Parker Compax3, Compax3 I11 T11, Compax3 S025 V2, Compax3 S038 V4, Compax3 S063 V2 Operating Instructions Manual

...
Page 1
Electromechanical Automation
Operating instructions Compax3 I11 T11
Positioning via digital I/Os
I11 T11 192-120101 N6 - March 2004
Release 1/2004 (as from firmware V2.03)
We reserve the right to make technical changes. 10.03.04 09:06 I11 T11 192-120101 N6 - March 2004 The data correspond to the technical state at the time of printing.
Page 2
Introduction
____________________________
Copyright © 2003 Parker Hannifin GmbH EME All rights reserved.
Microsoft Word, Microsoft Office, Windows®, Window 95™, Window 98™, Windows NT®, Window 2000™, Window XP™ and MS-DOS™ are trademarks of Microsoft Corporation.
EME - Electromechanical Automation Europe
Germany:
England:
Italy:
Parker Hannifin GmbH Electromechanical Automation Postfach: 77607-1720 Robert-Bosch-Str. 22 D-77656 Offenburg Tel.: +49 (0)781 509-0 Fax: +49 (0)781 509-176
E-mail: sales.hauser@parker.com mailto:sales.hauser@parker.com Internet: www.parker-eme.com http://www.parker-eme.com
Parker Hannifin plc Electromechanical Automation 21 Balena Close Poole, Dorset England, BH17 /DX UK Tel.: +44 (0)1202 69 9000 Fax: +44 (0)1202 69 5750
E-mail: sales.digiplan@parker.com mailto:sales.digiplan@parker.com Internet: www.parker-eme.com http://www.parker-eme.com
Parker Hannifin S. p. A Electromechanical Automation Via Gounod 1 I-20092 Cinisello Balsamo (MI), Italy Tel.: +39 (0)2660 12459 Fax: +39 (0)2660 12808
E-mail: sales.sbc@parker.com mailto:sales.sbc@parker.com Internet: www.parker-eme.com http://www.parker-eme.com
EMN - Electromechanical Automation North America
USA:
Parker Hannifin Corporation Electromechanical Automation 5500 Business Park Drive Rohnert Park, CA 94928 Phone #: (800) 358-9068 FAX #: (707) 584-3715
E-mail: CMR_help@parker.com mailto:CMR_help@parker.com Internet: www.compumotor.com http://www.compumotor.com
Page 3
Parker EME
Device assignment
New Compax3 functions
Contents
1. Introduction .............................................................................................7
1.1 Device assignment .................................................................................. 7
1.2 Type specification plate .......................................................................... 8
1.3 Release 1/2004 ......................................................................................... 9
1.3.1. New Compax3 functions ................................................................................... 9
1.3.1.1 Direct drives ............................................................................................ 9
1.3.1.2 Switching frequency of the power output stage can be set .................... 9
1.3.1.3 Predefined external setpoint value optimized via analogue input........... 9
1.3.1.4 UL certification ........................................................................................ 9
1.3.1.5 New machine zero modes .................................................................... 10
1.3.1.6 RS485 / RS232 interface ...................................................................... 10
1.3.2. New functions of the Compax3 software tools............................................. 10
1.3.2.1 C3 ServoManager: configuration, setup and optimization of
Compax3............................................................................................... 10
1.3.2.2 C3 MotorManager: configuration of almost any motors........................ 11
1.3.2.3 C3 IEC61131-3 - Debugger .................................................................. 11
1.3.2.4 CoDeSys - IEC61131-3 - development tool.......................................... 11
1.3.2.5 CamEditor: cam creation for C3 T40 .................................................... 11
1.3.3. Complements / corrections in manual and online help ............................... 11
1.4 Safety Instructions................................................................................. 12
1.4.1. General hazards ............................................................................................... 12
1.4.2. Safety-conscious working .............................................................................. 12
1.4.3. Special safety instructions ............................................................................. 13
1.5 Warranty conditions .............................................................................. 13
1.6 Conditions of utilization ........................................................................ 14
1.6.1. Conditions of utilization for CE-conform operation..................................... 14
1.6.2. Conditions of utilization for UL permission.................................................. 16
2. Compax3 I11 T11: Positioning via digital I/Os.....................................17
3. Compax3 device description................................................................19
3.1 Plug and connector assignment Compax3.......................................... 20
3.1.1. Function of the LEDs on the front panel ....................................................... 21
3.1.2. Power supply plug X1 for 230VAC devices................................................... 21
3.1.3. Power supply plug X1 for 400 VAC devices.................................................. 22
3.1.4. Ballast resistor / high voltage supply plug X2 for 230VAC devices........... 22
3.1.5. Ballast resistor / high voltage supply plug X2 for 400VAC devices........... 23
3.1.6. Motor / Motor brake (plug X3)......................................................................... 24
3.1.7. Control voltage 24VDC / enable (plug X4) ..................................................... 25
3.1.8. RS232 / RS485 interface (plug X10) ............................................................... 26
I11 T11 192-120101 N6 - March 2004 3
Page 4
Introduction
New Compax3 functions
3.1.9. Analog / Encoder (plug X11)........................................................................... 27
3.1.9.1 Wiring of the analog input ..................................................................... 27
3.1.9.2 Wiring of analog outputs ....................................................................... 27
3.1.10. Digital inputs/outputs (plug X12) ................................................................... 28
3.1.10.1 Input wiring of digital inputs................................................................... 28
3.1.10.2 Output wiring of digital outputs.............................................................. 29
3.1.11. Resolver / Feedback (connector X13)............................................................ 29
3.2 Installation and dimensions Compax3................................................. 31
3.2.1. Installation and dimensions of Compax3 S0xx V2....................................... 31
3.2.2. Installation and dimensions of Compax3 S038 and S075 V4...................... 32
3.2.3. Installation and dimensions of Compax3 S150 V4....................................... 33
3.2.4. Installation and dimensions of Compax3 S300 V4....................................... 34
4. Setting up Compax3..............................................................................35
4.1 Configuration ......................................................................................... 35
4.1.1. Motor selection ................................................................................................ 37
4.1.2. Optimize motor reference point and switching frequency of the
power output stage.......................................................................................... 38
4.1.3. Ballast resistor ................................................................................................. 39
4.1.4. General drive .................................................................................................... 40
4.1.5. Defining the reference system ....................................................................... 40
4.1.5.1 Measure reference................................................................................ 41
4.1.5.2 Machine reference modes (MN-Ms) ..................................................... 44
4.1.5.3 Adjusting the machine zero proximity switch ........................................ 48
4.1.5.4 Software end limits................................................................................ 49
4.1.6. Defining jerk / ramps ....................................................................................... 50
4.1.6.1 Ramp upon error / deenergize ............................................................. 51
4.1.7. Limit and monitoring settings ........................................................................ 52
4.1.7.1 Current Limit ......................................................................................... 52
4.1.7.2 Positioning window - Position reached ............................................... 52
4.1.7.3 Tracking error limit ................................................................................ 53
4.1.8. Encoder simulation ......................................................................................... 54
4.1.9. Positioning ....................................................................................................... 55
4.1.9.1 Operating modes .................................................................................. 56
4.1.9.2 Define positioning data records ............................................................ 59
4.1.9.3 Dynamic positioning.............................................................................. 62
4.1.10. RS485 setting values....................................................................................... 62
4.1.11. Configuration name / comments.................................................................... 63
4.2 Test commissioning Compax3 ............................................................. 64
4.3 Device status.......................................................................................... 66
4.4 Optimization ........................................................................................... 68
4.4.1. Control dynamics ............................................................................................ 68
4.4.1.1 Stiffness of the speed controller ........................................................... 69
4.4.1.2 Damping of the speed controller ........................................................... 70
4.4.1.3 Filter for speed value ............................................................................ 70
4.4.1.4 Advanced control parameters............................................................... 71
4.4.2. Commissioning mode ..................................................................................... 75
4.4.3. Turning the motor holding brake on and off................................................. 76
Page 5
Parker EME
Device assignment
New Compax3 functions
5. RS232 & RS485 – interface record .......................................................77
5.1 ASCII - record......................................................................................... 77
5.2 Binary record.......................................................................................... 79
6. Status values.........................................................................................82
6.1 Device ..................................................................................................... 83
6.2 Motor....................................................................................................... 83
6.3 Positions................................................................................................. 84
6.4 Speeds .................................................................................................... 85
6.5 Currents.................................................................................................. 87
6.6 Inputs ...................................................................................................... 88
6.7 CAM......................................................................................................... 89
6.8 IEC61131-3.............................................................................................. 90
6.9 Transmitter ............................................................................................. 91
7. Error .......................................................................................................92
7.1 Error list.................................................................................................. 92
8. Compax3 Accessories ........................................................................105
8.1 Order code for Compax3..................................................................... 105
8.2 Accessories order code ...................................................................... 106
8.3 Parker servo motors ............................................................................ 108
8.3.1. Direct drives ................................................................................................... 108
8.3.1.1 Transmitter systems for direct drives .................................................. 108
8.3.1.2 Linear motors ...................................................................................... 109
8.3.1.3 Torque motors..................................................................................... 109
8.3.2. Rotary servo motors...................................................................................... 110
8.3.2.1 Motor data table for standard motors.................................................. 113
8.3.2.2 Holding brake ...................................................................................... 114
8.3.2.3 Pulse encoder systems ....................................................................... 114
8.3.2.4 Dimensions of the SMH(A)-motors ..................................................... 115
8.3.2.5 Dimensions of the MH(A)105-motors ................................................. 116
8.3.2.6 Dimensions of the MH(A)145 and MH(A)205 motors ......................... 117
8.3.2.7 Order code for SMH/MH motors ......................................................... 118
8.4 Connections to the motor ................................................................... 119
8.4.1. Resolver cable................................................................................................ 119
8.4.2. SinCos cable .................................................................................................. 120
8.4.3. Overview of motor cables ............................................................................. 120
8.4.4. Motor cable with plug.................................................................................... 121
8.4.5. Motor cable for terminal box ........................................................................ 122
I11 T11 192-120101 N6 - March 2004 5
Page 6
Introduction
New Compax3 functions
8.5 EMC measures ..................................................................................... 123
8.5.1. Mains filter ...................................................................................................... 123
8.5.1.1 Mains filter NFI01/01 ........................................................................... 123
8.5.1.2 Mains filter NFI01/02 ........................................................................... 124
8.5.1.3 Mains filter for NFI01/03...................................................................... 124
8.5.2. Motor output filter.......................................................................................... 125
8.5.2.1 Motor output filter MDR01/04.............................................................. 125
8.5.2.2 Motor output choke MDR01/01........................................................... 125
8.5.2.3 Motor output choke MDR01/02........................................................... 126
8.5.2.4 Wiring of the motor output filter........................................................... 126
8.6 External ballast resistors .................................................................... 127
8.6.1. BRM8/01 ballast resistors ............................................................................. 128
8.6.2. BRM5/01 ballast resistor ............................................................................... 128
8.6.3. Ballast resistor BRM6/02............................................................................... 128
8.6.4. Ballast resistor BRM4/0x............................................................................... 129
8.7 Operator control module BDM............................................................ 130
8.8 EAM06 terminal block for inputs and outputs................................... 131
8.9 ZBH plug set......................................................................................... 134
8.10 Interface cable...................................................................................... 135
8.10.1. RS232 cable.................................................................................................... 135
8.10.2. RS485 cable to Pop ....................................................................................... 136
8.10.3. I/O interface X12............................................................................................. 137
8.10.4. Ref X11............................................................................................................ 138
8.10.5. Encoder cable ................................................................................................ 139
9. Technical Data.....................................................................................140
10.Index.....................................................................................................147
Page 7
Parker EME
1. Introduction
In this chapter you can read about:
Device assignment ...........................................................................................................................7
Type plate ........................................................................................................................................8
Release 1/2004 ................................................................................................................................9
Safety instructions ..........................................................................................................................12
Warranty conditions........................................................................................................................13
Conditions of utilization...................................................................................................................14
1.1 Device assignment
This manual applies to the following devices:

Introduction

! Compax3 S025 V2 + supplement ! Compax3 S063 V2 + supplement ! Compax3 S038 V4 + supplement ! Compax3 S075 V4 + supplement ! Compax3 S150 V4 + supplement
! Compax3 S300 V4 + supplement
With the supplement:
! F10 (Resolver)
! F11 (SinCos) ! F12 (linear and rotary direct drives)
! I11 T11
I11 T11 192-120101 N6 - March 2004 7
Page 8
Introduction
1.2 Type specification plate
You will find the exact description of the device on the type specification plate, which is located on the right side of the device:
Compax3 - Type
specification plate:
1
10
2
3
4
56
Explanation:
1 Type designation
The complete order designation of the device (2, 5, 6, 10, 9)
C3S025V2
2
C3: Abbreviation for Compax3
S: Single axis device with direct AC mains power supply
025: Device current drain in 100mA (025=2.5A)
V2: 230VAC (single phase); V4: 400VAC (three phase)
3 Unique number of the particular device
4 Nominal power supply voltage of the device
5 Designation of the feedback system
F10: Resolver
F11: SinCos© / Single- or Multiturn
F12: Feedback module for direct drives
6 Device interface
I10: Analog, Step/Direction and Encoder Input
I11: Digital inputs/outputs
I20: Profibus DP
I21: CANopen
7 Corresponding fuse protection
8 Date of factory test
9 Options
10 Technology function
T10: Servo Controller
T11: Positioning
T30: Motion control programmable according to IEC61131-3
T40: Electronic cam control
9
8
7
Page 9
Parker EME
1.3 Release 1/2004
In this chapter you can read about:
New Compax3 functions...................................................................................................................9
New functions of the Compax3 software tools ................................................................................10
Complements / corrections in manual and online help ....................................................................11

1.3.1. New Compax3 functions

In this chapter you can read about:
Direct drives .....................................................................................................................................9
Switching frequency of the power output stage can be set................................................................9
Optimization of the predefined external setpoint via the analog input................................................9
UL certification..................................................................................................................................9
New machine zero modes ..............................................................................................................10
RS485 / RS232 interface ................................................................................................................10
Introduction
1.3.1.1 Direct drives
The feedback module F12 supports the following feedback systems:
! Distance coding with 1VSS - Interface ! Distance coding with RS422 - Interface (Encoder)
1.3.1.2 Switching frequency of the power output stage can be set
The switching frequency of the power output stage (see on page 38) can be increased if necessary. This helps mainly to reduce motor sounds.
Please note that power output stage losses increase with rising switching frequency. Therefore the nominal device currents must be reduced.
1.3.1.3 Predefined external setpoint value optimized via analogue input
Given an external discrete signal read in via the analog input (possible with I10 T10 and T40), signal steps can only be avoided by averaging.
1.3.1.4 UL certification
Compax3 now with UL certification. (see on page 16)
I11 T11 192-120101 N6 - March 2004 9
Page 10
Introduction
1.3.1.5 New machine zero modes
! Several new machine zero modes with limit switch: MN-Mode 1,2 7-10, 11-14,
17,18, 23-26, 27-30
! New machine zero modes in connection with the feedback module F12 F12
(direct drives) and distance coded feedback system: MN-Mode 130 - 133
! Limit switch can be configured
1.3.1.6 RS485 / RS232 interface
Compax3 objects can be read in and written via RS232 and RS485 (see on page
77).

