 Economy enable = 1 = 1
3.12 Fault relay 3.12 Fault relay on stop =1 on stop =1
3.13 Machine number 3.13 Machine number = 1 = 1
3.14 Remote control 3.14 Remote control = 1 = 1
3.15 Modbus parity 3.15 Modbus parity = Even = Even
3.16 EST enable 3.16 EST enable = 0 = 0
3.6 Pressure units = Bar = Bar
3.6 Pressure units 3.6 Pressure units = Bar
3.6 Pressure units = PSI = PSI
Page 24
22 - EN
4.5 Oxygen Content
The residual oxygen content of the N2 process gas is continually monitored during normal operation. If the oxygen content increases above the alarm level the nitrogen gas is vented to atmosphere at a reduced flow until the purity recovers.
4.6 Economy Mode
Economy mode is designed to switch the generator into standby mode when there is no demand for gas.
The generator monitors the outlet pressure and, if it exceeds a pre-determined level for a sustained period of time (Economy Period *), the N2 outlet valve will close. The generator will continue to cycle as normal without delivering gas to the application. If the back pressure is maintained for an additional 5 minutes, the generator will stop cycling and enter Economy mode. If at any time the pressure falls below the regulated outlet pressure, the generator will resume normal operation.
If the generator is in economy shutdown when the pressure falls it will complete the cycle and then run through the a clean up cycle prior to going back online..
The Economy over-ride facility (optional) can be used to maintain the beds when the generator is in economy mode. If the over-ride is enabled, a clean up cycle will be performed once every 20 minutes (default). This allows the generator to go straight on-line when the outlet pressure falls below the regulated outlet pressure.
*The Economy Period is factory set to 5 minutes.
4.7 Energy Saving Technology - EST
If the generator is not operating at full capacity, it is unlikely that the CMS in the on-line chamber will be fully saturated at the point of changeover.
The EST system is used to monitor the O2 content of the gas at both the outlet of the buffer vessel and directly from the CMS bed. If the O2 content is below the production purity by >5% at the outlet and >20% from the CMS bed at the end of the current cycle, the EST system extends the cycle of the generator and changeover is delayed. Depending upon the production purity requirements, the generator will remain in this state for up to 300 seconds.
If at any point the O2 content of the gas rises to within 5% (at the outlet) or 20% (from the CMS bed) of the production purity the generator will resume normal cyclic operation.
Note. The economy mode described above will override the EST as required.
The economy mode can be disabled within the customer settings menu, however Parker domnick hunter strongly recommend that this option remains enabled.
Page 25
23 - EN
4.8 Oxygen Sensor Calibrationn
The O2 sensor(s) should be checked every 3 months and calibrated, if required, using a calibrated gas supply.
Note. The purity of the calibration gas should be as close to the production gas purity as possible (minimum of 50ppm). Do not exceed 7bar g (101.5psi g)
pressure.
If the generator is fitted with a second O
2
sensor for EST (as illustrated)
both sensors must be calibrated at the same time.
For low purity applications the calibration may be performed using compressed air. This method is not recommended when the purity of the gas is critical.
1 Navigate to menu 3.2 and enable the Oxygen Alarm Over-ride.
2 If using a calibrated gas supply - connect the gas to the Calibration Port
on the side of the generator.
3 Locate the calibration ball valve and rotate the handle clockwise so that it
is pointing towards Calibration from Calibrated Gas position.
Note. The calibration ball valve should be left in its original position if using compressed air.
4 Rotate the handles of the Outlet Gas O2 Sensor ball valve and the CMS
Gas O2 Sensor ball valve (if fitted) 180
o
so that they are pointing towards
the Calibration (as indicated on the calibration label).
5 Wait approximately fifteen minutes for the O2 reading to stabilise.
6 Navigate to menu 3.3 and press .
Using the and keys enter the purity of the calibration gas.
Press to send the calibration level to the O2 Analyser.
On successful completion of the calibration the new O
2
reading will be
shown on the bottom line of the display.
If the calibration is not successful the original reading from the analyser will be loaded. Should this occur repeat the above steps.
7 Repeat step 6 for the EST sensor (if fitted) in menu 3.4.
8 On completion of the calibration, return the ball valves back to their
original position and remove the regulated calibration gas supply as applicable.
9 Navigate to menu 3.2 and disable the O2 Alarm Over-ride.
When returning to the main operating menu, “CAL” will be shown on the top line of the display. This will remain for a period of twenty minutes after the calibration. Throughout this time period the O2 alarm is overridden, to allow the sensor(s) to return to the required level.
The following procedure must be carried only be performed by a Responsible Body or Service Personnel only. Operators should not perform this operation.
