Parker MAXIGAS MX104, MAXIGAS MX108, MAXIGAS MX106, MAXIGAS MX110, MAXIGAS MX112 User Manual

...
Page 1
EN
MAXIGAS
MX104 - MX120
User Guide
Original Language
aerospace climate control electromechanical
filtration
fluid & gas handling hydraulics pneumatics process control sealing & shielding
Page 2
Page 3
CONTENTS
EN
1 Safety Information............................................................................................................................................................................................... 4
1.1 Markings and Symbols................................................................................................................................................................................ 5
2 Description........................................................................................................................................................................................................... 6
2.1 Technical Specification ............................................................................................................................................................................... 6
2.1.1 Dimensions............................................................................................................................................................................................. 7
2.2 Unpacking the equipment ........................................................................................................................................................................... 7
2.3 Overview of the equipment ......................................................................................................................................................................... 8
3 Installation ........................................................................................................................................................................................................... 9
3.1 System layout and location ........................................................................................................................................................................ 9
3.2 Mechanical Installation.............................................................................................................................................................................. 10
3.3 Electrical Installation ................................................................................................................................................................................. 10
3.3.1 Generator Supply ................................................................................................................................................................................. 11
3.3.2 Dryer Supply......................................................................................................................................................................................... 11
3.3.3 Remote Switching ................................................................................................................................................................................ 11
3.3.4 Alarm Contacts..................................................................................................................................................................................... 11
3.3.5 4–20mA Analogue Output .................................................................................................................................................................... 11
4 Operating the Generator................................................................................................................................................................................... 12
4.1 Overview of controls ................................................................................................................................................................................. 12
4.2 Starting the generator ............................................................................................................................................................................... 13
4.3 Stopping the generator ............................................................................................................................................................................. 13
4.4 Menu Interface............................................................................................................................................................................................ 14
4.4.1 Hour Meters.......................................................................................................................................................................................... 14
4.4.2 Fault Log .............................................................................................................................................................................................. 14
4.4.3 Customer Settings................................................................................................................................................................................ 15
4.5 Start Clean Up ............................................................................................................................................................................................ 16
4.6 Economy Mode .......................................................................................................................................................................................... 16
4.7 Oxygen Analyser Calibration 17
4.7.1 Entering the calibrated level 17
5 Servicing ............................................................................................................................................................................................................ 18
5.1 Cleaning 18
5.2 Service Intervals ........................................................................................................................................................................................ 18
5.3 Service Kits ................................................................................................................................................................................................ 18
5.4 Service Procedures ................................................................................................................................................................................... 19
5.4.1 Exhaust Silencer Replacement ............................................................................................................................................................ 19
5.4.2 Dust Filter Element Change ................................................................................................................................................................. 19
5.4.3 Oxygen Sensor Replacement .............................................................................................................................................................. 19
5.5 Service Record........................................................................................................................................................................................... 20
6 Troubleshooting ................................................................................................................................................................................................ 21
7 Warranty............................................................................................................................................................................................................. 22
Page 4
1 Safety Information
Important: Do not operate this equipment until the safety information and instructions in this user guide have been read and understood by all personnel concerned.
WARNING - USER RESPONSIBILITY
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker-Hannifin Corporation, its subsidiaries and authorized distributors provide product or system options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance, endurance, maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry standards, and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user, the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and reasonably foreseeable uses of the components or systems.
Only competent personnel trained, qualified, and approved by Parker domnick hunter should perform installation, commissioning, service and repair procedures.
Use of the equipment in a manner not specified within this user guide may result in an unplanned release of pressure, which may cause serious personal injury or damage.
When handling, installing or operating this equipment, personnel must employ safe engineering practices and observe all related regulations, health & safety procedures, and legal requirements for safety.
Ensure that the equipment is depressurised and electrically isolated, prior to carrying out any of the scheduled maintenance instructions specified within this user guide.
Note: Any interference with the calibration warning labels will invalidate the gas generator’s warranty and may incur costs for the re-calibration of the gas generator.
Parker domnick hunter can not anticipate every possible circumstance which may represent a potential hazard. The warnings in this manual cover the most known potential hazards, but by definition can not be all-inclusive. If the user employs an operating procedure, item of equipment or a method of working which is not specifically recommended by Parker domnick hunter the user must ensure that the equipment will not be damaged or become hazardous to persons or property.
Most accidents that occur during the operation and maintenance of machinery are the result of failure to observe basic safety rules and procedures. Accidents can be avoided by recognising that any machinery is potentially hazardous.
Details of your nearest Parker domnick hunter sales office can be found at www.domnickhunter.com
Retain this user guide for future reference.
4
Page 5
EN
1.1 Markings and Symbols
NITROX
NITROGEN (N2)
GAS
NON-FLAMMABLE
DO NOT BREATHE
COMPRESSED
Asphyxiant in high concentrations. No odour Slightly lighter than air. Ensure adequate ventilation. Breathing 100% nitrogen will produce immediate unconsciousness and death due to lack of oxygen.
The following markings and international symbols are used on the equipment:
Caution, Read the User Guide. Pressurised components on the system
Safety Information
Risk of electric shock.
Wear ear protection Read the User Guide
Use a forklift truck Conformité Européenne
The following symbols are used within this user guide:
Highlights actions or procedures which, if not performed correctly, may lead to personal injury or death.
Highlights actions or procedures which, if not performed correctly, may lead to damage to this product.
Remote control. Generator may start automatically without warning.
