Para systems ETR500, ETR1000, ETR700, ETR1500, ETR1500p15 User Manual

...
Page 1
User's Manual
Entrust
Series UPS
Page 2
1
© Copyright 2007
1. Introduction 2
3. Installation 7
4. Operation 10
5. Troubleshooting 12
6. Replacing the Battery 13
7. Obtaining Service 16
8. Specifications 17
9. Limited Product Warranty 19 A1 . Declaration of Conformity 20
English
Page 3
2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
English
Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service.
Please read this manual before installing your Entrust Series UPS, models ETR500, ETR700, ETR1000, ETR1500, ETR700p15, ETR1500p15 as it pro­vides important information that should be followed during installation and main­tenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the Technical Support Depart­ment can rapidly assist you.
This symbol indicates "A TTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply"
This symbol indicates "Alternating Current Supply Phase"
Page 4
3
WARNING: Risk of Electrical Shock. Hazardous live parts inside
these power supplies are energized from the battery even when the AC input is disconnected.
CAUTION! T o de-energize the output s of the UPS:
1. If the UPS is on press and release the On/Off Button.
2. Disconnect the UPS from the AC wall outlet.
3. T o de-energize the UPS completely, disconnect the battery.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect the UPS from the AC wall outlet before inst alling a computer interface cable. Reconnect the power cord only after all signaling connections are made.
CAUTION! Connect the UPS to a two pole, three wire grounding
AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse). Connection to any other type of receptacle may result in a shock hazard and violate local electrical codes. Do not use extension cords, adapter plugs, or surge strips.
English
CAUTION! T o reduce the risk of electrical shock with the installa-
tion of this UPS equipment and the connected equipment, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
W ARNING: This Uninterruptible Power Supply contains potentially
hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user ser­viceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONL Y.
CAUTION! To reduce the risk of fire, connect only to a circuit
provided with 20 amperes maximum branch circuit over-current pro­tection in accordance with the National Electric Code, ANSI/NFPA
70.
Page 5
4
English
After removing your UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to the manufacturer, please use the original packing material. Since the manufacturer is not responsible for ship­ping damage incurred when the system is returned, the original packing mate­rial is inexpensive insurance. PLEASE SA VE THE P ACKING MA TERIALS!
Receiving Inspection
NOTICE: This equipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Sub­part J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Depart­ment of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equip­ment generates and uses radio frequency and if not installed and used properly , that is, in strict accordance with the manufacturer's instructions, this equip­ment may cause interference to radio and television reception. If this equip­ment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient the receiving antenna. Relocate the computer with respect to the receiver. Move the computer away from the receiver . Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's authority to operate the equipment.
NOTE: These UPSs are shipped with the batteries disconnected. The batter­ies must be connected before putting these UPSs into service. Refer to Sec­tion 3 "Installation" for connecting the batteries.
Page 6
5
English
Life Support Policy
As a general policy , we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reason­ably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. We do not recommend the use of any of our prod­ucts in direct patient care. We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) our liability is adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices desig­nated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options on many of our UPS systems. We do not claim that units with this modification are certified or listed as Hospital Grade by us or any other organization. There­fore, these units do not meet the requirements for use in direct patient care.
Page 7
6
English
1. On/Off Button.
2. AC Mode (Green) LED.
3. On Battery (Y ellow) LED.
4. Bad Battery/Overload/Fault (Red) LED.
5. Input power cord.
6. Surge Only output power receptacles.
7. The USB communications port is for UPS monitoring and control.
8. The RJ1 1/45 are used for phone/fax/modem and network protection.
9. Battery Backup and Surge output power receptacles.
10. Input circuit breaker .
Output Power Receptacles
ETR500
NEMA 5-15P W/6 ft cord
Model #
ETR700
4-NEMA 5-15R Surge Only 4-NEMA 5-15R Battery Backup & Surge
Input Power Plug
ETR1000 ETR1500 ETR700p15
ETR1500p15
NEMA 5-15P W/15 ft cord
Page 8
7
English
INSTALLATION PLACEMENT
This UPS series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Select a location which will provide good air circulation for the UPS at all times. Route power cords so they cannot be walked on or damaged.
