Recommended sensor placement includes (3) temperature / humidity / airflow / dewpoint sensors and (1) Temperature Sensor.
•Install (3) PVQ-ESTAFHD-12 to the front door using (6) 5/8” plastic retainers, (6) #6-32 screws, (6) #6-32 nuts (or cable ties for
PVQ-EST-12) , and route cable on door using small clips (ACC19-AV-M300).
•Install (1) temperature sensor in the rear of cabinet, route cable using cable ties.
Note: attach sensors
to door, then route
5/8” Plastic Retainers
cable to Networked
POU.
Note: For CS Cabinets
slit the seal in the air
dam and route cable
thru the slit.
PVQ-EST-12
Note: Route / secure
to inside of Top Cap.
(3) PVQ-ESTAFHD-12
Note: Sensor must be oriented as
shown, with open slots facing the
front of the door for proper
air flow readings.
APPLICATION 1
Front
Rear
Cable tie
(3) PVQ-EST-12
APPLICATION 2
For Technical Support: www.panduit.com/resources/install_maintain.asp
Note: Before securing sensors,
rotate door to the maximum open
position to ensure enough slack for
proper door operation.
Page 1 of 8
Page 2
INSTRUCTIONS CM539
Routing Sensor cable to Networked with Environmental or Switched POU
•Route cable to Networked with Environmental or Switched POU, as shown below after mounting CNFBB and WMPFSE.
(1) Temperature Sensor
Note: Manage sensor cable slack
on cabinet post or on rear of the
POU, using adhesive back clips.
For 48” Deep Cabinets manage
slack on the inside of Side Panel
extension using adhesive mount
clips.
Rear
Front
CNFBB
Bracket for mounting
cable manager.
For Technical Support: www.panduit.com/resources/install_maintain.asp
POU
WMPFSE
Note: Manage slack
in cable manager.
Route sensor cable thru the
cable manager to the Networked
with Enviromental or Switched
POU. Manage slack in cable
manager.
REAR DOORS REMOVED FOR CLARITY
Page 2 of 8
Page 3
INSTRUCTIONS CM539
Installation of Front Door Sensors
•For CS Cabinet: Install (1) door sensor with (1) air dam bracket, (2) #6-32 nuts, and (2) #6-32 screws.
•For CN Cabinet: Install (1) door sensor with (1) front door bracket, (2) #6-32 nuts, and (2) #6-32 screws.
•Install (1) sensor with (1) double sided tape.
•Note: Ensure proper alignment with mating frame sensor before permanently affixing sensor with double sided tape on door.
Note: For CS Installationremove air dam screws,
place bracket and reinstall screws to attach
bracket to cabinet.
Front of cabinet
(1) Door Sensor
Air Dam Bracket
Note: For proper readings,
sensors must be aligned as
shown.
3.6”
1/8”
(2) #6-32 Screws
Note: For CN installtion
use this bracket.
(1) Door Sensor
Note: Apply double
sided tape to sensor
and install as shown.
Center sensor on
door.
(2) #6-32 Screws
(2) #6-32 Nuts
(2) #6-32 Nuts
CS INSTALLATION
(2) #12-24 Screws
CN INSTALLATION
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 3 of 8
Page 4
INSTRUCTIONS CM539
Front Door Sensor Cable Routing
•Route front door sensor cable to the Networked with Environmental or Switched POU in the rear of the cabinet, as shown below.
Route sensor cable thru the
cable manager to the Networked
with Environmental or Switched
POU. Manage slack in cable
manager.
Front
POU
Rear
Front Door Sensor Cable
Note: For CS Application
route through clearance
hole in the equipment
rail and attach to post
with push mount cable
ties.
Front Door Sensor
Note:For CS Application
route through bolt down
hole and underneath the air
dam.
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 4 of 8
Page 5
INSTRUCTIONS CM539
Installation of Rear Door Sensors
•For 41” Deep: Install (2) rear door sensors with (1) 41” rear bracket, (1) double sided tape, (2) #6-32 nuts, and (2) #12-24 screw.
•For 48” Deep: Install (2) rear door sensors with (1) 48” rear bracket, (1) double sided tape, (2) #6-32 nuts, and (2) #12-24 screw.
Note: For proper readings,
sensors must be aligned as
shown.
(2) #12-24 Screw
41” Rear Bracket
1/8”
(1) Door Sensor
41” Deep
Rear of Cabinet
(2) #6-32 Nuts
(1) #5/16-18 Nut
(1) Door Sensor
48” Rear Bracket
(1) Door Sensor
Note: Install with
double sided tape
Rear of Cabinet
(2) #6-32 Nuts
48” Deep
(1) Door Sensor
Note: Install with
double sided tape
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 5 of 8
Page 6
INSTRUCTIONS CM539
Rear Door Sensor Cable Routing
•Route rear door sensor cable to Networked with Environmental or Switched POU, as shown below.
POU
Front
Rear
Rear Door Sensor Cable
Note: Attach cable to outside
of post using adhesive back
clips.
Rear Door Sensor
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 6 of 8
Page 7
INSTRUCTIONS CM539
Installation of Remote Display / Cable Routing
•Install remote display to rear door with (2) sheet metal screws, (2) #6-32 nuts, (2) #6-32 screws, and (2) #6 washers.
•Route remote display cable to Networked with Environmental or Switched POU.
Note: Remote Display can be intalled facing into the cabinet, or facing out of the cabinet.
Remote Display
POU
Note: Additional Remote Displays can be added at any
position on the perforation of
the door.
(2) #6-32 Screws
Front
Remote Display Cable
Note: Use Adhesive back
Clips to manage slack
behind POU.
(2) #6-32 Nuts
Rear
(2) #6 Washers
(2) Sheet Metal Screws
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 7 of 8
Page 8
INSTRUCTIONS CM539
Installation of Remote Display in 48” Deep Applications
•Install Remote Display with (2) #12-24 screws, (2) sheet metal screws and (1) remote display bracket to POU Bracket in the rear of
the cabinet.
CVPDUB48
(2) #12-24 Screws
(2) Sheet Metal Screws
For Instructions in Local Languages
and Technical Support:
www.panduit.com/resources/install_maintain.asp
Remote Display
www.panduit.com
Page 8 of 8
E-mail:
cs@panduit.com
Fax:
(708)444-6448
Loading...
+ hidden pages
You need points to download manuals.