Parameter Generation and Control 9354-4250 Installation And Operation Manual

Parameter Generation and Control, Inc.
Black Mountain, North Carolina
(828) 669-8717
500-1000 CFM Air Handler
460V, 60 Hz
Model #9354-4250
Installation and Operation Manual
Customer Serial # Ship Date
Parameter Generation and Control, Inc.
P. O. Box 129 1054 Old US 70 West Black Mountain, NC 28711
(800) 438-5494 (828) 669-6928 FAX
. . .
PGC Inc. Horizontal 500-1000 CFM June 2006
Parameter Generation and Control, Inc.
2
PGC Inc. Horizontal 500-1000 CFM June 2006
Inspection........................................................................................................................ 4
Installation....................................................................................................................... 4
Plumbing..................................................................................................................... 4
Electrical Connections................................................................................................7
Electrical Connections................................................................................................8
Operation......................................................................................................................... 9
Turning the Chamber Off and On............................................................................... 9
Process Variable Display.......................................................................................... 10
Adjusting Set Points.................................................................................................. 10
Operation After Loss of Power................................................................................. 10
Fault Displays ........................................................................................................... 11
Control Modes .......................................................................................................... 12
Specifications, 500-1000 CFM..................................................................................... 13
Replacement Parts, 500-1000 CFM.............................................................................. 14
Appendices
Appendix A – Technical Information Appendix B – SmartPad™ Operation Manual Appendix C – Diagrams Appendix D - Manuals for Accessory Equipment
Parameter Generation and Control, Inc.
3
PGC Inc. Horizontal 500-1000 CFM June 2006
Inspection
If the equipment is damaged upon receipt, immediately request the delivering carrier to perform an inspection and prepare a report. All claims for damage must be made against the delivering carrier. Report the nature and extent of the damage to PGC, 828-669-8717, and include instrument serial and catalog numbers to facilitate repair or replacement.
Installation
The 500-1000 CFM Conditioner was designed to be located adjacent to or on top of the chamber to be conditioned. Allow at least 36 inches on the right side and front of the unit for service. The location must be convenient to an adequate process water supply, drains and electrical power. The conditioner must be reasonably level for proper water level control.
Electrical power and water must be connected to this unit prior to operation. The required voltage and current are listed on the nameplate located on the unit. The sump drain may be connected directly to a facility drain, but the condensate drain must be connected to an open (vented) trapped drain (see Figure 3) to ensure that backpressure on the facilities’ drain does not prevent proper drainage.
Note
The condensate drain has been supplied with a copper trap.
Plumbing
To prevent damage to the water pump and water heater, the unit must not
CAUTION
be operated until water is supplied to the unit and the sump has filled to the proper level.
Process Water Supply Specifications
Units Maximum Typical Minimum
Process Water Pressure PSIG (Bar) Process Water Daily
Gallons (Liters)
125 (8.6) N/A 5 (0.35)
5.0 (19) 1.5 (5.7) 0 (0)
Consumption Condensate Production
Gallons (Liters)
5.0 (19) 1.5 (5.7) 0 (0)
per Day Sump Water Volume Gallons (Liters)
15 (57) 15 (57) 6.6 (25)
Process Water Inlet
Connect a clean water supply line through an external customer-supplied hand valve to the Process Water Inlet connection on the rear of the conditioner; this is a ½” male NPT connection.
Parameter Generation and Control, Inc.
4
PGC Inc. Horizontal 500-1000 CFM June 2006
Condensate Drain
Connect the condensate drain to an open (vented) trapped external drain. This drain is a ¾” female copper sweat connection on the rear of the conditioner.
Sump Drain
Connect the sump drain to a facilities drain. This drain does not require a trap. This drain connection is made to the ¾” ¼ turn ball valve, supplied on the rear of the
Coolant Water
Outlet
conditioner.
Coolant Water Supply and Return
If the refrigeration system is equipped with a water-cooled condenser. Connect coolant water to the condenser inlet connection on the rear of the chamber cabinet. Connect the coolant water return line to the coolant water outlet connection.
Coolant Water
Inlet
Coolant flow requirements will vary based on the operating conditions of condensing units, as the temperature of the coolant fluid. The following graph indicates the maximum
Coolant Water Connections
500-1000 CFM
coolant flow requirements for the condenser.
Maximum Condensor Water Flow Requirements
5.00
4.00
3.00
2.00
Gallons Per Minute
1.00
0.00 45 50 55 60 65 70 75 80 85 90 95 100 105
500-1000 CFM
Entering Water Temperature (Degrees F)
Parameter Generation and Control, Inc.
5
PGC Inc. Horizontal 500-1000 CFM June 2006
Filling the sump
To fill the conditioner with water, ensure that the sump drain valve is closed and open the customer-supplied external water inlet valve. When the sump is filled to the proper
Process Water
Inlet
level, a mechanical float valve will automatically shut off the flow and maintain the proper water level during operation. The float valve is preset at the factory to maintain the proper level (1/2” above the evaporator tubing); to change the water
Condensate
Drain
level, adjust the angle of the float arm slightly.
A low-water safety switch is located in the front, left corner of the sump. This switch will open when the water level is too low for safe operation of the pump and water heater. When the water level is correct, the float
Plumbing Connections
Service
Drain
switch will close and allow the controller to resume operation of the unit.
