Parker DFplus, DFE, DFP, D30FP, Parker DFplus Operation Manual

Page 1
Bulletin HY11-5715-687/UK
Proportional Directional Control Valve
Operation Manual Series DFplus
Design > 30
Parker Hannifin Manufacturing Germany GmbH & Co. KG
Hydraulic Controls Division Europe Gutenbergstr. 38 41564 Kaarst, Germany Tel.: (+49) 181 99 44 43 0 E-mail: valveshcd@parker.com Copyright © 2016, Parker Hannifin Corp.
Page 2
2
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Offer of Sale
Please contact your Parker representation for a detailed ”Offer of Sale”.
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker-Hannifin Corporation, its subsidiaries and authorized distributors provide product or system options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance, endurance, maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry standards, and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user, the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and reasonably foreseeable uses of the components or systems.
WARNING — USER RESPONSIBILITY
Page 3
Prop. Directional Control Valve
Series DFplusOperation Manual
3
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Contents Page
1. Introduction 4
Ordering Code D*FE 4
Ordering Code D*FP 5
Ordering Code D30FP 6
Name Plate 7
Characteristics of Valve Driver 7
Block Diagram of Onboard Electronics 7
Technical Data 8
2. Safety Instructions 9
Symbols 9
Service 9
3. Important Details 9
Intended Usage 9
Common Instructions 9
Liability 9
Storage 9
4. Mounting / Installation 10
Scope of Supply 10
Mounting 10
Limits of Use 10
Pressure Fluids 10
Electrical Connection 11
5. Operating Instructions 15
Spool Position at Power Down/Center Position 15
ProPxD parameterizing software 15
Filter 20
Flushing 20
6. Trouble Shooting 21
7. Accessories / Spare Parts 21
Accessories 21
Spare Parts 21
Page 4
4
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
AB
1. Introduction
D*FE
Ordering Code
Nominal
size
Direct.
control
valve
Spool-
type
(see
catalogue)
Command-
signal
Y-port
(plugged)
1)
Seal Design
series
(not re-
quired for
ordering)
Spool
position
on power
down
Elec-
tronics
option
Code Signal Function
B +/- 10 V 0...+10 V -> P-A
E +/- 20 mA 0...+20 mA -> P-A
K +/- 10 V 0...+10 V -> P-B
S 4...20 mA 12...20 mA -> P-A
D F E C 9 3
Spool/
body
design
Code Seal
N NBR
V FPM
H for HFC fluid
Code Size
1 NG06 / CETOP 03
3 NG010 / CETOP 05
Code
Spool position on
power down
C
1)
Needs to be removed at tank pressure >35 bar.
Code Connection
0 6 + PE
5 11 + PE
7 6 + PE + Enable
Page 5
Prop. Directional Control Valve
Series DFplusOperation Manual
5
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Code
Spool position on
power down
Code
Spool position on
power down
A
3)
H
5) 6)
a
0b
A
B
PT
B
3)
J
5) 6)
a
0b
A
B
PT
C
4)
AB
Y
D*FP
Ordering Code
Nominal
size
Direct.
control
valve
Spool-
type
(see
catalogue)
Command-
signal
Y-port
(plugged)
2)
Seal Design
series
(not
required for
ordering)
Spool
position
on power
down
1)
Code Nominal size
1 NG06 / CETOP 03
3 NG10 / CETOP 05
Code Connection
0 6 + PE
5 11 + PE
7 6 + PE + Enable
Code Signal Function
B +/- 10 V 0...+10 V -> P-A
E +/- 20 mA 0...+20 mA -> P-A
K +/- 10 V 0...+10 V -> P-B
S 4...20 mA 12...20 mA -> P-A
D F P 9 0
Spool/ sleeve
design
Code Seal
N NBR
V FPM
H for HFC fluid
1)
On power down the spool moves in a defined position.
This cannot be guaranteed in case of single flow path on the control edge A – T resp.
B – T with pressure drops above 120 bar or contamination in the hydraulic fluid.
2)
Needs to be removed at tank pressure >35 bar.
3)
Approx. 10 % opening, only zero lapped spools and underlap spools.
4)
Only for overlapped spools.
5)
Not for flow code M (40 l/min).
