514C DC Controller
Product Manual
HA463296 Issue 8
Copyright 2016 Parker Hannifin Manufacturing Ltd.
All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed by a Parker Hannifin Manufacturing Limited company without written permission from Parker Hannifin Manufacturing Ltd. Although every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to make amendments or correct omissions. Parker Hannifin Manufacturing Limited cannot accept responsibility for damage, injury, or expenses resulting therefrom.
WARRANTY
The general terms and conditions of sale of goods and/or services of Parker Hannifin Europe Sarl, Luxembourg, Switzerland Branch, Etoy apply to this product unless otherwise agreed. The terms and conditions are available on our website www.parker.com/termsandconditions/switzerland
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Cont.2
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS
DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL
INJURY AND PROPERTY DAMAGE.
This document and other information from Parker-Hannifin
Corporation, its subsidiaries and authorized distributors
provide product or system options for further investigation by
users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance, endurance,
maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry standards, and follow
the information concerning the product in the current product
catalog and in any other materials provided from Parker or its
subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized
distributors provide component or system options based upon
data or specifications provided by the user, the user is
responsible for determining that such data and specifications
are suitable and sufficient for all applications and reasonably
foreseeable uses of the components or systems.
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Cont.3
Requirements
IMPORTANT: Please read this information BEFORE installing the equipment.
Intended Users
This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation.
The information given is intended to highlight safety issues, EMC considerations, and to enable the user to obtain maximum benefit from the equipment.
Complete the following table for future reference detailing how the unit is to be installed and used.
INSTALLATION DETAILS
Serial Number (see product label)
Where installed
(for your own information)
Unit used as a:
(refer to Certification for the Inverter)
Component Relevant Apparatus
Unit fitted:
Wall-mounted Enclosure
Application Area
The equipment described is intended for industrial motor speed control utilising DC Shunt Wound or DC Permanent Magnet Motors.
Personnel
Installation, operation and maintenance of the equipment should be carried out by qualified personnel. A qualified person is someone who is technically competent and familiar with all safety information and established safety practices; with the installation process, operation and maintenance of this equipment; and with all the hazards involved.
Product Warnings
Caution
Risk of electric
shock
Caution
Refer to
documentation
Earth/Ground
Protective Conductor
Terminal
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Cont.4
Hazards
DANGER! - Ignoring the following may result in injury
1. This equipment can endanger life by exposure to
rotating machinery and high voltages.
2. The equipment must be permanently earthed due to
the high earth leakage current, and the drive motor must be connected to an appropriate safety earth.
3. Ensure all incoming supplies are isolated before
working on the equipment. Be aware that there may be more than one supply connection to the drive.
4. There may still be dangerous voltages present at
power terminals (motor output, supply input phases, DC bus and the brake, where fitted) when the motor is at standstill or is stopped.
5. For measurements use only a meter to IEC 61010 (CAT
III or higher). Always begin using the highest range. CAT I and CAT II meters must not be used on this product.
6. Allow at least 5 minutes for the drive's capacitors to
discharge to safe voltage levels (<50V). Use the specified meter capable of measuring up to 1000V dc & ac rms to confirm that less than 50V is present between all power terminals and earth.
7. Unless otherwise stated, this product must NOT be
dismantled. In the event of a fault the drive must be returned. Refer to "Routine Maintenance and Repair".
WARNING! - Ignoring the following may result in injury or damage to equipment
SAFETY
Where there is conflict between EMC and Safety requirements, personnel safety shall always take precedence.
Never perform high voltage resistance checks on the
wiring without first disconnecting the drive from the circuit being tested.
Whilst ensuring ventilation is sufficient, provide
guarding and /or additional safety systems to prevent injury or damage to equipment.
When replacing a drive in an application and before
returning to use, it is essential that all user defined parameters for the product’s operation are correctly installed.
All control and signal terminals are SELV, i.e. protected
by double insulation. Ensure all external wiring is rated for the highest system voltage.
Thermal sensors contained within the motor must have
at least basic insulation.
All exposed metalwork in the Inverter is protected by
basic insulation and bonded to a safety earth.
RCDs are not recommended for use with this product
but, where their use is mandatory, only Type B RCDs should be used.
EMC
In a domestic environment this product may cause
radio interference in which case supplementary mitigation measures may be required.
This equipment contains electrostatic discharge
(ESD) sensitive parts. Observe static control precautions when handling, installing and servicing this product.
This is a product of the restricted sales distribution class
according to IEC 61800-3. It is designated as “professional equipment” as defined in EN61000-3-2. Permission of the supply authority shall be obtained before connection to the low voltage supply.
CAUTION!
APPLICATION RISK
The specifications, processes and circuitry described herein are for guidance only and may need to be adapted to the
user’s specific application. We can not guarantee the suitability of the equipment described in this Manual for individual applications.