The water fill valve float may be padded to prevent damage during
CAUTION
shipping. Remove the padding before connecting the water supply to the inlet.
NOTE
The conditioner will not operate until the low water level safety is satisfied.
Parameter Generation and Control, Inc.
6
PGC Inc. Horizontal 500-1000 CFM June 2006
CAUTION
Do not connect the drain connection to an un-vented drain.
NOR
Ensure that the drain connection is vented, as shown below.
OR
“Open” (Vented) Drain Connections
Parameter Generation and Control, Inc.
7
PGC Inc. Horizontal 500-1000 CFM June 2006
Electrical Connections
Turn all electrical switches, circuit breakers, and motor starter protectors
CAUTION
(MSPs) off to prevent accidental starting of equipment when power is connected.
Determine voltage and current requirements of equipment before making
NOTE
electrical connections. This information is on a data plate attached to the machine.
Connect the air handler in accordance with all applicable codes, using a customer­supplied disconnect device.
The SmartPad™ user interface and the optional circular chart recorder can be located remote from the air handler. Typically, the controller is located on the front of the chamber to be controlled. These components are usually disconnected for shipment and must be re-connected prior to operation. Refer to the attached wiring diagrams for re­connection information.
The SmartPad™ user interface interconnect cable has a maximum voltage
NOTE
of 24VDC. Refer to local codes to determine the proper conduit requirements for the control cable.
The optional circular chart recorder can be powered by 24VDC or 120/230VAC. Refer to the wiring diagrams or the data plate on the recorder for more information.
CAUTION
The compressor and blower will not operate properly and may be damaged if permitted to run backward. After the Conditioner has filled with water and is operating, observe the rotation of the blower through the air bypass damper. Ensure that the blower is turning as indicated in the diagram below. If necessary, turn off the wall disconnect and interchanging any two phase wires at the wall disconnect or of the line connection terminals. Exchanging
phases at this point will reverse the rotation of all 3-phase motors.
Parameter Generation and Control, Inc.
8
PGC Inc. Horizontal 500-1000 CFM June 2006
Operation
The 500-1000 CFM Conditioner is a self-contained conditioner designed to control dry­bulb temperatures over a range of 7°C - 60°C (44.6ºF - 140ºF), dependent upon the size
and construction of the test chamber. The dry-bulb temperature is held to ± 0.2°C and relative humidity constancy to ± 0.5% with dew points above 5°C (41°F).
The SmartPad™ may be remotely mounted; refer to the PGC SmartPad™ section at the rear of this manual for instructions.
Operating Range
Turning the Chamber Off and On
When the chamber is energized and the Standby key has been pressed, the system should begin to operate and control the temperature and humidity in the chamber at the set points entered into the SmartPad™ user interface.
The SmartPad™ user interface is configured with a Standby key located in the lower right corner of the keypad. Pressing this key will disable the system and place the controller in a Standby mode. The SmartPad™ display will indicate:
Parameter Generation and Control, Inc.
9
PGC Inc. Horizontal 500-1000 CFM June 2006
STANDBY MODE
Press the ON/OFF key
to energize the system
When the system is in Standby mode, it can be energized by pressing the Standby key
Process Variable Display
The Process Variable screen is the first screen that will be displayed when the conditioner is energized. This screen will display the measured process variables and will allow access to the other screens in the SmartPad™.
The bottom line of the SmartPad™ display is a label for the four function keys on the key pad. This label will vary from screen to screen to reflect the action of each of the function keys.
Refer to the SmartPad™ manual in the appendix for a complete listing and discussion of available screens.
Adjusting Set Points
In the Process Variable screen, pressing the SP function key will access the Set Point screen. The Set Point screen will allow the user to enter the desired air temperature and relative humidity set points for the chamber.
The SmartPad™ has no ENTER key. In order to enter a value in any field
NOTE
all digits must be entered. For example, to enter 25.0°C air set point you must press “2”, “5” and “0”. When the field has been filled and the data has been entered, the cursor will jump back to the beginning of the field.
Operation After Loss of Power
If power is removed from the conditioner, the controller will resume operation in the same mode when power is regained. For instance, if the SmartPad™ was in Standby mode when power was lost, it will be in Standby mode when power is restored. If the SmartPad™ was operating and controlling the chamber, it will return to that mode of operation.
Parameter Generation and Control, Inc.
10
PGC Inc. Horizontal 500-1000 CFM June 2006
The SmartPad™ is not equipped with a battery backup.
NOTE
All set points, tuning values and ramping profiles are stored in non-volatile memory and will be permanently stored in the SmartPad™.
If power is removed from the controller it will resume operation when power is restored.
In Steady State set point mode the controller will resume operation at the previous steady state set points.
In Programmable set point mode the controller will resume operation at exactly the same segment and time remaining in that segment if the
duration of the power loss is less than approximately 20 minutes. If the duration of the power loss exceeds approximately 30 minutes the
controller will re-initiate the program according to the loop parameters defined in the INIT screen.
Fault Displays
If the system encounters a temperature, low-water, remote on/off switch, or refrigerant pressure fault, the system will shut down and the SmartPad™ will indicate the fault that has occurred. The SmartPad™ will continue to indicate that the fault exists, and will indicate if/when the fault has cleared.
