Displays next digit or next section
Advances to the next section
[9]
What Do I See?
[1] to [9][1] to [9]
[11]B
[12]C
[13]D
[14]E
[15]F
Trouble Display
Press the [TBL] or [TRBL] key to view the Trouble Display. Please note that the keypad can be programmed to emit a BEEP
every 5 seconds whenever a new trouble condition has occurred. Press the [
[1]
- No Battery or Low Battery
[2]
- Wireless Transmitter Low Battery
[3]
- Power Failure
[4]
- Bell Output Disconnected[11]/[STAY] - Fire Loop Trouble*
[5]
- Maximum Bell Current[12]/[BYP] - Module Loss
[6]
- Maximum Auxiliary Current[13]/[MEM] - Wireless Transmitter Supervision Loss*
[7]
- Communicator Report Failure[16]/[FORCE] and [TBL]/[TRBL] flashes - Keypad Fault
[8]
- Timer Loss**
[9]
- Tamper or Zone Wiri ng Failure*
[10]
- Telephone Line Monitoring Failure
TBL] or [TRBL] key to stop the beeping.
* Press the illuminated key ([9], [
Tamper troubles.
** Press [8] to re-program the time.
STAY] or [MEM]) to view which zones are causing the trouble. Enter the Installer Code to clear
Default System Master Code ..................................................................................................................... ..................... 1
How Do I Enter Programming Mode? ..................................................................................................................... .... ... . 1
System Options............................................................................................................................................................. 12
Communication Settings ............................................................................................................................................... 15
System Settings ............................................................................................................................................................ 18
Reprogram All Modules................................................................................................................................................. 19
Serial Number Display................................................................................................................................................... 24
Signal Strength Display................................................................................................................................................. 24
Remote Control User Assignment................................................................................................................................. 25
Remote Control Assignment ......................................................................................................................................... 26
Zone Expansion Bus Modules ......................................................................................................... 27
Quick Function Keys ..................................................................................................................................................... 29
Appendix A - Ademco CID Report Code List (Prog.) ..................................................................... 30
Appendix B - Ademco CID Report Code List (All Codes).............................................................. 31
Bus Module Connections ................................................................................................................. 32
Single Zone Inputs........................................................................................................................................................ 36
Connecting Fire Circuits, Keyswitches and PGMs .. ... ... ... .............................................. ... ... ... .... .................................. 36
Programming a Wireless Fire Zone ........................................... ... .... ... ... ... .... ............................................................... 36
Alarm Relay and PGM Connections ............................................................................................................................. 37
Connecting More Than Two Keypads........................................................................................................................... 37
AC Power & Backup Battery Connections.................................................................................................................... 37
View the section’s programming one digit at a time. Does not function with sections using Feature Select Programming.
To access the Data Display Mode, press the[ENTER] key afte r entering a se ction and before ente ring any dat a. The
three LEDs as indicated below will begin to flash indicating that you are in the Data Display Mode.
Each time the
[ENTER] key is pressed, the keypad will display the next digit in the current section and will continue
through all the following sections one digit at a time without changing the programmed values. Not available for
sections using the Multiple Feature Select Method. Press the [
CLEAR] key at any time to exit the Data Display Mode.
Configuring the 1686H, 1686V and 1689 Keypads (V2.0 or higher)
The keypad’s zone number, EOL definition and anti-tamper switch are programmed through the keypad’s programming
mode. To do so:
How Do I Configure The Keypad?
1) Press [
2) Enter your [
3) Press the [
4) Press the desired key ([1] to [3]. See below)
5) Press [
PLEASE NOTE: After two minutes, the keypad exits programming mode.
Key [1] - Keypad Zone Selection
Key [1] determines whether the keypad’s zone is Keypad Zone 1 or Keypad Zone 2. When key [1] is OFF (not illuminated),
the keypad’s zone is Keypad Zone 1. When key [1] is ON (illuminated), the keypad’s zone is Keypad Zone 2. Refer to the
Zone Recognition Table on page 6 for more information.
Key [1] OFF - Keypad Zone 1 (default)
Key [1] ON - Keypad Zone 2
ENTER]
INSTALLERCODE] (default: 0000 / 000000)
PG] (1686H/V) / [FNC1] (1689) key and hold it for 3 seconds.
ENTER] to exit programming mode
Key [2] - EOL Definition
Key [2] determines the keyp ad zone’ s EOL definitio n. When key [2] is OFF (not illuminated), EOL is disabled and the keypad
zone uses the on-board EOL resistor . When key [2] is ON (illuminated), EOL is enabled and the keypad zone requires that an
external EOL resistor be connected (refer to Spectra 1759MG PCB Layout on page 38 for more details).
Key [2] OFF - EOL disabled
Key [2] ON - EOL enabled (default)
Key [3] - On-Board Tamper
Key [3] enables or disables the keyp ad’ s o n-board an ti-t amper switch. When key [3] is OFF (not illuminated), the anti-tamper
switch is disabled. When key [3] is ON (illuminated), the anti-tamper switch is enabled.
Key [3] OFF - On-board anti-tamper switch disabled
Key [3] ON - On-board anti-tamper switch enabled
PLEASE NOTE: The keypad can be ordered with or without an anti-tamper switch. If the keypad has no antitamper switch, key [3] will be OFF by default. If the keypad has an anti-tamper switch, key [3] will be ON by default.
Spectra 1759MG - 5 - Programming Guide
Zone Programming
When programming zones, the zone assignments are dependent on where the detection devices are connected to in the
system (see Zone Recognition Table). In installations that require using mostly the expansion inputs, refer to Reassign
Keypad Zone 2 (see section [126] option [7] on page 12) and Reassign zones to expansion inputs (see section [126] option
[8] on page 12).
.
Do not assign inputs from different modules to the same expansion input.
Zone 1Zone 1Zone 1Zone 1
Zone 2Zone 2Zone 2Zone 2
Zone 3Zone 3N/AN/A
Zone 4Zone 4N/AN/A
Zone 5Zone 5N/AN/A
Zone 6Zone 6Zone 3Zone 3
Zone 7N/AZone 4N/A
Zone 8Zone 7Zone 5Zone 4
Zone 9Zone 8Zone 6Zone 5
Zone 10Zone 9Zone 7Zone 6
Zone 11Zone10Zone 8Zone 7
Zone 12Zone 11Zone 9Zone 8
Zone 13Zone 12Zone 10Zone 9
Zone 14Zone 13Zone 11Zone 10
Zone 15Zone 14Zone 12Zone 11
= not displayed on 10-Zone LED Keypads
Option [7]= Reassign Keypad Zone 2
Option [8]= Reassign zones to expansion inputs
Spectra 1759MG - 6 - Programming Guide
How Do I Program the Zones?