NITROGEN (N NITROX
DO NOT BREATHE Asphyxiant in high concentrations. No odour. Slightly lighter than air. Ensure adequate ventilation. Breathing 100% nitrogen will produce
)
2
immediate unconsciousness and death due to lack of oxygen.
NON-FLAMMABLE COMPRESSED GAS
Highlights actions or procedures which, if not performed correctly, could lead to electric shock.
When disposing of old parts always follow local waste disposal regulations.
5
Page 6
2 Description
The MAXIGAS range of nitrogen generators operates on the Pressure Swing Adsorption (PSA) principle to produce a continuous stream of nitrogen gas from clean dry compressed air.
Pairs of dual chamber extruded aluminium columns, filled with Carbon Molecular Sieve (CMS), are joined via an upper and lower manifold to produce a two bed system. Compressed air enters the bottom of the ‘online’ bed and flows up through the CMS. Oxygen and other trace gases are preferentially adsorbed by the CMS, allowing nitrogen to pass through.
After a pre-set time the control system automatically switches the bed to regenerative mode. All of the contaminants are vented from the CMS and a small portion of the outlet nitrogen gas is expanded into the bed to accelerate the regeneration. At the same instant the second bed comes on-line and takes over the separation process.
The lower purity (%) generators use an equalisation phase designed to reduce energy consumption and enhance the overall performance of the generator. Immediately after the adsorption phase the inlet, outlet and exhaust valves close on both beds. The upper and lower equalisation valves open, allowing the pressure to equalise between the beds.
Once equalised the bed entering regeneration is depressurised. The oxygen adsorbed during the adsorption phase is vented to atmosphere via an exhaust valve and silencer. The bed entering the adsorption phase is pressurised using a controlled flow of nitrogen gas from the nitrogen buffer vessel (Back Fill) and a controlled flow of clean, dry, particulate free compressed air (Front Fill).
The CMS beds alternate between separation and regeneration modes to ensure continuous and uninterrupted nitrogen production.
The oxygen concentration in the nitrogen stream is analysed continuously. If the concentration exceeds the required production level, the nitrogen outlet is closed and the gas is vented to atmosphere. Normal operation will resume when the purity recovers.
2.1 Technical Specification
Parameter Units
Inlet Air Quality ISO 8573.1: 2001 Class 3.2.2
Inlet Pressure
Inlet Temperature
Port Connections
Air Inlet G1”
N2 Outlet to Buffer G1”
N2 Inlet from Buffer G1/2”
N2 Outlet G1/2”
Supply Voltage
Powe r W 38
Fuse A
Ambient Temperature
Humidity
IP Rating IP20 / NEMA 1
Pollution Degree 2
Installation Category II
Altitude
Noise dB(A) <75 <80
barg
(psig)
o
C
o
F)
(
V ac
(50/60Hz)
o
C
o
(
F)
m
(ft)
104 106 108 110 112 116 120
(88 – 145) and (145 - 261)
(Anti Surge (T), 250v, 5 x 20mm HBC,
Breaking Capacity 1500A @ 250v, UL Listed)
50% @ 40
MAXIGAS
6 – 10 and 10 - 18
5 – 50
(41 – 122)
115 / 230 ± 10%
3.15
5 – 50
41 – 122
o
C (80% MAX d 31oC)
< 2000
(6562)
6
Page 7
EN
2.1.1 Dimensions
Please refer to diagram A1 in Annex A.
Description
Model
104
106
108
110
112
116
120
A
mm
(ins)
692
(27.24)
861
(33.90)
1029
(40.51)
1198
(47.17)
1368
(53.86)
1765
(69.49)
2043
(80.43)
B
mm
(ins)
322
(12.68)
491
(19.33)
660
(25.98)
829
(32.64)
998
(39.29)
1314
(51.73)
1652
(65.04)
C
mm
(ins)
1895
(74.59)
1895
(74.59)
1895
(74.59)
1895
(74.59)
1895
(74.59)
1895
(74.59)
1895
(74.59)
D
mm
(ins)
550
(21.65)
550
(21.65)
550
(21.65)
550
(21.65)
550
(21.65)
550
(21.65)
550
(21.65)
E
mm
(ins)
500
(19.68)
500
(19.68)
500
(19.68)
500
(19.68)
500
(19.68)
500
(19.68)
500
(19.68)
F
mm
(ins)
366
(14.41)
G
mm
(ins)
861
(33.90)
H
mm
(ins)
981
(38.62)
I
mm
(ins)
1724
(67.87)
Weight
Kg
(lbs)
336
(741)
394
(869)
488
(1076)
582
(1283)
676
(1490)
864
(1905)
1052
(2319)
2.2 Unpacking the equipment
The generator is supplied in a wooden crate. It is recommended that the crate be moved into position using a forklift truck or pallet truck.
Remove the generator from the wooden crate using an overhead crane. The following illustrations give guidance on the safe slinging and lifting techniques. Please refer to diagram A2 in Annex A.
Remove the silencer from the generator prior to unpacking it.
Care should be taken and inspection undertaken during unpacking to ensure that the product is not damaged.
Verify that all component parts have been supplied with the generator as listed below:
Description Part Number Qty
User Guide 17 650 0000 1
Ball valve Kit Comprising of:
1/2” Ball Valve
1/2” 3 – way Ball Valve
1” BSPP Ball Valve (x 2)
Dust Filter AR020CBMX 60 446 2300 1
Access door key 27 650 0044 1
Non-return valve *. 60 650 0024 1
* The non-return valve is only supplied with high purity generators (10ppm and 100ppm).
60 650 0001 1
7
Page 8
2.3 Overview of the equipment
Please refer to diagram A3 in Annex A.