6)
Only D1FP
Elec-
tronics
option
Page 6
6
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
AB
Y
Code
Spool position on
power down
A
1)
B
1)
C
2)
D30FP
Ordering Code
Nominal
size
NG10 /
CETOP 05
Direct.
control
valve
Spool-
type
(see
catalogue)
Command-
signal
SealSpool
position
on power
down
D 30 F P 3
Code Inlet Drain
1
3)
internal external
4 internal internal
Pilot con-
nection
Design
series
(not re­quired for ordering)
Spool/
body
design
Code Seal
N NBR
V FPM
H for HFC fluid
1)
Approx. 10 % opening, only zerolapped spools.
2)
Only for overlapped spools.
3)
For tank pressure >35 bar.
Code Signal Function
B +/- 10 V 0...+10 V -> P-A
E +/- 20 mA 0...+20 mA -> P-A
K +/- 10 V 0...+10 V -> P-B
S 4...20 mA 12...20 mA -> P-A
Elec-
tronics
option
Code Connection
0 6 + PE
5 11 + PE
7 6 + PE + Enable
Page 7
Prop. Directional Control Valve
Series DFplusOperation Manual
7
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
µC
Parametrizing
interface
Command
Diagnostic
spool stroke
Supply Voltage
PE
0...±10 V
22...30 V=
Reference
1)
0V
0...±10 V
4...20 mA
0...±20 mA
B, K:
S:
E:
Reference
µC
Parametrizing
interface
0...±10 V
22...30 V=
Command
Diagnostic
spool stroke
Supply
Voltage
PE
+5...30 V=
Enable
Reference
1)
0V
0...±10 V
4...20 mA
0...±20 mA
B, K:
S:
E:
Reference
Characteristics of Valve Driver
The integral electronic driver combines all func­tions for optimal operation of the valve. Thanks to its excellent dynamic the valve is deployable within closed loop control applications. The most important features are:
• high dynamic actuator with specially designed electronic driver
• closed loop controlled spool position
• constant current actuator control with overcur­rent shutoff
• excellent properties for response sensitivity and temperature drift
• differential input stage with various command signal options
• diagnostic output for spool stroke / overcurrent state
• meets relevant European EMC-standards
Name Plate Block Diagram of Onboard Electronics
Code 0 (6+PE)
Code 5 (11+PE)
Code 7 (6+PE with enable)
hydr. spool symbol order code nominal pressure
µC
Parametrizing
interface
0...±10 V
22...30 V=
+5...30 V=
Command
Diagnostic
spool stroke
Supply Voltage
PE
Enable
0...±10 V
4...20 mA
0...±20 mA
B, K:
S:
E:
Reference
1)
0V
1)
Do not connect with supply voltage zero.
Page 8
8
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Technical Data
General
Model Proportional directional control valve, direct operated (D*FE, D*FP),
pilot operated (D30FP)
Drive
VCD®-actuator Mounting interface NG06 (CETOP 03) / NG10 (CETOP 05) Installation position D*FE, D*FP: unrestricted; D30FP: horizontal mounting preferred
(other mounting positions after consultation) Sensitivity [%] < 0.03 Hysteresis [%] < 0.05 (D*FE: <0.1) Temp. drift of center postion [%/K] < 0.025 Ambient temperature [°C] -20...+50 Vibration resistance [G] 10 Sinus 5...2000 Hz acc. IEC 68-2-6
30 Random noise 20...2000 Hz acc. IEC 68-2-36
15 Shock acc. IEC 68-2-27 Weight [kg] NG06: 3.6 / NG10: 6.5
Hydraulic
Fluid Hydraulic oil according to DIN 51524 ... 535, other on request Fluid temperature [°C] -20...+60 (NBR: -25...+60) Viscosity permitted [cSt]/
recommended [cSt]/
[mm2/s] [mm2/s]
20...400
30...80 Filtration ISO 4406 (1999); 18/16/13 Operating pressure max. [bar] 350 for ports P, A, B / max. 35 for port T at internal drain,
250 (D1FE, D1FP: 350) at external drain / port Y max. 35
1)
Electrical
Duty ratio [%] 100 Protection class
IP65 in accordance with EN 60529 (with correctly mounted plug-in connector) Supply voltage / ripple [V] 22...30, electric shut-off < 19, ripple < 5 % eff., surge free Current consumption max. [A] 3.5 Pre-fusing [A] 4.0 A medium lag Input signal Code B, (K) voltage
Impedance
[V]
kOhm]
+10...0...-10, ripple < 0.01 % eff., surge free, 0...+10 V P–>A (P–>B)
100 Code E voltage
Impedance
[mA]
[Ohm]
+20...0...-20, ripple < 0.01 % eff., surge free, 0...+20 mA P–>A
< 250 Code S current
Impedance
[mA]
[Ohm]
4...12...20, ripple < 0.01 % eff., surge free, 12...20 mA P–>A
< 250
< 3.6 mA = enable off, > 3.8 mA = enable on acc. NAMUR NE43 Input capacitance typ. [nF] 1 Differential input voltage max.