1.3.2. New functions of the Compax3 software tools

In this chapter you can read about:
C3 ServoManager: configuring Compax3, setup and optimization..................................................10
C3 MotorManager: configuration of almost any motors...................................................................11
C3 IEC61131-3 - Debugger............................................................................................................11
CoDeSys - IEC61131-3 – development tool .................................................................................11
CamEditor: Cam creation for C3 T40..............................................................................................11
1.3.2.1 C3 ServoManager: configuration, setup and optimization of Compax3
A modified recipe array can be loaded separately (without complete download) into the device.
Firmware - Download
The Compax3 firmware can only be modified resp. updated with the aid of the C3 ServoManager.
For this you will need a so-called “firmware-package“ (File: .*.fwp).
Setup support
You can set up all Compax3 technology functions easily in the optimization window.
Page 11
Parker EME
1.3.2.2 C3 MotorManager: configuration of almost any motors
New:
! Integration of distance coded feedback systems ! Export / Import of user defined (customer’s) motor ! Calibration of commutation also for linear motors with small travel path
Changes
! Linear motors with brakes can be configured ! Calculation of the recommended number of poles was corrected ! Calibration of SinCos motors was corrected ! The minimum moment of inertia was reduced from 10kgmm ! Configuration of rotatory motors with analog hall sensors was completed
1.3.2.3 C3 IEC61131-3 - Debugger
2
to 1kgmm
Introduction
2
Forcing of the inputs for T30 and T40 is possible.
1.3.2.4 CoDeSys - IEC61131-3 - development tool
New CoDeSys version 2.3.2.6
1.3.2.5 CamEditor: cam creation for C3 T40
-

1.3.3. Complements / corrections in manual and online help

New structure of the manual:
! All technology functions are described in a help. ! Manuals (PDF files) have a new structure:
! I10 T10 manual ! I11 T11 manual ! I20 T11 manual ! I21 T11 manual ! A single manual for all devices programmable according to IEC
(I11 T30, I20 T30, T21 T30, I11 T40, I20 T40, I21 T40) The assignment of the respective chapters is indicated.
I11 T11 192-120101 N6 - March 2004 11
Page 12
Introduction
1.4 Safety Instructions
In this chapter you can read about:
General hazards.............................................................................................................................12
Working safely................................................................................................................................12
Special safety instructions ..............................................................................................................13
1.4.1. General hazards
General Hazards on Non-Compliance with the Safety Instructions
The device described in this manual is designed in accordance with the latest technology and is safe in operation. Nevertheless, the device can entail certain hazards if used improperly or for purposes other than those explicitly intended.
Electronic, moving and rotating components can
! constitute a hazard for body and life of the user, and ! cause material damage
Usage in accordance with intended purpose
The device is designed for operation in electric power drive systems (VDE0160). Motion sequences can be automated with this device. Several motion sequences can be can combined by interconnecting several of these devices. Mutual interlocking functions must be incorporated for this purpose.
1.4.2. Safety-conscious working
This device may be operated only by qualified personnel. Qualified personnel in the sense of these operating instructions consists of:
! Persons who, by virtue to their training, experience and instruction, and their
knowledge of pertinent norms, specifications, accident prevention regulations and operational relationships, have been authorized by the officer responsible for the safety of the system to perform the required task and in the process are capable of recognizing potential hazards and avoiding them (definition of technical personnel according to VDE105 or IEC364),
! Persons who have a knowledge of first-aid techniques and the local emergency
rescue services.
! Persons who have read and will observe the safety instructions. ! Those who have read and observe the manual or help (or the sections pertinent
to the work to be carried out).
This applies to all work relating to setting up, commissioning, configuring, programming, modifying the conditions of utilization and operating modes, and to maintenance work.
This manual and the help information must be available close to the device during the performance of all tasks.
Page 13
Parker EME

1.4.3. Special safety instructions

! Check the correct association of the device and its documentation. ! Never detach electrical connections while voltage is applied to them.
! Safety devices must be provided to prevent human contact with moving or
rotating parts.
! Make sure that the device is operated only when it is in perfect condition. ! Implement and activate the stipulated safety functions and devices.
! Operate the device only with the housing closed. ! Ensure that motors and any linear drives present are mounted securely. ! Check that all live terminals are secured against contact. Fatal voltage levels of to
750V occur.
1.5 Warranty conditions
! The device must not be opened. ! Do not make any modifications to the device, except for those described in the
manual.
! Make connections to the inputs, outputs and interfaces only in the manner
described in the manual.
! When installing the device, make sure the heat dissipater receives sufficient air. ! Attach the devices according to the mounting instructions, using the provided
fixing holes. We cannot provide any guarantee for any other mounting methods.
Introduction
Note on exchange of options
Compax3 options must be exchanged in the factory to ensure hardware and software compatibility.
I11 T11 192-120101 N6 - March 2004 13
Page 14
Introduction
r

1.6 Conditions of utilization

1.6.1. Conditions of utilization for CE-conform operation

- Industry and trade -
The EC guidelines for electromagnetic compatibility 89/336/EEC and for electrical operating devices for utilization within certain voltage limits 73/23/EEC are fulfilled when the following boundary conditions are observed:
Operation of the devices only in the condition in which they were delivered,
i.e. with all housing panels.
Mains filter:
Motor and resolve
cable:
A mains filter is required in the mains input line if the motor cable exceeds a certain length. Filtering can be provided centrally at the plant mains input or separately at the mains input to each device.
Commercial and residential area (limit values of Class A in accordance with EN 61800-3)
The following mains filters are available for independent utilization:
Device: Compax3 Order No.: Condition:
S0xx V2: NFI01/01 Only for motor lines longer than 10m
S038, S075, S150 V4: NFI01/02 Only for motor lines longer than 10m
S300 NFI01/03 Only for motor lines longer than 10m
Industrial area (limit values in accordance with EN 61800-3)
Longer motor cable lengths are possible in industrial areas without a mains power filter.
Connection length: connection between mains filter and device:
unscreened: < 0.5m shielded: < 5m (fully shielded on ground – e.g. ground of control cabinet)
Operation of the devices only with Parker motor and resolver cables (their
plugs contain a special full surface area screening).
The following cable lengths are permitted:
Motor cable
< 100 m (the cable should not be rolled up!) A motor output filter is required for motor cables >20 m.
! MDR01/04 (max. 6.3A rated motor current) ! MDR01/01 (max. 16A rated motor current) ! MDR01/02 (max. 30A rated motor current)
Page 15
Parker EME
Introduction
Screening connection of the motor cable
The motor cable should be fully screened and connected to the Compax3 housing. We offer a special shield connecting terminal as accessory item (see on page
134).
Resolver cable
Motors:
Control:
Grounding:
Cable installation:
Accessories:
Warning:
< 100 m
Operation with standard motors.
Use only with aligned controller (to avoid control loop oscillation).
Connect the filter housing and the Compax3 (grounding screw on the underside) to the cabinet frame, making sure that the contact area is adequate and that the connection has low resistance and low inductance.
Never mount the filter housing and the device on paint-coated surfaces!
Signal lines and power lines should be installed as far apart as possible. Signal leads should never pass close to excessive sources of interference (motors,
transformers etc.).
Make sure to use only the accessories recommended by Parker
Connect all cable shields at both ends, ensuring large contact areas!
This is a product in the restricted sales distribution class according to EN
61800-3. In a domestic area this product can cause radio frequency
disturbance, in which case the user may be required to implement
appropriate remedial measures.
I11 T11 192-120101 N6 - March 2004 15
Page 16
Introduction

1.6.2. Conditions of utilization for UL permission

UL certification
conform to UL:
Certified
! according to UL508C ! E-File_No.: E235 342
The UL certification is documented by a “UL” logo on the device (type specification plate)
“UL“ logo
Conditions of utilization
! The devices are only to be installed in a degree of contamination 2 environment
(maximum).
! The devices must be appropriately protected (e.g. by a switching cabinet). ! The terminals are suitable for field wiring. ! Tightening torque of the field wiring terminals (green Phoenix plugs)
! C3SxxxV2 0.57-0.79Nm 5 - 7Lb.in ! C3SxxxV4 exept C3S300V4 0.57-0.79Nm 5 - 7Lb.in
! C3S300V4 1.25-1.7Nm 11 - 15Lb.in
! Temperature rating of field installed conductors shall be at least 60°C Use
copper conductors only Please use the cables described in the accessories chapter ( see on page 105) they do have a temperature rating of at least 60°C.
! Maximum ambient temperature: 45°C. ! Suitable for use on a circuit capable of delivering not more than 500 rms
symmetrical amperes, 400 volts maximum.
ATTENTION Danger of electric shock. Discharge time of the bus capacitator is 5 minutes.
! The drive provides internal motor overload protection.
This must be set so that 200% of the nominal motor current are not exceeded.
! Cable cross-sections
! Mains input: corresponding to the recommended fuses (see on page 140) ! Motor cable: ( see on page 121) corresponding to the nominal output
currents (see on page 140)
! Maximum cross-section limited by the terminals mm
! C3SxxxV2 2.5mm
! C3SxxxV4 exept C3S300V4 4.0mm ! C3S300V4 6.0mm
! Circuit protection
2
2
2
2
/ AWG
AWG 12
AWG 10 AWG 7
In addition to the branch circuit protection, the devices have to be protected with the supplementary protector S 261 L, manufactured by ABB.
! C3S025V2: ABB, nom 400V 10A, 6kA ! C3S063V2: ABB, nom 400V, 16A, 6kA ! C3S038V4: ABB, nominal 400V, 10A, 6kA ! C3S075V4: ABB, nominal 400V, 16A, 6kA ! C3S150V4: ABB, nominal 400V, 20A, 6kA ! C3S300V4: ABB, nominal 400V, 25A, 6kA ! C3S300V4: ABB, nominal 400V, 25A, 6kA
Page 17
Parker EME
/

Compax3 I11 T11: Positioning via digital I/Os

2. Compax3 I11 T11: Positioning via digital I/Os
Due to its high functionality, the Positioning version of Compax3 forms an ideal basis for many applications in high-performance motion automation.
Up to 31 motion profiles (target position, speed, acceleration, retardation, jerk) can be programmed with the PC software. Positioning is triggered either via the parallel interface (digital inputs) as single positioning or as positioning sequence. For the positioning sequence the following motion profile is triggered by each START. The number of repetitions can be specified for each motion profile.
High-performance control technology and openness for various sender systems are fundamental requirements for a fast and high-quality automation of movement.
Model / standards
auxiliary material
The structure and size of the device are of considerable importance. Powerful electronics is an important feature which made it possible to manufacture the Compax3 so small and compact. All connectors are located on the front of the Compax3.
Internal mains filters permit connection of motor cables up to a certain length without requiring additional measures. EMC compatibility is within the limits set by EN 61800-3, Class A. The Compax3 is CE-conform.
The intuitive user interface familiar from many applications, together with the oscilloscope function, wizards and online help, simplifies making and modifying settings via the PC.
The optional Operator control module (BDM01/01 (see on page 130 )) for Compax3 makes it possible to exchange devices quickly without the need for a PC.
I11 T11 192-120101 N6 - March 2004 17
Page 18
Compax3 I11 T11: Positioning via digital I/Os
Operating modes
You can select between two operating modes:
! Absolute mode or ! Endless mode
Furthermore, you can activate the functions Manual+ and Manual- via a set-up mode.
Configuration
Configuration is made on a PC using the Compax3 ServoManager. Install the program on your PC and connect the PC to the Compax3 X 10 via the RS232 port.
Page 19
Parker EME

Compax3 device description

3. Compax3 device description
In this chapter you can read about:
Plug and connector assignment Compax3......................................................................................20
Installation and dimensions Compax3.............................................................................................31
I11 T11 192-120101 N6 - March 2004 19
Page 20
Compax3 device description
Conditions of utilization for UL permission

3.1 Plug and connector assignment Compax3

In this chapter you can read about:
Function of the LEDs on the front panel..........................................................................................21
Power supply plug X1 for 230VAC devices.....................................................................................21
Power supply plug X1 for 400VAC devices.....................................................................................22
Ballast resistor / High voltage supply plug X2 for 230VAC devices .................................................22
Ballast resistor / High voltage supply plug X2 for 400VAC devices .................................................23
Motor / Motor brake (plug X3).........................................................................................................24
Control voltage 24 VDC / enable (plug X4) .....................................................................................25
RS 232 / RS485 interface (plug X10)..............................................................................................26
Analog / Encoder (Plug X11) ..........................................................................................................27
Digital inputs/outputs (plug X12).....................................................................................................28
Resolver / Feedback (plug X13)......................................................................................................29
Connection assignment based on the example of Compax3 S025 V2:
X1 AC Versorgung AC supply
X2 Ballast / DC LS Ballast / DC HV
X3 Motor / Bremse Motor / Brake
X4 24VDC / Freigabe 24 VDC / Enable
X10 RS232 / RS485
X11 Analog/Encoder Analog/Encoder
X12 Ein-/Ausgänge Inputs/Outputs
X13 Geber Feedback
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after switching off the power supply!
Page 21
Parker EME
Plug and connector assignment Compax3
Caution!
When the control voltage is missing there is no indication whether or not high voltage supply is available.
3.1.1. Function of the LEDs on the front panel
State LED red LED green
Voltages missing off off
While booting alternately flashing
! No configuration present. ! SinCos feedback not detected. ! IEC program not compatible with the
firmware.
! For F12: Hall signals invalid.
Axis without current excitation off Flashes slowly

Function of the LEDs on the front panel

flashing off
Power supplied to axis; commutation calibration
off Flashes quickly
running
Axis with current excitation off on
Axis in fault status / fault present on off

3.1.2. Power supply plug X1 for 230VAC devices

PIN Description
1L
2N
3PE
Mains connection: Compax3 S0xx V2
Controller type S025 V2 S063 V2
Mains voltage
Rated input current
Maximum fuse rating per device
Single phase 230VAC + 10%
80-230VAC+10% / 50-60Hz
6Aeff 16Aeff
10A (automatic circuit breaker K)
16 A (automatic circuit breaker K)
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after switching off the power supply!
I11 T11 192-120101 N6 - March 2004 21
Page 22
Compax3 device description

Power supply plug X1 for 400 VAC devices

3.1.3. Power supply plug X1 for 400 VAC devices
PIN Description
1L1
2L2
3L3
4PE
Mains connection Compax3 Sxxx V4
Controller type S038 V4 S075 V4 S150 V4 S300 V4
Mains voltage
Rated input current
Maximum fuse rating per device
Three-phase 3*400VAC
80-480 VAC+10% / 50-60 Hz
6Aeff 10 Aeff 16Aeff 22Aeff
10A (automatic circuit breaker K)
16 A (automatic circuit breaker K)
25A (automatic circuit breaker K)
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after switching off the power supply!
3.1.4. Ballast resistor / high voltage supply plug X2 for 230VAC
devices
PIN Description
1 + Ballast resistor
2 - Ballast resistor
3PE
4 + DC high voltage supply
5 - DC high voltage supply
Caution! The connector assignment of X2 is changed!
Please note the screen printing on the front plate of the device: this is valid
Page 23
Parker EME