INST ALLATION
Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries discon­nected. The batteries must be connected before putting these UPSs into service. See the Connecting The Batteries procedure to connect the batteries.
Low Battery
Green LED
Short/Fault Mode
Overload
AC Mode
Over-Bat/Bat Fault
Off
Overload
Normal
Self low Battery
Buck
Boost
Normal
Self-Test
UPS Status
Status LED and Alarm Table
Battery Mode
Yellow LED Red LED Alarm
Off Off
Off Off
OffOff Off Off
Off
Off
Off
Off
Off Off
Off Off
Off Off
Off
On On
On Continuous
On
On
On
1-Beep/5-sec
1-Blink/1.5sec
2-Blinks/sec
2-Blinks/sec
2-Blinks/sec 2-Blinks/sec
2-Blinks/sec
2-Blinks/sec
1-Beep/5-sec
3-Beeps/30-sec
2-Beeps/sec
2-Beeps/5-sec
2-Beeps/sec
3-Beeps/5-sec
All LEDs cycle (each LED Blinks 1/1.5seconds)
Page 9
8
English
CONNECTING THE BA TTERIES
(QUALIFIED SERVICE PERSONNEL ONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to connect the batteries.
1. Remove the UPS from the shipping box and set on a table or a bench top.
2. Remove the retaining screws from the bottom of the front panel of the UPS. (FIG. 1)
3. Gently push the top of the battery compartment cover inward and then slide the battery compartment cover off the UPS. (FIG. 2)
4. For the ETR500/700: Grasp the battery pull tab and gently pull the battery out far enough to connect the battery positive (Red) wire. (FIG. 3) NOTE: The ETR1000/1500 have Red Anderson connectors to connect the battery.
5. Verify proper polarity. For the ETR500/700: Connect the battery positive (Red) wire to the battery positive (Red) terminal. For the ETR1000/1500: Connect the two Red Anderson connectors together. (FIG. 3) NOTE: Some sparking might occur, this is normal.
6. Re-install the battery compartment cover onto the UPS. WARNING: DO NOT pinch the battery wires with battery comp artment cover.
7. Re-install the battery compartment cover retaining screws.
8. Continue with the rest of the Installation.
FIG. 3: ETR500
FIG. 1
FIG. 2
Page 10
9
English
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to an AC source and there is an acceptable AC voltage present (90 - 150VAC). It is recommended that the UPS's batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately, however, the “On Battery” runtime maybe less than normally expected. NOTE: If the UPS is going to be out of service or stored for a prolonged period of time, the batteries must be recharged for at least twenty-four hours every ninety days.
USB COMMUNICATIONS PORT CONNECTION (OPTIONAL) The Power Monitoring Software can be used with the UPS. Use the interface cable that comes with the UPS. Connect one end of the USB cable to the USB communications port on the rear panel of the UPS. Connect the other end of the USB cable to the device that will be monitoring/controlling the UPS. NOTE: Connecting to the communications port is optional. The UPS works properly without this connection.
CONNECTING THE UPS TO AN AC SOURCE
CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA 70. Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, or surge strips.
CONNECTING YOUR EQUIPMENT
Plug the mission critical equipment into the Battery Backup & Surge output receptacles on the rear panel of the UPS. Plug the non-critical equipment into the Surge Only output receptacles on the rear panel of the UPS. Do not use extension cords, adapter plugs or surge strips on the output of the UPS. En­sure that you do not exceed the maximum output rating of the UPS (refer to the information label or the electrical specifications in this manual).
CAUTION! DO NOT connect a laser printer to the output recep­tacles on the UPS.
