• Maximum Peak to peak ripple voltage on AUX is 500 millivolts.
• Low voltage on the battery generated when battery is below 10.7 volts
• Deep discharge protection on the battery operates 7.7 ± 0.3 volts.
• If voltage drops below 11.3 volts a fault is signal is generated.
War rant y
For complete warranty information on this p roduc t please refer to the Limited Warranty Statement
found on our Web site: www.paradox.com/terms. Your use of this Paradox product signifies your
acceptance of all warranty terms and c onditions.
Limitations of Alarm Systems
It must be understood that whil e your Paradox alarm system is highly advanced and secure, it does not
offer any guaranteed protection against burgla ry, fire or other emergency (fire and emergency
options are only available on certain Paradox models). This is due to a number of reasons, in cluding by
not limited to inadequate or improper i nstallation/positioning, sensor limitations, battery
performance, wireless signa l interruption, inadequate maintenance or the potential for th e system or
telephone lines to be compromised or circumvented. As a result, Paradox does not represent that the
alarm system will prevent personal inju ry or property damage, or in all cases provide adequate
warning or protection.
Your security system should therefore be considered as one of many tools available to reduce risk and/
or damage of burglary, fire or other emergencies, such other tools include but are not limited to
insurance coverage, fire prevention and extinguish devices, and sprinkler systems.
We also strongly recommend that you regularly maintai n your security systems and stay aware of new
and improved Paradox products and developments.
TBR-21: In order to comply with TBR-21, standard force dialing must be enabled.
UL And ULC Warnings
This equipment has the capabil ity of being programmed with features not verified for use in UL
installations. To stay within UL and ULC standards, the installer shou ld use the following guidelines
when configuring the system:
• All components of the system should be UL listed for the intended application.
• If used for fire detection, the inst aller should refer to NFPA Standards #72, Chapter 2. In a ddition,
once installation is complete, the local fire authority must be notified of the install ation.
• WARNING: This equi pment must be installed and maintained by qualified service personne l
only
• This equipment must be verified by a qu alified technician once every three years.
• All keypads must use an anti-t amper switch.
• Do not bypass fire zones.
• Maximum allowed entry delay i s 45 seconds.
• Maximum allowed exit delay is 60 s econds.
• Minimum 4 minutes for bell cut-off time.
• The following features do not comply with UL requirements: Bypass Recall and Auto Trouble
Shutdown.
• Do not connect the primary indicating device to a relay. The installer must use the bell output.
• To comply with UL985, the auxiliary power output should not exceed 200mA.
• Do not connect the zone ground terminal with UL Listed products.
• The metallic enclosure must be grounded to the cold water pipe.
• All outputs are Class 2 or powe r-limi ted, except for th e battery terminal. The Class 2 and powerlimited fire alarm circuits shall be installed using CL3, CL3R, CL3P, or substitute cable permitted by
the National Electrical Code, ANSI/NFPA 70.
• EOL resistor part #2011002000
• For UL Instal lations : Universal UB1640W 16.5VAC min 40VA
• 12 Vdc 4 Ah rechargeable acid/lead or gel cell backup battery ( YUASA model #NP7-12
recommended) for residential use. Use a 7 Ah battery to comply with fire requirements.
This device complies with FCC Rules P art 15 and with Industry Canada license exempt RSS standard(s) .
Operation is subject to two conditions:
· This device may not cause harmful interference
· This device must accept any interference that may be received or th at may cause undesired
operation.
Le présent appareil est conforme aux CNR d'Indu strie Canada applicables aux appareils radio exempts
de licence. L'exploitation est autorisée aux deux conditions suivantes :
· L'appareil ne doit pas produire de brouillage, et
· l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage
est susceptible d'en compromettre le fonctionnement.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numerique de la classe B est conforme a la norme NMB-003 du Canada.
FCC ID: KDYMG5050V2
IC: 2438A-MG5050V2
FCC WARNING
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the interference by one
or more of the following mea sures:
· Reorient or relocate the receiving antenna.
· Increase the separation between the equipment and the receiver.
· Connect the equipment into an outlet different from that to which the receiver is connected.
· Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications to this equipment not expressly approved by the party responsible for
compliance (Paradox Security Systems Ltd.) could void the user’s authority to operate t he equipment.
Reference & Installation Manual
1.1Features
• 32 zones (any of which can be wireless or keypad zones).
• 32 users and 32 remote controls (one per user).
• In-field upgrades: Update the panel’s firmware by connecting it to a PC via a 307USB Interface and then using the Winload
software (V2.80 or higher).
• Menu-driven programming for the Installer, Master, and Maintenance codes. This enables you to program the panel through a
simple and easy to use interface, without the use of section numbers.
• Multiple telephone numbers for event reporting: Three for the monitoring station, five for personal dialling and one for pager
reporting. Up to five persons can now be contacted by the panel in case of alarm.
• Calendar with daylight savings time (enable section [730], option [1] and choose section [731] to put in the Country Code):
You can now select 1 out of 18 different country groups each with its own pre-programmed local daylight savings time. You can
also customize the daylight saving time by programming sections [732] and [733].
• New Sleep arming method: Similar to Stay arming, Sleep arming allows users to remain in a protected area, but provides a
higher level of protection. For example, in a two-story house, the perimeter is protected with Stay arming. With Sleep arming,
the perimeter as well as the main floor is protected (motion detectors, etc.), allowing you to roam the second floor and sleeping
quarters.
• Connect up to 15 hardwire keypads on the 4-wire communication bus.
• Push button power reset: Convenient reset button saves time when a momentary powerdown is required as opposed to having
to physically disconnect the control panel’s power cables. Press and hold the RESET switch for five seconds. The STATUS
LED will start flashing. Within 2 seconds of this flashing, press the reset switch again. The panel will reset to default and
restart. Also, you can reset all programmable sections to factory default values in section [950].
• Available in 433MHz or 868MHz.
• Supports Memory Key (PMC-4 and PMC5).
• RF jamming supervision (section [700], option [5]): The control panel will report a trouble if the RF signal is being jammed.
• Supports SIA reporting format to central station.
Part 1: Introduction
1.2System Overview
ModuleDescriptionMaximum number per system
K32RF 32-Zone Wireless LED Keypad Module8
K10V/H, K32, K32+,K32LCD,
K32LCD+, K32LX, K35, K636,
TM50
ZX8 ZX8SP 8-Zone Expansion Module3
RPT1 Magellan Wireless Repeater Module2
VDMP3 Plug-In Voice Dialer1
IP100 or IP150IP Internet Module1
RTX3 Wireless Expansion Module (Spectra SP only)1
PCS250 or PCS250GGSM/GPRS Communicator Module1
RX1Wireless Receiver Module1
PGM44 output Expansion Module1
HUB22-Port HUB and Bus Isolator1
10 and 32-Zone Hardwired LED and LCD Keypad
Module, Touchscreen
Power rating16.5 VAC (50 or 60Hz) minimum 20 VA (40 VA recommended)
Power consumptionMG5000: 1.2A(Max.), 85mA (Idle) MG5050: 1.2A(Max.), 95mA (Idle)
Aux. BUS *600 mA typical, 700 mA maximum, fuseless shutdown at 1.1A
Battery12 VDC, 4Ah/7Ah
Battery charging current350 mA
On-board zonesMG5000: 2, MG5050: 5
Bell current **1A (fuseless shutdown at 3A)
On-board PGMsMG5000: 2
DimensionsMG5000: 14 x 10.4cm (5.5 x 4.1”)
Weight18 g
Operating temperature0°C to 50°C (32°F to 122°F)
Humidity5% - 90%
* Cannot exceed 200 mA for UL installations
** Cannot exceed 1A for UL installations
Bell, PGMs and Auxiliary are rated to operate between 10.8Vdc and 12.1Vdc
30hrs backup60hrs backupRecharge to 80%(@350mA)
7AHr150mA50mA20 hrs.
MG5050: 4 (1+/- trigger)
All on-board PGMS are 100mA low-current outputs
MG5050: 19 x 10.2cm (7.5 x 4”)
2 Reference & Installation Manual
2.1Location and Mounting
UL Warning:
A 12Vdc / 7Ah battery is required to comply
with UL fire requirements.