If the fault has been cleared, the system can be re-energized by pressing the Standby key
. If the fault has not cleared, the source of the fault must be determined and corrected
before the system can be re-energized.
Some faults will clear automatically and others will require user
NOTE
intervention. Regardless of the fault clearing mechanism, the user must press the Standby
key in order for the conditioner to resume operation.
Parameter Generation and Control, Inc.
11
PGC Inc. Horizontal 500-1000 CFM June 2006
Control Modes
The PGC conditioning system offers four modes of temperature and humidity control.
1. Cascade Temperature Mode
This is the most commonly used mode because the user specifies only the desired air temperature and relative humidity (Rh) level in the chamber. The temperature of the water spray controls the dew point of the discharge air and the water temperature is adjusted in order to achieve desired humidity level. The air is then re-heated to the desired temperature before returning to the test chamber. This allows the system to respond to load variations while retaining the basic stability of a spray system.
2. Two-Temperature Mode
In this mode, the user establishes the desired air and water temperatures that are required to produce the desired relative humidity level, as determined by a psychometric chart. The Two-Temperature mode can be used when operating the very edges of the system capabilities.
3. Slow Damper Mode
This mode is similar to Cascade mode with the difference being that the air bypass damper control loop and the air heater control loop have been separated. In this mode the damper is moved slowly and its final position is when the desired percentage of air heat output is achieved. The desired percentage of air heat is determined by the user in the tuning parameters (Manual Adjust) section of the controller. In some situations, slow damper mode can be applied to improve energy efficiency or extend the operating range of the system. Typically, slow damper mode is most effective when the system is operated at a single condition as it will often require manual tuning adjustments for proper operation at multiple set points.
4. Dry Mode
This mode is required to control dew points below 4°C. In this mode, all water is removed from the spray chamber and an optional desiccant dryer is used to control humidity. Although this mode is accessible in SmartPad, it is non­functional unless the system is equipped with a desiccant dryer.
Parameter Generation and Control, Inc.
12
PGC Inc. Horizontal 500-1000 CFM June 2006
Specifications, 500-1000 CFM
Voltage-------------------------------------------------------------------------------- 460V~ Frequency----------------------------------------------------------------------3ph, 60 hertz Current------------------------------------------------------------------------------ 8.8 FLA Circuit Capacity (Max / Min)--------------------------------------------------30A / 12A Heater, Water ------------------------------------------------------------------- 1800 watts Heater, Air (Two, 1500 watt) ------------------------------------------------- 3000 watts Refrigerant-------------------------------------------------------------R-404a, 96 Ounces. Process Water Pressure, (Max/Min) ------------------------------------------125/5 psig Weight Net --------------------------------------------------------------------------1000 lb. Weight Shipping--------------------------------------------------------------------1400 lb. Temperature Range -------------------------------------------------------------7° to 60°C Relative Humidity Range----------------------------------------------------10% to 95%
1
Temperature Constancy (control) ------------------------------------------------ ± 0.2°C Rh Constancy (control) ----------------------------------------------------------± 0.5%
1
Minimum Rh is limited by a minimum dew point of 5°C (41°F) for standard Spray
Mode. For example:
Air
Max. Rh Min. Rh
Temperature
10°C (50°F) 88% 70% 25°C (77°F) 93% 32%
40°C (104°F) 95% 17%
> 50°C
95% 10%
(122°F)
Parameter Generation and Control, Inc.
13
PGC Inc. Horizontal 500-1000 CFM June 2006
Replacement Parts, 500-1000 CFM
Description Mfg. / Supplier Mfg./Supplier # PGC #
ACE Master Micro Controller PGC ACE 503g N/A ACE4 Controller Assy. PGC OEM 6000-1559 ACE4 Power Supply Meanwell PS45-24 1607-0024 Circuit Breaker,1 Pole, 2AMP Siemens 5SX2102-8 0426-1020 Circuit Breaker,2 Pole, 2AMP Siemens 5SX2202-8 0426-2020 Compressor Copeland CS14K6E-TFD-230 1510-0298 Contactor Siemens 3RT1025-1BB40 0419-0948 Damper Drive Motor Actuator Belimo
OEM
1608-
0916A Door, Spray Chamber, Inner PGC N/A 6000-0303 Door, Spray Chamber, Outer PGC N/A 6000-0392 Evaporator Coil, 5/8 OD x .032 wall Super Radiator Co. OEM 1244-0066 Filter Bag,5 Micron, Polyester McMaster-Carr 9316T22 0215-1800 Fuse, Door Heat 5A Bussman FNM5 0409-0123 Gasket, Return Duct Transition
Refrig. Hardware 47-131 1604-0101 Box, 140” Gasket, Spray Chamber Inner
Refrig. Hardware 47-131 1604-0101 Door, 95” Gasket, Spray Chamber Outer
Refrig. Hardware 47-131 1604-0101 Door, 95” Gasket, Supply Duct Transition Box Refrig. Hardware 47-131 1604-0101 Heater, Air Vulcan OEM 0416-0508 Heater, Water Watlow OEM 0416-0599 Hour meter, UV Durant E42DIR48230 0215-2821 HygroClip Connector and Cable, 5 meters, amplified analog, 0ºC to
PGC MOK-05-XX-005V-1-
DIO
1636-0159
100ºC HygroClip Micro Controller PGC Hygro 503 N/A HygroClip T/Rh Transmitter,
PGC OEM
1608-0865b
Full-Range Calibration HygroClip T/Rh Transmitter,
PGC OEM
1608-0865a
Single-Point Calibration HygroClip T/Rh Transmitter, Un-
Rotronic HygroClip S 1608-0865 calibrated HygroPalm Calibration Cable PGC AC1620-modified 1609-0866 HygroPalm Calibrator Rotronic HygroPalm 2 1609-0865 Latches, Access Panel Southco 62-43-251-3 1008-0080 Latches, Inner Doors Southco OEM 1001-0082 Latches, Outer Doors McMaster-Carr 5481K19 1009-1017 Mist Eliminator PGC N/A 5000-0135 Motor Protector Siemens 3RV1021-1KA10 0427-1250 Motor Protector Siemens 3RV1021-0GA10 0427-0063
Parameter Generation and Control, Inc.
14
PGC Inc. Horizontal 500-1000 CFM June 2006
Description Mfg. / Supplier Mfg./Supplier # PGC #
Motor Protector Siemens 3RV1021-1BA10 0427-0200 Motor, Blower Continental Fan RO-TMK280-2-34 1602-0199 Pump March TE5.5CMD 1619-0091 Refrigeration Dryer, Filter Sporlan CW-165S 0215-0887 Relay , Solid State, Door Heat Omron G3NE-210T-US 0416-0414 Relay, Solid State, 4-28 VDC Continental RVDC/6V25 0416-0403 Sensor , Door Jamb Temperature JMS Southeast OEM 1607-0652 Sensor ,Water Temperature JMS Southeast 3ESCK6BZZ3120JYTA1619-0862 SmartPad™ controller PGC OEM 1607-1100 SmartPad™ Micro Controller PGC Spad 503D N/A Spray Nozzle Spraying System NO. 1/4A-SS5-15. 1612-0201 Stepper Micro Controller PGC Step 503 (SDR3) N/A Strainer, Bronze “Y” McMaster-Carr 43935K24 0215-0904 Supply Duct Transition, 10” Round PGC N/A 5000-1389 Surge Suppressor Siemens 3RT1936-1TR00 0419-0891 Switch, Float Gems LS1750-192-908 0421-0060 Switch, Hi-Lo Refrig Pressure Copeland 085-CP2M-7K 0423-0683 Thermostat, Safety Thermtrol TS-120SR 30F-240F 1636-0223 Timer, Chamber Light Intermatic FF60MC 0419-0355 Transformer Micron B100MBT713XK 0419-0326 UV Lamp Severn Trent Water 5340UD 0215-2825 UV Lamp Power Supply Severn Trent Water 20697UD 0215-2831 UV Lamp Quartz jacket Severn Trent Water 2450UD 0215-2824 UV Plastic Support PGC OEM 0215-2826 Valve, Expansion, Body Danfoss 068U2287 0215-0872 Valve, Expansion, Cartridge Danfoss 068U1037 0215-0777 Valve, Hot Gas Temp Control Sporlan SDR-3-20-S 0215-0873 Valve, Sump Float Hawkeye Steel
UFV600 0209-0050
Products
Parameter Generation and Control, Inc.
15
Parameter Generation and Control, Inc
Precise Humidity Control
Notes:
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
www.humiditycontrol.com sales@humiditycontrol.com
(800) 438-5494
Fax (828) 669-6928 (828) 669-8717
Black Mountain, North Carolina
PGC, Inc 500-1000 CFM Air Handler May 2006
Appendix A
System Construction ................................................................................................................... 2
Theory of Operation.................................................................................................................... 3
Description of Operation............................................................................................................. 4
Measurement of Test Chamber Conditions ............................................................................ 4
Air Flow.................................................................................................................................. 4
Water Flow ............................................................................................................................. 5
Temperature Controls ............................................................................................................. 5
Description of Circuitry .............................................................................................................. 7
Safety Devices............................................................................................................................. 9
Troubleshooting ........................................................................................................................ 12
Operating Range of the System. ........................................................................................... 12
Water Temperature ...............................................................................................................12
Air Temperature.................................................................................................................... 13
Water Level .......................................................................................................................... 13
Rh Control ............................................................................................................................ 14
Maintenance .............................................................................................................................. 15
Preventive Maintenance Schedule........................................................................................ 15
Automatic Damper Motor Adjustments ............................................................................... 18
Calibration ............................................................................................................................ 18
Calibration ............................................................................................................................ 19
Calibration, Air/Rh ............................................................................................................... 19
Water Temperature Calibration ............................................................................................ 22
Appendix A A-1
PGC, Inc 500-1000 CFM Air Handler May 2006
SYSTEM CONSTRUCTION
The 500-1000 CFM Conditioner consists of four main sections:
1. Conditioning Compartment: spray bypass damper, blower, spray eliminators, spray
jets, water sump, low water level safety float switch, process water float valve, stirring jet, evaporator coil, and particulate filter
2. Mechanical Compartment (side access panels): refrigeration condenser, compressor,
receiver, , high- and low-pressure safety switches, filter/dryer, hot gas bypass valve, water pump, water heater, water RTD, Programmable Logic Controller (PLC), and power panel with terminal strips, circuit breakers, motor starter, and contactors
3. Conditioner Exterior: sump drain valve, air bypass damper actuator, UV filter, and air
temperature safety thermostat.
4. Control Enclosure: SmartPad™ user interface and optional chart recorder.
The unit is sturdily constructed, with a stainless steel interior and exterior, and insulated door with heavy refrigerator-type latches and vapor-resistant seals. Double walls separated by insulation are used around the conditioning chamber. All internal seams are welded to preclude saturation of the insulation.
The spray tree is a 3” stainless steel tube (spray header) with spray nozzles attached along the sides, and a clamp on each end for sealing the tube. The clamp on the right end secures a blank plate against an O-ring gasket. A UV lamp is inserted from the electrical compartment, through the plate on the left end.
Appendix A A-2
PGC, Inc 500-1000 CFM Air Handler May 2006
THEORY OF OPERATION
PGC’s method of control is the same for both reach-in chambers and conditioning systems. The environment to be conditioned is controlled at a
Supply Air
targeted dew point temperature, and then reheated to the desired air temperature. This methodology follows a proven technique that maintaining a constant dew point and air temperature will produce a very constant relative humidity. The desired air temperature and relative humidity or water
Blower
Air Filter
Return Air
Dampers
temperature are set via the SmartPad™. If equipped with
Sprayed Coil
an optional recorder, it can be wired to record the actual air temperature and relative humidity or water temperature.
Mechanical
The air is cooled by means of a water spray which constantly sprays water across the air stream, saturating the air. A submerged refrigeration evaporator coil operates 1°C­2ºC (1.8°F-3.6°F) below the desired dew point and cools the
Figure A-1 - Generic Conditioning Unit
water that is sprayed across the air stream. The air is then re­heated before it is returned to the test chamber.
NOTE
Dew point is the temperature at which the air can contain no more moisture and some moisture begins to condense.
A portion of the air can be diverted around the water spray saturator by a bypass damper. If the air does not pass through the water spray, it will not be cooled; if the air is not cooled, it will not require as much (if any) air heat to be applied before it is returned to the test chamber. The amount of air that passes through the saturator, or bypasses the saturator, is determined by the air temperature control loop.
Appendix A A-3
PGC, Inc 500-1000 CFM Air Handler May 2006
DESCRIPTION OF OPERATION
The 500-1000 CFM Conditioner is a self-contained conditioner designed to control dry-bulb temperatures over a range of 7°C – 60°C (44.6ºF - 140ºF), dependent upon the size and construction of the test chamber. The dry-bulb temperature is held to ± 0.2°C and relative humidity constancy to ± 0.5% with dew points above 5°C (41°F).
The temperature of the water spray saturator controls the dew point of the discharge air. When in Rh Cascade or Slow Damper mode, the water temperature in the saturator is varied slowly in response to a humidity control system. This allows the system to respond to wide load variations while retaining the basic stability of a spray system. When in Two-Temperature mode, the user establishes the air and water temperatures.
M
EASUREMENT OF TEST CHAMBER CONDITIONS
Precise control of temperature and humidity within the test chamber is obtained by accurately measuring the dry-bulb temperature and the dew point temperature of the air in the test chamber or the duct. The temperature of the water in the spray chamber controls the dew point temperature, and is measured prior to the spray nozzles.
When operating in one of the spray modes, the dew point of the air exceeds the water temperature by approximately 1°C for each 10°C difference between the air and water temperatures. During the ramp portion of program cycling, the dynamic heat exchange process that takes place makes it difficult to establish any exact relationship. When operating in the Two-Temperature mode, refer to the air/Rh/water spray graph provided with the unit for air and water temperatures necessary for the desired relative humidity.
A
IR FLOW
As the air enters the conditioner through the round, flexible duct connection in the removable top cover. The process blower, located beneath this cover, will force the air into the conditioning section. Entering the conditioning section, the air first encounters the by-pass damper; the damper determines the volume of air that enters the saturator, and the volume that is bypassed around the saturator. When the damper is fully closed, all of the air is forced through the water spray. As the air passes through the water spray, it is saturated and cooled, nearly to the water temperature. This method provides a stable dew point for the air as it leaves the saturator section. The chilled and saturated air then passes through the water droplet eliminator to remove any free moisture that may be present. The air then continues over the dry-bulb heaters, where it is heated to the desired chamber air temperature (without affecting the dew point) and is returned to the chamber through the round, flexible duct connection on the left end of the conditioner.
When the damper is fully open, most of the air bypasses the water spray and travels directly to the air heaters. The bypassed air is then mixed with any air that traveled through the saturator section and then returns to the test chamber. The spray bypass damper will be automatically positioned by the actuator operating on a control signal derived from the duty cycle of the air heater. The position of the damper can range from 0% to 100% open.
The dew point of the air stream is controlled even when most of the air is bypassed around the water spray saturator. The air bypass damper is not 100% efficient, allowing some air to enter the water spray saturator even when closed.
Appendix A A-4
PGC, Inc 500-1000 CFM Air Handler May 2006
In Slow Damper mode, the position of the damper is load dependent; the damper will change slowly to achieve the desired conditions. The damper will also change
NOTE
position in order to compensate for droop or overshoot in the air temperature control loop.