Code 0 Code 5
Code 7
[V]
[V]
[V]
30 for terminal D and E against PE (terminal G)
11 for terminal D and E against 0V (terminal B)
30 for terminal 4 and 5 against PE (terminal W )
11 for terminal 4 and 5 against 0V (terminal 2)
30 for terminal D and E against PE (terminal G) Enable signal Code 5/7 [V] 5...30, Ri = > 8 kOhm Diagnostic signal [V] +10...0...-10 / +12.5 error detection, rated max. 5 mA EMC EN 61000-6-2, EN 61000-6-4 Electrical connection
Code 0/7 Code 5
6 + PE acc. EN 175201-804
11 + PE acc. EN 175201-804 Wiring min. Code 0/7
Code 5
[mm²] [mm²]
7 x 1.0 (AWG16) overall braid shield
8 x 1.0 (AWG16) overall braid shield Wiring length max. [m] 50
1)
For applications with pT>35 bar (max 350 bar) the Y-port has to be connected and the plug in the Y-port has to be
removed.
Page 9
Prop. Directional Control Valve
Series DFplusOperation Manual
9
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
2. Safety Instructions
Please read the operation manual before installa­tion, start-up, service, repair or stocking! Disregard may result in damaging the valve or incorporated system parts.
Symbols
This manual uses symbols which have to be fol­lowed accordingly:
Instructions with regard to the warranty
Instructions with regard to possible dam-
aging of the valve or linked system com­ponents
Helpful additional instructions
Service
Workings in the area of installation, commissioning, maintenance and repair of the valve may only be allowed by qualified personnel. These are persons which have, because of education, experience and instruction, sufficient knowledge on relevant direc­tives and approved technical rules.
3. Important Details
Intended Usage
This operation manual is valid for proportional directional control valves DFplus series. Any dif­ferent or unintended usage is to be considered as not intended. The manufacturer is not liable for warranty claims resulting from this.
Common Instructions
Parker reserves the right for technical modifications of the described product. Illustrations and drawings within this manual are simplified representations. Due to improvement or modification of the product the illustrations might not match precisely with the described valve. The technical specifications and dimensions are not binding. No claims can be derived of it. Copyrights are reserved.
Liability
Parker does not assume liability for damage due to the following failures:
• incorrect mounting / installation
• improper handling
• lack of maintenance
• unintended usage
Do not disassemble the valve! In case of suspicion for a defect please contact Parker.
Storage
In case of temporary storage the valve must be protected against contamination, atmospheric ex­posure and mechanical damages. Each valve has been factory tested with hydraulic oil, resulting in protection of the internal parts against corrosion. Yet this protection is only ensured under the following conditions:
Outdoor storage or within sea and tropical
climate will lead to corrosion and might disable the valve!
Storage period
Storage requirements
12 months
constant humidity < 60 % as well as constant temperature < 25 °C
6 months
varying humidity as well as varying temperature < 35 °C
Page 10
10
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
4. Mounting / Installation
Scope of Supply
Please check immediately after receiving the valve, if the content is matching with the specified scope of supply. The delivery includes:
• valve
• operation manual The central connector has to be ordered separately and is not included in the delivery.
Please check the delivery immediately after
receiving the shipment for apparent dam­ages due to shipping. Report shipment losses at once to the carrier and the supplier!
Mounting
• Compare valve type (located on the name plate) with bill of materials respectively circuit diagram.
• The valve may be mounted fix or movable in any direction.
• Check mounting surface for the valve. Uneve­ness of 0.01 mm/100 mm, surface finish of 6.3 µm are tolerable values.
Keep valve mounting surface and work envi-
ronment clean!
• Remove protection plate from the valve mounting surface
• Check the proper position of the valve ports and the O-rings.
• Mounting bolts:
D1FE/D1FP: 4 pcs. M5x30 D3FP/D30FP: 4 pcs. M6x40 use property class ISO 4762-12.9
• Bolt kits:
D1FE/D1FP: BK375 D3FE/D3FP/D30FP: BK385
• Tighten the bolts crisscross with the following torque values:
D1FE/D1FP: 7.6 Nm D3FE/D3FP/D30FP: 13.2 Nm
Insufficient condition of the valve mounting
surface might create malfunction!