Caution:
Disconnect battery before replacing the fuse.
Improper connection of the
transformer may result in
damage to the system.
Rechargeable Battery
UL/ULC - 12Vdc / 4Ah or 7Ah
Partial PCB view
Before mounting the cabinet, push the five white nylon mounting studs into the back of the cabinet. Pull all cables into the cabinet
and prepare them for connection before mounting the circuit board into the back of the cabinet. Select a centralized installation
site on the main floor that isn't easily accessible to intruders and leave at least 5cm (2in) around the panel box to permit adequate
ventilation and heat dissipation. The installation site should be dry and close to an AC source, ground connection and telephone
line connection. Avoid installation near or in the path of strong RF fields (i.e. neon lights, computers), on or near metal objects,
circuit breaker boxes, air conditioners and heater ducts since they may cause interference and reduce sensitivity. Avoid installing
the control panel in the basement. IMPORTANT: To comply to EN 50131 requirements, unit must be installed in an
approved tamper enclosure.
Do not cut, bend or alter the antennas and ensure that electrical wires do not cross over the antennae as these
may affect the signal reception.
2.2EN 50131 Compliancy
In order to meet with EN 50131 compliancy you will require the following:
•EN Metal Box
• Tamper Antenna
• Tamper Kit (TK278)
• Firmware version 4.96
2.3Earth Ground
Connect the zone and dialer ground terminals from the control panel to the metallic enclosure and cold water pipe or grounding
rod as per local electrical codes.
For maximum lightning protection, use separate earth grounds for the zone and dialer grounds as shown in the
PCB Layouts for each respective panel. For UL installations, the metallic enclosure must be grounded to the
cold water pipe.
Part 2: Installation
2.4AC Power
Do not use any switch-controlled outlets to power the transformer in order to avoid accidental user AC shut off. Connect the
transformer as shown in Figure 1. Use Table 1 for appropriate transformer.
Use only safety approved Transformer with rated output voltage of 16.5Vac and rated power of 40 VA maximum.
Transformer:
(use only one of the following)
Battery Charge Currents350mA350mA/700mA (programmable via panel)
2.5Backup Battery
To provide power during a power loss, connect a 12Vdc 4Ah rechargeable acid/lead or gel cell backup battery as shown in Figure 1
below. Use a 7Ah battery to comply with UL fire requirements. Connect the backup battery after applying AC power. When installing,
verify proper polarity as reversed connections will blow the battery fuse.
Use only safety approved rechargeable battery with rated voltage of 12Vdc and rated current of 7A maximum.
2.5.1Battery Test
If the battery is disconnected or if the battery fuse is blown, a No/Low Battery failure will appear in the keypad’s trouble
display (see Trouble Display on page 53). This trouble will also appear if the battery’s capacity is too low or if the voltage
drops to 10.5V or lower while the control panel is running on the backup battery. At 8.5V or lower, the panel shuts down
and all outputs close.
Table 1: Transformer Requirements Table
16VAC 20VA
(not verified by UL)
Figure 1: AC Power and Backup Battery Connections
For UL
16.5VAC 40VA
Magellan3
2.6MG5050 / MG5050 EN PCB Layout
Used for In-Field Firmware
upgrade through a 307USB
Direct Connect Interface.
See Connecting to WinLoad
on page 51 for details.
Antenna
Do not cut, bend or alter
the antennas and ensure
that electrical wires do not
cross over the antennae,
as this may affect signal
reception.
Four pin connector can
be used for quick
installation of a
MG5050 keypad.
Refer to AC Power
& Backup Battery
Connections on
page 3.
Charge LED:
Charging and battery
test LED
Status LED:
• Flash once every
second = Normal
•Flashes ON 1
second and OFF 1
second = Any
trouble
• Always ON = Panel
is using phone line
• Fast flash 6
seconds after power
up = Installer lock
enabled
"RX" & “TX” LED:
Flashes quickly when
receiving or
transmitting RF signals
from wireless devices.
To metallic
enclosure
Ground
clamp
AWG#14 single conductor
solid copper wire
Cold water
pipe grounding
The "BELL" output will
shutdown if the current
exceeds 3A.
Refer to
Single
Zone
Inputs
on
page 6
Max. amount of keypads = 15 keypads
Max. current = 700 mA
Max. distance of keypad from panel = 76m (250 feet)
Max. total run of wire = 230m (750 feet)
BUS (RED BLK GRN YEL)
Connect Paradox devices accordingly.
This is a unique connection interface
used for interconnection between
Paradox devices.
This equipment must be installed and maintained by qualified service personnel only.
For UL and C-UL warnings, refer to the UL and C-UL Warnings section at the back of the Reference & Installation Manual.
Press and hold the RESET button for
five seconds. The STATUS LED will
start flashing. Within 2 seconds of this
flashing, press the reset switch again.
The panel will reset to default and
restart.
EBUS and Dialer used for
VDMP3 plug-in voice module
for voice reporting.
PGM Trigger: This
jumper allows you to
choose whether the solid
state relay PGM (PGM4
only) is grounded (-), or
gives out 12V (+).
For the keypad’s zone
configurations, refer to the
Installer Quick Menu. If EOL
is enabled: see section [706]
option [2]. Also refer to Single
Zone Inputs on page 6.
Disconnect
telephone
line before
servicing.
MG5050 EN 50131 Immunity to Attenuation Test
When performing the attenuation test, replace antenna A with the following:
• For a 433 MHz panel, use an antenna with a length of 10.2 cm (4 in.)
• For a 868 MHz panel, use an antenna with a length of 6.1 cm (2.4 in.)
Once the test is complete, reinsert the original antenna (A) in its place, and
connect the wires (not shown) to a zone input programmed for tamper.
Tamper
antenna for
EN 50131
compliancy
To provide maximum
lightning protection we
strongly recommend having
separate earth connections
for the dialer and zone
ground terminals.
4 Reference & Installation Manual
2.7Metal Box Installation
The crosses and dotted line represent the mounting location. If you need specific dimensions, contact Paradox Distributor
Support. For UL recommended installation for the MG5000 only, place the PCB one notch lower than the mounting location.
MG5050 / MG5050 (11x11”)
2.8Telephone Line Connection
In order to report system events to the monitoring station, you must connect the incoming telephone company wires into the TIP
and RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as
shown in PCB Layouts for each respective panel.
2.9Bell Connection
The BELL+ and BELL- terminals power bells, sirens and other warning devices requiring a steady voltage output during an alarm.
The bell terminal supplies 12Vdc upon alarm and can support one 30-watt or two 20-watt sirens. The bell connection uses a
fuseless circuit and will automatically shut down if the current exceeds 3A. When this occurs the Maximum Bell Current failure will
only appear in the keypad’s trouble display (see Trouble Display on page 53) during an alarm. If the load on the BELL terminals
returns to normal, the control panel will re-instate power to the BELL terminals during the next alarm. When connecting sirens,
please verify correct polarity. Connect the positive lead to the BELL+ terminal and the negative lead to the BELL- terminal of the
control panel as shown in PCB Layouts for each respective panel.
If the BELL connection is not being used, the Bell Disconnected failure will remain in the keypad’s trouble
display (see Trouble Display on page 53). To avoid this connect a 1K resistor across the BELL terminals.
For connection of a self-contained bell/siren, see PCB Layouts for each respective panel.
Figure 2: Relay and PGM Connections
Magellan5
2.10Single Zone Inputs
Detection devices such as motion detectors and door contacts are connected to the control panel's zone input terminals. Figure 3
demonstrates single zone input terminal connections recognized by the panel. Once connected, the associated zone's
parameters must be defined.
Figure 3: Single Zone Input Connections
6 Reference & Installation Manual
2.11Advanced Technology Zone (ATZ) Connections
The ATZ feature is a software oriented feature that enables two detection devices to be installed per hardwired input terminal.
Each detection device has its own zone, displays its zone status on the keypad and sends its own alarm codes. Fire zones
cannot be doubled.
Figure 4: Advanced Technology Zone Connections
Magellan7
Part 3: Programming Methods
3.1WinLoad Software for Windows
Program the control panels remotely or on-site using the WinLoad Software (V2.80 or higher) for Windows®. For more
information, contact your local Paradox Distributor or visit our web site at paradox.com. If you are using the WinLoad software,
you must program the features (see Settings for WinLoad Software on page 51). Update the panel’s firmware by connecting it to
a PC via a 307 Direct Connect Interface and then using the Winload software. (Not investigated by UL).
3.2Programming Using a Keypad
Use the supplied programming guide to keep track of which sections were programmed and how. We recommend you read the
entire manual before you begin programming.
How Do I Enter Programming Mode?
1) Press [ENTER]
2) Enter your [
3) Enter 3-digit [SECTION] you wish to program
4) Enter required [DATA]
3.2.1Single Digit Data Entry Method (Decimal and Hexadecimal)
INSTALLERCODE] (default: 0000 / 000000) or [MAINTENANCECODE] (empty by default)
Single Digit Data Entry is used in all sections except those specified in the Feature Select Programming Method
(below). After entering Programming Mode as described in the shaded box above, some sections will require that you
enter Decimal values from 000 to 255. Other sections will require that you enter Hexadecimal values from 0 to F. The
required data will be clearly indicated in this manual as well as in the programming guide. When entering the final digit
in a section, the control panel will automatically save and advance to the next section. Except sections 001 to 032,
after entering the first three digits the control panel will switch to Feature Select Programming. For phone number
programming, press [
ENTER] to save the data.
Table 2: Decimal and Hexadecimal Programming Table
Value or Action
Value 0 / Replace Current Digit
with 0
Values 1 to 9[1] to [9] Zone 1 to 9[1] to [9]
A (hex only)[0]Zone 10[0]
B (hex only)[
C (hex only)[BYP]Zone 12[BYP]
D (hex only)[
E (hex only)[
F (hex only)
Exit Without Saving[
Save Data (hex only)[
What Do I
Press?
[SLEEP]Erase digit and remain in section Erase digit and remain in
OFF]Zone 11[OFF]
MEM]Zone 13[MEM]
TBL] Zone 14[TBL]
[]
CLEAR]ARM & STAY LED flashARM & STAY LED flash
ENTER]Advances to the next sectionAdvances to the next section
3.2.2Feature Select Programming Method
After entering certain sections, eight options will be displayed where each option from [1] to [8] represents a specific
feature. Press the key corresponding to the desired option. This means the option is ON. Press the key again to
remove the digit, thereby, turning OFF the option. When the options are set, press the [
advance to the next section.
What Do I See?
32-zone LED10-zone LED
section
Zone 15
ENTER] key to save and
[]
8 Reference & Installation Manual
3.2.3Data Display Mode (except K32LCD and K32LCD+)
To access the Data Display Mode, press the[ENTER] key after entering a section and before entering any data. The four LEDs
as indicated below will begin to flash indicating that you are in the Data Display Mode.
Each time the
[ENTER] key is pressed, the keypad will display the next digit in the current section and will continue through
all the following sections one digit at a time without changing the programmed values. Not available for sections using the
Multiple Feature Select Method. Press the
[CLEAR] key at any time to exit the Data Display Mode.
In the Data Display Mode you can view the programmed contents of each section one digit at a time.
Figure 5: Data Display Mode
3.3Configuring the Keypad Zone Number
How Do I Configure The Keypad?
Press [ENTER]
Enter your [INSTALLERCODE] (default: 0000 / 000000) or [MAINTENANCECODE] (empty by default)
Press [] and hold for three seconds
Enter the desired zone number key (K32/K32+, K32LCD/K32LCD+: 2-digit entry 01 to 32, K10V/H: 1-digit entry 1 to
0(10))
ENTER] to save and exit programming mode
Press [
Press [CLEAR] to erase data without saving
Press [CLEAR]+[CLEAR] to exit programming mode without saving
PLEASE NOTE: After five minutes, the keypad exits programming mode.
3.4Programming Using A Paradox Memory Key*
Copy the sections of one control panel into the Paradox Memory Key (PMC-4/PMC5). Then copy the contents of the Memory Key
into as many control panels as needed. Each panel is programmed in less than 3 seconds.
Download to DESTINATION Control Panel or module
1) Remove AC and battery power from the control panel.
2) Place the Memory Key on the serial connector labeled
is to receive the contents of the Memory Key.
3) Reapply AC and battery power.
4) In Installer Programming Mode, enter section [970], the keypad emits a confirmation beep.
5) When the keypad emits a second confirmation beep, remove the Memory Key.
Copy to Memory Key from SOURCE Control Panel or module
1) Remove AC and battery power from the control panel.
2) Place Memory Key on the serial connector labeled MEMORYKEY of the Control Panel that you
want to copy. Make sure the write protect jumper of the Memory Key is on.
3) Reapply AC and battery power.
4) In Installer Programming Mode, enter section [975]. The keypad emits a confirmation beep.
5) After the keypad emits a second confirmation beep, remove the Memory Key. Remove the
Memory Key’s jumper if you do not wish to accidentally overwrite its contents.
* Not investigated by UL
MEMORYKEY of the Control Panel that
Magellan9
Figure 6: Paradox Memory Key
Insert Paradox Memory Key
onto the ‘MEMKEY’
connector.
Partial view of control panel
Prevents overwriting
content of key.
Connection to
module or panel.
Blue LED flashes only
during transfer between
the key and the PC.
Connection to
USB Com Port.
Copy and download content of
the key.
Lock Switch
10 Reference & Installation Manual
4.1Input Keys
Alphanumeric Key Input
[1]A / B / C
[2]D / E / F
[3]G / H / I
[4]J / K / L
[5]M / N / O
[6]P / Q / R
[7]S / T / U
[8]V / W / X
[9]Y / Z
Special Function Keys
KeyFunction
[
STAY]Insert space
[
SLEEP]Delete
[ARM]Delete whole entry
[
OFF]Toggle numeric/alphanumeric keys
[
BYP]Toggle lower case/upper case
[MEM]Special characters
Label Sections
[181]
to
[212]
32 Zone Labels
[341]
to
[356]
16 PGM Labels
[511]
to
[542]
32 User Labels
[771]
to
[772]
2 Partition Labels
[568]
to
[569]
2 Wireless Labels
[599]
to
[606]
8 Wireless Keypads
[781]
to
[795]
15 Bus Modules Labels
Polish
001002003004005006007
Hungarian
001002003
Tur kis h
001
Special Character CataloguePolish / Hungarian / Turkish Special Character Catalogue
4.2Label Sections
Part 4: LCD Keypad Labels
4.3Special Characters and Keypad Letter Assignment
Magellan11
Hebrew Keypad Letter AssignmentHebrew Special Characters Catalogue
032048064080096112160176192208224240
033049065081097113161177193209225241
034050066082098114162178194210226242
035051067083099115163179195211227243
036052068084100116164180196212228244
037053069085101117165181197213229245
038054070086102118166182198214230246
039055071087103119167183199215231247
040056072088104120168184200216232248
041057073089105121169185201217233249
042058074090106122170186202218234250
043059075091107123171187203219235251
044060076092108124172188204220236252
045061077093109125173189205221237253
046062078094110126174190206222238254
047063079095111127175191207223239255
Greek Keypad Letter Assignment
Key
Press key
once
Press key
twice
Press key
three times
[1]ABG
[2]DEZ
[3]HQ I
[4]KLM
[5]NO
[6]PRS
[7]TUF
[8]CYW
Greek Special Characters Catalogue
016032048064080096112128144160176192208224240
017033049065081097113129145161177193209225241
018034050066082098114130146162178194210226242
019035051067083099115131147163179195211227243
020036052068084100116132148164180196212228244
021037053 A069 085101117133149165181197213229245
022038054070086102118134150166182198214230246
023039055071087103119135151167183199215231247
024040056072088104120136152168184200216232248
025041057073089105121137153169185201217233249
026042058074090106122138154170186202218234250
027043059075091107123139155171187203219235251
028044060076092108124140156172188204220236252
029045061077093109125141157173189205221237253
030046062078094110126142158174190206222238254
031047063079095111127143159175191207223239255
12Reference & Installation Manual
Russian Special Characters CatalogueRussian Keypad Letter Assignment
Magellan13
Part 5: Access Codes
The control panel supports the following access codes:
Installer Code [397]:Used to program all control panel settings except user access codes.
Maintenance Code [398]:The Maintenance code is similar to the Installer code. It can be used to enter programming mode, which
allows you to program all the features, options and commands except
settings. The maintenance code is empty by default.
System Master Code [399]:Provides full access. Arm and disarm using any method described in the User Code Options below as
well as program the user access codes.
Master Code 1:Permanently assigned to partition 1. Same as a regular user code except it can also program access
codes for user codes assigned to partition 1.
Master Code 2: Permanently assigned to partition 2. Same as a regular user code except it can program access codes
for user codes assigned to partition 2. If the system is not partitioned Master Code 2 will be assigned to
partition 1.
29 User Codes: Can arm and disarm as per User Code Options on page 14.
5.1Access Code Length
Section [701]: System Options
Option [1] OFF = 6-Digit Access Codes
Option [1] ON = 4-Digit Access Codes (default)
All access codes can be set to lengths of either 4- or 6-digits. When the 4-digit option is selected, entering a 4-digit code will allow
access. Using the 6-digit option, entering 6 digits is required to allow access.
If the access code length is changed from four digits to six digits when access codes have already been
programmed, the control panel will automatically add the last 2 digits by using the first 2 digits. For example, if
the access code is 1234 and you switch to 6 digits, the code will become 123412. Be sure to verify the access
codes after switching from 4-digit access codes to 6-digit codes. When switching from six digits to four digits, the
control panel will simply remove the final two digits of the access code. For example, 123456 will become 1234.
for the panel’s communication
5.2Installer Code (Default: 0000 / 000000)
The Installer Code is used to enter the system‘s programming mode, which allows you to program all the features, options and
commands of the control panel. The Installer Code can be 4- or 6-digits in length (see Access Code Length on page 14) where
each digit can be any value from 0 to 9. The Installer Code cannot be used to program Master Code 1, Master Code 2 or user
access codes. To program the Installer Code press:
ENTER]+ [CURRENTINSTALLERCODE] + [397] + new 4- or 6-digit Installer Code
[
5.3Maintenance Code (Default: Empty)
The Maintenance code is similar to the Installer code. It can be used to enter programming mode, which allows you to program all
the features, options and commands except for the system’s communication settings (sections [395], [397], [398], [815], [816],
[817], [910], and [911]) as well as any user codes. The Maintenance code can be 4 or 6 digits in length where each digit can be
any value from 0 to 9. The Maintenance code is empty by default. Set the Maintenance in section [398].
ENTER]+ [INSTALLERCODE] + [398] + new 4- or 6-digit Maintenance Code
[
5.4System Master Code (Default: 1234 / 123456)
The Installer Code can be used to program the System Master Code. With the System Master Code a user can use any arming
method and can program any user access code, but not the User Code Options. The System Master Code can be 4 or 6 digits in
length, where each digit can be any digit from 0 to 9. The System Master Code can be modified but cannot be erased. To change
the System Master Code press:
[ENTER]+ [INSTALLERCODE] + [399] + new 4- or 6-digit System Master Code
5.5User Code Options
Sections [404] to [432]: Options [1] to [8]
The User Code Options define which arming methods each user can use to arm or disarm the system. Regardless of these
settings, all users can Regular arm assigned partitions and all users except those with the Arm Only option can disarm an
assigned partition, regardless of how it is armed. Select one or more of the options described on the following pages for each
user access code, where sections [404] to [432] represent user access codes 004 to 032.
5.5.1Partition 1 Assignment
Sections [404] to [432]: User codes 004 to 032
Option [1] OFF = Deny access to partition 1
Option [1] ON= User code has access to partition 1 (default)
14Reference & Installation Manual
Loading...
+ 40 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.