NET-ACCESS SENSOR MOUNTING AND CABLE ROUTING TO NETWORKED
W / ENVIRONMENTAL OR SWITCHED POU
INSTRUCTIONS CM539
© Panduit Corp. 2011
Installation of Environmental Sensors
Install (3) PVQ-ESTAFHD-12 to the front door using (6) 5/8” plastic retainers, (6) #6-32 screws, (6) #6-32 nuts (or cable ties for PVQ-EST-12) , and route cable on door using small clips (ACC19-AV-M300).
Install (1) temperature sensor in the rear of cabinet, route cable using cable ties.
Note: attach sensors to door, then route
5/8” Plastic Retainers
cable to Networked POU.
Note: For CS Cabinets slit the seal in the air dam and route cable thru the slit.
PVQ-EST-12 Note: Route / secure to inside of Top Cap.
(3) PVQ-ESTAFHD-12 Note: Sensor must be oriented as shown, with open slots facing the front of the door for proper air flow readings.
APPLICATION 1
Front
Rear
Cable tie
(3) PVQ-EST-12
APPLICATION 2
For Technical Support: www.panduit.com/resources/install_maintain.asp
Note: Before securing sensors, rotate door to the maximum open position to ensure enough slack for proper door operation.
Page 1 of 8
Page 2
INSTRUCTIONS CM539
Routing Sensor cable to Networked with Environmental or Switched POU
Route cable to Networked with Environmental or Switched POU, as shown below after mounting CNFBB and WMPFSE.
(1) Temperature Sensor Note: Manage sensor cable slack on cabinet post or on rear of the POU, using adhesive back clips. For 48” Deep Cabinets manage slack on the inside of Side Panel extension using adhesive mount clips.
Rear
Front
CNFBB Bracket for mounting cable manager.
For Technical Support: www.panduit.com/resources/install_maintain.asp
POU
WMPFSE Note: Manage slack in cable manager.
Route sensor cable thru the cable manager to the Networked with Enviromental or Switched POU. Manage slack in cable manager.
REAR DOORS REMOVED FOR CLARITY
Page 2 of 8
Page 3
INSTRUCTIONS CM539
Installation of Front Door Sensors
For CS Cabinet: Install (1) door sensor with (1) air dam bracket, (2) #6-32 nuts, and (2) #6-32 screws.
For CN Cabinet: Install (1) door sensor with (1) front door bracket, (2) #6-32 nuts, and (2) #6-32 screws.
Install (1) sensor with (1) double sided tape.
Note: Ensure proper alignment with mating frame sensor before permanently affixing sensor with double sided tape on door.
Note: For CS Installation­remove air dam screws, place bracket and re­install screws to attach bracket to cabinet.
Front of cabinet
(1) Door Sensor
Air Dam Bracket
Note: For proper readings, sensors must be aligned as shown.
3.6”
1/8”
(2) #6-32 Screws
Note: For CN installtion use this bracket.
(1) Door Sensor Note: Apply double sided tape to sensor and install as shown. Center sensor on door.
(2) #6-32 Screws
(2) #6-32 Nuts
(2) #6-32 Nuts
CS INSTALLATION
(2) #12-24 Screws
CN INSTALLATION
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 8
Page 4
INSTRUCTIONS CM539
Front Door Sensor Cable Routing
Route front door sensor cable to the Networked with Environmental or Switched POU in the rear of the cabinet, as shown below.
Route sensor cable thru the cable manager to the Networked with Environmental or Switched POU. Manage slack in cable manager.
Front
POU
Rear
Front Door Sensor Cable Note: For CS Application route through clearance hole in the equipment rail and attach to post with push mount cable ties.
Front Door Sensor Note:For CS Application route through bolt down hole and underneath the air dam.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 8
Page 5
INSTRUCTIONS CM539
Installation of Rear Door Sensors
For 41” Deep: Install (2) rear door sensors with (1) 41” rear bracket, (1) double sided tape, (2) #6-32 nuts, and (2) #12-24 screw.
For 48” Deep: Install (2) rear door sensors with (1) 48” rear bracket, (1) double sided tape, (2) #6-32 nuts, and (2) #12-24 screw.
Note: For proper readings, sensors must be aligned as shown.
(2) #12-24 Screw
41” Rear Bracket
1/8”
(1) Door Sensor
41” Deep
Rear of Cabinet
(2) #6-32 Nuts
(1) #5/16-18 Nut
(1) Door Sensor
48” Rear Bracket
(1) Door Sensor Note: Install with double sided tape
Rear of Cabinet
(2) #6-32 Nuts
48” Deep
(1) Door Sensor Note: Install with double sided tape
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 8
Page 6
INSTRUCTIONS CM539
Rear Door Sensor Cable Routing
Route rear door sensor cable to Networked with Environmental or Switched POU, as shown below.
POU
Front
Rear
Rear Door Sensor Cable Note: Attach cable to outside of post using adhesive back clips.
Rear Door Sensor
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 8
Page 7
INSTRUCTIONS CM539
Installation of Remote Display / Cable Routing
Install remote display to rear door with (2) sheet metal screws, (2) #6-32 nuts, (2) #6-32 screws, and (2) #6 washers.
Route remote display cable to Networked with Environmental or Switched POU.
Note: Remote Display can be intalled facing into the cabinet, or facing out of the cabinet.
Remote Display
POU
Note: Additional Remote Dis­plays can be added at any position on the perforation of the door.
(2) #6-32 Screws
Front
Remote Display Cable Note: Use Adhesive back Clips to manage slack behind POU.
(2) #6-32 Nuts
Rear
(2) #6 Washers
(2) Sheet Metal Screws
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 8
Page 8
INSTRUCTIONS CM539
Installation of Remote Display in 48” Deep Applications
Install Remote Display with (2) #12-24 screws, (2) sheet metal screws and (1) remote display bracket to POU Bracket in the rear of the cabinet.
CVPDUB48
(2) #12-24 Screws
(2) Sheet Metal Screws
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Remote Display
www.panduit.com
Page 8 of 8