Panduit VS-ACK-CPWR, VS-ACK-EXT, VS-ACK-KEY, VS-ACK-BATTERY User manual

VeriSafe Access
Control Kit
1003190
© Panduit Corp. 2019
Original Instructions
The VeriSafe Access Control Kit, inst alled with the VeriSafe Abse nce of Volta ge Te ster, provide s an added layer
to the equipment.
VS-ACK-CPWR
VS-ACK-EXT
VS-ACK-BATTERY
VS-ACK-KEY
Instruction Manual
Rev: 01; 1-2020
of protection by preventing enclo sure doors from being opened until absence o f voltage is confirmed. Before entering the electrical cabinet, personnel will use the VeriSafe Absence of Volt ag e T este r to test for absence of voltage. The VeriSafe Access Control Kit will receive a signal from the VeriSafe Absence of Voltage Tester when the absence of voltage is confirmed. The rotary latch will unlock, releasing the enclosure door and allow access
TO REDUCE THE RISK OF INJURY, USER MUST READ INSTRUCTION MANUAL
NOTE: In the interest of higher quality and value, Panduit products are continually being improved and updated. Consequently, pictures may vary from the enclosed product.
North America Tech Support:
techsupport@panduit.com
Tel: 1-866-405-6654
EU Tech Support :
emeatoolservicecenter
@panduit.com
Tel: +31-546-580-452
Fax: +31-546-580-441
NOTE: Updates to this Instruction Manual may be available. Check www.panduit.com for the latest version of this manual.
Asia Pacific Tech Support:
TechSupportAP@ panduit.com
Telephone:
Korea: 02-21827300
www.panduit.com
Singapore: 1-800-Panduit (7263848)
Australia: 1-800-Panduit (7263848)
© Panduit Corp. 2019
Warning: Do not use this product outside of the specified performance and environmental limits.
Failure to comply with these specifications could result in product failure, personal injury, or death.
Standards
Applications
Degree of Protection*
For Flat Surface Mounting in a TYPE (UL, NEMA and CSA) 1, 12, 4, IP65 Enclosure
Environment
Operating Temperature
-25°C to 60°C (-13°F to 140°F)
Storage Temperature
-45°C to 85°C (-50°F to 185°F)
Humidity
5 to 90% non-condensing; Rated 80% at 40°C, decreasing linearly to 50% at 60°C
VS-ACK-BATTERY
Type
Industrial 9V Metal Lithium (qty: 2)
INSTRUCTION MANUAL VeriSafe ACK

Safety Information

This manual contains information and warnings which must be follow ed to ensure safe operation of the Access Control Kit. If the Access Control Kit is not used as described in this manual, the safety features of the Access Control Kit might be imp aire d. The Access Control Kit is designed for use with the VeriSafe AVT. Reference the VeriSafe AVT instruction manual for critical safety information, installation and operating instructions. Failure to comply with the warnings and information in this manual
could result in product failure, electrical shock, severe injury or death.
Warning:
Always de-energize power before accessing an electrical enclosure.
Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
Use of the Access Control Kit does not replace lockout/tagout procedures. The Access Contr ol Kit is intended to be used in conjuncti on with the VeriSafe AVT and the lockout/tagout processes.
Use proper personal protective equipment (PPE) when working around sources of hazardous electrical energy.
Do not use this product outside of the specified performance and environmental lim its. Failure to comply with these specifications could result in product failure, personal injury or death.
This product must be installed by a qualified electrical worker familiar with local and national electrical codes.
Always comply with local installation codes and standards.
The VS-ACK-BATTERY product uses a lithi um battery that is a fire, explosion and s evere bur n hazard. Do not crush, rechar ge, disassemble or heat above 85° C, incinerate, or expose contents to water.
Use only the included Wire Harness or approved replacement harness to connect the Rotary Latch and VeriSafe AVT.

Technical Specifications

RoHS Restriction of hazardous substances
Electrical System For use in 1 and 3-phase AC or DC systems
*Degree of protection specified is related to the Latch Cam only. To meet the TYPE (UL, NEMA and CSA) 1, 12, 4, IP65 requirements, mount on a flat surface of an enclosure meeting the appropriate TYPE rating. Verify that the Sealing Washer is clean and properly seated onto the Latch Cam to ensure proper sealing.
Classification Non-Rechargeable Designation ANSI-1604LC Operating Temperature -20°C to 60°C (-4°F to 140°F) Mounting Type DIN Rail or Surface Mount Estimated Capacity 1 cycle per week for 10 years
1003190 R00 Page: 1 of 7 10-2019
© Panduit Corp. 2019
INSTRUCTION MANUAL VeriSafe ACK

VS-ACK-CPWR Install Instructions

Figure 1 - Componen ts of the VeriSaf e A cces s C ontr ol Kit – Control Power (VS-ACK-CPWR)
Figure 2 – Quick Assembly Guide 1 – Contr ol Powe r (VS-ACK-CPWR)
1003190 R00 Page: 2 of 7 10-2019