FIG. 3: ETR700 FIG. 3: ETR1000/1500
Page 11
10
English
SYSTEM OVERVIEW
This Line-Interactive UPS protects computers, internetworking, and telecom­munications equipment from blackouts, brownouts, overvoltages, and surges. The A VR function continuously corrects the voltages, in-between the brownout and overvoltage transfer points (90 - 150V AC), to a safe usable level. When the UPS is operating in the A VR mode the audible alarm will remain silent and the AC Mode indicator will blink. During normal AC operation, the UPS will quietly and confidently protect your system from power anomalies.
The UPS will charge the batteries with the UPS in the on or off position when the UPS is plugged into the wall outlet and there is an acceptable AC volt age present (90 - 150V AC). When a blackout, brownout, or an overvoltage condition occurs; the UPS will transfer to the battery mode, the On Battery indicator will illuminate and the audible alarm will sound once every five seconds indicating that the commercial power is lost or unacceptable. When the commercial power returns or is at an acceptable level, the UPS will automatically transfer back to the AC normal mode and start recharging the batteries. During an extended outage when there is approximately two minutes of backup time re­maining the audible alarm will sound twice every five seconds. This Low Bat­tery Warning is letting the user know that they should save all open files and turn off their computer . When the batteries reach the predetermined level the UPS will automatically shutdown protecting the batteries from over discharg­ing. Once the commercial power returns the UPS will automatically restart, providing safe usable power to the connected equipment and start recharging the batteries.
PHONE/F AX/MODEM/NETWORK PROTECTION CONNECTION (OPTIONAL) Connect a 10/100 Base-T network, single line phone, fax or modem line to the RJ-1 1/45 modular connectors on the rear p anel of the UPS. This connection will require another length of telephone cable (provided) or network cable. The cable coming from the telephone service or network system is connected to the port marked “IN”. The equipment to be protected is connected to the port marked "OUT". NOTE: Connecting to the phone/fax/modem/network modular connectors is optional. The UPS works properly without this connection.
Page 12
11
English
USB COMMUNICA TIONS PORT
The USB communications protocol is HID. The HID USB driver comes stan­dard in the Windows OS. Simply plug the USB cable into the UPS and the computer then follow the prompts on the screen.
WEAK/BAD BA TTERY
The UPS automatically tests the battery’s condition and will illuminate the Bad Battery/Overload/Fault LED and sound the alarm. This alarm will be repeated until the batteries pass a self test. If the battery is weak, bad or disconnected, the Bad Battery/Overload/Fault LED will illuminate and the alarm will beep three times every thirty seconds until the battery is reconnected or replaced. It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the Bad Battery/Overload/Fault LED will illuminate and the UPS will sound 1 beep every half second (AC and Battery modes). This alarm will remain on until the excess load is removed or the UPS’s self protection circuit shuts the UPS down.
POWER MONITORING SOFTW ARE
The UPS comes with power monitoring software. See the software CD for the installation of the power monitoring software.
ALARMS
ON BA TTERY
When the UPS is operating on the batteries, the On Battery LED will illuminate and the audible alarm will sound once every five seconds. The alarm will stop once the UPS returns to the AC normal mode.
LOW BA TTERY WARNING
The UPS will sound two beeps every five seconds when the battery reserve runs low . This condition will continue until AC returns or the UPS shut s down from battery exhaustion.
UPS FAULT
When the UPS detects a hardware fault, the Bad Battery/Overload/Fault LED will illuminate and the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS off and then on.
TURNING THE UNIT ON/OFF
On / Off Button
Press and release the On/Off Button to turn the UPS on. The alarm will sound one beep and the LEDs will cycle while the UPS performs a five second internal self-test. Once the UPS has passed its internal self-test the UPS will provide an output and the load will be powered. Press and release the On/Off Button to turn the UPS off. The UPS will continue to charge the batteries whenever it is plugged into a wall outlet and there is an acceptable AC voltage present.