W
ATER FLOW
The water pump is located in the right section of the cabinet (accessible through the front or side access doors). The water is picked up by the pump and heated, and then forced across the water temperature sensor (100 platinum RTD) and into the spray header in the spray chamber. The spray header is situated to spray water across air stream. The remainder of the water passes through the particulate filter to remove debris.
T
EMPERATURE CONTROLS
The water temperature is sensed immediately prior to entering the spray headers, and the air & humidity are measured by the HygroClip™ T/Rh transmitter that is located in the air stream.
The air heaters are positioned in the air-stream path between the chamber and the saturator. The amount of heat applied is controlled by the dry-bulb control system with the sensing element in the air stream. The duty cycle (the percentage of heat applied) for the air heater can be accessed from the SmartPad™.
The water in the sump is cooled by the refrigeration evaporator, and is then sprayed across the air stream to cool and saturate the air. Since the refrigeration system has a greater capacity than is needed for most conditions, a hot gas bypass valve is provided to modulate the refrigeration capacity as required. This valve is automatically adjusted by an actuator operating on a control signal derived from the duty cycle of the water temperature control loop; the more the hot gas valve opens, the more the refrigeration capacity is reduced. The relative position of the hot gas bypass valve is represented by the water heater output percentage: Zero (0%) out is full refrigeration capacity (hot gas bypass valve closed); one hundred percent (100%) out is minimum refrigeration capacity (hot gas bypass valve open).
There are four factors that limit or control Water Set Point:
1. Humidity Control Band
Water Set Point will change in order to control Rh. If the measured Rh value is less than the Rh set point, the Water Set Point will increase in order to increase the Rh by increasing the dew point. The maximum rate at which the Water Set Point will change is adjustable; the most common Water Set Point Rate of Change is
0.25ºC/minute (the maximum value). The Water Set Point Rate of Change is proportional to the deviation from Rh Set Point. For example, if the Rh control band is +/- 10% and the measured Rh is 10% below Set Point (at 100% of the control bandwidth), the water Set Point will change at the rate of 0.25°C/minute (the maximum Rate of Change X 100%). If the measured Rh is 5% below the Rh Set Point (at 50% of the control bandwidth), the water Set Point will change at the rate of
0.125ºC/minute (the maximum rate of change X 50%).
Appendix A A-5
PGC, Inc 500-1000 CFM Air Handler May 2006
2. Water Temperature Set Point Limits
Minimum and maximum Water Set Point limits are factory pre-set in order to prevent freezing or overheating the pump.
3. Dew Point
Humidity is a function of air temperature and dew point, and the water temperature is directly related to dew point The controller limits the Water Set Point to 1ºC < Air Set Point to prevent a runaway temperature control. Without this limit, a runaway condition could be experienced when operating the unit with a high humidity set point. Such a setting could cause the water temperature to keep increasing in order to achieve the humidity set point, which would have the side effect of increasing the air temperature; this increase in air temperature would increase the capacity of the air to hold moisture, such that the system would never reach the humidity set point.
4. Measured Water Temp
If the Rh Set Point is set above or below the current Rh control band, the Water Set Point Rate of Change will automatically maximize to change the water temperature as quickly as possible. Many variables affect how fast the water temperature will change, such as the efficiency of the pump, how much water is in the sump, how often the test chamber is opened, etc. These are beyond the capability of the control system to measure; however, the controller measures how quickly the water temperature is actually changing, regardless of the uncontrollable variables. When the measured Rh is outside of the control band, the Water Set Point is changed automatically:
Water Set Point = Measured Water Temp + Control Bandwidth
For example, assume that the unit is operating with a Water Set Point of 25ºC and the water control bandwidth is 5ºC, with the humidity controlling at 50% with the control bandwidth at 10%. If the Humidity Set Point is set above the upper level of the control band (>60%), then:
Measured Water Temperature + the Water Control Band = new Water Set Point
In this example, the new water Set Point would be (25ºC + 5ºC=) 30ºC. This will cause 100% water heater output, and the Water Set Point will continue to increase at a value equal to the rate that the water temperature is changing. As soon as the measured humidity value is back within the control band (in this example, when the measured Rh is 65.01%), the Water Set Point will resume changing at the normal rate.
Appendix A A-6
PGC, Inc 500-1000 CFM Air Handler May 2006
DESCRIPTION OF CIRCUITRY
Although this conditioner utilizes 24 volts DC for the control circuits, some
CAUTION
components require 120 or 460VAC; these voltages can be present even when the conditioner is not operating.
CAUTION
Power to the unit should be removed at the wall disconnect prior to opening any of the access panels.
Line voltage is applied to the 24 VDC power supply. The 24VDC power supply provides power to the Programmable Logic Controller (PLC), the HygroClip T/Rh transmitter, the air bypass damper actuator, safety devices, and the line contactor.
The PLC has an on-board DC-DC converter that will produce +5VDC for the board-level logic components. A second DC-DC converter produces +15VDC for use by the SmartPad user interface, stepper motor, and the RTD amplifiers.
When power is applied to the conditioner, and control circuit breaker(s) are closed, the SmartPad user interface will be energized. If all of the safety devices are satisfied (pressure switches, thermostats, float switches, etc.), then the conditioner can be energized by pressing the Standby
key on the SmartPad™ user interface. This will instruct the PLC to energize the line contactor (1CON).
When 1CON is closed, power is applied to the motor starter protectors (MSPs) and the heater circuit breaker. If the MSPs are closed, then the compressor, blower, and pump will be energized. If the heater circuit breakers are closed, then the air and water heaters will be enabled. The operation of the air heaters and water heater is controlled by the PLC; the PLC determines the duty cycle (On time verses Off time) for each of the heaters, based on the requirements of each temperature control loop. The PLC will open and close digital outputs that will control the input signals to solid-state relays, which will apply power to the respective heater based on the respective control loop. An LED on each relay will indicate the On or Off status of that particular heater control loop.
The UV filter will also be enabled by the control circuit breaker(s). Any time power is applied to the conditioner, the control circuit breakers are closed, and the unit is operational (i.e. 1CON is closed), the UV filter should be energized.
On initial power up, the PLC will determine the hot gas bypass valve position by driving the stepper motor to fully close (0% output) the hot gas bypass valve in order to “zero” the valve. This involves driving the motor past the full closed position; the valve will be seated against the full closed stop but is not damaged by this over driving maneuver. Bumping the valve against the full-closed stop can correct for any “lost steps” or accumulated errors that could occur over time due to the constant reversal of the stepper motor.
During normal operation, the position of the hot gas valve is based on the output percentage of the water temperature control loop. This output percentage is translated into a percentage of “open” value for the stepper motor. The PLC converts this percentage open value into a step count that will position the valve accordingly. When the valve is adjusted to the desired position, the PLC will cease to step the motor, and the motor will maintain its current position.
Appendix A A-7
PGC, Inc 500-1000 CFM Air Handler May 2006
The position of the air bypass damper is determined by the PLC based on the air output percentage. The input to the damper actuator is a frequency modulated (FM) square-wave signal. The damper will be positioned based on the frequency of the FM signal. A yellow LED on the PLC indicates the duty cycle. Zero percent (0%) air heat output will produce a 0.59 second On time pulse, which instructs the damper to move to the full spray position. One hundred percent (100%) air heat output will produce a 2.93 second On time pulse, which instructs the damper to move to the full bypass position. An On time between 0.59 seconds and 2.93 seconds will produce a proportional response in the damper position.
The water temperature is measured using a positive-coefficient 100 Platinum RTD temperature sensor. This sensor consists of a very thin Platinum wire that is wound around a ceramic core. As the temperature of this wire increases, the resistance of the Platinum element increases linearly. This resistance is placed in a bridge network to produce a linear voltage proportional to the change in temperature. This voltage is then converted to a digital value that can be used by the PLC by and the A/D converter.
The air temperature is also measured using a 100 RTD located in the HygroClip T/Rh transmitter. A circuit in the HygroClip converts this RTD input to a digital signal that is transmitted to the PLC using a single-wire serial interface. The PLC receives this digital signal and converts it to a digital value that the PLC can use in its calculations.
The HygroClip also converts the RTD input into a 0-1VDC analog signal that is scaled so that
0.1VDC = 1°C. This analog signal is applied to an amplifier built into the HygroClip connection cable, which converts the 0-1VDC signal into a 0-5VDC signal (0-5VDC is required if the analog signal is transmitted more than 10 feet). The 0-5VDC amplifier can be used to scale the analog output for different ranges; the most common range is (0-5VDC) = (0°C to 100°C). However, amplifiers are available for (-30°C to +70°C) and (-40°C to +60°C). This 0-5VDC analog amplifier is not used by the chamber controller, and is only required when an analog device (such as a chart recorder) is connected to the system. This analog output is available on the chart recorder connector of the PLC.
The relative humidity is measured using a thin-film polymer capacitive element that changes capacitance as moisture is absorbed or given off. The HygroClip T/Rh transmitter will convert this change in capacitance into a digital value. This digital value is transmitted to the PLC in the same single-line serial interface as the air temperature measurement. The PLC will decode the digital value and convert it to a digital value that can be used by the PLC. The HygroClip T/Rh transmitter will also convert the measured Rh to a 0-1VDC analog output. The same analog amplifier that is used in the analog air temperature output will convert the 0-1VDC signal to a 0­5VDC signal. In all instances, the Rh output will be scaled so that 0-5VDC will equal 0-100% Rh. This analog output is also available at the chart recorder connection on the PLC.
A separate voltage to current converter is installed in the air handler electrical compartment for both the air temperature and relative humidity. This device will convert the 0-5VDC analog signal from the HygroClip to 4-20mA. The output will be scaled so that 4-20mA corresponds to the same temperature or Rh range as the analog signal from the HygroClip (typically this will be 4-20mA = 0-100°C or 0-100% Rh). The 4-20mA signal is provided as an interface to a customer supplied monitoring device. This converter is equipped with a zero and span calibration potentiometer that can be field adjusted in order to match the 4-20mA output with the NIST traceable temperature and Rh output from the HygroClip.
Appendix A A-8
PGC, Inc 500-1000 CFM Air Handler May 2006
SAFETY DEVICES
The unit is equipped with several safety devices to guard against serious trouble due to failure of any components.
Alarm contacts are available on the PLC, which will switch when either of the process variables is in an alarm condition. The process variables are Air and Water in Two-Temperature mode, or Air and Rh in any other mode. The alarm type, set points, and time delay are all programmable from the SmartPad™; and the alarm can be disabled from the SmartPad™; refer to the SmartPad™ manual for further information. The alarm contact is a single-pole double-throw (SPDT), Normally Open / Normally Closed, dry contact relay rated at 6 Amps @ 250VAC.
Compressor Internal Overload: The refrigeration compressor is equipped with an internal
thermal protector. If the compressor draws excessive current, the motor windings will overheat. If the windings overheat, the internal thermal protector will open and the compressor will not operate. The rest of the chamber will continue to function, although it is not possible to control air or water temperature unless the compressor is operating. As soon as the internal temperature of the compressor motor drops to a safe operating level, the compressor will resume operation. This reset process will normally require about 45 minutes.
Several potential causes of a compressor internal overload include the loss of coolant water flow, excessive coolant water temperature, clogged coolant water inlet filter, high ambient temperature, or excessive refrigerant charge, low line voltage, or unusually high ambient temperature.
Refrigeration High Pressure Fault: A pressure switch monitors the discharge pressure in the
refrigeration system. This switch is located beside the compressor. If the pressure is allowed to operate at an excessive level, the compressor will be damaged. If the high-pressure switch opens, the SmartPad™ will pad indicate “HIGH PRESSURE FAULT SET” and the system will shut down. The high-pressure switch will automatically reset after the refrigeration discharge pressure falls below the pressure trip point. When the switch is reset, the SmartPad™ display will indicate “HIGH PRESSURE FAULT CLEAR”, and the system may be restarted by pressing the Standby
key on the SmartPad™ key
Several potential causes of a compressor internal overload include obstructed or dirty air cooled condenser, excessive refrigerant charge, low line voltage, or unusually high ambient temperature.
Refrigeration Low Pressure Fault A pressure switch monitors the suction pressure in the
refrigeration system. If this pressure is allowed to operate below a safe level, the compressor may be damaged. If the low-pressure switch opens, the SmartPad™ will indicate “LOW PRESSURE FAULT SET” and the system will shut down. The low-pressure fault will automatically reset when the refrigeration suction pressure rises above the pressure trip point; when this occurs, the SmartPad™ display will indicate “LOW PRESSURE FAULT CLEAR”, and the system may be
restarted by pressing the Standby key on the SmartPad™ key pad.
Some potential causes of a low-pressure fault include, but are not limited to, low refrigerant
charge, frozen evaporator, or a poor spray pattern.
Appendix A A-9
PGC, Inc 500-1000 CFM Air Handler May 2006
r
High Pressure
Reset
Low Pressure
Switch
High Pressure
Switch
Figure A-2 - Pressure Switches
Air Temperature
Safety Thermostat
Over Temperature Thermostat An air over-temperature safety
thermostat has been incorporated into the chamber. The temperature adjustment for this device is located at the rear of the unit, on the side of the heater housing. This safety thermostat is designed to protect the contents of the test chamber from excessive temperature rise in the event of a system failure. The operator may set this manually to protect the product under test, normally 2-3°C (5°F) degrees above highest test temperature. If this thermostat opens due to excessive temperature, the chamber will shut down and the SmartPad™ user interface will indicate “TEMPERATURE FAULT SET”. The thermostat will automatically reset when the temperature inside the chamber drops below the cut-out temperature. After the thermostat has reset, the SmartPad™ user interface will indicate “TEMPERATURE FAULT CLEAR”, and the system may
UV Time
be restarted by pressing the Standby key on the SmartPad™ key pad.
Low-Water Safety Switch A low-water level safety float
switch is located in the front left corner of the sump, near the floor of the sump; this switch will shut down the air handler if the
Figure A-3 – Low Water
Safety Float Switch
Condensate
water level in the sump falls below a safe operating level. If this float switch opens, the air handler will shut down. The SmartPad™ user interface will indicate “LOW WATER FAULT SET”. The float switch will automatically reset when the water level in the sump returns to a safe operating level. After the switch has reset, the SmartPad™ user interface will indicate “LOW WATER FAULT CLEAR”, and the system may be
restarted by pressing the Standby key on the SmartPad™ key pad.
Blower Motor Thermal Contact The blower motor is
equipped with a contact that will open if the blower motor
Figure A-4 – Low Water
Safety Float Switch
temperature exceeds a safe operating level. If this contact
Appendix A A-10
Drain
Low Water
Safety Float
PGC, Inc 500-1000 CFM Air Handler May 2006
opens, the air handler will shut down. The SmartPad™ user interface will indicate “FAN TEMP FAULT SET”. The thermostat will automatically reset when the blower motor tempeature returns to a safe operating level. After the thermostat has reset, the SmartPad™ user interface will indicate “FAN TEMP FAULT CLEAR”, and the system may be restarted by pressing the
Standby key on the SmartPad™ key pad.
Motor Starter Protector If a motor starter protector (MSP) trips, that component will not
operate. The starter must be reset by turning it to the Off position and then to the On position. MSPs are used by the process blower, pump, and compressor.
Manual motor starters in on, off and tripped positions
On Off Tripped
Figure A-5 – Motor Starter Protector (MSP)
Appendix A A-11
Loading...
+ 63 hidden pages