RISK ASSESSMENT
Under fault conditions, power loss or unintended operating conditions, the drive may not operate as intended. In particular:
Stored energy might not discharge to safe levels as
quickly as suggested, and can still be present even though the drive appears to be switched off
The motor's direction of rotation might not be controlled The motor speed might not be controlled The motor might be energised
A drive is a component within a drive system that may influence its operation or effects under a fault condition. Consideration must be given to:
Stored energy
Supply disconnects
Sequencing logic
Unintended operation
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Cont.5
Contents
Chapter 1 Product Overview 1-1
Description ................................................................... 1-1
Product Range .............................................................. 1-1
540 TO 514C upgrade ................................................ 1-1
Product Identification .................................................... 1-2
Technical Specification ................................................. 1-3
Environmental Requirements ......................................... 1-5
EMC Technical Ratings ................................................. 1-6
Product Code ............................................................... 1-6
Chapter 2 Pre-Installation Planning 2-1
Basic Wiring Diagrams ................................................. 2-1
Terminal Descriptions ................................................... 2-2
Terminal Comparison 540/1 to 514C .......................... 2-4
Block Diagram ............................................................. 2-1
Functional Differences 514C - 540 ............................... 2-2
Chapter 3 Installation Procedure 3-1
Installation Precautions ................................................. 3-1
Mechanical Installation ................................................. 3-1
Installation Information ................................................. 3-3
Electrical Installation ..................................................... 3-3
Requirements for UL Compliance .................................. 3-5
Chapter 4 Setting-Up & Commissioning 4-1
Option Switches ........................................................... 4-1
Potentiometers ............................................................. 4-2
Basic Setting-up Procedure ........................................... 4-3
Running Performance Adjustments ................................ 4-7
Chapter 5 Diagnostics and Fault Finding 5-1
Diagnostic Leds ............................................................ 5-1
Drive Trips ................................................................... 5-2
Diagnostic Test Point Descriptions ................................. 5-2
Troubleshooting ........................................................... 5-4
Chapter 6 Certification 6-1
European Directives and the CE Mark ........................... 6-1
Chapter 7 Service and Repair 7-1
DISPOSAL .................................................................... 7-1
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Product Overview1-1
514C Product Manual
Chapter 1 Product Overview
DESCRIPTION
The 514C controller is intended for use in an Industrial Environment, it should be mounted within an enclosure which provides protection to the controller and the user.
The controller should be permanently earthed at the terminals provided.
The 514C controller is designed to control the speed of a DC Shunt wound or permanent magnet motor. It will provide control of the motor speed in all 4 Quadrants of operation.
The controllers are designed to operate from a single phase AC mains supply in the range of 110 Vac to 415 Vac at 50 or 60 Hz. An auxiliary supply is required for internal power supply generation and main supply contactor sequencing. Coding is derived from the main power terminals and is functional over the whole input voltage range.
The Speed of the DC Motor is controlled using a linear closed loop system with a feedback signal from either tachogenerator or armature voltage, the feedback source being switch selectable.
A current loop within the speed loop always ensures that controlled levels of current are applied to the motor, actual levels being scaleable via programmable switches.
Motor protection is provided by a Stall detection circuit which will remove current from the motor after approximately 60 seconds.
Controller protection is provided by an Instantaneous Overcurrent trip circuit overriding control in the event of a Short Circuit.
PRODUCT RANGE
Product
Rating
514C-04
4A DC Full Load Current
514C-08
8A DC Full Load Current
514C-16
16A DC Full Load Current
514C-32
32A DC Full Load Current
540 TO 514C UPGRADE
The 514C is designed to be functionally equivalent to the 540 series controllers not a direct replacement. Comparisons between the two controllers connectors are included throughout the manual.
Chapter 2 describes the terminal connectors to the 514C controller, in that section on page 2-4 is given a terminal to terminal comparison of 540/1 to 514C.
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
1-2 Product Overview
514C Product Manual
PRODUCT IDENTIFICATION
FIELD TERMINALS
HEATSINK
LEGEND PLATE
CONTROL
FIXING POINTS
PCB
PROTECTIVE
GROUND
POWER PCB
AUXILIARY
POWER
TERMINALS
SW2
SW3 SW4
1
ON
SW1
1 2 3 4 5 6 7 8 9 10
DIAGNOSTIC
SOCKET
Option Switches
Current Calibration
Switches
POTENTIOMETERS
DIAGNOSTIC LEDS
SUPPLY
AUXILIARY SUPPLY SELECTOR SWITCH
24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
L1 POWER ON L2 STALL TRIP L3 OVERCURRENT L4 PLL LOCK L5 CURRENT LIMIT
RAMP UP P1 RAMP DOWN P2 SPEED PROPORTIONAL P3 SPEED INTEGRAL P4 CURRENT LIMIT P5 CURRENT PROPORTIONAL P6 CURRENT INTEGRAL P7 IR COMPENSATION P8 P9 MAX SPEED CALIBRATION P10 ZERO SPEED ADJUST P11 ZERO SPEED THRESHOLD P12
A1 A2 A3 A4
CONTROL TERMINAL BLOCK
FL1 FL2 F- F+
L2/N L1 A+ A-
Tenths Unit Tens
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Product Overview1-3
514C Product Manual
TECHNICAL SPECIFICATION
General
SPEED CONTROL
Control Action
Closed Loop with Proportional Integral Control and Adjustable Stability
Speed Feedback
Armature Voltage
Tachogenerator
100% Load Regulation
2 % Typical
0.1 % Typical
Maximum Torque/Speed Range
20:1
100:1
Overload
150% for 60 seconds.
TORQUE CONTROL
Control Action
Closed Loop with Proportional Integral Control.
Accuracy
2 %
Overspeed
Inherent.
Overload
None 100% continuous (consideration must be given to motor when operating at low speed).
INPUTS / OUTPUTS
Analogue
Setpoint Ramp
0 to ±10V
100 Kohm
Inputs
Positive Trim Setpoint
0 to ±10V
100 Kohm
Negative Trim Setpoint
0 to ±10V
100 Kohm
Current Limit
0 to +7.5V
50 Kohm
Current Demand
0 to ±10V
100 Kohm
Tachogenerator Input
0 to ±350Vdc
220 Kohm
Thermistor / Microtherm Input
<200 ohm = Normal >1800 ohm = Overtemperature
5 Kohm Outputs
Setpoint Ramp
0 to ±10V
5 mA
Analogue
Total Setpoint
0 to ±10V
5 mA
Speed
0 to ±10V
5 mA
Current Demand
0 to ±10V
5 mA
Current Meter
0 to ±5V (0 to Ical)
5 mA
Bipolar or Modulus
See SW1/8
+10V Reference
+10V
5 mA
-10V Reference
- 10V
5 mA
Digital
Run
+10 to +24V
100 Kohm
Inputs
Enable
+10 to +24V
100 Kohm
Stall Override
+10
100 Kohm
Digital
Health
+24V
50 mA Source
Outputs
Zero Speed or Setpoint
+24V
50 mA Source
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
1-4 Product Overview
514C Product Manual
Electrical Ratings
INPUT RATINGS
SYMBOL
514C-04
514C-08
514C-16
514C-32
Supply Voltage
Vs
110 - 480 Vac 10%
Maximum Supply Voltage (Derived from
480Vac L - L Non earth referenced (IT) or earth referenced (TN)
Three Phase Supply)
480Vac L - N Earth referenced (TN)
Supply Current
Is
6A
12A
24A
48A
Supply Frequency
fs
50/60 Hz ñ 5 Hz
Auxiliary Supply
Vaux
110/120 or 220/240 Vac ±10%
Aux. Supply Current
Iaux
3A (Includes Contactor Coil Current)
Contactor Coil Current
3A Maximum
Installation Category
Overvoltage Category III
Earth Leakage
Without Filter - 5mA
(1)
Current at 480Vac
With Filter - 50mA
OUTPUT RATINGS
Nominal Armature Voltage
Va
90 Vdc at 110/120 Vac 180 Vdc at 220/240 Vac
320 Vdc at 380/415 Vac
Maximum Armature Current
Ia
4A dc 10%
8A dc 10%
16A dc 10%
32A dc 10%
Armature Current Calibration 100%
Ical
0.1 to 4A
in 0.1A steps
0.1 to 8A
in 0.1A steps
0.1 to 16A in 0.1A
steps
0.1 to 32A
in 0.1A steps
Nominal Motor Power
Pm
1.125kW
2.25 kW
4.5 kW
9 kW
at 320 Vdc Armature
HP
11/2 HP
3 HP
6 HP
12 HP
Overload
150% for 60 seconds
Field Current
If
3 A dc
Field Voltage
Vf
0.9 X Supply Voltage (Vs)
Maximum Armature Form Factor
1.5
Thyristor I2t
300 A2s
Typical Controller Dissipation at Ia 100%
15W
(2)
25W
(2)
50W
(2)
75W
(2)
UL Listed Rating @ 180V dc
HP 1/2 HP
1 HP
3 HP
5 HP
Notes:- (1) Permanent earthing mandatory.
(2) See page 3-2 for filter watt loss information.
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Product Overview1-5
514C Product Manual
Mechanical
514C-04
514C-08
514C-16
514C-32
Overall Width
160mm
Overall Height
240mm
Overall Depth
90mm
90mm
130mm
130mm
Weight
1.6Kg
1.6Kg
3.0Kg
3.0Kg
Airflow Clearance
75mm Above and Below
Mounting Centres
210mm Vertical x 148mm Horizontal
Control Terminals - 1 to 24
Screw Terminals will accept 2.5mm2 stranded wire.
Terminal Tightening Torque 0.45 Nm, 4.0 lbf-in.
Auxiliary Supply Terminals - A1 to A4
Screw Terminals will accept 4mm2 stranded wire.
Terminal Tightening Torque 0.5 Nm, 4.5 lbf-in.
Field Terminals - FL1, FL2, F-, F+
Screw Terminals will accept 4mm2 stranded wire.
Terminal Tightening Torque 0.5 Nm, 4.5 lbf-in.
Power Terminals ­L2/N, L1, A+, A-
M5 Studs with Clamp.
Terminal Tightening Torque 2.7 Nm, 24 lbf-in.
Earth (Grounding) Terminals
M5 Cheese Head Screw.
Terminal Tightening Torque 7.1 Nm, 63 lbf-in.
ENVIRONMENTAL REQUIREMENTS
Enclosure
Chassis Mounting IP00 (UL open-type)
Operating Temperature
0 to +40oC. (Derate 1.5%/Degree above 40oC).
Humidity
85% R.H. at 40oC. (Non-condensing).
Altitude
Above 1000m derate at 1% / 100m to a maximum of 2000m.
Storage Temperature
-25oC to +55oC.
Pollution
Pollution Degree 2.
Transport Temperature
-25oC to +70oC.
Overvoltage
III
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
1-6 Product Overview
514C Product Manual
EMC TECHNICAL RATINGS
Immunity
Port
Phenomenon
Test Standard
Level
Criterion
Generic
Standard
Enclosure Port
ESD RF Field
BS EN 61000-4-2
(1995)
8kV AD 10V/m,1kHz, AM
Self Recovery No Change
EN50082-1
(1992),
RF Field Pulse Modulation
ENV 50140 ENV
50204
10 V/m P.M.
Self Recovery
and
EN50082-2
Power Ports
Fast Transient Burst
BS EN 61000-4-4
(1995)
2kV
Self Recovery
(1995)
Bulk Current Injection
ENV 50141
10V, 1kHz, AM
No Change
Surge Test
BS EN 61000-4-5
(1995)
2kV Common Mode 2kV Differential Mode
Self Recovery
Signal & Control
Fast Transient Burst
BS EN 61000-4-4
(1995)
2kV
Self Recovery
Bulk Current Injection
ENV 50141
10V, 1kHz, AM
No Change
Power Interfaces
Fast Transient Burst
BS EN 61000-4-4
(1995)
2kV
Self Recovery
Bulk Current Injection
ENV 50141
10V, 1kHz, AM
No Change
Emissions
Port
Phenomenon
Test Standard
Level
Generic Standard
Enclosure Port
Radiated
EN55011
Class B #
EN50081-1 (1992),
Power Port
Conducted
EN55011
Class B *
EN50081-2 (1994)
Notes: These levels of performance are achieved when installed as specified with the
recommended Supply Filter.
* Achieved with up to 50m of motor cable. # Achieved with unscreened signal
and control cables.
PRODUCT CODE
Block
Product
Code
Feature
1
Basic Product
514C
2
Current Rating
04
4 amp
08
8 amp
16
16 amp
32
32 amp
3
Livery
00
Standard
01 to 99
Customer
4
Cover
00
IP00 Open Frame
5
Special Options
00
Standard
01-99
Documented Special Options
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
Pre-Installation Planning 2-1
514C Product Manual
Chapter 2 Pre-Installation Planning
BASIC WIRING DIAGRAMS
Basic Connection
FS5 FS6
1 3 4 5 6 7 8 9 10 11 12 14 15 16 19 23 13
10K
SPEED
FS1
L1
L2/N
FS2
A4
RUN
TACHOGENERATOR
Branch Protection (Fuses or Circuit Breaker)
10K
10K
100%
CURRENT
LIMIT
EXTERNAL
(Optional)
SETPOINT
Speed Relay
Health Relay
PE
0 to
24
A3 A2 A1
AC Supply Contactor
22
Microtherm
A+ A-
F+ F- FL1 FL2
FS3 FS4
DC Motor
OPTIONAL
20
ENABLE
Auxillary AC Supply
Mains Supply
PE
GRD
Signal Ground
1
2
GND
1
It is recommended that the “0V/common” be connected to protective earth/ground for safety reasons. In a system comprising of more than one controller, the 0V/common” signals
should be connected together and joined to protective earth/ground at one point only.
2
Stall override link between terminals 14 and 15 required when using controller in current control.
EMC Connections With Filter
Product
L1 L2 PE
F+ F-
A+ A-
PE
PE
DC MotorScreened Cable
AC Supply
PE
FL1 FL2
Filter
Screened Cable
PE
A3 A4 A1 A2
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com