Key:
Outlet port to buffer (G1”) *
1
N
2
Outlet port (G1/2”) *
5
N
2
2 Cable Glands
3 Pressure Gauges
4
Pre-treatment dryer power supply cable gland. (Rating: 115V 1A / 230V 0.5A) External start / stop circuit cable gland.
Pre-treatment dryer purge economy cable gland.
Remote alarm circuit cable gland.
Mains supply cable gland
Column A pressure gauge
Column B pressure gauge
N
Outlet pressure gauge
2
Air inlet pressure gauge
N
inlet port from buffer vessel
2
(G1/2”) *
6 Air Inlet port (G1”) *
7 User control interface with 20 x 2 line menu display.
8 Access door
9Facia
10 4 – 20mA cable gland
Analyser calibration port
11
O
2
* Connection available on both sides of the generator.
8
Page 9
3 Installation
Only competent personnel trained, qualified, and approved by Parker domnick hunter should perform installation, commissioning, service and repair procedures.
3.1 System layout and location
Please refer to diagram A4 in annex A.
Ref Description Ref Description
1 Compressor 8 Buffer Vessel
2 Oil / Water Separator 9 Pressure Relief Valve
3 Wet air receiver 10 Dust Filter
4 Water separator 11 Maxi Generator
5 Dryer pre-filtration 12 Nitrogen Outlet
6 Pre-treatment Dryer 13 Non Return Valve
Installation
EN
7 Dust Filter Isolation Valve
The generator should be located indoors on a flat surface and protected from direct sunlight, moisture, and dust (Refer to section 2.1 of this user guide for the generators environmental specification). When considering the final location, take into account the noise generated when in use.
Lift the generator by the lower manifold, using a fork lift truck or similar, and position it in a suitably ventilated area close to the application.
Note: Due to the nature of operation there is a possibility of oxygen enrichment surrounding the generator.
Ensure that there is sufficient free space for maintenance access and lifting equipment.
DO NOT position the generator so that it is difficult to operate or disconnect.
When positioned in its final location, secure the generator to the floor using M20 bolts through the support legs.
Due to the nature of operation there is a possibility of oxygen enrichment surrounding the generator. Ensure that the area is adequately ventilated. Where the risk of oxygen enrichment is high, such as a confined space or poorly ventilated room, the use of oxygen monitoring equipment is advisable.
9
Page 10
3.2 Mechanical Installation
Please refer to diagram A5 in annex A
Once located fit the ball valves to the ports on the generator. All ppm generators are supplied with a non return valve, this should be fitted to the ball valve on the port marked “To Buffer Vessel”. Install the pipe-work ready for connection to the buffer vessel and compressed air supply. The diameter of the pipes must be sufficient to allow unrestricted inlet air supply to the generator and nitrogen supply to the application as shown in the table below.
Connection Pipe-work
(1) 1” Ball Valve (a) 1” NB / 28mm ID
(2) 1” Ball Valve (b) 1” NB / 28mm ID
(3) 1/2” Ball Valve (c) 1/2” NB / 16mm ID
(4) 3 Way Ball Valve (d) 1/2” NB / 16mm ID
Ensure that all piping materials are suitable for the application, clean and debris free. All outlet piping must be solid and non-porous to minimise the ingress of oxygen. When routing the pipes ensure that they are adequately supported to prevent damage and leaks in the system.
The nitrogen buffer vessel must be rated to at least the maximum operating pressure of the generator and must be fitted with suitable pressure gauge and pressure relief valve
It is recommended that the system be protected with suitably rated pressure relief valves upstream of the generator.
3.3 Electrical Installation
A fully qualified electrical engineer must undertake all field wiring and electrical work in accordance with local regulations.
Please refer to diagram A6 in Annex A.
In order to maintain the IP rating of the generator, all cables entering the electrical enclosure must do so through the dedicated cable glands located on the side of the generator. All cables used must be sized such that the voltage drop between the supply and the load does not exceed 5% of the nominal voltage under normal conditions. All cables external to the generator must be adequately supported and protected against physical damage.
REF CONNECTION TERMINAL NOTES CABLE DIAMETER
L - Fuse terminal for the phase conductor.
A Generator Supply
B Dryer Supply
C Purge Economy
D
E Alarm Contacts
F
Remote Switching
MODBUS
4-20mA
O
2
L (Grey) Dryer Live conductor N (Blue) Dryer Neutral conductor
(Yellow / Green)
JP17-2 (NC) JP17-3 (NO)
JP19-7 JP19-8 A B
JP18-1 (COM)
JP18-3 (NO)
Analyser - 6 (+ve) The screen should be bonded to the back plate Analyser - 7 (-ve)
(INPUT 4)
RS485 MODBUS
N - Neutral conductor
- Earth conductor
Dryer Earth conductor.
Refer to installation instructions for the dryer. 3 – 7 mm
Remote switching is activated in the customer Settings menu 3.11 For MODBUS communication setup details refer to dh publication 17 650 012.
The relay is energised when no faults are present
of the shroud.
6 - 12 mm
3 – 7 mm
3 – 7 mm
3 – 7 mmJP18-2 (NC)
3 – 7 mm
10
Page 11
3.3.1 Generator Supply
Connection to the electrical supply should be made through a switch or circuit breaker rated at 250VAC, 15A with a minimum short circuit rating of 10KA. All of the current carrying conductors should be disconnected by this device.
The device chosen should be clearly and indelibly marked as the disconnecting device for the equipment and be located in close proximity to the equipment and within easy reach for the operator.
