Copyright 1998 Paradyne Corporation.
All rights reserved.
Printed in U.S.A.
Notice
This publication is protected by federal copyright law. No part of this publication may be copied or distributed,
transmitted, transcribed, stored in a retrieval system, or translated into any human or computer language in any form
or by any means, electronic, mechanical, magnetic, manual or otherwise, or disclosed to third parties without the
express written permission of Paradyne Corporation, 8545 126th Avenue North, P.O. Box 2826, Largo,
Florida 33779-2826.
Paradyne Corporation makes no representation or warranties with respect to the contents hereof and specifically
disclaims any implied warranties of merchantability or fitness for a particular purpose. Further, Paradyne Corporation
reserves the right to revise this publication and to make changes from time to time in the contents hereof without
obligation of Paradyne Corporation to notify any person of such revision or changes.
Changes and enhancements to the product and to the information herein will be documented and issued as a new
release to this manual.
Trademarks
All products and services mentioned herein are the trademarks, service marks, registered trademarks or registered
service marks of their respective owners.
Warranty, Sales, and Service Information
Contact your local sales representative, service representative, or distributor directly for any help needed. For
additional information concerning warranty , sales, service, repair , installation, documentation, training, distributor
locations, or Paradyne worldwide office locations, use one of the following methods:
Via the Internet: Visit the Paradyne World Wide W eb site at http://www.paradyne.com
Via Telephone: Call our automated call system to receive current information via fax or to speak with a
company representative.
— Within the U.S.A., call 1-800-870-2221
— Outside the U.S.A., call 1-727-530-2340
This guide contains information needed to set up, configure, and operate the
Model 7112 T1 DSU/CSU and is intended for use by installers and operators.
Document Summary
SectionDescription
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
About the T1 DSU/CSU.
and SNMP management capabilities with a typical
configuration example.
Using the ASCII Terminal Interface.
accessing the user interface and navigating the screens.
Configuring the DSU/CSU.
up the user interface, and DSU/CSU configuration steps.
Security.
the effective access levels, and controlling SNMP access.
IP Addressing.
examples.
Monitoring the DSU/CSU.
about the LEDs, DSU/CSU status, and network statistics.
Testing.
setup.
Messages and Troubleshooting.
SNMP traps, device messages, and troubleshooting.
Presents procedures for creating a login, setting
Provides details about available tests and test
Describes the DSU/CSU features
Provides instructions for
Provides procedures for setting
Provides details regarding IP addresses with
Describes monitoring details
Provides information on
7112-A2-GB20-20
March 1998
vii
About This Guide
SectionDescription
Appendix A
Appendix B
Appendix C
Appendix D
Appendix E
Appendix F
GlossaryDefines acronyms and terms used in this document.
IndexLists key terms, acronyms, concepts, and sections in
Product-Related Documents
Configuration Option Tables.
options, default settings, and possible settings.
Worksheets.
settings, and possible settings to use for planning.
MIB Descriptions.
DSU/CSU.
Contains all the configuration options, default
Provides all MIBs supported by the
Standards Compliance for SNMP Traps.
trap compliance details.
Cables and Pin Assignments.
interface details.
Technical Specifications.
specifications, network and port interfaces, power
consumption values, etc.
alphabetical order.
Contains all configuration
Contains SNMP
Contains connector and
Contains physical and regulatory
Document NumberDocument Title
7112-A2-GN10
Contact your sales or service representative to order additional product
documentation.
Paradyne documents are also available on the World Wide Web at:
http://www.paradyne.com
Select
Service & Support → Technical Manuals
Model 7112 T1 DSU/CSU with Internal Ethernet LAN
Adapter Startup Instructions
viii
March 1998
7112-A2-GB20-10
About the T1 DSU/CSU
Model 7112 T1 DSU/CSU Features
1
NMS
LAN A
Router
The 7112 T1 DSU/CSU provides an interface between the T1 digital network and
the customer premises equipment, converting signals received from the DTE
(Data Terminal Equipment) to bipolar signals that can be transmitted over T1
lines.
The T1 DSU/CSU offers these features:
10BaseT Port. Allows the DSU/CSU to connect directly to an Ethernet LAN.
SNMP (Simple Network Management Protocol) Management. Provides
network management via an industry-standard SNMP management system.
10BaseT
Connection
SNMP
DSU/CSU
T1
Network
SNMP
DSU/CSU
Facility
Data Link
Router
LAN B
97-15692
7112-A2-GB20-20
Facility Data Link (FDL). Provides remote management via SNMP or Telnet
session capability over the T1 network.