Page 13
12
English
Possible Cause
Symptom
What To Do
Press and release the On/Off button to start UPS
On/Off/ button not pressed
UPS will not turn on
Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS
UPS operates in battery mode only, even though there is normal AC present
Input AC circuit breaker is tripped
UPS has detected an internal fault
Call for service
Fault LED is illuminated
The AC Mode LED is illuminated, but there is no output
Disconnect the computer cable from the UPS and press the On button. If UPS works normally, the software has control of the UPS
The UPS is being controlled via its communications port
The batteries may be weak or at the end of use­ful service life
Charge the batteries for 8­hours and retest. If the runtime is still less than expected, the batteries may need to be replaced, even though the Weak/Bad Battery LED is not illuminated
UPS does not provide expected runtime
Bad Battery LED is illuminated
Overload LED is illuminated
Loose connections at the batteries, Weak batteries, Bad batteries
The load has exceeded the UPS's capacity
Check battery connections, charge the batteries for 8­hours, replace the batteries
Check the specifications (see section 8). Remove part of the load
The AC Mode LED is blinking once every second and the audible alarm is silent
The AC Mode LED is blinking twice every second and the audible alarm is silent
The UPS is operating in the Boost Mode
The UPS is operating in the Buck Mode
The UPS is performing its intended function
The UPS is performing its intended function
Page 14
13
English
REPLACING THE BATTERY
W ARNING!
This UPS contains potentially hazardous voltages. Do not at­tempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Re­pairs and battery replacement must be performed by QUALIFIED
SERVICE PERSONNEL ONL Y.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION:
(QUALIFIED SERVICE PERSONNEL ONL Y)
CAUTION:
Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are recyclable. Dispose of the batter­ies properly . The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly . Refer to local codes for proper disposal requirements or return the battery to the supplier .
Although the battery system voltage is only 12VDC and 24VDC the battery system can still present a risk of electrical shock. These batteries produce sufficient current to burn wire or tools very rapidly , producing molten metal. Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco­ nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the bat­ tery is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock. The likelihood of such shock will be reduced, if such grounds are removed during installation and maintenance.
CAUTION:
Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries.
Page 15
14
English
BA TTER Y REPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING TO REPLACE THE BATTERIES
Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. To hot-swap the batteries start with step number 6.
1. Turn off the equipment that is plugged into the output receptacles of the UPS.
2. Press and release the On/Off Button to turn the UPS off.
3. Unplug the UPS's power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the the UPS.
6. Remove the retaining screws from the bottom of the front panel of the UPS. (FIG. 1)
7. Gently push the top of the battery compartment cover inward and then slide the battery compartment cover off the UPS. (FIG. 2)
8. For the ETR500/700: Grasp the battery pull tab and gently pull the battery out far enough to disconnect the battery positive (Red) wire. (FIG. 3) NOTE: The ETR1000/1500 have Red Anderson connectors to connect the battery.
9. Disconnect the battery negative (Black) wire. (FIG. 3) NOTE: DO NOT short the battery wires together .
10. Remove the battery and set aside. NOTE: Orient the new battery in the same direction as the original battery.
11. Place the new battery close enough to connect the battery wires.
12. Connect the battery negative (Black) wire to the battery negative terminal.
13. For the ETR500/700: Connect the battery positive (Red) wire to the battery posi­ tive terminal. For the ETR1000/1500: Connect the Red Anderson connectors together NOTE: Some sparking might occur, this is normal.
14. Install the new battery into the UPS.
15. Re-install the battery compartment cover onto the UPS. W ARNING: DO NOT pinch the battery wires with battery comp artment cover.
16. Re-install the battery compartment cover retaining screws.
17. Properly dispose of the old batteries at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.
18. The UPS is now ready for normal operation.
Battery Qty/Rating
ETR1500
ETR1500p15
2-12V9Ah
Model #
Replace batteries with the same number and type as originally in­stalled in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable maintenance-free lead acid batteries.
CAUTION:
CSB Part #
First Power Part #
HR1234W
FP1290
ETR500
1-12V5Ah
HR1221W
FP1245
ETR700
ETR700p15
1-12V7Ah
GP1272
FP1270
ETR1000
2-12V7Ah
GP1272
FP1270
Page 16
15
English
FIG. 1
FIG. 2
FIG. 3: ETR500
FIG. 3: ETR700
FIG. 3: ETR1000/1500
Page 17
16
English
IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the problem call or fax the Technical Support department at the following numbers; V oice phone (972) 446-7363, FAX line (972) 446-901 1 or contact Minuteman UPS at [email protected].
Please have the following information available BEFORE calling the Techni-
cal Support Department. A. Your name and address. B. Where and when the unit was purchased. C. All of the model information about your UPS. D. Any information on the failure, including LEDs that may be illuminated. E. A description of the protected equipment, including model numbers if
possible.
F. A technician will ask you for the above information and, if possible, help
solve your problem over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Authoriza­ tion Number (RMA #).
G . If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be a charge for repair .
4. Pack the UPS in its original packaging. If the original packaging is no longer
available, ask the Technical Support T echnician about obtaining a new set. It is important to pack the UPS properly in order to avoid damage in transit. Never use S tyrofoam beads for a packing material. A. Include a letter with your name, address, day time phone number , RMA
number , a copy of your original sales receipt, and a brief description of the problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc. MINUTEMAN UPS
1455 LeMay Drive
Carrollton, TX 75007
A TTN: RMA # _______
Page 18
17
English
120VAC
500VA 300W
1000VA 600W
700VA 420W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Simulated Sine Wave (Step Wave)
Frequency
50/60Hz, +/-0.5Hz (unless synchronized to utility)
Nominal Volt age
Maximum Power Capacity
6 ms T ypical
>90% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-5Hz, autosensing
0 - 160VAC
90 - 150VAC
105 - 130VAC
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
ETR1000
ETR700
ETR700p15
ETR500
Model Number
SYSTEM SPECIFICA TIONS
Voltage Range
Topology
Line-Interactive, Simulated Sine Wave
OUTPUT NON-BA TTERY OPERA TION
INPUT
Number of Phase Single (1∅ 2W +G)
Nominal Voltage 120VAC
Low Voltage Transfer Point
90V resets to Utility Power at 94V or higher
High Voltage Transfer Point
150V resets to Utility Power at 146V or lower
Voltage Regulation 120VAC: -12.5% - +8.4%
Frequency Range 60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
OUTPUT BA TTERY OPERA TION
Voltage Regulation Nominal +/-6% (until Low Battery Warning)
Overload Capacity
110% for 10-seconds 120% Shutdown Immediately
ETR1500
ETR1500p15
1500VA 900W
REGULA TORY COMPLIANCE
Safety and Approvals EMC Verification
UL1778, cUL (CSA 22.2 no. 107.1)
FCC Class B, CE certified
Page 19
18
English
BA TTERY SYSTEM
Typical Recharge T ime Typical Battery Life
Battery: Quantity/Rating
3-5 years, depending on discharge cycles and ambient temp
1-12V5Ah
2-12V7Ah
8-hours from total discharge
2-12V9Ah
Battery Type
Sealed, Non-Spillable, Maintenance Free, V alue Regulated Lead Acid
System Voltage
12VDC
24VDC 24VDC
Runtime: Full Load (minutes)
Runtime: Half Load (minutes)
9 2
SURGE PROTECTION AND FIL TERING
Audible Noise at 1 m (3 ft.)
10/100 Base-T surge protection let-through (as a percentage of an applied +/-6 kV 1.2/50 us, 500 a 8/20 uS test)
T elephone line surge protection let-through (as a percentage of an applied +/-6 kV 1.2/50 us, 500a 8/20 uS test)
Noise Filter
Surge voltage let-through (as a percentage of an applied ANSI C62.41 Cat. A +/-6 kV)
Surge Response Time
Surge Current Capability
Surge Energy Rating 320 J
0 ns (instantaneous) normal mode; <5 ns common mode
< 5%
normal and common mode EMI/RFI suppression
<45 dBA
< 1%
< 5%
6500 Amps total
PHYSICAL
Weight - Net (ETR700p15, ETR1500p15)
Size - Net L X W X H
Size - Shipping L X W X H (ETR700p15, ETR1500p15)
Weight - Shipping (ETR700p15, ETR1500p15)
13.23 lbs
6.0 Kgs
10.91 x 3.43 x 10.80"
277.2 x 87 x 274.4 mm
16.14 x 7.09 x 15.94" 410 x 180 x 405 mm (16.04 x 8.19 x 15.94" 410 x 208 x 405 mm)
20.0 lbs
9.0 Kgs (21.0 lbs
9.32 Kgs)
12VDC
1-12V7Ah
16.4 x 3.43 x 10.80"
412.5 x 87 x 274.4 mm
21.26 x 7.09 x 15.94" 540 x 180 x 405 mm (21.26 x 8.19 x 15.94" 540 x 208 x 405 mm)
29.33 lbs
13.3 Kgs (30.12 lbs
13.66 Kgs)
34.0 lbs
15.4 Kgs (35.0 lbs
15.66 Kgs)
ENVIRONMENT AL
Operating/Storage Humidity
95% Non-Condensing
Storage Elevation
0 to 15,000m (0 to +50,000 ft)
Storage Temperature -15 to +45°C (+5 to +1 13°F)
Operating Temperature 0 to 40 degrees C (+32 to +104 degrees F) at Operating Elevation 0 to 1,500m (0 to +5,000 ft)
Operating Temperature 0 to 35 degrees C (+32 to +95 degrees F) at Operating Elevation 1501 to 3,000m (0 to +10,000 ft)
28.89 lbs
13.1 Kgs
15.44 lbs
7.0 Kgs (16.14 lbs
7.32 Kgs)
18.0 lbs
8.0 Kgs
34.0 lbs
15.2 Kgs
11
3
14
4
10
3
Page 20
19
English
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials (excluding the batteries) or workmanship for a period of three years from the date of purchase. Para Systems Inc. (Para Systems) warrants the batteries for a period of two years from the date of purchase. For equipment sites within the United St ates and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replace­ment parts and warranty labor will be borne by Para Systems. For equipment lo­cated outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be warranted for the unexpired portion of the warranty applying to the original prod­uct. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is improperly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel; or (c) has been used in a manner contrary to the product’s User's Manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or application of Para Systems’s equipment is furnished without charge and on the basis that it represents Para Systems’s best judgment under the circumstances, but it is used at the recipient’s sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO W ARRANTIES, EX­PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the pur­chaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSI­BILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for breach of any warranty, expressed or implied, con­cerning Para Systems’s products and the only obligation of Para Systems hereun­der, shall be the repair or replacement of defective equipment, components, or parts; or, at Para Systems’s option, refund of the purchase price or substitution with an equivalent replacement product. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Page 21
20
English
A1. DECLARATION OF CONFORMITY
Application of Council Directive(s): 89/336/EEC, 73/23/EEC
S tandard(s) to which Conformity is declared:
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) Manufacturer’s Address: 1455 LeMay Drive
Carrollton, Texas 75007 USA
T ype of Equipment: Uninterruptible Power Supplies (UPS) Model No: ETR500, ETR700, ETR1000, ETR1500, ETR700p15,
ETR1500p15
I hereby declare that the equipment specified above conforms to the above Directive(s).
Place: Carrollton, Texas, USA
Date: February 1, 2007
Robert Calhoun (Name)
Manager Engineering (Position)
Y ear of Manufacture: Beginning February 1, 2007
EN55022, EN55024 EN61000-6-1, EN61000-6-3 EN61000-4-5
Page 22
21
English
Notes:
Page 23
22
English
Notes:
Page 24
Page 25
Para Systems, Inc.
1455 Lemay Dr .
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com
PN - 34000295 R1
Loading...