Incorrect mounting resp. bolt torque may
result in abrupt leakage of pressure fluid on the valve ports.
Limits of Use
The valve may be operated within the determined limits only. Please refer to the “technical data“ sec­tion as well as to the “characteristic curves“ in the Parker catalogue HY11-3500/UK “Hydraulic Valves Industrial Standard”.
Follow the environmental conditions! Unal-
lowable temperatures, shock load, aggresive chemicals exposure, radiation exposure, il­legal electromagnetic emissions may result in operating trouble and may lead to failure! Follow the operating limits listed in the “specifications“ table!
Pressure Fluids
The following rules applies for the operation with various pressure fluids:
This above information serves for orientation
and does not substitute user tests among the particular operating conditions. In particular, no liability for media compatibility may be derived out of it.
Mineral oil: usable without restriction. HFC: choose the right seal option.
For operation with the following pressure fluids please consult Parker:
For detailed information concerning pressure
fluids note VDMA-document 24317 as well
as DIN 51524 & 51502. Special gaskets may be available depending on the utilized fluid. In case of doubt please consult Parker.
HFA oil-in-water emulsion
HFB water-in-oil emulsion
HFD unhydrous fluids (Phosphor-Ester)
Page 11
Prop. Directional Control Valve
Series DFplusOperation Manual
11
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Electrical Connection
The valve is connected electrically by one common cable and a central connector.
The connection codes 0 and 7 require a 6 + PE female connector EN 175201-804.
The female connector can be ordered sepa-
rately under article nr. 5004072.
In case third party connectors are used, ac­cordance to the relevant EMC directives must be ensured.
The connecting cable has to comply to the follow­ing specification:
Cable type control cable, flexible, 7 conductors, overall braid shield Cross section min. AWG16 Outer dimension 8...12 mm Cable length max. 50 m
For cable lengths > 50 m consult Parker.
The connection cable is coupled to the female connector by solder joints. Skinning lengths for the connecting cable:
The connection Code 5 requires a 11 + PE female connector EN 175201-804.
The female connector has to be ordered
separately under article nr. 5004711.
In case third party connectors are used, ac­cordance to the relevant EMC directives must be ensured.
The connecting cable has to comply to the follow­ing specification:
Cable type control cable, flexible, 8 conductors, overall braid shield Cross section min. AWG16 Outer dimension 12...15 mm Cable length max. 50 m
For cable lengths > 50 m consult factory.
The connection cable is coupled to the female connector by crimp contacts.
Skinning lengths for the connecting cable:
Do not disconnect cable socket under voltage!
The shielding has to be assembled according the outline below:
Ø27.5
AF22
M26x1.5
~92
7/8-20
UNEF-2B
Ø28.6
max. 67
PG13.5
Page 12
12
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Electrical Interfacing
Supply Voltage
The supply voltage for the valve has to cover the range of 22...30 V. Valve is de-energized below 19 V. The residual ripple may not exceed 5 % eff.
The applied power supply must comply to the
relevant regulations (DIN EN 61558) and must
carry a CE-mark. The operating voltage for
the valve must be free of inductive surges.
Do not exceed the max. value of 30V! Higher
voltage can lead to failure of the valve.
The increased inrush current of the valve
should be considered when selecting the
power supply. A stabilized power supply with
overcurrent limiting feature should not be
used. Due to the inrush current of the valve
the current limit circuit may respond prema-
turely and create problems during energizing
of the supply voltage.
The operation of the valve is blocked if the
supply voltage polarity is interchanged.
Each valve requires a separate pre-fuse of 4
Amp semi time-lag. Failure to observe this
instruction may create irreparable damage of
valve respectively incorporated system parts.
The backshell nut of the cable gland has to be tighten with a suitable tool. The target value for the tightening torque is 4 Nm. Tighten the cap nut with a torque of 5 Nm after attaching the female connector on the socket.
Incomplete tightening of backshell nut respec-
tively cap nut may result in undesired release of the connection as well as degradation of the water tightness.
When using female connectors of other
manufacturers, the relevant regulations must be observed.
The cable may only be connected to the female
connector by authorized and qualified person­nel. A short between individual conductors resp. to the connector housing , bad soldering as well as improper shield connection may result in malfunction and breakdown of the valve.