ASCII Terminal Interface (ATI). Provides a menu-driven VT100-compatible
interface for configuring and managing the DSU/CSU locally or remotely by
Telnet session or External Modem.
access to alternate sets of configuration options.
March 1998
1-1
About the T1 DSU/CSU
Management. Provides management via:
— ASCII terminal connection through the Terminal port
— External modem through the Terminal port
— Telnet through the Ethernet port or the FDL
— SNMP through Ethernet port or the FDL
Alarm Indication. Activates front panel LEDs.
Diagnostics. Provides the capability to diagnose device and network
problems and perform tests, including digital loopbacks, pattern tests, and
self-test.
Device and Test Monitoring. Provides the capability of tracking and
evaluating the unit’s operation, including health and status, and error-rate
monitoring.
Security. Provides multiple levels of security, which deters unauthorized
access to the DSU/CSU.
Typical DSU/CSU Configurations
Figures 1-1 and 1-2 show typical LAN/WAN interconnection applications for the
DSU/CSU. The routers connected to the DSU/CSU at each location provide the
LAN interconnection.
RouterRouter
DSU/CSUDSU/CSU
T1
98-15688-01
Figure 1-1. Typical Configuration (through a T1 network)
Two SNMP DSUs can be connected back-to-back to act as Local Area Data Sets.
Router
DSU/CSU
DSU/CSU
Router
98-15697-01
Figure 1-2. Typical Configuration (DSU/CSU to DSU/CSU)
1-2
March 1998
7112-A2-GB20-20
User Interface Types
There are three types of user interfaces to the T1 DSU/CSU:
About the T1 DSU/CSU
Menu-driven ASCII terminal interface screens (see Chapter 2,
ASCII Terminal Interface (ATI)
SNMP NMS Access – Refer to
page 1-1. Provides the capability to access the DSU/CSU via an SNMP
management system connected to the Ethernet port or remotely through the
Facility Data Link (FDL). Refer to Chapter 5,
Front panel LED status indicators. Refer to Chapter 6,
DSU/CSU
.
Front Panel LED Status Indicators
Refer to Chapter 6,
FT1/T1
Monitoring DSU/CSU LEDs
7112 SNMP DSU/CSU
MONITOR
In Out
).
Model 7112 T1 DSU/CSU Features
IP Addressing
Monitoring the
.
OK
FAIL
TEST
SIG
OOF
ALARM
EER
TXD (103)
RXD (104)
RTS (105)
NetworkSystem
Port
Using the
.
CTS (106)
on
DTR (108)
97-15687
Figure 1-3. Model 7112 SNMP DSU/CSU Fr ont Panel
7112-A2-GB20-20
March 1998
1-3
About the T1 DSU/CSU
Rear Panel Interface Connections
Figure 1-4 shows the physical interfaces of the DSU/CSU. Information about the
installation of the DSU/CSU is contained in
Internal Ethernet LAN Adapter Startup Instructions
Model 7112 T1 DSU/CSU with
.
POWER
TERMINAL
or
Terminal
Figure 1-4. Rear Panel Connectors
CAUTION:
The 10BaseT and Network connectors are not keyed. Follow the
installation procedures carefully to avoid connection errors.
SNMP Management Capabilities
The DSU/CSU supports SNMP Version 1, and has the capability of being
managed by any industry-standard SNMP manager and accessed using SNMP
protocol by external SNMP managers.
10BaseT
Modem
Ethernet
DTE
D
T
E
NETWORK
T1
Network
97-15694
Management Information Base (MIB) Support
The following MIBs are supported:
MIB II (RFC 1213 and RFC 1573) – Defines the general objects for use with
a network management protocol in TCP/IP internets and provides general
information about the DSU/CSU. MIB II is backward-compatible with MIB I.
Ethernet-like MIB (RFC 1643) – Defines objects for managing Ethernet-like
interfaces (e.g., 10BaseT).
RS-232-Like MIB (RFC 1659) – Defines objects for managing RS-232-type
interfaces and supports the V.35 synchronous data port on the DSU/CSU.
Enterprise MIB – Supports configuration, status, statistics, and tests on the
DS1 network interface.
DS1/E1 MIB (RFC1406) – Defines objects for managing DS1 interfaces and
supports the network interface on the DSU/CSU. DS1 Near End Group and
DS1 Fractional Group are supported.