Ballast resistor / high voltage supply plug X2 for 400VAC devices

Plug and connector assignment Compax3
Brake operation Compax3 Sxxx V2
Controller type S025 V2 S063 V2
Capacitance / storable energy
Minimum ballast - resistance
Recommended nominal power rating
Pulse power rating for 1s
560µF / 15Ws 1120µF /30Ws 100 56
20 ... 60W 60 ... 180W
1kW 2.5kW
Caution!
The power voltage DC of two Compax3 V2 devices (230V devices) must not be connected.
3.1.5. Ballast resistor / high voltage supply plug X2 for 400VAC
devices
PIN Description
1 + Ballast resistor
2 - Ballast resistor
3PE
4 + DC high voltage supply
5 - DC high voltage supply
Caution! The connector assignment of X2 is changed!
Please note the screen printing on the front plate of the device: this is valid
Compax3 Sxxx V4 brake operation
Controller type S038 V4 S075 V4 S150 V4 S300 V4
Capacitance / storable energy
Minimum ballast ­resistance
Recommended nominal power rating
Pulse power rating for 1s
235µF / 37Ws 470µF / 75Ws 690µF /
110Ws
100 56 22 15
60 ... 250W 60 ... 500 W 60 ... 1000 W 60 ... 1000 W
2.5kW 5kW 10 kW 42kW
1100µF /
176Ws
I11 T11 192-120101 N6 - March 2004 23
Page 24
Compax3 device description

Motor / Motor brake (plug X3)

Connection of the power voltage of 2 Compax3 V4 devices (400V devices)
In order to improve the conditions during brake operation, the DC power voltage of 2 devices may be connected.
The capacity as well as the storable energy are increased; furthermore the braking energy of one device may be utilized by a second device, depending on the application.
Please connect as follows:
Device 1 X2/4 to device 2 X2/4 Device 1 X2/5 to device 2 X2/5
Please note the following:
Caution! In case of non-compliance with the following instructions, the device may be destroyed!
! You can only connect two similar devices (same power supply; same rated
currents)
! Connected devices must always be fed separately via the AC power supply.
3.1.6. Motor / Motor brake (plug X3)
PIN Description
1 U (motor)
2 V (motor)
3 W (motor)
4 PE (motor)
5 BR+ Motor holding brake
6 BR- Motor holding brake
Screening connection of the motor cable
The motor cable should be fully screened and connected to the Compax3 housing. We offer a special shield connecting terminal as accessory item (see on page
134).
Connect the brake only on motors which have a holding brake! Otherwise make no brake connections at all.
Motor holding brake output
Controller type Compax3
Voltage range
Maximum output current (short circuit proof)
Motor cable (see on page 121)
21 – 27VDC
1.6 A
Page 25
Parker EME

3.1.7. Control voltage 24VDC / enable (plug X4)

PIN Description
1 +24 V
2 Gnd24 V
3 Enable_in
4 Enable_out_a
5 Enable_out_b
Control voltage 24 VDC
Controller type Compax3
Voltage range
Current drain of the device
Total current drain
Ripple
Requirement according to safe extra low voltage (SELV)
21 - 27VDC
0.8 A
0.8 A + Total load of the digital outputs + current for the motor holding brake
0.5Vpp
yes
Compax3 device description
Power stage enable: X4/3=24 VDC
Tolerance range: 18.0 V – 33.6 V / 720
The +24V supply can be taken, for example, from Pin 1.
Safe standstill (X4/3=0V)
For implementation of the "Safe standstill" safety feature in accordance with the “protection against unexpected start-up“ described in EN1037. Please refer to the respective chapter (in the paper version “Installation Manual Compax3) with the respective circuitry examples!
The energy supply to the drive is reliably shut off, the motor has no torque. A relay contact is located between X4/4 and X4/5 (normally closed contact)
Enable_out_a - Enable_out_b Power output
stage is
Contact opened activated
Contact closed deactivated
Series connection of these contacts permits certain determination of whether all drives are de-energized.
Relay contact data:
Switching voltage (AC/DC): 100 mV – 60 V Switching current: 10 mA – 0.3 A
I11 T11 192-120101 N6 - March 2004 25
Page 26
Compax3 device description

3.1.8. RS232 / RS485 interface (plug X10)

Interface selectable by contact functions assignment of X10/1: X10/1=0V RS232 X10/1=5V RS485
RS232
PIN X10
1 (Enable RS232) 0V 2RxD 3TxD 4DTR 5GND 6DSR 7RTS 8CTS 9+5V
RS232 (Sub D)
RS485 2-wire
PIN X10
1 Enable RS485 (+5V) 2res. 3TxD_RxD/ 4res. 5GND 6res. 7TxD_RxD 8res. 9+5V
RS485 two wire (Sub D) Pin 1 and 9 jumpered externally
RS485 4-wire
PIN X10
1 Enable RS485 (+5V) 2RxD 3TxD/ 4res. 5GND 6res. 7TxD 8RxD/ 9+5V
RS485 four wire (Sub D) Pin 1 and 9 jumpered externally
Page 27
Parker EME

3.1.9. Analog / Encoder (plug X11)

PIN X11 Reference
High Density Sub D
1 +24V (output for encoder) max. 70mA
2 Reserved
3 D/A monitor channel 1 (±10V, 8-bit resolution)
4 D/A monitor channel 0 (±10V, 8-bit resolution)
5 +5V (output for encoder) max. 150mA
Compax3 device description
6
7
8
A/ (Encoder simulation)
A (Encoder simulation)
B (Encoder simulation)
9 Reserved
10 Reserved
11 Reserved
12
13
14
15 GND
B/ (Encoder simulation)
N/ (Encoder simulation)
N (Encoder simulation)
3.1.9.1 Wiring of the analog input
2.2K
10nF
10K
Ain+
Ain-
X11/9
X11/11
10K
2.2K
Ω Ω
10nF
3.1.9.2 Wiring of analog outputs
332
I11 T11 192-120101 N6 - March 2004 27
X11/4 X11/3
+/-10V/1mA (max: 3mA)
X11/15
Page 28
Compax3 device description
3.1.10. Digital inputs/outputs (plug X12)
The assignment of X12 depends on the operating mode "Normal or Commissioning Mode".
Only 4 motion profiles can be selected in commissioning mode. The inputs "Manual+" and "Manual-" are available for this.
PIN
X12/
1 O +24VDC output (max. 400mA)
2 O0 No fault
3 O1 Position reached (max. 100 mA)
4 O2 No power output stage current (max. 100mA)
5 O3 Motor stationary with current, with setpoint 0 (max. 100mA)
6I0 No stop
7 I1 Start (edge)
Input/output I/O /X12
High density/Sub D
Normal mode Commissioning mode
8
I2="1": Quit (positive edge) / Energize the motor
The address of the current positioning data record is newly read in.
I2="0": Motor deenergized with delay
9 I3 Address 0
10 I4 Address 1
11 I 24V input for the digital outputs Pins 2 to 5
12 I5 Address 2 Manual+
13 I6 Address 3 Manual-
14 I7 MN-Ini* / Address 4 MN-Ini*
15 O Gnd 24 V
*Machine home proximity switch only when the corresponding mode has been selected. 15 motion profiles (address 0-3) and machine zero run are then possible.
All inputs and outputs have 24V level. Maximum capacitive load on the outputs: 50 nF (max. 4 Compax3 inputs)
3.1.10.1 Input wiring of digital inputs
SPS/PLC
X12/1
X12/6
X12/15
22K
F2
22K
22K
10K
100K
F1
X4/1
X4/2
24V
0V
Page 29
Parker EME
The circuit example is valid for all digital inputs! F1: Delayed action fuse
F2: Quick action electronic fuse; can be reset by switching the 24VDC supply off and on again.
3.1.10.2 Output wiring of digital outputs
Compax3 device description
24V
0V
F1
X4/1
18.2K
X4/2
F2
X12/1
X12/11
X12/2
X12/15
The circuit example is valid for all digital outputs! The outputs are short circuit proof; a short circuit generates an error.
F1: Delayed action fuse F2: Quick action electronic fuse; can be reset by switching the 24VDC supply off
and on again.
3.1.11. Resolver / Feedback (connector X13)
PIN X13
Feedback /X13
High Density /Sub D (dependent on the Feedback Module)
Resolver (F10) SinCos (F11) Direct drives (F12)
SPS/
PLC
1 res. res. Sense -
2 res. res. Sense +
3 GND GND Hall1
4 REFres+ Vcc (+8V) Vcc (+5V) (controlled on the encoder
side) max. 200mA load
5 +5V (for temperature sensor) +5V (for temperature and hall
sensors)
6 CLKfbk CLKfbk Hall2
7 SIN- SIN- SIN- / A- (Encoder)
8 SIN+ SIN+ SIN+ / A+ (Encoder)
9 CLKfbk/ CLKfbk/ Hall3
10 Tmot Tmot Tmot
11 COS- COS- COS- / B- (Encoder)
12 COS+ COS+ COS+ / B+ (Encoder)
13 res. DATAfbk N+
14 res. DATAfbk/ N-
15 REFres- GND (Vcc) GND (Vcc)
I11 T11 192-120101 N6 - March 2004 29
Page 30
Compax3 device description
Note on F12:
+5V (Pin 4) is measured and controlled directly at the end of the line via Sense – and Sense +.
Maximum length of cable: 100m
Caution! Pin 4 and Pin 5 must under no circumstances be connected! Resolver cable (see on page 119) SinCos cable (see on page 120)
Page 31
Parker EME
Compax3 device description

3.2 Installation and dimensions Compax3

In this chapter you can read about:
Installation and dimensions Compax3 S0xx V2...............................................................................31
Installation and dimensions Compax3 S038 and S075 V4..............................................................32
Installation and dimensions Compax3 S150 V4..............................................................................33
Installation and dimensions Compax3 S300 V4..............................................................................34

3.2.1. Installation and dimensions of Compax3 S0xx V2

Mounting:
3 socket head screws M5
Mounting spacing:
Device separation 15 mm
I11 T11 192-120101 N6 - March 2004 31
Page 32
Compax3 device description

3.2.2. Installation and dimensions of Compax3 S038 and S075 V4

Mounting:
3 socket head screws M5
Mounting spacing:
Device separation 15 mm
40
7
9
6
7
2
8 4 2
9 5 2
65
Compax3 S038 V4:
8
0
100
Compax3 S075 V4:
115
2
7,5
Page 33
Parker EME
Compax3 device description

3.2.3. Installation and dimensions of Compax3 S150 V4

Mounting:
4 socket head screws M5
Mounting spacing:
Device separation 15 mm
7
8 4
9 5 2
2
80
158
39
9
6
7
2
2
I11 T11 192-120101 N6 - March 2004 33
Page 34
Compax3 device description

3.2.4. Installation and dimensions of Compax3 S300 V4

Mounting:
4 socket head screws M5
Mounting spacing:
Device separation 15 mm
1 9 3
0 8 3
80
175
0
2
0
1
4
4
6
Compax3 S300 V4 is force-ventilated via a fan integrated into the heat
dissipater!
Page 35
Parker EME
4. Setting up Compax3
In this chapter you can read about:
Configuration..................................................................................................................................35
Test setup Compax3.......................................................................................................................64
Device states..................................................................................................................................66
Optimization ...................................................................................................................................68
4.1 Configuration
In this chapter you can read about:
Motor selection ...............................................................................................................................37
Optimize motor reference point and switching frequency of the power output stage ......................38
Ballast resistor................................................................................................................................39
General drive..................................................................................................................................40
Define reference system.................................................................................................................40
Defining jerks and ramps ................................................................................................................50
Limit and monitoring settings ..........................................................................................................52
Encoder simulation.........................................................................................................................54
Positioning......................................................................................................................................55
RS485 setting values......................................................................................................................62
Designation of configuration /comments ......................................................................................... 63

Setting up Compax3

Caution!
De-energize the motor before downloading the configuration software.
N.B.!
Incorrect configuration settings entail danger when energizing the motor. Therefore take special safety precautions to protect the travel range of the system.
Mechanical limit values!
Observe the limit values of the mechanical components!
Ignoring the limit values can lead to destruction of the mechanical components.
I11 T11 192-120101 N6 - March 2004 35
Page 36
Setting up Compax3
Installation and dimensions of Compax3 S300 V4
Configuration sequence:
Installation of the C3
ServoManager
The Compax3 ServoManager can be installed directly from the Compax3 CD. Click on the appropriate hyperlink or start the installation program
"C3Mgr_Setup_V.... .exe" and follow the instructions.
Minimum requirements
For successful installation, your PC must meet the following minimum requirements:
! Windows 98, Windows Me, Windows NT 4.0 (Intel) with Service Pack 6, Windows
2000 or Windows XP.
! Administrator authorisation* on the system ! Microsoft Internet Explorer 4.01 (SP2) or higher ! Pentium-PC (300 MHz or faster is recommended)
! 64 MB RAM (128 MB recommended) ! Required HD capacity
! CD-Installation: 350 MB before installation, 200 MB after installation
! Super VGA-Monitor (with a resolution of at least 800 x 600, setting: small fonts)
Connection between
PC and Compax3
Device selection
Configuration
* you do not need administrator authorization for an update version!
Your PC is connected with the Compax3 via an RS232 cable (SSK1 (see on page 135 )) (COM 1/2 interface on the PC based on X10 Compax3).
Start the Compax3 ServoManager and make the setting for the selected interface in the menu Options: Port (RS232) COM 1 or COM 2.
In the menu tree under device selection you can read the device type of the connected device (Online Device Identification) or select a device type (Device Selection Wizard).
Then you can double click on "Configuration" to start the configuration wizard. The wizard will lead you through all input windows of the configuration.
Input quantities will be described in the following chapters, in the same order
in which you are queried about them by the configuration wizard.
Page 37
Parker EME
4.1.1. Motor selection
The selection of motors can be broken down into:
! Motors that were purchased in Europe and ! Motors that were purchased in the USA. ! You will find non-standard motors under "Additional motors" and
! Under "User-defined motors" you can select motors set up with the C3
MotorManager.
For motors with holding brake SMHA or MHA you can enter brake deceleration times. See also brake delay times (see on page 76).
Please note the following equivalence that applies regarding terms to linear
! Rotary motors / linear motors
! Revolutions Pitch ! Rotation speed Speed ! Torque Power ! Moment of inertia Load
Configuration

Motor selection

motors:
Notes on direct drives (see on page 143 ) (Linear and Torque - Motors)
I11 T11 192-120101 N6 - March 2004 37
Page 38
Setting up Compax3

Optimize motor reference point and switching frequency of the power output stage

4.1.2. Optimize motor reference point and switching frequency of the
power output stage
Optimization of the
motor reference
point
The motor reference point is defined by the reference current and the reference (rotational) speed.
Standard settings are:
! Reference current = nominal current
! Reference (rotational) speed = nominal (rotational) speed
These settings are suitable for most cases.
The motors can, however, be operated with different reference points for special applications.
! By reducing the reference (rotational) speed, the reference current can be
increased. This results in more torque with a reduced speed.
! For applications where the reference current is only required cyclically with long
enough breaks in between,you may use a reference current higher than I limit value is however reference current = max. 1,33*I
. The reference (rotational)
0
. The
0
speed must also be reduced.
The possible settings or limits result from the respective motor characteristics.
Caution!
Wrong reference values (too high) can cause the motor to switch off during operation (because of too high temperature) or even cause damage to the motor.
Optimizing the
switching frequency
of the power output
stage
The switching frequency of the power output stage is preset to optimize the operation of most motors.
It may, however, be useful to increase the switching frequency especially with direct drives in order to reduce the noise of the motors. Please note that the power output stage must be operated with reduced nominal currents in the case of increased switching frequencies. The switching frequency may only be increased.
Caution!
By increasing the power output stage switching frequency, the nominal current and the peak current are reduced. This must already be observed in the planning stage of the plant!
The preset power output stage switching frequency depends on the performance variant of the Compax3 device.
The respective Compax3 devices can be set as follows:
Resulting nominal and peak currents depending on the switching frequency of the power output stage
Page 39
Parker EME
Configuration