Overcurrent protection must be fitted as part of the building installation. This protection should be selected in accordance with local and national code regulations with a minimum short circuit rating of 10KA.
The protective earth conductor should be longer than the associated phase conductors so that in the event of the cable slipping in the cable gland, the earth will be the last to take the strain.
3.3.2 Dryer Supply
If a Parker domnick hunter pre-treatment air dryer is used, it should be connected to the generator at the dedicated DIN rail terminals.
Note: Refer the documentation provided with your dryer for additional information on installation requirements.
3.3.3 Remote Switching
The generator may be controlled remotely by connecting a remote start / stop circuit to digital input #4 on the control board. When the circuit is open the generator should remain in standby mode, closing the circuit should initiate a start command.
To enable the remote switching function refer to 4.4.3 of this guide. Once the remote switching function has been enabled the local start control will no longer function.
When the remote switching function is enabled the generator can start without warning.
3.3.4 Alarm Contacts
Each generator is fitted with a set of volt free relay contacts designed for remote alarm indication and are rated 1A max @ 250Vac (1A @ 30Vdc). The alarm circuit should be connected between the “COM” and the NC terminals of JP18. Under normal operation the relay will be energised and the alarm circuit will be open. When a fault occurs, e.g. power failure, the relay will de-energise causing the alarm circuit to be complete.
If remote fault indication relay is used, the electrical enclosure will now contain more than one live circuit and in the event of the mains supply being disconnected, the fault relay connections will remain live.
3.3.5 4–20mA Analogue Output
The oxygen content detected by the generators internal analyser may be re-transmitted to external peripherals using the 4-20mA linear analogue output. The output is a linear current source, with 10 bit resolution, which increases from 4mA (Zero Oxygen) to 20mA (Full Scale Deflection). The FSD of the internal analyser is factory set to a default value of twice the generators specified purity. For % purity generators the maximum FSD is set to 6%.
Note: The oxygen purity setting of the generator is marked on the rating plate.
The table below shows the correlation between the purity settings of the generator and the output current. The FSD can be altered in menu 3.8 of the control software (refer to section 4.4.3 for details).
Generator
Purity
10ppm 0 - 20ppm 1ppm = 0.8mA
100ppm 0 - 200ppm 1ppm = 0.08mA
0.05% 0 - 0.1% 0.01% 1.6mA
0.1% 0 - 0.2% 0.01% = 0.8mA
0.5% 0 - 1% 0.01% = 0.16mA 1% 0 - 2% 0.01% = 0.08mA 2% 0 - 4% 0.01% = 0.04mA 3% 0 - 6% 0.01% = 0.026mA 4% 0 - 6% 0.01% = 0.026mA 5% 0 - 6% 0.01% = 0.026mA
Full Scale Deflection
4mA - 20mA
Resolution
11
Page 12
4 Operating the Generator
4.1 Overview of controls
Local Start / Stop Controls
Local Start control – This control is inactive when the generator is configured for remote control.
Local Stop control – This control is active for both local and remote control.
Menu navigation keys
Moves upwards through the menus
Moves downwards through the menus
Selects the current menu
Generator status indicators
Green - Cycling Amber - Start clean up, shutting down, N2 vent (No gas is delivered to the application), and entering economy Red - Standby
Green - Economy mode
Amber - Service due Red - Active Fault
12
Page 13
Operating the Generator
EN
4.2 Starting the generator
Inspect all of the system connection points and verify that they are secure.
With both the inlet and outlet ball valves of the buffer vessel closed, open the ball valve on the air inlet port to allow the compressed air into the generator.
Switch the electrical power on to the generator and wait whilst it runs through the controller initialisation routine.
If the generator was in standby mode when the electrical power was removed it will default to standby mode on completion of the initialisation routine.
Press to initiate the start up routine.
If the start clean up option is enabled the generator will run through the Rapid Cycle / Pure Start before opening the buffer valve and the N2 outlet valve.
[Refer to section 4.5 for more details on Rapid Cycle and Pure Start]
If the generator was running when the electrical power was removed (e.g. power failure) it will automatically run through a start up cycle (if enabled) and then commence normal operation. Wait until this cycle is complete and the menu displays “Running”. This may take several minutes in ppm generators.
Slightly open the ball valve on the inlet to the buffer vessel and leave it to pressurise slowly. When the pressure gauge on the buffer vessel reads within 0.5 barg (7psig, 0.05MPa) of the inlet pressure, check for leaks in the inlet piping and then fully open the ball valve.
Open the ball valve on the outlet of the buffer vessel and check for leaks in the piping between the vessel and the generator.
Open the ball valve on the Nitrogen outlet.
Note: If the purity of the gas is not within specification it will be vented to atmosphere through a vent solenoid within the generator and not delivered to the application. When the required purity is achieved the gas will be delivered to the application.
4.3 Stopping the generator
Close the ball valve on the N2 Outlet port.
Press [ ] to initiate the shutting down sequence.
The generator will complete the current cycle and then exhaust both beds. This may take several minutes particularly on ppm generators.
When the generator is depressurised it will revert to standby mode.
Note: There may be a residual pressure of approximately 1.5 bar within the columns due to the release of oxygen from the CMS. This can be released by turning the Kaddis drain, or small ball valve if fitted, on the inlet valve assembly.
13
Page 14
4.4 Menu Interface
All of the operational parameters and data are accessed through the menu driven interface. To prevent unauthorised access to the configurable parameters, the customers setting menu is password protected.
Menu Map
Please refer to diagram A7 in annex A.
The interface will automatically default back to the main operating menu if no key activity has been detected for one minute.
Note: After and additional two minutes of inactivity the display will shutdown. To bring the display back on-line press .
The customer settings menu contains the parameters that may be customised by the end user. To prevent unauthorised changes being made this menu is password protected and cannot be accessed until the password has been entered correctly.
To enter the password from the main operating menu press and hold both the and keys for approximately 5 seconds until the menu changes to the password prompt as shown
The flashing cursor will be positioned over the first digit.
Using the key change the first digit of the code and press . The cursor will move to the next digit.
Repeat the process and enter the following password 1 2 1 _ _ .
When the password has been entered correctly the Hour Meters menu will be displayed.
Use the key to navigate to page 3 “Customer Settings”.
4.4.1 Hour Meters
There are three hour meters available for viewing:
The time in hours that the generator has been producing gas.
The time in operating hours that the generator can produce gas before a service is required.
The time in hours that the generator has been operating in Economy mode.
4.4.2 Fault Log
The fault log menu allows the user to access the 10 most recent fault messages.
Each fault is represented by a fault code and is displayed along with the run hours at which the fault occurred. If a fault is active the fault code displayed will flash.
Any faults that are active when the power is switched off and are still active when the power is re­applied will cause a new entry to be added into the fault log.
Fault Codes Notes
C1 Pressure Start Inhibit Low inlet pressure. Inhibits start.
P1 Inlet Pressure Fault Low inlet pressure during cycling.
P2 Pressure Sensor Fault Pressure sensor communication error.
E1 Power Failure
Alarm
Y1
Y2
Y3 Incorrect cell selected
Y4
Y5
S1 Service due
O
2
Communication failure Communication fault between O2 analyser and control board
O
2
high (out of range) Occurs when O2 > 25% (% generators) / O2> 1.05% (ppm generators)
O
2
zero drift error
O
2
Contact Parker domnick hunter
14
Page 15
Operating the Generator
3.7 Fault Relay On Stop = 1
EN
4.4.3 Customer Settings
The customer settings menu contains all of the generator parameters that may be altered by the end user. The following example demonstrates the method of altering a parameter, however it is recommended that none of the parameters are altered until their functionality is fully understood.
Use the and keys to scroll through to the desired menu and press .
Referring to the menu map select the desired. The flashing cursor should be positioned over the “=” sign to indicate that the parameter may be changed.
Use the / keys to change the parameter.
Press to accept the changes or press and simultaneously to cancel the changes.
Press and simultaneously to return to the customer settings menu and then again to return to the main operating menu.
All settings marked in bold text are the default settings.
When enabled the O 0 = Over-ride disabled, 1 = Override Enabled
[OVR]
O
cell calibration menu.
2
Refer to section 4.7 for details on calibration.
Sets the purity level at which an oxygen fault is initiated. Default Settings:
% Generators - 0.05% above the selected production purity ppm Generators - 5ppm above the selected production purity
If the purity level exceeds the oxygen alarm level for a period longer than the alarm delay, the oxygen alarm will be activated and the gas will be vented to atmosphere..
alarm is over-ridden.
2
Delay Range = 0 – 600 Seconds, Default = 60 Seconds
When enabled the bed cleaning cycles will run whenever the generator is powered up, comes out of standby mode and economy mode.
0 = Disabled, 1 = Enabled
Enables the economy mode.
0 = Disabled, 1 = Enabled
When enabled the actuation of the Stop control will generate an alarm.
0 = Disabled, 1 = Enabled
Sets the Full Scale Deflection value for the 4 – 20mA Analogue Output.
Sets the ppm O
cell calibrated offset value marked on the cell.
2
Note: This value must be entered only when the cell is changed.
Sets the address for the generator when communicating on a network via the RS485 MODBUS port.
Address range is 1 – 32
Sets the mode of control for the generator
1 = Local Start / Stop control, 2 = Remote Start / Stop control via the digital input
15
Page 16
4.5 Start Clean Up
The clean up cycles are designed to clean the CMS bed of impurities, bring the generator up to production purity more rapidly, and prevent poor quality gas flowing into the buffer. The operation of the cycle is dependant upon the purity as described below:
Rapid Cycle – this cycle is used for lower purity generators (0.05 – 5.0%). The chambers are filled and exhausted alternately on a fixed cycle time. The Rapid Cycle takes 160 seconds to complete.
Pure Start - The higher purity generators (10 - 100ppm) require a two stage cleaning process:
Pure Start A – with the N
Pure Start B – immediately following Pure Start A the N
The chambers are then filled and exhausted again.
The pure start cycle times are dependant upon the production purity of the generator.
On completion of the start up cycles the N
The Start clean up cycle can be disabled within the customer settings menu, however Parker domnick hunter strongly recommend that the start up cycles remain enabled.
outlet to buffer valve closed, the chambers are filled and exhausted alternately.
2
outlet to buffer valve is opened to allow gas flow into the buffer vessel.
2
PRODUCTION PURITY
10 ppm 4 x 120 120/90
100 ppm 4 x 90 90/70
0.05% 4 x 90 90/70
outlet valve will open, allowing gas to be delivered to the application.
2
PURE START CYCLE
AB
4.6 Economy Mode
Economy mode is designed to switch the generator into standby mode when there is no demand for gas.
The generator monitors the outlet pressure and if it exceeds a pre-determined level for a sustained period of time (Economy Period *), the N outlet valve will close. The generator will continue to cycle as normal without delivering gas to the application. If the back pressure is maintained
for an additional 5 minutes, the generator will stop cycling and enter Economy mode.
When the pressure falls below the regulated outlet pressure, the generator will resume normal operation. If the generator is in Economy mode when this occurs, it will run through the relevant clean up cycle.
The economy mode can be disabled within the customer settings menu, however Parker domnick hunter strongly recommend that this option remains enabled.
The Economy over-ride facility (optional) can be used to maintain the beds when the generator is in economy mode. If the over-ride is enabled, a clean up cycle will be performed once every 20 minutes. This allows the generator to go straight on-line when the outlet pressure falls below the regulated outlet pressure.
*The Economy Period is factory set to 5 minutes.
2
16
Page 17
4.7 Oxygen Analyser Calibration
4
Select menu 3.1 and enable the O2 Alarm Over-ride.
3.2 O2 Calibration = 4.95%
3.2 O2 Calibration = 5.00%
3.2 O2 Calibration Please Wait...
3.2 O2 Calibration = 5.00%
3.1 O2 Alarm Over-ride = 1
O2 = 5.00 % CAL Running
The O2 analyser should be calibrated at least once every three months against a calibrated gas supply or a calibrated independent analyser.
Note. If using calibration gas, ensure that purity is as close to the production gas purity as possible (minimum of 50ppm). Do not exceed 7barg pressure.
For low purity applications the calibration may be performed using compressed air. This method is not recommended when the purity of the gas is critical.
3.1 O2 Alarm Over-ride = 1
Operating the Generator
EN
Calibrated Gas Supply
Connect the gas supply to the O
Analyser calibration port (1) on the side of the
2
generator.
Locate the calibration ball valve (2) inside of the shroud and rotate the handle clockwise so that it is pointing upwards as shown. Wait approximately fifteen minutes for the O
reading to stabilise. Once stable enter the calibrated level
2
as specified below.
Calibrated Independent Analyser
Connect the analyser to the nitrogen outlet port of the generator. Wait approximately fifteen minutes for the O
reading to stabilise. Once stable enter
2
the calibrated level as specified below.
Compressed Air
Connect the O ball valve (3), and the O
sample line between the elbow push in fitting, located on the
2
Analyser calibration port (1).
2
If a sample line other than the one provided by domnick hunter is used ensure that it is suitable rated for the working pressure of the generator.
Open the ball valve (3) and rotate the handle of the calibration ball valve (2) so that it is pointing upwards as shown. Wait approximately fifteen minutes for the O
reading to stabilise. Once stable enter the calibrated level as specified below.
2
The sample line will need to be depressurised prior to disconnection. Close the ball valve (3) and wait until the pressure shown on the pressure gauge (4) reaches zero. When the line is fully depressurised, rotate the handle of the calibration ball valve (2) so that it is pointing downwards and disconnect the line from the generator.
4.7.1 Entering the calibrated level
Select menu 3.2. The current reading from the 02 analyser will be displayed on the controller.
Using the and keys enter one of the following as appropriate:
the purity of the calibration gas,
the purity reading from the independent analyser,
Oxygen content of the compressed air (20.9%).
Press to send the calibration level to the O
On successful completion of the calibration the new O display. If the calibration is not successful the original reading from the analyser will be loaded. Should this
occur repeat the above steps.
On completion of the calibration, return the calibration ball valve back to its original position and remove the regulated calibration gas supply or independent analyser as applicable.
Disable the O
Alarm Over-ride.
2
When returning to the main operating menu, “CAL” will be shown on the top line of the display. This will remain for a period of twenty minutes after the calibration. Throughout this time period the O2 alarm is overridden, to allow the sensor to return to the required level.
analyser.
2
reading will be shown on the bottom line of the
2
17
Page 18
5 Servicing
5.1 Cleaning
Clean the equipment with a damp cloth only and avoid excessive moisture around any electrical sockets. If required you may use a mild detergent, however do not use abrasives or solvents as they may damage the warning labels on the equipment.
5.2 Service Intervals
Description Of Maintenance Required Typical Recommended Maintenance Interval
Component Operation
Generator Check status indicators located on the control panel.
System Check inlet air quality
Generator Check for air leaks
Generator Check pressure gauges during purging for excessive back pressure
Generator Check condition of electrical supply cables and conduits
Generator Check cyclic operation
Generator
Filtration
Generator
Generator
Replace active exhaust silencers
Recommended Service A
Replace dust and control air filters.
Recommended Service B
Replace/Calibrate oxygen sensor
Recommended Service C
Replace/Service valves
Recommended Service D
Daily
(3-month)
2000 Hours
(6-month)
4000 Hours
(12-month)
8000 Hours
(24-month)
16000 Hours
- Check – Replace
5.3 Service Kits
Please refer to diagram A8 in Annex A.
Service Kit Description Kit No.
A – Silencer Service Exhaust Silencer Kit 608620090
B – Filter Service Filter Element Kit 020AR
PPM O
Cell Service
C – O
2
D – Valve Service
The valve overhaul (Service D) and all other repair and calibration work should be undertaken by a Parker domnick hunter trained, qualified and approved engineer.
Cell Kit
2
% O
Cell Kit
2
PPM Valve Overhaul Kit (without equalisation valve)
% Valve Overhaul (with equalisation valve) 606500005
18
606500002
606500003
606500004
Page 19
EN
AB C
DE F
5.4 Service Procedures
Ensure that the generator is isolated from the mains power supply and fully depressurised before carrying out any of the following service procedures.
5.4.1 Exhaust Silencer Replacement
The exhaust silencer is located under the inlet manifold assembly. Unscrew the silencer assembly from the exhaust flange plate and remove. Slide the silencer element off the baffle (A) and replace.