1) Press the [ENTER] key
2) Enter the [
3) Enter 3-digit [
4) Enter one digit from the Zone Definition table (see page 7)
5) Enter one digit from the Partition Assignment table (see page 7)
6) Select one or more options from the Zone Options table (see page 7)
7) Press the [
INSTALLERCODE] (Default: 0000 / 000000)
SECTION]
ENTER] key
Zone Definition
Empty 1 2 3 4 5 6 -
Additional definitions for
on-board terminals:
7 8 9 -
Zone Disabled
Entry Delay 1
Entry Delay 2
Follow
Instant
24Hr Burglary
24Hr Buzzer
Keyswitch
Fire 24Hr
Delayed Fire 24Hr
Partition Assignment
Empty 1 2 3 -
Zone Disabled
Partition 1
Partition 2
Both Partitions
Zone Options
1 -
Auto Zone Shutdown
2 -
Bypass Enabled
3 -
Stay Zon e
4 - 5 -
Zone Alarm Type
off off Audible alarm (steady)
off on Audible alarm (pulsed)
on off Silent alarm
on on Generates a report only
6 -
Intellizone
7 -
Delay alarm transmission
8 -
Force Zone
Keyswitch Options
1 -
off = Maintained
[FORCE] key = empty
Second DigitFirst Digit
SectionDescription
[001]
= Zone 01:1 2 3 4 5 6 7 8
[002]
= Zone 02:1 2 3 4 5 6 7 8
[003]
= Zone 03:1 2 3 4 5 6 7 8
[004]
= Zone 04:1 2 3 4 5 6 7 8
[005]
= Zone 05:1 2 3 4 5 6 7 8
[006]
= Zone 06:1 2 3 4 5 6 7 8
[007]
= Zone 07:1 2 3 4 5 6 7 8
[008]
= Zone 08:1 2 3 4 5 6 7 8
[009]
= Zone 09:1 2 3 4 5 6 7 8
[010]
= Zone 10:1 2 3 4 5 6 7 8
[011]
= Zone 11:1 2 3 4 5 6 7 8
[012]
= Zone 12:1 2 3 4 5 6 7 8
[013]
= Zone 13:1 2 3 4 5 6 7 8
[014]
= Zone 14:1 2 3 4 5 6 7 8
[015]
= Zone 15:1 2 3 4 5 6 7 8
Defaults =
Zone
Definition
EmptyPartition 11 and 2
Partition
Assignment
on = Momentary
2 -
off = Regular Arm
on = Stay Arm
Zone Options
ON
Only the control panel’s on-board inputs can be defined as a Fire, Delayed Fire or a Keyswitch zone.
The on-board zones are zones 01 to 05. To program a wirele ss f ire zon e, refer to Prog ramming a W i reles s Fire
Zone on page 36.
Spectra 1759MG - 7 - Programming Guide
System Timers
Section #Decimal Value (000 to 255)Descriptio nDefault
___/___/___ x 10 msec.ZONESPEED (ZONE 1)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 2)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 3)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 4)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 5)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 6)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 7)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 8)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 9)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 10)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 11)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 12)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 13)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 14)600 msec.
___/___/___ x 10 msec.ZONESPEED (ZONE 15)600 msec.
FUTURE USE
___/___/___ seconds (000 = follow Deactivation Event)PGM1 TIMER5 sec.
___/___/___ seconds (000 = follow Deactivation Event)PGM2 TIMER5 sec.
___/___/___ seconds (000 = follow Deactivation Event)GLOBALPGMTIMER5 sec.
___/___/___ secondsENTRYDELAY 145 sec.
___/___/___ secondsENTRYDELAY 245 sec.
___/___/___ secondsEXITDELAY 130 sec.
___/___/___ secondsEXITDELAY 230 sec.
___/___/___ minutes (000 = no bell on alarm)BELLCUT-OFFTIMER (PARTITION 1)4 min.
___/___/___ minutes (000 = no bell on alarm)BELLCUT-OFFTIMER (PARTITION 2)4 min.
___/___/___ x 15 minutes (000 = disabled)NOMOVEMENTTIMER (PARTITION 1)Disabled
___/___/___ x 15 minutes (000 = disabled)NOMOVEMENTTIMER (PARTITION 2)Disabled
___/___/___ seconds (minimum 10 sec.)ANSWERINGMACHINEOVERRIDEDELAYDisabled
___/___/___ (000 = no answer, maximum = 15 rings)NUMBEROFRINGS8 rings
___/___/___ x 2 sec. (minimum 32 sec.)TLMFAILTIMER32 sec.
___/___/___ secondsDELAYALARMTRANSMISSIONDisabled
___/___/___ (000 = 16, maximum = 16)MAXIMUMDIALINGATTEMPTS8 attempts
___/___/___ secondsDELAYBETWEENATTEMPTS20 sec.
___/___/___ secondsPAGERDELAY5 sec.
___/___/___ seconds (minimum 10 sec.)INTELLIZONEDELAY48 sec.
___/___/___ secondsRECENTCLOSINGDELAYNo delay
___/___/___ minutesPOWERFAILUREREPORTDELAY15 min.
___/___/___ days (000 = disabled)AUTOTESTREPORTDisabled
___/___/___ 000 to 127 = +1 to +127 seconds
Each PGM Deactivation event can be used as another start (activation) event if their respective PGM timer (see sections
[066] to [068]) is programmed with a value other than 000.
Example: section [120] = 05 03 02: this means PGM1 will activate whenever partition 2 is Stay Armed.
PG] or [FNC1] key was pressed (Partition 1 only). This
option can also be used to reset smoke detectors.
02 = Instant Arming
03 = Stay Arming
04 = Force Arming
05 = Fast Exit (Force & Regular Only)
06 = PC Fail to Communicate (Partition 1 only)
07 = Midnight (Partition 1 only)
99 = Any Sub-Group (Partition 1 only, except 02 to 05)
06 = Arm/Disarm with Remote Control01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
07 = Button Pressed on Remote
(see button option “B” on page 25)
08 = Button Pressed on Remote
(see button option “C” on page 25)
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
Spectra 1759MG - 9 - Programming Guide
Event Group #Sub-Group #
09 = Button Pressed on Remote
(see button option “D” on page 25)
10 = Bypass Programming01 to 48 = User Code Numbers 001 to 048
11 = User Activated PGM01 to 48 = User Code Numbers 001 to 048 (Partition 1 only)
12 = Zone with Delay T ransmission Option Enabled is
Breached
13 = Arm with User Code01 to 48 = User Code Numbers 001 to 048
14 = Special Arm00 = Auto Arming (timed/no movement)
15 = Disarm with User Code01 to 48 = User Code Numbers 001 to 048
16 = Disarm After Alarm w/ User Code01 to 48 = User Code Numbers 001 to 048
17 = Cancel Alarm with User Code01 to 48 = User Code Numbers 001 to 048
18 = Special Disarm00 = Cancel Auto Arm (timed/no movement)
19 = Zone Bypassed on Arming01 to 15 = Zones 1 to 15
20 = Zone in Alarm01 to 15 = Zones 1 to 15
21 = Fire Alarm01 to 05 = Zones 1 to 5 (on-board inputs)
22 = Zone Alarm Restore01 to 15 = Zones 1 to 15
23 = Fire Alarm Restore01 to 05 = Zones 1 to 5 (on-board inputs)
24 = Special Alarm00 = Emergency Panic
25 = Auto Zone Shutdown01 to 15 = Zones 1 to 15
26 = Zone Tamper01 to 15 = Zones 1 to 15
27 = Zone Tamper Restore01 to 15 = Zones 1 to 15
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
99 = Any User Code
99 = Any User Code
01 to 15 = Zones 1 to 15
99 = Any Zone
99 = Any User Code
01 = Late to Close (Auto-Arming failed)
02 = No Movement Auto-Arming
03 = Partial Arming (Stay, Force, Instant, Bypass)