Generic-Interface Extension MIB (RFC 1229) (Generic Interface Test
table only) – Provides extensions to the generic interface group defined in
MIB II.
1-4
March 1998
7112-A2-GB20-20
Using the ASCII Terminal
Interface (ATI)
Accessing the ATI
You can communicate with the ATI using one of the following methods:
Direct connection through the Terminal port.
Dialing in through an external modem to the Terminal port.
Telnet session through the Ethernet port.
Telnet session through the Facility Data Link (FDL).
2
NOTE:
Only one ATI session can be active at a time, and another user’s session
cannot be forced to end. To automatically log out a user due to inactivity,
enable the Inactivity Timeout option (see Table A-6, Terminal Port Options
and Table A-7, Telnet Session Options).
The user interface is blank until activated. Press Enter to activate the user
interface. Security can limit ATI access several ways. To setup security or a login
ID, refer to Chapter 4,
Security
Connecting to the Terminal Port
Ensure that the device you connect communicates using the following settings:
Data rate set to 9.6 kbps.
Character length set to 8.
Parity set to None.
Stop Bits set to 1.
To change Terminal port settings, refer to Table A-6, Terminal Port Options.
.
7112-A2-GB20-20
March 1998
2-1
Using the ASCII Terminal Interface (ATI)
Initiating an ATI Session
The Main Menu screen is displayed on the screen unless a login ID and
password is required or the ATI is already in use.
If security is enabled
you enter a valid login ID and password, the Main menu appears. If you enter an
invalid login ID and password after three attempts, the Telnet session closes or
the terminal connection returns to an idle state. Refer to Chapter 4,
If the ATI is already in use
failed” message (if you are using a Telnet session) or you will see the IP address
of the other user (if you are using the Terminal port).
Entry to all of the DSU/CSU’s tasks begins at the Main Menu screen.
Menu Path
main PARADYNE
Device Name: Model: 7112
, the system prompts you for a login ID and password. After
Security
.
, you will see a “connection refused” or “connection
MAIN MENU
Screen
Area
Screen
Function
Keys
Status
Test
Configuration
Control
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Ctrl-a to access these functions, ESC for previous menuM
S
ave
Input Fields
ainMenuExit
Select . . .To . . .
StatusView system status, diagnostic test results, cross connections, statistics,
and LEDs identity information.
TestSelect and cancel tests for the DSU/CSU’s interfaces.
Configuration Display and edit the configuration options.
ControlControl the user interface for device naming, login administration, or to
initiate a power-up reset of the DSU/CSU.
2-2
March 1998
7112-A2-GB20-20
Screen Work Areas
There are two user work areas:
Screen area – Provides the menu path, access level, menus, and input fields
above the dotted line.
The menu path appears as the first line on the screen. In this manual, the
menu path is presented as a menu selection sequence with the names of the
screens For example:
Screen function key area – Provides functions available below the dotted
line based upon screen selection and access level.
Screen Format Types
Three types of screen formats are available on the ATI.
Using the ASCII Terminal Interface (ATI)
Main Menu→Configuration→Load Configuration From→
Edit
→
Terminal Port
Use the screen format . . .
Menu selectionDisplay a list of available functions for user selection.
InputAdd or change information on a screen.
DisplayDisplay configuration information and results from
What Affects Screen Displays
What appears on the screens depends on the:
Current configuration – How your DSU/CSU is currently configured.
Effective security access level – An access level that is typically set by the
system administrator for each interface and each user.
Data selection criteria – What you entered in previous screens.
To . . .
Input or edit fields that have an Underline
or selection. See
performance and DSU/CSU-specific tests.
Display-only fields that have no underline in the field value.
Screen Work Areas
in the field value
.
7112-A2-GB20-20
March 1998
2-3
Using the ASCII Terminal Interface (ATI)
Navigating
You can navigate the screens by:
Using keyboard keys
Using screen function keys
Switching between the two screen work areas
MAIN MENU
Status
Test
Configuration
Control
Load Configuration
from . . .
Keyboard Keys
Status
• System and Test Status
• Network Performance Statistics
• Cross Connect Status
• Ethernet Port Status
• Management Protocol Satistics
• Display LEDs
• Identity
Test
• Network T ests
• Data Port Tests
• Lamp Test
• Abort Tests
Configuration
Edit/Display
• System
• Network
• Cross Connect
• Data Port
• Ethernet Port
• Terminal Port
• Telnet Session
• SNMP
SNMP
• General SNMP Management
• SNMP NMS Security
• SNMP Traps
Use the following keyboard keys to navigate within the screen.
Press . . .
To . . .
Control
• Device Name
• Administer Logins
• Reset Device
97-15686
2-4
Ctrl-aMove cursor between the screen area and the screen function
keys area below the dotted line at the bottom of the screen.
EscReturn to the previous screen.
TabMove cursor to the next field on the screen.
BackspaceMove cursor to the previous field on the screen.
March 1998
7112-A2-GB20-20
Using the ASCII Terminal Interface (ATI)
Press . . .To . . .
EnterAccept entry or display valid options on the last row of the screen
when pressed before entering data or after entering invalid data.
Ctrl-kTab backwards (moves cursor one field to the left).
SpacebarSelect the next valid value for the field.
Delete (Del)Delete character that the cursor is on.
Up Arrow or Ctrl-uMove cursor up one field within a column on the same screen.
Down Arrow or Ctrl-d Move cursor down one field within a column on the same screen.
Right Arrow or Ctrl-fMove cursor one character to the right if in edit mode.
Left Arrow or Ctrl-bMove cursor one character to the left if in edit mode.
Ctrl-lRedraw the screen display , clearing information typed in but not
yet entered.
" Procedure
To make a menu or field selection:
1. Press the tab key or the right arrow key to position the cursor on a menu or
field selection. Each selection is highlighted as you press the key to move the
cursor from position to position.
2. Press Enter. The selected menu or screen appears.
3. Continue Steps 1 and 2 until you reach the screen you want.
The current setting or value appears to the right of the field name. You can enter
information into a selected field by:
HTyping in the first letter(s) of a field value or command, using the DSU/CSU’s
character matching feature.
HSwitching from the screen area to the screen function area below the dotted
line and selecting or entering the designated screen function key.
If a field is blank and the Field Values screen area displays valid selections, press
the spacebar and the first valid value for the field will appear. Continue pressing
the spacebar to scroll through other valid values.
7112-A2-GB20-20
March 1998
2-5
Using the ASCII Terminal Interface (ATI)
Screen Function Keys
All screen function keys located below the dotted line operate the same way
(upper- or lowercase) throughout the screens.
For the screen
function . . .
MainMenuM or mReturn to the Main Menu screen.
ExitE or eTerminate the async terminal session.
NewN or nEnter new data.
DeleteL or lDelete data.
SaveS or sSave information.
RefreshR or rUpdate screen with current information.
ClrStatsC or cClear network performance statistics and refresh the
Select . . . And press Enter to . . .
screen, Clear status messages for one-time events.
PgUpU or uDisplay the previous page.
PgDnD or dDisplay the next page.
ResetMonR or rReset an active Monitor of active pattern test counter to
Switching Between Screen Work Areas
Selecting Ctrl-a allows you to switch between the two screen work areas to
perform all screen functions.
Procedure
To access the screen function area below the dotted line:
1. Press Ctrl-a to switch from the screen area to the screen function key area
below the dotted line. The available selections for the first input field appear
on the last line as shown below.
2. Select either the function’s designated (underlined) character or press the tab
key until you reach the desired function key.
Example:
To save the changes you have made on this screen, enter s or S (Save).
3. Press Enter.
zero.
2-6
4. To return to the screen area above the dotted line, press Ctrl-a again.
March 1998
7112-A2-GB20-20
Ending an ATI Session
Use the Exit function key from any screen to terminate the session.
Procedure
To end a session with the ASCII terminal interface:
1. Press Ctrl-a to go to the screen function key area below the dotted line.
Using the ASCII Terminal Interface (ATI)
2. Tab to E
appears.
xit (or type e or E) and press Enter. The User Interface Idle screen
7112-A2-GB20-20
March 1998
2-7
Using the ASCII Terminal Interface (ATI)
This page intentionally left blank.
2-8
March 1998
7112-A2-GB20-20
Configuring the DSU/CSU
Entering Device and System Information
Use the Device Name screen to determine the name that will be displayed at the
top of all ATI screens, and SNMP system information that will be displayed on the
Identity screen. To access the Device Name screen, follow this menu selection
sequence:
Device Name:NE815378
System Name:lllQJ98-001
System Location: Bldg. A412, 2nd Floor, Left cabinet
System Contact: Joe Smith 800-555-5555 pager 888-555-5555Clear
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Ctrl-a to access these functions, ESC for previous menuM
S
ave
Fields on the Device Name screen are null until you enter values. Allowable
values are any printable ASCII character except the ^ (caret).
Use the left and right arrow keys to scroll through the fields. Select Clear to reset
a field to a null value.
Clear
Clear
Clear
ainMenuExit
7112-A2-GB20-20
March 1998
3-1
Configuring the DSU/CSU
" Procedure
To enter Device Name screen information:
1. Position the cursor in the Device Name field. Enter a name unique in your
system to identify the unit.
The maximum length of Device Name is 20 characters.
2. Position the cursor in the System Name field. Enter a name unique in your
network to identify the system.
The maximum length of System Name is 255 characters.
3. Position the cursor in the System Location field. Enter the physical location of
the system.
The maximum length of System Location is 255 characters.
4. Position the cursor in the System Contact field. Enter the name and contact
information for the person responsible for the unit.
The maximum length of System Contact is 255 characters.
5. Save the Device Name screen information.
Configuring the DSU/CSU
Configuration option settings determine how the DSU/CSU operates. Use the
Configuration branch of the DSU/CSU menu to display or change configuration
option settings.
Configuration Option Areas
The DSU/CSU is shipped with factory settings in all four strap areas. You can find
default information by:
HReferring to Appendix A,
Worksheets
HAccessing the Default Factory Configuration branch of the DSU/CSU menu.
The DSU/CSU has four sets of configuration option settings. The Current
Configuration matches the Default Factory Configuration until modified and saved
by the user.
Configuration Option Area
Current ConfigurationThe DSU/CSU’s active set of configuration options.
Customer Configuration 1Use to set up and store a set of configuration options for
Customer Configuration 2Use to set up and store a second set of configuration
Default Factory ConfigurationA read-only configuration area containing the factory
Configuration Option Tables
.
Configuration Option Set
future use.
options for future use.
default configuration options.
or Appendix B,
3-2
If the factory default settings do not support your network’s configuration, you can
customize the configuration options for your application.
March 1998
7112-A2-GB20-20
Accessing and Displaying Configuration Options
To display the configuration options, you must first copy one configuration option
set into the edit area.
Procedure
To load a configuration option set into the configuration edit area:
1. Follow this menu selection sequence:
Main Menu→Configuration (Load Configuration From)
2. Select the Current, Customer 1, Customer 2, or Default Factory Configuration
and press Enter.
The selected configuration option set is loaded and the Configuration
Edit/Display menu screen appears.
See Appendix A for a list and explanation of the configuration options available.
Saving Configuration Options
Configuring the DSU/CSU
When changes are made to the configuration options, the changes must be
saved to take effect. The S
when the user has an effective access level of 1. All other effective access levels
have read-only permission.
ave key and Save Configuration To screen appear
Procedure
To save configuration options changes:
1. Press Ctrl-a to switch to the screen function key area below the dotted line.
2. Select S
3. Select one of the three configuration option areas on the screen and press
Enter. When Save is complete, Command Complete appears in the message
area at the bottom of the screen.
ave and press Enter. The Save Configuration To screen appears.
NOTE:
When Exit is selected before Save, a Save Configuration screen appears
requiring a Yes or No confirmation response.
If you select . . .
YesSave Configuration T o screen appears.
NoMain Menu appears and changes are not saved.
Then the . . .
7112-A2-GB20-20
March 1998
3-3
Configuring the DSU/CSU
Assigning DS0 Channels to the Data Port
The DSU/CSU provides Cross Connect configuration options that allow you to do
the following:
Display network DS0 channels assigned to the data port.
Allocate network DS0 channels to the data port.
Clear (unassign) all DS0 channels from the data port interface.
The DSU/CSU’s default configuration has all DS0 channels assigned to the data
port.
To access the Cross Connect Assignments screen, follow this menu selection
sequence:
Main Menu→Configuration→Load Configuration From
Cross Connect
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Ctrl–a to access these functions, ESC for previous menu M
S
ave Clrassign
Select: Block, ACAMI, Channel.
ainMenu Exit
3-4
March 1998
7112-A2-GB20-20
Displaying DS0 Channel Assignments
Use the Cross Connect Assignments screen to view which DS0 channels are
currently assigned to the data port. Below each DS0 channel you will see either
“Available” or “P”. DS0s with a “P” designation are assigned to the data port.
DS0s marked “Available” are unused (unassigned).
Cross Connect Assignments may also be displayed by accessing the Cross
Connect Status screen under the Status branch of the Main Menu.
Using the Block or ACAMI Assignment Method
By using the block or ACAMI (Alternate Channel Alternate Mark Inversion)
assignment method, you can assign a data port to a block of contiguous DS0
channels on the network interface.
The block assignment method allows a block of contiguous channels to be
assigned by specifying the number of DS0’s to allocate and an initial DS0
channel (the first DS0 channel in a block of DS0 channels). The number of
channels assigned is determined by the port rate. These channels are
automatically assigned to the destination network interface when the initial DS0
channel is selected.
Configuring the DSU/CSU
The ACAMI assignment method also allows a block of contiguous channels to be
assigned. However, with ACAMI, the number of channels assigned is twice the
number needed for the port rate. This is because with ACAMI, every alternate
n
DS0 channel (starting with the
port, but instead always transmits and receives all ones.
+1 DS0 channel), does not carry data from the
Procedure
To assign data ports by the block or ACAMI method:
1. Access the Cross Connect Assignments screen by following this menu
selection sequence:
Main Menu→Configuration→Load Configuration From
Cross Connect
2. Use the Assign By field to specify the assignment method (Block or ACAMI).
3. After filling in the DS0s to Allocate field, specify a port assignment for the
first DS0 channel in a block of contiguous, available DS0 channels.
4. Select Ctrl-a and then S
ave to save your changes.
→
7112-A2-GB20-20
March 1998
3-5
Configuring the DSU/CSU
Using the Individual Channel Assignment Method
This channel method allows you to select the individual DS0 channels to allocate
to the data port. The data port rate is automatically determined based on the
number of channels selected. The DS0s do not need to be contiguous.
Procedure
To assign the data port by the individual channel method:
1. Access the Cross Connect Assignments screen by following this menu
selection sequence:
Main Menu→Configuration→Load Configuration From
Cross Connect
2. Use the Assign By field to specify the assignment method (Channel).
3. Specify the port assignments for the individual DS0 channels. The DS0
channels do not need to be contiguous.
4. The port rate increases as the port is assigned to each additional DS0
channel. For example, if two DS0 channels (at 64 kbps each) are assigned to
the data port, a port rate of 128 kbps is required.
→
5. Select Ctrl-a and then S
Clearing DS0 Channel Assignments
You can clear (deallocate) all the DS0 channels currently allocated to network
interface.
Procedure
To clear DS0 channel allocation:
1. Access the Cross Connect Assignments screen by following this menu
selection sequence:
Main Menu→Configuration→Load Configuration From
Cross Connect
2. Select Ctrl-a and then Clrassign.
3. Press Enter to clear the specified DS0 channels.
ave to save your changes.
→
3-6
March 1998
7112-A2-GB20-20
Security
Overview
4
The DSU/CSU provides several methods of security by limiting user access to the
ATI through option settings. Refer to
Enable the Login Required option to require a Login ID for the:
— Terminal Port
— Telnet Session
ATI Access
on page 4-4.
Limit the access:
— Port Access Level option of 1, 2, or 3 for the Terminal port
— Session Access Level option of 1, 2, or 3 for the Telnet Session
Disable the access:
— Telnet Session option
— Facility Data Link (FDL) option
— Ethernet Port Use option
SNMP security is handled through Community Names with access levels and
IP address validation. Refer to
Controlling SNMP Access
on page 4-6.
7112-A2-GB20-20
March 1998
4-1
Security
Creating a Login
Logins apply to Terminal port and Telnet access to the ATI. Six login ID/password
combinations are available. Each Login ID and Password must be unique and
include an access level.
For additional information regarding the ATI access using the Login Required
option, refer to
ATI Access
on page 4-4
.
Procedure
To create a login record:
1. Follow this menu selection sequence:
Main Menu→Control→Administer Logins
2. Press Ctrl-a to switch to the screen function key area below the dotted line.
3. Select N
4. Create the login by entering the following fields. Login IDs and passwords are
case-sensitive.
On the Administer
Logins screen, for the . . .
Login ID1 to 10 ASCII printable characters
Password1 to 10 ASCII printable characters
Access LevelLevel 1, Level 2, or Level 3
ew and press Enter.
Enter . . .
NOTE:
Assign at least one Level 1 Access Level. Full access is necessary to
make configuration option changes and administer logins.
5. Press Ctrl-a to switch to the screen function key area below the dotted line.
Select S
6. When Save is complete, Command Complete appears at the bottom of the
screen. Select:
—N
ave and press Enter.
ew to add another login record
4-2
—M
ainMenu to go to the Main Menu
xit to end the ATI session
—E
March 1998
7112-A2-GB20-20
Loading...
+ 126 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.