Ensure that the replacement element is inserted into the groove of the baffle end cap and screw the exhaust silencer assembly back into the exhaust flange plate.
When fitted correctly there should be no movement of the element on the baffle.
5.4.2 Dust Filter Element Change
Close the ball valves located on the inlet and outlet ports of the filter and de-pressurise it by opening the drain valve on filter bowl.
Once de-pressurised unscrew the filter bowl from the head (D) and remove the old filter element. Holding the replacement element by the end caps, fit it into the bowl ensuring that the element is correctly seated (E). Assemble the filter bowl back onto the filter and tighten. The markers on the filter head and filter bowl must line up with each other when fully assembled (F).
Close the drain valve on the filter and slowly open the filter outlet valve and inlet valve.
Servicing
5.4.3 Oxygen Sensor Replacement
Disconnect the O2 cell lead from the O2 analyser. Terminals 1, 2 and 3 (% vol O2 cells) or 3, 4 and 5 (ppm vol O2 cells) (B) Unscrew the tube nut holding the O Fit the replacement sensor onto the t-piece and perform a leak test. All leaks must be repaired.
Refit the electrical connections to the O
.
Terminal Colour Function
1 Blue -ve % vol sensor
2 Red +ve % vol sensor
3 Green Ground
4 Blue -ve ppm vol sensor
5 Red +ve ppm vol sensor
Calibrate the sensor as detailed in section 4.7 (Note: PPM cells require the offset value to be entered prior to calibrating)
cell in place and remove the cell (C).
2
analyser
2
19
Page 20
5.5 Service Record
Date of Commissioning
Service (Hours)
8,000
16,000
20,000
24,000
28,000
32,000
36,000
40,000
Hours
Shown
Date
Serviced By
Comments / Observations
Print Initials
20
Page 21
EN
6 Troubleshooting
In the unlikely event that a problem occurs on the equipment, this troubleshooting guide can be used to identify the probable cause and remedy.
Troubleshooting should only be attempted by competent personnel. All major repair, and calibration work should be undertaken by a Parker domnick hunter trained, qualified and approved engineer.
Fault Probable Cause Remedy
Power Connected but LCD and status indicators not illuminated.
No / Low gas outlet pressure Service Overdue Service the generator
High Oxygen concentration. Defective Oxygen cell. Replace.
Low inlet pressure Compressor or ring main pressure low. Check and Rectify
Excessive noise or vibration Silencer loose or defective. Check and Rectify
High outlet pressure. Outlet regulator defective. Reset or replace.
Fuse Blown Replace Fuse
Ribbon cable disconnected Reconnect Ribbon cable
Power disconnected Reconnect Power
Internal gas leak Check and Rectify
External gas leak Check and Rectify
Low inlet pressure Ensure pressure meets required specification
Leak in system piping. Check and Rectify
Inlet valve not open Check and Rectify
Defect on pre-treatment package. Refer to pre-treatment manual.
Solenoid valve wear or coil loose. Check and replace if required.
21
Page 22
7 Warranty
This warranty applies to the Maxigas Generator and associated parts (the equipment) manufactured and supplied by Parker Hannifin ltd, Parker domnick hunter division (the company).
Use of the Maxigas Generator without the recommended inlet air quality or genuine parts will expressly invalidate the warranty.
Should the equipment be defective as to materials or workmanship, the company warrants that it will remedy such defect. Where the Equipment is a Maxigas Generator, the warranty period will be 12 months from date of commissioning or 18 months from date of manufacture, whichever is the earlier. In the case of equipment other than a Maxigas Generator, the warranty period shall commence from the date of despatch. Should any defect occur during the warranty period and be notified in writing to the company or its authorised distributor within the said period, the company will, as its sole option, remedy such defect by repair or provision of a replacement part, provided that the equipment has been used strictly in accordance with the instructions provided with each item of equipment and has been stored, installed, commissioned, operated and maintained in accordance with such instruction and with good practice. the company shall not be under any liability whatsoever under the warranty, if, before giving notification in writing to the company as aforesaid, the Customer or any third party meddles, interferes, tampers with or carries out work whatsoever (apart from normal maintenance as specified in the said instructions) in relation to the Equipment or any part thereof.
Any accessories, parts and equipment supplied by the company but not manufactured by the company shall carry whatever warranty the manufacturer has given the company providing it is possible for the company to pass on such warranty to the customer.
To claim under the warranty, the equipment must have been installed and continually maintained in the manner specified in the User Guide. Our product support engineers are qualified and equipped to assist you in this respect. They are also available to make repairs that may become necessary in which event they will require an official order before carrying out the work. If such work is to be the subject of a warranty claim, the order should be endorsed for consideration under warranty.
Where equipment is sold outside the UK mainland direct to the end user the warranty will cover parts only. Any substitution of parts not manufactured or approved by the company will expressly invalidate the warranty.
22
Page 23
Dukesway, TVTE, Gateshead, Tyne & Wear, NE11 0PZ. UK
Directives 97/23/EC
Declaration of Conformity EN
Parker Hannifin ltd, Industrial division
MAXIGAS Nitrogen Generator
MAXIGAS 102 - MAXIGAS 120
2006/95/EC 2004/108/EC 93/68/EEC, 92/31/EEC
Standards used EN 61010-1 : 2001
PED Assessment Route : B & D EC Type-examination Certificate: COV 0623606/1 Notified body for PED: Lloyds Register Verification
Authorised Representative Derek Bankier
Divisional Quality Manager Parker Hannifin ltd, Industrial division
EN 61000-6-2 : 2005 EN 61000-6-3 : 2007 EN 61000-3-2 : 2000 EN 61000-3-3 : 1995 Generally in accordance with ASMEVIII Div 1 : 2004.