Ballast resistor

Compax3 S0xx V2 at 230VAV
Power output
S025 V2 S063 V2 stage switching frequency
8kHz
pre-set
16kHz
I
nominal
I
(<5s)
peak
I
nominal
I
(<2,5s) 5.5A
peak
2.5A
5.5A
2.5A
Compax3 S0xx V4 at 3*400VAC
Power output stage switching frequency
4kHz
8kHz
16kHz
I
nominal
I
(<5s) - -
peak
I
nominal
I
(<2,5s) 9.0A
peak
I
nominal
I
(<2,5s) 5.0A
peak
S038 V4 S075 V4 S150 V4 S300 V4
--
3.8A
2.5A
Compax3 S0xx V4 at 3*480VAC
eff
eff
eff
eff
eff
eff
eff
eff
6.3A
12.6A
5.5A
12.6A
7.5A
15.0A
3.7A
10.0A
eff
eff
eff
eff
15A
eff
30A
eff
eff
eff
eff
eff
10.0A
20.0A
5.0A
10.0A
eff
eff
eff
eff
30A
60A
26A
52A
14A
28A
eff
eff
eff
eff
eff
eff
Power output stage switching frequency
4kHz
pre-set
8kHz
16kHz
The values marked with grey re the pre-set values (standard values)!
4.1.3. Ballast resistor
If the regenerative brake output exceeds the amount of energy that can be stored by the servo-controller (see on page 143), an error will be generated. To
ensure safe operation, it is then necessary to either
! reduce the accelerations resp. the decelerations, ! or an external ballast resistor (see on page 127) is required.
Please select the connected ballast resistor or enter the characteristic values of your ballast resistor directly.
S038 V4 S075 V4 S150 V4 S300 V4
I
nominal
I
(<5s) - -
peak
I
nominal
I
(<2,5s)
peak
I
nominal
I
(<2,5s) 4.0A
peak
--
3.8A
eff
7.5A
eff
2.0A
eff
eff
6.5A
15.0A
2.7A
8.0A
13.9A
eff
30A
eff
eff
eff
eff
eff
8.0A
16.0A
3.5A
7.0A
eff
eff
eff
eff
30A
60A
21.5A
43A
10A
20A
eff
eff
eff
eff
eff
eff
Please note that with resistance values greater than specified, the power
output from the servo drive can no longer be dissipated in the ballast
resistor.
I11 T11 192-120101 N6 - March 2004 39
Page 40
Setting up Compax3

General drive

4.1.4. General drive
External moment of inertia / load
The external moment of inertia is required for adjusting the servo controller. The more accurately the moment of inertia of the system is known, the better is the stability and the shorter is the settle-down time of the control loop.
It is important to specify the minimum and maximum moment of inertia for best possible behavior under varying load.
Minimum moment of inertia / minimum load
Maximum moment of inertia / maximum load
Enter minimum = maximum moment of inertia when the load does not vary.

4.1.5. Defining the reference system

The reference system for positioning is defined by:
! a unit,
! the travel distance per motor revolution, ! a machine zero point with true zero, ! positive and negative end limits.
Page 41
Parker EME
r
r
4.1.5.1 Measure reference
In this chapter you can read about:
You can select from among the following for the unit:
Unit
! mm,
! increments or ! angle degree.
The unit of measure is always [mm] for linear motors.
Configuration
Defining the reference system
Travel distance pe
motor revolution /
pitch
Input as numerato
and denominator
Example 1:
The measure reference to the motor is created with the value: "travel distance per motor revolution / pitch" in the selected unit.
You can enter the "travel distance per motor revolution" as a fraction (numerator divided by denominator). This is useful in the case of endless operation mode or in reset mode if the value cannot be specified as a rational number. This makes it possible to avoid long-term drifts.
Rotary table control
144° 7
M
70
4
Example 2:
Unit: degrees gear transmission ratio 70:4 => 4 load revolutions = 70 motor revolutions Travel distance per motor revolution = 4/70 * 360° = 20.571 428 5 ...° (number
cannot be represented exactly) Instead of this number, you have the option of entering it exactly as a numerator
and denominator: Travel distance per motor revolution = 144/7
This will not result in any drift in endless operation mode or in reset mode, even with relatively long motion in one direction.
Conveyor belt
74
M
7
4
I11 T11 192-120101 N6 - March 2004 41
10mm
Page 42
Setting up Compax3
Defining the reference system
Unit: mm gear transmission ratio 7:4 => 4 load revolutions = 7 motor revolutions
Number of teeth for pinion: 12 Tooth spacing: 10 mm Travel path per motor revolution = 4/7 * 12 * 10mm = 68.571 428 5 ... mm (this
number cannot be expressed exactly) Instead of this number, you have the option of entering it exactly as a numerator
and denominator: Travel distance per motor revolution = 480/7 mm For "travel distance per motor revolution" that can be represented exactly, enter 1
as the denominator.
Travel distance per motor revolution / pitch
Counter
Unit: unit of measure Range: depends on the unit selected Standard value: depends
on the unit selected
Reset mode
Resolution: 0.000 000 1 (7 places after the decimal point)
Unit Division Standard value
Increments* 10 ... 1 000 000 1024
mm 0,010 000 0 ... 2000,000 000 0 1,000 000 0
Degrees 0,010 000 0 ... 720,000 000 0 360,000 000 0
Denominator
Unit: - Range: 1 ... 1 000 000 Standard value: 1
Integer value
* The ”Increments” unit applies only to position values; speed, acceleration and jerk are specified in this case in revolutions/s, revolutions/s pitch/s, pitch/s
2
, pitch/s3).
2
and revolutions/s3 (or
Rotation direction reversal
Unit: - Range: no / yes Standard value: no
Reverse direction inverts the sense of rotation, i.e. the direction of movement of the motor is reversed in the case of equal setpoint.
For applications in which the positioning range is repeated, reset mode is made available. Examples include rotary table applications, conveyor belt, etc. .
After the reset path (which can be specified exactly as numerator and
denominator (see on page 41)) the position values in the Compax3 are reset to 0.
Example:
Conveyor belt (from the "Conveyor belt" example) with reset path
74
M
7
4
10mm
300 mm
Page 43
Parker EME
Note:
Configuration
Defining the reference system
A reset path of 300 mm can be entered directly with numerator = 300 mm and denominator = 1.
Reset mode is not possible for linear motors.
Please do use the reset function only in normal mode! It is not appropriate to use the reset function in continuous mode.
Reset travel distance
Counter
Unit: unit of measure Range: depends on the unit selected Standard value: depends
on the unit selected
Unit Division Standard value
Increments 10 ... 1 000 000 0
mm 1 ... 2000 0
Degrees 1 ... 720 0
Denominator
Unit: - Range: 1 ... 1 000 000 Standard value: 0
Integer value
Turn off reset mode
Reset mode is turned off for numerator = 0 and denominator = 0.
I11 T11 192-120101 N6 - March 2004 43
Page 44
Setting up Compax3
Defining the reference system
4.1.5.2 Machine reference modes (MN-Ms)
Position reference
point
Essentially, you can select between operation with or without machine reference. However, when operating without machine zero, bear in mind that only operation in continuous mode is possible.
31 position data records are possible for operation without machine zero, whereas only 15 position data records are possible for operation with machine zero, because the machine zero proximity switch is read in via the input I7 (X12/14) to which address 4 was assigned previously.
The zero point for positionings in absolute mode is defined via the machine zero and the machine zero offset.
Machine reference run
A machine reference run is required each time after turning on the system for operation with machine reference. A START after "Power on" automatically activates a machine zero run irrespective of the selected data record.
In a machine zero run the drive moves to the position value 0 immediately after finding the machine zero proximity switch. The position value 0 is defined via the machine zero offset.
Using a SinCos Multiturn absolute value encoder (Motor - Option A7) as feedback system, the absolute position can read in when switching on the Compax3. A machine zero run after switch-on is then not necessary.
In this case the reference only needs to be established once
! at initial commissioning time ! after an exchange of motor / feedback system ! after a mechanical modification and ! after replacing the device (Compax3)
by carrying out a machine zero run. The machine zero run mode 35 "MN at the current position(see on page 47 )" is
appropriate for this, because it is therewith possible to operate without proximity switch, but any other machine zero run mode is possible too – if the hardware prerequisites are fulfilled.
When you have once re-established the reference, reset the machine zero run mode to "without machine zero run".
Triggering of a machine zero run
A machine zero run is triggered with address 0 and START. Note: When operating with machine zero, the address 0 is reserved for the
machine zero run.
Page 45
Parker EME
Configuration
Defining the reference system
Machine reference modes (MN-M)
MN-M 3.4: MN-Initiator = 1 auf der positiven Seite
The MN initiator can be positioned at any location within the travel range. The travel range is then divided into 2 contiguous ranges: one range with deactivated MN initiator (left of the MN initiator) and one range with activated MN initiator (right of the MN initiator).
When the MN initiator is inactive (signal = 0) the search for the machine reference is in the positive travel direction.
With motor zero
point, without
direction reversal
switches
MN-M 3: The first motor reference point is used as MN with MN initiator = "0".
MN-M 4: The first motor reference point is used as MN with MN initiator = „1“.
3
3
4
4
1
2
1: motor reference point 2: Initiator signal level of the home switch
I11 T11 192-120101 N6 - March 2004 45
Page 46
Setting up Compax3
MN-M 5,6: MN-Initiator = 1 on the negative side
The MN initiator can be positioned at any location within the travel range. The travel range is then divided into 2 contiguous ranges: one range with deactivated MN initiator (positive part of the travel range) and one range with activated MN initiator (negative part of the travel range).
When the MN initiator is inactive (signal = 0) the search for the machine reference is in the negative travel direction.
With motor zero
point, without
direction reversal
switches
MN-M 5: The first motor reference point is used as MN with MN initiator = "0". MN-M 6: The first motor reference point is used as MN with MN initiator = „1“.
5
5
6
6
1
2
1: motor reference point 2: Initiator signal level of the home switch
MN-M 33,34 MN on the motor zero point
The motor reference point is now evaluated (no MN initiator):
Without machine
reference initiator
MN-M 33: For an MN trip, the next motor reference point in the negative travel
direction starting from the current position is used as the MN. MN-M 34: For an MN trip, the next motor reference point in the positive travel
direction starting from the current position is used as the MN.
33
34
1
1: motor reference point
Page 47
Parker EME
Setting up Compax3
MN-M 35: MN at the current position
The current position when the MN run is activated is used as an MN.
35
MN-M 128/129: Rising of current while moving to block
Without an MN initiator, an end of travel region (block) is used as an MN.
The increase in the current is evaluated for this purpose (adjustable up to 100% of the reference current), if the motor is pressing against the end of the travel region. If the limit is exceeded, the MN is set. Tracking error is deactivated during the MN run.
Please observe:
The machine zero offset must be set so that the zero point (reference point) for positioning lies witihn the travel range.
MN-M 128: Travel in the positive direction to the end of the travel region
MN-M 129: Travel in the negative direction to the end of the travel region
Caution!
Wrong settings can cause hazard for man and machine.
It is therefore essential respect the following:
! Choose a low machine zero speed. ! Set the machine zero acceleration to a high value, so that the drive changes
direction quickly, the value must, however, not be so high that the current limit threshold is already reached by accelerating or decelerating (without mechanical limitation).
! The mechanical limitation as well as the load drain must be set so that they can
absorb the resulting kinetic energy.
I11 T11 192-120101 N6 - March 2004 47
Page 48
Setting up Compax3
4.1.5.3 Adjusting the machine zero proximity switch
This is helpful in some cases with machine reference modes that work with the MN initiator and motor reference point.
If the motor reference point happens to coincide with the position of the MN initiator, there is a possibility that small movements in the will cause the machine reference point to shift by one motor revolution (to the next motor reference point).
1
2
-
+
1: motor reference point 2: Initiator level of the home switch
A solution to this problem is to move the MN initiator by means of software. This is done using the value initiator adjustment.
Initiator adjustment
Unit: Motor angle in degrees
Move the machine reference initiator using software
Range: -360 ... 360 Standard value: 0
Machine reference offset
1
1: machine reference offset.
The machine reference offset is used to determine the actual reference point for positioning.
The rule for this is: Referene point = machine reference + machine reference offset Note: if the machine reference initiator is located at the positive end of the travel
range, the machine reference offset must = 0 or be negative.
A change in the machine reference offset does not take effect until the next
0
machine reference run.
Page 49
Parker EME
4.1.5.4 Software end limits
The travel range is defined via the negative and positive end limits.
0
1 2
1: negative end limit 2: positive end limit
End limit in absolute operating mode
Positioning is limited to the end limits. The drive remains in place at the end limits if a larger destination has been specified.
12
Setting up Compax3
Behavior after the
system is turned on
Note:
V
1: negative end limit 2: positive end limit
The reference is the position reference point that was defined with the machine reference and the machine reference offset.
End limit in endless operating mode
Each single positioning is limited to the end limits; the drive continues only by the value of the end limits, even if a greater target distance was specified.
The reference is the respective current position.
After the system is turned on, the end limits refer to the current position. The end limits do not refer to the position reference point until after a machine reference run.
In the case of inter-axis coupling the end limits are not monitored.
I11 T11 192-120101 N6 - March 2004 49
Page 50
Setting up Compax3

4.1.6. Defining jerk / ramps

In this chapter you can read about:
Ramp upon error/deenergize ..........................................................................................................51
Jerk
You can use the jerk limit (= maximum change in acceleration) to limit the maximum change in acceleration.
A motion process generally starts from a standstill, accelerates constantly at the specified acceleration to then move at the selected speed to the target position. The drive is brought to a stop before the target position with the delay that has been set in such a manner as to come to a complete stop at the target position. To reach the set acceleration and deceleration, the drive must change the acceleration (from 0 to the set value or from the set value to 0). This change in speed is limited by the maximum jerk.
1
2
3
4
t
t
t
t
1: Position 2: Speed 3: Acceleration 4: Jerk
Changes in acceleration (jerks) often have negative effects on the mechanical systems involved. There is a danger that mechanical resonance points will be excited or that impacts will be caused by existing mechanical slack points.
You can reduce these problems to a minimum by specifying the maximum jerk.
Jerk
Unit: unit/s
3
Range: 0 ... 10 000 000 Standard value:
1 000 000
Page 51
Parker EME
STOP delay
After a STOP signal, the drive applies the brakes with the delay that is set (2).
NO STOP: I0: no STOP The STOP delay applies only when STOP with delay (see also page 58) has
been configured. For STOP without discontinuation (see also page 58) the ramp of the current
position data record is used.
4.1.6.1 Ramp upon error / deenergize
Ramp (delay) upon error and "De-energize"
Setting up Compax3
3 3
QUIT
3: Deceleration on “de-energize” and on “error”. QUIT: I2: Quit (with positive edge) START: I1: START (with positive edge)
The same delay is used for "Deenergizing" and when an error appears (errors which do not deenergize immediately).
Manual acceleration/deceleration and speed control
You can set the motion profile for moving with Manual+ or Manual- here.
-
-
--
1: Manual acceleration / delay 2: Manual speed
I11 T11 192-120101 N6 - March 2004 51
Page 52
Setting up Compax3
+: I5: HAND+ (only in commissioning mode)
-: I6: HAND- (only in commissioning mode)
Manual travel control is possible only in setup mode - this is activated in the optimizing window with the Compax3 ServoManager.

4.1.7. Limit and monitoring settings

In this chapter you can read about:
Current limit....................................................................................................................................52
Positioning window – position reached ...........................................................................................52
Tracking error limit..........................................................................................................................53
4.1.7.1 Current Limit
The current required by the speed controller is limited to the current limit.
4.1.7.2 Positioning window - Position reached
Position reached indicates that the target position is located within the position window.
In addition to the position window, a position window time is supported. If the actual position goes inside the position window, the position window time is started. If the actual position is still inside the position window after the position window time, "Position reached" is set.
If the actual position leaves the position window within the position window time, the position window time is started again.
When the actual position leaves the position window with Position reached = “1", Position is immediately reset to "0".
Position monitoring is active even if the position leaves the position window because of measures taken externally.
POS
1: position window 2: position window time
POS: O1: Position reached
Page 53
Parker EME
f
Setting up Compax3
No position monitoring takes place in status START (E1=24VDC).
Therefore reset the start signal to 0 after the START flank.
Behaviour o
"Position reached"
after Power On
Handshake with PLC
for small
positionings
O1 is set to "0" after Power On O1 goes to "1" after the machine zero run (after position 0 has been reached)
START: I1: START Signal
POS: O1: Position reached
Sequence:
PLC Reaction Compax3
START of a positioning Position reached goes to "0"
From position reached = "0" follows:
START = 0
Positioning finished " Position reached = "1"
From position reached = "1" follows:
Next START can take place
4.1.7.3 Tracking error limit
The tracking error is a dynamic error.
The dynamic difference between the target position and the actual position during a positioning process is referred to as the tracking error - not to be confused with the static difference, which is always 0. The destination position is always approached exactly.
The change of position over time can be specified exactly using the parameters jerk, acceleration and speed. The integrated target value generator calculates the course of the target position. Because of the delay in the feedback loop, the actual position does not follow the target position exactly. This difference is referred to as the tracking error.
Disadvantages
caused by a tracking
error
In joint operation of several servo controllers (e.g. master controller and slave controller), tracking errors lead to problems due to the dynamic position differences, and a large tracking error can lead to positioning overshoot.
Position reached goes to "0"
I11 T11 192-120101 N6 - March 2004 53
Page 54
Setting up Compax3
Error message
Minimizing the
tracking error
If the tracking error exceeds the specified tracking error limit, the “tracking error time“ then expires. If the tracking error is even greater than the tracking error limit at the end of the tracking error time, an error is reported.
If the tracking error falls short of the tracking error limit, a new tracking error time is then started.
The tracking error can be minimised with the help of the extended (advanced) controller parameters, in particular with the forward feed parameters (see on page
71) (forward feed of rotation speed, acceleration, current and jerk).
1: tracking error limit
2: tracking error time NO ERROR: O0: no error QUIT: I2: Quit (with positive edge)
4.1.8. Encoder simulation
You can make use of a permanently integrated encoder simulation feature to make the actual position value available to additional servo drives or other automation components.
Resolution of the encoder simulation
Unit: Increments per rotation / pitch
Adjustable in powers of two (2n):
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048, 4096, 8192, 16384
Limit frequency: 620 kHz i. e.
Increments per revolution Max. speed
1024 36000 rpms
4096 9000 rpms
16384 2250 rpms
Range: 4 - 16384 Standard value: 1024
Page 55
Parker EME
4.1.9. Positioning
Setting up Compax3
Function
Positioning takes place with 31 positioning data records (15 when operating with machine zero) which are defined via address, mode (POSA,POSR), target position, speed, acceleration, deceleration (delay) and number of repetitions.
The desired positioning data record is selected via the inputs (I3-I7) and started via a START edge.
The positioning data record address is thereby read in with the START edge.
Condition START
Minimum pulse duration: 1ms
edge
Reaction time
Maximum 1.4ms (0.4 - 1.4ms)
4.1.9.1 Operating modes
Operating mode: absolute mode or endless mode
Absolute mode
A fixed measuring system is associated with the travel range: A fixed defined zero point exists. All positions are referred to this zero point.
0
-100-200-300
+100 +200 +300
I11 T11 192-120101 N6 - March 2004 55
Page 56
Setting up Compax3
r
Endless mode
Note
Sequential
positioning
The actual position is set to 0 before each positioning. Thus the travel range has no fixed zero point. All positionings are relative - in relation to the actual position.
START START START
000
Since the positioning mode (relative or absolute) can be selected additionally for each positioning data record, mixed operation is possible too.
Execution of the positioning data records: sequential / single positioning
With a START edge (X12/7=24VDC) after
! Machine zero run or after the ! "Deenergized state"
the selected positioning data record is executed.
! On the next STARTedge the next positioning data record is executed
(irrespective of the set positioning data record address). If the positioning data record address 0 is still present, the machine zero run is executed.
! With a repetition number >1 this can be the same positioning data record. ! Subsequent STARTs execute the current positioning data record the number of
times corresponding to the repetition number.
! The next start thereafter switches to the next positioning data record. ! After the last positioning data record, the positioning data record 1 is executed
next.
! Number of repetitions (see on page 56 ) = 0 reads in the address new.
Behaviour afte
STOP
Example 1:
After a STOP with termination (see on page 58 ), the positioning address is read in new.
After STOP without termination (see also on page 58 ) the sequential positioning is interrupted; on the next START the sequential positioning is resumed with the interrupted positioning data record.
0/1
12 x x x x
x x x x
--5--
1
2
3
4
5
1 1 1 2 1
E/I4 E/I5 E/I6
START
1
0/1 0/1
x x x x
--4--
1E/I3 11 00 00
12345
home --3-- --4--
Column 1: Positioning data record address Column 2: Repetition counter
Action Behaviour
START 1 after Power On Machine zero run (home)
Positioning data record address irrelevant
START 2 Positioning data record address is read in
Positioning data record 3 is executed
Page 57
Parker EME
Setting up Compax3
START 3 Positioning data record address irrelevant
Positioning data record 4 is executed
START 4 Positioning data record address irrelevant
Positioning data record 4 is executed, because repetition counter = 2
START 5 Positioning data record address irrelevant
Positioning data record 5 is executed
End of a sequential
positioning
procedure
Example 2:
A sequential position procedure can be terminated with a repetition number = 0. For this purpose the repetition number 0 must stand for the data record following after the last valid positioning data record.
When Compax3 encounters a data record with the repetition number 0, a new positioning data record address is read in and the corresponding positioning data record is executed immediately.
12
1
1
1
2
1
E/I3
E/I4
E/I5
E/I6
START
0/1 0/1
1
11
00
00
12345
home --3-- --4--
x
1
x
x
x
--4--
0/1
x
x
x
x
x
x
x
x
--5--
0/1
1
1
1
0
6
--7--
1
0/1
2
x
3
x
4
x
5
x
60
7
72
81
--7--
Column 1: Positioning data record address Column 2: Repetition counter
START 1 to START 5 see Example 1
Action Behaviour
START 6
START 7 Positioning data record address irrelevant
Repetition counter = 0
Positioning data record address is read in Positioning data record 7 is executed
Positioning data record 7 is executed, because repetition counter = 2
Single positioning
On a START edge (X12/7=24VDC), the positioning data record addressed via the inputs I3 to I6 (I7) is always executed.
Therefore the desired positioning data record must be addressed before each START.
1E/I3
11
E/I4
E/I5
E/I6
START
Action Behaviour
START 1 Positioning data record address is read in
010
011
001
123
--1-- --7-- --13--
Positioning data record 1 is executed
I11 T11 192-120101 N6 - March 2004 57
Page 58
Setting up Compax3
STOP with
termination
START 2 Positioning data record address is read in
Positioning data record 7 is executed
START 3 Positioning data record address is read in
Positioning data record 13 is executed
Defining the STOP function
The function of the input I0 "no STOP" (I0=0V = STOP) can be set.
STOP and terminate the current positioning
A new START does not continue the positioning at the interruption point.
Single positioning
Sequential
positioning
STOP without
termination
The positioning address is read in new and the positioning data record is executed completely.
Single positioning example: The positioning data record address “Pos x+1” was created before the new START.
NO STOP: I0: no STOP START: I1: START-Signal (with edge)
! On STOP with termination, the sequentional positioning procedure is
discontinued.
! The positioning data record address is read in new.
STOP and interruption of the current positioning procedure.
Page 59
Parker EME
Overview:
Setting up Compax3
NO STOP: I0: no STOP START: I1: START-Signal (with edge)
A new START resumes the positioning process at the position where it was interrupted.
Relationship between the chosen STOP function and the positioning mode
A START flank after previous STOP produces:
- on condition that no STOP (E0=24V) is still present -
Single positioning Sequential positioning
STOP and termination of the current positioning procedure
(STOP with termination)
STOP and interruption of the current positioning procedure (STOP without termination)
The positioning data record address is read in and the positioning data record is executed.
Note: In continuous mode a
complete positioning, starting from the current position, takes place to the target position contained in the data record.
The positioning procedure which was active before the STOP is continued irrespective of the set positioning data record address.
The positioning data record address is read in and a new sequential positioning procedure is started.
4.1.9.2 Define positioning data records
Positioning data
record:
1
2
3
4
5
t
t
t
t
I11 T11 192-120101 N6 - March 2004 59
Page 60
Setting up Compax3
1: Target position
2: Travel speed
3. Maximum acceleration 4: Maximum deceleration 5: Maximum jerk (see on page 5) (the same for all positioning data records)
Input window:
A positioning data record has the following contents:
Address Mode Target
position
Posi-
tion
Accele-
ration
Decele-
ration (delay)
Repetition
number
Page 61
Parker EME
r
Setting up Compax3
Address:
Mode
Target position
Speed
Acceleration
Address of the positioning data record. The desired positioning data record is selected via the inputs I3 to I6 (to I7 without machine zero proximity switch). The address is given by the binary value of the inputs, whereby
0
= 1
I3 2
1
I4 2
= 2
2
I5 2
= 4
3
I6 2
= 8
4
I7 2
= 16
POSA: absolute positioning. Inappropriate in continuous mode and in operation without machine zero.
POSR: Relative positioning. You can carry out relative positionings in absolute mode, too.
Target position in the chosen unit
Speed in length unit/s
Acceleration in Unit/s
2
Deceleration
(retardation)
Repetition numbe
Deceleration in Unit/s
2
Only relevant for sequential positioning (see also on page 56 ).
Specifies how many times execution of the particular positioning data record is repeated.
Special feature
Repetition number = 0: End of a sequential positioning The data record with repetition number 0 is invalid
The positioning data record address is read in new and the new positioning data record is executed.
I11 T11 192-120101 N6 - March 2004 61
Page 62
Setting up Compax3
4.1.9.3 Dynamic positioning
You can change the positioning data record during a positioning procedure. Thereby the following conditions apply:
! Acceleration and deceleration remain constant irrespective of the values set in
the new positioning data record.
! The jerk, too, remains constant. ! The speed of the new positioning data record becomes active. ! The drive runs to the target position specified in the new positioning data record.
! The new positioning data record address must not be 0.
Example:
Pos 1
Pos 5
V 1
V 5
START
E/I3 - E/I6 -1- -5-
4.1.10. RS485 setting values
t
t
If “Master=Pop“ was selected, only the settings compatible with the Pops (Parker Operator Panels) made by Parker are possible.
Please note that the connected Pop has the same RS485 setting values.
You can test this with the "PopDesigner" software.
"Master=General" makes all Compax3 settings possible.
Multicast address
You can use this address to allow the master to access multiple devices simultaneously.
Device address
Baud rate
Protocol
The device address of the connected Compax3 can be set here.
Adjust the transfer speed (baud rate) to the master.
Adjust the protocol settings to the settings of your master.
Page 63
Parker EME
4.1.11. Configuration name / comments
Here you can name the current configuration as well as write a comment.
Setting up Compax3
I11 T11 192-120101 N6 - March 2004 63
Page 64
Setting up Compax3
r
4.2 Test commissioning Compax3
Required wiring:
X1: Mains supply
/1: 230V AC +10% /2: 0V /3: PE
X10 to PC RS232 / RS485
X3 Motor / Brake
X12 (see below) Inputs/Outputs
X4: 24VDC
/3: enable with 24VDC
X13 to the moto position transmitter
Operational enable of the servo controller:
Plug/Pin Assignment
X12/6 (no STOP) = 24V DC (jumper to X12/1)
X12/8 (Energize the motor) = 24V DC (jumper to X12/1)
X4/3 (Enable power output stage) = 24V DC (jumper to X4/1)
Page 65
Parker EME
Setting up Compax3
After you have configured the Compax3 according to your application with the help of the Compax3 ServoManager, you can now carry out the first motor movements.
Travel via Manual+
and Manual-
Positioning
In the optimising window of the Compax3 ServoManager you can run the motor in positive or negative movement direction.
In order to be able to position according to the specified positioning data records, it is usually necessary to carry out a machine zero run after switching on (if machine zero has been configured). This takes place automatically with the first START after Power On. For this purpose the machine zero proximity switch must be connected to X12/14.
When sequential positioning mode has been chosen the first positioning takes place in response to a START signal (X12/7=24VDC).
In single positioning mode the desired positioning data record is selected via the digital inputs I3-I7(I6) (plug X12 (see on page 28 )) and activated via a START signal (X12/7=24VDC)
I11 T11 192-120101 N6 - March 2004 65
Page 66
Setting up Compax3
4.3 Device status
Positioning to selected positioning data record
I1
Motor energized-
/I2
Deceleration
ramp upon „Stop/
de-energize"
De-energize
motor with delay
/I0
/I2
/I2
O1
/I0
Motor energized /
Positioning data records
/I2
Motor de-energized
I1 & I0
disabled
I2
Energize motor
with delay
I2
I2
Quit
Error
with reaction 2
Deceleration
ramp upon
error
Key:
! I0, I1, I2: Input = 24VDC ! /I0, /I1: Input = 0V ! $I2: positive edge on I2 ! O1: position reached
The device can be brought into various states via the inputs:
! I0: no Stop
! I1: Start
De-energize
motor with
delay
Error
with reaction 5
Error
Page 67
Parker EME
Setting up Compax3
! I2: energize motor ! $%
%2: Quit
%%
The device is brought into various device states. The transitions are implemented via various ramps and the defined switching of the
motor brake (see on page 76 ).
An error can occur in any device state. The reactions to the individual error causes are described in the list of errors (see on page 92).
I11 T11 192-120101 N6 - March 2004 67
Page 68
Setting up Compax3
4.4 Optimization
In this chapter you can read about:
Controller dynamic..........................................................................................................................68
Setup mode....................................................................................................................................75
Engaging and disengaging the motor holding brake .......................................................................76
The controller optimization of the Compax3 is carried out in 2 steps:
! Via the standard settings (stiffness, damping, rotation speed controller and
rotation speed filter), with the help of which many applications can be optimized in a simple manner.
! With advanced settings for users familiar with control loops.
4.4.1. Control dynamics
In this chapter you can read about:
Stiffness of speed controller............................................................................................................69
Damping of speed controller...........................................................................................................70
Filter actual speed value.................................................................................................................70
Advanced controller parameters .....................................................................................................71
Page 69
Parker EME
4.4.1.1 Stiffness of the speed controller
The stiffness is proportional to the control loop speed.
Nominal value: 100%
On increasing stiffness:
Control action becomes faster. The control loop oscillates above a critical threshold value. Set the stiffness with an adequate safety margin with respect to the oscillation threshold value.
On decreasing stiffness:
Control action becomes slower. This increases the tracking error. Current limiting will be reached later.
3
>100%
1
3
3
Setting up Compax3
=100%
<100%
2
t
1: target value 2: actual value 3: stiffness
2100.2: Stiffness of the speed controller
Unit: % Range: 10 ... 100 000 Standard value: 100%
The stiffness is proportional to the control loop speed.
I11 T11 192-120101 N6 - March 2004 69
Page 70
Setting up Compax3
4.4.1.2 Damping of the speed controller
The damping influences the target value overshoot magnitude and the decay time constant of control loop oscillation.
Nominal value: 100%
On increasing the damping:
Overshoot decreases. High frequency oscillation of the servo drive takes place as from a certain threshold value.
On decreasing the damping:
The target value overshoot of the actual value increases, and the actual value oscillates for a longer time above and below the target value. As from a certain threshold value the servo drive oscillates continuously.
1: target value 2: actual value
3: damping
2100.3: Damping of the speed controller
Unit: % Range: 0 ... 500 Standard value: 100%
The damping influences the target value overshoot magnitude and the decay time constant of control loop oscillation.
4.4.1.3 Filter for speed value
Can be used to improve (filter) the rotation speed signal. The greater the value, the stronger becomes the filter effect. However, the rotation speed delay increases with this value, so that the maximum possible control loop dynamic range becomes smaller with values which are too large.
! Set the value to 0 when using motors with SinCos. ! In the case of large load inertia in relation to the moment of inertia of the motor, a
large value can achieve further improvement in the attainable stiffness.
t
2100.5: Filter actual speed value
Unit: % Range: 0 ... 550 Standard value: 100%
This is used to improve signals (filtering) of the speed control signal
Page 71
Parker EME
4.4.1.4 Advanced control parameters
Controller structure:
Setting up Compax3
Switching of the
user level
The status values are divided into 2 groups (unser levels):
standard: here you can find all important status values advanced: advanced status values, require a better knowledge
The user level can be changed in the optimization window (left hand side lower part under selection (TAB) "optimization") with the following button.
2100.8: Current controller bandwidth
Unit: % Range: 10 ... 200 Standard value: 50%
2100.9: Damping current controller
Unit: % Range: 0 ... 500 Standard value: 100%
I11 T11 192-120101 N6 - March 2004 71
Page 72
Setting up Compax3
2100.7: D component speed controller
Unit: % Range: 0 ... 4 000 000 Standard value: 0
2100.6: Actual acceleration value filter
Unit: % Range: 0 ... 550 Standard value: 100
2100.4: Moment of inertia
Unit: % Range: 10 ... 500 Standard value: 100%
Forward control measures
Advantages:
Principle:
Forward control of rotation speed, acceleration and current
! Minimizes tracking error
! Improves the transient response ! Gives greater dynamic range with lower maximum current
A positioning is calculated in the target value plate and specified as the target value for the position controller. This provides the target value plate with the preliminary information on changes in speed, acceleration and current required for positioning. Switching this information to the controller then makes it possible to reduce tracking errors to a minimum. The transient response of the controller is also improved and the drive dynamics are increased.
The stability of the control loop is unaffected by the forward control.
Page 73
Parker EME
Setting up Compax3
Positioning without forward control:
1
2
t
4
3
t
2010.1: Forward speed control
Unit: % Range: 0 ... 500 Standard value: 100%
Effect of the rotation speed forward control
1
2
t
3
4
t
1: target speed value 2: actual speed value 3: motor current 4: tracking error
2010.2: Acceleration forward control
Unit: % Range: 0 ... 500 Standard value: 100%
I11 T11 192-120101 N6 - March 2004 73
Page 74
Setting up Compax3
Additional effect of forward acceleration control
2
1
t
3
4
t
1: target speed value 2: actual speed value 3: motor current 4: tracking error
2010.4: Current forwards control
Unit: % Range: 0 ... 500 Standard value: 0%
Additional effect of forward current control
2
1
t
3
4
t
1: target speed value 2: actual speed value 3: motor current 4: tracking error
2010.5: Jerk forward control
Unit: % Range: 0 ... 500 Standard value: 0%
Page 75
Parker EME
4.4.2. Commissioning mode
The functions Manual+/- are made available via the setup mode. Setup mode can be activated in the ServoManager under the menu item "Optimization". The following applies in setup mode:
Function Input PIN
Manual+ I5 X12/12
Manual- I6 X12/13
Thus only 3 positioning data records, which can be accessed via the address lines 0 and 1, are available in setup mode.
Setting up Compax3
I11 T11 192-120101 N6 - March 2004 75
Page 76
Setting up Compax3

4.4.3. Turning the motor holding brake on and off

COMPAX controls the stationary state holding brake of the motor and the power output stage. The time behavior can be set.
Application:
For an axis to which torque is applied in the stationary state (e.g. for a z-axis) the drive can be switched on and off in a manner such that no load movement takes place. The drive thereby remains energized during the holding brake response time. This is adjustable.
The power output stage current is de-energized by:
! Error or ! I2=X12/8="0V"
Thereafter the motor is braked to zero rotation speed on the set ramp.
When zero speed is reached, the motor is de-energized with the delay "brake closing delay time".
1
2
3
4
5
t
t
1: Motor energized
2. Motor deenergized 3: Open brake 4: Apply brake 5: brake closing delay time
The power output stage is enabled by:
! Quit (after an error) ! I2=X12/8 = 24V
The motor is energized with the delay "delay time for brake release".
1
2
3
t
4
5
t
1: Motor energized
2. Motor deenergized 3: Open brake
4: Apply brake 5: Delay time for brake release
Page 77
Parker EME

RS232 & RS485 – interface record

5. RS232 & RS485 – interface record
In this chapter you can read about:
ASCII protocol ................................................................................................................................77
Binary protocol ...............................................................................................................................79
You can communicate with Compax3 in order to read or write objects via plug X10 on the front plate either with RS232 or with RS485.
As a rule 2 records are possible:
! ASCII record: simple communication with Compax3 ! Binary record: fast and secure communication with Compax3 by the aid of block
securing.
Switching between the ASCII and the binary record via automatic record
Wiring
RS232: SSK1 (see on page 135 ) RS485: as SSK27 (see on page 136) / RS485 is activated by +5V on X10/1.

5.1 ASCII - record

The general layout of a command string for Compax3 is as follows:
[Adr] command CR
Adr
Command
CR
detection.
RS232: no address
RS485: Compax3 address in the range 0 ... 99 Address settings can be made in the C3 ServoManager under "RS485 settings"
valid Compax3 command
End sign (carriage return)
Command
Answer strings
A command consists of the representable ASCII characters (0x21 .. 0x7E). Small letters are converted automatically into capitals and blanks (0x20) are deleted, if they are not placed between two quotation marks.
Separator between places before and after the decimal is the decimal point (0x2E).
A numeric value can be given in the Hex-format if it is preceded by the “$“ sign. Values can be requested in the Hex-format if the CR is preceded additionally by the “$“ sign.
All commands requesting a numeric value from Compax3 are acknowledged with the respective numeric value in the ASCII format followed by a CR without preceding command repetition and following statement of unit. The length of these answer strings differs depending on the value.
I11 T11 192-120101 N6 - March 2004 77
Page 78
RS232 & RS485 – interface record
Commands requesting an Info-string (e.g. software version), are only acknowledged with the respective ASCII character sequence followed by a CR, without preceding command repetition. The length of these anser strings is here constant.
Commands transferring a value to Compaxe or triggering a function in Compax3 are acknowledged by:
>CR
if the value can be accepted resp. if the function can be executed at that point in time.
If this is ot the case or if the command syntax was invalid, the command is
is acknowledged with !xxxxCR
The 4 digit error number xxxx is given in the HEX format; you will find the meaning in the appendix (see on page 4.)
RS485 answer string
Read object
Write object
When using RS485, each answer string is preceded by a "*" (ASCII - character: 0x2A).
Compax3 commands
RS232: O [$] Index , [$] Subindex [$]
RS485: Address O [$] Index , [$] Subindex [$]
The optional "$" after the subindex stands for "hex-output" which means that an object value can also be requested in hex;
e.g. "O $0192,2$":
RS232: O [$] Index , [$] Subindex = [$] Value [ ; Value2 ; Value3 ; ...]
RS485: Address O [$] Index , [$] Subindex = [$] Value [ ; Value2 ; Value3 ; ...]
The optional "$" preceding Index, Subindex and value stands for "Hex-input" which means that Index, Subindex and the value to be transferred can also be entered in hex (e.g. O $0192,2=$C8).
Page 79
Parker EME
RS232 & RS485 – interface record
5.2 Binary record
The binary record with block securing is based on 5 different telegrams:
! 2 request telegrams which the control sends to Compax3 and ! 3 response telegrams which Compax3 returns to the control.
Telegram layout
Basic structure:
Start code Address Number of data bytes - 1 Data block securing
SZ O L D0 D1 ... Dn Crc(Hi) Crc(Lo)
The start code defines the frame type and is composed as follows:
Bit 7 6 5 4 3 2 1 0 Frame type Frame identification PLC Gateway Address
RdObj Read object 1 0 1 0 x 1 x x WrObj Write object 1 1 0 0 x 1 x x
RspAnswer 0000010 1 Ack Positive command acknowledgement 0 0 0 0 0 1 1 0 Nak Negative command acknowledgement 0 0 0 0 0 1 1 1
Bits 7, 6, 5 and 4 of the start code form the telegram identification; Bit 2 is always “1“.
Bits 3, 1 and 0 have different meanings for the request and response telegrams.
The address is only necessary for RS484.
Request telegrams
Response telegram
-> Compax3
! the address bit (Bit 0 = 1 ) shows if the start code is followed by an address (only
for RS485; for RS232 Bit 0 = 0)
! the gateway bit (Bit 1 = 1) shows if the message is to be passed on.
(Please set Bit 1 = 0, as this function is not yet available)
! the PLC bit (Bit 3 = 0 ) allows access to objects in the PLC format (U16, U32,
IEEE Floating Point). For information into which PLC format the objects are converted, please refer to the object description.
Compax3 ->
! Bits 0 and 1 are used to identify the response
! Bit 3 is always 0
The maximum number of data bytes in the request telegram is 256, in the response telegram 253.
The block securing (CRC16) is made via the CCITT table algorith for all characters. After receiving the start code, the timeout monitoring is activated in order to avoid
that Compax3 waits in vain for further codes (e.g. connection interrupted) The timeout period between 2 codes received is fixed to 5ms (5 times the code time at 9600Baud)
I11 T11 192-120101 N6 - March 2004 79
Page 80
RS232 & RS485 – interface record
Write object – WrObj telegram
SZ Adr L D0 D1 D2 D3 ... Dn Crc(Hi) Crc(Lo)
0xCX n Index(Hi) Index(Lo) Subindex value 0x.. 0x..
Describing an object by a value.
Positive acknowledgement – Ack-telegram
SZ L D0 D1 Crc(Hi) Crc(Lo)
0x06 1 0 0 0x.. 0x..
Answer from Compax3 if a writing process was successful, i.e. the function could be executed and is completed in itself.
Negative acknowledgement – Nak - telegram
SZ L D0 D1 Crc(Hi) Crc(Lo)
0x07 1 F-No.(Hi) F-No.(Lo) 0x.. 0x..
Answer from Compax3 if access to the object was denied (e.g. function cannot be executed at that point in time or object has no reading access). The error no. is coded according to the DriveCom profile resp. the CiA Device Profile DSP 402.
Read object – RdObj - telegram
SZ Adr L D0 D1 D2 D3 D4 D5 ... Dn Crc(Hi) Crc(Lo)
0xAX n Index1(Hi) Index1(Lo) Subindex1 Index2(Hi) Index2(Lo)Subindex2 ... ... 0x.. 0x..
Reading one or several objects
Answer – Rsp - telegram
SZ L D0 ... Dx-1 Dx ... Dy-1 Dy-D.. D ... D.. D ... Dn Crc(Hi) Crc(Lo)
0x05 n Value1 Value 2 Value 3 Value .. Value n 0x.. 0x..
Answer from Compax3 if the object can be read. If the object has no reading access, Compax3 answers with the Nak – telegram.
Page 81
Parker EME
RS232 & RS485 – interface record
Block securing:
Function call:
Function
Checksum calculation for the CCITT table algorithm
The block securing for all codes is performed via the following function and the corresponding table:
The “CRC16“ variable is set to “0“ before sending a telegram.
CRC16 = UpdateCRC16(CRC16, Character);
This function is called up for each Byte (Character) of the telegram. The result forms the last two bytes of the telegram Compax3 checks the CRC value on receipt and reports CRC error in the case of a
deviation.
const unsigned int _P CRC16_table[256] = { 0x0000, 0x1021, 0x2042, 0x3063, 0x4084, 0x50a5, 0x60c6, 0x70e7, 0x8108, 0x9129, 0xa14a, 0xb16b, 0xc18c, 0xd1ad, 0xe1ce, 0xf1ef, 0x1231, 0x0210, 0x3273, 0x2252, 0x52b5, 0x4294, 0x72f7, 0x62d6, 0x9339, 0x8318, 0xb37b, 0xa35a, 0xd3bd, 0xc39c, 0xf3ff, 0xe3de, 0x2462, 0x3443, 0x0420, 0x1401, 0x64e6, 0x74c7, 0x44a4, 0x5485, 0xa56a, 0xb54b, 0x8528, 0x9509, 0xe5ee, 0xf5cf, 0xc5ac, 0xd58d, 0x3653, 0x2672, 0x1611, 0x0630, 0x76d7, 0x66f6, 0x5695, 0x46b4, 0xb75b, 0xa77a, 0x9719, 0x8738, 0xf7df, 0xe7fe, 0xd79d, 0xc7bc, 0x48c4, 0x58e5, 0x6886, 0x78a7, 0x0840, 0x1861, 0x2802, 0x3823, 0xc9cc, 0xd9ed, 0xe98e, 0xf9af, 0x8948, 0x9969, 0xa90a, 0xb92b, 0x5af5, 0x4ad4, 0x7ab7, 0x6a96, 0x1a71, 0x0a50, 0x3a33, 0x2a12, 0xdbfd, 0xcbdc, 0xfbbf, 0xeb9e, 0x9b79, 0x8b58, 0xbb3b, 0xab1a, 0x6ca6, 0x7c87, 0x4ce4, 0x5cc5, 0x2c22, 0x3c03, 0x0c60, 0x1c41, 0xedae, 0xfd8f, 0xcdec, 0xddcd, 0xad2a, 0xbd0b, 0x8d68, 0x9d49, 0x7e97, 0x6eb6, 0x5ed5, 0x4ef4, 0x3e13, 0x2e32, 0x1e51, 0x0e70, 0xff9f, 0xefbe, 0xdfdd, 0xcffc, 0xbf1b, 0xaf3a, 0x9f59, 0x8f78, 0x9188, 0x81a9, 0xb1ca, 0xa1eb, 0xd10c, 0xc12d, 0xf14e, 0xe16f, 0x1080, 0x00a1, 0x30c2, 0x20e3, 0x5004, 0x4025, 0x7046, 0x6067, 0x83b9, 0x9398, 0xa3fb, 0xb3da, 0xc33d, 0xd31c, 0xe37f, 0xf35e, 0x02b1, 0x1290, 0x22f3, 0x32d2, 0x4235, 0x5214, 0x6277, 0x7256, 0xb5ea, 0xa5cb, 0x95a8, 0x8589, 0xf56e, 0xe54f, 0xd52c, 0xc50d, 0x34e2, 0x24c3, 0x14a0, 0x0481, 0x7466, 0x6447, 0x5424, 0x4405, 0xa7db, 0xb7fa, 0x8799, 0x97b8, 0xe75f, 0xf77e, 0xc71d, 0xd73c, 0x26d3, 0x36f2, 0x0691, 0x16b0, 0x6657, 0x7676, 0x4615, 0x5634, 0xd94c, 0xc96d, 0xf90e, 0xe92f, 0x99c8, 0x89e9, 0xb98a, 0xa9ab, 0x5844, 0x4865, 0x7806, 0x6827, 0x18c0, 0x08e1, 0x3882, 0x28a3, 0xcb7d, 0xdb5c, 0xeb3f, 0xfb1e, 0x8bf9, 0x9bd8, 0xabbb, 0xbb9a, 0x4a75, 0x5a54, 0x6a37, 0x7a16, 0x0af1, 0x1ad0, 0x2ab3, 0x3a92, 0xfd2e, 0xed0f, 0xdd6c, 0xcd4d, 0xbdaa, 0xad8b, 0x9de8, 0x8dc9, 0x7c26, 0x6c07, 0x5c64, 0x4c45, 0x3ca2, 0x2c83, 0x1ce0, 0x0cc1, 0xef1f, 0xff3e, 0xcf5d, 0xdf7c, 0xaf9b, 0xbfba, 0x8fd9, 0x9ff8, 0x6e17, 0x7e36, 0x4e55, 0x5e74, 0x2e93, 0x3eb2, 0x0ed1, 0x1ef0 };
unsigned int UpdateCRC16(unsigned int crc,unsigned char value) {
unsigned int crc16;
crc16 = (CRC16_table[(crc >> 8) & 0x00FF] ^ (crc << 8) ^ (unsigned int)(value));
return crc16;
}
Access to Compax3 objects
Via RS232 and RS485 you can access the status objects (see on page 82)
I11 T11 192-120101 N6 - March 2004 81
Page 82

Status values

r
6. Status values
In this chapter you can read about:
Device............................................................................................................................................83
Motor..............................................................................................................................................83
Positions.........................................................................................................................................84
Speeds ...........................................................................................................................................85
Currents .........................................................................................................................................87
Inputs .............................................................................................................................................88
CAM...............................................................................................................................................89
IEC61131-3 ....................................................................................................................................90
Feedback system ...........................................................................................................................91
A list of the status values supports you in optimization and commissioning. Open the optimization function in the C3 ServoManager (double-click on
optimization in the tree) You will find the available status values in the lower right part of the window under
selection (TAB) “Status values“ You can pull them into the oscilloscope (upper part of the left side) or into the
status display (upper part of the right side) by the aid of the mouse (drag and drop).
Switching of the
user level
D/A-Monito
The status values are divided into 2 groups (unser levels):
standard: here you can find all important status values advanced: advanced status values, require a better knowledge
The user level can be changed in the optimization window (left hand side lower part under selection (TAB) "optimization") with the following button.
A part of the status values can be output via the D/A monitor channel 0 (X11/4) and channel 1 (X11/3).
The reference for the output voltage can be entered individually in the reference unit of the D/A monitor.
Note
The unit of measurement of the D/A monitor values differs from the unit of measurement of the status values.
Page 83
Parker EME
6.1 Device
Status values
Status of device utilization
Available in technology function:
Unit of measurement D/A monitor output
Remark:
%
not possible
Device utilization
User level
D/A monitor: measurement unit of the reference value
Stated in % of the nominal device current
Status of power output stage temperature
Available in technology function:
Unit of measurement D/A monitor output
Remark:
C
not possible
Power output stage temperature
User level
D/A monitor: measurement unit of the reference value
Status of auxiliary voltage
Available in technology function:
Unit of measurement D/A monitor output
Remark:
V
not possible
Control voltage
User level
D/A monitor: measurement unit of the reference value
Object 683.2
T10, T11, T30, T40
standard
-
Object 684.1
T10, T11, T30, T40
standard
-
Object 685.1
T10, T11, T30, T40
standard
-
6.2 Motor
Status DC bus voltage
Available in technology function:
Unit of measurement D/A monitor output
Remark:
V
possible
unfiltered signal
User level
D/A monitor: measurement unit of the reference value
Status of motor temperature
Available in technology function:
Unit of measurement D/A monitor output
Remark:
C
not possible
Motor temperature
User level
D/A monitor: measurement unit of the reference value
measured via the sensor in the motor, correct display only with KTY84
Status of short-term motor utilization
Available in technology function:
Object 685.2
T10, T11, T30, T40
standard
V
Object 684.2
T10, T11, T30, T40
standard
-
Object 683.4
T10, T11, T30, T40
I11 T11 192-120101 N6 - March 2004 83
Page 84
Status values
Unit of measurement D/A monitor output
Remark:
%
not possible
Motor pulse utilization,
User level
D/A monitor: measurement unit of the reference value
Stated in & of the motor pulse current.
Dynamic motor utilization with reference to the nominal motor current resp., in the case of a selected motor reference point, with reference to the motor reference current. For the monitoring the impulse current and the impulse current time are required in order to calculate a time constant. 1.15*I can be set permanently. Error object 500.6 Bit 6, Error Code 7180
Status of long-term motor utilization
Available in technology function:
Unit of measurement D/A monitor output
Remark:
%
not possible
Motor utilization,
Stated in & of the motor pulse current.
Effective motor utilization with reference to the nominal motor current resp. if a motor reference point is selected, with reference to the motor reference current. For the monitoring the thermal time constant Tau is required. 1.05*I can be set permanently. Error object 500.1 Bit 13, Error Code 2311
User level
D/A monitor: measurement unit of the reference value
standard
-
Object 683.3
T10, T11, T30, T40
standard
-
6.3 Positions
Status target position
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit
possible
Stated in user units, reset position
Status actual position
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit
possible
Stated in user units, reset position
Status of tracking error
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit
possible
Stated in user units, difference between target and actual value of position
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
Object 680.4
T11, T30, T40
standard
Revolutions
Object 680.5
T11, T30, T40
standard
Revolutions
Object 680.6
T11, T30, T40
standard
Revolutions
Status target position without absolute reference
Object 680.12
Page 85
Parker EME
Status values
6.4 Speeds
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit
possible
Stated in user units, continuous position
User level
D/A monitor: measurement unit of the reference value
Status actual position without absolute reference
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit
possible
Stated in user units, continuous position
User level
D/A monitor: measurement unit of the reference value
Status target speed of setpoint encoder
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s
possible
Target value according to the fine interpolator
User level
D/A monitor: measurement unit of the reference value
T11, T30, T40
advanced
Revolutions
Object 680.13
T11, T30, T40
advanced
Revolutions
Object 681.4
T10, T11, T30, T40
standard
Rev/s
Status target speed controller input
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s
possible
Nominal speed
User level
D/A monitor: measurement unit of the reference value
Target speed value on the controller input including feed forward
Status actual speed filtered
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s
possible
Actual speed filtered
User level
D/A monitor: measurement unit of the reference value
Status actual speed unfiltered
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s
possible
User level
D/A monitor: measurement unit of the reference value
Object 681.10
T10, T11, T30, T40
standard
Rev/s
Object 681.9
T10, T11, T30, T40
standard
Rev/s
Object 681.5
T10, T11, T30, T40
advanced
Rev/s
Status control deviation of speed
Available in technology function:
Unit of measurement
Unit/s
I11 T11 192-120101 N6 - March 2004 85
User level
Object 681.6
T10, T11, T30, T40
standard
Page 86
Status values
D/A monitor output
Remark:
possible
Difference between speed target value and filtered actual value
D/A monitor: measurement unit of the reference value
Status target acceleration
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s²
not possible
Target acceleration of setpoint encoder
User level
D/A monitor: measurement unit of the reference value
Stated in user units
Output value of the fine interpolator
Status of speed and acceleration feed forward
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s
not possible
Speed and acceleration feed forward
User level
D/A monitor: measurement unit of the reference value
Rev/s
Object 682.4
T10, T11, T30, T40
advanced
-
Object 681.11
T11, T30, T40
advanced
-
Status of filtered actual acceleration
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s²
possible
Signal is smoothed by acceleration filter 1 and 2 resp. by the rotational
User level
D/A monitor: measurement unit of the reference value
speed monitor and acceleration filter 2.
Signal is the source of the D-component in the (rotational) speed controller
Status of actual acceleration unfiltered
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s²
possible
Please note that this signal is often rather noisy.
User level
D/A monitor: measurement unit of the reference value
Status of external influences monitored
Available in technology function:
Unit of measurement D/A monitor output
Remark:
%
possible
Load moment resp. load force detected by the (rotational) speed monitor.
Unit is % of Mnominal resp. of Fnominal
(100% = Moment resp. force given the configured nominal resp. reference current)
User level
D/A monitor: measurement unit of the reference value
Object 682.6
T10, T11, T30, T40
advanced
Rev/s²
Object 682.5
T10, T11, T30, T40
advanced
Rev/s²
Object 683.5
T10, T11, T30, T40
advanced
%
Page 87
Parker EME
6.5 Currents
Status values
Status of effective target current (torque forming)
Available in technology function:
Unit of measurement D/A monitor output
Remark:
mA
possible
Effective target current (torque forming)
User level
D/A monitor: measurement unit of the reference value
Cross-flow target value including current and jerk feed forward
Status of effective actual current (torque forming)
Available in technology function:
Unit of measurement D/A monitor output
Remark:
mA
possible
Effective actual current (torque forming), actual value after filter
User level
D/A monitor: measurement unit of the reference value
Status of control deviation of effective current
Available in technology function:
Unit of measurement D/A monitor output
Remark:
mA
possible
Control deviation of effective current (torque forming)
User level
D/A monitor: measurement unit of the reference value
Object 688.1
T10, T11, T30, T40
standard
O
Object 688.2
T10, T11, T30, T40
standard
O
Object 688.8
T10, T11, T30, T40
advanced
O
Status of voltage control signal
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Control signal of current controller (torque forming)
0.577 correspond to full range (Terminal voltage=DC bus voltage)
Status of current phase U
Available in technology function:
Unit of measurement D/A monitor output
Remark:
mA
not possible
Phase current U, Output as peak value
Actual value after oversampling
Status of current phase V
Available in technology function:
Unit of measurement
mA
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
User level
Object 688.11
T10, T11, T30, T40
advanced
-
Object 688.9
T10, T11, T30, T40
advanced
-
Object 688.10
T10, T11, T30, T40
advanced
I11 T11 192-120101 N6 - March 2004 87
Page 88
Status values
D/A monitor output
Remark:
not possible
Phase current V, Output as peak value
D/A monitor: measurement unit of the reference value
Actual value after oversampling
Status of target jerk setpoint encoder
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit/s³
not possible
Target jerk of setpoint encoder
User level
D/A monitor: measurement unit of the reference value
Stated in user units
Output value of the fine interpolator
Status of effective current and jerk forward feed
Available in technology function:
Unit of measurement D/A monitor output
Remark:
mA
not possible
Forward feed of effective current and jerk
Stated in amperes RMS
after filter
User level
D/A monitor: measurement unit of the reference value
-
Object 688.13
T11, T30, T40
advanced
-
Object 688.14
T10, T11, T30, T40
advanced
-
6.6 Inputs
Status of analog input 0
Available in technology function:
Unit of measurement D/A monitor output
Remark:
V
possible
Analog input 0
Analog input on plug X11/9 and X11/11
Indication of the voltage measured on the input in volts
Status of analog input 1
Available in technology function:
Unit of measurement D/A monitor output
Remark:
V
possible
Analog input 1
Analog input on plug X11/10 and X11/2
Indication of the voltage measured on the input in volts
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
Object 685.3
T10, T11, T30, T40
standard
10V
Object 685.4
T10, T11, T30, T40
standard
10V
Status of encoder input 0 (5V)
Available in technology function:
Object 680.10
T10, T11, T30, T40
Page 89
Parker EME
Status values
6.7 CAM
Unit of measurement D/A monitor output
Remark:
Revolutions
not possible
Encoder input 0 (5V), counter state in turns of the encoder
User level
D/A monitor: measurement unit of the reference value
Status of encoder input 0 (24V)
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Revolutions
not possible
Encoder input 1 (24V), counter state in turns of the encoder
User level
D/A monitor: measurement unit of the reference value
Status of signal source of master position monitoring
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Revolutions
possible
User level
D/A monitor: measurement unit of the reference value
standard
-
Object 680.11
T10, T11, T30, T40
standard
-
Object 3021.2
- T40
standard
Revolutions
Status of master position
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Munit
possible
reset
Status of slave position
Available in technology function:
Unit of measurement D/A monitor output
Remark:
Unit
possible
reset position after cam table [Units]
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
Object 3030.1
- T40
standard
Units
Object 3032.1
- T40
standard
Units
I11 T11 192-120101 N6 - March 2004 89
Page 90
Status values
6.8 IEC61131-3
Status of cycle time of the control program
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Current cycle time [unit: 1=500 µs] of the control program
User level
D/A monitor: measurement unit of the reference value
Status of maximum cycle time
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Maximum cycle time [unit : 1=500 µs]
User level
D/A monitor: measurement unit of the reference value
Very large values may occur here with the command "Save objects permanently". Then the control program will no longer be executed for the execution time (about 1.5 sec)
Setpoint for analog output 0
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
possible
Setpoint for analog output 0 (DA0 - X11/4); can be used as a DA monitor.
This output must be previously activated to be able to access it. You can do this in the ServoManager in the optimization window in the partial window at the bottom left under DA monitor.
Convert the signal source to IEC61131.
User level
D/A monitor: measurement unit of the reference value
Object 50.3
T10, T11, T30, T40
standard
-
Object 50.4
T10, T11, T30, T40
standard
-
Object 634.4
T11, T30, T40
advanced
-
Setpoint for analog output 1
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
possible
Setpoint for analog output 1 (DA1 - X11/3); can be used as DA monitor.
This output must be previously activated to be able to access it. You can do this in the ServoManager in the optimization window in the partial window at the bottom left under DA monitor.
Convert the signal source to IEC61131.
User level
D/A monitor: measurement unit of the reference value
Object 635.4
T11, T30, T40
advanced
-
Page 91
Parker EME
6.9 Transmitter
Status values
Status of sine in signal processing
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Sinus trace resolver, für F10 devices
The value 1 corresponds to 2.5 Volts
The amplitude must be <1 and > 0.1 at the resolver; otherwise a level error is reported.
Status of cosine in signal processing
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Cosine trace of resolver, for F10 devices
The value 1 corresponds to 2.5 Volts
The amplitude must be <1 and > 0.1 at the resolver; otherwise a level error is reported.
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
Object 692.1
T10, T11, T30, T40
advanced
-
Object 692.2
T10, T11, T30, T40
advanced
-
Status of analog input sine
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Sine trace of encoder, für F11 and F12 devices (0.5 = 2.5V)
Status of analog input cosine
Available in technology function:
Unit of measurement D/A monitor output
Remark:
n/a
not possible
Cosine trace of encoder, für F11 and F12 devices
Status of feedback level
Available in technology function:
Unit of measurement D/A monitor output
Remark:
V
not possible
Feedback level, for F11 and F12 devices, display in Vpp
(=sqrt(sin²+cos²))
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
User level
D/A monitor: measurement unit of the reference value
Object 692.3
T10, T11, T30, T40
advanced
-
Object 692.4
T10, T11, T30, T40
advanced
-
Object 692.5
T10, T11, T30, T40
advanced
-
I11 T11 192-120101 N6 - March 2004 91
Page 92

Error

7. Error
All errors lead to error status. Reaction 2: downramp with “deenergize ramp” then apply brake (see on page 76)
and deenergize.
Reaction 5: De-energize immediately (with no ramp), close brake.
Caution! A Z-axis may drop down due to the brake delay times
Most pending errors can be acknowledged with Quit!
The following errors must be acknowledged with Power on:
0x7381, 0x7382, 0x7391, 0x7392, 0x73A0
7.1 Error list
0x2311
0x2312
0x2320
The errors as well as the error history can be viewed in the C3 ServoManager under optimization (at the top right of the optimization window).
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
0x2311 Monitor (Effective Motor Current) Reaction 2: downramp / apply brake / deenergize.
Adjustable monitoring (with motor parameter: thermal time constant and reference current) The current value can be read with the "Motor utilization" status display. An error message is generated for a motor load of 105%.
0x2312 Device rms current monitoring Reaction 2: downramp / apply brake / deenergize.
Adjustable monitoring (dependant on device parameters) The current value can be read with object 683.2 or the "Device utilization" status display.
0x2320 Overcurrent (Power output Stage) Reaction 5: deenergize immediately (without ramps), apply brake. Check motor cable Origin is a hardware signal
0x3210
Error code (hex): Error: Error reaction: Measure: Note:
0x3210 DC bus voltage too high Reaction 5: deenergize immediately (without ramps), apply brake.
The voltage on the output bus has exceeded the maximum permissible value
Page 93
Parker EME
Error
0x3222
0x4210
0x4310
0x5111
0x5112
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
0x3222 Voltage in DC bus too low (< 70V) Reaction 2: downramp / apply brake / deenergize.
Measurement via PAP
0x4210 Temperature of power output stage / device Reaction 2: downramp / apply brake / deenergize.
Measurement via PAP; source from power stage
0x4310 Motor temperature Reaction 2: downramp / apply brake / deenergize.
Source is motor temperature signal
0x5111 Auxiliary voltage 15V defective Reaction 2: downramp / apply brake / deenergize.
Measurement via PAP
0x5112 Overvoltage 24V Reaction 2: downramp / apply brake / deenergize.
Measurement via PAP
0x5116
0x5117
0x5380
0x5420
0x5421
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
0x5116 Undervoltage 24V Reaction 2: downramp / apply brake / deenergize.
Measurement via PAP
0x5117 Undervoltage options None
Used for M expansion with I/O if the external power supply is missing
0x5380 Short circuit at digital output Reaction 2: downramp / apply brake / deenergize.
Applies to the 4 on-board outputs
0x5420 Ballast resistor overload, pulse current Reaction 2: downramp / apply brake / deenergize.
Setting via tool input
0x5421 Braking Resistor overloaded (Continuous Current) Reaction 2: downramp / apply brake / deenergize.
Setting via tool input
0x5480
Error code (hex): Error: Error reaction: Measure:
0x5480 Short Circuit - Motor Brake None
I11 T11 192-120101 N6 - March 2004 93
Page 94
Error
0x5481
0x5491
0x54A0
0x54A1
Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Diagnostic lines from power stage interface
0x5481 Open Circuit - Motor Brake None
Diagnostic lines from power stage interface
0x5491 Disable power output stage Reaction 5: deenergize immediately (without ramps), apply brake.
Hardware input (safe standstill)
0x54A0 Limit switch E5 (X12/12) active Reaction 2: downramp / apply brake / deenergize. Move axis into the travel range. The error may occur if E5 is designed as a freely assignable input and for example C3_ErrorMask is used in the IEC­program. Limit switch on input 5 is active. Is only set with rising edge.
0x54A1 Limit switch E6 (X12/13) active Reaction 2: downramp / apply brake / deenergize. Move axis into the tavel range. The error may occur if E6 is designed as a freely assignable input and for example C3_ErrorMask is used in the IEC program. Limit switch on input 6 is active. Is only set with rising edge.
0x6011
0x6012
0x6280
0x6281
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure:
Note:
0x6011 Runtime overflow 31.25us Reaction 2: downramp / apply brake / deenergize.
0x6012 Runtime overflow 500us Reaction 2: downramp / apply brake / deenergize.
Runtime monitoring. Internal error
0x6280 IEC61131-3 Division by zero Reaction 2: downramp / apply brake / deenergize. Debug IEC program Division by zero occurred in the IEC program. Execution is aborted at this point and the cycle is restarted after the selected cycle time.
0x6281 IEC61131-3 cycle time exceeded Reaction 2: downramp / apply brake / deenergize. Optimize program (runtime), increase target cycle time, suppress time­intensive processes (for example saving objects in Flash) Preset nominal cycle time could not be kept. Execution is aborted and the cycle is restarted after the selected cycle time.
0x6282
0x6283
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error:
0x6282 IEC61131-3 Program stack overflow Reaction 2: downramp / apply brake / deenergize. Reduce nesting depth in function and subprogram calls Stack overflow in IEC runtime. Execution is aborted at this point and the cycle is restarted after the selected cycle time.
0x6283 IEC61131-3 FB stack overflow
Page 95
Parker EME
Error
0x6284
0x7121
0x7180
Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Reaction 2: downramp / apply brake / deenergize. Reduce the number of or the nesting depth of function module instances Stack overflow in the IEC runtime caused by too many function module entities. Execution is aborted at this point and the cycle is restarted after the selected cycle time.
0x6284 IEC61131-3 Invalid command Reaction 2: downramp / apply brake / deenergize. Recompile the program / download and verify the compiler version Invalid opcode in the IEC program Execution is aborted at this point and the cycle is restarted after the selected cycle time.
0x7121 Motor stalled Reaction 5: deenergize immediately (without ramps), apply brake.
Speed controller signal at limit for specific time
0x7180 Motor impulse current monitoring Reaction 2: downramp / apply brake / deenergize.
Adjustable monitoring (with motor parameters: pulse current time and pulse current) The current value can be read with the "Motor impulse utilization" status display. An error message is generated for a motor impulse utilization of 115%.
0x7310
0x7320
0x7381
0x7382
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
0x7310 Rotation speed too high Reaction 5: deenergize immediately (without ramps), apply brake.
Rotation speed too high
0x7320 Tracking error Reaction 2: downramp / apply brake / deenergize.
Monitoring of tracking error window incl. time
0x7381 Resolver level too high Reaction 2: downramp / apply brake / deenergize. Check feedback cable or feedback Note: The feedback excitation voltage is deactivated for level errors! Level limit exceeded, can only be reset by powering on the device again.
0x7382 Resolver level too low Reaction 2: downramp / apply brake / deenergize. Check feedback cable or feedback Note: The feedback excitation voltage is deactivated for level errors! Level has fallen below limit, can only be reset by powering on the device again.
0x7391
0x7392
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error:
0x7391 Encoder level too high Reaction 2: downramp / apply brake / deenergize. Check feedback cable (shield, abort, short-circuit) or feedback Note: The feedback power supply voltage is deactivated for F11! SinCos feedback/encoder: Level of Sine/Cosine trace too high, can only be reset by powering on the device again. The limit for Firmware >V2.x.x is at the physical limit 2.5Vss.
0x7392 Encoder level too low
I11 T11 192-120101 N6 - March 2004 95
Page 96
Error
A
0x73A0
0x73A5
0x73A6
Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Reaction 2: downramp / apply brake / deenergize. Check feedback cable (shield, abort, short-circuit) or feedback Note: The feedback power supply voltage is deactivated for F11! SinCos feedback/encoder: Level of Sine/Cosine or A/B trace too low, can only be reset by powering on the device again. The limit for Firmware >V2.x.x is at 0.4Vss. With RS422 feedback one or both traces are missing.
0x73A0 Hall commutation: invalid combination of hall signals Reaction 5: deenergize immediately (without ramps), apply brake. Check hall wiring and hall sensors for functionality. Eliminate any (EMC) malfunctions in hall signals. A hall combination that is not permitted with correct wiring was recorded during hall commutating. Can only be reset by PowerOn.
0x73A5 Automatic commutation: no standstill of the drive on start Reaction 2: downramp / apply brake / deenergize. Check the signal quality of the feedback (noise), bring the drive to a standstill (Filtered) speed of the motor within 10 s after the start of automatic commutation not zero
0x73A6 Automatic commutation: more than 60 degrees of electrical movement Reaction 2: downramp / apply brake / deenergize. Malfunction (motion caused by external source) of the motor during automatic commutation, starting current too great, incorrect parameter for commutation direction (use MotorManager to determine the values). Check feedback resolution and/or number of feedback or motor poles. The motor has moved more than permitted during automatic commutation.
0x73A7
0x73A8
0x73A9
0x73A
Error code (hex): Error:
Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
0x73A7 Automatic commutation: More than 5 degrees of electrical movement during Phase 2 Reaction 2: downramp / apply brake / deenergize. Eliminate external influence on the motor or device current is too small resp. friction is too great. Motor is not following controlled movement. In this case, the motor should stand still.
0x73A8 Automatic commutation: no standstill during phase 3 Reaction 2: downramp / apply brake / deenergize. Eliminate external influence on the motor. Check feedback. The motor is not following controlled movement (in this case: motor does not come to a standstill).
0x73A9 Auto commutation: Timeout during phase 3 Reaction 2: downramp / apply brake / deenergize. Increase the starting current and eliminate very high direction dependence or friction if any. Check feedback resolution and/or number of feedback or motor poles. The maximum time for automatic commutation has been exceeded.
0x73AA Automatic commutation: too many trials during phase 3 Reaction 2: downramp / apply brake / deenergize. Increase the starting current or eliminate external influence on the motor. Check feedback resolution and/or number of feedback or motor poles. The motor is not following assigned controlled movement.
0x73AB
Error code (hex): Error: Error reaction:
0x73AB Automatic commutation: timeout Reaction 2: downramp / apply brake / deenergize.
Page 97
Parker EME
Error
0x73AC
0x73B0
0x8120
0x8121
Measure:
Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Increase automatic commutation starting current, eliminate motor block, check parameters for motor current (too small, device extremely under­dimensioned), current controller unstable. It was not possible to successfully complete automatic commutation within 30 s.
0x73AC Automatic commutation: mo motor connected Reaction 2: downramp / apply brake / deenergize. Connect motor resp. check wiring Current controller setting full voltage without current flowing.
0x73B0 Distance coding: invalid position of reference mark Reaction 2: downramp / apply brake / deenergize.
0x8120 CRC error or passive mode (CAN) None
Field bus error: adjustable reaction (no, reaction 2)
0x8121 Bus off (CAN) None
CAN Bus inactive status Field bus error: adjustable reaction (no, reaction 2)
0x8130
0x8181
0x8182
0x8183
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure:
Note:
0x8130 FB Timeout None Check connection and master Field bus communication failure Field bus error: adjustable reaction (none, reaction2)
0x8181 Invalid velocity None Reduce setpoint value Preset speed ins too high (also externally); command was rejected
0x8182 Error CAM command Reaction 2: downramp / apply brake / deenergize.
0x8183 Watchdog test movement Reaction 2: downramp / apply brake / deenergize. Acknowledge Error occurs for example if the response times of the PC are too long for RS232 communication. Error is triggered if o40.3=0. Watchdog cannot be deactivated via o40.3=-1. Watchdog time=o40.3*100ms
0x8612
Error code (hex): Error: Error reaction: Measure:
Note:
0x8612 Reference Limit Reaction 2: downramp / apply brake / deenergize. Reference position could not be accessed. One of the limit switches was detected twice. There was no home switch or feedback zero pulse. Homing was aborted No reference point for machine zero detected within the travel range. The homing sequence was aborted. Check reference point feedback.
I11 T11 192-120101 N6 - March 2004 97
Page 98
Error
0xFF03
0xFF04
0xFF05
0xFF06
0xFF07
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
0xFF03 Object is "read only" None
No write access
0xFF04 Object cannot be read None
No read access
0xFF05 Version conflict; object data not valid in flash None
Internal error
0xFF06 No object for process data; object cannot be mapped None
This object cannot be mapped on the cyclic data
0xFF07 Data not valid None
No OPM text present
0xFF08
0xFF10
0xFF11
0xFF12
0xFF13
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
0xFF08 No convert function None
Internal error
0xFF10 Command syntax error None
Syntax error
0xFF11 Value not valid None
Argument incorrect
0xFF12 Checksum error None
Checksum CRC incorrect
0xFF13 Timeout error None
Active in binary protocol; 5 ms
0xFF14
Error code (hex): Error: Error reaction:
0xFF14 Overflow error None
Measure:
Page 99
Parker EME
Error
0xFF15
0xFF16
0xFF20
0xFF21
Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Utype error
0xFF15 Parity error None
Utype error
0xFF16 Frame error None
Utype error
0xFF20 Flash sector delete failed None
Error while deleting flash
0xFF21 Program flash cell failed None
Error while programming flash
0xFF22
0xFF23
0xFF24
0xFF30
0xFF40
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
0xFF22 Checksum error of prog. Flash area None
Error for flash checksum
0xFF23 DOWN/UPLOAD activated None
Download or upload is active
0xFF24 DOWN/UPLOAD not activated None
Download or upload is inactive
0xFF30 EEPROM Delay Count Error None
Internal error
0xFF40 Not enough memory for OSZI or AWL reserved None
An attempt was made to reserve too much memory (IEC, osci)
0xFF42
0xFF43
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error:
0xFF42 No objects available None Load application data into device (objects) Application data error; no valid objects present LED red flashing
0xFF43 No IEC61131 program
I11 T11 192-120101 N6 - March 2004 99
Page 100
Error
0xFF45
0xFF46
0xFF47
Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure: Note:
None Load application data into device (IEC61131 program). Turn device off and back on again. Application data error; no IEC61131 program available LED red flashing
0xFF45 No FBI None De-energize motor, then perform function Motor is energized! An attempt was made to execute a function at a time when the motor must be de-energized, e.g. device duplication via BDM.
0xFF46 Motor energized None
An attempt was made to perform a device duplication even though the source and target device are different (different order code)
0xFF47 Different device types None
The hardware of the source is not compatible with the hardware of the target for duplicating a device
0xFF90
0xFF91
0xFF92
0xFFA1
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure:
Note:
Error code (hex): Error: Error reaction: Measure: Note:
0xFF90 Feedback system does not correspond with feedback option None „Replace“ or update firmware, use device required for feedback. The connected feedback system cannot be used with the firmware currently in use. (for example with commutation wizard F12 feedback for F10/F11 device and vice-versa).
0xFF91 Invalid combination of hall signals gross commutation None Check hall wiring and hall sensors for functionality. Eliminate any (EMC) malfunctions in hall signals. Invalid hall combinations “000“ or “111“ were detected during hall commutation.
0xFF92 Compax3 must be started again. None Switch device off and on again or execute commands 9 and 10 one after the other. Only for F12 devices: Compax3 must be started again, as the commutation resp. the configured motor was changed by means of a configuration download. The error cannot be acknowledged.
0xFFA1 SinCos analog signals outside specification Reaction 2: downramp / apply brake / deenergize. Change feedback Feedback reports error
0xFFA2
0xFFA3
Error code (hex): Error: Error reaction: Measure: Note:
Error code (hex): Error: Error reaction:
0xFFA2 SinCos internal angle offset fault Reaction 2: downramp / apply brake / deenergize. Change feedback Feedback reports error
0xFFA3 SinCos table was destroyed via data field partition Reaction 2: downramp / apply brake / deenergize.
Loading...