Hot surfaces and hazardous live voltages. Take care when performing the following calibration procedure as there are hazardous live voltages and potentially hot surfaces within the enclosure.
Note. The ball valves are shown in the normal operation position and should be
returned to this position on completion of the calibration.
1
Calibration Port
2
Calibration ball valve
3
Outlet Gas O2 Sensor
4
Outlet Gas O2 Sensor ball valve
5
CMS Gas O2 Sensor (EST)
6
CMS Gas O2 Sensor (EST) ball valve
Page 26
24 - EN
5 Preventative Maintenance
5.1 Cleaning
Clean the equipment with a damp cloth only and avoid excessive moisture around any electrical sockets. If required you may use a mild detergent, however do not use abrasives or solvents as they may damage the warning labels on the equipment.
5.2 Maintenance Schedule
Key:
Description Of Service Required
Service Recommended Every:
1
1.The service operations should be performed at the hours run or fixed time intervals specified (whichever occurs first)
Component Operation
Daily
3 Months
(2000 Hrs.)
6 Months
(4000 Hrs.)
12 Months
(8000 Hrs.)
24 Months
(16000 Hrs.)
36 Months
(24000 Hrs.)
60 Months
(40000 Hrs.)
Generator Check the status indicators located on the front panel.
System Check the inlet air quality.
Generator Check for air leaks
Generator Check the pressure gauges during purging for excessive back pressure.
Generator Check the condition of the electrical supply cables and conduits.
Generator Check oxygen sensor(s) and calibrate if necessary
Generator Check for cyclic operation
Filtration
Replace Exhaust silencer and filter element(s)
Recommended Service A
Generator
Replace Oxygen sensor(s)
Recommended Service B
Generator
Replace control valves
Recommended Service C
Generator
Replace cylinder and solenoid valves
Recommended Service D
Check
(Operator)
Essential Procedure
(Service Personnel only)
Essential Procedure
(Responsible Body or Service Personnel only)
Page 27
25 - EN
5.3 Preventative Maintenance Kits
The following preventative maintenance kits must be installed by service personnel only.
5.3.1 High Purity Generators (PPM)
Generators without EST Functionality (Model Nos. N2XXPAXN)
Generators with EST Functionality (Model Nos. N2XXPAXY)
5.3.2 Low Purity Generators (%)
Generators without EST Functionality (Model Nos. N2XXPBXN)
Generators with EST Functionality (Model Nos. N2XXPBXY)
Ref. Catalogue No. Description 12 24 36 48 60 72 84 96 108 120
A M12.NONEST.0001
12 Month Non EST Service Kit
(Every 12 Months)
D D D D D D D D D D
B M24.PPM.0001
24 Month PPM Service Kit
(Every 24 Months)
D D D D D
C M36.STD.0001
36 Month Standard Service Kit
(Every 36 Months)
D D D
D M60.STD.0001
60 Month Standard Service Kit
(Every 60 Months)
D D
Ref. Catalogue No. Description 12 24 36 48 60 72 84 96 108 120
A M12.EST.0001
12 Month EST Service Kit
(Every 12 Months)
D D D D D D D D D D
B M24.PPM.0001
24 Month PPM Service Kit
(Every 24 Months)
(x2) (x2) (x2) (x2) (x2)
C M36.STD.0001
36 Month Standard Service Kit
(Every 36 Months)
D D D
D M60.STD.0001
60 Month Standard Service Kit
(Every 60 Months)
D D
Ref. Catalogue No. Description 12 24 36 48 60 72 84 96 108 120
A M12.NONEST.0001
12 Month Non EST Service Kit
(Every 12 Months)
D D D D D D D D D D
B M24.PCT.0001
24 Month Percentage Service Kit
(Every 24 Months)
D D D D D
C M36.STD.0001
36 Month Standard Service Kit
(Every 36 Months)
D D D
D M60.STD.0001
60 Month Standard Service Kit
(Every 60 Months)
D D
Ref. Catalogue No. Description 12 24 36 48 60 72 84 96 108 120
A M12.EST.0001
12 Month EST Service Kit
(Every 12 Months)
D D D D D D D D D D
B M24.PCT.0001
24 Month Percentage Service Kit
(Every 24 Months)
(x2) (x2) (x2) (x2) (x2)
C M36.STD.0001
36 Month Standard Service Kit
(Every 36 Months)
D D D
D M60.STD.0001
60 Month Standard Service Kit
(Every 60 Months)
D D
Page 28
26 - EN
5.3.3 Kit Contents
Catalogue No. Description Contents
M12.NONEST.0001
12 Month Non EST Service Kit
(Every 12 Months)
Exhaust Silencer
025AR Dust filter element
Catalogue No. Description Contents
M12.EST.0001
12 Month EST Service Kit
(Every 12 Months)
Exhaust Silencer
025AR Dust filter element
In-line filter
Catalogue No. Description Contents
M24.PPM.0001
24 Month PPM Service Kit
(Every 24 Months)
PPM Cell c/w wiring
M24.PCT.0001
24 Month Percentage Service Kit
(Every 24 Months)
% Cell c/w wiring
Catalogue No. Description Contents
M36.STD.0001
36 Month Standard Service Kit
(Every 36 Months)
8 Bank solenoid valve
Catalogue No. Description Contents
M60.STD.0001
60 Month Standard Service Kit
(Every 60 Months)
40 x 25mm stroke cylinders (x6) Over moulded valve discs and guides (x6) 50 x 100mm stroke cylinders (x2) Valve discs (x2 sets) Valve bonnets (x2) Assorted o-rings Fixing screws
Page 29
27 - EN
6 Troubleshooting
In the unlikely event that a problem occurs on the equipment, this troubleshooting guide can be used to identify the probable cause and remedy.