71 Fenchurch St. London EC3M 4BS
Declaration
I declare that as the authorised representative, the above information in relation to the supply / manufacture of this product, is in conformity with the standards and other related documents following the provisions of the above Directives.
Signature: Date: 06/00/2010
Declaration Number: 0035/60110
Page 24
AE – UAE, Dubai Tel: +971 4 8127100 parker.me@parker.com
AR – Argentina, Buenos Aires Tel: +54 3327 44 4129
AT – Austria, Wiener Neustadt Tel: +43 (0)2622 23501-0 parker.austria@parker.com
AT – Eastern Europe,
Wiener Neustadt Tel: +43 (0)2622 23501 900 parker.easteurope@parker.com
A
U – Australia,Castle Hill
Tel: +61 (0)2-9634 7777
AZ – Azerbaijan, Baku Tel: +994 50 2233 458 parker.azerbaijan@parker.com
BE/LU – Belgium, Nivelles Tel: +32 (0)67 280 900 parker.belgium@parker.com
BR – Brazil, Cachoeirinha RS Tel: +55 51 3470 9144
BY – Belarus, Minsk Tel: +375 17 209 9399 parker.belarus@parker.com
CA – Canada, Milton, Ontario Tel: +1 905 693 3000
CH – Switzerland, Etoy Tel: +41 (0) 21 821 02 30 parker.switzerland@parker.com
CL – Chile, Santiago Tel: +56 2 623 1216
CN – China, Shanghai Tel: +86 21 5031 2525
CZ – Czech Republic, Klecany Tel: +420 284 083 111 parker.czechrepublic@parker.com
DE – Germany, Kaarst Tel: +49 (0)2131 4016 0 parker.germany@parker.com
DK – Denmark, Ballerup Tel: +45 43 56 04 00 parker.denmark@parker.com
ES – Spain, Madrid Tel: +34 902 33 00 01 parker.spain@parker.com
FI – Finland, Vantaa Tel: +358 (0)20 753 2500 parker.nland@parker.com
FR – France, Contamine s/Arve Tel: +33 (0)4 50 25 80 25 parker.france@parker.com
GR – Greece, Athens Tel: +30 210 933 6450 parker.greece@parker.com
HK – Hong Kong
Tel: +852 2428 8008
HU – Hungary, Budapest Tel: +36 1 220 4155 parker.hungary@parker.com
IE – Ireland, Dublin T
el: +353 (0)1 466 6370
parker.ireland@parker.com
IN – India, Mumbai Tel: +91 22 6513 7081-85
IT – Italy, Corsico (MI) Tel: +39 02 45 19 21 parker.italy@parker.com
JP – Japan, Tokyo Tel: +(81) 3 6408 3901
KR – South Korea, Seoul Tel: +82 2 559 0400
KZ – Kazakhstan, Almaty Tel: +7 7272 505 800 parker.easteurope@parker.com
LV – Latvia, Riga Tel: +371 6 745 2601 parker.latvia@parker.com
MX – Mexico, Apodaca Tel: +52 81 8156 6000
MY – Malaysia, Shah Alam Tel: +60 3 7849 0800
NL – The Netherlands,
Oldenzaal Tel: +31 (0)541 585 000 parker.nl@parker.com
NO – Norway, Ski Tel: +47 64 91 10 00 parker.norway@parker.com
NZ – New Zealand, Mt Wellington Tel: +64 9 574 1744
PL – Poland, Warsaw Tel: +48 (0)22 573 24 00 parker.poland@parker.com
PT – Portugal, Leca da Palmeira Tel: +351 22 999 7360 parker.portugal@parker.com
RO – Romania, Bucharest Tel: +40 21 252 1382 parker.romania@parker.com
RU – Russia, Moscow Tel: +7 495 645-2156 parker.russia@parker.com
SE – Sweden, Spånga Tel: +46 (0)8 59 79 50 00 parker.sweden@parker.com
SG – Singapore
Tel: +65 6887 6300
SK – Slovakia, Banská Bystrica T
el: +421 484 162 252
parker.slovakia@parker.com
SL – Slovenia, Novo Mesto Tel: +386 7 337 6650 parker.slovenia@parker.com
TH – Thailan
d, Bangkok
Tel: +662 717 8140
TR – Turkey, Istanbul Tel: +90 216 4997081 parker.turkey@parker.com
TW – Taiwan, Taipei Tel: +886 2 2298 8987
UA – Ukraine, Kiev Tel +380 44 494 2731 parker.ukraine@parker.com
UK – United Kingdom,
Warwick Tel: +44 (0)1926 317 878 parker.uk@parker.com
US – USA, Cleveland Tel: +1 216 896 3000
VE – Venezuela, Caracas Tel: +58 212 238 5422
ZA – South Africa,
Kempton Park Tel: +27 (0)11 961 0700 parker.southafrica@parker.com
Parker Worldwide
European Product Information Centre
Free phone: 00 800 27 27 5374
(from AT, BE, CH, CZ, DE, DK, ES, FI, FR, IE,
IT, NL, NO, PL, PT, RU, SE, UK, ZA)
© Parker Hannifin Corporation. All rights reserved. Catalogue: 176500000
03/09 Rev: 02
Parker Hannifin ltd
Industrial division Dukesway, Team Valley Trading Est Gateshead, Tyne and Wear England NE11 0PZ Tel: +44 (0) 191 402 9000 Fax: +44 (0) 191 482 6296 www.domnickhunter.com
Loading...