The mounting surface of the valve has to be
connected to the earth grounded machine frame. The earth ground wire from the valve connecting cable as well as the cable shield have to be tied to the protective earth termi­nal within the control unit. It is necessary to use a low ohmic potential connection between control unit and machine frame to prevent earth loops (cross section AWG 6).
Page 13
Prop. Directional Control Valve
Series DFplusOperation Manual
13
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
=
~
V
A
F
B
E
C
G
D
+
Power supply
24 V
Command
0...±10 V
Diagnostics
valve stroke
Reference
Reference
1)
0...±10 V
0...±20 mA
4...20 mA
B, K:
E: S:
0V
Wiring
Code 0, 6 + PE acc. EN 175201-804 Code 5, 11 + PE acc. EN 175201-804
Code 7, 6 + PE acc. EN 175201-804 + enable
=
~
V
+
Power supply
24 V
Enable
Command
+
5...30 V
0...±10 V
Diagnostics valve stroke
4
5
3
6
10
2
11
9
7
1
8
Pin 3 and 8 internally connected Pin 9 and 11 internally connected Pin 10 not connected
Reference
0...±10 V
0...±20 mA
4...20 mA
B, K:
E: S:
0V
0V
Reference
1)
=
~
V
A
F
B
E
C
G
D
+
+
Power supply
24 V
Enable
Command
0...±10 V
5...30 V
Diagnostics
valve stroke
Bezugspotential
1)
0V
0V
0...±10 V
0...±20 mA
4...20 mA
B, K:
E: S:
1)
Do not connect with supply voltage zero.
Page 14
14
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Enable input (only for Code 5 / 11+PE as well as Code 7 / 6+PE)
A signal voltage enables the actuator drive of the valve. Continuous operation of the valve requires a permanent voltage 5...30 V (e.g. the supply voltage). In case of disabling the signal the valve will reach its power down position spring-actuated independently from the command signal value.
The enable function represents no safety
arrangement against unwanted valve opera­tion in terms of accident prevention regula­tions.
Command signal input
The spool stroke is proportional to the command signal amplitude.
The command input signal needs to be filtered
as well as free of inductive surges and modulations. Due to the sensitivity of the valve a high signal quality is recommended. This will prevent malfunction.
Code
command
signal
Command
signal
Function
VCD
actuator
Diagnostic
signal
B
0…+10 V on 0…+10 V
0…-10 V on 0…-10 V
Overload
off 12.5 V
E
0…+20 mA on 0…+10 V
0…-20 mA on 0…-10 V
Overload
off 12.5 V
K
0…+10 V on 0…-10 V
0…-10 V on 0…+10 V
Overload
off 12.5 V
S
4…12 mA on 0…-10 V
12…20 mA on 0…+10 V
0…3.6 mA
off
Cable break,
12.5 V
Overload
off 12.5 V
The option 4...20 mA uses the “3.6 mA“
condition as breakdown-information. If the
input signal line is interrupted, an evaluable
failure information is available. In this case
the actuator drive will be switched off. The
drive will switch on when the input signal
reaches a value of 3.8 mA, it switches off
when the command falls below 3.6 mA. This
determination follows the NAMUR-specifica-
tion NE43.
NAMUR is an association of users of process control technology.
Diagnostic output
A diagnostic signal is available. Its voltage repre­sents the operating condition of the valve.
The output may drive a load of max. 5 mA.
Exceeding of this limit leads to malfunction.
Code
command
signal
Command
signal
Function
VCD
actuator
Diagnostic
signal
B
0…+10 V on 0…-10 V
0…-10 V on 0…+10 V
Overload
off 12.5 V
E
0…+20 mA on 0…-10 V
0…-20 mA on 0…+10 V
Overload
off 12.5 V
K
0…+10 V on 0…+10 V
0…-10 V on 0…-10 V
Overload
off 12.5 V
S
4…12 mA on 0…+10 V
12…20 mA on 0…-10 V
0…3.6 mA
off
Cable break,
12.5 V
Overload
off 12.5 V
Valves NG06 Valves NG10
1)
Diagnostic signal 12,5 V in error case. Spool
moves in a defined postion, please see order­ing code „spool position at power down“.
Page 15
Prop. Directional Control Valve
Series DFplusOperation Manual
15
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Hardware requirements
• PC with operating system from Windows® XP upwards
• Interface RS232C
• display resolution at least 800 x 600
• connection cable between PC and electronic module
• memory requirement approximately 40 MB
If your PC has no serial interface according
to RS232C standard you require in addition an USB-RS232C adapter.
Cable Specification
Attention! The valve electronic provides no
USB interface, but can only be parametrized via an RS232C - connection. Therefore the usage of USB standard cables is not allowed and may result in damaging of valve respec­tively PC.
Parametering interface
Parametrizing
Ordering code: 40982923
The cover plug has to be re-installed after
completion of the parametrizing work.
Plug for parametering interface
5. Operating Instructions
Spool Position at Power Down/Center Position
For valves with zero lap spools, distinction
must be made between hydraulic neutral position and power-down position. Neutral position is taken at neutral input signal, cor­responding to zero position of the hydraulic symbol. When the valve is switched off – no supply voltage, no enable, current signal (code S) < 3,8 mA – zero lap valves take the power down position (approximately 10 % opening) according to the ordering code. For valves with overlap spools, neutral position and power down position are the same (zero position).
Supply pressure must be ensured before valve
is energized.
Solenoid Current Monitoring
If the actuator current time interval exceeds 10 seconds, the actuator is switched off to prevent overheating. For normal operating conditions this state will not reached, but it may occur with a con­taminated sluggish valve.
In this case the reason for the contamination
should be rectified (hydraulic fluid exchange,
filtration review, valve flushing). The overcurrent shutoff condition may be resetted by the actions below:
Code 0: Temporary disconnection of the supply voltage.
Code 5: Temporary disconnection of the enable signal.
Code 7: Temporary disconnection of the enable signal.
The shutoff of the VCD actuator due to over-
load will be indicated via the diagnostics
output.
ProPxD parameterizing software
The ProPxD software permits comfortable param­eter setting. Via the clearly arranged entry mask the parameters can be noticed and modified. Storage of complete parameter sets is possible as well as printout or record as a text file for further documentation.
The PC software can be downloaded free of charge at www.parker.com/euro_hcd – see page “Support” or directly at www.parker.com/propxd. Please check periodical for updates.
Page 16
16
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Program installation
Please check before installation if the above hard­ware requirements are met. If your PC has already stored an older version of the “ProPxD” program, it has to be deinstalled by using the Windows® ­system control feature.
Program installation sequence:
• terminate the execution of other programs
• execute the file “setup.exe”
• follow the instructions on the screen Answer the question, if an older version should be overwritten, with “ok”. During the installation you may change destination drive respectively instal­lation path, if needed.
Please answer “ok” if at the end of the installation the program reports any system information. After successful installation the desktop display shows the ProPxD icon for starting the program.
Software Operating
Brief instruction for first startup:
Connect the valve electronic to the supply voltage.
• Connect the valve electronic to a PC via the parametrizing cable.
• Start the operating program.
• After displaying the program respectively data base version a program window opens and the connected valve will be automatically identified (possibly a manual identification via the button “Receive all” is necessary).
• Select the desired version via the menu “Op­tions/Optionen” with the menu item “Language/ Sprache”.
The valve specific default parameters are already available within the parameter table.
• Parameter changes are possible via mouse or the arrow buttons on the bottom left within the program screen, also the parameter values may be edited via the keyboard.
Modified parameters will be stored via the “Enter” key or via the button “Update list”.
• Parameters have to be nonvolatile stored on the valve via the button “save parameter”.
The chosen parameters may be optionally stored on the PC via the “File”-menu with the menu item “Save as”, data retrieving is always possible via the function “Load file”
Extended functions:
The user software is segmented into 2 parameter ranges:
• basic mode
• expert mode For normal startup the basic mode is sufficient. It permits the setting of all application specific pa­rameters to match the valve function with the task setting.
In case of special applications the valve parameters may be adapted via the expert mode. The operating mode may be selected from the “Options”- menu and remains after terminating and re-start of the program.
Changing of expert parameters is only permit-
ted for qualified personnel. Incorrect settings may lead to malfunction! In case of parameter changes shut the drive down!
To prevent an unauthorized access for the expert mode, a password is requested. The name is “parker” and cannot be changed. Thus additionally to the button “Default” for loading of the default param­eters, the button “Send parameter” appears in the “Expert”-operating mode. This button transmits only the setting of one single parameter to the connected valve. Thus a quick tuning of single parameters is permitted during the setup.
A horizontal bar graph readout between
the communication buttons shows the data transfer state.
Because the ProPxD program has also
without connection to the valve functionality, a manual pre-selection of the parameters is possible. After selection of the valve type via the menu “Options” the parameters may be set and stored for later transmission.
Note the design series while selection of the
valve!
The “File” menu provides the functions “Printer setup”, “Print preview” and “Print”. The print preview includes the option for parameter set storage as text file (format.txt) prior to further processing. The “Options” menu provides also the selection of the RS232C interface port via the menu item “Port”. Via the menu item “Load file” previously stored parameter sets may be loaded.
Page 17
Prop. Directional Control Valve
Series DFplusOperation Manual
17
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
LED flashing signals of the valve electronics
enable valve OK: approx. 0.5 Hz (slowly, green)
disable valve OK: approx. 1 Hz (fast, green)
valve error: approx. 10 Hz (very fast, green)
Closer information can be can be displayed via the ProPxD Parametrier software.
LED
Error code
(additive)
Error description
0 no errors 1 over current 2 cable break command signal 4 cable break feedback signal
8 undervoltage error 16 bus communication error 32 hardware failure
Error code
Page 18
18
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
P1
Adjustment of zero position shifting (offset). To compensate for unbalances.
P3
MAX +
Adjustment of maximum signal span for positive output signal. To match the command signal span to the valve operating range.
P4
MAX -
Adjustment of maximum signal span for negative output signal. To match the command signal span to the valve operating range.
P7
MIN +
Adjustment of stroke step for valve side A at min. operating threshold. To compensate for the overlap of the valve spool.
P8
MIN -
Adjustment of stroke step for valve side B at min. operating threshold. To compensate for the overlap of the valve spool.
E17
option command
Adjustment of the command signal option. To match the command signal input to the input signal mode.
E19
cable break detection command
Adjustment of the operating mode for the command cable break detection. To turn on resp. off of the cable break detection of the command signal at a selected command signal option of 4...20 mA.
E25
operating threshold
Adjustment of the MIN operating threshold. To match the response sensitivity for the MIN-stroke step.
Individual Description of Basic Parameters
Parameter overview for basic mode
Parameter Description Unit
Parameter Range Default
Setting
Comment
from up to
P1 Zero adjust % -90.0 90 0.0 P3 MAX channel A % 50.0 100.0 100.0 P4 MAX channel B % 50.0 100.0 100.0 P7 MIN channel A % 0.0 50.0 0.0 P8 MIN channel B % 0.0 50.0 0.0
E17 option command
1 = ±10 V
2 = ±20 mA
3 = 4-20 mA
5 = ±10 mA
1 = ±10 V
only displayed,
not adjustable
E19
cable break detection
command
0
0 (±10 V /
±20 mA)
0/1
code S0 only,
only displayed,
not adjustable
1 (4...20 mA)
E25 MIN operating threshold 0.01 % 50 200 100
Adjustment parameters
The available parameters may be divided into multiple groups and are characterized by different letters:
S-parameters P-parameters J-parameters
Page 19
Prop. Directional Control Valve
Series DFplusOperation Manual
19
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Parameter Description Unit
Parameter Range
Default Setting
Comment
from up to
J8
Min supply voltage
supervision
V
17 28
18
J9
Relay time out off range
min supply voltage
ms
0 3200
1000
J12 Errorhandling
0 = no fault acknowled-
gement necessary;
255 = fault acknowled-
gement necessary;
768 = no fault acknowled-
gement + fault report about diag­nosis;
1023 = fault acknowledge-
ment + fault report about diagnosis
768
J8
Min supply voltage supervision
Adjustment of the minimal supply voltage: Below this supply voltage the valve switches off with an error message.
J9 Relay time out off range min supply voltage
Adjustment of the runtime monitoring: The supply voltage must be at least constantly before the valve is ready for operation.
J12 Errorhandling
Adjustment of the fault response or report: 0 = no fault acknowledgement necessary 255 = fault acknowledgement necessary 768 = no fault acknowledgement + Fault report about diagnosis 1023 = fault acknowledgement + Fault report about diagnosis
Overview for additional expert mode parameter
Individual description of additional expert parameters
Page 20
20
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
Failure message Description/corrective action
The Com Port is not available! Terminate the other program, or quit the message and select
another RS232C port via the menu “Options > Port”. Afterwards reconnect the parametrizing cable.
Unable to open COM port Com port is not available. Quit the message and select another
RS232C port via the menu “Options > Port”. Afterwards reconnect the parametrizing cable.
There is no module/valve con­nected or the communication is disturbed! Please check also the interface!
No data exchange possible. Either the electronic has been re­moved, the port is mismatched, or the connection will be disturbed by strong electrical fields. Check if the Com port is set for “9600, 8,
1. none, none” via the menu “Options > Port”.
Wrong password Retype the password, notice the exact spelling (case sensitivity).
Wrong input An unvalid character or a value outside the permitted range has
been used at parameter entry.
Keep the entered param­eters?
During parameter loading from the electronics memory the preset parameters from the left hand screen display may be rejected or maintained.
The chosen module/valve isn´t the same as the con­nected hardware. Attention! Unsaved parameters will be lost.
In principle, parameters dedicated to a type which deviates from the connected valve may be edited. However, for data transmitting the correct valve has to be connected. If parameters will be loaded from a valve which deviates from the selected one, the param­eters from the left hand side screen display of the program will be overwritten.
The chosen hardware isn´t the same as the connected module/valve.
The wrong valve type has been selected from the database, after­wards the function “send all” has been executed.
Attention! Factory settings will be changed! Transmit anyhow?
Default parameters has been read out from the database instead from the valve via the function “receive all”.
file name.pxd already exists. Do you want to replace the file?
The file name already exists within the indicated directory. Select another name, another directory or overwrite the existing file with “OK”.
Error messages
Malfunctions when using the ProPxD software program will be indicated via appropriate failure messages.
Failure messages and corrective actions:
Air Bleeding of Hydraulic System
During initial startup, after an oil change as well as after the opening of lines or valves the hydraulic system must be air bleeded.
Filter
The function and lifetime of the valve are strongly affected by the cleanliness of the fluid.
Purity level class of 18/16/13 acc. ISO4406 is required.
Flushing
It is recommended to flush the pipelines by short circuiting the pressure and return lines. This prevents the installation dirt from entering the valve.
Page 21
Prop. Directional Control Valve
Series DFplusOperation Manual
21
Parker Hannifin Corporation
Hydraulic Controls Division
D_F_30 5715-687 UK.indd CM 03.08.17
6. Trouble Shooting
Basis of troubleshooting is always a systematic approach.
For suspect of a sluggish spool the valve may
be flushed with clean pressure fluid.
7. Accessories / Spare Parts
Accessories
The following accessories are available for the valve series DFplus:
Bolt kit
D1FE/D1FP ordering code BK 375 D3FE/D3FP/D30FP ordering code BK 385
Female connection
Code 0: 6+PE ordering code 5004072 Code 5: 11-PE ordering code 5004711 Code 7: 6-PE ordering code 5004072
Spare Parts
Seal kit NBR
D1FE/D1FP ordering code SK-D1FP D3FE/D3FP/D30FP ordering code SK-D3FP
Hotline in Europe
Phone: 00800-2727-5374
Please direct technical product enquiries to:
Parker Hannifin Manufacturing Germany GmbH & Co. KG
Hydraulic Controls Division Europe Gutenbergstr. 38 41564 Kaarst, Germany Tel.: (+49) 181 99 44 43 0 E-mail: valveshcd@parker.com
malfunction at hydraulic load runtime
- generally no function
- high frequent oscillation
- low frequent oscillation
- one way operation only
- speed variations at unchanging command
- different speeds depending on travel direction
- speed too low
- drifting without command
- poor dynamic
possible reasons for malfunction corrective actions
X hydraulic pump resp. motor defective replace hydraulic pump resp. motor X X X X X X X drive overloaded reduce pressure resp. speed, increase valve size X X X X X X X X valve contaminated clean pressure fluid, filter / flush valve
X X X hydraulic fluid too viscous / too cold change fluid grade, provide operational temperature
X X X too low oil level within tank refill pressure fluid
X X X filter contaminated replace filter
X X X X supply voltage too low keep supply voltage range
X supply voltage carries too much ripple reduce ripple
X X X command signal too low increase command signal
X command signal carries too much ripple reduce ripple
X X center position adjustment incorrect check center position adjustment X X X X X contacts of central connector contaminated clean contacts / replace plug X feed cable interrupted fix feed cable X X X X X X X wiring sequence incorrect correct wiring sequence
X X feed cable without shielding change cable grade
X pilot pressure too low or failed increase pilot pressure to min. 20 bar
X X X pilot pressure too low increase pilot pressure to min. 20 bar
X pilot pressure too low increase pilot pressure to min. 50 bar
Troubleshooting in a hydraulic system requires