Fault Codes
Troubleshooting should only be attempted by competent personnel. All major repair, and calibration work should be undertaken by a Parker domnick hunter trained, qualified and approved engineer.
Fault Probable Cause Remedy
Power Connected but LCD and status indicators not illuminated.
Fuse Blown Replace Fuse
Ribbon cable disconnected Reconnect Ribbon cable
Power disconnected Reconnect Power
No / Low gas outlet pressure
Service Overdue Service the generator
Internal gas leak Check and Rectify
External gas leak Check and Rectify
Low inlet pressure Ensure pressure meets required specification
High Oxygen concentration.
Defective Oxygen cell. Replace.
Leak in system piping. Check and Rectify
Low inlet pressure
Compressor or ring main pressure low. Check and Rectify
Inlet valve not open Check and Rectify
Defect on pre-treatment package. Refer to pre-treatment manual.
Excessive noise or vibration
Silencer loose or defective. Check and Rectify
Solenoid valve wear or coil loose. Check and replace if required.
High outlet pressure. Outlet regulator defective. Reset or replace.
Fault Codes Notes
C1
Pressure Start Inhibit Low inlet pressure. Inhibits start.
P1
Inlet Pressure Fault Low inlet pressure during cycling.
P2
Pressure Sensor Fault Outlet pressure sensor communication error.
E1
Power Failure
Y1
High oxygen alarm - outlet
Y2
Oxygen sensor communication failure - outlet
Communication fault between O2 analyser and control board
Y3
Incorrect oxygen cell selected - outlet
Y4
Oxygen reading high out of range - outlet
Occurs when O2 > 25% (% generators) / O2> 1.05% (ppm generators)
Y5
Oxygen sensor fault - outlet Contact Parker domnick hunter
Y6
Oxygen sensor communication failure - EST
Y7
Incorrect oxygen cell selected - EST
Y8
Oxygen sensor high out of range - EST
Y9
Oxygen sensor fault - EST
Y10
EST Board communication failure
S1
Service due
Page 30
R
Declaration of Conformity EN
Parker Hannifin Manufacturing Limited, domnick hunter Filtration and Separation
Dukesway, TVTE, Gateshead, Tyne & Wear, NE11 0PZ. UK
NitroSource N2 Nitrogen Gas Generator
N2-20P - N2-80P
Directives
97/23/EC 2006/95/EC 2004/108/EC
Standards used
EN 61010-1 : 2010 EN 61326-1 : 2013 EN 61000-3-2 : 2006 + A2:2009 EN 61000-3-3 : 2013 Generally in accordance with ASMEVIII Div 1 : 2010 2011a Addenda.
PED Assessment Route :
CAT III (N2-20P - N2-35P) CAT IV (N2-45P - N2-80P)
EC Type-examination Certificate:
TBA
Notified body for PED:
Lloyds Register Verification 71 Fenchurch St. London EC3M 4BS
Authorised Representative
Derek Bankier
Divisional Quality Manager Parker Hannifin Manufacturing Limited, dhFNS
Declaration
I declare that as the authorised representative, the above information in relation to the supply / manufacture of this product, is in conformity with the standards and other related documents following the provisions of the above Directives.