04 = One-Touch Arming
05 = Arm with WinLoad Software
07 = Closing Delinquency (Partition 1 only)
99 = Any Sub-Group
99 = Any User Code
99 = Any User Code
99 = Any User Code
01 = Disarm with WinLoad Software
02 = Disarm after alarm with WinLoad Software
03 = Cancel Alarm with WinLoad Software
99 = Any Sub-Group
99 = Any Zone
99 = Any Zone
99 = Any Zone
99 = Any Zone
99 = Any Zone
01 = Auxiliary Panic
02 = Fire Panic
03 = Recent Closing
04 = Auto Zone Shutdown
05 = Duress Alarm
06 = Keypad Lockout
99 = Any Sub-Group
99 = Any Zone
99 = Any Zone
99 = Any Zone
Spectra 1759MG - 10 - Programming Guide
Event Group #Sub-Group #
28 = System Trouble01 = AC Loss: only after Power Failure Delay has elapsed
(Partition 1 only)
02 = Battery Failure (Partition 1 only)
03 = Auxiliary current overload (Partition 1 only)
04 = Bell current overload (Partition 1 only)
05 = Bell disconnected (Partition 1 only)
06 = Timer Loss (Partition 1 only)
07 = Fire Loop Trouble (Partition 1 only)
08 = Future Use
09 = Module Fault (Partition 1 only)
10 = Printer Fault (Partition 1 only)
11 = Fail to Communicate (Partition 1 only)
99 = Any Sub-Group (Partition 1 only)
01 = AC Loss restore (Partition 1 only)
02 = Battery Failure restore (Partition 1 only)
03 = Auxiliary current overload restore (Partition 1 only)
04 = Bell current overload restore (Partition 1 only)
05 = Bell disconnected restore (Pa r titio n 1 on ly)
06 = Timer Programmed (Partition 1 only)
07 = Fire Loop Trouble restore (Partition 1 only)
08 = Future Use
09 = Module Fault restore (Partition 1 only)
10 = Printer Fault restore (Partition 1 only)
11 = Fail to Communicate restore (Partition 1 only)
99 = Any Trouble Restore (Partition 1 only)
30 = Special Reporting00 = System Power Up (Partition 1 only)
01 = Test Report (Partition 1 only)
02 = WinLoad Software Access (Partition 1 only)
03 = WinLoad Soft w a r e A c c e s s finished ( Partition 1 only)
04 = Installer enters programming mode (Partition 1 only)
05 = Installer exits programming mode (Partition 1 only)
99 = Any Sub-Group (Partition 1 only
31 = Wireless Transmitter Supervision Loss01 to 15 = Zones 1 to 15
99 = Any Zone
32 = Wireless Transmitter Supervision Loss Restore01 to 15 = Zones 1 to 15
99 = Any Zone
33 = Arming with a Keyswitch01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
34 = Disarming with a Keyswitch01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
35 = Disarm after Alarm with a Keyswitch01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
36 = Cancel Alarm with a Keyswitch01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
37 = Wireless Transmitter Low Battery01 to 15 = Zones 1 to 15
99 = Any Zone
38 = Wireless Transmitter Low Battery Restore01 to 15 = Zones 1 to 15
99 = Any Zone
)
Event Group #Sub-Group #Partition #
80 = PGM follows Clock (APR3-PGM4 only) HH = hour according to 24hr. clock MM = minutes according to 24hr. clock
Spectra 1759MG - 11 - Programming Guide
System Options
Bold = Default Setting
Section [126]: General Options
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
* Reassign Keypad Zone 2 and Reassign zones to expansion inputs change the zone numbering to increase the number of
expansion inputs that can be displayed on 10-Zone LED Keypads. Refer to the Zone Recognition Table on page 6 and the
Spectra 1759MG Reference & Installation Manual for details.
Confidential ModeN DisabledN Enabled
To exit Confidential Mode N Enter Access CodeN Press a Key
Confidential Mode timerN 2 minutesN 5 seconds
PGM1 normal stateN Normally Open (N.O.)N Normally Closed (N.C.)
PGM2 normal stateN Normally Open (N.O.)N Normally Closed (N.C.)
Global PGM normal stateN Normally Open (N.O.) N Normally Closed (N.C.)
Reassign Keypad Zone 2*N DisabledN Enabled
Reassign zones to expansion inputs* N DisabledN Enabled
OFFON
Section [127]: General Options
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
PartitioningN DisabledN Enabled
Access code lengthN 6-digitsN 4-digits
Keypad audible trouble warningN DisabledN Enabled
Lock System Master CodeN DisabledN Enabled
Battery charge currentN 350mAN 700mA
User Code 048 is a Duress CodeN DisabledN Enabled
Alarm relay followsN Bell OutputN Global PGM
Future useN N/AN N/A
OFFON
Section [128]: General Options
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
Panic 1: keys [1] & [3] N DisabledN Enabled
Panic 2: keys [4] & [6] N DisabledN Enabled
Panic 3: keys [7] & [9] N DisabledN Enabled
Panic 1: silent or audibleN SilentN Audible
Panic 2: silent or audibleN SilentN Audible
Panic 3: silent or fireN SilentN Fire
Keypad 1 tamper supervisionN DisabledN Enabled
Keypad 2 tamper supervisionN DisabledN Enabled
Section [129]: General Options
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
PGM2 output activation optionN SteadyN Pulse (flash)
PGM2 pulse once every 30 sec. if system armedN DisabledN Enabled
PGM2 pulse on Arm, twice on DisarmN DisabledN Enabled
ZX4 & ZX8 zone expansion module supervisionN DisabledN Enabled
Future use N N/AN N/A
Wireless module low battery supervisionN DisabledN Enabled
4-PGM Output Module supervision (APR3-PGM4)N DisabledN Enabled
Printer Module supervision (APR3-PRT1)N DisabledN Enabled
OFFON
OFFON
Spectra 1759MG - 12 - Programming Guide
Bold
= Default Setting
Section [130]: Arming/Disarming Options
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
One-touch Regular ArmingN DisabledN Enabled
One-touch Stay ArmingN DisabledN Enabled
One-touch Force ArmingN DisabledN Enabled
One-touch bypass programmingN DisabledN Enabled
Restrict arming on battery failureN DisabledN Enabled
Restrict arming on Tamper failureN DisabledN Enabled
Bell Squawk on Arm/Disarm with keypadN DisabledN Enabled
Beep on exit delayN Disabled N Enabled
Section [131]: Arming/Disarming Options
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
Report DisarmingN Always N Only after alarm
Regular Arming switches to Force Arming *N DisabledN Enabled
Bell Squawk on Arm/Disarm with remote control
(must be enabled for UL installations)
No exit delay when Arming with a remote controlN DisabledN Enabled
No exit delay beeps and no Bell Squawk when
Stay Arming
Restrict arming on wireless transmitter
supervision loss
Generate supervision loss if detected on
bypassed wireless zone
Future UseN N/AN N/A
OFFON
OFFON
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
N YesN No
* This option cannot be done using a keyswitch. Force arming is not supported by keyswitches.
Section [132]: Zone Options
Option
[1]&[2]
[3]
[4]
[5]
[6]
[7]&[8]
Tamper Recognition Options
[1][2]
OFFOFF Disabled (default)
OFFON When disarmed: GENERATESTROUBLEONLY
ONOFF When disarmed: GENERATESSILENTALARM
ONONWhen disarmed: GENERATESAUDIBLEALARM
When armed: Follows Zone Alarm Types
When armed: Follows Zone Alarm Types
When armed: Follows Zone Alarm Types
Generate tamper if detected on bypassed zone N YesN No
EOL (end-of-line) resistorsN No EOLN Use EOL Resistors
Future useN N/AN N/A
Report zone restoreN On Bell Cut-offN On Zone Closure
WirelessTransmitter SupervisionOptions
[7][8]
OFFOFF Disabled (default)
OFFON When disarmed: GENERATESTROUBLEONLY
ONOFF When disarmed: GENERATESSILENTALARM
ONONWhen disarmed: GENERATESAUDIBLEALARM
When armed: Follows Zone Alarm Types
When armed: Follows Zone Alarm Types
When armed: Follows Zone Alarm Types
OFFON
N see table N see table
N see table N see table
N see table N see table
N see table N see table
Spectra 1759MG - 13 - Programming Guide
Bold = Default Setting
Section [133]: Partition 1 Options
Option
[1]
[2]
[3]
[4]
[5]
[6] to [8]
Auto-arm on timeN DisabledN Enabled
Auto-arm on no movementN DisabledN Enabled
Auto Arming = Regular or StayN RegularArmingN Stay Arming
Switch to Stay Arming if no entry delay is openedN DisabledN Enabled
Stay Arming with Delay Partition 1 (Delay = [070]) N DisabledN Enabled
Future useN N/AN N/A
Section [134]: Partition 2 Options
Option
[1]
[2]
[3]
[4]
[5]
[6] to [8]
Auto-arm on timeN DisabledN Enabled
Auto-arm on no movementN DisabledN Enabled
Auto Arming = Regular or StayN RegularArmingN Stay Arming
Switch to Stay Arming if no entry delay is openedN DisabledN Enabled
Stay Arming with Delay Partition 2 (Delay = [070]) N DisabledN Enabled
Future useN N/AN N/A
Section [135]: Dialer Options
Option
[1] & [2]
OFFOFF TLM Disabled (default)
OFFON TLM generates a trouble if armed
TelephoneLine Monitoring (TLM)Options
[1][2]
ONOFF TLM generates an audible alarm if armed
ONONSilent alarms become audible
OFFON
OFFON
OFFON
N see table N see table
N see table N see table
[3]
[4]
[5]
[6]
[7] & [8]
Reporting (Dialer)N DisabledN Enabled
Dialing methodN Pulse DialingN Tone (DTMF) Dialing
Pulse ratioN 1:2 N 1:1.5
If armed, activate bell output on Com. Failure N DisabledN Enabled
Future useN N/AN N/A
Section [136]: Dialer Options
Option
[1]
[2]
[3]
[4]
[5]
[6] & [7]
[8]
Call back WinLoadN DisabledN Enabled
Automatic event buffer transmissionN DisabledN Enabled
Contact I.D. report codesN ProgrammableN All Codes (automatic)
Alternate dialN Disabled N Enabled
If no dial tone is presentN Continue after 4 sec. N Hang-up after 16 sec.
Pager Reporting Format Dialer Options
[6][7]
OFFOFF 1 call to pager or cellular telephone (default)
OFFON 2 calls to pager or cellular telephone
ONOFF 3 calls to pager or cellular telephone
ONON4 calls to pager or cellular telephone
Pager Format Transmission OptionsN Transmit report code
OFFON
N see table N see table
N see table N see table
N Transmit report code
after Pager delay
immediately
Spectra 1759MG - 14 - Programming Guide
Bold = Default Setting
Section [137]: Event Call Direction
Option
[1]
[2]
[3]
[4]
[5]
[6]
[7] & [8]
Call Telephone #1 for Arming/Disarming Report CodesN Disabled N Enabled
Call Telephone #2 for Arming/Disarming Report CodesN DisabledN Enabled
Call Telephone #1 for Alarm/Restore Report CodesN DisabledN Enabled
Call Telephone #2 for Alarm/Restore Report CodesN DisabledN Enabled
Call Telephone #1 for Tamper/Restore Report CodesN DisabledN Enabled
Call Telephone #2 for Tamper/Restore Report CodesN DisabledN Enabled
Future useN N/AN N/A
Section [138]: Event Call Direction
Option
[1]
[2]
[3]
[4]
[5] to [8]
Call Telephone #1 for Trouble/Restore Report CodesN Disabled N Enabled
Call Telephone #2 for Trouble/Restore Report CodesN DisabledN Enabled
Call Telephone #1 for Special Report CodesN DisabledN Enabled
Call Telephone #2 for Special Report CodesN DisabledN Enabled
Future useN N/AN N/A
5 = ADEMCOCONTACTID (DEFAULT) see option [3] in section [136] on page 14
6 =
PAGERFORMAT
If Hexadecimals (0 to FF) are used to program the report codes, verify that the pager also supports
Hexadecimals. If the pager does not support Hexadecimals, use only the digits 0 to 9.
PANELIDENTIFIER (WINLOADSOFTWARE)
PCPASSWORD (WINLOADSOFTWARE)
PARTITIONACCOUNTNUMBER 1 (For less than 4 digits, use the [FORCE] key to enter blan ks.)
PARTITIONACCOUNTNUMBER 2 (For less than 4 digits, use the [FORCE] key to enter blan ks.)
BACKUPTELEPHONENUMBER (32-digits, if less than 32 press [ENTER] to accept)
Special Keys for Telephone Numbers
[STAY] = *[MEM] = Switch from pulse to tone dialing or vice versa[FORCE] = Delete current digit
[
BYP] = #[TBL] or [TRBL] = 4-second pause[PG] or [FNC1] = Inserts Blank Space
Spectra 1759MG - 15 - Programming Guide
Report Codes
Ademco Slow, Silent Knight, SESCOA, Ademco Express and Pager Formats: Enter the desired 1- or 2-digit hex-value
(0-F or 00-FF). Ademco “Programmable” Format: Enter the desired 2-digit hex values from the “Ademco Report Cod e List
- Programmable” (see Appendix A on page 30). Also Note that entering FF will set the report code to the default Ademco
Report Code. Ademco “All Codes” Format: The control panel automatically generates report codes from the “Ademco
Report Code List - All Codes” (see Appendix B on page 31).
System Master Code arms or disarm partitions using any arming method and can create, modify or de lete any User Access
Code. Only the System Master Code can modify or delete User Access Codes assigned to both partitions.
Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that
are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 (except when partitioning is disabled, Master Code 2 will be assigned
to partition 1) and can be used to create, modify or delete User Access Codes that are assigned to the same partition.
750]After removing an expansion module from the communication bus, the control panel keeps the module’s
programmed sections in memory. Therefore, if you add or replace a module you can re-program the module with the
settings saved in the control panel. To do so, enter section [750] and press [
1) Remove AC and battery power from the control panel.
2) Insert the Memory Key onto the serial connector labelled
which you wish to download the contents of the memory key to.
3) Re-apply AC and battery power.
4) Enter installer programming mode, enter section [900], then press [
5) When the keypad emits a “confirmation beep”, remove the Memory Key.
6) Enter section [750] to reprogram the modules with the information downloaded from the
Paradox Memory Key.
Copy to Memory Key from SOURCE Control Panel
1) Remove AC and battery power from the control panel.
2) Insert Memory Key onto the serial connector labelled
you want to copy. Make sure the write protect jumper of the Memory Key is on.
3) Re-apply AC and battery power.
4) Enter installer programming mode, enter section [902], then press [
5) When the keypad emits a Confirmation Beep, remove the Memory Key. Remove the
Memory Key’s jumper if you do not wish to accidentally overwrite its contents.
KEY on the Spectra contro l panel to
ENTER] to acknowledge.
KEY on the Spectra control panel that
ENTER] to acknowledge.
Jumper ON =
Read from and/or write to
memory key
Insert Paradox Memory Key
onto the ‘MEMORY KEY’
connector.
Paradox
Memory Key
PMC-3
Partial view of Spectra
1759MG control panel
Jumper OFF =
Write protected (read
from memory key only)
Spectra 1759MG - 19 - Programming Guide
4-PGM Output Modules V2.0
Due to the APR3-PGM4’s Auto-recognition feature, it can be used with either the Spectra (V2.0 or higher), DGP-848 or
DGP-NE96 control panel. When connected to the bus, the APR3-PGM4 automatically detects which control panel it is
connected to and adjusts its internal communication parameters to function accordingly. Only one APR3-PGM4 can be
connected to each Spectra control panel.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-848. Mo d ule s wi th the
APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Bold = Default Setting
Section [500]: General Options
Option
[1]PGM1 Time Base SelectionN SecondsN Minutes
[2]PGM2 Time Base SelectionN SecondsN Minutes
[3]PGM3 Time Base SelectionN SecondsN Minutes
[4]PGM4 Time Base SelectionN SecondsN Minutes
[5] to [8] Future useN N/AN N/A
PGM Programming
Each PGM Deactivation event can be used as another activation event if their respective PGM timer (see sections [501] to
[504]) is programmed with a value other than 000. The APR3-PGM4 uses the same PGM events as the Spectra control
panel, please refer to Programmable Outputs on page 9.
OFFON
Section #Decimal Value (000-255)DescriptionDefault Value
PGM1TIMER5 sec.
PGM2TIMER5 sec.
PGM3TIMER5 sec.
PGM4TIMER5 sec.
Spectra 1759MG - 20 - Programming Guide
Printer Module V2.0
Due to the APR3-PRT1’s Auto-recognition feature, it can be used with either the Spectra (V2.0 or higher), DGP-848 or
DGP-NE96 control panel. When connected to the bus, the APR3-PRT1 automatically detects which control panel it is
connected to and adjusts its internal communication parameters to function accordingly. Only one APR3-PRT1 can be
connected to each Spectra control panel.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-8 48. Mo d ule s wi th the
APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Bold = Default Setting
Section [550]: General Options
Option
[1]Assigned to Partition 1N DisabledN Enabled
[2]Assigned to Partition 2N DisabledN Enabled
[3]PGM normal stateN Normally Open (N.O.)N Normally Closed (N.C.)
[4]Print Arming and disarming eventsN DisabledN Automatically
[5]Print Alarm and Alarm Restore eventsN DisabledN Automatically
[6]Print Tamper and Tamper Restore eventsN DisabledN Automatically
[7]Print Trouble and Trouble Restore eventsN DisabledN Automatically
[8]Print Special eventsN DisabledN Automatically
OFFON
Section [551]: Automatic Zone Status Printing
Option
[1]Print status of Zone 1N DisabledN Automatically
[2]Print status of Zone 2N DisabledN Automatically
[3]Print status of Zone 3N DisabledN Automatically
[4]Print status of Zone 4N DisabledN Automatically
[5]Print status of Zone 5N DisabledN Automatically
[6]Print status of Zone 6N DisabledN Automatically
[7]Print status of Zone 7N DisabledN Automatically
[8]Print status of Zone 8N DisabledN Automatically
OFFON
Section [552]: Automatic Zone Status Printing
Option
[1]Print status of Zone 9N DisabledN Automatically
[2]Print status of Zone 10N DisabledN Automatically
[3]Print status of Zone 11N DisabledN Automatically
[4]Print status of Zone 12N DisabledN Automatically
[5]Print status of Zone 13N DisabledN Automatically
[6]Print status of Zone 14N DisabledN Automatically
[7]Print status of Zone 15N DisabledN Automatically
[8]N/AN N/AN N/A
OFFON
Spectra 1759MG - 21 - Programming Guide
Bold = Default Setting
Section [553]: Serial and Parallel Port Setup Options
Option
[1]
[2]&[3]
Serial portN Disabled N Enabled
Baud Rate Settings
[2][3]APR-PRT1APR3-PRT1
OFFOFF 1200 baud (default)2400 baud (default)
ONOFF 2400 baud9600 baud
OFFON9600 baud19200 baud
ONON19200 baud57600 baud
OFFON
N see table N see table
N see table N see table
[4]
[5]
[6]
[7]
[8]
Parallel portN DisabledN Enabled
Off-line status ignored (parallel port only)N DisabledN Enabled
Paper empty status ignored (parallel port only)N DisabledN Enabled
Printer fault status ignored (parallel port only)N DisabledN Enabled
Printer busy status ignored (parallel port only)N DisabledN Enabled
PGM Programming
The PGM Deactivation event can be used as anoth er activation event if the PGM Timer (section [554]) is programmed with a
value other than 000. The APR3-PRT1 module uses the same PGM events as the Spectra control panel, please refer to
Programmable Outputs on page 9.
Section # Decimal Value (000-255)DescriptionDefault Value
[554] ___/___/___ seconds (000 = follow deactivation event)
For example, to enter the date March 26, 2004 you would enter 2004 (year), 03 (month), and 26 (day).
Section #Value
[557]Year ___/___/___/___ Month ___/___ Day ___/___
Spectra 1759MG - 22 - Programming Guide
Voice-assisted Arm/Disarm Bus Module V2.0
Due to InTouch’s Auto-recognition feature, it can be used with either the Spectra (V2.0 or higher), DGP-848 or DGP-NE96
control panels. When connected to the bus, InTouch automatically detects which control panel it is connected to and adjusts
its internal communication parameters to function accordingly. Only one InTouch can be connected to each Spectra control
panel.
APR3-ADM2 can also be programmed using the WinLoad Software. Refer to the WinLoad Online Help for more information.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-8 48. Mo d ule s wi th the
APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Section #Decimal Value (000-255)DescriptionDefault Value
Section #Description
[630]Press the anti-tamper switch of the Magellan Wireless Transmitter. The keypad will emit a confirmation
beep. On LED keypads, press the [
3 digits of the serial number will appear. Press the [
activating the desired transmitters or press [
ENTER] key to view the digits one at a time. On LCD keypads, the first
ENTER] key 3 times to view the next 3 digits. Continue
CLEAR] to exit.
Signal Strength Display
Section #Description
After entering the desired section, activate the Magellan Wireless Transmitter by opening/closing the zone
or by pressing the anti-tamper switch. Always ignore the first reading as it won’t be accurate. An average
reading of 3 or higher is acceptable.
[631]Display Signal Strength of Expansion Input 1 - Section [601]
[632]Display Signal Strength of Expansion Input 2 - Section [602]
[633]Display Signal Strength of Expansion Input 3 - Section [603]
[634]Display Signal Strength of Expansion Input 4 - Section [604]
[635]Display Signal Strength of Expansion Input 5 - Section [605]
[636]Display Signal Strength of Expansion Input 6 - Section [606]
[637]Display Signal Strength of Expansion Input 7 - Section [607]
[638]Display Signal Strength of Expansion Input 8 - Section [608]
Spectra 1759MG - 24 - Programming Guide
Remote Control User Assignment
Section #Decimal ValueDescriptionDefault Value
[701]___/___/___(001-048 = user #)remote control #1 - section [731]*000
[702]___/___/___(001-048 = user #)remote control #2 - section [732]*000
[703]___/___/___(001-048 = user #)remote control #3 - section [733]*000
[704]___/___/___(001-048 = user #)remote control #4 - section [734]*000
[705]___/___/___(001-048 = user #)remote control #5 - section [735]*000
[706]___/___/___(001-048 = user #)remote control #6 - section [736]*000
[707]___/___/___(001-048 = user #)remote control #7 - section [737]*000
[708]___/___/___(001-048 = user #)remote control #8 - section [738]*000
* refer to Remote Control Assignment on page 26.
Button Options
Button Options Table
Empty Slot [FORCE] - Button disabled
1 - Regular arming
2 - Stay arming
3 - Instant arming
4 - Force arming
5 - Disarm
6 - Disarm when no alarm
7 - Regular arm and disarm
8 - Panic 1
9 - Panic 2
A - Panic 3
MG-REM1
B - PGM Activation (Event Group #7, see PGM Programming)
C - PGM Activation (Event Group #8, see PGM Programming)
D - PGM Activation (Event Group #9, see PGM Programming)
Please note that the User Code assigned to the remote control (sections [701] to [708]) must have the same User
Options and Button Options enabled. For example, if you enable the Force Arming button option you must enable the
appropriate Force Arming user option . Also, if you enab l e any of the Panic button options, you must enable the Panic
options in the control panel.
= These button combinations are not available with the MG-REM1or MG-RAC1 remote controls and cannot be programmed.
Spectra 1759MG - 25 - Programming Guide
Remote Control Assignment
Enter the appropriate section and press any button on the remote control twice to assign the remote control. If you hear a
rejection beep, an error has occurred or the remote control has already been assign ed. To delete a remote control, enter the
desired section and then press the [
Only one SPC/APR3-ZX4 or one SPC/APR3-ZX8 can be connected to each Spectra control panel. The following sections
are for SPC-ZX4 version 1.0, APR3-ZX4 version 1.0, SPC-ZX8 version 1.0 and APR3-ZX8 version 2.0.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-8 48. Mo d ule s wi th the
APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Bold = Default Setting
Section [650]: Options
Option
[1]
[2]
[3]
EOL (end-of-line) resistors for hardwire modulesN No EOLN Use EOL Resistors
Zone Expansion Module tamper recognitionN DisabledN Z1 becomes tamper input
PGM1 on SPC/APR3-ZX8 follows Global PGM
The PGM will only activate or deactivate 100mS after the selected event occurs. The PGM Deactivation event can be used
as another activation event if the PGM Timer (section [655]) is programmed with a value other than 000. The system will
ignore the PGM if it has been programmed to follow the Global PGM ( option [3] in section [650]). Only PGM events from the
table below can be used.
Section #Decimal Value (000-255)DescriptionDefault Value
[655] ___/___/___ seconds (000 = follow deactivation event)
For APR3-ZX8:
60 = Hardwire Zone/Hardwire Tamper Opened
61 = Hardwire Zone/Hardwire Tamper Closed
07 = Expansion Input 7 - Section [651] - [7]
08 = Expansion Input 8 - Section [651] - [8]
99 = Any zone expansion bus module input
PGM1TIMER5 sec.
Not used; enter 00
Spectra 1759MG - 27 - Programming Guide
User Operation
Partitioning
The Spectra system is equipped with a pa rtitioning feature which can divide the alarm sy stem into two distinct areas identified
as Partition 1 and Partition 2. Partitioning can be used in installations where shared security systems are more practical, such
as an office/warehouse building. If the system is not partitioned, all User Codes and features will be recognized as
belonging to Partition 1.
How does a partitioned system work?
•Users can only arm or disarm their assigned partitions.
•Only zones assigned to Partition 1 will arm or disarm when Partition 1 is armed or disarmed.
•Only zones assigned to Partition 2 will arm or disarm when Partition 2 is armed or disarmed.
•Zones assigned to both partitions will arm when both partitions are armed and will disarm when
at least one disarms.
•Some of the system’s features can be programmed separately for each partition.
Programming Access Codes
User Access Codes are personal identification numbers that a llow users to en ter certain programming modes, arm or disa rm
the alarm system as well as activate or deactivate PGMs. Spectra security systems support the following:
System Master Code can arm or disarm any partition using any arming method and can create, modify or delete any User
Access Code. Only the System Master Code can modify or delete User Access Codes assigned to both partitions.
Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that
are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 (except when partitioning is disabled, Master Code 2 will be assigned
to partition 1) and can be used to create, modify or delete User Access Codes that are assigned to the same partition.
45 User Access Codes (including 1 Duress code)
How Do I Program Access Codes?
1) Press [
2) Key in the [
3) Key in 3-digit [
4) Key in new 4- or 6-digit [
[
ENTER]
SYSTEMMASTERCODE] or [MASTERCODE]
SECTION] (see User Code Table)
ACCESSCODE]
ENTER] flashes. Return to step 3
How Do I Delete Access Codes?
1) Repeat steps 1 to 3 (see above)
2) Press the [
FORCE] key once for each digit in the access code (4 or 6 times) until the
keypad emits a Confirmation Beep.
User Code Table
SectionUser Codes
[001]User Code 001 = System Master Code
[002]User Code 002 = Ma ster Code 1
[003]User Code 003 = Ma ster Code 2
[004]
TO [047]User Code 004 to User Code 047
[048]User Code 048 or Duress Code
Spectra 1759MG - 28 - Programming Guide
Programming Chime Zones
This feature allows users to program which zones will be Chime Enabled. A Chime Enabled zone will cause the keypad to
emit a rapid intermittent beep tone (
BEEP-BEEP-BEEP-BEEP) advising the user every time it is opened. Each keypad must be
Chime Programmed separately . Keyp ad chimes must be re-programmed if the system suf fers a total power loss (16-zone LED
and LCD Keypads only).
10-Zone LED Keypad
Press and hold any key from [1] to [10] for 3 seconds to activate or deactivate Chiming for zones 1 to 10. For example,
press and hold the [1] key to enable chiming on zone 1. If, after pressing and holding a key, the keypad emits a confirmation beep, this means the chime feature has been enable d for tha t zo ne. If the keypad emits a Rejection Beep, this mea ns
the Chime feature has been disabled for the correspond ing zone.
16-Zone LED Keypad
Press and hold the [9] key. Enter the 2-digit (01 to 16) zone number(s). When the corresponding LED is on, the zone is
chimed. When the corresponding LED is off, the zone is unchimed. When the desired zones ar e chimed, press [
ENTER].
LCD Keypad
Press and hold the [9] key. Enter the 2-digit (01 to 16) zone number(s) or use the arrow keys to scroll through the zones.
When the appropriate zone is displayed, press the [
FNC1] key. When the desired zones are chimed, press [ENTER].
Keypad Muting
Press and hold the [CLEAR] key for 3 seconds to enable or disable keypad muting. When muted, the keypad will only beep
when a key is pressed or when the keypad emits a Rejection or Confirmation Beep. All other beep functions are disabled.
Keypad Backlight (1686H and 1686V Only)
The illumination level behind the keys can be modified to suit the user’s needs. There are four backlight levels. The [MEM] key
is used to set the desired level. Each consecutive push of the [
level is reached. After reaching the maximum level, the backlight level will return to the lowest level and the whole process is
repeated. To change the backlight level:
MEM] key will increase the backlight level until the maximum
How do I Modify the Backlight?
1) Press and hold the [MEM] key for 3 seconds
2) The [
3) Press the [
4) Press [
MEM] key will illuminate
MEM] key to set the desired backlight level
CLEAR] or [ENTER] to exit
Quick Function Keys
Installer Test Mode
[
ENTER] + [INSTALLERCODE] + [TBL] or [TRBL]
The Installer Test Mode allows you to perform walk tests where the bell/siren will squawk once to indicate an open zone and
twice to indicate a closed zone. To enter this mode, press [
emit a Confirmation Beep. To disable this mode, press the [
Test Report
[
ENTER] + [INSTALLER/MASTERCODE] + [MEM]
Sends the Test Report report code programmed in section [211] to the central station.
Call WinLoad Software
[
ENTER] + [INSTALLER/MASTERCODE] + [BYP]
This feature is used to establish communication between the control panel and a computer using the WinLoad Software.
After entering this mode, the control panel will dial the telephone number programmed in section [150].
Cancel Communication
[
ENTER] + [INSTALLER/MASTERCODE] + [STAY]
Cancels all communication until the next reportable event. If the Master Code was used, only communication with WinLoad
would be cancelled.
ENTER] + [INSTALLERCODE] + [TBL] or [TRBL]. The keypad will
TBL] or [TRBL] key again. The keypad will emit a Rejection Beep.
Answer WinLoad Software
[
ENTER] + [INSTALLER/MASTERCODE] + [FORCE]
Forces the control panel to pick-up an incoming telephone call.
Spectra 1759MG - 29 - Programming Guide
Appendix A - Ademco CID Report Code List (Prog.)
If using the Ademco Contact ID Programmable code format, enter the 2-dig it hexadecimal value from the table below (Prog.
Value) into sections [160] to [213] to program the desired report codes. To enter a 0 value press the [
FORCE] key.
CID#Reporting Prog.
CodeValue
MEDICAL ALARMS - 100203Gate Valve Sensor2E401O/C by User5B
100Medical Alarm01204Low Water Level2F402Group O/C5C
101Pendant Transmitter02205Pump Activated30403Automatic O/C5D
102Fail to Report In03206Pump Failure31404Late to O/C5E
FIRE ALARMS - 110SYSTEM TROUBLES - 300 & 310405Deferred5F
Appendix B - Ademco CID Report Code List (All Codes)
System EventDefault Contact ID Report Code when
Arming with Master Code (##)3 4A1 - Close by userAuxiliary supply trouble1 3AA - System trouble
Arming with User Code (##)3 4A1 - Close by userBell output current limit1 321 - Bell 1
Arming with Keyswitch (##)3 4A9 - Keyswitch CloseBell absent1 321 - Bell 1
Auto Arming3 4A3 - Automatic CloseClock lost1 626 - Time/Date inaccurate
Arm with PC software3 4A7 - Remote arm/disarmFire loop trouble1 373 - Fire trouble
Late To Close3 4A4 - Late to CloseWireless Transmitter
No Movement 3 4A4 - Late to CloseWireless Transmitter
Disarm with Master Code (##)1 4A1 - Open by userWireless Transmitter
Disarm with User Code (##)1 4A1 - Open by userTLM trouble restore3 351 - Telco 1 fault restore
Disarm with Keyswitch (##)1 4A9 - Keyswitch OpenAC Failure restore3 3A1 - AC loss restore
Disarm after alarm with
Master Code (##)
Disarm after alarm with
User Code (##)
Disarm after alarm with
Keyswitch (##)
Auto Arming Cancellation1 4A5 - Deferred Open/CloseClock programmed3 626 - Time/Date Reset
Disarm with PC software1 4A7 - Remote arm/disarmFire loop trouble restore3 373 - Fire trouble restore
Disarm after an alarm with
PC software
Zone Bypassed (##)1 57A - Zone bypassModule fault restore3 333 - Expansion module failure
Zone alarm (##)1 13A - Burglary AlarmPrinter fault restore3 336 - Local printer failure restore
Fire alarm (##)1 11A - Fire alarmFail to communicate with
Zone alarm restore (##)3 13A - Burglary Alarm Restore
Fire alarm restore (##)3 11A - Fire alarm RestoreCold Start1 3A8 - System shutdown
Panic 2 - Medical 1 1AA - Medical alarmInstaller on site1 627 - Program mode Entry
Panic 3 - Fire 1 115 - Pull StationInstaller programming finished1 628 - Program mode Exit
Recent closing3 4AA - Open/Close
Global zone shutdown1 574 - Group bypass
Duress alarm1 121 - Duress
Zone shutdown (##)1 57A - Zone bypass
option [3] is on in section [136]
1 4A1 - Open by userBattery Failure restore3 3A9 - Battery test restore
1 4A1 - Open by userAuxiliary supply trouble restore3 3AA - System trouble restore
1 4A9 - Keyswitch OpenBell output current limit restore3 321 - Bell 1 restore
1 4A7 - Remote arm/disarmWireless Transmitter
System EventDefault Contact ID Report Code when
Low Battery
Supervision Loss
Fail to communicate with
central station
Low Battery
Bell absent restore3 321 - Bell 1 restore
Low Battery
Wireless Transmitter
Supervision Loss
central station
Test Report engaged1 6A2 - Periodic test report
finished
Delinquency1 654 - Inactivity
option [3] is on in section [136]
1 384 - RF xmtr. low battery
1 381 - Loss of super. - RF
1 354 - Fail to communicate
1 384 - RF xmtr. low battery
3 384 - RF xmtr. low battery
3 381 - Loss of super. - RF
restore
3 354 - Fail to communicate restore
1 412 - Successful - download access
Zone tampered (##)1 144 - Sensor tamper
Zone tamper restore (##)3 144 - Sensor tamper restore
AC Failure1 3A1 - AC loss
Battery Failure1 3A9 - Battery test failure
Spectra 1759MG - 31 - Programming Guide
Printer Module (APR3-PRT1)
B
Spectra 1759MG
Control Panel
Bus Module Connections
Press the “
A
PRINTTEST” switch to perform a print test
C
RX LED
reserved for
future use
Not Used
Communication
Bus
D
A Green “Locate” LED: Remains illuminated during power up
B Red “Watchdog” LED: Flashes to indicate proper operation. If the re is a communication
failure, the red LED will flash ON for one second and OFF for one second.
C Red “TX” LED: Flashes when the Printer Modul e is transmitting data thr ough the serial
port only.
D 25-pin Parallel Port: Connect the Printer Module’s 25-pin p arallel port to any dot matrix
printer. Note: The dot matrix printer must support a minimum of 80 columns.
E 9-Pin Serial Port: Connect the Printer Module’s 9-Pin serial port to a dot matrix printer.
Note: The dot matrix printer must support a minimum of 80 columns.
F 9-Pin Serial Port: Connect the Printer Module’s 9-Pin serial port to a computer’s COM
port to view the control panel’s events on the computer’s monitor. The events displayed
on the monitor can then be printed through the printer connected to the computer.
E
F
Connecting the PGM Output
Remove AC power and battery before adding APR3-PRT1 to the system. Do not connect any modules more than
76m (250ft) from the control panel. Only one Printer Module can be connected per Spectra c ontrol panel.
Spectra 1759MG - 32 - Programming Guide
4-PGM Output Module (APR3-PGM4)
To Spectra 1759MG
control panel
Red “Watchdog” LED:
Status: flashes once per second to indicate proper operation.
Flash 1 second on and 1 second off: The module is experiencing a communication
failure with the control panel.
Not Used
Communication
Bus
Remove AC and battery from the control panel before adding the 4-PGM Out put Module to the system. Do
not connect the APR3-PGM4 more than 76m (250ft) from the control panel. Only one APR3-PGM4 can be
connected per Spectra control panel.
4-zone expansion Bus Module (SPC-ZX4 and APR3-ZX4)
Not Used
Spectra 1759MG
control panel
Communication
Bus
Connect the detection devices to the
module's input terminals exactly as shown
in the Spectra 1759MG Reference & Installation Manual.
External Power Supply
(Recommended: Paradox
PSW817 1.75A Switching
Power Supply)
Any device such as a garage
door opener, light or siren
Not Used
Red “WDG” LED:
Status = Flashes to indicate proper operation.
Flash 1 sec. on & 1 sec. off = Trouble and/or
communication failure.
Connecting the Anti-
Tamper Switch
Input terminal Z1 can be used
as an anti-tamper switch input
Option [2]: Section [650]
Remove AC and battery power from the control panel before connecting the module to the
communication bus. Do not connect the APR3-ZX4 or SPC-ZX4 more than 76m (250ft) from the
control panel. Only one APR3-ZX4 or one SPC-ZX4 can be connected per Spectra control pane l.
Spectra 1759MG - 33 - Programming Guide
Voice-assisted Arm/Disarm Bus Module (APR3-ADM2)
Remove AC and battery power from the control panel before adding the APR3-ADM2 module to t he
system. Do not connect the APR3-ADM2 more than 76m (250ft) from the control panel. Only one APR3ADM2 can be connected per Spectra control panel.
Green "PULSE"LED:
Monitors the dialer. The LED will illuminate when the dialer
is in use. When the dialer is not being used, the LED will
remain off.
Red “WATCHDOG” LED:
Flashes once every second = normal.
Flashes 1 second on & 1 second off = trouble and/or
communication failure.
Not Used
Communication
Bus
Refer to Inset 1
T o S pectra 1759MG
control panel
Ground
clamp
Cold water pipe
grounding
Household
telephone
Inset 1: Connecting the APR3-ADM2 PGM Output
Partial view of the
APR3-ADM2
External Power Supply
(Recommended: Paradox
PSW817 1.75A Switching
Power Supply)
Spectra 1759MG
Dialer
Any device such as a garage
door opener, light or siren
Spectra 1759MG - 34 - Programming Guide
8-Zone Expansion Bus Modules (SPC-ZX8 and APR3-ZX8)
Red “WDG” LED:
Not Used
Flash once every sec. = normal.
Flash 1 sec. on & 1 sec. off = Trouble and/or communication failure.
Inset 2
Refer to the Spectra 1759MG Reference & Installation Manual
about connecting devices to the Expansion Input Terminals.
Inset 1: Connecting the
PGM output
Inset 2: Anti-Tamper
Switch Connection
Input terminal Z1 can be used
as an anti-tamper switch input.
Option [2]: Section [650]
Inset 1
Communication
Bus
Not Used
Spectra 1759MG
control panel
Remove AC power and battery before adding a module t o the system. Do not con nect the APR3-ZX8
or SPC-ZX8 more than 76m (250ft) from the control panel. Only one SPC-ZX8 or APR3-ZX8 can be
connected per Spectra control panel.
Spectra 1759MG - 35 - Programming Guide
Single Zone Inputs
Hardware Connections
Connecting Fire Circuits, Keyswitches and PGMs
Program the PGM with the “[PG]/[FNC1] Key
was pressed” Activation Event so that the
smoke detectors can be reset by pressing the
PG] or [FNC1] key. See Event Group # 5 on
[
page 9.
All 4-wire smoke detectors must be
connected using the daisy chain
configuration.
4-Wire Installation
Control Panel Terminals
Programming a Wireless Fire Zone
Fire zones cannot be assigned to expansion zones. As
a result, when installing a wireless smoke detector, the
corresponding zone must be programmed as follows:
1)Enter [5] in the Zone Definition to define it as a
24Hr Burglary Alarm (see page 7).
2)Disable [4] and enable [5] in Zone Options to set
the zone’s alarm type to a pulsed Audible Alarm
(see page 7).
3)Disable [1] and [2] in Zone Options to disable the
zone’s Auto Zone Shutdown and Bypass Enabled
features (see page 7).
4)Change the zone’s report code from a Burglary Report Code (Prog. Value
Fire Circuits
11) to a Fire Report Code (Prog. Value 04). See Appendix A on page30. If
using Ademco Contact I.D., set the Contact ID Options from All Codes to
Programmable (section [136] option [3] = OFF) and then enter the report
code manually (see page 14).
KeyswitchPGM
Spectra 1759MG - 36 - Programming Guide
Alarm Relay and PGM Connections
Alarm Relay (5A) can be
programmed to follow the
BELL output or the Global
PGM
PGMs
When the device connected to a PGM is powered by:
AUX+ terminal = must not exceed 700mA
External power supply = PGM1 cannot exceed 150mA
PGM2 can be used as a strobe output.
PGM2 cannot exceed 1A
If power supply's current limit is less than
that of the PGM it is connected to, then the
current consumption cannot exceed the
power supply's current limit.
External
Power
Supply
AUX+
External
power
supply
Any device such
as a strobe light
or siren
Connecting More Than Two Keypads
If there are more than 2 keypads connected to the control panel and at least one keypad zone is being used, connect as
shown and program as described in the Spectra 1759MG Reference & InstallationManual.
When a 1641 LCD keypad is connected to Spectra, the Keypad Zone Sending option (Option [2] key [1]) determines
whether the status of the keypad zone will be transmitted to the control panel. Refer to the 1641 Inst aller’s Guide for more
information. The Keypad Zone Sending option of the 1641 keypad must be enabled during the following conditions:
• If you are using both keypad zones and at least one is from a 1641 keypad.
• If you are using the keypad zones of other types of keypads, such as a 1686H 10-zone LED keypad, and th e keypad
zone definition of the 1641 keypad (keypad zone 1 or keypad zone 2; Option [2] key [3]) matches that of another
connected keypad.
typ: 600mA
max: 700mA
UL installations: typ. 200mA
Spectra 1759MG - 37 - Programming Guide
1686H
(Not using keypad zone)
Rechargeable Battery
UL/ULC - 12Vdc / 4Ah or 7Ah
Warning:
Improper connection
of the transformer may
result in damage to the system.
1641 LCD Keypad
(Not using keypad zone)
Be sure to enable option [1] (”Keypad
Zone Sending”) of option [2]
(”Options”) in the 1641’s LCD
Programming Mode.
Partial view of Spectra
1759MG control panel
UL Warning:
A 12Vdc / 7Ah battery
is required to comply
with UL fire
requirements.
Caution:
Disconnect battery
before replacing the
fuse.
Spectra 1759MG PCB Layout
"STATUS" LED:
Flash once every second = normal
Flashes ON 1 second and OFF 1 second = trouble
Always ON = panel is using phone line
Fast flash 4 seconds after power up = installer lock enabled
"RX" LED:
Flashes quickly when
receiving signals from
wireless devices.
Antennae
Paradox Memory
Key (PMC-3)
Reset Jumper
Refer to AC Power
& Backup Battery
Connections on
page 37.
Four pin connector
can be used for
quick installation of a
Spectra keypad or
Expansion Module.
To connect the 5A Alarm Relay and the PGMs,
refer to Alarm Relay and PGM Connections on
page 37. To connect AC power, refer to AC Power & Backup Battery Connections on page 37.
BELL" output will
The "
shutdown if the current
exceeds 3A.
Communication Bus
Refer to Single Zone Inputs on
page 36
To provide maximum lightning protection
we strongly recommend having separate
earth connections for the dialer and zone
ground terminals.
AWG#14 single
conductor solid
copper wire
To metallic
enclosure
Warning:
Do not cut, bend or
alter the antennae
and ensure that
electrical wires do
not cross over the
antennae, as this
may affect signal
reception.
Warning:
Disconnect
telephone line
before servicing.
Cold water
pipe
grounding
Ground
clamp
The maximum number of keypads per installation is dependent on the auxiliary
output, which cannot exceed 700mA.
AUX Power
Refer to transformer requirements on page37 for Aux.
Power Output. To connect additional wiring to auxiliary
power, use the red (+) and black (-) keypad connectors.
Auxiliary power will shut down if current exceeds 1.1A. If the
auxiliary output is overloaded and is shut down, you must
disconnect all loads from the output for at least 10 seconds
before reconnecting any load back to the auxiliary output.
For the keypad’s zone, EOL and tamper configurations,
refer to page 5.
Warning:
Do not connect
keypads more than
76m (250ft) from the
control panel.
Warning:
This equipment must be installed and maintained by
qualified service personnel only.
A Door Contact or any other detection
device can be connected to the
Keypad Zone.
For UL and C-UL warnings, refer to the UL and C-UL Warnings section at the back of the Spectra 1759MG
Reference & Installation Manual.
Spectra 1759MG - 38 - Programming Guide
Spectra Keypads
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under
normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever,
statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular
purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be
used in conjunction with products not manufactured by Seller, Seller cannot guarantee the performance of the security
system and shall not be responsible for circumstances resulting from the product’s inability to operate. Seller obligation and
liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the
specifications. Returns must include proof of purchase and be within the warranty period. In no event shall the Seller be liable
to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental, including
without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or
otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the
defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional
warranties that are binding on the Seller.
5886632. Canadian and international patents may also apply.
Spectra, Digiplex and Magellan are trademarks or registered trademarks of Paradox Security Systems Ltd. or its affiliates in
Canada, the United States and/or other countries.
For technical support in Canada or the U.S., call 1-800-791-1919 for English or 1-866-912-0600 for French, Monday to Friday from 8:00 a.m. to 8:00 p.m. EST. For technical support outside Canada and the U.S., call 00-1-450-491-7444 , Monday
to Friday from 8:00 a.m. to 8:00 p.m. EST. Please feel free to visit our website at www.paradox.ca.