Gas Cooler & Flash Gas Bypass
Pressure Regulating Valves
Type GC and FGB
INSTALLATION AND SERVICING INSTRUCTIONS
SD-398
The Sporlan GC and FGB valve families are stepper motor driven pressure regulating valves engineered specifically for transcritical CO2 (R-744) refrigeration systems. The GC family is designed
for application as a Gas Cooler valve, but can also be applied as a Flash Gas Bypass valve. The FGB
family is designed to extend the capacity range of the GC valves when applied as Flash Gas Bypass
valves. Both families are rated for 140 barg (2030 psig) maximum working pressure. Offered with a
PSD4BX3XXXVP Valve Positioner and PSS4B Backup Power Module, the GC/FGB valves are easy to
implement, and feature:
• High resolution actuators with 2500 steps and 7.25 second full stroke actuation
• Uniquely characterized pin and port combinations for excellent full range flow control
• Cartridge valve designs with interchangeable bodies
• Tight seating capability
• Replaceable / serviceable screens (GC only)
For more information on these Sporlan Transcritical CO2 valves, please refer to Bulletin 100-80.
INSTALLATION
Valves are shipped fully assembled, but must be disassembled prior to installation.
1. Supporting the valve body on the provided flats, loosen and remove the motor adapter assembly using the 1-1/2” (38.1mm) hex flats.
GC
NOTE: The motor adapter assemblies are extremely tight, so proper tools are required to support
and loosen the components. Be careful not to warp the body by clamping too tightly.
NOTE (FGB ONLY): If the valve has been energized at any time, the piston must be retracted prior
to disassembly. Failure to do so can permanently damage the valve. The valve pistons are shipped
at approximately half stroke, so if the valve has not been energized, retracting the piston is not
necessary.

2. FGB ONLY – Remove the port using a standard 1-1/8” deep well socket. The gasket will now
be loose, and should be removed from the body as well.
FGB
3. Butt or socket weld the GC valve body into the system piping (1/2”, 3/4” or 1”connection).
The FGB body can be installed with a butt weld (1”), or brazed with the ODF (1-1/8”) or ODM
(1-3/8”) connection.
NOTE: The body should be oriented to position the motor within 45° of vertical.
NOTE: Ensure proper flow direction with respect to the flow arrow on the valve body.
FGBGC
FLOW FLOW
4. Lubricate all gaskets and o-rings using suitable refrigeration oil.
GC
FGB
5. FGB ONLY – Insert the gasket into the valve body. Install the port and tighten using a standard
1-1/8” deep well socket.

6. Insert the motor adapter assembly into the valve body, and tighten using the 1-1/2” (38.1mm)
hex flats.
GC
55-80 N-m
(40-60 ft.-lbs.)
FGB
55-80 N-m
(40-60 ft.-lbs.)
40-60 N-m
(30-45 ft.-lbs.)
NOTE (FGB ONLY): If the valve has been energized at any time, the piston must be retracted prior
to assembly. Failure to do so can permanently damage the valve. The valve pistons are shipped at
approximately half stroke, so if the valve has not been energized, retracting the piston is not necessary.
7. Attach the 4-conductor M12 cable and tighten the nut,
using care to avoid twisting the cable itself. The cable is
not position dependent, and can be installed in any of
four orientations (90° apart).
8. Wire the valve cable to the controller according to the
1.1-1.6 N-m
(10-14 in.-lbs.)
for IP-67
controller specifications. If using the PSD4BX3XXXVP
and PSS4B controllers, refer to Bulletin 100-80 for a
wiring schematic.
9. Pressurize the system, and check for leaks.
10. Apply power to the controller. The valve will perform
an initialization routine and should then begin controlling.
FIELD SERVICE INSTRUCTIONS
1. If the valve is not responding properly, disconnect line voltage and any backup power supply
from the valve controller.
2. Disconnect the valve leads from the controller.
3. Check the resistance of each motor phase. On a Sporlan cable, resistance between the black
and white leads, and between the red and green leads, should be approximately 12.8Ω ± 10%
(at valve internal temperature of 72°F / 22°C ). Differences of more than 10% between phases
may indicate a defective motor, and the valve should be replaced.

4. Check to ensure that the resistance between any valve lead and the valve body is greater than
1MΩ. Lower resistance readings may indicate a short, and the valve should be replaced.
NOTE: Prior to removing the motor adapter assembly, make sure the refrigerant has been
properly recovered or contained, and the pressure has been reduced to a safe level.
5. Follow Installation Step 1 to remove the motor adapter assembly, and Installation Step 2 (FGB
only) to remove the port (if necessary).
NOTE: The FGB piston is not replaceable, and no attempt should be made to remove it. None
of the GC or FGB valves have removable pins.
6. GC ONLY – Carefully remove the bottom o-ring in order to remove the port screen.
NOTE: Screen and o-ring must be carefully reinstalled or replaced prior to installation of the
motor adapter assembly. Failure to install the bottom o-ring will degrade valve performance.
7. Inspect the screen, pin and port area or valve body for damage or debris. If no obstruction or
other correctable issue is identified, and the valve is still not responding properly, controller
functionality should be investigated.
8. Follow Installation Steps 4-9 to install the original or a replacement motor adapter assembly.
9. Reapply power to the controller. The valve will perform an initialization routine, and should
then resume normal operation.
⚠WARNING – USER RESPONSIBILITY
Failure or improper selection or improper use of the products described herein or related items can
cause death, personal injury and property damage.
This document and other information from Parker Hannin Corporation, its subsidiaries and authorized
distributors provide product or system options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the nal selection of the
system and components and assuring that all performance, endurance, maintenance, safety and warning
requirements of the application are met. The user must analyze all aspects of the application, follow
applicable industry standards, and follow the information concerning the product in the current product
catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options
based upon data or specications provided by the user, the user is responsible for determining that such
data and specications are suitable and sufcient for all applications and reasonably foreseeable uses of
the components or systems.
FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY