Parker BAM20, BAM10, BAM30, BAM40, BAM50, BAM70 User Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
EN
FRESIT
Breathing Air Module
BAM10 - BAM70
User Guide
Original Language
DE
aerospace
climate control
electromechanical
filtration
fluid & gas handling
hydraulics
pneumatics
process control
sealing & shielding
CONTENTS
1 Safety Information ........................................................................................................................................................................................1
1.1 Markings and Symbols ........................................................................................................................................................................2
2.2 Approvals Compliance and Exemptions ............................................................................................................................................ 4
2.3 Materials of Construction ....................................................................................................................................................................5
2.4 Weights and Dimensions.....................................................................................................................................................................6
2.5 Receiving and Inspecting the Equipment ..........................................................................................................................................7
2.5.3 Lifting and Handling......................................................................................................................................................................7
2.6 Overview of the equipment..................................................................................................................................................................8
3 Installation and Commissioning..................................................................................................................................................................9
3.1 Recommended System Layout ...........................................................................................................................................................9
3.2 Locating the Equipment.......................................................................................................................................................................9
3.2.2 Space Requirements.................................................................................................................................................................... 9
3.3.1 General Requirements ...............................................................................................................................................................10
3.3.2 Securing the Module ..................................................................................................................................................................10
3.4.3 CO Monitor Remote Alarm.........................................................................................................................................................12
4 Operating the Dryer ...................................................................................................................................................................................13
4.1 Overview of controls ..........................................................................................................................................................................13
4.1.2 CO Analyser Controls.................................................................................................................................................................13
4.2 Starting the equipment ......................................................................................................................................................................14
4.3 Stopping and depressurising the equipment ..................................................................................................................................14
5 Service intervals .........................................................................................................................................................................................15
7 Declaration of Conformity..........................................................................................................................................................................21
1 Safety Information
Do not operate this equipment until the safety information and instructions in this user guide have been read and understood by all
personnel concerned.
USER RESPONSIBILITY
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE
DEATH, PERSONAL INJURY AND PROPERTY DAMAGE.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorised distributors provide product or system
options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring
that all performance, endurance, maintenance, safety and warning requirements of the application are met. The user must analyse all aspects of
the application, follow applicable industry standards, and follow the information concerning the product in the current product catalogue and in
any other materials provided from Parker or its subsidiaries or authorised distributors.
To the extent that Parker or its subsidiaries or authorised distributors provide component or system options based upon data or specifications
provided by the user, the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and
reasonably foreseeable uses of the components or systems.
Only competent personnel trained, qualified, and approved by Parker Hannifin should perform installation, commissioning, service and repair
procedures.
Use of the equipment in a manner not specified within this user guide may result in an unplanned release of pressure, which may cause serious
personal injury or damage.
When handling, installing or operating this equipment, personnel must employ safe engineering practices and observe all related regulations,
health & safety procedures, and legal requirements for safety.
Ensure that the equipment is depressurised and electrically isolated, prior to carrying out any of the scheduled maintenance instructions specified
within this user guide.
Parker Hannifin can not anticipate every possible circumstance which may represent a potential hazard. The warnings in this manual cover the
most known potential hazards, but by definition can not be all-inclusive. If the user employs an operating procedure, item of equipment or a
method of working which is not specifically recommended by Parker Hannifin the user must ensure that the equipment will not be damaged or
become hazardous to persons or property.
Most accidents that occur during the operation and maintenance of machinery are the result of failure to observe basic safety rules and
procedures. Accidents can be avoided by recognising that any machinery is potentially hazardous.
Should you require an extended warranty, tailored service contracts or training on this equipment, or any other equipment within the Parker
Hannifin range, please contact your local Parker Hannifin office.
Details of your nearest Parker Hannifin sales office can be found at www.parker.com/dhfns
Retain this user guide for future reference.
1
1.1 Markings and Symbols
The following markings and international symbols are used on the equipment or within this manual:
Caution, Read the User Guide.Wear ear protection
Risk of electric shock.Pressurised components on the system
Highlights actions or procedures which, if not performed
correctly, may lead to personal injury or death.
Highlights actions or procedures which, if not performed
correctly, may lead to damage to this product.
Highlights actions or procedures which, if not performed
correctly, could lead to electric shock.
Read the User Guide
Use a fork lift truck to move the dryer.
Remote control. The dryer may start automatically without
warning.
Conformité Européenne
When disposing of old parts always follow local waste
disposal regulations.
Waste electrical and electronic equipment should not be
disposed of with municipal waste.
2
2 Description
2.1 Technical Specification
Flow Data
ModelPipe Size
BAM10
BAM20
BAM30
BAM40
BAM50
BAM70
Stated flows are for operation at 7 bar g (100 psi g / 0.7 MPa g) with reference to 20ºC, 1 bar a, 0% relative water vapour pressure.
G 21136.840824090.45.4326.4192
G 217010.26123601368.2489.6288
G 221312.8765450170.410.2612360
G 228317.01020600226.413.6816480
G 21/2354211275750283.216.81020600
G 21/24963017851050396.8241428840
L/s
InletOutlet
m3/minm3/hr
cfmL/s
m3/minm3/hr
Performance
Pressure Dewpoint
Dryer Model
o
All Models
ISO 8573-1 classifications apply when the dryer is installed with the filtration supplied
Oxygen (O2)
Nitrogen Oxides (NO + NO2)
Sulphur Dioxide (SO2)
o
Reference conditions: 20
C, 1 bar(a), dry. Compressed air conditions: 7 bar overpressure, 35oC
ppm744109500
Vol. -%20.920.920.4 - 21.4
ppm131.82
ppm7<0.011
ISO 8573-1:2010
Water Classification
(Standard)
Inlet Challenge
(All Models)
11. 30.011
Outlet Levels
(All Models)
European
Pharmacopoeia
Operating Data
cfm
0.1
Model
All Models
Min Operating Pressure
Max Operating
bar gpsi gbar gpsi g
45813188.55413595
Pressure
Min Operating
Temperature
o
C
o
F
Electrical Data
BAM10BAM20BAM30BAM40BAM50BAM70
Supply Voltage
Connection Type
Power
1
Fuse
1 Fuses are Anti surge (T) 250VAC, 5x20mm, HBC, Breaking capacity 1500A @250VAC, IEC 60127-2, UL/CSA Ceramic body.
90 - 264V 1PH 50/60Hz
Hard wired
21 W (Max)
T3.15A
Max Operating
Temperature
o
C
o
F
3
Correction Factors
Temperature Correction Factor CFT
o
Maximum Inlet
Temperature
Pressure Correction Factor CFP
Maximum Inlet
Pressure
Dewpoint Correction Factor CFDStandard
Maximum Inlet
Pressure
C
o
F
CFT
bar g
psi g
CFP
PDP oC
PDP oF
CFD
1.601.331.141.000.890.800.730.670.620.57
253035
778695
1.001.001.00
45678910111213
587387100116131145160174189
Environmental Data
-40
-40
1.00
Relative Humidity
IP Rating
Pollution Degree
Maximum Altitude
Noise
1 Pollution Degree 2 indicates that in order for this equipment to operate safely, only non-conductive pollution (i.e. solids, liquids or ionised gases) or temporary condensation may
be present within the environment.
1
55%
IP55, indoor use only
2
2000 m
(6562) (ft)
< 80 dB(A)
2.2 Approvals Compliance and Exemptions
APPROVALS, ACCREDITATIONS AND ASSOCIATIONS
Compliance
The BAM range of compressed air breathing air purifiers have been independently performance
tested for the reduction of harmful contaminants, found in compressed air, to the levels stated in
European Pharmacopoeia.
3rd Party Performance Verification
The OIL-X EVOLUTION Coalescing Filters, used on the BAM breathing air purifiers, have been
tested in accordance with ISO12500-1 & ISO8573-4
The OIL-X EVOLUTION Dry Particulate Filters have been tested in accordance with ISO8573-4.
The air quality produced by the BAM series has been certified by a 3rd Party independent
authority test house. The air quality delivered by the BAM series exceeds the requirements of
European Pharmacopoeia (Medical book 2011, 7th Edition).
All performance validation independently has been verified by Lloyds Register and / or IUTA
(Institut fur Energie und Umwelttechnik e.v).
INTERNATIONAL APPROVALS
4
2.3 Materials of Construction
Skid base
Filter Support Frame
Inlet and Outlet Connections
Silencer Baffle and End Cap
Columns, Manifolds and Valve Blocks
Manifold and Purge End Plates
Inlet, Outlet and Exhaust Valve Block End Plates
Inlet and Exhaust Cylinders
Dryer Feet
Rear Mounting Plate
Coalescing Filter
Hygrometer Housing
Fittings
Pressure Gauge
Adsorbant
Seal Materials
Paint
150 x 75 x 18mm BS4 Parallel Flange channel
5mm Mild Steel Plate
50x50x6mm Equal Angle (BS4 and BSEN10056)
316 Steel
Aluminium
Aluminium Extrusion EN AW-6063 T6
Cast Machined EN AW-6082 T6
Cast Machined EN AC-44100-F
Aluminium Alloy
8MM Steel Plate
14SWG Mild Steel
Aluminium Housing
GR316 – BS970
Nickel Plated Brass and Nickle Plated Mild Steel
ABS Plastic casing and dial, brass connector and movement
The equipment is supplied in a sturdy wooden crate designed to be moved using a forklift truck or pallet truck. On delivery of the equipment check
the crate and its contents for damage and verify that the following items have been included with the dryer. If there are any signs of damage to the
crate please inform the delivery company immediately and contact your local Parker domnick hunter office.
2.5.1 Storage
The equipment should be stored, within the packing crate, in a clean dry environment. If the crate is stored in an area where the environmental
conditions fall outside of those specified in the technical specification, it should be moved to its final location (installation site) and left to stabilise
prior to unpacking. Failure to do this could cause condensing humidity and potential failure of the equipment.
2.5.2 Unpacking
The panels of the crate are secured using nails. Starting with the top, carefully remove each panel in turn and store them safely for future use.
2.5.3 Lifting and Handling
Lifting pockets have been provided on the module to facilitate lifting with a fork lift truck. The centre of gravity for the modules are illustrated below.
7
2.6 Overview of the equipment
Key:
RefDescriptionRefDescription
1Compressed Air Inlet Port7High Efficiency Dust filter
5PNEUDRI Compressed Air Dryer11Electrical control box
6Catalyst12Outlet Port
1.The pressure regulator is factory set to 2 Bar (29 psi) and should not require adjustment.
Carbon Monoxide Analyser and Pressure Regulator
1
8
3Installation and Commissioning
Only competent personnel trained, qualified, and approved by Parker domnick hunter should perform installation,
commissioning, service and repair procedures.
3.1 Recommended System Layout
The module should be installed, downstream of a 'wet' air receiver, with the pre-filtration supplied and optional condensate management
equipment to meet both the specification and local environmental requirements. This includes the following components:
Note. Failure to maintain the pre and after filtration will invalidate the warranty for the module.
1Compressor4Breathing Air Module
2Wet air receiver5Outlet to system
3Isolation valve
3.2 Locating the Equipment
3.2.1 Environment
The equipment should be located indoors in an environment that protects it from direct sunlight, moisture, and dust. Changes in temperature,
humidity, and airborne pollution will affect the environment in which the equipment is operating and may impair the safety and operation. It is the
customers' responsibility to ensure that the environmental conditions specified for the equipment are maintained.
3.2.2 Space Requirements
The equipment should be mounted on a flat surface capable of supporting its own weight plus the weight of all ancillary parts. The minimum
footprint requirements are specified below, however there must be adequate space around the equipment to allow airflow and access for
maintenance purposes and lifting equipment. A minimum spacing of approximately 500mm (20 ins) is recommended around all sides of the
modules and 1000mm (39.4 ins) above it.
Do Not position the equipment so that it is difficult to operate or disconnect from the electrical supply.
9
3.3 Mechanical Installation
3.3.1 General Requirements
Ensure that each filter condensate drain is suitably piped away and any effluent is disposed of in accordance with local regulations.
It is important to ensure that all piping materials are suitable for the application, clean and debris free. The diameter of the pipes must be sufficient
to allow unrestricted inlet air supply to the equipment and outlet air supply to the application.
When routing the pipes ensure that they are adequately supported to prevent damage and leaks in the system.
All components used within the system must be rated to at least the maximum operating pressure of the equipment. It is recommended that the
system be protected with suitably rated pressure relief valves.
1M20 Mounting bolt 4Isolation valve
2Compressed air inlet port 5Outlet port
3Protective dust cover6Electrical control box
3.3.2 Securing the Module
Mounting holes are provided on each corner of the skid. Once the module has been positioned in its final location ensure that it is securely fixed
in place using M20 fixing bolts.
3.3.3 Piping Connections
Remove the protective dust covers from the inlet and outlet ports and connect the system piping. Isolation valves should be fitted to both ports to
allow the module to be isolated during maintenance.
10
3.4 Electrical Installation
A fully qualified electrical engineer must undertake all field wiring and electrical work in accordance with local regulations.
3.4.1 BAM Electrical Supply
The module should be connected to a single phase electrical supply through
a switch or circuit breaker.
This device should be:
• Suitable for the application and selected in accordance with local and
national code regulations.
• Clearly and indelibly marked as the disconnecting device for the
equipment.
• Located in close proximity to the equipment and be easily accessible
to the operator.
Note. The disconnection device must be locked in the ‘OFF’ position
during installation.
Overcurrent protection must be fitted as part of the building installation. This
protection should be selected in accordance with local and national code
regulations.
Feed the supply cable through the spare cable gland and connect it to the
electrical supply terminal block. Each wire should be terminated using
suitable ferrules. Secure the cable gland to protect the terminations.
3.4.2 BAM Remote alarm indication
The module is fitted with a set of volt free relay contacts (1A max @ 250Vac
/ 30Vdc) designed for remote alarm indication.
Connection should be made to the Remote alarm terminal block.
O/NNormally open contacts
Comm Common terminal
N/CNormally closed contact
The cable used should be 0.75mm
that it is routed away from high voltage cables.
Note. The relay is energised when the module is operating under normal
conditions.
2
and not exceed 30m in length. Ensure
If the remote alarm indication relay is used, the electrical enclosure will contain more than one live circuit. The relay
connections will remain live when the mains supply is disconnected.
1Socket
2Solder pin
3Main body
4Locking cap
5Cable gland
6Gland nut
Pin configuration viewed
from the front of the socket.
The carbon monoxide analyser is fitted with a set of volt free relay contacts (1A max @ 24Vac / dc) designed for remote alarm indication. The
relay is energised in the non-alarm state (fail-safe) and releases in any alarm condition or in the event of a power failure. The relay can be set to
respond to a given set-point or level of measured carbon monoxide, please refer to the BACO200 user guide for details.
Connection to the monitor is made using the multi-pole connector supplied.
Wiring the connector
1 The connector supplied with the generator will accept 5 - 7mm cable.
2 Strip 17mm of insulation from the cable, and strip 2mm from each wire.
3 Disassemble the plug provided into its component parts.
4 Thread the cable through the component parts of the plug (items 3 - 6) as illustrated below.
5 Solder the pins onto the wires and insert the pins into the socket.
6 Push the socket into the main body until the tabs snap into place.
7 Push the cable gland and nut into the main body and tighten.
8 Attach the connector to the CO Monitor and tighten the locking cap.
1Power “ON” indicator
2Service interval indicator
3Temperature Units
4LCD
4.1.2 CO Analyser Controls
1.1
-40
Software version
Sizing dewpoint
Actual dewpoint
Dewpoint sensor fault
Service required
Economy mode
13
4.2 Starting the equipment
1 Ensure that the inlet and outlet isolation valves are closed.
2 Connect the electrical supply to the module and verify that the power on indicator on the front of the dryer is illuminated.
3 Slowly open the inlet isolation valve and verify that there are no leaks within the module.
4 Check that the system pressure relief valve is closed.
5 Test the condensate drains of the filters and ensure they are discharging correctly into a suitable collection vessel.
6 Slowly open the outlet isolation valve to allow the system to pressurise.
The module is designed for continuous use and, once running, requires no further operator intervention.
4.3 Stopping and depressurising the equipment
1 Close the outlet isolation valve followed by the inlet isolation valve.
2 De-pressurise the module by venting through the drain ball valve on the outlet dust filter.
Note: The drain valve should be opened gradually.
3 Disconnect the electrical supply to the dryer
Note: A small amount of air may be trapped between the inlet isolation valve and the dryer inlet.
14
5 Service intervals
Description of Service Required Recommended Interval:
Component Operation
MX DryerCheck POWER ON indicator is illuminated.
MX DryerCheck STATUS / FAULT indicators located on the controller.
SystemCheck for air leaks.
MX DryerCheck the pressure gauges during purging for excessive back pressure.
MX DryerCheck the condition of electrical supply cables and conduits.
MX DryerCheck for cyclic operation.
MX Dryer
Filtration
CO Safe
MX Dryer
- Replace the active exhaust silencers
Recommended Service
Replace the inlet, outlet and control air filters, and service drains.
Recommended Service
Replace the activated carbon cartridges
Recommended Service
Replace / Calibrate dewpoint transmitter (DDS Units only).
Recommended Service
(1)
CO Monitor Calibrate the CO Monitor
CO Monitor
CO Safe
Replace the electrochemical sensor
Recommended Service
Replace the Catalyst cartridges
(2)
Day
Every
Week
Every
Every
Every
Every
Every
Every
Every
month
3 months
6 months
12 months
18 months
24 months
Every
36 months
MX Dryer
MX Dryer
(1) Unlike oil aerosol removal filters which are changed annually to guarantee compressed air quality, the lifetime of the activated carbon cartridges can be attributed to various factors
and require more frequent changes. Factors affecting the lifetime of the cartridges are:
Oil vapour concentration - The higher the inlet concentration of oil vapour, the faster the activated carbon capacity will expire.
Bulk oil - Adsorption filters are designed to remove oil vapour and odours, not liquid oil or aerosols. Poorly maintained or non-existent pre-filtration will cause the OVR filter capacity to
quickly expire.
Temperature - Oil vapour content increases proportionally to inlet temperature, reducing element life. Additionally, as temperature increases, the adsorption capacity decreases, again
reducing element life.
Relative Humidity or Dewpoint - Wet air reduces the adsorptive capacity of the carbon.
Compressor oil changes - When compressor oil is changed, the new lubricant burns off “light ends” which increases the oil vapour content for hours or even weeks
afterwards. This increase in oil vapour content is adsorbed by the OVR filter, significantly reducing its adsorptive life.
The cartridge performance is based upon a maximum oil vapour inlet concentration of 0.018mg/m
These cartridges should be replaced upon detection of vapour, odour or taste.
(2) Under normal operating conditions the catalyst cartridges should be replaced every 24 months. If an oil vapour incident occurs then we recommend that the carbon and catalystcartridges are replaced at the same time .
Replace the valve seats and seals.
Recommended Service
Replace the Desiccant.
Recommended Service
3
, with compressed air at 21oC and a pressure dewpoint of -40oC PDP.
Key:
Check
ProcessReplace
15
5.1 Preventative Maintenance Kits
Note. The number of kits required is dependent upon the model of dryer as illustrated below.
Note. The quantity of desiccant material required is dependent upon the size of the module.
Ensure that the dryer is filled using a Snowstorm filler and replace the column seals.
DescriptionCatalogue NumberContentsOrder Qty
Kit: Desiccant AA60820366111 Litre Container of AA
--
Kit: Desiccant MS60820366211 Litre Container of MS
DescriptionBAM10BAM20BAM30BAM40BAM50BAM70
Kit: Desiccant AA (11.2 Ltr)81214192433
Kit: Desiccant MS (11.2 Ltr)122334
Note. One kit is required for each dryer.
DescriptionCatalogue NumberContentsOrder Qty
Kit: Column Seals608620098
Column o-rings
1
Outlet plate o-ring
DescriptionCatalogue NumberContentsOrder Qty
Snowstorm Filler608201051
Jumbo Snowstorm Filler1
Column Seal Kits
Snowstorm Filler
18
ELEMENTS
Parker filters are designed to produce clean compressed air, gas
and liquid to the highest industry standards. To maintain
impeccable results, Elements within the filter must be replaced
annually.
Choosing the Parker brand means you can be assured that
Elements are readily available, affordable and the most energy
efficient product of its kind on the market. The elements are also
supplied in 100% recyclable packaging. An additional advantage of
purchasing Parker Elements is that you will reduce your company’s
carbon footprint by 190kg. This is the equivalent of a 700 mile flight
from Edinburgh to Berlin!
Parker Filter Elements also prove to be highly efficient when used
in any leading competitor’s filters.
SPECIALISED
SERVICES
Parker Specialist Service Engineers test on-site efficiency
measuring many variables including airflow, pressure,
temperature, dewpoint and power consumption.
Our team of highly trained experts are the best in the industry.
They take into account a range of environmental factors that could
affect your system’s performance. The results from this Specialist
Service are extremely accurate and produce invaluable
information.
Importantly, Parker informed recommendations lead to significant
savings for our customers, which mean they return time and time
again for our advice and products.
SUPPORT
SERVICES
PARTS
Parker Kits make everyday maintenance easy. They are available
for all of our products and are simply value-for money. The Parts
within the kits support our customers’ varied maintenance, repair
and overhaul activities.
Additionally, Preventative Maintenance Kits can be purchased for
dryers and gas generators. These kits mean our customers dryer’s
and generator’s can be serviced easily to ensure optimum
performance.
An extensive range of durable Parker Parts can be obtained within
24 hours to any European, Middle East or African destination.
M.R.O
Maintenance Repair & Overhaul - Parker Technicians are the
industry’s finest. Their skills and qualifications are annually
approved to keep their product and legislation knowledge fresh
and expertise relevant.
With this in mind, Parker offers onsite and on demand servicing to
meet customers’ unique requirements in a timely and efficient
manner.
Parker MRO service ranges from a basic maintenance check
covered under product warranty right through to a comprehensive
programme, which even puts the onsite application under the
microscope.
With customers at the heart of everything Parker does, the MRO
service is no exception to this.
Parker Filter Elements also prove to be highly efficient when used
in any leading competitor’s filters.
Parker Support Services are the first port of call for customers in
need of help or guidance.
The fact that this team is responsible for the production of User
Guides and Manuals gives you an insight into the level and detail
of their parts and product knowledge.
Over-the-phone support is just one way in which Parker’s
extremely knowledgeable team, quickly reduces downtime or
resolves product queries.
On some occasions engineers need to be on site to carry out a
repair. In these cases, the local engineer will be quickly dispatched
to ensure our customers can return to production as soon as
possible.
One-to-one training can also be provided by our Support Services
team. This has enabled hundreds of Parker distributors to gain an
in-depth understanding. Training will also ensure distributors can
make timely repairs and easily maintain their customers’ products.
19
6 Troubleshooting
In the unlikely event that a problem occurs on the equipment, this troubleshooting guide can be used to identify the probable cause and remedy.
Troubleshooting should only be attempted by competent personnel. All major repair, and calibration work should be undertaken by a Parker
domnick hunter trained, qualified and approved engineer.
FaultProbable CauseRemedy
Check actual inlet parameters and environmental conditions
against the values quoted at the time of sizing.
Check the condensate drain(s) for faults.
Check the drain hoses are free from kinks and obstructions.
Ensure that the drain isolation valves are fully open.
Check and replace.
Check actual inlet conditions against the values quoted at
the time of sizing.
Check the system for leaks.
Ensure that the drain cocks and pressure relief valves are
closed.
Check that the dryer “POWER ON” indicator is illuminated. If
it is not check the isolator and fuses.
Check that the compressor “POWER ON” indicator is
illuminated. If it is not check the isolator and fuses.
Poor dewpoint identified by water in the
downstream piping and equipment
High pressure drop resulting in low pressure
gauge readings or intermittent operation of the
downstream equipment.
Interruption of the air supply downstream
leading to a rapid loss of system pressure.
Dryer is operating outside of its sizing criteria
Bypass valve is open.Check bypass valve is fully closed.
Dryer has recently been started.Allow time for the system to “dry down”
The condensate is not being drained.
Regeneration column pressure > 350mbar.Replace the exhaust silencers.
Timer malfunction.Contact a PdhFNS approved service agent.
Valve malfunction.Contact a PdhFNS approved service agent.
Desiccant is approaching the end of its useful life.Contact a PdhFNS approved service agent.
The pre / after filtration is approaching the end of its
operational life.
The dryer is being overflowed or is operating at a
reduced system pressure.
An isolation valve is partially closed.Check the position of all the isolation valves.
Pressure loss from the system.
The dryer tripped due to power supply interruption to
the dryer.
The compressor tripped due to power supply
interruption to the compressor.
Isolation valve closedCheck the position of the isolation valves.
Compressor switched off.Check the compressor.
Fault shutdown event.Check the dryer fault indicators.
20
R
Declaration of Conformity
EN
BAM10, BAM20, BAM30, BAM40, BAM50, BAM70
Directives
2014/68/EU
2014/30/EU
2014/35/EU
2011/65/EU
Standards used
EN60204-1: 2006 + A1:2009
EN 61000
-6-2 : 2005
EN 61000
-6-3 : 2007 + A1:2011
EN 61000
-3-2 : 2006 + A2:2009
EN 61000
-3-3 : 2008
Generally in accordance with ASMEVIII Div 1 : 2004.
PED Assessment Route :
B + D
EC Type-examination Certificate:
COV0912556/1
Notified body for PED:
Lloyds Register Verification
71 Fenchurch St. London
EC3M 4BS
Authorised Representative
Damian Cook
Division Engineering Manager
Parker Hannifin Manufacturing Limited
I declare that as the authorised representative, the above information in relation to the supply / manufacture of this product, is
in conformity with the standards and other related documents following the provisions of the above Directives.
Signature:
Date: 24/11/2016
Declaration Number: 00273/241116
Dukesway, TVTE, Gateshead, Tyne & Wear, NE11 0PZ. UK
1.1 Kennzeichen und Symbole................................................................................................................................................................ 26
2.4 Gewichte und Abmessungen ............................................................................................................................................................30
2.4.2 Modul mit Verpackung................................................................................................................................................................30
2.5 Annahme und Prüfung des Geräts ...................................................................................................................................................31
2.5.3 Anheben und Handhabung ........................................................................................................................................................ 31
2.6 Übersicht über das Gerät...................................................................................................................................................................32
3 Installation und Inbetriebnahme................................................................................................................................................................ 33
3.2 Aufstellort des Geräts ........................................................................................................................................................................33
3.3.2 Befestigung des Moduls .............................................................................................................................................................34
3.4.2 BAM-Fernüberwachung von Alarmen ........................................................................................................................................35
3.4.3 CO-Monitor zur Fernanzeige von Alarmen.................................................................................................................................36
4 Bedienung des Trockners..........................................................................................................................................................................37
4.1 Übersicht über die Bedienelemente .................................................................................................................................................37
4.1.1 Bedienelemente des Trockners..................................................................................................................................................37
4.1.2 Bedienelemente des CO-Analysators ........................................................................................................................................37
4.2 Starten des Geräts..............................................................................................................................................................................37
4.3 Stoppen des Geräts und Ablassen des Drucks...............................................................................................................................38
5.1 Sätze für die vorbeugende Wartung .................................................................................................................................................40
Vor der Inbetriebnahme des Geräts müssen die Sicherheitshinweise und Anweisungen in diesem Handbuch vom zuständigen Personal
gründlich gelesen und verstanden worden sein.
BENUTZERHAFTUNG
MÄNGEL AN ODER FALSCHE AUSWAHL BZW. VERWENDUNG DER HIER BESCHRIEBENEN PRODUKTE ODER ZUGEHÖRIGEN
ELEMENTE KÖNNEN ZUM TOD FÜHREN ODER VERLETZUNGEN BZW. SACHSCHÄDEN ZUR FOLGE HABEN.
Dieses Dokument und andere Mitteilungen der Parker Hannifin Corporation, der Tochtergesellschaften und Vertragshändler stellen Produkt- oder
Systemvarianten zur weiteren Auswertung durch Anwender mit technischem Know-how dar.
Der Anwender ist auf der Grundlage seiner eigenen Analyse und Testergebnisse allein für die endgültige Auswahl des Systems und der
Komponenten verantwortlich. Er hat sicherzustellen, dass alle Leistungs-, Haltbarkeits-, Wartungs-, Sicherheits- und Warnvoraussetzungen des
jeweiligen Einsatzbereichs erfüllt sind. Der Anwender ist dazu verpflichtet, alle Aspekte der Anwendung zu analysieren, geltende
Branchennormen einzuhalten und die Produktinformationen im aktuellen Produktkatalog sowie in anderen von Parker bzw. den
Tochtergesellschaften oder Vertragshändlern zur Verfügung gestellten Materialien zu beachten.
Soweit Parker, die Tochtergesellschaften oder Vertragshändler Komponenten oder Systemvarianten basierend auf technischen Daten oder
Spezifikationen liefern, die vom Anwender bereitgestellt wurden, ist der Anwender dafür verantwortlich, festzustellen, dass diese technischen
Daten und Spezifikationen für alle Anwendungen und vernünftigerweise vorhersehbaren Verwendungszwecke der Komponenten oder Systeme
geeignet und ausreichend sind.
Installation, Inbetriebnahme, Wartung und Reparatur dürfen nur von entsprechend ausgebildetem und von Parker Hannifin zugelassenem
Personal durchgeführt werden.
Wenn das Gerät nicht gemäß der in diesem Benutzerhandbuch spezifizierten Anweisungen verwendet wird, kann es zu einem unbeabsichtigten
Druckabbau und infolgedessen zu schweren Verletzungen oder Sachschäden kommen.
Beim Umgang, bei der Installation und der Bedienung des Geräts muss das Personal sichere technische Verfahren einsetzen und alle
entsprechenden Bestimmungen, Gesundheits- und Sicherheitsvorschriften befolgen sowie alle gesetzlichen Sicherheitsbestimmungen einhalten.
Vergewissern Sie sich vor der Durchführung jeglicher in diesem Handbuch beschriebener Wartungsarbeiten, dass das Gerät drucklos und von
der Stromversorgung getrennt ist.
Parker Hannifin kann nicht jeden Umstand vorhersehen, der eine potenzielle Gefahrenquelle darstellt. Die Warnungen in diesem Handbuch
decken die bekanntesten Gefahrenquellen ab, können jedoch niemals allumfassend sein. Setzt der Anwender ein Bedienverfahren, ein
Geräteteil oder eine Arbeitsmethode ein, die nicht ausdrücklich von Parker Hannifin empfohlen wurden, muss der Anwender sicherstellen, dass
das Gerät nicht beschädigt wird bzw. keine Personen- oder Sachschäden verursachen kann.
Die meisten Unfälle, die während des Betriebs und der Wartung von Maschinen passieren, lassen sich darauf zurückführen, dass grundlegende
Sicherheitsvorschriften und -verfahren missachtet wurden. Unfälle können durch das Bewusstsein vermieden werden, dass jede Maschine eine
potenzielle Gefahr darstellt.
Sollten Sie eine verlängerte Garantiezeit wünschen oder einen an Ihre Bedürfnisse angepassten Wartungsvertrag bzw. Schulungen für dieses
oder ein anderes Gerät aus der Produktpalette von Parker Hannifin benötigen, wenden Sie sich bitte an die nächstgelegene Vertretung von
Parker Hannifin.
Informationen zur nächstgelegenen Vertriebsniederlassung von Parker Hannifin finden Sie unter www.parker.com/dhfns.
Bewahren Sie dieses Handbuch zur späteren Verwendung auf.
25
1.1 Kennzeichen und Symbole
Folgende Kennzeichen und internationale Symbole dienen als Hinweise auf dem Gerät und in diesem Handbuch: