Paradox Digiplex Liberator DGP-319 Owner's Manual

Page 1
I319EI01.fm Page 1 Wednesday, September 29, 1999 10:56 AM
DGP-319
Installer’s Guide
Wireless Bus Module V1.0
Page 2
I319EI01.fm Page 3 Wednesday, September 29, 1999 10:56 AM
1.0 TABLE OF CONTENTS
INTRODUCTION ...........................................................................5
1.1 Technical Specifications ...................................................................... 5
1.2 System Features ................................................................................. 5
INSTALLATION ............................................................................6
2.1 Location ............................................................................................... 6
2.2 Connections and Mounting ................................................................. 6
PROGRAMMING ...........................................................................8
3.1 Entering Module Programming Mode .................................................8
3.2 Low Battery Supervision ..................................................................... 9
3.3 Check-in Supervision .........................................................................10
3.4 Tamper Supervision on Receiver Module .......................................... 10
3.5 PGM Deactivation Mode ....................................................................11
3.6 PGM Base Time ................................................................................. 11
3.7 PGM Timers ....................................................................................... 12
3.8 PGM Activation Event ........................................................................ 12
3.9 PGM Deactivation Event .................................................................... 13
3.10 PGM Override ...................................................................................14
3.11 System Reset .................................................................................... 14
3.12 Viewing Unknown Serial Numbers .................................................... 15
DETECTORS AND CONTACT SWITCHES ................................16
4.1 Assigning Detectors & Contact Switches to Receiver ........................ 16
4.2 Assigning Detectors & Contact Switches to Zones ............................ 18
4.3 Viewing Signal Strength of Detectors & Contact Switches ................18
Page 3
I319EI01.fm Page 4 Wednesday, September 29, 1999 10:56 AM
REMOTE CONTROLS .................................................................19
5.1 Assigning Remote Controls to Receiver Module ............................... 20
5.2 Assigning Remote Controls to User Access Codes ........................... 21
5.3 Programming Remote Control Buttons ..............................................21
5.4 Replacing the Remote Control’s Battery ............................................ 26
PROGRAMMING GUIDE .............................................................27
PGM PROGRAMMING TABLE ................................................... 32
4 Installer’s Guide
Page 4
I319EI01.fm Page 5 Wednesday, September 29, 1999 10:56 AM
1.0 INTRODUCTION
1.1 TECHNICAL SPECIFICATIONS
Manchester Decoding Diversity Antenna Error Detection & Correction Frequency Hopping: @ 902 MHz - 928 MHz or 868MHz Range: Detectors & Contact Switches:
1000 m (3280’) or 300 m (984’) for 868 MHz
Remote Controls: 30 m (100‘) Data Rate: 10 KB/s Sensitivity: -105dBm Current: 70 mA Dimension (without antenna) 15 cm H x 16 cm L x 3 cm W
(6” H x 6.5” L x 1.1” W) Operating Temperature: 0°C - 50°C (32°F - 122°F) Operating Humidity: 85% PGM Outputs: 1 (an additional PGM Output is available) PGM Output current: 5A relay
1.2 SYSTEM FEATURES
Add 16 wireless detectors or contact switches to the Digiplex System Add 16 remote controls to the Digiplex System Reflow Design No tuned Circuit Tamper Switch Low Battery, Check-in, and Tamper supervision through Digiplex Control Panel Trouble Display through Digiplex Control Panel Signal Strength Indicator
Digiplex Liberator 5
Page 5
I319EI01.fm Page 6 Wednesday, September 29, 1999 10:56 AM
2.0 INSTALLATION
2.1 LOCATION
Mount the Liberator Wireless Bus Module on a wall allowing at least 5 cm (2") around the module to permit adequate ventilation and heat dissipation. Select a site that is not susceptible to drastic temperature changes. Avoid installation near or in the path of strong RF fields (i.e. neon lights, computers), on or near metal objects, circuit breaker boxes, air conditioners, and heater ducts since they may cause interference and reduce its sensitivity. We recommend installing it in a centralized location on the main floor. Avoid installing it in the basement. Refer to the Digiplex Control Panel's Reference & Installation Manual for maximum allowable distances between the control panel and the Liberator Wireless Bus Module.
2.2 CONNECTIONS AND MOUNTING
Firmly screw the two antennae into the connectors marked "ANT" on the Receiver Module (see Figure 2-1). Using a drill or screwdriver, punch out the four mounting holes on the back of the plastic case. Align the six holes of the printed circuit board with the six pins on the back plastic mounting case and snap into place. If placed correctly, the antennae will lean directly over the grooves in the mounting case.
Do not cut, bend, or alter the antennae. Avoid mounting the Receiver Module near or on metal as this may affect its sensitivity.
The Liberator Wireless Bus Module is connected to the control panel's DIGI-BUS in a star and/or daisy chain configuration. The DIGI-BUS is a 4-wire communication bus that provides power and two-way communication between the control panel and all the modules connected to it. Connect the “GRN” and “YEL” terminals from the Receiver Module to the corresponding “GRN” and “YEL” terminals of the control panel. Connect the “RED” terminal to the “AUX+” of the control panel. Connect theBLK” terminal to the “AUX-” of the control panel.
Remove AC power and then remove the battery before adding a bus module to the system or it may cause communication trouble.
6 Installer’s Guide
Page 6
I319EI01.fm Page 7 Wednesday, September 29, 1999 10:56 AM
Figure 2-1: Connections for Receiver Module to Control Panel
Digiplex Liberator 7
Page 7
I319EI01.fm Page 8 Wednesday, September 29, 1999 10:56 AM
3.0 PROGRAMMING
3.1 ENTERING MODULE PROGRAMMING MODE
All programming is done through Module Programming Mode in the Digiplex Control Panel from any keypad as shown in Figure 3-1. The sections referred to in Step 5
and the data referred to in Step 6 from Figure 3-1 are explored in the following sections of the manual.
Figure 3-1: Module Programming Mode
8 Installer’s Guide
Page 8
I319EI01.fm Page 9 Wednesday, September 29, 1999 10:56 AM
3.1.1 Feature Select Programming
Feature Select Programming is accomplished by enabling and/or disabling options. Feature Select Programming is used to program sections [001] and [002] and is also used in PGM Programming. Within the sections, numbers from 1 to 8 represent a specific option to enable or disable. Press the key corresponding to the desired option and the digit should appear on the LCD screen or illuminate the corresponding LED on the LED Keypad. This means that the option is enabled or ON. For example, in Step 6 of Figure 3-1, options [1] and [4] are enabled and show on the LCD screen. The 1 and 4 LEDs would illuminate on the LED Keypad. Press the key again to remove or extiguish the digit, thereby disabling (turning OFF) the option.
3.2 LOW BATTERY SUPERVISION
SECTION [001]: OPTION [1]
The wireless detectors and contact switches function on two 3.6V Lithium batteries. When a detector or contact switch detects a battery voltage of 6.5V or less, its yellow light (LED) will flash and it will transmit a signal to the Liberator Wireless Bus Module indicating that the voltage is low. If this option is enabled, the Receiver Module will transmit a signal to the control panel, which it will recognize as a Zone Low Battery. If this option is disabled, the Receiver Module will not transmit the low voltage signal to the control panel.
From Step 6 in Figure 3-1, page8, enable or disable the option: Option [1] OFF = Low Battery Supervision disabled
Option [1] ON = Low Battery Supervision enabled (default)
Digiplex Liberator 9
Page 9
I319EI01.fm Page 10 Wednesday, September 29, 1999 10:56 AM
3.3 CHECK-IN SUPERVISION
SECTION [001]: OPTIONS [2] AND [3]
The Liberator Wireless Bus Module waits for each of its assigned detectors and/or contact switches to send a status signal within a specified time period to confirm their presence and functionality. If a device has not sent a signal within the time period, the Receiver Module will automatically transmit a signal to the control panel, which it can recognize a supervision loss. Option [2] enables the Check-in Supervision feature and option [3] specifies the time period required for the devices to send their signal.
From Step 6 in Figure 3-1, page8, enable or disable the options: Option [2] OFF = Check-in Supervision disabled
Option [2] ON = Check-in Supervision enabled (default) Option [3] OFF = Check-in every 12 hours (default)
Option [3] ON = Check-in every 12 minutes
3.4 TAMPER SUPERVISION ON RECEIVER MODULE
SECTION [001]: OPTION [4]
If this option is enabled and the Receiver Module's cover is removed, the on-board tamper switch will be triggered. The Receiver Module will send a signal to the control panel, which it will recognize as a Module Tamper.
From Step 6 in Figure 3-1, page8, enable or disable the option: Option [4] OFF = Receiver Module's Tamper Supervision disabled (default)
Option [4] ON = Receiver Module's Tamper Supervision enabled
10 Installer’s Guide
Page 10
I319EI01.fm Page 11 Wednesday, September 29, 1999 10:56 AM
3.5 PGM DEACTIVATION MODE
SECTION [002]: OPTION [1] AND [5]
The Liberator Wireless Bus Module has one or two on-board PGMs. Each PGM can be in Follow Mode or in Timed Mode. If the PGM is in Follow Mode, it will deactivate according to its PGM Deactivation Event. If the PGM is in Timed Mode, it will deactivate according to its PGM Timer. However, if PGM Override is enabled, Follow Mode and Timed Mode will be ignored.
From Step 6 in Figure 3-1, page8, enable or disable the options: Option [1] OFF = PGM 1 in Follow Mode
Option [1] ON = PGM 1 in Timed Mode (default) Option [5] OFF = PGM 2 in Follow Mode
Option [5] ON = PGM 2 in Timed Mode (default)
Ensure that both the PGM Activation Event and PGM Deactivation Event are programmed for each PGM for Follow Mode to function properly.
3.6 PGM BASE TIME
SECTION [002]: OPTION [2] AND [6]
These options define the Base Time of the PGM Timers when the PGM is in Timed Mode. From Step 6 in Figure 3-1, page8, enable or disable the options: Option [2] OFF = PGM 1 Base Time is 1 second (default)
Option [2] ON = PGM 1 Base Time is 1 minute Option [6] OFF = PGM 2 Base Time is 1 second (default)
Option [6] ON = PGM 2 Base Time is 1 minute
Digiplex Liberator 11
Page 11
I319EI01.fm Page 12 Wednesday, September 29, 1999 10:56 AM
3.7 PGM TIMERS
SECTIONS [003] AND [004]
When PGM(s) are in Timed Mode, the value programmed for PGM 1 in section [003] and for PGM 2 in section [004] are multiplied by the PGM Base Time. This value can be any decimal from 001 to 255. This defines the time period the PGM(s) will remain activated unless the PGM Override is enabled. (Default 005)
From Step 5 in Figure 3-1, page8:
Timer PGM 1: Timer PGM 2:
1) Enter section [003] 1) Enter section [004]
2) Enter value (001 to 255) 2) Enter value (001 to 255)
3.8 PGM ACTIVATION EVENT
SECTIONS [005] AND [007]
The PGM Activation Events determine which events will activate the Liberator Wireless Bus Module's one or two on-board PGMs. If other PGM(s) on other modules or the control panel are programmed with the same PGM Activation Event as the Receiver Module, those PGM(s) will also be activated when the event occurs. For details on the available activation events, refer to the PGM Programming Table (see section 7.0 of this manual).
Both the PGM Activation Event and PGM Deactivation Event must be programmed for the PGM(s) in Follow Mode to function properly.
From Step 5 in Figure 3-1, page8: PGM 1: enter section [005]
PGM 2: enter section [007]
12 Installer’s Guide
Page 12
I319EI01.fm Page 13 Wednesday, September 29, 1999 10:56 AM
Use the PGM Programming Table to program a PGM Activation Event by following these steps:
1) In the selected section, enter the first digit where each digit is a hexadecimal
value from 8 to F that represents a specific event (0 = PGM Disabled).
2) Then enter the second digit, which can be any hexadecimal value from 0 to F
depending on the first digit chosen.
3) After entering the second digit, use Feature Select Programming to enable/
disable options [1] to [8]. Select up to eight specific events as detailed in the PGM Programming Table.
These keys represent the hexadecimal values from A to F: [STAY] = A [DISARM] = D [FORCE] = B [BYP] = E [ARM] = C [MEM] = F
For installations using the LED Keypads, the hexadecimal values will illuminate the following LEDs:
(A) = [STAY] LED (D) = [A4] LED (B) = [FORCE] LED (E) = [BYP] LED (C) = [A1] LED (F) = [MEM] LED
3.9 PGM DEACTIVATION EVENT
SECTIONS [006] AND [008]
When PGM Activation Events occur, the Liberator Wireless Bus Module's on-board PGM(s) will deactivate when the events programmed in section [006] for PGM 1 or in section [008] for PGM 2 occur unless it is in PGM Timed Mode. The PGM Deactivation Event is programmed in the same manner as the PGM Activation
Event (see section 3.8 of this manual).
Digiplex Liberator 13
Page 13
I319EI01.fm Page 14 Wednesday, September 29, 1999 10:56 AM
3.10 PGM OVERRIDE
SECTION [002]: OPTIONS [3] AND [7], [4] AND [8]
When the PGM Override is enabled in options [3] and/or [7], the Liberator Wireless Bus Module will ignore the PGM Mode, PGM Activation Events, PGM Deactivation Events, and PGM Timers of the corresponding PGM(s). Enabling and disabling options [4] and [8] controls whether each PGM is activated or deactivated once PGM Override is enabled.
From Step 6 in Figure 3-1, page8, enable or disable the options: Option [3] OFF = PGM 1 Override disabled (default)
Option [3] ON = PGM 1 Override enabled Option [4] OFF = PGM 1 deactivated (default)
Option [4] ON = PGM 1 activated Option [7] OFF = PGM 2 Override disabled (default)
Option [7] ON = PGM 2 Override enabled Option [8] OFF = PGM 2 deactivated (default)
Option [8] ON = PGM 2 activated
3.11 SYSTEM RESET
Performing a system reset will erase all the sections in the Liberator Wireless Bus Module's programming and set the following sections to their defaults:
Sections:
[001] = Options 1 and 2 ON; options 3 to 8 OFF [002] = Options 1 and 5 ON; options 2, 3, 4, 6, 7, and 8 OFF [003] = 005 (seconds) [004] = 005 (seconds)
14 Installer’s Guide
Page 14
I319EI01.fm Page 15 Wednesday, September 29, 1999 10:56 AM
To perform the system reset:
1) Disconnect the DIGI-BUS from the Receiver Module
2) Place the reset jumper on both reset pins on the Receiver Module.
3) Reconnect the DIGI-BUS to the Receiver Module
4) Wait until the "Locate" LED is off (takes about 4 seconds)
5) Remove the jumper The module can also be reset using the Module Reset feature in the Digiplex Control
Panel (see Digiplex Control Panel's Reference & Installation Manual).
3.12 VIEWING UNKNOWN SERIAL NUMBERS
SECTION [025]
The serial number of a detector, contact switch, or remote control can be displayed. From Step 5 in Figure 3-1, page8:
1) Enter section [025]
2) On LCD Screen: Press and hold the tamper switch on the detector or contact switch
or press and hold the remote's A and B buttons simultaneously until the keypad squawks and the device's serial number appears on the LCD screen under the words "View Data". On LED Screen: Press and hold the tamper switch on the detector or contact switch or press and hold the remote's A and B buttons simultaneously until the keypad squawks. The first number of the device's serial number will illuminate (10 = zero). Press the button to view each subsequent number. When you press the button on the last number of the serial number, the control panel will exit the section.
Digiplex Liberator 15
Page 15
I319EI01.fm Page 16 Wednesday, September 29, 1999 10:56 AM
4.0 DETECTORS AND CONTACT SWITCHES
Programming for the wireless detectors and the contact switches is accomplished in three steps:
1) Detectors and contact switches must be assigned to the Liberator Wireless Bus Module.
2) The detectors and contact switches from the Liberator Wireless Bus Module must
be assigned to zones in the Digiplex Control Panel.
3) The zone parameters must be defined in the Digiplex Control Panel.
For more details concerning zones, refer to the Digiplex Control Panel's Reference & Installation Manual.
Complete the Programming Guide (see section 6.0 of this manual) while assigning the detectors and contact switches. The serial numbers and the inputs that they are assigned to will be needed when programming the
zones in the control panel. Sections [020], [021], [101] to [116], and [201] to [216] are all interrelated. For example, when assigning a detector or contact switch to the Receiver Module:
1) The serial number and input number will be assigned in section [101]
2) The number of devices will automatically appear in section [020]
3) Its signal strength can be viewed in section [201]
4.1 ASSIGNING DETECTORS & CONTACT SWITCHES TO RECEIVER
In these sections you will assign the detectors and contact switches to the Liberator Wireless Bus Module. Up to 16 detectors or contact switches can be assigned to each Receiver Module.
16 Installer’s Guide
Page 16
I319EI01.fm Page 17 Wednesday, September 29, 1999 10:56 AM
SECTIONS [101] TO [116]
Enter the serial numbers of the detectors and contact switches in the sections [101] to [116]. The serial numbers can be found inside the devices. Inputs 001 to 016 are automatically assigned when the serial number is entered. For example, Section [101] is assigned to input 001, Section [102] is assigned to input 002, etc,. When one section is programmed, the keypad will automatically switch to the next section.
From Step 5 in Figure 3-1, page8:
1) Enter the desired section from [101] to [116]
2) Enter the serial number of the detector or contact switch If you are unable to find the serial number, refer to section 3.12 of this
manual.
SECTIONS [020] AND [021]
The number of devices assigned to sections [101] to [108] can be viewed in section [020]. The number of devices assigned to sections [109] to [116] can be viewed in
section [021].
In section [021] devices assigned to sections [109] to [116] appear as 1 through 8. For example, the device assigned to section [109] would appear as 1 in section [021].
Digiplex Liberator 17
Page 17
I319EI01.fm Page 18 Wednesday, September 29, 1999 10:56 AM
4.2 ASSIGNING DETECTORS & CONTACT SWITCHES TO ZONES
Once the detectors and the contact switches have been assigned to the Liberator Wireless Bus Module, they must be assigned to zones in the control panel. For instructions how to assign the devices to the zones and then program the zones, refer to the Digiplex Control Panel's Reference & Installation Manual.
Zones assigned to detectors or contact switches cannot be programmed as Fire Zones.
4.3 VIEWING SIGNAL STRENGTH OF DETECTORS & CONTACT SWITCHES
SECTIONS [201] TO [216]
Once the detectors and/or contact switches have been installed and assigned to the Liberator Wireless Bus Module, the average signal strength of each device can be verified in these sections. Each section represents the signal strength viewer for a specific device. For example, section [201] is the viewer for the device in section [101] and section [216] is the viewer for the device in section [116].
From Step 5 in Figure 3-1, page8, enter a section from [201] to [216] to view the average strength of each device.
For installations using the LCD Keypads:
The signal strength is represented by one to ten characters that will appear on the LCD screen below the words "Signal Strgh". The reading (number of characters) will appear beside the characters.Three characters or less is a very weak signal and the device should be moved. An average reading above four characters is acceptable.
For installation using the LED Keypads:
The signal strength is represented by the illumination of the numerical LEDs from LED 1 to LED 10. A reading from LED 1 to LED 3 is a very weak signal and the device should be moved. An average reading above LED 4 is acceptable.
18 Installer’s Guide
Page 18
I319EI01.fm Page 19 Wednesday, September 29, 1999 10:56 AM
5.0 REMOTE CONTROLS
To program the remote controls:
1) Remote controls must be assigned to the Liberator Wireless Bus Module
2) The remote controls from the Liberator Wireless Bus Module must be assigned to
User Access Codes in the Digiplex Control Panel.
3) The buttons on the remote controls must be programmed Complete the Programming Guide (see section 6.0 of this manual) while
assigning the remote controls. The serial numbers will be needed when assigning the remote controls to User Access Codes. Also, knowing which User Access Code was assigned to which remote control may affect how the remote's buttons are programmed.
Sections [030], [031], [301] to [316], [401] to [416], and [501] to [516] are all interrelated.
For example, when assigning a remote control to the Receiver Module:
1) The serial number will be entered in section [301]
2) It will automatically appear in section [030]
3) It is assigned to a User Access Code in section [401]
4) Its buttons are programmed in section [501] When using the remote controls, users must press the button(s) until the red
LED on the remote control illuminates. This short delay (0.25 sec.) before sending a signal is to avoid accidental transmissions. After pressing and holding a button continuously for five seconds, the remote control will no longer transmit any signals until the button is released and pressed again.
Digiplex Liberator 19
Page 19
I319EI01.fm Page 20 Wednesday, September 29, 1999 10:56 AM
5.1 ASSIGNING REMOTE CONTROLS TO RECEIVER MODULE
In these sections you will assign the remote controls to the Receiver Module. Up to 16 remote controls can be assigned to each Receiver Module.
SECTION [301] TO [316]
Enter the serial numbers from the remote controls in the sections [301] to [316]. When one section is programmed, the keypad will automatically switch to the next section.
If you are unable to find the serial number, refer to section 3.12 of this manual.
From Step 5 in Figure 3-1, page8:
1) Enter a section from [301] to [316]
2) Enter the serial number of the remote control
SECTIONS [030] AND [031]
The number of remote controls assigned to the Receiver Module can be viewed in sections [030] and [031]. The remotes assigned in [301] to [308] will appear in section [030] and the remotes assigned in [309] to [316] will appear in section [031].
In section [031] remote controls assigned in [309] to [316] appear as 1 through 8. For example, the remote assigned in [309] would appear as 1 in section [031].
20 Installer’s Guide
Page 20
I319EI01.fm Page 21 Wednesday, September 29, 1999 10:56 AM
5.2 ASSIGNING REMOTE CONTROLS TO USER ACCESS CODES
SECTIONS [401] TO [416]
Each remote control must be assigned to a User Access Code. All User Access Codes are given a User Number from 01 to 64 (01 is the System Master Code).
Each section from [401] to [416] represents the remote control assigned to sections [301] to [316] (see section 5.1 of this manual). For example, the remote assigned in
section [301] will be assigned to the User Access Code designated in section [401]. From Step 5 in Figure 3-1, page8:
1) Enter a section from [401] to [416]
2) Enter the User Number (01 to 64) to be assigned to the remote control.
5.3 PROGRAMMING REMOTE CONTROL BUTTONS
SECTIONS [501] TO [516]
For each remote control, each button or a combination of the buttons pressed simultaneously can be programmed to send a signal to the control panel to perform certain actions as if users had gone to a keypad and entered their User Access Codes. When a user arms or disarms using the remote, the control panel will arm or disarm all the areas assigned to the User Access Code. For example, you arm with a remote control whose User Access Code is assigned to areas 1 and 3, the control panel will attempt to arm areas 1 and 3.
Each section from [501] to [516] represents the remote control assigned to the sections [301] to [316] (see section 5.1 of this manual). For example, the buttons for the remote control assigned in section [301] will be programmed in section [501].
Digiplex Liberator 21
Page 21
I319EI01.fm Page 22 Wednesday, September 29, 1999 10:56 AM
Figure 5-1: Remote Controls with button identification
When you enter each section from [501] to [516], each digit represents a button or a combination of buttons pressed simultaneously.
Table A: Button choices:
[0] = Not used [8] = Panic 2 [1] = Regular Arm [9] = Panic 3 [2] = Stay Arm [A] = Smoke reset [3] = Instant Arm [B] = PGM Table: First Digit: 8, Second Digit: 0, Feature 1 [4] = Force Arm [C] = PGM Table: First Digit: 8, Second Digit: 0, Feature 2 [5] = Disarm [D] = PGM Table: First Digit: 8, Second Digit: 0, Feature 3 [6] = Stay/Instant Disarm [E] = PGM Table: First Digit: 8, Second Digit: 0, Feature 4 [7] = Panic 1 [F] = PGM Table: First Digit: 8, Second Digit: 0, Feature 5
The button choices [1] to [9] function only with control panel (DGP-48) versions 2.12 or higher. In versions prior to 2.12, these button choices will ONLY function with the System Master Code (Code 01).
22 Installer’s Guide
Page 22
I319EI01.fm Page 23 Wednesday, September 29, 1999 10:56 AM
These keys represent the hexadecimal values from A to F: [STAY] = A [DISARM] = D [FORCE] = B [BYP] = E [ARM] = C [MEM] = F
For installations using the LED Keypads, the hexadecimal values will illuminate the following LEDs:
(A) = [STAY] LED (D) = [A4] LED (B) = [FORCE] LED (E) = [BYP] LED (C) = [A1] LED (F) = [MEM] LED
For explanations concerning the function of each of the Button choices, refer to their respective sections in the Digiplex Control Panel's Reference & Installation Manual.
For installations using LCD Keypads:
From Step 5 in Figure 3-1, page8:
1) Enter a section from [501] to [516] depending on the remote control you want to
program. For example, program the buttons for the remote control assigned in section [301] in section [501].
2) Place the underline under the digit of the button or button combination you want to
program (Figure 5-2). Enter a hexadecimal value (0 to F) of the option you want from Table A page22.
3) Return to Step 2 for each button or button combination for the remote control.
4) Press [ENTER] once the remote control is programmed. The LCD screen will
automatically switch to the next section for the next remote control.
For example: You have programmed section [501] for the remote control assigned in section [301]. Press [ENTER]. Section [502] will appear on the screen for you to program the remote control that is assigned in [302].
Digiplex Liberator 23
Page 23
I319EI01.fm Page 24 Wednesday, September 29, 1999 10:56 AM
Figure 5-2: Button programming shown on LCD screen
*Four-button remote control not currently available. Therefore, C, D, C+D, A+C, and B+D are for future use.
In Figure 5-3 button A is programmed to Regular Arm , button B is programmed to Disarm, and the combination of buttons A+B is programmed to activate the PGM(s)
according to PGM Table, First Digit 8, Second Digit 0, Feature 4. The other buttons and their combinations are not programmed.
Figure 5-3: Programmed buttons on LCD screen
24 Installer’s Guide
Page 24
I319EI01.fm Page 25 Wednesday, September 29, 1999 10:56 AM
For installations using LED Keypads:
Completing the Programming Guide (see section 6.0 of this manual) before beginning Button Programming is suggested.
From Step 5 in Figure 3-1, page8:
1) Enter a section from [501] to [516] depending on the remote control you want to
program. For example, program the buttons for the remote control assigned in section [301] in section [501].
2) In each section there are eight digits available to program. Each digit represents a
button or a combination of buttons. Enter a hexadecimal value (0 to F) of the option you want from Table A (page22). After every second digit programmed, the keypad will emit beeps.
First digit: enter the choice for Button A Second digit: enter the choice for Button B
(BEEP-BEEP-BEEP) Third digit*: enter the choice for Button C
Fourth digit*: enter the choice for Button D (BEEP-BEEP-BEEP) Fifth digit: enter the choice for Buttons A+B
Sixth digit*: enter the choice for Buttons C+D (BEEP-BEEP-BEEP) Seventh digit*: enter the choice for Buttons A+C
Eighth digit*: enter the choice for Buttons B+D (BEEP-BEEP-BEEP-BEEP-BEEP) Confirmation Beep
*Four-button remote control not currently available. Therefore, the third, fourth, and sixth to eighth digits are for future use.
Digiplex Liberator 25
Page 25
I319EI01.fm Page 26 Wednesday, September 29, 1999 10:56 AM
3) Press [ENTER] once the remote control is programmed. The keypad will automatically switch to the next section for the next remote control.
Once you have programmed section [501], the keypad will emit a Confirmation Beep. The keypad will automatically switch to section [502] and so on. You can verify the programming in each section by returning to the sections and pressing the
button. The numerical LEDs and the LEDs representing the hexadecimal
values will illuminate one at a time as you press the button.
5.4 REPLACING THE REMOTE CONTROLS BATTERY
26 Installer’s Guide
Page 26
I319EI01.fm Page 27 Wednesday, September 29, 1999 10:56 AM
6.0 PROGRAMMING GUIDE
Enter Module Programming Mode (see section 3.1 of this manual):
[0] + [INSTALLER CODE] + [953] + [SERIAL #] + [SECTION] Bold = default
SECTION [001]: Supervision
Option OFF ON
[1] Low Battery l Disabled l Enabled [2] Check-in l Disabled l Enabled [3] Check-in Base Time l 12 hours l 12 minutes [4] Receiver’s On-Board Tamper l Disabled l Enabled [5] Not used l N/A l N/A [6] Not used l N/A l N/A [7] Not used l N/A l N/A [8] Not used l N/A l N/A
SECTION [002]: PGM Options
Option OFF ON
[1] PGM 1 Deactivation Mode l Follow l Timed [2] PGM 1 Base Time l 1 second l 1 minute [3] PGM 1 Override l Disabled l Enabled [4] PGM 1 Override Control l Deactivate l Activate [5] PGM 2 Deactivation Mode l Follow l Timed [6] PGM 2 Base Time l 1 second l 1 minute [7] PGM 2 Override l Disabled l Enabled [8] PGM 2 Override Control l Deactivate l Activate
Both the PGM Activation Event and PGM Deactivation Event must be programmed for the PGM(s) in Follow Mode to function properly.
Digiplex Liberator 27
Page 27
I319EI01.fm Page 28 Wednesday, September 29, 1999 10:56 AM
Section:
[003] ___/___/___ (default 005)
PGM 1 Timer (001 to 255) [004] ___/___/___ (default 005)
PGM 2 Timer (001 to 255) [005] PGM 1 Activation Event
___/___ (1 2 3 4 5 6 7 8 ) PGM Table
1st / 2nd (Select Feature)
[006] PGM 1 Deactivation Event ___/___ (1 2 3 4 5 6 7 8 ) PGM Table
1st / 2nd (Select Feature)
[007] PGM 2 Activation Event ___/___ (1 2 3 4 5 6 7 8 ) PGM Table
1st / 2nd (Select Feature)
[008] PGM 2 Deactivation Event ___/___ (1 2 3 4 5 6 7 8 ) PGM Table
1st / 2nd (Select Feature)
Motion Detectors and Contact Switches
[101] to [116] (see Table 1)
Assignment of the detectors and contact switches to the Receiver Module [201] to [216] (see Table 1)
Viewing the signal strength of the devices assigned to sections [101] to [116]
28 Installer’s Guide
Page 28
I319EI01.fm Page 29 Wednesday, September 29, 1999 10:56 AM
Table 1: Motion Detectors and Contact Switches
Section: Input: Serial Number:
Motion
Detector
Contact
Switch
[101] 001 ___/___/___/___/___/___ l l [102] 002 ___/___/___/___/___/___ l l [103] 003 ___/___/___/___/___/___ l l [104] 004 ___/___/___/___/___/___ l l [105] 005 ___/___/___/___/___/___ l l [106] 006 ___/___/___/___/___/___ l l [107] 007 ___/___/___/___/___/___ l l [108] 008 ___/___/___/___/___/___ l l [109] 009 ___/___/___/___/___/___ l l [110] 010 ___/___/___/___/___/___ l l [111] 011 ___/___/___/___/___/___ l l [112] 012 ___/___/___/___/___/___ l l [113] 013 ___/___/___/___/___/___ l l [114] 014 ___/___/___/___/___/___ l l [115] 015 ___/___/___/___/___/___ l l [116] 016 ___/___/___/___/___/___ l l
[020] and [021]
Viewing the input numbers of the assigned detectors and contact switches [025] Viewing the serial number of an unlabeled device
Digiplex Liberator 29
Page 29
I319EI01.fm Page 30 Wednesday, September 29, 1999 10:56 AM
Complete Table 2: Remote Controls
[301] to [316] (see Table 2)
Assignment of the Remote Controls to the Receiver Module [401] to [416] (see Table 2)
Assignment of Remote Controls to User Acces Codes [501] to [516] (see Table 2)
Programming the button functions for the Remote Controls
[025] To view the serial number of an unlabeled device [030] and [031]
To view the input numbers of the assigned Remote Controls Digiplex the Liberator Wireless Bus Module Serial Number:
___/___/___/___/___/___/___/___
30 Installer’s Guide
Page 30
I319EI01.fm Page 31 Wednesday, September 29, 1999 10:56 AM
Table 2: Remote Controls
Section and Name: Serial Number:
301:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 302:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 303:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 304:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 305:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 306:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 307:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 308:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 309:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 310:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 311:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 312:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 313:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 314:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 315:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ ) 316:__________ __/__/__/__/__/__ __/__/__ ( _/_ ) ( _/_ ) ( _/_ ) ( _/_ )
User
Number
(A B) (C D) (A+B C+D) (A+C B+D)
Button Programming
Button choices:
[0] = Not used [8] = Panic 2 [1] = Regular Arm [9] = Panic 3 [2] = Stay Arm [A] = Smoke reset [3] = Instant Arm [B] = PGM Table: First Digit: 8, Second Digit: 0, Feature 1 [4] = Force Arm [C] = PGM Table: First Digit: 8, Second Digit: 0, Feature 2 [5] = Disarm [D] = PGM Table: First Digit: 8, Second Digit: 0, Feature 3 [6] = Stay/Instant Disarm [E] = PGM Table: First Digit: 8, Second Digit: 0, Feature 4 [7] = Panic 1 [F] = PGM Table: First Digit: 8, Second Digit: 0, Feature 5
The Button Choice “Stay/Instant Disarm” functions only with Digiplex control panel version 1.20 or higher.
Digiplex Liberator 31
Page 31
I319EI01.fm Page 32 Wednesday, September 29, 1999 10:56 AM
32 Installer’s Guide
7.0 PGM PROGRAMMING TABLE
Page 32
I319EI01.fm Page 33 Wednesday, September 29, 1999 10:56 AM
Digiplex Liberator 33
Page 33
I319EI01.fm Page 34 Wednesday, September 29, 1999 10:56 AM
34 Installer’s Guide
Page 34
I319EI01.fm Page 35 Wednesday, September 29, 1999 10:56 AM
Digiplex Liberator 35
Page 35
I319EI01.fm Page 36 Wednesday, September 29, 1999 10:56 AM
36 Installer’s Guide
Page 36
I319EI01.fm Page 37 Wednesday, September 29, 1999 10:56 AM
Warranty
The Seller warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not manufactured by Seller, Seller cannot guarantee the performance of the security system. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental, including without limitation, any damages for lost profits, stolen goods, or claims by any other party caused by defective goods or otherwise arising from the improper, incorrect, or otherwise faulty installation or use of the merchandise sold.
Digiplex Liberator 37
Page 37
I319EI01.fm Page 38 Wednesday, September 29, 1999 10:56 AM
Loading...