Signature: Date: 41969
Declaration Number: 00278/261114
Page 31
Page 32
Parker Hannifin Manufacturing Limited
domnick hunter Filtration and Separation Division Dukesway, Team Valley Trading Est Gateshead, Tyne and Wear England NE11 0PZ Tel: +44 (0) 191 402 9000 Fax: +44 (0) 191 482 6296 www.parker.com/dhfns
© Parker Hannifin Corporation. All rights reserved. Catalogue: 176500100
12/14 Rev: A
Ed. 2011-03-03
Europe, Middle East, Africa
AE – United Arab Emirates,
Dubai Tel: +971 4 8127100 parker.me@parker.com
AT – Austria, Wiener Neustadt Tel: +43 (0)2622 23501-0 parker.austria@parker.com
AT – Eastern Europe, Wiener Neustadt Tel: +43 (0)2622 23501 900 parker.easteurope@parker.com
AZ – Azerbaijan, Baku Tel: +994 50 2233 458 parker.azerbaijan@parker.com
BE/LU – Belgium, Nivelles Tel: +32 (0)67 280 900 parker.belgium@parker.com
BY – Belarus, Minsk Tel: +375 17 209 9399 parker.belarus@parker.com
CH – Switzerland, Etoy Tel: +41 (0)21 821 87 00 parker.switzerland@parker.com
CZ – Czech Republic, Klecany Tel: +420 284 083 111 parker.czechrepublic@parker.com
DE – Germany, Kaarst Tel: +49 (0)2131 4016 0 parker.germany@parker.com
DK – Denmark, Ballerup Tel: +45 43 56 04 00 parker.denmark@parker.com
ES – Spain, Madrid Tel: +34 902 330 001 parker.spain@parker.com
FI – Finland, Vantaa Tel: +358 (0)20 753 2500 parker. nland@parker.com
FR – France, Contamine s/Arve Tel: +33 (0)4 50 25 80 25 parker.france@parker.com
GR – Greece, Athens Tel: +30 210 933 6450 parker.greece@parker.com
HU – Hungary, Budapest Tel: +36 23 885 470 parker.hungary@parker.com
IE – Ireland, Dublin Tel: +353 (0)1 466 6370 parker.ireland@parker.com
IT – Italy, Corsico (MI) Tel: +39 02 45 19 21 parker.italy@parker.com
KZ – Kazakhstan, Almaty Tel: +7 7272 505 800 parker.easteurope@parker.com
NL – The Netherlands, Oldenzaal Tel: +31 (0)541 585 000 parker.nl@parker.com
NO – Norway, Asker Tel: +47 66 75 34 00 parker.norway@parker.com
PL – Poland,
Warsaw Tel: +48 (0)22 573 24 00 parker.poland@parker.com
PT – Portugal, Leca da Palmeira Tel: +351 22 999 7360 parker.portugal@parker.com
RO – Romania, Bucharest Tel: +40 21 252 1382 parker.romania@parker.com
RU – Russia, Moscow Tel: +7 495 645-2156 parker.russia@parker.com
SE – Sweden, Spånga Tel: +46 (0)8 59 79 50 00 parker.sweden@parker.com
SK – Slovakia, Banská Bystrica Tel: +421 484 162 252 parker.slovakia@parker.com
SL – Slovenia, Novo Mesto Tel: +386 7 337 6650 parker.slovenia@parker.com
TR – Turkey, Istanbul Tel: +90 216 4997081 parker.turkey@parker.com
UA – Ukraine, Kiev Tel +380 44 494 2731 parker.ukraine@parker.com
UK – United Kingdom, Warwick Tel: +44 (0)1926 317 878 parker.uk@parker.com
ZA – South Africa, Kempton Park Tel: +27 (0)11 961 0700 parker.southafrica@parker.com
North America
CA – Canada, Milton, Ontario
Tel: +1 905 693 3000
US – USA, Cleveland Tel: +1 216 896 3000
Asia Pacifi c
AU – Australia, Castle Hill
Tel: +61 (0)2-9634 7777
CN – China, Shanghai Tel: +86 21 2899 5000
HK – Hong Kong
Tel: + 852 2428 8 0 08
IN – India, Mumbai Tel: +91 22 6513 7081-85
JP – Japan, Tok yo Tel: +81 (0)3 6408 3901
KR – South Korea, Seoul Tel: +82 2 559 0400
MY – Malaysia, Shah Alam Tel: +60 3 7849 0800
NZ – New Zealand, Mt Wellington Tel: +64 9 574 1744
SG – Singapore
Tel: +65 6887 6300
TH – Thailand, Bangkok Tel: +662 186 7000-99
TW – Taiwan, Taipei Tel: +886 2 2298 8987
South America
AR – Argentina, Buenos Aires
Tel: +54 3327 44 4129
BR – Brazil, Sao Jose dos Campos Tel: +55 800 727 5374
CL – Chile, Santiago Tel: +56 2 623 1216
MX – Mexico,
Parker Worldwide
European Product Information Centre
Free phone: 00 800 27 27 5374
(from AT, BE, CH, CZ, DE, DK , EE, ES, FI,
FR, IE , IL, I S, IT, LU, MT, NL, NO, PL, PT, RU,
SE, SK, UK , ZA)
Toluca
Tel: +52 72 2275 4200
Loading...